This document is an attachment to the solicitation for the EHRM Infrastructure Upgrades West Campus - North Chicago Construction project. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking construction services to upgrade infrastructure at the West Campus of the VA Medical Center in North Chicago, Illinois. Solicitation number 36C77623B0019 has a response due date that is not specified. The attachment appears to include combined drawings for the construction project but does not provide further details on requirements, pricing, terms, or evaluation criteria.
View the file
Other files for this federal contract opportunity
Show all 50
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P
A
ED
HAZARD CLASSIFICATION LEGEND
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGHTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
FIRE SUPPRESSION GENERAL NOTES:
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
FX409
A104-134
TR
A104-134
B116-134
TE ROOM
B116-134
FX409
FX409
FX409
A206-134
TR
A206-134
B216-134
TR
B216-134
FX409
A305-134
TR
A305-134
B318-134
TR
B318-134
FX409
FX410
K1-138
TR
K1-138
FX410
03-140
TR
03-140
FX410
102-188
TR
102-188
A02-135
IT ROOM
A02-135
A29A-135
TR
A29A-135
FX409
FX409
108-135
TR
108-135
142A-135
TR
142A-135
FX409
FX409
242A-135
TR
242A-135
208-135
TR
208-135
FX409
FX409
06-187
IRM RACK
ROOM
06-18707-187
UTILITY
07-187
FX410
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :2
P
M
OVERALL FIRE SUPPRESSION PLANS
SAB 101 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX106
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1" = 40'-0"
B134 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN1
N
1" = 40'-0"
B134 - LEVEL TWO - OVERALL FIRE SUPPRESSION PLAN2
N
1" = 40'-0"
B134 - LEVEL THREE - OVERALL FIRE SUPPRESSION PLAN3
N
1" = 40'-0"
B138 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN7
N
1" = 40'-0"
B140 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN8
N
1" = 40'-0"
B188 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN10
N
1" = 40'-0"
B135 - BASEMENT - OVERALL FIRE SUPPRESSION PLAN4
N
1" = 40'-0"
B135 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN5
N
1" = 40'-0"
B135 - LEVEL TWO - OVERALL FIRE SUPPRESSION PLAN6
N
1" = 40'-0"
B187 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN9
No. REVISION DESCRIPTION DATE
UP
RAMP
UP
UP
DW
C O U R T Y A R D
D W
D
W
S T R I P E D
B I C Y C L E
P A R K I N G
DW
C O U R T Y A R D
P A T I O
S T
R
IP
E D
B
IC
Y C
L E
P A
R K
IN
G
HAZARD CLASSIFICATION LEGEND
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGHTH EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
FIRE SUPPRESSION GENERAL NOTES:
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
FX410
FX410
114-195
TR
114-195
122-195
TR
122-195
FX410
128-201
TR
128-201
FX410
128-202
TR
128-202
FX410
132-205
TR
132-205
FX410
132-206
TR
132-206 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :2
P
M
OVERALL FIRE SUPPRESSION PLANS
SAB 102 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX107
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1" = 40'-0"
B195 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN1
N
1" = 40'-0"
B201 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN2
N
1" = 40'-0"
B202 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN3
N
1" = 40'-0"
B205 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN4
N
1" = 40'-0"
B206 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN5
100A-1
STORAGE
100A-1 100-1
TR
100-1
201-1
TR
201-1 1 300-1
TR
300-1 2
102-3
TR
102-3
202-3
TR
202-3
111-4
TR
111-4
185-4
TR
185-4 1
208-4
TR
208-4
209-4
STORAGE
209-4
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :3
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 103 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX401
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B1 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1001
N
1/4" = 1'-0"
B1 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2012
N
1/4" = 1'-0"
B1 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3003
N
1/4" = 1'-0"
B3 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1024
N
1/4" = 1'-0"
B3 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2025
N
1/4" = 1'-0"
B4 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1116
N
1/4" = 1'-0"
B4 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1857
N
1/4" = 1'-0"
B4 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2098
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
SPRINKLERS.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE
BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER
SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA
IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT
REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.
THE SPACE WILL REMAIN UNSPRINKLERED.
120-6
TR
120-6 1
130-6
TR
130-6
130B-6
MECHANICAL
130B-6
130B-7
TR
130B-7
130A-7
STORAGE
130A-7
227B-7
TR
227B-7
227A-7
STORAGE
227A-7
103-9
IT ROOM
103-9
210A-9
TR
210A-9
105-11
TR
105-11
25-32
TR
5-32 2
10-36
PAINT
STORAGE
10-36
106-7
TR
106-7
148-7
TR
148-7
233B-7
TR
233B-7
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :4
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 104 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX402
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B6 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1201
N
1/4" = 1'-0"
B6 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1302
N
1/4" = 1'-0"
B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 130B3
N
1/4" = 1'-0"
B7 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 227B7
N
1/4" = 1'-0"
B9 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1038
N
1/4" = 1'-0"
B9 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2109
N
1/4" = 1'-0"
B11 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 10510
N
1/4" = 1'-0"
B32 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 511
N
1/4" = 1'-0"
B36 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1012
N
1/4" = 1'-0"
B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1064
N
1/4" = 1'-0"
B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1485
N
1/4" = 1'-0"
B7 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 233B6
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
SPRINKLERS.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE
BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER
SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA
IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT
REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.
5A-37
BREAKROOM
5A-37
114-46
TR
114-46
214-46
TR
214-46
9A-66
TR
9A-66
125-66
TR
125-66
226-66
TR
226-66
103-92
TE
103-92
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :4
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 105 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX403
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B37 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 51
N
1/4" = 1'-0"
B46 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1142
N
1/4" = 1'-0"
B46 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2143
N
1/4" = 1'-0"
B66 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - 9A4
N
1/4" = 1'-0"
B66 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1255
N
1/4" = 1'-0"
B66 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2266
N
1/4" = 1'-0"
B92 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1037
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
SPRINKLERS.
1H-131
1H-131 1
101B-131
TR
101B-131 1
207-131
TR
207-131 1
302-131
TR
302-131 1
402A-131
TR
402A-131
BC113-133
TR
BC113-133
BD129-133
TR
BD129-133
BD139-133
TR
BD139-133
BD105-133
TR
BD105-133
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :5
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 106 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX404
SPUR #: 2113
N
1/4" = 1'-0"
B131 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - 1H1
N
1/4" = 1'-0"
B131 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 101B2
N
1/4" = 1'-0"
B131 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2073
N
1/4" = 1'-0"
B131 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3024
N
1/4" = 1'-0"
B131 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 402A5
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BC1136
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1297
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1398
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1059
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
BA140-133
TR
BA140-133
BB101H-133
TELECOM
BB101H-133
BE215-133
TR
BE215-133 1
BF117-133
TR
BF117-133 1BF329-133
TR
BF329-133 1
BE405-133
TR
BE405-133
1A143-133
TR
1A143-133
1A120A-133
TR
1A120A-133 1
BA130B-133
TR
BA130B-133
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :0
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 107 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX405
SPUR #: 2113
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BA1401
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BB101H2
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BE2154
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BF1175
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BF3296
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BE4047
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E107A8
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1A120A9
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BA130B3
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
1B117A-133
1B117A-133
1D225-133
TR
1D225-133
11D226-133
TR
1D226-133
1D117-133
TR
1D117-133 1 1E226-133
TR
1E226-133 1
1E104-133
TR
1E104-133
1F347-133
TR
1F347-133 1 1F101F-133
TR
1F101F-133 11E344-133
TR
1E344-133 1
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :0
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 108 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX406
SPUR #: 2113
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1B117A1
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D2252
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D2263
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D1174
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E2265
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E1046
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1F3477
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1F101F8
N
1/4" = 1'-0"
B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E3449
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
2B117A-133
2B117A-133
2A106-133
TR
2A106-133
2D129-133
TR
2D129-133
2D146-133
TR
2D146-133 1
2D174-133
TR
2D174-133 1
2E224-133
TR
2E224-133 1
2F311-133
TR
2F311-133 1 2F123-133
TR
2F123-133 12E408-133
TR
2E408-133 1
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :1
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 109 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX407
SPUR #: 2113
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2B1171
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2A1062
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D129A3
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D1464
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D1745
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2E2246
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2F3117
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2F1238
N
1/4" = 1'-0"
B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2E4089
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
3A148-133
3A148-133
13D111-133
TR
3D111-133
3D126-133
TR
3D126-133
3D100-133
TR
3D100-133 13F119-133
TR
3F119-133
3F323-133
TR
3F323-133
4A115-133
TR
4A115-133
4B117-133
TR
4B117-133
3B123-133
TR
3B123-133
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :2
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 110 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX408
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3A1471
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D111A2
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D126A4
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D1005
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3F1196
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3F3237
N
1/4" = 1'-0"
B133 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 4A1139
N
1/4" = 1'-0"
B133 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 4B11710
N
1/4" = 1'-0"
B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3B1233
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
A104-134
A104-134
A206-134
TR
A206-134
1B216-134
TR
B216-134
A305-134
TR
A305-134
B116-134
TE ROOM
B116-134
B318-134
TR
B318-134
A02-135
IT ROOM
A02-135
A29A-135
TR
A29A-135
108-135
TR
108-135
142A-135
TR
142A-135
208-135
TR
208-135
242A-135
TR
242A-135
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :3
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 111 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX409
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B134 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - A1041
N
1/4" = 1'-0"
B134 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - A2062
N
1/4" = 1'-0"
B134 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - B2164
N
1/4" = 1'-0"
B134 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - A3055
N
1/4" = 1'-0"
B134 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - B1163
N
1/4" = 1'-0"
B134 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - B3186
N
1/4" = 1'-0"
B135 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - A027
N
1/4" = 1'-0"
B135 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - A29A8
N
1/4" = 1'-0"
B135 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1089
N
1/4" = 1'-0"
B135 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 142A10
N
1/4" = 1'-0"
B135 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 20811
N
1/4" = 1'-0"
B135 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 242A12
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
122-195
122-195
114-195
TR
114-195 2
128-201
TR
128-201 1128-202
TR
128-202 1
132-205
TR
132-205 1 132-206
TR
132-2061
102-188
TR
102-188
06-187
IRM RACK
ROOM
06-18707-187
UTILITY
07-187
03-140
TR
03-140
02-140
DISPATCH
02-140
K1-138
TR
K1-138
HAZARD CLASSIFICATION LEGEND
OUT OF SCOPE AREA
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
RATED WALL LEGEND
AREA NOT IN CONTRACT
EXISTING WALLS TO REMAIN
NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.
EXISTING 2 HOUR FIRE WALL
EXISTING 1 HOUR FIRE WALL
EXISTING 30 MINUTE SMOKE BARRIER
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022
MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023
ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023
CIVIL ENGINEER
OLSSON
550 E. ST. LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING ST., SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
STRUCTURAL ENGINEER
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST., STE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.,
OLATHE, KANSAS 66062
(913) 829-8690
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
CONTROLLED UNCLASSIFIED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
C
U I)
/2
/2
:5 :3
P
M
ENLARGED FIRE SUPPRESSION PLANS
SAB 112 OF 348BLS
ISSUED FOR BID & CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES, WEST CAMPUS -
NORTH CHICAGO
12/08/2022
556-21-701
3001 GREEN BAY ROAD
NORTH CHICAGO, ILLINOIS 60064
FX410
SPUR #: 2113
4 69
KEY PLAN
G R
E E
N B
A Y
R O
A D
BUCKLEY ROAD
N
202 201
205206
N
1/4" = 1'-0"
B195 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1225
N
1/4" = 1'-0"
B195 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1146
N
1/4" = 1'-0"
B201 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1287
N
1/4" = 1'-0"
B202 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1288
N
1/4" = 1'-0"
B205 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1329
N
1/4" = 1'-0"
B206 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 13210
N
1/4" = 1'-0"
B188 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1024
N
1/4" = 1'-0"
B187 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 063
N
1/4" = 1'-0"
B140 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 032
N
1/4" = 1'-0"
B138 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - K11
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH QUICK-RESPONSE
SPRINKLERS.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE
BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER
SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA
IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT
REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.
ABBREVIATIONS
HVAC PIPING TYPES
GENERAL DUCT SYMBOLS
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
A
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
FSD COMBINATION FIRE / SMOKE DAMPER
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIONALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
H
HU HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPC HIGH PRESSURE STEAM CONDENSATE RETURN
HPS HIGH PRESSURE STEAM (61-300 PSIG)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HC HOT WATER HEATING COIL
HHP HEATING HOT WATER PUMP
HHR HEATING HOT WATER RETURN
HHS HEATING HOT WATER SUPPLY
HHUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPC LOW PRESSURE STEAM CONDENSATE RETURN
CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM (0-15 PSIG)
CLPS LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
M
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPC MEDIUM PRESSURE STEAM CONDENSATE
RETURN
MPS MEDIUM PRESSURE STEAM (16-60 PSIG)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OSD ORGANIC SOIL FILTER
Q
Q INTENTIONALLY LEFT BLANK
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
DSD DUCT SMOKE DETECTOR
SD SMOKE DAMPER
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
T
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
U
X INTENTIONALLY LEFT BLANK
W
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFM WATER FLOWMETER
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
X
V
GENERAL NOTES:
A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE
SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.
B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT
DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS
ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS
COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND
NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR
INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.
D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
E. PROVIDE VIBRATION ISOLATION AS RECOMMENDED BY THE MANUFACTURER FOR ALL
MOTORIZED…