Residence Hall Mechancial_partial set.pdf
PDF 4 MB Posted
- Solicitation number
- 87-07082026
- Issued by
- Cabarrus County, North Carolina
About this file
This document is a set of HVAC mechanical piping plans for a residence hall at the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building E in Durham, North Carolina. The plans were prepared by Newcomb & Boyd Consulting Engineers as part of the MEP (Mechanical, Electrical, Plumbing & Fire Protection) design team, with the adaptive reuse architect Belk Architecture and prime architect Duda|Paine Architects. The construction documents represent bid set SCO # 16-14368-02B, with a project number 17N0541, issued on December 19, 2019. The plans detail HVAC piping layouts across multiple floors, including basement (Level 0), Levels 1 through 5, showing chilled water supply/return (CHS/R and CHS/R), hot water supply/return (HWS/R), refrigerant piping, and condensate drain routing with specified pipe diameters ranging from 0.75 inches to 4 inches. The drawings include typical dorm room layouts, mechanical shaft details, roof equipment plans, and various building spaces including double rooms, single rooms, communal bathrooms, lounges, corridors, and mechanical rooms across the five-story structure.
The document includes key technical specifications such as seismic expansion joint requirements for piping crossings, insulation requirements (1 inch for chilled water mains), condensate drain connections to fan coil units, and provisions for future HVAC expansion with 500 CFM supply and 300 CFM exhaust capacity. Wall fire rating legends indicate 1-hour, 2-hour, and 3-hour fire barriers along with smoke partition designations. The plans reference related drawings including ME602 for piping installations adjacent to occupied spaces, ME200-ME205 for floor plan continuations, and ME301-ME302 for enlarged plans and sections. Multiple change orders (CPR-013, CPR-023, CPR-048, and CPR-064) dated between March 2020 and February 2021 indicate design modifications during the construction document development phase. The design incorporates equipment routing to ERU-E-1 (Energy Recovery Unit), chillers CH-E-1 and CH-E-2, and boiler systems with combustion air intake and vent provisions.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ME301
EXP JTEXP JT
1" CONDENSATE
DRAIN UP
0.75" D
FC-E-CFC-E-C
FC-E-A
ROUTE DRAIN PIPE
DOWN TIGHT TO WALL
TO MOP SINK
SCWP-E-1
SCWP-E-2
PCWP-E-1
PCWP-E-2
FC-E-A
1.25"1.25"1"1"
1.5"1.5" 1.25"1.25"
CHS/R
HWS/R
CHS/R UP
HWS/R UP
T T
T
T
FC-E-C
5 6
A
B
D
10.1
C
2 3 4
7 8 9.2
8.9 9.3
E
D.4
HW BYPASS
CONTROL VALVE
Main Electrical Room
G110 E005
Emergency Electrical Room
G108 E004
Unoccupied Space
G105 E020
Bike Storage
G106 E003
Laundry Room
G102 E001
Vending Machine Area
G004 E012
Utility Room
G103 E006
Trash and Recycle
G101 E007
Corridor
G100 E000
Storage
G010 E009
Washer/ Dryer Service Room
G104 E002
Jan.
G006 E008
Unisex
G008 E010C
T
T T
T
UH-E-3
UH-E-1
UH-E-2
UH-E-4
Stair 3 - East
G100A
E - ST3
Stair 2
G000B
E-ST2
Wall Rating Legend
1-Hour Fire Barrier
2-Hour Fire Barrier
Unrated Walls
Smoke Partition
3-Hour Fire Barrier
2-Hour Smoke Barrier
1-Hour Smoke Barrier
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0541
/2
/2
:3
:1
P
M
ME200
HVAC PIPING
BASEMENT
FLOOR PLAN
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
1/8" = 1'-0"ME200
1 HVAC PIPING FLOOR PLAN LEVEL 0 - EAST
KEY NOTES:
PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS
EXPANSION JOINT.
N
A
B
C
E
D
F
KEY PLAN
GENERAL NOTES THIS SHEET:
1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED
ADJACENT TO NORMALLY OCCUPIED SPACES.
MARK DATE DESCRIPTION
18 03/06/20 CPR-013
54 10/28/2020 CPR-048
10/23/2020
DocuSign Envelope ID: A820F921-9859-49E9-82D1-96C1D448CB5B
FTR-E1-5
REFER TO DRAWING ME202
FOR TYPICAL LAYOUTS
5 6
A
B
D
C
2 3 41 2.6
3 3 3 3 3 3 3
33333333
CHS/R
HWS/R
1.25" D
1.25" D UP
R ef
M E
1.5" D
Double Room
E179
Floor Lounge
E181
Double Room
E177
Double Room
E175
Double Room
E173
Double Room
E171
Double Room
E169
Double Room
E167
Double Room
E180
Double Room
E178
Double Room
E176
Double Room
E174
Double Room
E172
Double Room
E170
Double Room
E168
Double Room
E166
Stair 3 - East
1100A
E - ST3
FC-E1-2
FC-E1-3
FC-E1-4
FC-E1-5
FC-E1-1
FTR-E1-1
FTR-E1-3
CHS/R UP/DN
HWS/R UP/DN
EXP JTEXP JT
R
REFRIGERANT
PIPE UP
1" CONDENSATE
DRAIN UP/DN
0.75" D
HWS/R
CHS/R
CHS/R HWS/R
CHS/R
HWS/R
CHS/R
HWS/R
2"2"
1.5" 2"2"
2"2"
1.5"1.5"
1.5"1.5"
1.5"
FTR-E1-4
FTR-E1-2
1.25"1.25"
1.25"1.25"
REFER TO DRAWING
ME202 FOR TYPICAL
LAYOUTS
T
T
T
T
T
T
A
B
D
10.1
C
8 9.2
8.9
9.3
E
7.1 9 10 11 12 13
15.4
15.9
D.1
XH
XG
XF.1
XF
XE
G
F
H
SS-1-1
Classroom / Flex Space
E101
Men's Room
E105
Women's Room
E104
Shared Kitchen
E109A
Stair 1 - West
1200C
E - ST1
Corridor
E150
Communal Bathroom
E159
Elec.
E161
C.C. Apartment
E147
Double Room
E167
Double Room
E165
Double Room
E166
Double Room
E164
Double Room
E162
Single Room
E160
Single Room
E158
Unisex Toilet
E103
Study Alcove
E108
Bathroom
E158A
Elec.
E102
TeleCom Room
E144
Shared Lounge
E109Vestibule
1000A E110A
Vestibule
1200B E100A
Lobby
E110
Classroom
E107
Jan.
1200A E106
Focus Room
E146
Bedroom
1104A E147A
Storage
1104D E147D
Bathroom
1104B E147B
W/D
1104C E147C
Closet
1104E
E147AB
Corridor
E100
1.5" D DN
1.25" D
1.25" D UP
1.25" D UP
3 1.25" D UP
R ef
M E
1.5" D
Wall Rating Legend
1-Hour Fire Barrier
2-Hour Fire Barrier
Unrated Walls
Smoke Partition
3-Hour Fire Barrier
2-Hour Smoke Barrier
1-Hour Smoke Barrier
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0541
/2
/2
:3
:2
P
M
ME201
HVAC PIPING
LEVEL 1 FLOOR
PLAN
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
1/8" = 1'-0"ME201
1 HVAC PIPING FLOOR PLAN LEVEL 1 - EAST
1/8" = 1'-0"ME201
2 HVAC PIPING FLOOR PLAN LEVEL 1 - WEST
KEY NOTES:
PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS
EXPANSION JOINT.
N
A
B
C
E
D
F
KEY PLAN
GENERAL NOTES THIS SHEET:
1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED
ADJACENT TO NORMALLY OCCUPIED SPACES.
MARK DATE DESCRIPTION
18 03/06/20 CPR-013
28 04/24/20 CPR-23
54 10/28/2020 CPR-048
1.5"1.5"
2"2"1.5"1.5"
1.25"1.25"1.25"1.25"
1.5"1.5"1.25"1.25"
1"1"1"1"
1.25"1.25"0.75"0.75"
0.75"0.75"
1"1"
HWS/R
CHS/R
HWS/R
CHS/R
FTR-E3-3
FC-E-B
T
REFER TO DETAIL 1/ME301
FOR TYPICAL ROOM LAYOUT
REFER TO DETAIL 1/ME301
FOR TYPICAL ROOM LAYOUT
5 6
A
B
D
C
2 3 41 2.3 2.6
Double Room
E479
Double Room
E477
Double Room
E475
Double Room
E473
Double Room
E471
Double Room
E469
Double Room
E467
Double Room
E480
Double Room
E478
Double Room
E476
Double Room
E474
Double Room
E472
Double Room
E470
Double Room
E468
Double Room
E466
Floor Lounge
E481
Corridor
E450
3 3 3 3 3 3 3
33333
R ef
M E
4 0.75" D 1" D0.75" D1" D
1.25" D
0.75" D
1.25" D DN
FC-E-C
FC-E-C
CHS/R UP/DN
HWS/R UP/DN
HWS/R
CHS/R
1.5"1.5"
2"2"
HWS/R CHS/R
2"2"
1.5"1.5"
2"2"
1.5"1.5"
HWS/R
CHS/R
1.5"1.5"
2"2"
1.25"1.25"
1.5"1.5"
1.5"1.5"
2"2"
HWS/R
CHS/R
1.25"1.25"
1.5"1.5"
1"1"
1.25"1.25"
1"1"
1.25"1.25"
0.75"0.75"
1"1"
EXP JTEXP JT
FC-E-E
DSS-E-A
FC-E-A
FC-E-D
FC-E-D
FC-E-A
R
REFRIGERANT
PIPES UP
(TYP.)
1" CONDENSATE
DRAIN UP/DN
0.75" D
T
T
T
T
T
T
FTR-E3-2
FTR-E3-1
FC-E-AFC-E-A
ME301
TYP
SEE DETAIL 1/ME301 FOR
TYPICAL ROOM LAYOUT
SEE DETAIL 1/ME301
FOR TYPICAL ROOM
LAYOUT
SEE DETAIL 1/ME301 FOR
TYPICAL ROOM LAYOUT
FC-E-B
T
T
FC-E-A
T
T
A
B
D
10.1
C
8 9.2
8.9
9.3
E
7.1 9 10 11 12 13
15.4
15.9
D.1
XH
XG
XF.1
XF
XE
8.4
G
F
H
W/D
4203C E441C
Double Room
E433
Double Room
E431
Double Room
E429
Double Room
E427
Double Room
E425
Double Room
E423
Double Room
E421
Single Room
E419
Single Room
E417
Double Room
E418
Double Room
E420
Double Room
E422
Double Room
E424
Double Room
E426
Communal Bathroom
E430
Double Room
E413
Double Room
E411
Double Room
E414
Double Room
E410
Double Room
E412
Floor Lounge
E401
Elec.
E428
Jan
E416
Double Room
E465
Double Room
E464
Double Room
E462
Single Room
E460
Single Room
E458
Focus Room
E446
Elec.
E461
Single Room
E415
Bathroom
E417A
Bathroom
E458A
TeleCom Room
E444
Corridor
E450
Elevator Lobby
E440
Corridor
E564
Bedroom
4203A E441A
Bathroom
4203B E441B
Focus Room
E442
C.C.Apartment
E441
Bedroom
4104A E447A
Closet
4104E
E447AB
C.C. Apartment
E447
Storage
4104D E447D
W/D
4104C E447C
Bathroom
4104B E447B
Storage
4203D E441D
Closet
4203E
E441AB
R ef
M E
4" CHS UP
4" CHS UP
2" HWS UP
2" HWS UP
3 3 3 3 3 3 3 3
1.25" D DN
1.25" D DN
1.25" D DN
1.25" D DN
1" D 1" D
0.75" D
1" D
1.25" D
1.25" D 0.75" D0.75" D
1.25" D
0.75" D
0.75" D
1.25" D 1" D
Wall Rating Legend
1-Hour Fire Barrier
2-Hour Fire Barrier
Unrated Walls
Smoke Partition
3-Hour Fire Barrier
2-Hour Smoke Barrier
1-Hour Smoke Barrier
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0541
/2
/2
:3
:3
P
M
ME202
HVAC PIPING
LEVELS 2-4
FLOOR PLANS
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
1/8" = 1'-0"ME202
1 HVAC PIPING FLOOR PLAN LEVEL 4 - EAST
1/8" = 1'-0"ME202
2 HVAC PIPING FLOOR PLAN LEVEL 4 - WEST
KEY NOTES:
PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS
EXPANSION JOINT.
CHS/R AND HWS/R PIPING ROUTED TO ERU-E-1 ON LEVEL 4 ONLY
0.75" CONDENSATE DRAIN CONNECTION TO FAN COIL UNIT.
REFER TO ENLARGED PLAN 1/ME301.
CONDENSATE DRAIN LINE CLEANOUT LOCATION.
N
A
B
C
E
D
F
KEY PLAN
GENERAL NOTES THIS SHEET:
1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED
ADJACENT TO NORMALLY OCCUPIED SPACES.
MARK DATE DESCRIPTION
18 03/06/20 CPR-013
28 04/24/20 CPR-23
54 10/28/2020 CPR-048
ERU-E-1
CHS/R DN
HWS/R DN
EXP JTEXP JT
CU-E-A CU-E-A
CU-E-A
CU-E-A
CU-E-A
R
1" CONDENSATE
DRAIN DN
0.75" D
REFRIGERANT
PIPE DN (TYP.)
REFER TO DRAWING ME202 FOR
TYPICAL LAYOUTS
ME301
TYP
SS-E-A
T
A
B
D
10.1
C
8.9
8.9
9.3
9.3
E
7.1 9 10 11 12 13
15.4
15.9
D.1
XH
XG
XF.1
XF
XE
G
F
H
CHW BYPASS
CONTROL VALVE
Corridor
E500
Double Room
E533
Double Room
E531
Double Room
E529
Double Room
E527
Double Room
E525
Double Room
E523
Single Room
E519
Single Room
E517
Double Room
E512
Double Room
E514
Bathroom
E517A
Double Room
E515
Double Room
E513
Double Room
E511
Double Room
E510
Floor Lounge
E501
C.C. Apartment
E541
Focus Room
E542
Jan
E516
Double Room
E518
Double Room
E520
Double Room
E522
Double Room
E524
Double Room
E526
Communal Bathroom
E530
Elec.
E528
Double Room
E521
TeleCom Room
E544
Bathroom
5203B E541B
Closet
5203E
E541AB
Boiler Room
5102A E565A
Bedroom
5203A E541A
W/D
5203C E541C
Storage
5203D E541D
Mechanical Room
E565
SEE DRAWING
ME202
Elevator Lobby
Wall Rating Legend
1-Hour Fire Barrier
2-Hour Fire Barrier
Unrated Walls
Smoke Partition
3-Hour Fire Barrier
2-Hour Smoke Barrier
1-Hour Smoke Barrier
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0541
/2
/2
:3
:4
P
M
ME205
HVAC PIPING
LEVEL 5 FLOOR
PLAN
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
1/8" = 1'-0"ME205
1 HVAC PIPING FLOOR PLAN LEVEL 5 - WEST
N
A
B
C
E
D
F
KEY PLAN
GENERAL NOTES THIS SHEET:
1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED
ADJACENT TO NORMALLY OCCUPIED SPACES.
MARK DATE DESCRIPTION
18 03/06/20 CPR-013
54 10/28/2020 CPR-048
Level 3 1196' - 4"
Level 4 1207' - 8"
ABC
BOTTOM OF 12" BEAM
INSULATED CHS/R MAINS
CEILING
SUPPLY DUCT 8" DEEP
WITH 1" INSULATION
SPRINKLER MAIN
INSULATED HWS/R MAINS
RECESSED LUMINAIRE
CEILING
COOLING SUPPLY
DIFFUSER
FAN-COIL UNIT
RETURN DUCT WITH
1" LINING
VENTILATION SUPPLY
DIFFUSER
ERU-E-1
30X30
OUTSIDE AIR INTAKE
EXHAUST AIR
DISCHARGE
THROUGH SCREEN
WALL LOUVER
DUCT SUPPORT
RAIL (TYPICAL)
ROOF CURB
FS FS
PROVIDE SLEEVE
AT DUCT WALL
PENETRATION
(TYPICAL)
B-E-2B-E-1
PHWP-E-1
PHWP-E-2
SHWP-E-2
SHWP-E-1
VFD SHWP-E-1
VFD SHWP-E-2
BCS PANEL
BCS PANELCOMM ROOM SPLIT
SYSTEM CONDENSING
UNIT (TYP. 6)
X
X
CHS/R DN
HWS/R DN
HWS/R
BOILER VENT UP INSTALLED
PER MANUFACTURER'S
INSTRUCTIONS (TYP. 2). SEE
DETAIL.
BOILER COMBUSTION AIR INTAKE UP (TYP. 2).
INSTALL PER MANUFACTURER'S INSTRUCTIONS.
TERMINATE WITH GOOSE NECK TURNED OVER
ROOF WITH OPENING AT MINIMUM HEIGHT OF 1'
ABOVE THE ROOF. PROVIDE BIRD SCREEN.
SEE DRAWING ME105
FOR CONTINUATION
SEE DRAWING ME205
FOR CONTINUATION
ME302
SA-E-4 IN
VERTICAL
SA-E-3 IN
VERTICAL
SA-E-2 IN
VERTICAL
SA-E-1 IN
VERTICAL
PROVIDE FLEXIBLE DUCT
CONNECTIONS WHERE
DUCT CROSSES
EXPANSION JOINT (TYP. 2)
PROVIDE SEISMIC
EXPANSION JOINTS WHERE
PIPING CROSSES
EXPANSION JOINT (TYP.)
ME302
HEATING WATER
EXPANSION TANK
STACKED
REFRIGERANT
PIPING
HWS/R DN AND
TO ERU PER
DETAIL 3/ME601
CHS/R
EQUIPMENT
PAD (TYP)
CHS/R AND HWS/R
ROUTED TO ERU
PER DETAIL 3/ME601
SS-E-A
FSFS
8X6 S-SR________
190 (TYP 2)
12X6 S-SR________
8X6 R-SR
(TYP 2)
FC-E-B14X8
EB
T
A
B
D
10.1
C
7 8 9.28.9 9.3
D.4
7.1 10
D.1
8.4
CHW BYPASS
CONTROL VALVE
DUCT SMOKE DETECTOR LOCATION
FOR STACKED SUPPLY AND
EXHAUST - REFER TO SECTION 23
0010-1.2 FOR DIVISION OF WORK
VFD ERU-E-1
EXHAUST
VFD ERU-E-1
SUPPLY
TeleCom Room
E544
Boiler Room
5102A E565A
Mechanical Room
E565
D
ROUTE 0.75"
CONDENSATE TO
NEAREST FLOUR DRAIN
HEATING WATER INLINE
AIR SEPARATOR
REFRIGERANT PIPING
HWP-E-ERU1
HWS/R ROUTED TO
ERU PREHEAT COIL
PER DETAIL
10/ME601
T
0.75" D
2'-6" DEEP PLENUM
FULLSIZE OF LOUVER
HEAT TRACE
CONTROLLER
SHADING INDICATES
EXTENT OF HEAT TRACE
ME301
6Ø S-PF
30 (TYP .)
24X24 R-EG
(TYP.)
8Ø S-PF
170 (TYP .)
FC-E-A FC-E-A
16X8
CHS/R
HWS/R
CHS/R
HWS/R
24X10
22X22 R-FG
(TYP .)
10Ø 10Ø
6X66X6 24X10
D
T
T
F F
A
B
7 87.1
F F
SCWP-E-1
SCWP-E-2
PCWP-E-1
PCWP-E-2
VFD SCWP-E-1
VFD SCWP-E-2
BCS PANEL
CHILLED WATER
INLINE AIR
SEPARATOR
DECOUPLER
BRIDGE
CHS/R TO BUILDING - SEE
DRAWING ME200 FOR
CONTINUATION
PLUMBING
EQUIPMENT -
SEE PLUMBING
DRAWINGS
CHILLED WATER
EXPANSION
TANK
FC-E-C
T
DROP CHS/R PIPES
UNDERGROUND
A
B
D
C
7 87.1
D.1
Utility Room
G103 E006
ROUTE 0.75" CONDENSATE TO
NEAREST FLOOR DRAIN
D
CAP SUPPLY AND
EXHAUST FOR FUTURE
EXPANSION. CAPACITY
IS 500 CFM FOR SUPPLY
AND 300 CFM FOR
EXHAUST
12X8
12X10
CHS/R TO CHILLERS CH-E-1 AND CH-
E-2 - SEE DRAWING M102 IN SITE
PACKAGE FOR CONTINUATION AND
ADDITIONAL INFORMATION
CONCENTRIC DIRECT VENT AND
INTAKE INSTALLED PER
MANUFACTURER'S INSTSTRUCTIONS.
TERMINATE MINIMUM 2' ABOVE
DOOR.
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0542
/1 /2
:3 :2
P
M
ME301
HVAC
ENLARGED
PLANS AND
SECTIONS
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
1/2" = 1'-0"ME301
3 HVAC SECTION - CORRIDOR AND TYPICAL DORM ROOM
1/4" = 1'-0"ME301
4 HVAC ENLARGED PLAN - MECHANICAL ROOF
1/4" = 1'-0"ME301
1 HVAC ENLARGED PLAN - TYPICAL DORM ROOM
1/4" = 1'-0"ME301
2 HVAC ENLARGED PLAN - UTILITY ROOM
A
B
C
E
D
F
KEY PLAN
MARK DATE DESCRIPTION
18 03/06/2020 CPR-013
28 04/24/2020 CPR-23
54 10/28/2020 CPR-048
70 02/12/2021 CPR-064
DocuSign Envelope ID: A6A96DAF-7FAA-4036-BAF6-4FDB4204473B
02/12/2021
Level 1 0' - 0"
Level 2 14' - 0"
Level 3 25' - 4"
Level 4 36' - 8"
Level 5 48' - 0"
T.O. High Parapet 61' - 4"
Basement -12' - 0"
28X26
FS FS
FS
FSFS
FS
FS
FS
FS
FS FS
FS
FS
FS
20X20
10X10 10X12
10X12
8X16 8X16
8X16 8X16 6X16
6X16
8X16
8X20
8X16
10X22
8X18
FS
FS
FS
FS
D D.4
D.1
Level 5 48' - 0"
T.O. High Parapet
61' - 4"ENTHALPY WHEEL
PREHEAT COIL
COOLING COIL
SUPPLY
FAN
SECTION
ACCESS
SECTION
ACCESS
SECTION
FILTERS
ACCESS
SECTION
EXHAUST
FAN
SECTION
FILTERS
ACCESS
SECTION
ACCESS
SECTION
ACCESS SECTION
ACCESS SECTION
ACCESS SECTION
REHEAT COILROOF CURB
ERU-E-1
ACCESS SECTION
26X26
28X26
FS
FS
CHS/R
HWS/R HWS/R
B DC
D.1
COORDINATE HEIGHT OF ROOF
CURB AND SUPPLY DUCT
DISCHARGE LOCATION TO AVOID
EXPANSION JOINT AND
STRUCTURAL STEEL AT WALL
PENETRATION
CH-E-1 CH-E-2
DROP CHS/R PIPING
UNDERGROUND
SEE DRAWING M102 IN THE SITE
PACKAGE FOR CONTINUATION
10.1
6" CHS/R
Newcomb&Boyd
CONSULTANTS AND ENGINEERS
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St, Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
ADAPTIVE RE-USE ARCHITECT
Belk Architecture
735 9th Street
Durham, NC 27705
LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
CIVIL ENGINEER
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
STRUCTURAL ENGINEER
Bennett & Pless
1309 Amble Drive
Charlotte, NC 28206
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
FOOD SERVICE DESIGN
Food Design Associates
615 South College Street
9th Floor
Charlotte, NC 28202
COST ESTIMATOR
RM Rutherford & Associates Inc
3328 Mill Pond Road
Charlotte, NC 28226
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2019 Duda|Paine Architects, PA
Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier
N&B PROJECT:17N0541
/1
/2
:2 :3
P
M
ME302
HVAC
ENLARGED
PLANS AND
SECTIONS
12/19/2019 21611
Construction Documents Bid Set
SCO # 16-14368-02B
N C
S S M
W e st e rn
C a m p u s
B u ild in g E
R e si d e n c e H a ll
A
B
C
E
D
F
KEY PLAN
1/4" = 1'-0"ME302
1 HVAC SECTION - MECH SHAFT
1/4" = 1'-0"ME302
2 HVAC SECTION - ERU-E-1
MARK DATE DESCRIPTION
1/4" = 1'-0"ME302
3 HVAC ENLARGED PLAN - CHILLERS
DocuSign Envelope ID: 87EEFB9D-D330-489C-82A2-A358420EA01E
12/18/19
File details come from the government source that posted it. Updated .