Residence Hall Mechancial_partial set.pdf

PDF 4 MB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This document is a set of HVAC mechanical piping plans for a residence hall at the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building E in Durham, North Carolina. The plans were prepared by Newcomb & Boyd Consulting Engineers as part of the MEP (Mechanical, Electrical, Plumbing & Fire Protection) design team, with the adaptive reuse architect Belk Architecture and prime architect Duda|Paine Architects. The construction documents represent bid set SCO # 16-14368-02B, with a project number 17N0541, issued on December 19, 2019. The plans detail HVAC piping layouts across multiple floors, including basement (Level 0), Levels 1 through 5, showing chilled water supply/return (CHS/R and CHS/R), hot water supply/return (HWS/R), refrigerant piping, and condensate drain routing with specified pipe diameters ranging from 0.75 inches to 4 inches. The drawings include typical dorm room layouts, mechanical shaft details, roof equipment plans, and various building spaces including double rooms, single rooms, communal bathrooms, lounges, corridors, and mechanical rooms across the five-story structure.

The document includes key technical specifications such as seismic expansion joint requirements for piping crossings, insulation requirements (1 inch for chilled water mains), condensate drain connections to fan coil units, and provisions for future HVAC expansion with 500 CFM supply and 300 CFM exhaust capacity. Wall fire rating legends indicate 1-hour, 2-hour, and 3-hour fire barriers along with smoke partition designations. The plans reference related drawings including ME602 for piping installations adjacent to occupied spaces, ME200-ME205 for floor plan continuations, and ME301-ME302 for enlarged plans and sections. Multiple change orders (CPR-013, CPR-023, CPR-048, and CPR-064) dated between March 2020 and February 2021 indicate design modifications during the construction document development phase. The design incorporates equipment routing to ERU-E-1 (Energy Recovery Unit), chillers CH-E-1 and CH-E-2, and boiler systems with combustion air intake and vent provisions.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ME301

EXP JTEXP JT

1" CONDENSATE

DRAIN UP

0.75" D

FC-E-CFC-E-C

FC-E-A

ROUTE DRAIN PIPE

DOWN TIGHT TO WALL

TO MOP SINK

SCWP-E-1

SCWP-E-2

PCWP-E-1

PCWP-E-2

FC-E-A

1.25"1.25"1"1"

1.5"1.5" 1.25"1.25"

CHS/R

HWS/R

CHS/R UP

HWS/R UP

T T

T

T

FC-E-C

5 6

A

B

D

10.1

C

2 3 4

7 8 9.2

8.9 9.3

E

D.4

HW BYPASS

CONTROL VALVE

Main Electrical Room

G110 E005

Emergency Electrical Room

G108 E004

Unoccupied Space

G105 E020

Bike Storage

G106 E003

Laundry Room

G102 E001

Vending Machine Area

G004 E012

Utility Room

G103 E006

Trash and Recycle

G101 E007

Corridor

G100 E000

Storage

G010 E009

Washer/ Dryer Service Room

G104 E002

Jan.

G006 E008

Unisex

G008 E010C

T

T T

T

UH-E-3

UH-E-1

UH-E-2

UH-E-4

Stair 3 - East

G100A

E - ST3

Stair 2

G000B

E-ST2

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0541

/2

/2

:3

:1

P

M

ME200

HVAC PIPING

BASEMENT

FLOOR PLAN

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

1/8" = 1'-0"ME200

1 HVAC PIPING FLOOR PLAN LEVEL 0 - EAST

KEY NOTES:

PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS

EXPANSION JOINT.

N

A

B

C

E

D

F

KEY PLAN

GENERAL NOTES THIS SHEET:

1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED

ADJACENT TO NORMALLY OCCUPIED SPACES.

MARK DATE DESCRIPTION

18 03/06/20 CPR-013

54 10/28/2020 CPR-048

10/23/2020

DocuSign Envelope ID: A820F921-9859-49E9-82D1-96C1D448CB5B

FTR-E1-5

REFER TO DRAWING ME202

FOR TYPICAL LAYOUTS

5 6

A

B

D

C

2 3 41 2.6

3 3 3 3 3 3 3

33333333

CHS/R

HWS/R

1.25" D

1.25" D UP

R ef

M E

1.5" D

Double Room

E179

Floor Lounge

E181

Double Room

E177

Double Room

E175

Double Room

E173

Double Room

E171

Double Room

E169

Double Room

E167

Double Room

E180

Double Room

E178

Double Room

E176

Double Room

E174

Double Room

E172

Double Room

E170

Double Room

E168

Double Room

E166

Stair 3 - East

1100A

E - ST3

FC-E1-2

FC-E1-3

FC-E1-4

FC-E1-5

FC-E1-1

FTR-E1-1

FTR-E1-3

CHS/R UP/DN

HWS/R UP/DN

EXP JTEXP JT

R

REFRIGERANT

PIPE UP

1" CONDENSATE

DRAIN UP/DN

0.75" D

HWS/R

CHS/R

CHS/R HWS/R

CHS/R

HWS/R

CHS/R

HWS/R

2"2"

1.5" 2"2"

2"2"

1.5"1.5"

1.5"1.5"

1.5"

FTR-E1-4

FTR-E1-2

1.25"1.25"

1.25"1.25"

REFER TO DRAWING

ME202 FOR TYPICAL

LAYOUTS

T

T

T

T

T

T

A

B

D

10.1

C

8 9.2

8.9

9.3

E

7.1 9 10 11 12 13

15.4

15.9

D.1

XH

XG

XF.1

XF

XE

G

F

H

SS-1-1

Classroom / Flex Space

E101

Men's Room

E105

Women's Room

E104

Shared Kitchen

E109A

Stair 1 - West

1200C

E - ST1

Corridor

E150

Communal Bathroom

E159

Elec.

E161

C.C. Apartment

E147

Double Room

E167

Double Room

E165

Double Room

E166

Double Room

E164

Double Room

E162

Single Room

E160

Single Room

E158

Unisex Toilet

E103

Study Alcove

E108

Bathroom

E158A

Elec.

E102

TeleCom Room

E144

Shared Lounge

E109Vestibule

1000A E110A

Vestibule

1200B E100A

Lobby

E110

Classroom

E107

Jan.

1200A E106

Focus Room

E146

Bedroom

1104A E147A

Storage

1104D E147D

Bathroom

1104B E147B

W/D

1104C E147C

Closet

1104E

E147AB

Corridor

E100

1.5" D DN

1.25" D

1.25" D UP

1.25" D UP

3 1.25" D UP

R ef

M E

1.5" D

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0541

/2

/2

:3

:2

P

M

ME201

HVAC PIPING

LEVEL 1 FLOOR

PLAN

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

1/8" = 1'-0"ME201

1 HVAC PIPING FLOOR PLAN LEVEL 1 - EAST

1/8" = 1'-0"ME201

2 HVAC PIPING FLOOR PLAN LEVEL 1 - WEST

KEY NOTES:

PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS

EXPANSION JOINT.

N

A

B

C

E

D

F

KEY PLAN

GENERAL NOTES THIS SHEET:

1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED

ADJACENT TO NORMALLY OCCUPIED SPACES.

MARK DATE DESCRIPTION

18 03/06/20 CPR-013

28 04/24/20 CPR-23

54 10/28/2020 CPR-048

1.5"1.5"

2"2"1.5"1.5"

1.25"1.25"1.25"1.25"

1.5"1.5"1.25"1.25"

1"1"1"1"

1.25"1.25"0.75"0.75"

0.75"0.75"

1"1"

HWS/R

CHS/R

HWS/R

CHS/R

FTR-E3-3

FC-E-B

T

REFER TO DETAIL 1/ME301

FOR TYPICAL ROOM LAYOUT

REFER TO DETAIL 1/ME301

FOR TYPICAL ROOM LAYOUT

5 6

A

B

D

C

2 3 41 2.3 2.6

Double Room

E479

Double Room

E477

Double Room

E475

Double Room

E473

Double Room

E471

Double Room

E469

Double Room

E467

Double Room

E480

Double Room

E478

Double Room

E476

Double Room

E474

Double Room

E472

Double Room

E470

Double Room

E468

Double Room

E466

Floor Lounge

E481

Corridor

E450

3 3 3 3 3 3 3

33333

R ef

M E

4 0.75" D 1" D0.75" D1" D

1.25" D

0.75" D

1.25" D DN

FC-E-C

FC-E-C

CHS/R UP/DN

HWS/R UP/DN

HWS/R

CHS/R

1.5"1.5"

2"2"

HWS/R CHS/R

2"2"

1.5"1.5"

2"2"

1.5"1.5"

HWS/R

CHS/R

1.5"1.5"

2"2"

1.25"1.25"

1.5"1.5"

1.5"1.5"

2"2"

HWS/R

CHS/R

1.25"1.25"

1.5"1.5"

1"1"

1.25"1.25"

1"1"

1.25"1.25"

0.75"0.75"

1"1"

EXP JTEXP JT

FC-E-E

DSS-E-A

FC-E-A

FC-E-D

FC-E-D

FC-E-A

R

REFRIGERANT

PIPES UP

(TYP.)

1" CONDENSATE

DRAIN UP/DN

0.75" D

T

T

T

T

T

T

FTR-E3-2

FTR-E3-1

FC-E-AFC-E-A

ME301

TYP

SEE DETAIL 1/ME301 FOR

TYPICAL ROOM LAYOUT

SEE DETAIL 1/ME301

FOR TYPICAL ROOM

LAYOUT

SEE DETAIL 1/ME301 FOR

TYPICAL ROOM LAYOUT

FC-E-B

T

T

FC-E-A

T

T

A

B

D

10.1

C

8 9.2

8.9

9.3

E

7.1 9 10 11 12 13

15.4

15.9

D.1

XH

XG

XF.1

XF

XE

8.4

G

F

H

W/D

4203C E441C

Double Room

E433

Double Room

E431

Double Room

E429

Double Room

E427

Double Room

E425

Double Room

E423

Double Room

E421

Single Room

E419

Single Room

E417

Double Room

E418

Double Room

E420

Double Room

E422

Double Room

E424

Double Room

E426

Communal Bathroom

E430

Double Room

E413

Double Room

E411

Double Room

E414

Double Room

E410

Double Room

E412

Floor Lounge

E401

Elec.

E428

Jan

E416

Double Room

E465

Double Room

E464

Double Room

E462

Single Room

E460

Single Room

E458

Focus Room

E446

Elec.

E461

Single Room

E415

Bathroom

E417A

Bathroom

E458A

TeleCom Room

E444

Corridor

E450

Elevator Lobby

E440

Corridor

E564

Bedroom

4203A E441A

Bathroom

4203B E441B

Focus Room

E442

C.C.Apartment

E441

Bedroom

4104A E447A

Closet

4104E

E447AB

C.C. Apartment

E447

Storage

4104D E447D

W/D

4104C E447C

Bathroom

4104B E447B

Storage

4203D E441D

Closet

4203E

E441AB

R ef

M E

4" CHS UP

4" CHS UP

2" HWS UP

2" HWS UP

3 3 3 3 3 3 3 3

1.25" D DN

1.25" D DN

1.25" D DN

1.25" D DN

1" D 1" D

0.75" D

1" D

1.25" D

1.25" D 0.75" D0.75" D

1.25" D

0.75" D

0.75" D

1.25" D 1" D

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0541

/2

/2

:3

:3

P

M

ME202

HVAC PIPING

LEVELS 2-4

FLOOR PLANS

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

1/8" = 1'-0"ME202

1 HVAC PIPING FLOOR PLAN LEVEL 4 - EAST

1/8" = 1'-0"ME202

2 HVAC PIPING FLOOR PLAN LEVEL 4 - WEST

KEY NOTES:

PROVIDE SEISMIC EXPANSION JOINTS WHERE PIPES CROSS

EXPANSION JOINT.

CHS/R AND HWS/R PIPING ROUTED TO ERU-E-1 ON LEVEL 4 ONLY

0.75" CONDENSATE DRAIN CONNECTION TO FAN COIL UNIT.

REFER TO ENLARGED PLAN 1/ME301.

CONDENSATE DRAIN LINE CLEANOUT LOCATION.

N

A

B

C

E

D

F

KEY PLAN

GENERAL NOTES THIS SHEET:

1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED

ADJACENT TO NORMALLY OCCUPIED SPACES.

MARK DATE DESCRIPTION

18 03/06/20 CPR-013

28 04/24/20 CPR-23

54 10/28/2020 CPR-048

ERU-E-1

CHS/R DN

HWS/R DN

EXP JTEXP JT

CU-E-A CU-E-A

CU-E-A

CU-E-A

CU-E-A

R

1" CONDENSATE

DRAIN DN

0.75" D

REFRIGERANT

PIPE DN (TYP.)

REFER TO DRAWING ME202 FOR

TYPICAL LAYOUTS

ME301

TYP

SS-E-A

T

A

B

D

10.1

C

8.9

8.9

9.3

9.3

E

7.1 9 10 11 12 13

15.4

15.9

D.1

XH

XG

XF.1

XF

XE

G

F

H

CHW BYPASS

CONTROL VALVE

Corridor

E500

Double Room

E533

Double Room

E531

Double Room

E529

Double Room

E527

Double Room

E525

Double Room

E523

Single Room

E519

Single Room

E517

Double Room

E512

Double Room

E514

Bathroom

E517A

Double Room

E515

Double Room

E513

Double Room

E511

Double Room

E510

Floor Lounge

E501

C.C. Apartment

E541

Focus Room

E542

Jan

E516

Double Room

E518

Double Room

E520

Double Room

E522

Double Room

E524

Double Room

E526

Communal Bathroom

E530

Elec.

E528

Double Room

E521

TeleCom Room

E544

Bathroom

5203B E541B

Closet

5203E

E541AB

Boiler Room

5102A E565A

Bedroom

5203A E541A

W/D

5203C E541C

Storage

5203D E541D

Mechanical Room

E565

SEE DRAWING

ME202

Elevator Lobby

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0541

/2

/2

:3

:4

P

M

ME205

HVAC PIPING

LEVEL 5 FLOOR

PLAN

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

1/8" = 1'-0"ME205

1 HVAC PIPING FLOOR PLAN LEVEL 5 - WEST

N

A

B

C

E

D

F

KEY PLAN

GENERAL NOTES THIS SHEET:

1. UTILIZE 1 AND 2 ON DRAWING ME602 WHERE PIPING IS INSTALLED

ADJACENT TO NORMALLY OCCUPIED SPACES.

MARK DATE DESCRIPTION

18 03/06/20 CPR-013

54 10/28/2020 CPR-048

Level 3 1196' - 4"

Level 4 1207' - 8"

ABC

BOTTOM OF 12" BEAM

INSULATED CHS/R MAINS

CEILING

SUPPLY DUCT 8" DEEP

WITH 1" INSULATION

SPRINKLER MAIN

INSULATED HWS/R MAINS

RECESSED LUMINAIRE

CEILING

COOLING SUPPLY

DIFFUSER

FAN-COIL UNIT

RETURN DUCT WITH

1" LINING

VENTILATION SUPPLY

DIFFUSER

ERU-E-1

30X30

OUTSIDE AIR INTAKE

EXHAUST AIR

DISCHARGE

THROUGH SCREEN

WALL LOUVER

DUCT SUPPORT

RAIL (TYPICAL)

ROOF CURB

FS FS

PROVIDE SLEEVE

AT DUCT WALL

PENETRATION

(TYPICAL)

B-E-2B-E-1

PHWP-E-1

PHWP-E-2

SHWP-E-2

SHWP-E-1

VFD SHWP-E-1

VFD SHWP-E-2

BCS PANEL

BCS PANELCOMM ROOM SPLIT

SYSTEM CONDENSING

UNIT (TYP. 6)

X

X

CHS/R DN

HWS/R DN

HWS/R

BOILER VENT UP INSTALLED

PER MANUFACTURER'S

INSTRUCTIONS (TYP. 2). SEE

DETAIL.

BOILER COMBUSTION AIR INTAKE UP (TYP. 2).

INSTALL PER MANUFACTURER'S INSTRUCTIONS.

TERMINATE WITH GOOSE NECK TURNED OVER

ROOF WITH OPENING AT MINIMUM HEIGHT OF 1'

ABOVE THE ROOF. PROVIDE BIRD SCREEN.

SEE DRAWING ME105

FOR CONTINUATION

SEE DRAWING ME205

FOR CONTINUATION

ME302

SA-E-4 IN

VERTICAL

SA-E-3 IN

VERTICAL

SA-E-2 IN

VERTICAL

SA-E-1 IN

VERTICAL

PROVIDE FLEXIBLE DUCT

CONNECTIONS WHERE

DUCT CROSSES

EXPANSION JOINT (TYP. 2)

PROVIDE SEISMIC

EXPANSION JOINTS WHERE

PIPING CROSSES

EXPANSION JOINT (TYP.)

ME302

HEATING WATER

EXPANSION TANK

STACKED

REFRIGERANT

PIPING

HWS/R DN AND

TO ERU PER

DETAIL 3/ME601

CHS/R

EQUIPMENT

PAD (TYP)

CHS/R AND HWS/R

ROUTED TO ERU

PER DETAIL 3/ME601

SS-E-A

FSFS

8X6 S-SR________

190 (TYP 2)

12X6 S-SR________

8X6 R-SR

(TYP 2)

FC-E-B14X8

EB

T

A

B

D

10.1

C

7 8 9.28.9 9.3

D.4

7.1 10

D.1

8.4

CHW BYPASS

CONTROL VALVE

DUCT SMOKE DETECTOR LOCATION

FOR STACKED SUPPLY AND

EXHAUST - REFER TO SECTION 23

0010-1.2 FOR DIVISION OF WORK

VFD ERU-E-1

EXHAUST

VFD ERU-E-1

SUPPLY

TeleCom Room

E544

Boiler Room

5102A E565A

Mechanical Room

E565

D

ROUTE 0.75"

CONDENSATE TO

NEAREST FLOUR DRAIN

HEATING WATER INLINE

AIR SEPARATOR

REFRIGERANT PIPING

HWP-E-ERU1

HWS/R ROUTED TO

ERU PREHEAT COIL

PER DETAIL

10/ME601

T

0.75" D

2'-6" DEEP PLENUM

FULLSIZE OF LOUVER

HEAT TRACE

CONTROLLER

SHADING INDICATES

EXTENT OF HEAT TRACE

ME301

6Ø S-PF

30 (TYP .)

24X24 R-EG

(TYP.)

8Ø S-PF

170 (TYP .)

FC-E-A FC-E-A

16X8

CHS/R

HWS/R

CHS/R

HWS/R

24X10

22X22 R-FG

(TYP .)

10Ø 10Ø

6X66X6 24X10

D

T

T

F F

A

B

7 87.1

F F

SCWP-E-1

SCWP-E-2

PCWP-E-1

PCWP-E-2

VFD SCWP-E-1

VFD SCWP-E-2

BCS PANEL

CHILLED WATER

INLINE AIR

SEPARATOR

DECOUPLER

BRIDGE

CHS/R TO BUILDING - SEE

DRAWING ME200 FOR

CONTINUATION

PLUMBING

EQUIPMENT -

SEE PLUMBING

DRAWINGS

CHILLED WATER

EXPANSION

TANK

FC-E-C

T

DROP CHS/R PIPES

UNDERGROUND

A

B

D

C

7 87.1

D.1

Utility Room

G103 E006

ROUTE 0.75" CONDENSATE TO

NEAREST FLOOR DRAIN

D

CAP SUPPLY AND

EXHAUST FOR FUTURE

EXPANSION. CAPACITY

IS 500 CFM FOR SUPPLY

AND 300 CFM FOR

EXHAUST

12X8

12X10

CHS/R TO CHILLERS CH-E-1 AND CH-

E-2 - SEE DRAWING M102 IN SITE

PACKAGE FOR CONTINUATION AND

ADDITIONAL INFORMATION

CONCENTRIC DIRECT VENT AND

INTAKE INSTALLED PER

MANUFACTURER'S INSTSTRUCTIONS.

TERMINATE MINIMUM 2' ABOVE

DOOR.

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0542

/1 /2

:3 :2

P

M

ME301

HVAC

ENLARGED

PLANS AND

SECTIONS

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

1/2" = 1'-0"ME301

3 HVAC SECTION - CORRIDOR AND TYPICAL DORM ROOM

1/4" = 1'-0"ME301

4 HVAC ENLARGED PLAN - MECHANICAL ROOF

1/4" = 1'-0"ME301

1 HVAC ENLARGED PLAN - TYPICAL DORM ROOM

1/4" = 1'-0"ME301

2 HVAC ENLARGED PLAN - UTILITY ROOM

A

B

C

E

D

F

KEY PLAN

MARK DATE DESCRIPTION

18 03/06/2020 CPR-013

28 04/24/2020 CPR-23

54 10/28/2020 CPR-048

70 02/12/2021 CPR-064

DocuSign Envelope ID: A6A96DAF-7FAA-4036-BAF6-4FDB4204473B

02/12/2021

Level 1 0' - 0"

Level 2 14' - 0"

Level 3 25' - 4"

Level 4 36' - 8"

Level 5 48' - 0"

T.O. High Parapet 61' - 4"

Basement -12' - 0"

28X26

FS FS

FS

FSFS

FS

FS

FS

FS

FS FS

FS

FS

FS

20X20

10X10 10X12

10X12

8X16 8X16

8X16 8X16 6X16

6X16

8X16

8X20

8X16

10X22

8X18

FS

FS

FS

FS

D D.4

D.1

Level 5 48' - 0"

T.O. High Parapet

61' - 4"ENTHALPY WHEEL

PREHEAT COIL

COOLING COIL

SUPPLY

FAN

SECTION

ACCESS

SECTION

ACCESS

SECTION

FILTERS

ACCESS

SECTION

EXHAUST

FAN

SECTION

FILTERS

ACCESS

SECTION

ACCESS

SECTION

ACCESS SECTION

ACCESS SECTION

ACCESS SECTION

REHEAT COILROOF CURB

ERU-E-1

ACCESS SECTION

26X26

28X26

FS

FS

CHS/R

HWS/R HWS/R

B DC

D.1

COORDINATE HEIGHT OF ROOF

CURB AND SUPPLY DUCT

DISCHARGE LOCATION TO AVOID

EXPANSION JOINT AND

STRUCTURAL STEEL AT WALL

PENETRATION

CH-E-1 CH-E-2

DROP CHS/R PIPING

UNDERGROUND

SEE DRAWING M102 IN THE SITE

PACKAGE FOR CONTINUATION

10.1

6" CHS/R

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0541

/1

/2

:2 :3

P

M

ME302

HVAC

ENLARGED

PLANS AND

SECTIONS

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

A

B

C

E

D

F

KEY PLAN

1/4" = 1'-0"ME302

1 HVAC SECTION - MECH SHAFT

1/4" = 1'-0"ME302

2 HVAC SECTION - ERU-E-1

MARK DATE DESCRIPTION

1/4" = 1'-0"ME302

3 HVAC ENLARGED PLAN - CHILLERS

DocuSign Envelope ID: 87EEFB9D-D330-489C-82A2-A358420EA01E

12/18/19

File details come from the government source that posted it. Updated .