ACAD COMM MB501-HVAC-SCHEDULES-Rev.4.pdf

PDF 248 KB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This is an HVAC Schedules technical document prepared by Newcomb & Boyd Consulting Engineers for the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building B Academic Commons project located at 1219 Broad Street, Durham, NC. The document outlines detailed specifications for heating, ventilation, and air conditioning equipment including two air handling units (AHU-B-1 and AHU-B-2) with capacities of 50,000 CFM and 7,000 CFM respectively, seven exhaust fans ranging from 225 to 28,000 CFM for laboratory fume hoods, kitchen makeup air, grease hoods, paint spray booths, and laser cutters, and one energy recovery unit (ERU-B-1) designed for both summer and winter operations. Additional HVAC components specified include 23 finned tube radiation units, 10 circulating and primary/secondary pumps for chilled and heating water systems, two air-cooled chillers with 115-ton capacity each, two condensing boilers with 1,400 MBH output, three fan-coil units for mechanical and electrical rooms, and two ductless split systems for telecommunications areas. All equipment specifications include detailed performance parameters such as CFM ratings, static pressures, motor horsepower requirements, vibration isolation requirements, control valve types, and operating conditions for summer and winter design scenarios.

The document serves as the technical basis for contractors bidding on HVAC maintenance and repair services for the NCSSM-Morganton Campus buildings. Design conditions are specified at 92.4°F DB/72.7°F WB for summer operations and 20°F for winter operations, with interior space temperatures maintained at 75°F DB and 50% relative humidity for most occupied spaces, 90°F DB for electrical rooms, and 104°F DB for mechanical spaces. The specifications indicate coordination among multiple design disciplines including architects (Duda|Paine Architects and Belk Architecture), structural and civil engineers (Bennett & Pless and Stewart, Inc.), and MEP engineers (Newcomb & Boyd), with construction documents dated December 19, 2019 and issued as Bid Set SCO #16-14368-02B. The document is the exclusive property of Duda|Paine Architects, PA and is protected by copyright, restricting its use to the specific Academic Commons project.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0544

/2 /2

:4

:5

A

M MB501

HVAC

SCHEDULES

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g B

A c a d e m ic

C o m m o n s

AIR HANDLING UNIT SCHEDULE

NO. AREA SERVED (NOTE 1) TYPE (NOTE 2)

FAN

MINIMUM

OA CFM

COOLING COIL HEATING COIL (NOTE 8) VIBRATION ISOLATION

NOTESCFM

MAXIMUM

RPM

TYPE

(NOTE 3)

ESP. IN. WG

(NOTE 4)

MOTOR

CFM

(NOTE 5)

MAXIMUM

CHILLED

WATER GPM

(NOTE 6)

EAT °F LAT °F

CONTROL

VALVE

TYPE

(NOTE 7)

CONDITIONS DURING MAXIMUM

HEATING DEMAND

TYPE-POSITION

(NOTE 10)

CONTROL

VALVE

TYPE

(NOTE 7) TYPE

MIN. STATIC

DEFLECTION,

IN.

MINIMUM

HP

MAXIMUM

BRAKE HP DB WB DB WB CFM

GPM

(NOTE 9) EAT °F LAT °F

AHU-B-1 BUILDING AIR DT-MO-HZ-VV 50,000 1800 P-AF 4.0 4 @ 25 78.8 22,000 50,000 270 86.0 66.0 52.0 51.5 2 50,000 65 35 50 S-P 2 SC 2 11,12

AHU-B-2 KITCHEN MAKE-UP AIR DT-MO-HZ-VV 7,000 1800 P-AF 2.5 2 @ 5 6.6 7,000 7,000 50 92.4 72.5 52.0 51.5 2 7,000 20 20 70 S-P 2 -- -- 11,12

FAN SCHEDULE

NO. AREA SERVED

TYPE

(NOTES 1

& 2) CFM

STATIC

PRESSURE,

IN.WG

MAXIMUM

RPM

MOTOR

DRIVE

(NOTE 3)

VIBRATION ISOLATION

NOTES

MINIMUM

HP

MAXIMUM

BRAKE HP TYPE

MINIMUM STATIC

DEFLECTION, IN.

F-B-1 FUME HOOD EXHAUST FAN FE 850 1.0 3,500 1.5 1.4 B NP 0.25 4,5

F-B-2 FUME HOOD EXHAUST FAN FE 850 1.0 3,500 1.5 1.4 B NP 0.25 4,5

F-B-3 FUME HOOD EXHAUST FAN FE 850 1.0 3,500 1.5 1.4 B NP 0.25 4,5

F-B-4 RELIEF FAN MF 28,000 2.0 1,800 20 17.2 B FS 1.5 4,5,7

F-B-5 GREASE HOOD EXHAUST FAN GE 6,000 2.5 1,200 5.0 4.1 B FS 1.5 4,5,7

F-B-6 PAINT SPRAY BOOTH EXHAUST FAN IP-R 225 1.8 2,350 0.25 0.2 B NP 0.25 4,6

F-B-7 LASER CUTTER EXHAUST FAN IP-R 300 9.0 4,800 1.5 1.0 B NP 0.25 4,6

3. FAN TYPE:

FAN: WHEEL:

P PLENUM AF AIRFOIL

4. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, PLENUMS, OR

UNIT MOUNTED HEATING AND COOLING COILS, BUT DOES INCLUDE FILTERS.

5. BASED ON 500 FPM COIL FACE VELOCITY AND MAXIMUM 0.85" WG APD.

6. CHILLED WATER BASED ON 44°F EWT, 60°F LWT AND MAXIMUM 18' WPD.

7. CONTROL VALVE TYPE:

2 2-WAY

3 3-WAY

8. COIL FACE AREA SHALL BE BASED ON MAXIMUM COOLING DESIGN CFM

WITH MAXIMUM 0.2" WG AIR PRESSURE DROP.

9. HOT WATER BASED ON 130°F EWT, 100°F LWT AND MAXIMUM 3' WPD.

10. TYPE: POSITION:

S STANDARD P PREHEAT

R REHEAT

11. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

12. PROVIDE TWO VARIABLE FREQUENCY DRIVES WITH EACH VARIABLE

FREQUENCY DRIVE SERVING HALF OF THE SUPPLY FANS.

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB,72.7°F WB 20°F

CLASSROOMS 75°F DB, 50% RH 70°F

OFFICES 75°F DB, 50% RH 70°F

LABORATORIES 75°F DB, 50% RH 70°F

COMMONS 75°F DB, 50% RH 70°F

ELECTRICAL 90°DB 50°F

MECHANICAL 104°F DB 50°F

COMMUNICATIONS 78°F DB 70°F

REMAINING SPACE 75°F DB, 50% RH 70°F

2. TYPE:

DT DRAW-THROUGH MO MODULAR

HZ HORIZONTAL VV VARIABLE VOLUME

NOTES:

1. TYPE:

FE FUME HOOD EXHAUST

MF MIXED FLOW

GE GREASE EXHAUST

TA TUBE AXIAL

IP INDUSTRIAL PROCESS

2. WHEEL TYPE:

AF AIR FOIL

B BACKWARD-INCLINED

R RADIAL BLADE

3. DRIVE:

B BELT

D DIRECT

4. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT

ELECTRICAL CHARACTERISTICS.

5. PROVIDE INTEGRAL MOTOR-OPERATED ISOLATION DAMPER

HARDWIRED TO OPEN WITH FAN ON AND CLOSE WITH FAN OFF.

ENERGY RECOVERY UNIT SCHEDULE

NO.

CONDITIONS

OF OPERATION

OUTSIDE AIR SIDE EXHAUST SIDE VIBRATION ISOLATION

NOTES

OUTSIDE AIR

CONDITIONS SUPPLY FAN ENERGY RECOVERY WHEEL (NOTE 3) EXHAUST FAN

ENERGY RECOVERY

WHEEL (NOTE 5)

TYPE

MIN. STATIC

DEFLECTION

IN.°F, DB °F, WB CFM

MAXIMUM

RPM

FAN TYPE

(NOTE 1)

ESP. IN. WG

(NOTE 2)

MOTOR

CFM

TOTAL ENERGY

EFFECTIVENESS

EAT °F LAT °F

CFM

MAXIMUM

RPM

FAN TYPE

(NOTE 1)

ESP. IN. WG

(NOTE 4)

MINIMUM

HP

MAXIMUM

BRAKE

HP CFM

EAT °F

MINIMUM

HP

MAXIMUM

BRAKE HP DB WB DB WB DB WB

ERU-B-1 SUMMER 92.4 72.7 22,000 1800 P-AF 1.0 1 @ 20 17.0 22,000 0.71 92.4 72.7 80.5 66.7 20,000 1800 P-AF 2.0 1 @ 25 19.3 20,000 75 62.5 SC 2 6,7

ERU-B-1 WINTER 20.0 18.0 -- -- -- -- -- -- 22,000 0.71 20.0 18.0 56.0 48.2 -- -- -- -- -- -- 20,000 70 58.0 -- --

NOTES:

1. FAN TYPE:

FAN: WHEEL:

P PLUG AF AIRFOIL

2. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT

CASING, ENERGY RECOVERY WHEELS, OR HEATING AND

COOLING COILS, BUT DOES INCLUDE FILTERS.

3. OUTSIDE AIR SUPPLY SIDE OF ENERGY RECOVERY WHEELS

SHALL HAVE MAXIMUM 0.7" WG APD.

4. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING,

ENERGY RECOVERY WHEELS, OR COILS, BUT DOES INCLUDE

FILTERS.

5. EXHAUST SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE

MAXIMUM 0.60" WG APD.

6. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT

ELECTRICAL CHARACTERISTICS.

7. PROVIDE ONE VARIABLE FREQUENCY DRIVE FOR SUPPLY FANS

AND ONE VARIABLE FREQUENCY DRIVE FOR EXHAUST FANS.

FINNED TUBE RADIATION SCHEDULE

NO.

TYPE

(NOTE 1)

MINIMUM ACTIVE

LENGTH (FT.)

MINIMUM

CAPACITY, kW NOTES

FTR-B-1 P 6 3 2

FTR-B-2 P 4 2 2

FTR-B-3 P 4 2 2

FTR-B-4 P 4 2 2

FTR-B-5 P 4 2 2

FTR-B-6 P 4 2 2

FTR-B-7 P 4 2 2

FTR-B-8 P 4 2 2

FTR-B-9 P 4 2 2

FTR-B-10 P 4 2 2

FTR-B-11 P 4 2 2

FTR-B-12 P 4 2 2

FTR-B-13 P 4 2 2

FTR-B-14 P 4 2 2

FTR-B-15 P 4 2 2

FTR-B-16 P 4 2 2

FTR-B-17 P 4 2 2

FTR-B-18 P 4 2 2

FTR-B-19 P 4 2 2

FTR-B-20 P 4 2 2

FTR-B-21 P 4 2 2

FTR-B-22 P 4 2 2

FTR-B-23 P 4 2 2

NOTES:

1. TYPE:

P PEDESTAL-MOUNTED

2. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT

ELECTRICAL CHARACTERISTICS.

PUMP SCHEDULE

NO. SERVICE

TYPE

(NOTE 1) GPM

TOTAL DYNAMIC

HEAD, FT. WG

MINIMUM

EFFICIENCY,

% RPM

MOTOR VIBRATION ISOLATION

NOTES

MINIMUM

HP

MAXIMUM

BRAKE HP TYPE

MINIMUM STATIC

DEFLECTION, IN.

INERTIA

BASE

HWP-B-AHU1 PREHEAT COIL CIRCULATING V 65 20 73 1800 0.75 0.5 -- -- N 3

HWP-B-AHU2 PREHEAT COIL CIRCULATING V 20 20 50.0 1800 0.5 0.2 -- -- N 3

PCWP-B-1 PRIMARY CHILLED WATER E 200 40 80 1800 3 2.5 FS 1.0 Y 3

PCWP-B-2 PRIMARY CHILLED WATER E 200 40 80 1800 3 2.5 FS 1.0 Y 3

PHWP-B-1 PRIMARY HEATING WATER V 120 20 68 1800 1 0.86 -- -- N 3

PHWP-B-2 PRIMARY HEATING WATER V 120 20 68 1800 1 0.86 -- -- N 3

SCWP-B-1 SECONDARY CHILLED WATER E 200 60 74 1800 7.5 4.1 FS 1.0 Y 2,3

SCWP-B-2 SECONDARY CHILLED WATER E 200 60 74 1800 7.5 4.1 FS 1.0 Y 2,3

SHWP-B-1 SECONDARY HEATING WATER E 120 50 72 1800 3 2.1 FS 1.0 Y 2,3

SHWP-B-2 SECONDARY HEATING WATER E 120 50 72 1800 3 2.1 FS 1.0 Y 2,3

NOTES:

1. TYPE:

E END-SUCTION

V VERTICAL INLINE

2. PROVIDE VARIABLE FREQUENCY DRIVE.

3. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

AIR-COOLED CHILLER SCHEDULE

NO.

CAPACITY,

TONS (NOTES

1 & 2)

MAXIMUM

POWER INPUT

kW AT FULL

LOAD

MINIMUM

EER

MINIMUM

IPLV

EVAPORATOR

NOTES

EWT

°F

LWT

°F GPM

MAXIMUM

PRESS. DROP,

FT. WG

CH-B-1 115 148.3 10.1 15.3 58 44 200 12 3

CH-B-2 115 148.3 10.1 15.3 58 44 200 12 3

NOTES:

1. CAPACITY BASED ON 105°F AMBIENT TEMPERATURE.

2. PROVIDE LOW AMBIENT OPERATION DOWN TO 30°F.

3. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

BOILER SCHEDULE

NO.

TYPE

(NOTE 1)

OUTPUT,

MBH

MINIMUM

EFFICIENCY,

% (NOTE 3)

HOT WATER INPUT

NOTES

EWT

°F

LWT

°F GPM FUEL RATE

B-B-1 C-H 1,400 93 105 130 120 NG 1,505 2

B-B-2 C-H 1,400 93 105 130 120 NG 1,505 2

NOTES:

1. TYPE:

C CONDENSING - H HOT WATER

2. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

3. PER THE TEST PROCEDURES AND CONDITIONS REQUIRED IN THE NORTH

CAROLINA ENERGY CONSERVATION CODE-2012 WITH 2017 ACCUMULATIVE

SUPPLEMENT.

FAN-COIL UNIT SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

MINIMUM

MOTOR HP

NOMINAL

CFM

(NOTE 2)

ESP

IN.

WG.

COOLING COIL (NOTE 3) HEATING COIL (NOTE 4)

NOTES

SENSIBLE

MBH

LATENT

MBH GPM

RUNOUT

SIZES, IN. MBH GPM

POSITION

(NOTE 5)

RUNOUT

SIZES, IN.

FC-B-1 LEVEL 01 MECHANICAL ROOM HC 2 @ 1/20 650 0.2 8.6 0.25 2.1 0.75 4,800 0.5 R 0.75 6

FC-B-2 MAIN ELECTRICAL ROOMS HC 2 @ 1/20 650 0.2 8.6 0.25 2.1 0.75 4,800 0.5 R 0.75 6

FC-B-3 LEVEL 01 MECHANICAL ROOM HC 2 @ 1/20 650 0.2 8.6 0.25 2.1 0.75 4,800 0.5 R 0.75 6

NOTES:

1. TYPE:

HC HORIZONTAL CONCEALED

2. CFM BASED ON MEDIUM FAN SPEED.

3. CHILLED WATER BASED ON: 75°F DB AND 62.5°F WB EAT, 44°F EWT, 14° DIFFERENTIAL, AND MAXIMUM 10' WPD.

4. HOT WATER BASED ON: 70°F DB EAT, 130°F EWT, 30° DIFFERENTIAL, AND MAXIMUM 5' WPD.

5. POSITION:

R REHEAT

P PREHEAT

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

6. FAN SHALL HAVE SPARK RESISTANT CONSTRUCTION.

7. PROVIDE VARIABLE FREQUENCY DRIVE.

A

B

C

E

D

F

KEY PLAN

MARK DATE DESCRIPTION

28 04/24/20 CPR-023

DUCTLESS SPLIT SYSTEM SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 2)

INDOOR UNIT

NOMINAL CFM

(NOTE 3)

COOLING (NOTE 4) REVERSE CYCLE HEATING INDOOR

UNIT

MOUNTING

HEIGHT NOTES

SENSIBLE

CAPACITY,

MBH

TOTAL

CAPACITY,

MBH

MINIMUM

SEER

CAPACITY,

MBH (NOTE 5)

MINIMUM

HSPF

DSS-B-1 MAIN COMM. AC 700 19 30 19 -- -- 8 6

DSS-B-2 IDF AC 500 12 18 18 -- -- 8 6

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB, 72.7°F WB 20°F

TELECOM ROOMS 76°F DB, 50% RH 70°F

2. TYPE:

AC COOLING ONLY

HP HEAT PUMP - HEATING AND COOLING

3. INDOOR UNIT CFM IS BASED ON MEDIUM FAN SPEED.

4. BASED ON 76°F DB 63°F WB ENTERING INDOOR COIL, AND 105°F DB ENTERING OUTSIDE COIL.

5. BASED ON 70°F ENTERING INDOOR COIL AND 47°F DB, 43°F WB ENTERING OUTSIDE COIL.

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

282828

DocuSign Envelope ID: 50DA66E2-D1D0-4275-B621-FE0963249A5D

04/24/20