RES HALL ME501-HVAC-SCHEDULES-Rev.4.pdf

PDF 412 KB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This is a mechanical engineering schedule document prepared for the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building E Residence Hall adaptive reuse project in Durham, North Carolina. The document, issued on December 19, 2019, provides comprehensive HVAC equipment specifications and schedules for the residence hall renovation. The project involves multiple engineering and architectural firms including Newcomb & Boyd (MEP/FP Engineer), Duda|Paine Architects, Belk Architecture, Bennett & Pless (Structural Engineer), Stewart, Inc. (Civil and Landscape Architect), Food Design Associates, and RM Rutherford & Associates Inc. (Cost Estimator). The schedules specify detailed performance parameters, capacities, and operational conditions for various mechanical systems including energy recovery units, fan-coil units, air-cooled chillers, boilers, ductless split systems, pumps, unit heaters, finned tube radiation units, and sound attenuators. Equipment specifications include precise CFM ratings, water pressure drops, energy efficiency requirements, sound power levels, vibration isolation specifications, and operating conditions for both summer and winter scenarios.

The document establishes stringent performance standards aligned with North Carolina Energy Conservation Code 2012 with 2017 Accumulative Supplement requirements. Key equipment includes two 100-ton air-cooled chillers (CH-E-1 and CH-E-2) with minimum 10.3 EER rating, two 1,400 MBH condensing hot water boilers (B-E-1 and B-E-2), multiple variable frequency drive-equipped pumps for primary and secondary chilled and heating water circuits, and one energy recovery unit (ERU-E-1) designed for 9,000 CFM supply and exhaust with enthalpy wheel energy recovery at 0.70 total energy effectiveness. All mechanical equipment must comply with referenced industry standards including AHRI 260, AHRI 370, AHRI 350, AMCA 300, and ASHRAE 68/AMCA 330 for sound and performance verification. The document includes revision history noting change order requests (CPR-023, CPR-041, RFI-1017) dated April 2020 through April 2022, indicating ongoing design development and refinement during the construction documentation phase.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0544

/2 /2

:2

:4

A

M ME501

HVAC

SCHEDULES

12/19/2019 21611

Construction Documents Bid Set

SCO # 16-14368-02B

N C

S S M

W e st e rn

C a m p u s

B u ild in g E

R e si d e n c e H a ll

ENERGY RECOVERY UNIT SCHEDULE

NO.

CONDITIONS

OF

OPERATION

OUTSIDE AIR

CONDITIONS OUTSIDE AIR SIDE EXHAUST SIDE VIBRATION ISOLATION

NOTES°F, DB °F, WB

SUPPLY FAN ENERGY RECOVERY WHEEL (NOTE 3) COOLING COIL PREHEAT COIL REHEAT COIL EXHAUST FAN

ENERGY RECOVERY

WHEEL (NOTE 10)

TYPE

MIN. STATIC

DEFLECTION IN.CFM

MAXIMUM

RPM

FAN TYPE

(NOTE 1)

ESP. IN.

WG

(NOTE 2)

MOTOR

CFM

TOTAL ENERGY

EFFECTIVENESS

EAT °F LAT °F

CFM

(NOTE 4)

CHILLED

WATER GPM

(NOTE 5)

EAT °F LAT °F

CFM

(NOTE 7)

HEATING

WATER

GPM

(NOTE 8)

EAT

°F

LAT

°F

CFM

(NOTE 7)

HEATING

WATER

GPM

(NOTE 8)

EAT

°F

LAT

°F CFM

MAXIMUM

RPM

FAN

TYPE

(NOTE 1)

ESP. IN.

WG

(NOTE 9)

MINIMUM

HP

MAXIMUM

BRAKE

HP CFM

EAT °F

MINIMUM

HP

MAXIMUM

BRAKE HP DB WB DB WB DB WB DB WB DB WB

ERU-E-1 SUMMER 92.4 72.7 9,000 2350 P 2.5 2 @ 7.5 12.04 9,000 0.70 92.4 72.7 87.2 70.0 9,000 65 87.2 70.0 52.0 51.5 -- -- -- -- -- -- -- -- 7,500 2200 P 2.0 2 @ 5 6.3 7,500 75 62.5 SC 2.0 11,12

ERU-E-1 WINTER 20 17 9,000 -- -- -- -- -- 9,000 0.70 20 17 55 42 -- -- -- -- -- -- 9,000 25 20 50 9,000 12 52 70 -- -- -- -- -- -- 7,000 70 52 -- -- --

NOTES:

1. FAN TYPE:

FAN: WHEEL:

P PLUG AF AIRFOIL

2. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, ENERGY

RECOVERY WHEELS, OR HEATING AND COOLING COILS, BUT DOES

INCLUDE FILTERS.

3. OUTSIDE AIR SUPPLY SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE

MAXIMUM 0.7" WG APD.

4. BASED ON 500 FPM COIL FACE VELOCITY AND MAXIMUM 0.85"

WG APD.

5. CHILLED WATER BASED ON 44°F EWT, 58°F LWT AND MAXIMUM

18' WPD.

6. CONTROL VALVE TYPE:

2 2-WAY

3 3-WAY

7. COIL FACE AREA SHALL BE BASED ON MAXIMUM COOLING DESIGN CFM WITH

MAXIMUM 0.2" WG AIR PRESSURE DROP.

8. HOT WATER BASED ON 130°F EWT, 100°F LWT AND MAXIMUM 3' WPD.

9. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, ENERGY

RECOVERY WHEELS, OR COILS, BUT DOES INCLUDE FILTERS.

10. EXHAUST SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE MAXIMUM 0.60"

WG APD.

11. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

12.PROVIDE SUPPLY AND EXHAUST FANS AND ENTHALPY WHEEL EACH WITH A

VARIABLE FREQUENCY DRIVE.

FAN-COIL UNIT SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

MINIMUM

MOTOR HP

NOMINAL

CFM

(NOTE 2)

ESP

IN.

WG.

COOLING COIL (NOTE 3) HEATING COIL (NOTE 4) SOUND POWER LEVEL

VIBRATION

ISOLATION

NOTES

SENSIBLE

MBH

LATENT

MBH GPM

RUNOUT

SIZES, IN. MBH GPM

POSITION

(NOTE 5)

RUNOUT

SIZES, IN.

FREE

INLET/CASING

RADIATED DISCHARGE

TYPE

MIN. STATIC

DEFLECTION,

IN.2 3 4 2 3 4

FC-E1-1 LOBBY/RECEPTION HC 1 2,300 0.3 36.3 3.6 5.7 1.0 9.5 1.0 R 0.75 68 64 61 86 87 90 SH 0.75 6

FC-E1-2 LEVEL 1 BLDG LOUNGE/KITCHEN HC 1 1,800 0.3 31.1 3.4 4.9 1.0 12 1.25 R 0.75 65 63 60 77 75 76 SH 0.75 6

FC-E1-3 STUDY ALCOVE/CORRIDOR HC 1/2 1,400 0.3 24.2 2.3 3.8 0.75 10.9 1.1 R 0.75 64 65 62 79 81 85 SH 0.75 6

FC-E1-4 CLASSROOM/FLEX HC 2 @ 1/20 500 0.2 7.7 2.5 1.8 0.75 1.7 0.5 R 0.75 58 56 56 57 55 60 NH 0.25 6

FC-E1-5 CLASSROOM/FLEX HC 2 @ 1/20 800 0.2 18.2 3.5 2.7 0.75 3.3 0.5 R 0.75 58 56 56 57 55 60 NH 0.25 6

FC-E-A TYPICAL DORM ROOM HC 1/20 175 0.2 3.0 0.4 0.5 0.75 4.0 0.5 R 0.75 54 52 53 52 52 53 NH 0.25 6

FC-E-B TYPICAL FLOOR LOUNGE HC 2 @ 1/20 500 0.2 11.2 2.2 2.0 0.75 4.2 0.5 R 0.75 59 60 57 65 60 65 NH 0.25 6

FC-E-B FLOOR COMMONS / ELEV VEST HC 2 @ 1/20 500 0.2 10.4 1.5 1.8 0.75 1.7 0.5 R 0.75 61 57 55 67 63 63 NH 0.25 6

FC-E-C COMMUNAL BATHROOMS HC 2 @ 1/20 650 0.2 12.2 2.2 2.1 0.75 4.8 0.5 R 0.75 58 56 56 57 55 60 NH 0.25 6

FC-E-D TYPICAL APARTMENTS HC 2 @ 1/20 750 0.2 12.2 2.2 2.1 0.75 4.8 0.5 R 0.75 58 56 56 57 55 60 NH 0.25 6

FC-E-E FLOOR COMMONS / ELEV VEST HC 2 @ 1/20 500 0.2 10.4 1.5 1.8 0.75 1.7 0.5 R 0.75 61 57 55 67 63 63 NH 0.25 6

NOTES:

1. TYPE:

HC HORIZONTAL CONCEALED

2. CFM BASED ON MEDIUM FAN SPEED.

3. CHILLED WATER BASED ON: 75°F DB AND 62.5°F WB EAT, 44°F EWT, 14° DIFFERENTIAL, AND MAXIMUM 10' WPD.

4. HOT WATER BASED ON: 70°F DB EAT, 130°F EWT, 20° DIFFERENTIAL, AND MAXIMUM 2' WPD.

5. POSITION:

R REHEAT

P PREHEAT

6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

FINNED TUBE RADIATION SCHEDULE

NO.

TYPE

(NOTE 1)

MINIMUM

ACTIVE

LENGTH (FT.)

MINIMUM

CAPACITY,

kW NOTES

FTR-E1-1 P 4 2 2

FTR-E1-2 P 4 2 2

FTR-E1-3 P 4 2 2

FTR-E1-4 P 4 2 2

FTR-E1-5 P 4 2 2

FTR-E3-1 P 4 2 2

FTR-E3-2 P 4 2 2

FTR-E3-3 P 4 2 2

NOTES:

1. TYPE:

P PEDESTAL-MOUNTED

2. REFER TO THE ELECTRICAL DRAWINGS FOR THE

EQUIPMENT ELECTRICAL CHARACTERISTICS.

PUMP SCHEDULE

NO. SERVICE

TYPE

(NOTE 1) GPM

TOTAL DYNAMIC

HEAD, FT. WG

MINIMUM

EFFICIENCY,

% RPM

MOTOR VIBRATION ISOLATION

NOTES

MINIMUM

HP

MAXIMUM

BRAKE HP TYPE

MINIMUM STATIC

DEFLECTION, IN.

INERTIA

BASE

HWP-E-ERU1 PREHEAT COIL CIRCULATING V 25 20 54 1800 0.5 0.21 -- -- -- 3

PCWP-E-1 PRIMARY CHILLED WATER E 175 40 74.2 1800 3 2.2 FS 0.75 Y 3

PCWP-E-2 PRIMARY CHILLED WATER E 175 40 74.2 1800 3 2.2 FS 0.75 Y 3

PHWP-E-1 PRIMARY HEATING WATER V 120 20 68 1800 1 0.86 FS 1.5 N 3

PHWP-E-2 PRIMARY HEATING WATER V 120 20 68 1800 1 0.86 FS 1.5 N 3

SCWP-E-1 SECONDARY CHILLED WATER E 175 50 72 1800 5 3.0 FS 0.75 Y 2,3

SCWP-E-2 SECONDARY CHILLED WATER E 175 50 72 1800 5 3.0 FS 0.75 Y 2,3

SHWP-E-1 SECONDARY HEATING WATER E 120 40 80 1800 2 1.6 FS 1.5 Y 2,3

SHWP-E-2 SECONDARY HEATING WATER E 120 40 80 1800 2 1.6 FS 1.5 Y 2,3

NOTES:

1. TYPE:

E END-SUCTION

V VERTICAL INLINE

2. PROVIDE VARIABLE FREQUENCY DRIVE.

3. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

AIR-COOLED CHILLER SCHEDULE

NO.

CAPACITY,

TONS (NOTES

1 & 2)

MAXIMUM

POWER INPUT

kW AT FULL

LOAD

MINIMUM

EER

MINIMUM

NPLV

EVAPORATOR

NOTES

EWT

°F

LWT

°F GPM

MAXIMUM

PRESS. DROP,

FT. WG

CH-E-2 100 130.4 10.3 15.5 58 44 175 15 3

CH-E-1 100 130.4 10.3 15.5 58 44 175 15 3

NOTES:

1. CAPACITY BASED ON 105°F AMBIENT TEMPERATURE.

2. PROVIDE LOW AMBIENT OPERATION DOWN TO 30°F.

3. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

BOILER SCHEDULE

NO.

TYPE

(NOTE 1)

OUTPUT,

MBH

MINIMUM

EFFICIENCY,

% (NOTE 3)

HOT WATER INPUT

NOTES

EWT

°F

LWT

°F GPM FUEL RATE

B-E-1 C-H 1,400 93 105 130 120 NG 1505 2

B-E-2 C-H 1,400 93 105 130 120 NG 1505 2

NOTES:

1. TYPE:

C CONDENSING - H HOT WATER

2. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL

CHARACTERISTICS.

3. PER THE TEST PROCEDURES AND CONDITIONS REQUIRED IN THE NORTH

CAROLINA ENERGY CONSERVATION CODE-2012 WITH 2017 ACCUMULATIVE

SUPPLEMENT.

DUCTLESS SPLIT SYSTEM SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 2)

INDOOR UNIT

NOMINAL CFM

(NOTE 3)

COOLING (NOTE 4) REVERSE CYCLE HEATING INDOOR

UNIT

MOUNTING

HEIGHT NOTES

SENSIBLE

CAPACITY,

MBH

TOTAL

CAPACITY,

MBH

MINIMUM

SEER

CAPACITY,

MBH (NOTE 5)

MINIMUM

HSPF

DSS-E-A TYP. COMM. AC 500 12 18 18 -- -- 8 6

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

OUTSIDE 92.4°F DB, 72.7°F WB 20°F

TELECOM ROOMS 76°F DB, 50% RH 70°F

2. TYPE:

AC COOLING ONLY

HP HEAT PUMP - HEATING AND COOLING

3. INDOOR UNIT CFM IS BASED ON MEDIUM FAN SPEED.

4. BASED ON 76°F DB 63°F WB ENTERING INDOOR COIL, AND 105°F DB ENTERING OUTSIDE COIL.

5. BASED ON 70°F ENTERING INDOOR COIL AND 47°F DB, 43°F WB ENTERING OUTSIDE COIL.

6. REFER TO ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

SOUND ATTENUATOR SCHEDULE

NO.

SA-E-1

NOTES:

1. TYPE:

R

2. ELBOW SOUND ATTENUATOR LENGTHS SHOWN ARE COMBINED CENTERLINE LENGTHS.

3. FORWARD AIR FLOW (+); REVERSE AIR FLOW (-).

4. AIR FLOW AND INSERTION LOSS PERFORMANCE SHALL BE IN ACCORDANCE WITH ASTM E477-2013e.

SERVICE

FC-E1-1

RECTANGULAR

TYPE

(NOTE 1)

RS

S

NOMINAL DIMENSIONS, IN.

LENGTH

(NOTE 2)

STANDARD

WIDTH/

INSIDE DIA.

HEIGHT/

OUTSIDE DIA.

FT/MIN

(NOTE 3)

MAX.

APD,

IN. WG

0.25

MINIMUM DYNAMIC INSERTION LOSS, dB

OCTAVE BAND CENTER FREQUENCY, Hz

MAXIMUM GENERATED NOISE, dB

OCTAVE BAND CENTER FREQUENCY, Hz

NOTES

A

B

C

E

D

F

KEY PLAN

MECHANICAL EQUIPMENT SOUND LIMITS SCHEDULE

NO.

CH-E-1 and CH-E-2

FCU-A

FCU-B

FCU-C

FCU-D

FCU-E

FC-E1-1

FC-E1-2

FC-E1-3

FC-E1-4

FC-E1-5

ERU-E-1

NOTES:

1. ALL AIR HANDLING UNITS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND

POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE AIR HANDLING

UNIT SCHEDULE AS DETERMINED IN ACCORDANCE WITH THE MOST RECENT VERSION OF AHRI 260

2. ALL AIR COOLED CHILLER UNITS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND

POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE AIR COOLED

CHILLER SCHEDULE AS DETERMINED IN ACCORDANCE WITH THE MOST RECENT VERSION OF AHRI 370

3. ALL FAN COIL UNITS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND

POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE FAN COIL

UNIT SCHEDULE AS DETERMINED IN ACCORDANCE WITH THE MOST RECENT VERSION OF AHRI 350

4. ALL FANS LISTED IN THIS SCHEDULE SHALL NOT EXCEED THE SOUND POWER LEVELS (Lw), in dB re 10-12 WATTS, INDICATED FOR THE OPERATING POINTS LISTED IN THE FAN SCHEDULE AS DETERMINED IN ACCORDANCE

WITH THE MOST RECENT VERSION OF AMCA 300 OR ASHRAE 68/AMCA 330

SOURCE

RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET PLUS CASING RADIATED

DISCHARGE

INLET

MAXIMUM Lw IN dB re 10-12 WATTS

OCTAVE BAND CENTER FREQUENCY, Hz

NOTES

1,4

MARK DATE DESCRIPTION

28 04/24/2020 CPR-023

47 08/21/2020 CPR-041

128 04/22/2022 RFI-1017

UNIT HEATER SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

CAPACITY,

MBH/kW

(NOTE 2)

NOMINAL

CFM

MOUNTING

HEIGHT, FT

(NOTE 3) NOTES

UH-E-1 UNOCCUPIED SPACE H 2.5 350 9 4

UH-E-2 UNOCCUPIED SPACE H 2.5 350 9 4

UH-E-3 UNOCCUPIED SPACE H 2.5 350 9 4

UH-E-4 UNOCCUPIED SPACE H 2.5 350 9 4

UH-E-5 LAUNDRY ACCESS AREA H 10 650 9 4

NOTES:

1. TYPE:

H HORIZONTAL

2. MBH GIVEN FOR HOT WATER UNITS, kW FOR ELECTRIC. BASED ON 60°F EAT.

3. HEIGHT IS TO CENTERLINE OF HEATER ABOVE FINISHED FLOOR.

4. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.

DocuSign Envelope ID: 039CDEFB-8CB7-421E-BC99-22D92249AC29

04/25/2022 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313 https://app.procore.com/694903/project/drawing_areas/710840/drawing_log/138310313