XRF Lead Report_WH-21_ p.1
Defense Logistics Agency - San Joaquin Tracy, California
XRF Lead Evaluation
Date: 27 June 2017 Subject: Field Analysis for Suspect Lead Paint Bulk Sample Collected from the DLASJ Tracy, Warehouse 21
Evaluation
On 27 June 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 21. Robert Miller, Certified Industrial Hygienist, and Lonny Jones, Industrial Hygiene Technician, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 21 is provided in Table 1 of this report.
Table 1 Sample Number
Coating / Paint Description Lead Concentration
0627-21-01 Warehouse Exterior: Yellow on floor on dock around conveyor
>2.05 mg/cm2
0627-21-02 Warehouse Interior: Safety yellow on floor Non-Detect (ND) 0627-21-03 Warehouse Interior: Blue on metal pedestrian door ND 0627-21-04 Warehouse Interior: Blue on walls ND 0627-21-05 Warehouse Interior: White on steel I-beams 3.54 mg/cm2 0627-21-06 Warehouse Interior: Fire red on floor (significant peeling) >5.0 mg/cm2 0627-21-07 Warehouse Interior: Yellow on former fire door columns >5.0 mg/cm2 0627-21-08 Warehouse Interior: Black on floor ND 0627-21-09 Warehouse Interior: Caution yellow on floor (significant damage, approx. 30 sq. ft on west side near fire riser) >1.01 mg/cm2
0627-21-10 Warehouse Interior: Blue on sheetrock covering above cargo door
ND
0627-21-11 Bubble Interior: White on concrete walls ND 0627-21-12 Bubble Interior: Blue on pedestrian door trims ND 0627-21-13 Bubble Interior: White on drywalls ND 0627-21-14 Warehouse Exterior: Safety yellow on stairwell ND
XRF Lead Report_WH-21_ p.2
Discussion The field testing of the coatings associated with the DLASJ Tracy, Warehouse 21, did identify
Lead concentrations that are described in Table 1 of this report. The Federal OSHA 29 CFR
1926.62 and 29 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.
Recommendations
• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 29 CFR 1926.62, 29 CFR
1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.
• Disposal of any building materials that are coated with Lead-containing paint must be disposed of per the requirements of the DS-FJ Installation Support Environmental Office.
Robert Miller, CIH Certified Industrial Hygienist
Lonny Jones
Industrial Hygiene Technician