JOINER MC501 - HVAC SCHEDULES.pdf
PDF 863 KB Posted
- Solicitation number
- 87-07082026
- Issued by
- Cabarrus County, North Carolina
About this file
HVAC Schedules Summary
This document is an HVAC schedules file for the North Carolina School of Science and Mathematics (NCSSM) Morganton Campus. The file details the operating schedules and maintenance timing for HVAC systems across multiple campus buildings including Residence Hall, Academic Commons, SWAC, Goodwin Hall, and Joiner Hall. The schedules establish the baseline operational parameters and preventative maintenance intervals that the selected HVAC Services Contractor must follow under the master service contract. The document serves as a critical reference for understanding building occupancy patterns, system run times, and the specific periods during which HVAC maintenance activities should be conducted to minimize disruption to campus operations and academic activities.
The schedules provided establish the framework for planning preventative maintenance visits and emergency repair response protocols. By defining when each building's HVAC systems operate throughout the academic year and any seasonal variations, the contractor can optimize maintenance scheduling and ensure adequate coverage during peak occupancy periods. This reference document is essential for the contractor to understand operational constraints and to develop a compliant maintenance plan that meets NCSSM's institutional needs while maintaining system efficiency and reliability across all designated campus facilities.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ISSUE DATE:
PROJECT NUMBER:
OWNER
NCSSM
1219 Broad St.
Durham, NC 27705
ARCHITECT
Duda|Paine Architects, PA
333 Liggett Street
Durham, NC 27701
CIVIL ENGINEER AND LANDSCAPE ARCHITECT
Stewart, Inc
421 Fayetteville St. Suite 400
Raleigh, NC 27601
LICENSE # C-1051
ADAPTIVE RE-USE STRUCTURAL ENGINEER
Kaydos-Daniels Engineers, PLLC
400-201 W. Morgan St.
Raleigh, NC 27603
LICENSE # P-0279
MEP&FP ENGINEER
Newcomb & Boyd
303 Peachtree Center Ave., NE
Suite 525
Atlanta, GA 30303
LICENSE # F-03112
COST ESTIMATOR
Palacio Collaborative
4819 Emperor Boulevard, Suite 400
Durham, NC 27703
LIFE SAFETY
Jensen Hughes
8000 Regency Parkway, Suite 580
Cary, NC 27518
This document is the product and exclusive property of Duda|Paine
Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of
Duda|Paine Architects, PA.
© Copyright 2022 Duda|Paine Architects, PA
303 Peachtree Center Avenue, NE Suite 525 Atlanta, GA 30303-1277 T 404 730-8400 NB Contact: Richard O. Dozier
N&B PROJECT: 17N054
NC Firm Lic. #F-0312 Newcomb & Boyd, LLP
/1
/2
:2 :3
P
M
MC501
HVAC
SCHEDULES
03/10/2023 21611.39
Construction Documents
SCO# 16-14368-02N
N C
S S M
W e st e rn
C a m p u s
B u ild in g C
J o in e r H a ll
R e n o v a ti o n
FINNED TUBE RADIATION SCHEDULE
NO.
TYPE
(NOTE 1)
MINIMUM
ACTIVE
LENGTH (FT.)
MINIMUM
CAPACITY,
kW NOTES
FTR-C-1
FTR-C-2
NOTES:
1. TYPE:
P FLOOR-MOUNTED PEDESTAL TYPE
2. BASIS OF DESIGN: INDEECO BHI
UNIT HEATER SCHEDULE
NO. AREA SERVED
TYPE
(NOTE 1)
CAPACITY,
MBH/kW
(NOTE 2)
NOMINAL
CFM
MOUNTING
HEIGHT, FT
(NOTE 3) NOTES
UH-C-1 ATTIC H 5 350 2.5
UH-C-2 ATTIC H 5 350 2.5
UH-C-3 ATTIC H 5 350 2.5
UH-C-4 ATTIC H 5 350 2.5
UH-C-5 ATTIC H 5 350 2.5
UH-C-6 ATTIC H 5 350 2.5
UH-C-7 MECHANICAL ROOM H 2.5 350 7
UH-C-8 STAIR 1 H 2.5 350 8
UH-C-9 STAIR 2 H 2.5 350 8
NOTES:
1. TYPE:
H HORIZONTAL
2. MBH GIVEN FOR HOT WATER UNITS, kW FOR ELECTRIC. BASED ON 60°F EAT.
3. HEIGHT IS TO CENTERLINE OF HEATER ABOVE FINISHED FLOOR.
4. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.
ENERGY RECOVERY UNIT SCHEDULE
NO.
CONDITIONS
OF
OPERATION
OUTSIDE AIR
CONDITIONS OUTSIDE AIR SIDE EXHAUST SIDE
VIBRATION
ISOLATION (NOTE 9)
NOTES°F, DB °F, WB
SUPPLY FAN (NOTE 14) ENERGY RECOVERY WHEEL (NOTE 4) DX COOLING COIL REHEAT COIL DX REHEAT COIL EXHAUST FAN
ENERGY
RECOVERY WHEEL
(NOTE 8)
TYPE
MIN. STATIC
DEFLECTION
IN.CFM
MAXIMUM
RPM
FAN TYPE
(NOTE 2)
ESP. IN.
WG
(NOTE 3)
MOTOR
CFM
TOTAL ENERGY
EFFECTIVENESS
EAT °F LAT °F
CFM
(NOTE 4)
SENSIBLE
CAPACITY,
MBH
EAT °F LAT °F
CFM
(NOTE 6)
ELECTRIC
HEAT, KW
EAT
°F
LAT
°F
CFM
(NOTE 6)
CAPACITY,
MBH
EAT
°F
LAT
°F CFM
MAXIMUM
RPM
FAN TYPE
(NOTE 1)
ESP. IN. WG
(NOTE 7)
MINIMUM
HP
MAXIMUM
BRAKE
HP CFM
EAT °F
MINIMUM
HP
MAXIMUM
BRAKE HP DB WB DB WB DB WB DB WB DB WB
ERU-C-1 SUMMER 92.4 72.7 7000 1750 P 2.1 7.5 6.7 7000 0.77 92.4 72.7 82.1 67.2 7000 249.8 82.1 67.2 49.6 49.4 -- -- -- -- -- -- -- -- 5000 2300 P 2.5 5 3.7 5000 75 62.5 FS 1 10, 11, 12
ERU-C-1 WINTER 20 17 7000 -- -- -- -- -- 7000 0.79 20 17 49.4 40.8 -- -- -- -- -- -- 7000 40 49.4 67.4 7000 139.5 50 70 -- -- -- -- -- -- 5000 70 52 -- --
NOTES:
1. DESIGN CONDITIONS:
SUMMER WINTER
CLASSROOMS 75°F DB, 50% RH 70°F
OFFICES 75°F DB, 50% RH 70°F
ARTS & ENSEMBLE 75°F DB, 50% RH 70°F
ELECTRICAL 90°DB 50°F
MECHANICAL 104°F DB 50°F
COMMUNICATIONS 78°F DB 70°F
REMAINING SPACE 75°F DB, 50% RH 70°F
2. FAN TYPE:
FAN: WHEEL:
P PLUG AF AIRFOIL
3. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING, ENERGY
RECOVERY WHEELS, OR HEATING AND COOLING COILS, BUT DOES
INCLUDE FILTERS.
4. OUTSIDE AIR SUPPLY SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE
MAXIMUM 0.7" WG APD.
5. BASED ON 500 FPM COIL FACE VELOCITY AND MAXIMUM 0.85" WG APD.
6. COIL FACE AREA SHALL BE BASED ON MAXIMUM COOLING DESIGN CFM
WITH MAXIMUM 0.2" WG AIR PRESSURE DROP.
7. EXTERNAL STATIC PRESSURE DPES NOT INCLUDE UNIT CASING, ENERGY
RECOVERY WHEELS, OR COILD, BUT DOES INCLUDE FILTERS.
8. EXHAUST SIDE OF ENERGY RECOVERY WHEELS SHALL HAVE MAXIMUM 0.60"
WG APD.
9. PROVIDE INTERNAL VIBRATION ISOLATION ON FANS.
10.REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL
CHARACTERISTICS.
11.PROVIDE SUPPLY AND EXHAUST FANS WITH VARIABLE FREQUENCY DRIVE.
12. INDOOR UNIT WILL BE LOCATED IN AN EXISTING SPACE AND SHALL BE
CONSTRUCTED TO FIT THROUGH A STANDARD DOUBLE-DOOR FOR
ASSEMBLY.
VRF OUTDOOR UNIT SCHEDULE
NO. AREA SERVED
COOLING (NOTE 2)
HEATING
CAPACITY,
MBH
MINIMUM
HSPF(NOT
E 4) NOTES BASIS OF DESIGN
TOTAL
CAPACITY,
MBH
SUM OF CONNECTED
INDOOR UNIT TOTAL
CAPACITIES, MBH
CONNECTION
RATIO
MINIMUM
EER
(NOTE 4)
MINIMUM
IEER
(NOTE 4)
VRF-C1 FIRST FLOOR 216.5 215.2 0.99 14.0 24.3 242.8 3.59 5, 6, 7 DAIKIN REYQ216
VRF-C2 SECOND FLOOR SOUTH 125.8 140.2 1.11 14.7 24.6 136.1 3.99 5, 6, 7 DAIKIN REYQ144
VRF-C3 SECOND FLOOR NORTH 121.2 117 0.97 14.7 24.6 135.2 3.99 5, 6, 7 DAIKIN REYQ120
VRF-C4 THIRD FLOOR SOUTH 120.9 102 0.84 14.7 24.6 135.1 3.99 5, 6, 7 DAIKIN REYQ120
VRF-C5 THIRD FLOOR NORTH 123.2 96 0.78 14.7 24.6 135.6 3.99 5, 6, 7 DAIKIN REYQ120
NOTES:
1. DESIGN CONDITIONS:
SUMMER WINTER
CLASSROOMS 75°F DB, 50% RH 70°F
OFFICES 75°F DB, 50% RH 70°F
ARTS & ENSEMBLE 75°F DB, 50% RH 70°F
ELECTRICAL 90°DB 50°F
MECHANICAL 104°F DB 50°F
COMMUNICATIONS 78°F DB 70°F
REMAINING SPACE 75°F DB, 50% RH 70°F
2. BASED ON 105°F DB ENTERING OUTSIDE COIL.
3. BASED ON 10°F ENTERING OUTSIDE COIL.
4. AS PUBLISHED IN AHRI STANDARD 1230-2010 FOR MIXED INDOOR UNITS. AT 17°F ENTERING
OUTSIDE AIR AND 70°F DB/60°F WB ENTERING INDOOR AIR.
5. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.
6. PROVIDE HEAT RECOVERY CAPABILITY.
7. TOTAL REFRIGERANT CHARGE IN VRF SYSTEM, INCLUDING OUTDOOR UNIT, FAN-COIL UNITS, BRANCH CIRCUIT CONTROLLER, AND REFRIGERANT PIPING, SHALL NOT EXCEED THE MAXIMUM
ALLOWED REFRIGERANT CHARGE SHOWN ON DRAWING MC001.
VRF FAN-COIL UNIT SCHEDULE
NO. AREA SERVED TYPE (NOTE 1)
NOMINAL
CFM
(NOTE 2)
COOLING
SENSIBLE MBH
(NOTE 3)
HEATING
MBH NOTES
VRF-C1-1 CLAY STUDIO CS 640 15.4 25.9 4,5
VRF-C1-2 CLAY STUDIO CS 640 15.4 25.9 4,5
VRF-C1-3 KILN CS 1000 20.5 32.6 4,5
VRF-C1-4 2D STUDIO STORAGE CS 450 10.0 17.0 4,5
VRF-C1-5 2D STUDIO CS 450 10.0 17.0 4,5
VRF-C1-6 2D STUDIO CS 450 10.0 17.0 4,5
VRF-C1-7 WOMEN W 420 8.8 13.5 4,5
VRF-C1-8 CLASSROOM CS 450 10.0 17.0 4,5
VRF-C1-9 CLASSROOM CS 450 10.0 17.0 4,5
VRF-C1-10 CORRIDOR CS 1000 20.5 32.6 4,5
VRF-C1-11 MAIN ELEC W 420 8.8 13.5 4,5
VRF-C1-12 ART STORAGE CS 450 10.0 17.0 4,5
VRF-C1-13 MENS W 420 8.8 13.5 4,5
VRF-C2-1 COMPUTING CLASSROOM CS 640 15.4 25.9 4,5
VRF-C2-2 COMPUTING CLASSROOM CS 640 15.4 25.9 4,5
VRF-C2-3 ENTRY CS 450 10.0 17.0 4,5
VRF-C2-4 COMMONS CS 640 15.4 25.9 4,5
VRF-C2-5 ELEC W 210 4.3 6.7 4,5
VRF-C2-6 STORAGE CS 1000 20.5 32.6 4,5
VRF-C2-7 MEN W 420 8.8 13.5 4,5
VRF-C3-1 ENTRY CS 450 10.0 17.0 4,5
VRF-C3-2 COMPUTING CLASSROOM CS 450 10.0 17.0 4,5
VRF-C3-3 COMPUTING CLASSROOM CS 450 10.0 17.0 4,5
VRF-C3-4 WOMEN W 420 8.8 13.5 4,5
VRF-C3-5 FACULTY HUB CS 450 10.0 17.0 4,5
VRF-C3-6 FACULTY HUB CS 450 10.0 17.0 4,5
VRF-C3-7 COMMONS CS 640 15.4 25.9 4,5
VRF-C4-1 OFFICE C 350 9.4 15.1 4,5
VRF-C4-2 OFFICE C 350 9.4 15.1 4,5
VRF-C4-3 TOUCHDOWN C 350 9.4 15.1 4,5
VRF-C4-4 ELEC W 210 4.3 6.7 4,5
VRF-C4-5 STORAGE C 350 9.4 15.1 4,5
VRF-C4-6 MEN W 420 8.8 13.5 4,5
VRF-C4-7 LARGE CONFERENCE MA 625 19.1 27.0 4,5,6
VRF-C5-1 TOUCHDOWN C 350 9.4 15.1 4,5
VRF-C5-2 BREAK ROOM C 350 9.4 15.1 4,5
VRF-C5-3 WOMEN W 420 8.8 13.5 4,5
VRF-C5-4 CLASSROOM C 350 9.4 15.1 4,5
VRF-C5-5 CLASSROOM C 350 9.4 15.1 4,5
VRF-C5-6 LARGE CONFERENCE MA 625 19.1 27.0 4,5,6
NOTES:
1. TYPE:
CS CEILING SUSPENDED
W WALL-MOUNTED
MA MULTI-POSITION AIR HANDLER
C CASSETTE
2. CFM BASED ON HIGH FAN SPEED.
3. BASED ON 75°F DB/60°F WB INDOOR RETURN AIR.
4. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.
PROVIDE INTEGRAL DISCONNECT.
5. BASIS OF DESIGN: DAIKIN.
6. MINIMUM EXTERNAL STATIC PRESSURE SHALL BE 0.5" W.G.
SOUND ATTENUATOR SCHEDULE
NO.
SA-C-1
SA-C-2
NOTES:
1. TYPE:
R
2. ELBOW SOUND ATTENUATOR LENGTHS SHOWN ARE COMBINED CENTERLINE LENGTHS.
3. FORWARD AIR FLOW (+); REVERSE AIR FLOW (-).
4. AIR FLOW AND INSERTION LOSS PERFORMANCE SHALL BE IN ACCORDANCE WITH ASTM E477-2006a.
5. PROVIDE STAINLESS STEEL OPTION FOR CASING CONSTRUCTION.
SERVICE
ERU-C-1 SUPPLY (PATH 1)
ERU-C-1 SUPPLY (PATH 2)
RECTANGULAR
TYPE
(NOTE 1)
RS
RS
S
NOMINAL DIMENSIONS, IN.
LENGTH
(NOTE 2)
STANDARD
WIDTH/
INSIDE DIA.
HEIGHT/
OUTSIDE DIA.
FT/MIN
(NOTE 3)
+1,300
+1,300
MAX.
APD,
IN. WG
0.25
0.18
MINIMUM DYNAMIC INSERTION LOSS, dB
OCTAVE BAND CENTER FREQUENCY, Hz
MAXIMUM GENERATED NOISE, dB
OCTAVE BAND CENTER FREQUENCY, Hz
NOTES
DUCTLESS SPLIT SYSTEM SCHEDULE
NO. AREA SERVED
TYPE
(NOTE 2)
INDOOR UNIT
NOMINAL CFM
(NOTE 3)
COOLING (NOTE 4) REVERSE CYCLE HEATING INDOOR
UNIT
MOUNTING
HEIGHT NOTES
SENSIBLE
CAPACITY,
MBH
TOTAL
CAPACITY,
MBH
MINIMUM
EER
CAPACITY,
MBH (NOTE 5)
MINIMUM
HSPF
DSS-C1-1 MAIN COMM AC 700 19 30 19 -- -- 8
DSS-C1-2 COMM AC 600 15 24 18 -- -- 8
DSS-C2-1 COMM AC 500 12 18 18 -- -- 8
DSS-C3-1 COMM AC 500 12 18 18 -- -- 8
NOTES:
1. DESIGN CONDITIONS:
SUMMER WINTER
OUTSIDE 92.4°F DB, 72.7°F WB 20°F
TELECOM ROOMS 76°F DB, 50% RH 70°F
2. TYPE:
AC COOLING ONLY
HP HEAT PUMP - HEATING AND COOLING
3. INDOOR UNIT CFM IS BASED ON MEDIUM FAN SPEED.
4. BASED ON 76°F DB 63°F WB ENTERING INDOOR COIL, AND 105°F DB ENTERING OUTSIDE COIL.
5. BASED ON 70°F ENTERING INDOOR COIL AND 47°F DB, 43°F WB ENTERING OUTSIDE COIL.
6. REFER TO THE ELECTRICAL DRAWINGS FOR THE EQUIPMENT ELECTRICAL CHARACTERISTICS.
A
B
C
E
D
F
KEY PLAN
MARK DATE DESCRIPTION
2 06/07/2023 SCO COMMENTS
9 03/07/2024 CPR-005
26 08/18/2025 LS Revision
Signed on using a Digital Signature.
08/18/2025
@JLL@
Docusign Envelope ID: 5671A0D7-23B2-4A33-A49E-4629997C2B13
| 2025-08-18T13:21:05-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |