Date: 07 June 2017 Subject: Field Analysis for Suspect Lead Paint Bulk Sample Collected from the DLASJ Tracy, Building 255
Evaluation On 07 June 2017, field testing for the presence of Lead was performed on the primary structural coatings (paints) identified on the surfaces of the building materials at the DLASJ, Tracy, Building 255. Robert Miller, a Certified Industrial Hygienist, performed the field sample analysis utilizing a handheld Innov-X Systems, Alpha Series, X-Ray Fluorescence (XRF) Spectrometer. Prior to this sampling event the calibration of the XRF instrument was verified by performing an analysis of a National Institute of Standards & Technology (NIST), Reference Material. The field testing data for Building 255 is provided in Table 1 of this report.
Table 1
Sample Number
Material Description Lead Concentration
0607-255-01 White coating on the breakroom walls Non-detect (ND) 0607-255-02 Dark yellow paint on the wood wall inside the east section by south overhead door
1.68 mg/cm2
0607-255-03 Factory applied gray coating on the corrugated metal on the exterior of the structure
ND
0607-255-04 Fire red coatings applied to the floors >5.0 mg/cm2 0607-255-05 Fire red coating on the fire sprinkler risers 2.90 mg/cm2 0607-255-06 Fire red coating on wood columns 4.95 mg/cm2 0607-255-07 Safety Yellow coating on columns >5.0 mg/cm2 0607-255-08 Gray coating applied to the concrete floors located in the east warehouse section
ND
0607-255-09 Bright white coating on wood columns throughout the two sections of the structure
>5.0 mg/cm2
0607-255-10 White coating on the concrete floor inside the east warehouse section
ND
0607-255-11 and 0607-255-12
Yellow coating identified underneath the gray and white surface coatings located throughout the west warehouse section
>5.0 mg/cm2
0607-255-13 White coating on the drywall walls located inside the west warehouse section
ND
0607-255-14 Light blue coating on the drywall walls inside the Production Control Office
ND
Lead-Based Paint Report, Building 255 Page 2 08 June 2017
Discussion The field testing of the coatings associated with the DLASJ Tracy, Building 255, did identify Lead concentrations that are described in Table 1 of this report. The Federal OSHA 29 CFR 1926.62 and 29 CFR 1910.1025 Standards and California OSHA 8CCR 1532.1, and Title 17 CCR Standards regulate exposures to materials with any detectable amount of Lead.
Recommendations
• Any activity that may include the disturbance of Lead containing materials must be performed within the regulations set forth in Federal OSHA 29 CFR 1926.62, 29 CFR 1910.1025 and California OSHA 8CCR 1532.1, and Title 17 CCR Standards.
• Disposal of any building materials that are coated with lead containing paint must be disposed of per the requirements of the DS-FJ Installation Support Environmental Office.
Robert Miller, CIH Certified Industrial Hygienist