This is a mechanical construction document set for the NCSSM (North Carolina School of Science and Mathematics) Western Campus Building C—Joiner Hall Renovation project, prepared by design and engineering firms including Duda|Paine Architects, Newcomb & Boyd (MEP&FP Engineer), and other supporting consultants. The document consists of HVAC piping floor plans for Levels 1, 2, 3, and the attic level, detailing the installation of Variable Refrigerant Flow (VRF) systems, condensate piping, and related mechanical infrastructure. The plans specify refrigerant piping routes to multiple indoor cassette units (VRF-C1 through VRF-C5) and branch control cassettes (BCC), with pipe diameters ranging from 0.75 inches to 1.5 inches. Key specifications include condensate routing to floor drains and mop sinks, isolation valve and hose end connection requirements at cleanout locations, and piping pathways following ductwork through soffits across corridors. The document was issued on March 10, 2023, with construction document status, and reflects revision updates through January 19, 2024 (CPR-005), indicating the plans are part of an active construction phase.

The document includes comprehensive wall rating legends distinguishing between 1-hour, 2-hour, and 3-hour fire barriers, smoke partitions, and related fire-safety designations relevant to the facility's life safety systems, which were evaluated by Jensen Hughes. Equipment installation specifications note that certain units are installed in Level 3 ceiling spaces with thermostats located in the attic above the ceiling. The piping plans serve as technical specifications for the HVAC contractor executing the renovation and are the exclusive property of Duda|Paine Architects, subject to copyright restrictions. This document directly supports the NCSSM-Morganton HVAC Maintenance Services RFP, which seeks a contractor to perform preventative maintenance and repair services on HVAC systems across multiple campus buildings including Joiner Hall.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ERU-C-1

FTR-C-2FTR-C-1

3 4 5 6 7 8 921 10

C

A

D

F

E

B

ERU-C-1 CU

VRF-C1-1 VRF-C1-2

VRF-C1-10

VRF-C1-4 VRF-C1-5 VRF-C1-6

VRF-C1-8

VRF-C1-9

VRF-C1-11

DSS-C1-1

VRF-C1-12

VRF-C1-13

BCC-C1

VRF-C1-3

VRF-C1-7

REFRIGERANT

PIPING (TYP.)

REFRIGERANT

PIPING (TYP.)

REFRIGERANT PIPING

UP TO BCC-2

REFRIGERANT PIPING

UP TO BCC-4

REFRIGERANT

PIPING UP TO BCC-3

REFRIGERANT

PIPING UP TO BCC-5

ROUTE 1.5"

CONDENSATE TO

FLOOR DRAIN

1.25" D UP

1.25" D UP

0.75" D

1" D

0.75" D

0.75" D

0.75" D

0.75" D T

T

T

T

T

T

T

T

UH-C-7

T

T

0.75" D

0.75" D

2D STUDIO

VESTIBULE

1100A

CORRIDOR

STAIR 1

1100B

ST1

STAIR 2

1200B

ST2

VESTIBULE

1200A

CLAY STUDIO

MECHANICAL

MEN

ART STORAGE

CLASSROOM

WOMEN

CORRIDOR

UNISEX

MAIN COMM.

1100C

MAIN ELEC. RM.

KILN

1103B 1103B

CORRIDOR

DSS-C1-2

DSS-C3-1 CU

DSS-C1-2 CU

DSS-C1-1 CU

DSS-C2-1 CU

ROUTE 0.75" CONDENSATE

TO FLOOR DRAIN

DROP REFRIGERANT PIPING IN THE

MECHANICAL ROOM AND ROUTE THROUGH

EXTERIOR WALL LOW. PIPING SHALL EXIT

BUILDING IN NEAT AND ORDERLY FASHION.

VRF-C5

VRF-C3VRF-C4

VRF-C2

VRF-C1

EM. ELEC

0.75" D UP

0.75" D

2 1.25" D

T

2D STUDIO STORAGE

3 4 5 6 7 8 921 10

C

A

D

F

E

B

VRF-C2-1 VRF-C2-2

VRF-C2-3

VRF-C2-4

DSS-C2-1

VRF-C2-6

VRF-C3-1

VRF-C3-3

VRF-C3-5

VRF-C3-7

BCC-C2

BCC-C3

VRF-C2-7

VRF-C3-4

VRF-C3-6

VRF-C3-2

VRF-C2-5

0.75" D

0.75" D

1.25" D

UP & DN

0.75" D

0.75" D 1" D

REFRIGERANT PIPING DOWN

TO VRF-C3 OUTDOOR UNIT

REFRIGERANT

PIPING UP TO BCC-C5

T

T

T

T

T T

T

T T

T

T

T

REFRIGERANT PIPING DOWN

TO VRF-C3 OUTDOOR UNIT

REFRIGERANT

PIPING UP TO BCC-C4

FACULTY HUB

DATA SCIENCE

COMPUTING

CLASSROOM

STAIR 1

2100B

ST1

STORAGE

VESTIBULE

2100A 2100A

STAIR 2

2200B

ST2

COMPUTING

CLASSROOM

WOMEN

COMMONS / GALLERY

VESTIBULE

2200A 2200A

MEN

CORRIDOR

ENTRY

ELEC

2100D 2100D

CORRIDOR

COMM

2102A 2102A

1.25" D UP & DN

REFRIGERANT PIPE

DN TO DSS-C2-1 CU

0.75" D DN

0.75" D

0.75" D

0.75" D

0.75" D

1.25" D

0.75" D

1" D

1" D

1.25" D

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St.

Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

CIVIL ENGINEER AND LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

LICENSE # C-1051

ADAPTIVE RE-USE STRUCTURAL ENGINEER

Kaydos-Daniels Engineers, PLLC

400-201 W. Morgan St.

Raleigh, NC 27603

LICENSE # P-0279

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

LICENSE # F-03112

COST ESTIMATOR

Palacio Collaborative

4819 Emperor Boulevard, Suite 400

Durham, NC 27703

LIFE SAFETY

Jensen Hughes

8000 Regency Parkway, Suite 580

Cary, NC 27518

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2022 Duda|Paine Architects, PA

303 Peachtree Center Avenue, NE Suite 525 Atlanta, GA 30303-1277 T 404 730-8400 NB Contact: Richard O. Dozier

N&B PROJECT: 17N054

NC Firm Lic. #F-0312 Newcomb & Boyd, LLP

/4

/2

:4 :0

P

M

MC201

HVAC PIPING

FLOOR PLANS

- LEVELS 1 & 2

03/10/2023 21611.39

Construction Documents

SCO# 16-14368-02N

N C

S S M

W e st e rn

C a m p u s

B u ild in g C

J o in e r H a ll

R e n o v a ti o n

1/8" = 1'-0"MC201

1 HVAC PIPING FLOOR PLAN LEVEL 1

1/8" = 1'-0"MC201

2 HVAC PIPING FLOOR PLAN LEVEL 2

KEY NOTES THIS SHEET:

PIPING SHALL FOLLOW PATH OF DUCTWORK THROUGH SOFFITS

ACROSS CORRIDOR

CONDENSATE CLEANOUT LOCATION. PROVIDE ISOLATION VALVE AND

HOSE END CONNECTION.

ROUTE CONDENSATE DOWN TIGHT TO WALL AND TERMINATE IN MOP

SINK.

N

A

B

C

E

D

F

KEY PLAN

MARK DATE DESCRIPTION

2 06/07/2023 SCO COMMENTS

6 01/19/2024 CPR-002

9 03/07/2024 CPR-005

Signed on using a Digital Signature.

03/06/2024

@JLL@

DocuSign Envelope ID: 2B245994-C24A-4A04-A97D-ACC4386A7238

3 4 5 6 7 8 921 10

C

A

D

F

E

B

VRF-C4-1 VRF-C4-2 VRF-C4-3

VRF-C4-5

VRF-C5-1

VRF-C5-2

VRF-C5-4VRF-C5-5

VRF-C4-6

VRF-C4-4

VRF-C5-3

T

T

T

T

T T

T

T

TT

T

REFRIGERANT PIPING DOWN

TO VRF-C4 OUTDOOR UNIT

REFRIGERANT PIPING DOWN

TO VRF-C5 OUTDOOR UNIT

LARGE CONFERENCE

STAIR 1

3100B

ST1

STAIR 2

3200B

ST2

STORAGE

WOMEN

CLASSROOM

BREAK ROOM

VESTIBULE

3200A 3200A

MEN

FOCUS

3001A

OFFICE

CORRIDOR

CORRIDOR

TOUCHDOWN

ELEC.

3100C 3100C

COMM.

3102A 3102A

FOCUS

3002A

VESTIBULE

3000A

DSS-C3-1 1" D DOWN

REFRIGERANT PIPING

DN TO DSS-C3-1 CU

T

FOCUS

3002B

FOCUS

3001B

3 4 5 6 7 8 921 10

C

A

D

F

E

B

UH-C-1

UH-C-2

UH-C-3

UH-C-5

UH-C-6

UH-C-4

VRF-C5-6

MC401

MC401

REFRIGERANT PIPING UP TO

BCC-C-5 INDOOR UNIT

T

T

T

T

T

T

REFRIGERANT PIPING DOWN

TO VRF-C4 OUTDOOR UNIT

0.75" D

0.75" D

0.75" D

0.75" D

1" D

1.25" D DN

BCC-C4

VRF-C4-1 VRF-C4-2

VRF-C4-5

DSS-C3-1

VRF-C5-5 VRF-C5-4

VRF-C5-2

VRF-C5-1VRF-C4-3

0.75" D

1" D

BCC-C5

VRF-C4-6

VRF-C5-3

REFRIGERANT PIPING DOWN

TO VRF-C5 OUTDOOR UNIT

1" D DOWN

VRF-C4-7

1" D

Wall Rating Legend

1-Hour Fire Barrier

2-Hour Fire Barrier

Unrated Walls

Smoke Partition

3-Hour Fire Barrier

2-Hour Smoke Barrier

1-Hour Smoke Barrier

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St.

Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

CIVIL ENGINEER AND LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

LICENSE # C-1051

ADAPTIVE RE-USE STRUCTURAL ENGINEER

Kaydos-Daniels Engineers, PLLC

400-201 W. Morgan St.

Raleigh, NC 27603

LICENSE # P-0279

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

LICENSE # F-03112

COST ESTIMATOR

Palacio Collaborative

4819 Emperor Boulevard, Suite 400

Durham, NC 27703

LIFE SAFETY

Jensen Hughes

8000 Regency Parkway, Suite 580

Cary, NC 27518

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2022 Duda|Paine Architects, PA

303 Peachtree Center Avenue, NE Suite 525 Atlanta, GA 30303-1277 T 404 730-8400 NB Contact: Richard O. Dozier

N&B PROJECT: 17N054

NC Firm Lic. #F-0312 Newcomb & Boyd, LLP

/1

/2

:0 :5

P

M

MC202

HVAC PIPING

FLOOR PLANS

- LEVELS 3 &

ROOF

03/10/2023 21611.39

Construction Documents

SCO# 16-14368-02N

N C

S S M

W e st e rn

C a m p u s

B u ild in g C

J o in e r H a ll

R e n o v a ti o n

1/8" = 1'-0"MC202

1 HVAC PIPING FLOOR PLAN LEVEL 3

1/8" = 1'-0"MC202

2 HVAC PIPING FLOOR PLAN ATTIC LEVEL

N

KEY NOTES THIS SHEET:

CONDENSATE CLEANOUT LOCATION. PROVIDE ISOLATION VALVE AND

HOSE END CONNECTION.

EQUIPMENT INSTALLED IN LEVEL 3 CEILING.

THERMOSTAT FOR UNIT HEATER LOCATED IN ATTIC ABOVE CEILING.

A

B

C

E

D

F

KEY PLAN

MARK DATE DESCRIPTION

2 06/07/2023 SCO COMMENTS

6 01/19/2024 CPR-002

Signed on using a Digital Signature.

01/19/2024

@JLL@