MIL-STD-1548G
31 July 2009
NOT MEASUREMENT
SENSITIVE
SUPERSEDING
MIL-STD-1548F
19 August 2005
DEPARTMENT OF DEFENSE
STANDARD PRACTICE
INTO - PLANE SERVICING OF FUELS
AT COMMERCIAL AIRPORTS
AMSC N/A FSC 91GP
DISTRIBUTION STATEMENT A. Approved for public release; distribution is unlimited.
FORWARD
1. This standard is approved for use by all Departments and Agencies of the Department of Defense
(DOD).
2. Comments, suggestions, or questions on this document should be addressed to HQ AFPET/PTOT, 2430 C Street, Bldg 70, Area B, Wright-Patterson AFB, OH 45433-7632 or e-mailed to AFPET.AFTH@wpafb.af.mil. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at http://assist.daps.dla.mil.
ii mailto:AFPET.AFTH@wpafb.af.mil http://assist.daps.dla.mil/
CONTENTS
PARAGRAPH PAGE
FOREWARD ................................................................................................................................ ii
1 SCOPE
1.1 Scope
1.2 Classification
2 APPLICABLE DOCUMENTS
2.1 General
2.2 Government documents
2.2.1 Specifications, standards, and handbooks
2.3 Non-Government publications
2.4 Order of precedence
3 DEFINITIONS
3.1 Definitions applicable to this standard
3.2 Full flow monitor cartridges
4 GENERAL REQUIREMENTS
4.1 Type I and Type II
4.1.1 Defueled product
4.1.1.1 Defueled JP-8+100 product
4.1.2 Safety
5 DETAILED REQUIREMENTS
5.1 Type I
5.1.1 Jet fuel specification and purity standards
5.1.1.1 Additive injection
5.1.2 Hydrant system checks
5.1.3 Aircraft fueling equipment requirements
5.1.3.1 Electrostatic bonding
5.1.3.1.1 Grounding plug
5.1.3.1.2 Grounding clamp
5.1.3.2 Aircraft pressure refueling nozzle
5.2 Type II
5.2.1 Jet fuel specifications
5.2.1.1 Additive injection
5.2.2 Maintenance and testing of fueling equipment
5.2.2.1 Bonding wires
5.2.2.2 Storage tanks
5.2.3 Fueling operations
5.2.3.1 Electrostatic bonding
5.2.3.1.1 Grounding plug
5.2.3.1.2 Grounding clamp
5.2.3.2 Aircraft pressure refueling nozzle
5.2.4 Filtration equipment
5.2.4.1 Filtration requirements
6 NOTES
6.1 Intended use
6.2 Acquisition requirements
6.3 Publications
6.4 Subject term (key word) listing
iii iv
CONTENTS
PARAGRAPH PAGE
6.5 Quality assurance requirements
6.6 Changes from previous issue
TABLE
I Defueled product quality criteria II Laboratories within the continental United States III Laboratories outside the continental United States
CONCLUDING MATERIAL
1. SCOPE
1.1 Scope. This standard establishes two types of standard practices for into-plane servicing of fuels at commercial airports.
1.2 Classification. Classification of into-plane servicing is as follows:
Type I Into-Plane Refueling Guidance per ATA Specification 103, Standard For Jet Fuel Quality Control at Airports.
Type II Into-Plane Refueling Guidance as per IATA's Guidelines for Aviation Fuel Quality Control and Operating Procedures for Joint Into-Plane Fueling Services
(JIG 1).
2. APPLICABLE DOCUMENTS
2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this standard. This section does not include documents cited in other sections of this standard or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this standard, whether or not they are listed.
2.2 Government documents.
2.2.1 Specifications, standards, and handbooks. The following specifications, standards and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract.
DEPARTMENT OF DEFENSE SPECIFICATIONS
MIL-DTL-83413/4 Connectors and Assemblies, Electrical, Aircraft Grounding, Plugs, for Types I and II Grounding Assemblies.
MIL-DTL-83413/7 Connectors and Assemblies, Electrical, Aircraft Grounding:
Grounding Clamp Connector for Types I and III Grounding Assemblies, Clip, Electrical
MIL-PRF-52308 Filter-Coalescer Element, Fluid Pressure
(Copies of these documents are available online at http://assist.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Bldg 4D, Philadelphia, PA 19111-5094.)
2.3 Non-government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract.
AIR TRANSPORT ASSOCIATION (ATA)
ATA Specification 103 Standards for Jet Fuel Quality Control at Airports
(Copies of these documents are available online at http://www.air-transport.org or from the Air Transport Association of America, 1301 Pennsylvania Ave. NW, Suite 1100, Washington, DC 20004.)
AMERICAN PETROLEUM INSTITUTE/ENERGY INSTITUTE (API/EI)
API/EI Specification 1581 Specifications and Qualification Procedures for Aviation Jet Fuel Filter/Separator (API/EI 1581)
API/EI Specification 1590 Specifications and Qualification Procedures for Aviation Fuel Microfilters (API/EI 1590) http://www.air-transport.org/
(Copies of these documents are available online at http://www.api.org or from the American Petroleum Institute, 1220 L Street, Northwest Washington DC, 20005-4070.)
ENERGY INSTITUTE (EI)
EI Specification 1583 Specifications and Qualification Procedures for Aviation Fuel Filter Monitors With Absorbent Type Elements (EI 1583)
(Copies of these documents are available online at http://www.energyinst.org.uk/ or from Energy Institute 61 New Cavendish Street, London, W1G 7AR.)
ASTM INTERNATIONAL
ASTM D56 Standard Test Method for Flash Point by Tag Closed Cup Tester (DoD Adopted)
ASTM D93 Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester (DoD Adopted)
ASTM D1298 Standard Test Method for Density, Relative Density (Specific Gravity), or API Gravity of Crude Petroleum and Liquid Petroleum Products by Hydrometer Method (DoD Adopted)
ASTM D1655 Standard Specification for Aviation Turbine Fuels (DoD Adopted)
ASTM D2276 Standard Test Method for Particulate Contaminant in Aviation Fuel by Line Sampling
ASTM D2624 Standard Test Methods for Electrical Conductivity of Aviation and Distillate Fuels (DoD Adopted)
ASTM D3241 Standard Test Method for Thermal Oxidation Stability of Aviation Turbine Fuels (JFTOT Procedure) (DoD Adopted)
ASTM D3828 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester (DoD Adopted)
ASTM D4052 Standard Test Method for Density and Relative Density of Liquids by Digital Density Meter (DoD Adopted)
ASTM D5452 Standard Test Method for Particulate Contamination in Aviation Fuels by Laboratory Filtration (DoD Adopted)
(Copies of these documents are available online at http://www.astm.org or the ASTM International, 100 Barr Harbor Drive, West Conshohocken PA 19428-2959.)
INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA)
IATA (JIG 1) Guidelines for Aviation Fuel Quality Control and Operating Procedures for Joint Into-Plane Fueling Services (JIG 1).
(Copies of these documents are available online at http://www.iata.org or from the International Air Transport Association Customer Svc, 800 Place Victoria, P.O. Box 113, Montreal Quebec, H4Z 1M1, Canada.)
NATIONAL FIRE PROTECTION ASSOCIATION
NFPA 407 Aircraft Fuel Servicing (DoD Adopted)
(Copies of these documents are available online http://www.nfpa.org or from the National Fire Protection Association, 1 Batterymarch Park, PO Box 9101, Quincy, MA 02269-9101.)
http://www.api.org/ http://www.energyinst.org.uk/ http://www.astm.org/ http://www.iata.org/ http://www.nfpa.org/
SAE INTERNATIONAL
SAE AS5877 Detailed Specification for Aircraft Pressure Refueling Nozzle (DoD Adopted)
(Copies of these documents are available online at http://www.sae.org or from SAE International, 400 Commonwealth Dr., Warrendale, PA USA 15096-0001.)
2.4 Order of precedence. Unless otherwise noted herein or in the contract, in the event of a conflict between the text of this document and the references cited herein (except for related specification sheets), the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained.
3. DEFINITIONS
3.1 Definitions applicable in this standard. The definitions for terms used in this standard are in accordance with ATA Specification 103 and the IATA Joint Into-plane Guidelines (JIG 1), with the following additional terms noted herein.
3.2 Full flow monitor cartridges. Fuse-type or fuel monitor elements, which remove free water and solid contaminants in the fuel. As the elements retain solids and water through absorption, fuel flow is restricted or shutoff.
4. GENERAL REQUIREMENTS
4.1 Type I and Type II. Receipt, storage, and issue of aviation products shall comply with ATA Specification 103 or IATA Joint Into-plane Guidelines (JIG 1) respectfully, except as noted herein.
4.1.1 Defueled product. Defueled product from other than U.S. Government aircraft shall not be used to refuel U.S. Government aircraft. Product defueled from U.S. Government aircraft may be returned to an authorized user and shall meet the defueled product quality criteria in Table I.
TABLE I. Defueled product quality criteria.
Property Requirement Test Method
Density at 15 °C (or API Gravity) Particulate contamination
(1) Particulate content before filtration, or:
(2) Particulate content after filtration into plane, or:
(3) Color rating Conductivity Without conductivity additive With conductivity additive
Water content (into plane) Appearance Flash point 1
0.775-0.840 kg/L (37-51)
1.0 mg/L, max
0.5 mg/L, max
A1,A2,B1,B2,G1, or G2
10 pS/m, max 50-700 pS/m
15 ppmv, max Clear and Bright 38 °C (100 °F), min
ASTM D1298 or D4052
ASTM D5452
ASTM D5452
ASTM D2276
ASTM D2624
ASTM D2624
See JIG 1 or ATA 103 Visual ASTM D56, D93, or D3828
Notes:
1. ASTM D56 may give results up to 1°C (2°F) below the ASTM D93 results. ASTM D3828 may give results up to 1.7°C (3°F) below the ASTM D93 results.
http://www.sae.org/
4.1.1.1 Defueled JP8+100 product. Aircraft containing JP-8+100 shall not be defueled unless an imminent emergency exists. The aircraft home station, applicable military Service Control Point (SCP), or Major Command shall be contacted regarding disposition instructions. JP-8+100 product can only be returned to the aircraft from which it was defueled.
4.1.2 Safety. Safety requirements as specified in NFPA 407 shall apply to Type I.
5 DETAILED REQUIREMENTS
5.1 Type I. Type I refueling at commercial airports shall be performed as specified in ATA Specification 103, except as noted herein.
5.1.1 Jet fuel specification and purity standards. The requirements of ATA Specification 103 shall apply except for the following.
5.1.1.1 Additive injection. There may be a requirement to add additives to the fuel. The additives are Fuel System Icing Inhibitor (FSII) or Static Dissipator Additive (SDA). The only authorized FSII for Department of Defense aircraft is diethylene glycol monomethyl ether. The following additive blending guidance is provided in order to assure proportional injection of the additives. The two basic methods for adding additives into fuel are manual blending and use of an injector.
a. The preferred method is proportional injection using a fuel driven design injector. This type injects additives proportionately at various flow rates.
b. Manually blending additives at various points in the system can be accomplished by several techniques, some of which are described below. When manual blending is performed, additive should first be diluted with the fuel. The greater the dilution, the easier it is for the additive to mix properly.
Fuel additives should not be mixed together in neat form as a cocktail blend for injecting into fuel.
1. Blending additives into bulk airfield tanks can be done by pouring the required quantity of additive into the tank heel followed by a receipt. Care should be taken when manually introducing additive to tank heels to avoid over/under additizing resulting from variations in anticipated
vs. actual quantities received. The required quantity of additive may also be added to the delivery tank trucks just prior to offloading into bulk tanks.
2. Blending into refueling units can be performed by introducing the required amount through the top hatch using a funnel and a length of hose with one end submerged below the surface of the fuel. This can best be accomplished by pouring the additive into the refueler, filled to not more than one-third of its capacity and then filling the unit with fuel. Wait approximately 10 minutes and then circulate fuel for at least three minutes before servicing to aircraft. If additives are put into a full refueler, circulate at least 150 percent of the refueler capacity prior to issue.
c. When required, fuel system icing inhibitor (FSII) may be added using the 590 mL (20 ounce) aerosol can during over-wing refueling. Determine the fuel load and calculate the amount of additive required. It should be added gradually during filling to permit proper blending in the fuel. One can of aerosol additive will inhibit 680 liters (180 gallons) of fuel to 0.087% by volume.
d. When FSII and/or static dissipator additive (SDA) is injected into fuel the following concentration levels apply: Fuel injected with FSII shall contain 0.07 – 0.20 vol. % FSII content; if the fuel is injected with SDA, the SDA content shall be between 50 and 700 conductivity units (CU).
5.1.2 Hydrant system checks. The requirements of ATA Specification 103 shall apply, except that for any modifications, changes, or construction work to hydrant systems, the contractor shall also notify the contracting officer.
5.1.3 Aircraft fueling equipment requirements. The requirements of ATA Specification 103 shall apply, except for electrostatic bonding, the following specific equipment shall be required.
5.1.3.1 Electrostatic Bonding.
5.1.3.1.1 Grounding plug. When the aircraft being serviced is equipped with grounding receptacles, a grounding plug conforming to or equivalent in design to MIL-DTL-83413/4 shall be used.
5.1.3.1.2 Grounding clamp. When the aircraft being serviced is not equipped with grounding receptacles or a plug is not available, a grounding clamp conforming to or equivalent in design to MIL- DTL-83413/7 shall be used on the bonding cables of the refueling equipment. When a grounding clamp is used, it shall be connected to a bare metal surface of the aircraft. Do not secure/attach to external doors, latches or hinges.
5.1.3.2 Aircraft Pressure Refueling Nozzle. Aircraft pressure refueling nozzles shall meet the requirements of SAE AS5877.
5.2 Type II. Type II Refueling at Commercial Airports shall be performed as specified in the IATA Joint Into-plane Guidelines (JIG 1), except as noted herein.
5.2.1 Jet fuel specifications. The IATA guide specification, ASTM D1655, or applicable specification cited in the contract, shall be used with the following additional requirements.
5.2.1.1 Additive injection. When additives are required, see paragraph 5.1.1.1.
5.2.2 Maintenance and testing of fueling equipment. The requirements in the IATA Joint Into-plane Guidelines (JIG 1) apply with the following exceptions.
5.2.2.1 Bonding wires. When testing for continuity, use either of the following methods.
a. Continuity tester N22T (Ray-O-Vac) or equivalent.
b. Simpson Model 260, Volt ohm Meter or equivalent. When using this type test equipment the resistance shall be 25 ohms or less.
5.2.2.2 Storage tanks. Storage tanks shall be inspected and cleaned as necessary whenever tank samples show a continuous solids build-up or when filtration elements on the downstream side of tanks show evidence of premature plugging from excessive solids.
5.2.3 Fueling operations. The requirements of the IATA Joint Into-plane Guidelines (JIG 1) apply in their entirety with exceptions noted herein.
5.2.3.1 Electrostatic Bonding.
5.2.3.1.1 Grounding plug. When the aircraft being serviced is equipped with a grounding receptacle, a grounding plug conforming to or equivalent in design to MIL-DTL-83413/4 shall be used.
5.2.3.1.2 Grounding clamp. When the aircraft being serviced is not equipped with grounding receptacles or a plug is not available, a grounding clamp conforming to or equivalent in design to MIL- DTL-83413/7 shall be used on the bonding cables of the refueling equipment. When a grounding clamp is used, it shall be connected to a bare metal surface of the aircraft. Do not secure/attach to external doors, latches or hinges.
5.2.3.2 Aircraft Pressure Refueling Nozzle. Aircraft pressure refueling nozzles shall meet the requirements of SAE AS5877.
5.2.4 Filtration equipment. The filtration equipment requirements in the IATA Joint Into-plane Guidelines (JIG 1) apply in their entirety with exceptions noted.
5.2.4.1 Filtration requirements. All aviation fuel shall pass through two filters. One filter shall be at the inlet to the operating tank and one filter shall be on the fueler-loading rack or hydrant delivery lines. The initial filter must be a filter separator. The final filtration of jet fuel shall be through a filter separator or a full flow monitor. One of the two filters used for aviation gasoline shall be a filter separator or fuel monitor. The filter separator referred to for both products shall meet the requirement of API/EI 1581 or MIL-PRF-52308. The full-flow monitor shall meet the requirements of EI1583. The micronic filter shall meet the requirement of API /EI1590. Filtration equipment shall be designed so that fuel bypass is not possible.
6. NOTES
(This section contains information of a general or explanatory nature that may be helpful, but is not mandatory.)
6.1 Intended use. The purpose of this standard is to ensure government aircraft are provided specification fuel at commercial facilities where a US Government Into-Plane Servicing Contract is in force. The JP-8+100 defueling procedures covered by this standard are unique as only DoD aircraft use JP-8+100. Defueling of JP-8+100 at commercial airports must only be accomplished under emergency situations after coordination with the aircraft's home station, military Service Control Point, of Major Air Command and must be handled appropriately to avoid contaminating systems not capable of handling the JP-8+100. Additive injection procedures mentioned in this standard are also military unique as the additive package required in fuel used by DoD aircraft is not used in commercial fuels -the additive package required in fuel destined for DoD aircraft is required as it provides additional safeguards against fuel system icing and fuel system static charges.
6.2 Acquisition requirements. Acquisition documents should specify the title, number, and date of this standard.
6.3 Publications. The JIG 1 publication referred to in Type II of the detailed requirements is available through two sources. It is prepared by and for members of the Joint Inspection Group, participants of the JIG can obtain the document through corporate channels. The JIG guidance referred to in Type II has also been written into the International Air Transport Association (IATA) Joint Into-Plane Guidance Material for Aviation Turbine Fuels Quality Control and Operating Procedures, 1st Edition. It is identical to the JIG used by JIG participants. The 1st Edition of the IATA publication can be procured from IATA Customer Svc, 800 Place Victoria, P.O. Box 113, Montreal Quebec, Canada, H4Z 1M1, Fax (514) 874-9659.
6.4 Subject term (key word) listing.
Aviation Gasoline JP8+100 product Defueled product Aircraft pressure refueling nozzle
6.5 Quality assurance requirements. Quality assurance requirements imposed as part of any contract may include sample submission to one of the laboratories listed in Table II or Table III of this standard.
TABLE II. Laboratories within the continental United States.
Mailing Address
Shipping Address
Telephone Numbers
FAX
Numbers
Area of Responsibility
HQ AFPET/PTPLA
Bldg 70, STE 01 2430 C St, Area B
WPAFB OH 45433-7632
HQ AFPET/PTPLA
Bldg 70, STE 01 2430 C St, Area B
WPAFB OH 45433-
DSN
785-0739
COM
(937) 255-0739
DSN
986-7744
COM
(937)656-7744
AL, AR, CT, DC,
DE, FL, GA, IA,
IL, IN, KS, KY,
LA, MA, MD, ME,
MI, MN, MO, MS,
NC, NE, NH, NJ,
NY, OH, OK, PA,
RI, SC, SD, TN,
TX, VA, VT, WI,
WV
HQ AFPET/PTPLE
1747 Utah Ave, Bldg Vandenberg AFB CA 93437-5220
HQ AFPET/PTPLE
1747 Utah Ave, Bldg Vandenberg AFB CA 93437-5220
DSN
276-6263
COM
(805) 606-6263
DSN
276-2756
COM
(805) 606-
AZ, CA, CO, ID,
MT, ND, NM, NV,
OR, UT, WA, &
WY
Army Petroleum Center
ATTN: AMSTA-LC-CJPT
U Avenue, Bldg 85-3 New Cumberland, PA 17070-5005
Army Petroleum Center
ATTN: AMSTA-LC
-CJPT
U Avenue, Bldg 85-3 New Cumberland, PA 17070-5005
DSN
771-6511
COM
(717) 770-6511
771-4743
COM
(717) 770-
All States
6.6 Changes from previous issue. The margins of this standard are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoever for any inaccuracies in these notations. Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue.
TABLE III. Laboratories outside the continental United States.
Mailing Address
Local Shipping Address Telephone Numbers
Fax Numbers
HQ AFPET/PTPLF
Unit 5025 Box 495
APO AE 09459-5025
HQ AFPET/PTPLF
RAF Mildenhall, Bldg 725 Bury ST Edmunds Suffolk, England IP28 8NF
DSN
314-238-2043
COM
44-1-638-542043
DSN
314-238-3626
COM
44-1-638- 543626
HQ AFPET/PTPLG
Unit 5161
APO AP 96368-5161
HQ AFPET/PTPLG
Bldg 854 Kadena, AB Okinawa, Japan 96368-5161
DSN
315-634-3394/1602
COM
611-734-3394
DSN
315-634-0584
505th QM Battalion
APAJ-GO-QL
Unit 35130
APO AP 96376-5130
505th QM Bn Petrol Lab Attn: APAJ-GO-QL Unit 35130 Kadena AFB, Okinawa
DSN
315-632-4058
COM
81-6117-324058
DSN
315-634-1376
COM
81-6117- 34137693043
Code 704, FISC Yokosuka Hakozaki Fuel Department PSC 473, Box 11
FPO AP 96349-0011
FISC Tsurumi Hakozaki Laboratory
PSC 471
FPO AP 9634 7-2000
DSN
244-2733
COM
81-311-734-2733
COM
81-311-734-
FISC Pearl Harbor POL Lab Code 704 1942 Gaffney St, Suite 100 Pearl Harbor HI 96860-4549
FISC Pearl Harbor POL Laboratory 300 Neches Avenue Bldg 1685, Code 704 Pearl Harbor, HI 96860
DSN
315-473-7989
COM
(808) 473-7989
DSN
315-473-7981
COM
(808) 473-17981
FISC Yokosuka, Fuel Department Sasebo Fuel Division Laboratory Branch Code 702.3, PSC 476, Box 6
FPO AP 96322-1504
FISC Yokosuka DetSasebo POL Laboratory PSC 476, Box 7
FPO AP 96322-1504
DSN
315-252-4134
COM
81-956-24-6111 Ext 4134
DSN
252-4139
COM
81-956-24-0968 Ext 4137
DEO-A
Attn: Laboratory 6-920 12th Street Elmendorf AFB AK 99506
Fuels Laboratory Bldg 986 Ft Richardson AK 99505
DSN
317-384-7180
COM
(907) 384-7180
DSN
317-384-2447
COM
(907) 384-2447
DESC Europe Petroleum Laboratory
CMR 422
APO AE 09067
DLA/DESC
Europe Pet Lab Rhein Ordnance Barracks Bldg 320 AM Opelkreisel 67663 Kaiserslautern, Germany
DSN
314-493-2286/4/8
COM
49-631-3406-2286/4/8
DSN
314-493-2289
COM
49-631-3406-
379th ELRS/AFPET
HQ AFPET/PTPLI
\APO AE 09309
QATAR
379th ELRS/AFPET
HQ AFPET/PTPLI
APO AE 09309
QATAR
318-437-2696
CONCLUDING MATERIAL
Custodians: Preparing activity:
Army – AV Air Force – 68 Navy – AS (Project 91GP-2008-002) Air Force – 68
DLA – PS
Review activities:
Army – CD Navy – SA
DLA – CC
Note: The activities listed above were interested in this document as of the date of this document.
Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at http://assist.daps.dla.mil .
| TABLE II. Laboratories within the continental United States. |
| TABLE III. Laboratories outside the continental United States. |
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 2_3_East_Amd_11__SF30__Solicit_BALT.pdf | ||
| 2_3_East_Amendment_10.pdf | ||
| 2_3_East_Amd_9__SF30__Solicit_KTTN-NJ_Combined_Pages.pdf | ||
| 2_3_East_Amd_8__SF30__Solicit_KMAI-FL.pdf | ||
| 2.3_East_Amendment_0007.pdf | ||
| SP060012R0238_2.3_East_Amendment_0006.pdf | ||
| 2.3_East_Amendment_0005.pdf | ||
| 2.3_East_Amendment_0004.pdf | ||
| 2.3_East_Amendment_0003.pdf | ||
| 2.3_East_Amendment_0002.pdf | ||
| 2.3_East_Amendment_0001.pdf | ||
| 23E Schedule of Supplies.pdf | ||
| 2 3 East OSP.pdf | ||
| 2 3 East Solicitation.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .