Lead_Report_Warehouse_16.pdf

PDF 64 KB Posted

Attached to
Paint the interior walls of offices and adjacent areas of Buildings
Solicitation number
SP330017B0014
Issued by

About this file

Lead Report Warehouse 16

View the file

Other files

File Type Posted
Amendment_0004_to_SP330017B0014.pdf PDF
Updated_Attachment_7_Drawings.pdf PDF
Updated_Attachment_6_Specifications.pdf PDF
Amendment_0003.pdf PDF
Lead_Report_Building_255.pdf PDF
Amendment_0002.pdf PDF
Lead_Report_Building_201.pdf PDF
Lead_Report_Warehouse_19.pdf PDF
Lead_Report_Warehouse_22.pdf PDF
Lead_Report_Warehouse_14.pdf PDF
Lead_Report_Building_247.pdf PDF
Lead_Report_Warehouse_21.pdf PDF
Lead_Report_Warehouse_28.pdf PDF
Updated_SF1449_Solicitation_SP330017B0014.pdf PDF
Lead_Report_Building_231.pdf PDF
Lead_Report_Warehouse_15.pdf PDF
Lead_Report_Warehouse_20.pdf PDF
Updated_Attachment_6_-_Specifications.pdf PDF
Lead_Report_Warehouse_13.pdf PDF
Site_Visit_Attendee_List.pdf PDF
Updated_Attachment_6_-_Specifications.pdf PDF
Updated_SF1449_Solicitation_SP330017B0014.pdf PDF
Amendment_0001.pdf PDF
Attachment_1_-__SF24_-_Bid_Bond.pdf PDF
Attachment_3_-__SF25A_(Payment_Bond).pdf PDF
Attachment_4_Construction_Wage_Determination.pdf PDF
Attachment_6_Specifications.pdf PDF
Attachment_5_Environmental_Checklist.pdf PDF
SF1442_Solicitation.pdf PDF
Attachment_8_Submittal_Register_.pdf PDF
Attachment_7_Drawings.pdf PDF
Attachment_2_-__SF25_(Performance_Bond).pdf PDF
synopsis.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

XRF Lead Report_WH-16_ p.1

Defense Logistics Agency - San Joaquin Tracy, California

XRF Lead Evaluation

Date: 14 June 2017 Subject: Field Analysis for Suspect Lead Paint Bulk Sample Collected from the DLASJ Tracy, Warehouse 16

Evaluation

On 14 June 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 16. Robert Miller, Certified Industrial Hygienist, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 16 is provided in Table 1 of this report.

Table 1 Sample Number

Coating / Paint Description Lead Concentration

0614-16-01 Building Interior: Beige on drywalls (Cafeteria) Non-Detect (ND) 0614-16-02 Building Interior: Beige on drywalls (Kitchen) ND 0614-16-03 Building Exterior: Tan on guardrails ND 0614-16-04 Building Exterior: Blue on trim on north windows and door metal

ND

0614-16-05 Building Exterior: Yellow on stair rails ND 0614-16-06 Warehouse Exterior: Blue on trim around roll-up doors >5.0 mg/cm2 0614-16-07 Warehouse Exterior: White on concrete walls ND 0614-16-08 Warehouse Exterior: Yellow on steel dock bumpers >5.0 mg/cm2 0614-16-09 Warehouse Exterior: Yellow on wood bumpers on docks ND 0614-16-10 Warehouse Exterior: Yellow on steel stair railings ND 0614-16-11 Warehouse Interior: White on concrete walls ND 0614-16-12 Warehouse Interior: Blue on concrete walls ND 0614-16-13 Warehouse Interior: Red on floors ND 0614-16-14 Warehouse Interior: Tan on bollards ND 0614-16-15 Warehouse Interior: Safety yellow on concrete floors ND 0614-16-16 Warehouse Interior: Yellow columns by former fire doors >5.0 mg/cm2 0614-16-17 Warehouse Interior: Yellow on metal spiral stairs (Section

A3)

ND

0614-16-18 Warehouse Interior: Blue on perimeter metal pedestrian doors

ND

0614-16-19 Warehouse Interior: Yellow on concrete floor (Section 5;

worn)

>4.3 mg/cm2

XRF Lead Report_WH-16_ p.2

0614-16-20 Warehouse Interior: Black coating on floor (Section 5;

worn)

>5.0 mg/cm2

0614-16-21 Warehouse Interior: Green on floor (eyewash) >1.5 mg/cm2 0614-16-22 Warehouse Interior: Black paint on floor (Sections B4 &

B3)

ND

0614-16-23 Warehouse Interior: Green chips on wall ND 0614-16-24 Warehouse Interior: Black paint on floor (Section B2;

worn) >1.0 mg/cm2

0614-16-25 Warehouse Interior: Yellow on floor (Section B2; worn) >2.70 mg/cm2

Discussion

The field testing of the coatings associated with the DLASJ Tracy, Warehouse 16, did identify Lead concentrations that are described in Table 1 of this report. The Federal OSHA 16 CFR

1926.62 and 16 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.

Recommendations

• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 16 CFR 1926.62, 16 CFR

1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.

• Disposal of any building materials that are coated with Lead-containing paint must be disposed of per the requirements of the DS-FJ Installation Support Environmental Office.

Robert Miller, CIH Certified Industrial Hygienist