GOODWIN MA502-HVAC-SCHEDULES-Rev.2.pdf

PDF 410 KB Posted

Attached to
NCSSM-Morganton - HVAC Maintenance Services - Residence Hall, Academic Commons, SWAC, Goodwin Hall, Joiner Hall
Solicitation number
87-07082026
Issued by
Cabarrus County, North Carolina

About this file

This document is a VRF (Variable Refrigerant Flow) fan-coil unit and outdoor unit schedule prepared by Newcomb & Boyd Consulting Engineers for the North Carolina School of Science and Mathematics (NCSSM) Western Campus Building A—Goodwin Hall adaptive reuse project in Durham, North Carolina. The schedule details HVAC specifications for the building's climate control system, which will serve the renovation of this academic facility. The document specifies 72 individual VRF fan-coil units distributed across multiple floors and zones, with unit types including ceiling-suspended, wall-mounted, cassette, and multi-position air handler configurations. Cooling capacities range from 4.3 to 33.9 MBH, while heating capacities range from 6.7 to 53.0 MBH. The document also identifies four outdoor VRF units—three Trane TURY-P series units (P216, P288, P192) and their associated specifications for second and third floor zones. Design conditions are established for various space types, including classrooms at 75°F DB with 50% RH for summer and 70°F for winter, with specialized conditions for mechanical spaces reaching 104°F DB and electrical spaces at 90°F DB.

The technical specifications include minimum efficiency ratings of 11.2 to 12.1 HSPF and 19.6 to 23.9 IEER per AHRI Standard 1230-2010 for the outdoor units, with connection ratios between 0.97 and 1.12. All indoor units are designated with a Trane basis of design and require integral disconnects per electrical drawings. The outdoor units incorporate heat recovery capability, and the total refrigerant charge for the complete VRF system, including all branch controllers and piping, is subject to maximum allowance specifications shown in drawing MC001. This schedule is part of the construction documents bid set for SCO #16-14368-02F and reflects design revisions dated through August 26, 2021. The document is the exclusive property of Duda|Paine Architects, PA, and is intended for the specific NCSSM-Morganton campus HVAC maintenance services project.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Newcomb&Boyd

CONSULTANTS AND ENGINEERS

ISSUE DATE:

PROJECT NUMBER:

OWNER

NCSSM

1219 Broad St, Durham, NC 27705

ARCHITECT

Duda|Paine Architects, PA

333 Liggett Street

Durham, NC 27701

ADAPTIVE RE-USE ARCHITECT

Belk Architecture

735 9th Street

Durham, NC 27705

LANDSCAPE ARCHITECT

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

CIVIL ENGINEER

Stewart, Inc

421 Fayetteville St. Suite 400

Raleigh, NC 27601

STRUCTURAL ENGINEER

Bennett & Pless

1309 Amble Drive

Charlotte, NC 28206

MEP&FP ENGINEER

Newcomb & Boyd

303 Peachtree Center Ave., NE

Suite 525

Atlanta, GA 30303

FOOD SERVICE DESIGN

Food Design Associates

615 South College Street

9th Floor

Charlotte, NC 28202

COST ESTIMATOR

RM Rutherford & Associates Inc

3328 Mill Pond Road

Charlotte, NC 28226

This document is the product and exclusive property of Duda|Paine

Architects, PA. Neither the document nor the information it contains may be copied, disclosed to others or used in connection with any work or project other than the specific project for which they have been prepared and developed without the written consent of

Duda|Paine Architects, PA.

© Copyright 2019 Duda|Paine Architects, PA

Copyright © 2019 Consulting Engineering Group T 404 730-8400 Firm License No. F-03112 Contact: Richard O. Dozier

N&B PROJECT:17N0548

/2 /2

:5 :2

P

M

MA502

HVAC

SCHEDULES

04/17/20 21611

Construction Documents Bid Set

SCO # 16-14368-02F

N C

S S M

W e st e rn

C a m p u s

B u ild in g A

G o o d w in H a ll

VRF FAN-COIL UNIT SCHEDULE

NO. AREA SERVED

TYPE

(NOTE 1)

NOMINAL CFM

(NOTE 2)

COOLING

SENSIBLE

MBH (NOTE 3)

HEATING

MBH NOTES

VRF-A1-1 OFFICE CS 450 10.0 17.0 4,5

VRF-A1-2 OFFICE CS 450 10.0 17.0 4,5

VRF-A1-3 TOILET W 210 4.3 6.7 4,5

VRF-A1-4 TOILET W 210 4.3 6.7 4,5

VRF-A1-5 MAIN ELEC. W 420 8.8 13.5 4,5

VRF-A1-6 OFFICE CS 640 15.4 25.9 4,5

VRF-A1-7 FACILITIES CS 640 15.4 25.9 4,5

VRF-A1-8 OFFICE W 210 4.3 6.7 4,5

VRF-A2-1 STORAGE W 210 4.3 6.7 4,5

VRF-A2-2 FACILITIES W 210 4.3 6.7 4,5

VRF-A2-3 FACILITIES W 420 8.8 13.5 4,5

VRF-A2-4 UTILITY ENTRANCE W 420 8.8 13.5 4,5

VRF-A2-5 CHECK-IN C 350 9.4 15.1 4,5

VRF-A2-6 OFFICE CS 640 15.4 25.9 4,5

VRF-A2-7 MAILROOM CS 1000 20.5 32.6 4,5

VRF-A2-8 OFFICE W 420 8.8 13.5 4,5

VRF-A2-9 OFFICE CS 450 10.0 17.0 4,5

VRF-A2-10 OFFICE W 420 8.8 13.5 4,5

VRF-A2-11 FACULTY BREAK W 420 8.8 13.5 4,5

VRF-A2-12 FACULTY HUB CS 1000 20.5 32.6 4,5

VRF-A2-13 CONECTOR W 420 8.8 13.5 4,5

VRF-A2-14 OFFICE CS 450 10.0 17.0 4,5

VRF-A3-1 GROUP STUDY CS 640 15.4 25.9 4,5

VRF-A3-2 GROUP STUDY W 210 4.3 6.7 4,5

VRF-A3-3 GROUP STUDY CS 640 15.4 25.9 4,5

VRF-A3-4 TOILET W 210 4.3 6.7 4,5

VRF-A3-5 OFFICE CS 450 10.0 17.0 4,5

VRF-A3-6 TOILET W 210 4.3 6.7 4,5

VRF-A3-7 ELECTRICAL W 210 4.3 6.7 4,5

VRF-A3-8 STORAGE W 210 4.3 6.7 4,5

VRF-A3-9 CONFERENCE W 420 8.8 13.5 4,5

VRF-A3-10 CLASSROOM CS 1000 20.5 32.6 4,5

VRF-A3-11 COMMONS CS 1000 20.5 32.6 4,5

VRF-A3-12 COMMONS CS 640 15.4 25.9 4,5

VRF-A3-13 CLASSROOM CS 640 15.4 25.9 4,5

VRF-A4-1 COMMONS CS 640 15.4 25.9 4,5

VRF-A4-2 COMMONS CS 1000 20.5 32.6 4,5

VRF-A4-3 CLASSROOM CS 1000 20.5 32.6 4,5

VRF-A4-4 CLASSROOM CS 1000 20.5 32.6 4,5

VRF-A4-5 MEETING W 420 8.8 13.5 4,5

VRF-A4-6 OFFICE CS 640 15.4 25.9 4,5

VRF-A4-7 MEETING W 420 8.8 13.5 4,5

VRF-A4-8 MEETING W 420 8.8 13.5 4,5

VRF-A4-9 OFFICE CS 450 10.0 17.0 4,5

VRF-A4-10 OFFICE CS 640 15.4 25.9 4,5

VRF-A5-1 CLASSROOM CS 640 15.4 25.9 4,5

VRF-A5-2 CLASSROOM CS 640 15.4 25.9 4,5

VRF-A5-3 TOILET W 210 4.3 6.7 4,5

VRF-A5-4 CONFERENCE CS 640 15.4 25.9 4,5

VRF-A5-5 TOILET W 210 4.3 6.7 4,5

VRF-A5-6 ELECTRICAL W 210 4.3 6.7 4,5

VRF-A5-7 ELEVATOR CONTROL W 210 4.3 6.7 4,5

VRF-A5-8 STORAGE W 210 4.3 6.7 4,5

VRF-A5-9 BREAKROOM CS 640 15.4 25.9 4,5

VRF-A5-10 CLASSROOM CS 450 10.0 17 4,5

VRF-A5-11 CLASSROOM CS 450 10.0 17 4,5

VRF-A5-12 DEANS SUITE CS 640 15.4 25.9 4,5

VRF-A5-13 FOCUS C 320 5.1 8 4,5

VRF-A5-14 RECEPTION C 320 5.1 8 4,5

VRF-A5-15 STUDY LOUNGE CS 1000 20.5 32.6 4,5

VRF-A5-16 MULTIPURPOSE MA 1485 33.9 53.0 4,5,6

VRF-A5-17 MULTIPURPOSE MA 875 21.9 34 4,5,6

VRF-A6-1 DEANS SUITE CS 640 15.4 25.9 4,5

VRF-A6-2 CONFERENCE C 350 9.4 15.1 4,5

VRF-A6-3 STUDY LOUNGE CS 1000 20.5 32.6 4,5

VRF-A6-4 OFFICE CS 640 15.4 25.9 4,5

VRF-A6-5 OFFICE CS 1000 20.5 32.6 4,5

VRF-A6-6 MEETING W 420 8.8 13.5 4,5

VRF-A6-7 MEETING W 420 8.8 13.5 4,5

VRF-A6-8 OFFICE CS 640 15.4 25.9 4,5

VRF-A6-9 MEETING W 420 8.8 13.5 4,5

VRF-A6-10 OFFICE CS 450 10.0 17.0 4,5

VRF-A6-11 ASST. DIR. HR CS 450 10.0 17.0 4,5

VRF-A6-12 HR TECH W 420 8.8 13.5 4,5NOTES:

1. TYPE:

CS CEILING SUSPENDED

W WALL-MOUNTED

C CASSETTE

MA MULTI-POSITION AIR HANDLER

2. CFM BASED ON MEDIUM FAN SPEED.

3. BASED ON 75°F DB/20°F WB INDOOR RETURN AIR

4. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

PROVIDE INTEGRAL DICONNECT.

5. BASIS OF DESIGN: TRANE.

6. MINIMUM ESP SHALL BE 0.5" W.G.

VRF OUTDOOR UNIT SCHEDULE

NO. AREA SERVED

COOLING (NOTE 2)

HEATING

CAPACITY,

MBH

MINIMUM

HSPF (NOTE 4) NOTES BASIS OF DESIGN

TOTAL

CAPACITY, MBH

SUM OF CONNECTED

INDOOR UNIT TOTAL

CAPACITIES, MBH

CONNECTION

RATIO

MINIMUM

EER (NOTE 4)

MINIMUM

IEER (NOTE 4)

VRF-A3 SECOND FLOOR NORTH 216.5 211 0.97 11.2 19.6 242.8 3.59 5, 6, 7 TRANE TURY-P216

VRF-A4 SECOND FLOOR SOUTH 216.5 211 0.97 11.2 19.6 242.8 3.59 5, 6, 7 TRANE TURY-P216

VRF-A5 THIRD FLOOR NORTH 288 297 1.03 11.2 19.6 323 3.59 5, 6, 7 TRANE TURY-P288

VRF-A6 THIRD FLOOR SOUTH 196.7 220.4 1.12 12.1 23.9 215.0 3.59 5, 6, 7 TRANE TURY-P192

NOTES:

1. DESIGN CONDITIONS:

SUMMER WINTER

CLASSROOMS 75°F DB, 50% RH 70°F

OFFICES 75°F DB, 50% RH 70°F

ARTS & ENSEMBLE 75°F DB, 50% RH 70°F

ELECTRICAL 90°DB 50°F

MECHANICAL 104°F DB 50°F

COMMUNICATIONS 78°F DB 70°F

REMAINING SPACE 75°F DB, 50% RH 70°F

2. BASED ON 105°F DB ENTERING OUTSIDE COIL.

3. BASED ON 10°F ENTERING OUTSIDE COIL.

4. AS PUBLISHED IN AHRI STANDARD 1230-2010 FOR MIXED INDOOR UNITS. AT 17°F ENTERING

OUTSIDE AIR AND 70°F DB/60°F WB ENTERING INDOOR AIR.

5. REFER TO THE ELECTRICAL DRAWINGS FOR EQUIPMENT ELECTRICAL CHARACTERISTICS.

6. PROVIDE HEAT RECOVERY CAPABILITY.

7. TOTAL REFRIGERANT CHARGE IN VRF SYSTEM, INCLUDING OUTDOOR UNIT, FAN-COIL UNITS, BRANCH CIRCUIT CONTROLLER, AND REFRIGERANT PIPING, SHALL NOT EXCEED THE MAXIMUM

ALLOWED REFRIGERANT CHARGE SHOWN ON DRAWING MC001.

A

B

C

E

D

F

KEY PLAN

MARK DATE DESCRIPTION

62 04/27/2021 CPR-056 Rev

90 06/23/2021 CPR-083

100 08/26/2021 CPR-090

DocuSign Envelope ID: 13633A38-FB58-4412-890A-A05967C6B9B4

08/25/2021

File details come from the government source that posted it. Updated .