XRF Lead Report_WH-14_ p.1
Defense Logistics Agency - San Joaquin Tracy, California
XRF Lead Evaluation
Date: 05 July 2017 Subject: Field Analysis for Suspect Lead Paint Bulk Sample Collected from the DLASJ Tracy, Warehouse 14
XRF Lead Evaluation
On 05 July 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Warehouse 14. Robert Miller, Certified Industrial Hygienist, and Lonny Jones, Industrial Hygiene Technician, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Warehouse 14 is provided in Table 1 of this report.
Table 1 Sample Number
Coating / Paint Description Lead Concentration
0705-14-01 Bubble Interior: White on concrete walls Non-Detect (ND) 0705-14-02 Bubble Interior: Restroom, white on drywalls ND 0705-14-03 Bubble Interior: Blue on metal pedestrian doors ND 0705-14-04 Bubble Interior: Supervisor’s Office, Cream white on panel walls
ND
0705-14-05 Bubble Interior: Breakroom, Cream white on panel walls ND 0705-14-06 Bubble Interior: White on steel pipes ND 0705-14-07 Warehouse Interior: Safety yellow on floor >2.0 mg/cm2 0705-14-08 Warehouse Interior: White and blue on steel I-beams 4.73 mg/cm2 0705-14-09 Warehouse Interior: White on concrete walls ND 0705-14-10 Warehouse Interior: Blue on concrete walls ND 0705-14-11 Warehouse Interior: Yellow on former fire door columns 4.01 mg/cm2 0705-14-12 Warehouse Interior: Yellow on firewalls >5.0 mg/cm2 0705-14-13 Warehouse Interior: Black on floor ND 0705-14-14 Warehouse Interior: Red on fire risers ND 0705-14-15 Warehouse Interior: Yellow layer beneath black on floor >4.1 mg/cm2 0705-14-16 Warehouse Interior: Dark gray on new portion of fire riser ND
XRF Lead Report_WH-14_ p.2
Warehouse Exterior Evaluation (Laboratory Analysis of Bulk Samples) On 01 May 2017, bulk samples were collected from exterior surfaces of the DLASJ Tracy, Warehouse 14. Robert Miller, a Certified Industrial Hygienist, collected the bulk paint samples.
Micro Analytical Laboratories, Inc., Emeryville, California, performed the laboratory analysis.
Micro Analytical Laboratories is an AIHA accredited laboratory, ID# 101768. The bulk paint samples were analyzed for Lead by Flame Atomic Absorption Spectrometry in accordance with
EPA/600/8-91/213, 1991.
Table 2
Sample Number Location Material Description Lead Concentration
0501-14-01 Section 1, East Wall Wall; Bluish white
<0.0080 <80 mg/kg (ppm)
0501-14-02 Section 1, East Wall Window trim on the East and West Perimeter Beneath the facia; Light blue
0.064% 640 mg/kg (ppm)
0501-14-03 Section 1, East Wall Facia (8 inches wide) along roof line; Light and dark (new) blue paint; Red paint beneath top layer
4.2% 42,000 mg/kg (ppm)
0501-14-04 Section 2, East Wall Awning trim; Faded blue
<0.0076% <76 mg/kg (ppm)
0501-14-05 Section 1, East Wall Cast iron portion of downspout;
Light blue
3.9% 39,000 mg/kg (ppm)
On 17 June 2016, bulk samples were collected from the yellow coatings (paint) applied to the exterior Loading Dock Building Materials at the DLASJ Tracy, Warehouse 14. Robert Miller, a Certified Industrial Hygienist, collected the bulk paint samples. Micro Analytical Laboratories, Inc., Emeryville, California, performed the laboratory analysis. Micro Analytical Laboratories is an AIHA accredited laboratory, ID# 101768. The bulk paint samples were analyzed for Lead by Flame Atomic Absorption Spectrometry in accordance with EPA/600/8-91/213, 1991.
Table 3 Sample Number
Material Description Lead Concentration
0617-14-01 Two layers of Yellow Coating (paint) on steel angle dock edge located on east loading dock of
WH 14, Section 1. The yellow paint included blistering.
72,000 mg/kg (ppm)
7.2 % Lead
0617-14-02 Yellow Coating (paint) on wood bumpers on east loading dock of WH 14, Section 1. The yellow paint had significant blistering and the wood bumper was deteriorated.
190,000 mg/kg (ppm)
19 % Lead
0617-14-03 Yellow Coating (paint) on steel hand rail located on west loading dock stairwell of WH 14, South of Bubble. The yellow paint had minimal blistering.
110,000 mg/kg (ppm)
11 % Lead 0617-14-04 Yellow Coating (paint) on steel angle dock edge located on west loading dock of WH 14, Section 4.
The yellow paint had minimal blistering
68,000 mg/kg (ppm)
6.8 % Lead
XRF Lead Report_WH-14_ p.3
Discussion
The field testing of the coatings associated with the interior of the DLASJ Tracy, Warehouse 14, did identify Lead concentrations that are described in Table 1 of this report. Laboratory analysis of the bulk samples taken of the exterior coatings of Warehouse 14 reported that the coatings contained Lead, as described in Tables 2 and 3 of this report. The Federal OSHA 29 CFR 1926.62 and 29 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.
Recommendations
• Any activity that may include the disturbance of Lead-containing materials must be performed within the regulations set forth in Federal OSHA 29 CFR 1926.62, 29 CFR
1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.
• Disposal of any building materials that are coated with Lead-containing paint must be disposed of per the requirements of the DS-FJ Installation Support Environmental Office.
Robert Miller, CIH Certified Industrial Hygienist
Lonny Jones
Industrial Hygiene Technician