GOODWIN MA501-HVAC-SCHEDULES-Rev.0.pdf

PDF 240 KB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This is a Heating, Ventilation, and Air Conditioning (HVAC) Systems Schedule document prepared for the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building A—Goodwin Hall adaptive reuse project, with construction document specifications dated April 17, 2020. The document provides comprehensive technical schedules for multiple HVAC system components, including finned tube radiation units (four units ranging from 1.5 to 3 kilowatts), unit heaters (seven horizontal units with capacities of 2.5 to 5 megabits per hour mounted at heights of 2.5 to 7 feet), energy recovery units (two units with variable capacities and operational parameters for both summer and winter conditions), sound attenuators (one rectangular unit with specific noise attenuation specifications), and ductless split systems (five cooling-only air conditioning units with sensible and total capacities ranging from 12 to 19 and 18 to 30 megabits per hour, respectively). The design conditions specified include summer temperatures of 92.4 degrees Fahrenheit and winter temperatures of 20 degrees Fahrenheit with corresponding humidity parameters for various building zones including classrooms, offices, mechanical spaces, and communication rooms.

The document was developed by a multidisciplinary design team including MEP&FP Engineer Newcomb & Boyd, Architect Duda|Paine Architects, PA, Adaptive Re-Use Architect Belk Architecture, and structural and civil engineering consultants. All specified equipment includes references to electrical drawings for additional equipment characteristics and operational requirements. The schedules establish performance criteria for vibration isolation, static pressure specifications, fan efficiency ratings, and air pressure drop limitations. This technical document serves as the basis for HVAC contractor selection and installation specifications for the Goodwin Hall renovation project and is proprietary to Duda|Paine Architects, PA, with copyright protection established as of 2019.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0544

/1 /2

:2 :3

P

M

MA501

HVAC

SCHEDULES

04/17/20 21611

Construction Documents Bid Set

SCO # 16-14368-02F

N C

S S M

W e st e rn

C a m p u s

B u ild in g A

G o o d w in H a ll

FINNED TUBE RADIATION SCHEDULE

NO.

TYPE

(NOTE 1)

MINIMUM ACTIVE

LENGTH (FT.)

MINIMUM

CAPACITY, kW NOTES

FTR-A-1 ADB 6 3

FTR-A-2 ADB 3 1.5

FTR-A-3 ADB 6 3

FTR-A-4 ADB 3 1.5

UNIT HEATER SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

CAPACITY,

MBH/kW

(NOTE 2)

NOMINAL

CFM

MOUNTING

HEIGHT, FT

(NOTE 4) NOTES

UH-A-1 UTILITY ENTRANCE H 2.5 350 7

UH-A-2 UTILITY ENTRANCE H 2.5 350 7

UH-A-3 MAIN MECHANICAL H 2.5 350 7

UH-A-4 ATTIC H 5 350 2.5

UH-A-5 ATTIC H 5 350 2.5

UH-A-6 ATTIC H 5 350 2.5

UH-A-7 ATTIC H 5 350 2.5

NOTES:

1. TYPE:

H HORIZONTAL

2. MBH GIVEN FOR HOT WATER UNITS, kW FOR ELECTRIC. BASED ON 60°F EAT.

3. HOT WATER BASED ON 130°F EWT, 20°F DIFFERENTIAL, AND MAXIMUM 5' WPD.

4. HEIGHT IS TO CENTERLINE OF HEATER ABOVE FINISHED FLOOR.

5. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

NOTES:

1. TYPE:

ADB ARCHITECTURAL DRAFT BARRIER

2. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT

ELECTRICAL CHARACTERISTICS.

ENERGY RECOVERY UNIT SCHEDULE

NO.

CONDITIONS

OF

OPERATION

OUTSIDE AIR

CONDITIONS OUTSIDE AIR SIDE EXHAUST SIDE

VIBRATION ISOLATION

(NOTE 9)

NOTES°F, DB °F, WB

SUPPLY FAN ENERGY RECOVERY WHEEL (NOTE 4) DX COOLING COIL ELECTRIC HEATING COIL DX REHEAT COIL EXHAUST FAN

ENERGY

RECOVERY

WHEEL (NOTE

10)

TYPE

MIN. STATIC

DEFLECTION

IN.CFM

MAXIMUM

RPM

FAN

TYPE

(NOTE 2)

ESP. IN. WG

(NOTE 3)

MOTOR

CFM

TOTAL ENERGY

EFFECTIVENESS

EAT °F LAT °F

CFM

(NOTE 4)

SENSIBLE

CAPACITY,

MBH

EAT °F LAT °F

CFM

(NOTE 6)

ELECTRIC

HEAT, KW

EAT

°F

LAT

°F

CFM

(NOTE 6)

CAPACITY,

MBH

EAT

°F

LAT

°F CFM

MAXIMUM

RPM

FAN

TYPE

(NOTE 1)

ESP. IN.

WG

(NOTE 7)

MINIMUM

HP

MAXIMUM

BRAKE

HP CFM

EAT °F

MINIMUM

HP

MAXIMUM

BRAKE HP DB WB DB WB DB WB DB WB DB WB

ERU-A-1 SUMMER 92.4 72.7 7200 1800 P 2.5 10 7.5 7200 0.70 92.4 72.7 81.3 66.7 7200 251.2 81.9 67.1 49.5 49.3 -- -- -- -- -- -- -- -- 6200 2350 P 2.5 2 @ 3 4.62 6200 75 62.5 FS 1.0 10, 11, 12

ERU-A-1 WINTER 20 17 7200 -- -- -- -- -- 7200 0.72 20 17 51.9 42.6 -- -- -- -- -- -- 7200 40 51.9 69.4 7200 141 50 70 -- -- -- -- -- -- 6200 70 52 -- --

ERU-A-2 SUMMER 92.4 72.7 5600 3000 P 1.5 7.5 5.5 5600 0.74 92.4 72.7 81.3 66.7 5600 190.6 81.3 66.7 50.3 50.0 -- -- -- -- -- -- -- 5600 2200 P 1.7 5 3.3 4600 75 62.5 FS 1.0 10, 11, 12

ERU-A-2 WINTER 20 17 5600 -- -- -- -- -- 5600 0.75 20 17 51.9 42.6 -- -- -- -- -- -- 5600 25 51.9 65.9 5600 100.6 50 70 -- -- -- -- -- -- 4600 70 52 -- --

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

CLASSROOMS 75°F DB, 50% RH 70°F

OFFICES 75°F DB, 50% RH 70°F

ARTS & ENSEMBLE 75°F DB, 50% RH 70°F

ELECTRICAL 90°DB 50°F

MECHANICAL 104°F DB 50°F

COMMUNICATIONS 78°F DB 70°F

REMAINING SPACE 75°F DB, 50% RH 70°F

2. FAN TYPE:

FAN: WHEEL:

P PLUG AF AIRFOIL

3. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, ENERGY

RECOVERY WHEELS, OR HEATING AND COOLING COILS, BUT DOES

INCLUDE FILTERS.

4. OUTSIDE AIR SUPPLY SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE

MAXIMUM 0.7" WG APD.

5. BASED ON 500 FPM COIL FACE VELOCITY AND MAXIMUM 0.85" WG APD.

6. COIL FACE AREA SHALL BE BASED ON MAXIMUM COOLING DESIGN CFM

WITH MAXIMUM 0.2" WG AIR PRESSURE DROP.

7. EXTERNAL STATIC PRESSURE DPES NOT INCLUDE UNIT CASING, ENERGY

RECOVERY WHEELS, OR COILD, BUT DOES INCLUDE FILTERS.

8. EXHAUST SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE MAXIMUM 0.60"

WG APD.

9. PROVIDE INTERNAL VIBRATION ISOLATION ON FANS.

10. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

11. PROVIDE ONE VARIABLE FREQUENCY DRIVE FOR SUPPLY FAN(S) AND ONE

VARIABLE FREQUENCY DRIVE FOR EXHAUST FAN(S).

12. INDOOR UNIT WILL BE LOCATED IN AN EXISTING SPACE AND SHALL BE

CONSTRUCTED TO FIT THROUGH A STANDARD DOUBLE-DOOR FOR ASSEMBLY.

A

B

C

E

D

F

KEY PLAN

SOUND ATTENUATOR SCHEDULE

NO.

SA-A-1

NOTES:

1. TYPE:

R

2. FORWARD AIR FLOW (+); REVERSE AIR FLOW (-).

3. AIR FLOW AND INSERTION LOSS PERFORMANCE SHALL BE IN ACCORDANCE WITH ASTM E477-2013e.

SERVICE

ERU-A-2 RETURN

RECTANGULAR

TYPE

(NOTE 1)

RS

S

NOMINAL DIMENSIONS, IN.

LENGTH

STANDARD

WIDTH

HEIGHT

FT/MIN

(NOTE 2)

-1,050

MAX.

APD,

IN. WG

0.18

MINIMUM DYNAMIC INSERTION LOSS, dB

OCTAVE BAND CENTER FREQUENCY, Hz

MAXIMUM GENERATED NOISE, dB

OCTAVE BAND CENTER FREQUENCY, Hz

NOTES

MARK DATE DESCRIPTION

DUCTLESS SPLIT SYSTEM SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 2)

INDOOR UNIT

NOMINAL CFM

(NOTE 3)

COOLING (NOTE 4) REVERSE CYCLE HEATING INDOOR

UNIT

MOUNTING

HEIGHT NOTES

SENSIBLE

CAPACITY,

MBH

TOTAL

CAPACITY,

MBH

MINIMUM

EER

CAPACITY,

MBH (NOTE 5)

MINIMUM

HSPF

DSS-A1-1 MAIN COMM. AC 700 19 30 19 -- -- 8

DSS-A1-2 EMERG. ELEC. AC 600 15 24 18 -- -- 8

DSS-A1-3 SECURITY AC 500 12 18 18 -- -- 8

DSS-A2-1 COMM AC 500 12 18 18 -- -- 8

DSS-A3-1 COMM AC 500 12 18 18 -- -- 8

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB, 72.7°F WB 20°F

TELECOM ROOMS 76°F DB, 50% RH 70°F

2. TYPE:

AC COOLING ONLY

HP HEAT PUMP - HEATING AND COOLING

3. INDOOR UNIT CFM IS BASED ON MEDIUM FAN SPEED.

4. BASED ON 76°F DB 63°F WB ENTERING INDOOR COIL, AND 105°F DB ENTERING OUTSIDE COIL.

5. BASED ON 70°F ENTERING INDOOR COIL AND 47°F DB, 43°F WB ENTERING OUTSIDE COIL.

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.