SWAC MG501 - HVAC SCHEDULES.pdf

PDF 1 MB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This HVAC Schedules document is a technical specification sheet prepared by Newcomb & Boyd for the North Carolina School of Science and Mathematics (NCSSM) Morganton Campus Student Wellness and Activities Center (Building G) project. The document details comprehensive HVAC equipment specifications including air handling units, fans, pumps, chillers, boilers, terminal units, and ancillary equipment required for the facility. Key equipment includes two variable volume air handling units (AHU-G-1 and AHU-G-2) serving the wellness center and gym with capacities ranging from 9,000 to 20,000 CFM, two 80-ton air-cooled chillers with minimum 10.1 EER ratings, two 720 MBH condensing hot water boilers, multiple supply terminal units with variable volume and reheat capabilities, ductless split systems for specialized spaces, and various exhaust and relief fans. The specifications establish design conditions with summer outside air at 92.4°F DB and 72.7°F WB and winter conditions at 20°F, along with specific temperature and humidity requirements for different building zones. Equipment is scheduled with detailed performance requirements including CFM ratings, pressure drops, motor horsepower, vibration isolation specifications, and control valve types.

The document incorporates multiple control requirements and performance standards referenced in the North Carolina Energy Conservation Code-2018 and AHRI testing conditions. Vibration isolation requirements are specified throughout, with detailed references to isolation mount types and installation details. Sound attenuation requirements are established with maximum allowable sound power levels for air handling units and fans specified in octave bands from 63 Hz to 8000 Hz. Terminal units include 21 variable volume boxes with reheat coils and one constant volume unit, with heating capacities ranging from 0.8 to 26.4 MBH. Two variable frequency drives are mandated for supply fan operation, and integral motor-operated isolation dampers are required on exhaust equipment. The specifications require dual primary and secondary pump configurations for both chilled and heating water systems, with secondary systems operating at 1200 RPM for energy efficiency. All equipment selections are based on standard industry testing procedures and include references to electrical drawings and detailed installation specifications for vibration isolation and mounting.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

CIVIL ENGINEER AND LANDSCAPE ARCHITECT

Stewart, Inc.

101 W Main Street

Durham, NC 27701

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP, FP, LIGHTING, AV AND SECURITY ENGINEER

Newcomb & Boyd

303 Peachtree Center Avenue, NE

Suite 525

Atlanta, GA 30303

COST ESTIMATOR

Palacio Collaborative

4819 Emperor Boulevard, Suite 400

Durham, NC 27703

LIFE SAFETY

Jensen Hughes

8000 Regency Parkway, Suite 580

Cary, NC 27518

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2022 Duda|Paine Architects, PA

16-14368-02J

303 Peachtree Center Avenue, NE Suite 525 Atlanta, GA 30303-1277 T 404 730-8400 NB Contact: Richard O. Dozier

N&B PROJECT: 17N054

NC Firm Lic. #F-0312 Newcomb & Boyd, LLP

/3

/2

:4

:5

A

M

MG501

HVAC

SCHEDULES

09.01.2023 21611.16

BID SET

W F le m in g

D ri v e M o rg a n to n

N C

(B u ild in g G

S tu d e n t

W e lln e ss a n d

A c ti v it ie s C e n te r

AIR HANDLING UNIT SCHEDULE

NO. AREA SERVED (NOTE 1) TYPE (NOTE 2)

FAN

MINIMUM

OA CFM

COOLING COIL HEATING COIL (NOTE 8) VIBRATION ISOLATION

NOTESCFM

MAXIMUM

RPM

TYPE

(NOTE 3)

ESP. IN. WG

(NOTE 4)

MOTOR

CFM

(NOTE 5)

MAXIMUM

CHILLED

WATER GPM

(NOTE 6)

EAT °F LAT °F

CONTROL

VALVE

TYPE

(NOTE 7)

CONDITIONS DURING MAXIMUM

HEATING DEMAND

TYPE-POSITION

(NOTE 10)

CONTROL

VALVE

TYPE

(NOTE 7) TYPE

MIN. STATIC

DEFLECTION,

IN.

MINIMUM

HP

MAXIMUM

BRAKE HP DB WB DB WB CFM

GPM

(NOTE 9) EAT °F LAT °F

AHU-G-1 WELLNESS & ACTIVITY CENTER DT-MO-HZ-VV 20,000 1,800 P-AF 3.75 4 @ 7.5 27.6 4,000 20,000 145 88.1 70.4 52.0 51.5 2 10,000 13 40.0 52.0 S-P 2 FS 0.75 11,12,13,14

AHU-G-2 GYM DT-MO-HZ-VV 9,000 1,800 P-AF 3.0 4 @ 3 9.1 2,700 9,000 65 88.1 70.4 52.0 51.5 2 9,000 22 53.3 75.0 S-P 2 FS 0.75 11,12,13,14

FAN SCHEDULE

NO. AREA SERVED

TYPE

(NOTES

1 & 2) CFM

STATIC

PRESSURE,

IN.WG

MAXIMUM

RPM

MOTOR

DRIVE

(NOTE 3)

VIBRATION ISOLATION

NOTES

MINIMUM

HP

MAXIMUM

BRAKE HP TYPE

MINIMUM STATIC

DEFLECTION, IN.

F-G-1 TOILET EXHAUST C 1,825 0.5 1800 0.75 0.4 B -- -- 4,5

F-G-2 BUILDING RELIEF TI-MF 16,000 0.6 800 5 3.8 B PSH 1.5 4,6

F-G-3 CLINIC EXHAUST CPRV-B 150 0.25 1800 0.17 0.05 B -- -- 4,5,7

F-G-4 GYM RELIEF RLP-B 7,000 0.2 500 1 0.75 B -- -- 4,5,6

3. FAN TYPE:

FAN: WHEEL:

P PLENUM AF AIRFOIL

4. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, PLENUMS, OR

UNIT MOUNTED HEATING AND COOLING COILS, BUT DOES INCLUDE FILTERS.

5. BASED ON 500 FPM COIL FACE VELOCITY AND MAXIMUM 0.85" WG APD.

6. CHILLED WATER BASED ON 44°F EWT, 60°F LWT AND MAXIMUM 18' WPD.

7. CONTROL VALVE TYPE:

2 2-WAY

3 3-WAY

8. COIL FACE AREA SHALL BE BASED ON MAXIMUM COOLING DESIGN CFM

WITH MAXIMUM 0.2" WG AIR PRESSURE DROP.

9. HOT WATER BASED ON 130°F EWT, 100°F LWT AND MAXIMUM 3' WPD.

10. TYPE: POSITION:

S STANDARD P PREHEAT

R REHEAT

11. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

12. PROVIDE TWO VARIABLE FREQUENCY DRIVES WITH EACH VARIABLE

FREQUENCY DRIVE SERVING HALF OF THE SUPPLY FANS.

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB,72.7°F WB 20°F

CLASSROOMS 75°F DB, 50% RH 70°F

OFFICES 75°F DB, 50% RH 70°F

COMMONS 75°F DB, 50% RH 70°F

MECHANICAL 104°F DB 50°F

REMAINING SPACE 75°F DB, 50% RH 70°F

2. TYPE:

DT DRAW-THROUGH MO MODULAR

HZ HORIZONTAL VV VARIABLE VOLUME

NOTES:

1. TYPE:

TI TUBULAR INLINE

CPRV CENTRIFUGAL POWER ROOF VENTILATOR

RLP ROOF LOUVERED PENTHOUSE

2. WHEEL TYPE:

AF AIR FOIL

B BACKWARD-INCLINED

MF MIXED FLOW

3. DRIVE:

B BELT

D DIRECT

4. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT

ELECTRICAL CHARACTERISTICS.

5. PROVIDE INTEGRAL MOTOR-OPERATED ISOLATION DAMPER

HARDWIRED TO OPEN WITH FAN ON AND CLOSE WITH FAN OFF.

FINNED TUBE RADIATION SCHEDULE

NO.

TYPE

(NOTE 1)

MINIMUM ACTIVE

LENGTH (FT.)

MINIMUM

CAPACITY, kW NOTES

FTR-G-1 P 4 2 2

FTR-G-2 P 4 2 2

FTR-G-3 P 4 2 2

FTR-G-4 P 4 2 2

FTR-G-5 P 4 2 2

FTR-G-6 P 4 2 2

NOTES:

1. TYPE:

P PEDESTAL-MOUNTED

2. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT

ELECTRICAL CHARACTERISTICS.

PUMP SCHEDULE

NO. SERVICE

TYPE

(NOTE 1) GPM

TOTAL DYNAMIC

HEAD, FT. WG

MINIMUM

EFFICIENCY,

% RPM

MOTOR VIBRATION ISOLATION

NOTES

MINIMUM

HP

MAXIMUM

BRAKE HP TYPE

MINIMUM STATIC

DEFLECTION, IN.

INERTIA

BASE

HWP-G-AHU1 PREHEAT COIL CIRCULATING V 15 20 50.0 1800 0.5 0.2 DN / NH 0.25 N 3

HWP-G-AHU2 PREHEAT COIL CIRCULATING V 25 20 60.0 1800 0.5 0.2 DN / NH 0.25 N 3

PCWP-G-1 PRIMARY CHILLED WATER E 120 40 72.0 1800 3 1.8 FS 0.75 Y 3

PCWP-G-2 PRIMARY CHILLED WATER E 120 40 72.0 1800 3 1.8 FS 0.75 Y 3

PHWP-G-1 PRIMARY HEATING WATER V 60 40 66.0 1800 2 1.0 DN / NH 0.25 N 3

PHWP-G-2 PRIMARY HEATING WATER V 60 40 66.0 1800 2 1.0 DN / NH 0.25 N 3

SCWP-G-1 SECONDARY CHILLED WATER E 120 50 64.0 1200 5 2.5 FS 0.75 Y 2,3

SCWP-G-2 SECONDARY CHILLED WATER E 120 50 64.0 1200 5 2.5 FS 0.75 Y 2,3

SHWP-G-1 SECONDARY HEATING WATER E 60 50 67.0 1800 2 1.2 FS 0.75 Y 2,3

SHWP-G-2 SECONDARY HEATING WATER E 60 50 67.0 1800 2 1.2 FS 0.75 Y 2,3

NOTES:

1. TYPE:

E END-SUCTION

V VERTICAL INLINE

2. PROVIDE VARIABLE FREQUENCY DRIVE.

3. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

AIR-COOLED CHILLER SCHEDULE

NO.

CAPACITY,

TONS (NOTES

1 & 2)

MAXIMUM

POWER INPUT

kW AT FULL

LOAD

MINIMUM

EER

MINIMUM

IPLV

EVAPORATOR

NOTES

EWT

°F

LWT

°F GPM

MAXIMUM

PRESS. DROP,

FT. WG

CH-G-1 80 70.7 10.1 15.1 58 44 120 15 4,5

CH-G-2 80 70.7 10.1 15.1 58 44 120 15 4,5

NOTES:

1. CAPACITY BASED ON 105°F AMBIENT TEMPERATURE.

2. PROVIDE LOW AMBIENT OPERATION DOWN TO 30°F.

3. MAXIMUM POWER IS BASED ON 105°F AMBIENT TEMPERATURE. MINIMUM EER SHALL BE BASED

ON STANDARD AHRI TESTING CONDITIONS IN ACCORDANCE WITH NCECC-2018.

4. INSTALL ON TYPE DN NEOPRENE ISOLATION MOUNTS OR TYPE NP NEOPRENE ISOLATION PADS

WITH TYPE IWG NEOPRENE ISOLATION WASHER AND BUSHINGS AT BOLTED CONNECTION

THROUGH ISOLATION PADS. REFER TO DETAIL 8 ON SHEET MG602.

5. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

BOILER SCHEDULE

NO.

TYPE

(NOTE 1)

OUTPUT,

MBH

MINIMUM

EFFICIENCY,

% (NOTE 4)

HOT WATER INPUT

NOTES

EWT

°F

LWT

°F GPM FUEL

RATE,

MBH

B-G-1 C-H 720 93 105 130 60 NG 750 3

B-G-2 C-H 720 93 105 130 60 NG 750 3

NOTES:

1. TYPE:

C CONDENSING - H HOT WATER

2. INSTALL ON TYPE DN NEOPRENE ISOLATION MOUNTS OR TYPE NP NEOPRENE ISOLATION

PADS WITH TYPE IWG NEOPRENE ISOLATION WASHER AND BUSHINGS AT BOLTED

CONNECTION THROUGH ISOLATION PADS. REFER TO DETAIL 8 ON SHEET MG602.

3. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

4. PER THE TEST PROCEDURES AND CONDITIONS REQUIRED IN THE NORTH CAROLINA

ENERGY CONSERVATION CODE-2018.

FAN-COIL UNIT SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

MINIMUM

MOTOR HP

NOMINAL

CFM

(NOTE 2)

ESP

IN.

WG.

COOLING COIL (NOTE 3) HEATING COIL (NOTE 4)

NOTES

SENSIBLE

MBH

LATENT

MBH GPM

RUNOUT

SIZES, IN. MBH GPM

POSITION

(NOTE 5)

RUNOUT

SIZES, IN.

FCU-G-1 UTILITY ROOM HC 2 @ 1/20 650 0.2 8.6 0.25 2.1 0.75 4.8 0.5 R 0.75 6,7

FCU-G-2 BOILER ROOM HC 2 @ 1/20 650 0.2 8.6 0.25 2.1 0.75 4.8 0.5 R 0.75 6,7

NOTES:

1. TYPE:

HC HORIZONTAL CONCEALED

2. CFM BASED ON MEDIUM FAN SPEED.

3. CHILLED WATER BASED ON: 75°F DB AND 62.5°F WB EAT, 44°F EWT, 14° DIFFERENTIAL, AND MAXIMUM 10' WPD.

4. HOT WATER BASED ON: 70°F DB EAT, 130°F EWT, 30° DIFFERENTIAL, AND MAXIMUM 5' WPD.

5. POSITION:

R REHEAT

P PREHEAT

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

7. PROVIDE VIBRATION ISOLATION PER DETAIL 9/MG601.

DUCTLESS SPLIT SYSTEM SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 2)

INDOOR UNIT

NOMINAL CFM

(NOTE 3)

COOLING (NOTE 4) INDOOR UNIT

MOUNTING

HEIGHT, FT

(NOTE 5) NOTES

SENSIBLE

CAPACITY,

MBH

TOTAL

CAPACITY,

MBH

MINIMUM

SEER

DSS-G-1 MAIN TELECOM AC 700 19 30 19 8 6

DSS-G-2 EM. ELEC. AC 700 19 30 19 8 6

DSS-G-3 MAIN ELEC. AC 700 19 30 19 8 6

DSS-G-4 L2 TELECOM AC 500 12 18 18 8 6

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB, 72.7°F WB 20°F

TELECOM ROOMS 72°F DB, 50% RH 70°F

2. TYPE:

AC COOLING ONLY

3. INDOOR UNIT CFM IS BASED ON MEDIUM FAN SPEED.

4. BASED ON 76°F DB 63°F WB ENTERING INDOOR COIL, AND 105°F DB ENTERING OUTSIDE COIL.

5. HEIGHT IS TO CENTERLINE OF INDOOR UNIT ABOVE FINISHED FLOOR.

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

7. SYSTEM PROVIDED AS PART OF ALTERNATE 1 ONLY.

6. PROVIDE VARIABLE FREQUENCY DRIVE. SEE

DRAWINGS FOR MOUNTING LOCATION

7. INCLUDE MANUFACTURER PROVIDED FAN

AND MOTOR VIBRATION ISOLATION.

13. IF VIBRATION ISOLATION AS SCHEDULED AND SPECIFIED IS PROVIDED

INTERNALLY ON UNIT FAN BY MANUFACTURER, PROVIDE EXTERIOR

NEOPRENE ISOLATION FROM SPECIFIED TYPE NP OR ND ISOLATORS.

IF TYPE NP ISOLATION IS USED, A TYPE IWG NEOPRENE ISOLATION

WASHER AND BUSHING SHALL BE USED TO PREVENT RIGID CONTACT

BETWEEN MOUNTING BOLT AND BUILDING ELEMENTS. REFER TO DETAIL 8

ON SHEET MG602.

14. PROVIDE 1" PLEATED PREFILTERS WITH MERV RATING OF 8 AND

4" PLEATED FINAL FILTERS WITH MERV RATING OF 13. REFER TO

SECTION 23 7000-2.27.

INTAKE/RELIEF HOOD SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

MINIMUM THROAT

AREA, FT²

MAXIMUM

FLOW, CFM

NOMINAL HOOD

SIZE, IN X IN

NOMINAL

HEIGHT, IN

MAXIMUM APD,

IN WG (NOTE 2) NOTES

RH-G-1 BUILDING RELIEF GRV-R 22.5 17000 36X90 5 0.1

NOTES:

1. TYPE:

GRV GRAVITY ROOF VENTILATOR - I - INTAKE

LP LOUVERED PENTHOUSE - R - RELIEF

2. THE STATIC AIR PRESSURE DROP THROUGH THE HOOD AT SCHEDULED CFM.

HOT WATER COIL SCHEDULE

NO.

AREA/SYSTEM

SERVED

CFM

(NOTE 1)

MAXIMUM

GPM

(NOTE 2)

EAT

°F

LAT

°F

PIPE

RUNOUT

SIZES, IN.

CONTROL

VALVE TYPE

(NOTE 3) NOTES

RHC-G-1 GYMNASIUM 9,000 20 55 85 1.5 2

NOTES:

1. MAXIMUM 0.2" WG APD.

2. HOT WATER BASED ON 130°F EWT AND MAXIMUM 5' WPD.

3. CONTROL VALVE TYPE:

2 2-WAY

MARK DATE DESCRIPTION

Signed on using a Digital Signature.

08/31/2023

@JLL@

DocuSign Envelope ID: 3A723061-D4F0-4A2D-AE65-09B756DD2E9F

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

CIVIL ENGINEER AND LANDSCAPE ARCHITECT

Stewart, Inc.

101 W Main Street

Durham, NC 27701

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP, FP, LIGHTING, AV AND SECURITY ENGINEER

Newcomb & Boyd

303 Peachtree Center Avenue, NE

Suite 525

Atlanta, GA 30303

COST ESTIMATOR

Palacio Collaborative

4819 Emperor Boulevard, Suite 400

Durham, NC 27703

LIFE SAFETY

Jensen Hughes

8000 Regency Parkway, Suite 580

Cary, NC 27518

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2022 Duda|Paine Architects, PA

16-14368-02J

303 Peachtree Center Avenue, NE Suite 525 Atlanta, GA 30303-1277 T 404 730-8400 NB Contact: Richard O. Dozier

N&B PROJECT: 17N054

NC Firm Lic. #F-0312 Newcomb & Boyd, LLP

/3

/2

:4

:5

A

M

MG502

HVAC

SCHEDULES

09.01.2023 21611.16

BID SET

W F le m in g

D ri v e M o rg a n to n

N C

(B u ild in g G

S tu d e n t

W e lln e ss a n d

A c ti v it ie s C e n te r

SUPPLY TERMINAL UNIT SCHEDULE

NO.

TYPE

(NOTE 1)

PRIMARY CFM HOT WATER COIL

NOTES

MAXIMUM

COOLING

MAXIMUM

HEATING MINIMUM

CAPACITY

MBH (NOTE 2) GPM (NOTE 3)

PIPE

RUNOUT

SIZES, IN.

TU-G1-1 VV-R 455 125 125 2.2 0.5 0.75

TU-G1-2 VV-R 135 30 30 1.0 0.5 0.75

TU-G1-3 VV-R 485 120 100 4.4 0.5 0.75

TU-G1-4 VV-R 200 40 40 1.3 0.5 0.75

TU-G1-5 VV-R 1,700 340 340 12.3 1.2 0.75

TU-G1-6 VV-R 400 80 80 2.6 0.5 0.75

TU-G2-1 VV-R 180 50 40 1.8 0.5 0.75

TU-G2-2 VV-R 670 350 135 12.8 1.3 0.75

TU-G2-3 VV-R 270 120 55 4.4 0.5 0.75

TU-G2-4 VV-R 360 150 75 5.6 0.6 0.75

TU-G2-5 VV-R 120 25 25 0.8 0.5 0.75

TU-G2-6 VV-R 360 140 75 5.2 0.5 0.75

TU-G2-7 VV-R 1,230 350 250 13.0 1.3 0.75

TU-G2-8 VV-R 1,825 700 365 26.4 2.6 0.75

TU-G2-9 VV-R 1,825 700 365 26.4 2.6 0.75

TU-G2-10 VV-R 170 35 35 1.1 0.5 0.75

TU-G2-11 VV-R 1,660 525 315 19.8 2.0 0.75

TU-G2-12 VV-R 1,040 350 210 13.0 1.3 0.75

TU-G2-13 VV-R 750 575 150 21.5 2.2 0.75

TU-G2-14 VV-R 205 45 45 1.6 0.5 0.75

TU-G2-15 VV-R 1,980 600 400 22.2 2.2 0.75

TU-G2-16 VV-R 450 165 90 6.2 0.6 0.75

TU-G2-17 VV-R 450 165 90 6.2 0.6 0.75

TU-G2-18 VV-R 50 25 25 0.8 0.5 0.75

TU-G2-19 VV-R 150 45 30 1.7 0.5 0.75

TU-G2-20 VV 225 - 50 - - -

TU-G2-21 VV-R 100 25 25 0.8 0.5 0.75

NOTES:

1. TYPE:

VV VARIABLE VOLUME - R REHEAT

CV CONSTANT VOLUME

2. CAPACITY BASED ON 55°F EAT.

3. HOT WATER BASED ON 130°F EWT, 110°F LWT, AND MAXIMUM 3' WPD.

4. SEE SPECIFICATIONS FOR AHRI TESTING/CERTIFICATION REQUIREMENTS AND SUPPLEMENTAL SOUND ATTENUATION REQUIREMENTS. THE MAXIMUM ALLOWABLE SOUND POWER LEVELS IN dB @ 10 pW, SHALL BE:

OCTAVE BAND

2 3 4

CASING RADIATED 52 48 43

DISCHARGE, LESS THAN 900 CFM 60 57 46

DISCHARGE, 900 CFM OR MORE 59 55 53

LEVELS BASED ON MAXIMUM PRIMARY CFM AND MINIMUM DIFFERENTIAL STATIC PRESSURE OF 1" WG.

5. DIFFERENTIAL STATIC PRESSURE DROP ACROSS COMPLETE ASSEMBLY, INCLUDING HEATING COIL, FOR ALL UNITS

SHALL NOT EXCEED 0.3" WG APD.

6. THE DRAWINGS INDICATE THE DESIGN INTENT TO PROVIDE ACCESS TO HEATING COILS, CONTROL PANELS, AND ACCESS DOORS. IF TERMINAL UNITS PROVIDED ARE CONFIGURED DIFFERENTLY, THE ACCESS REQUIREMENTS SHALL BE

ADJUSTED IN THE FIELD.

SOUND ATTENUATOR SCHEDULE

NO.

SA-1

SA-2

NOTES:

1. TYPE:

R

2. ELBOW SOUND ATTENUATOR LENGTHS SHOWN ARE COMBINED CENTERLINE LENGTHS.

3. FORWARD AIR FLOW (+); REVERSE AIR FLOW (-).

4. AIR FLOW AND INSERTION LOSS PERFORMANCE SHALL BE IN ACCORDANCE WITH ASTM E477-2013e.

SERVICE

AHU-G-1 Supply

AHU-G-1 Return

RECTANGULAR

TYPE

(NOTE 1)

RS

RS

S

LENGTH

(NOTE 2)

STANDARD

NOMINAL DIMENSIONS, IN.

WIDTH/

INSIDE DIA.

HEIGHT/

OUTSIDE DIA.

AIRFLOW

CFM

20000

20000

VELOCITY,

FT/MIN

(NOTE 3)

+1043

-1200

MAX.

APD,

IN. WG

0.15

0.15

MINIMUM DYNAMIC INSERTION LOSS, dB

OCTAVE BAND CENTER FREQUENCY, Hz

MAXIMUM GENERATED NOISE, dB

OCTAVE BAND CENTER FREQUENCY, Hz

NOTES

MECHANICAL EQUIPMENT SOUND LIMITS SCHEDULE

NO.

AHU-G-1

AHU-G-2

F-G-1

F-G-2

F-G-3

NOTES:

1. ALL AIR HANDLING UNITS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND

POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE AIR HANDLING

UNIT SCHEDULE AS DETERMINED IN ACCORDANCE WITH THE MOST RECENT VERSION OF AHRI 260

2. ALL FANS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE FAN SCHEDULE AS DETERMINED IN ACCORDANCE

WITH THE MOST RECENT VERSION OF AMCA 300 OR ASHRAE 68/AMCA 330

SOURCE

DISCHARGE

INLET

DISCHARGE

INLET

INLET

INLET

INLET

MAXIMUM Lw IN dB re 10-12 WATTS

OCTAVE BAND CENTER FREQUENCY, Hz

NOTES

MARK DATE DESCRIPTION

Signed on using a Digital Signature.

08/31/2023

@JLL@

DocuSign Envelope ID: 3A723061-D4F0-4A2D-AE65-09B756DD2E9F