This is a technical service report documenting troubleshooting work performed on an Intrusion Detection System (IDS) at the YTC ASP facility on December 6, 2021. Technician EFS arrived at 0830 and performed repairs on four accounts (Yak1060, Yak1080, Yak1054, and Yak1095), with work beginning at 0845.

The repairs included: replacement of a faulty II zim component on Yak1060 to resolve sporadic S-faults on the Building Management System; tightening of wiring connections and reduction of loop resistance from 1055 to 1025 ohms on Yak1080 to clear grid tamper alarms; documentation of Yak1054 and Yak1064 as no longer licensable for ammunition storage with a recommendation to deactivate both accounts to minimize false alarms; and extensive repairs on Yak1095 including replacement of a non-functional Kud8 unit, damaged KP ribbon cable, PB2000 front end unit, and faulty RIM card, repair of a broken copper wire lead in the TELCO communications line, and identification of a stuck PIM2 alarm requiring a follow-up visit with specialized equipment and pricing for an intrinsically safe Sentrol PIM replacement. The technician also noted configuration discrepancies on RIM cards where valid devices were showing as spared out on the front end system. All CSOs were completed and left at the MP station.

View the file

Other files

File Type Posted
TE-V -Preventative Maintenance Schedule.xlsx XLSX spreadsheet
Solicitation Amendment W911S826RA0170002 SF 30.pdf PDF
TE-U - ICIDS and CCTV Master spreadsheet (SANITIZED).xlsx XLSX spreadsheet
ICIDS PERFORMANCE WORK STATEMENT 11AUG26.pdf PDF
ATTACHMENT 01 PRICING SCHEDULE.xlsx XLSX spreadsheet
Solicitation W911S826RA017 Questions.pdf PDF
ICIDS PERFORMANCE WORK STATEMENT 29 JULY 2026.pdf PDF
Solicitation Amendment W911S826RA0170001 SF 30 (2026-08-06).pdf PDF
ICIDS PWS 2026-07-16.pdf PDF
TE-G-ICIDS COMMS - ICIDS Failure Reports.pdf PDF
TE-Q -Activation Worksheet.pdf PDF
TE-T - New ICIDS Account Acvtivation Request.pdf PDF
TE-M-CCTV Performance Verification Test (PVT) - 2021.pdf PDF
TE-D - Alarm Test Log.pdf PDF
TE-H - ICIDS PIN User Agreement.pdf PDF
TE-U - ICIDS and CCTV Master spreadsheet 01AUG2025.xlsx XLSX spreadsheet
TE-P-ICIDS CCTV Addition Removal Request.pdf PDF
TE-N-QUALITY CONTROL CHECK SHEET - 2021.pdf PDF
TE-E- Contract Service Order.pdf PDF
Solicitation - W911S826RA017.pdf PDF
TE-R -Deactivation Worksheet.pdf PDF
TE-J - Labor Materials and Travel Estimate (LMT).pdf PDF
TE-B - ICIDS-DailyAlarmEventLog_example - 2021.pdf PDF
TE-A - ICIDS CCTV-GBR SOP.pdf PDF
TE-K - MCA-ICIDS V-MaterialOrder.pdf PDF
TE-C - Open Accounts Report example - 2021.pdf PDF
TE-S - ICIDS Accounts Map.pdf PDF
TE-L - IDS PerformanceVerificationTest (PVT) - 2021.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date: 6 Dec 2021 Job Title: YTC ASP IDS Troubleshooting

CS0: 2021-12

Technician: EFS

Arrived at YTC 0830 and checked in with Jason Kesselring at the MP station Arrived at the ASP at 0845 and started work at Yak1060 – Sporadic S-fault on the BMS. The loop metered fine however the II zim was extremely out of whack so I replaced it. Able to arm and disarm with no more sfaults on this account while I was on site today.

Yak1080 – Grid tamper. I metered the loop and it was around 1055 ohms. It was in alarm when I got there so I checked on the wiring connections in the panel as well as the J boxes at the two lower grids and tightened all the connections. I was able to get it down to 1025 ohms which cleared the alarm. We might have to put in a potentiometer at a later date.

No more sfaults on this account while I was on site today.

Yak1054 – Grid tamper. I couldn’t replicate this issue. However Gene Bell (ASP supervisor) informed me that as per John Sly, Yak1054 and Yak1064 are no longer licensable so they can’t store ammo in them anymore. I recommend that they deactivate those two accounts to minimize the false alarms.

Yak1095- Users unable to arm/disarm, having to call and get it force closed/opened daily. Multiple issues on this one.

The Kud8 was no longer working so I replaced it with a new Kud8. The KP ribbon cable was damaged so I replaced it. I realized that the front end was receiving any alarm activity from this account. Jonathan worked with me and I installed a new PB2000. We were able to get comms up but the first RIM card wasn’t forwarding alarm info. I replaced that RIM. I also checked all wiring inside the RADC and discovered that the 2 Wire copper for comms coming into the TELCO had a broken lead on the transmit side. I fixed that and we were able to get alarms to the front end in a timely manner. I also found that PIM2 was stuck in alarm. I couldn’t clear that alarm. It will take a 10’ or 12’ ladder and a return trip to work on that. Criss okayed me to 1k that point for now. He wants us to get a price for replacing that PIM, it’s an intrinsically safe one, Sentrol if I remember correctly. This account could really use a couple people to go through it thoroughly. I ran out of time today plus I wasn’t as prepared as I wanted to be (no tall ladder), but I noticed that with all the hands that have been in that account that a valid point on RIM1 had a point on the front end spared out. It has a valid device wired to it and to my knowledge shouldn’t be spared out. The 2nd RIM card has one device wired to it, which I believe was a PIM at once point, but the front end shows it as a spare.

I filled out all the CSOs and left copies at the MP station. Jason Kesselring wasn’t there so I checked out with the desk.