S02 - ATTACHMENT 13 - Combined Drawings 3 of 6 - EHRM Upgrades Chicago.pdf

PDF 22 MB Posted

Attached to
EHRM Infrastructure Upgrades West Campus – North Chicago - Construction Federal contract opportunity
Solicitation number
36C77623B0019
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document is an attachment to the solicitation for the EHRM Infrastructure Upgrades West Campus - North Chicago Construction project. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking construction services to upgrade infrastructure at the West Campus of the VA Medical Center in North Chicago, Illinois. Solicitation number 36C77623B0019 has a response due date that is not specified. The attachment appears to include combined drawings for the construction project but does not provide further details on requirements, pricing, terms, or evaluation criteria.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades West Campus – North Chicago - Construction, newest first.
File Type Posted
36C77623B0019 0010 - EHRM N Chicago West - Conference Line_Wage Rates_52.204-27.pdf PDF
Updated Wage Rates - Lake County - 06.30.23.pdf PDF
36C77623B0019 0009 - Note and Site Visit 2 Sign In Sheet.pdf PDF
Site Visit 2 Sign-In Sheet - 556-21-701 EHRM West Campus.pdf PDF
S02 - 36C77623B0019 0008 - Extension and Additional Site Visit.pdf PDF
556-21-701 EHRM West PreBid RFIs 20JUN23.pdf PDF
Revised Drawing Sheet GS007 - Item 133.pdf PDF
36C77623B0019 0007 - EHRM North Chicago (West) - Revised RFI Responses.pdf PDF
36C77623B0019 0006 - EHRM North Chicago (West) - Technical Questions.pdf PDF
36C77623B0019 0005 - EHRM North Chicago (West) - Extension 6.26.23.pdf PDF
36C77623B0019 0004 - EHRM North Chicago (West) - Extension 3.16.23.pdf PDF
36C77623B0019 0003 - EHRM North Chicago (West) - Extension.pdf PDF
36C77623B0019 0003 - Updated Wage Rates - Lake County - 05.12.23.pdf PDF
36C77623B0019 0002 - Site Visit Sign-In Sheet - North Chicago (West).pdf PDF
West Campus Site Visit sign in sheet May 15 2023.pdf PDF
01 45 29 Testing Laboratory Services.pdf PDF
27 05 33 Raceways and Boxes for Communication Systems.pdf PDF
27 52 23 Nurse call.pdf PDF
36C77623B0019 0001 - EHRM North Chicago (West) - Addendum 01.pdf PDF
Addendum 001.pdf PDF
00 01 10- Table of Contents.pdf PDF
01 35 26 Safety Requirements.pdf PDF
01 35 33 Infection Control Requirements.pdf PDF
26 05 33 Raceway and Boxes for Electrical Systems.pdf PDF
27 51 16 Public Address and Mass Notification.pdf PDF
01 00 00 General Requirements.pdf PDF
01 33 23 Shop Drawings Product Data and Samples.pdf PDF
01 91 00 General Commissioning Requirements.pdf PDF
S02 - ATTACHMENT 3 - EHRM North Chicago-100 Cost Narrative.pdf PDF
S02 - ATTACHMENT 18 - Limitations on Subcontracting - Jan 2023.pdf PDF
S02 - ATTACHMENT 19 - Contractor Safety - Environmental Form.pdf PDF
S02 - ATTACHMENT 20 - Wage Rates - Lake County - 01.20.23.pdf PDF
S02 - ATTACHMENT 4 - Environmental Comb - EHRM Upgrades Chicago.pdf PDF
S02 - SOLICITATION - 36C77623B0019_1 North Chicago EHRM (West Campus).pdf PDF
S02 - ATTACHMENT 1 - 556-21-701 Bid Specifications - Final.pdf PDF
S02 - ATTACHMENT 2 - Chicago EHRM - Design Narratives.pdf PDF
S02 - ATTACHMENT 6 - Safety Requirements.pdf PDF
S02 - ATTACHMENT 11 - Combined Drawings 1 of 6 - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 14 - Combined Drawings 4 of 6 - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 17 - Brand Name Justification - Redacted.pdf PDF
S02 - ATTACHMENT 5 - 01 35 33 Infection Control Requirements FHCC 15NOV22.pdf PDF
S02 - ATTACHMENT 8 - Mechanical Calculations - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 16 - Combined Drawings 6 of 6 - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 22 - Illinois Tax Memo - 1.26.2023.pdf PDF
S02 - ATTACHMENT 7 - Mechanical Equipment - EHRM Upgrade Chicago.pdf PDF
S02 - ATTACHMENT 9 - ICRA Form - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 10 - 556-21-701 EHRM West Const SOW 20 DEC22.pdf PDF
S02 - ATTACHMENT 12 - Combined Drawings 2 of 6 - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 15 - Combined Drawings 5 of 6 - EHRM Upgrades Chicago.pdf PDF
S02 - ATTACHMENT 21 - Site Visit Instructions.pdf PDF
Show all 50

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P

A

ED

HAZARD CLASSIFICATION LEGEND

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGHTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

FIRE SUPPRESSION GENERAL NOTES:

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

FX409

A104-134

TR

A104-134

B116-134

TE ROOM

B116-134

FX409

FX409

FX409

A206-134

TR

A206-134

B216-134

TR

B216-134

FX409

A305-134

TR

A305-134

B318-134

TR

B318-134

FX409

FX410

K1-138

TR

K1-138

FX410

03-140

TR

03-140

FX410

102-188

TR

102-188

A02-135

IT ROOM

A02-135

A29A-135

TR

A29A-135

FX409

FX409

108-135

TR

108-135

142A-135

TR

142A-135

FX409

FX409

242A-135

TR

242A-135

208-135

TR

208-135

FX409

FX409

06-187

IRM RACK

ROOM

06-18707-187

UTILITY

07-187

FX410

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :2

P

M

OVERALL FIRE SUPPRESSION PLANS

SAB 101 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX106

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1" = 40'-0"

B134 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN1

N

1" = 40'-0"

B134 - LEVEL TWO - OVERALL FIRE SUPPRESSION PLAN2

N

1" = 40'-0"

B134 - LEVEL THREE - OVERALL FIRE SUPPRESSION PLAN3

N

1" = 40'-0"

B138 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN7

N

1" = 40'-0"

B140 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN8

N

1" = 40'-0"

B188 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN10

N

1" = 40'-0"

B135 - BASEMENT - OVERALL FIRE SUPPRESSION PLAN4

N

1" = 40'-0"

B135 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN5

N

1" = 40'-0"

B135 - LEVEL TWO - OVERALL FIRE SUPPRESSION PLAN6

N

1" = 40'-0"

B187 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN9

No. REVISION DESCRIPTION DATE

UP

RAMP

UP

UP

DW

C O U R T Y A R D

D W

D

W

S T R I P E D

B I C Y C L E

P A R K I N G

DW

C O U R T Y A R D

P A T I O

S T

R

IP

E D

B

IC

Y C

L E

P A

R K

IN

G

HAZARD CLASSIFICATION LEGEND

1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE

SYSTEM SHALL BE DESIGNED AND INSTALLED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL - EIGHTH EDITION AND NFPA 13-2022.

2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO

BE INSTALLED IN TELECOMMUNICATION SPACES.

SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE

INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL

ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA

70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).

3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES

DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-

MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.

FIRE SUPPRESSION GENERAL NOTES:

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

FX410

FX410

114-195

TR

114-195

122-195

TR

122-195

FX410

128-201

TR

128-201

FX410

128-202

TR

128-202

FX410

132-205

TR

132-205

FX410

132-206

TR

132-206 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :2

P

M

OVERALL FIRE SUPPRESSION PLANS

SAB 102 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX107

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1" = 40'-0"

B195 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN1

N

1" = 40'-0"

B201 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN2

N

1" = 40'-0"

B202 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN3

N

1" = 40'-0"

B205 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN4

N

1" = 40'-0"

B206 - LEVEL ONE - OVERALL FIRE SUPPRESSION PLAN5

100A-1

STORAGE

100A-1 100-1

TR

100-1

201-1

TR

201-1 1 300-1

TR

300-1 2

102-3

TR

102-3

202-3

TR

202-3

111-4

TR

111-4

185-4

TR

185-4 1

208-4

TR

208-4

209-4

STORAGE

209-4

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :3

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 103 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX401

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B1 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1001

N

1/4" = 1'-0"

B1 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2012

N

1/4" = 1'-0"

B1 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3003

N

1/4" = 1'-0"

B3 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1024

N

1/4" = 1'-0"

B3 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2025

N

1/4" = 1'-0"

B4 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1116

N

1/4" = 1'-0"

B4 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1857

N

1/4" = 1'-0"

B4 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2098

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

SPRINKLERS.

2 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE

BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER

SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA

IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT

REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.

THE SPACE WILL REMAIN UNSPRINKLERED.

120-6

TR

120-6 1

130-6

TR

130-6

130B-6

MECHANICAL

130B-6

130B-7

TR

130B-7

130A-7

STORAGE

130A-7

227B-7

TR

227B-7

227A-7

STORAGE

227A-7

103-9

IT ROOM

103-9

210A-9

TR

210A-9

105-11

TR

105-11

25-32

TR

5-32 2

10-36

PAINT

STORAGE

10-36

106-7

TR

106-7

148-7

TR

148-7

233B-7

TR

233B-7

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :4

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 104 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX402

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B6 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1201

N

1/4" = 1'-0"

B6 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1302

N

1/4" = 1'-0"

B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 130B3

N

1/4" = 1'-0"

B7 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 227B7

N

1/4" = 1'-0"

B9 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1038

N

1/4" = 1'-0"

B9 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2109

N

1/4" = 1'-0"

B11 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 10510

N

1/4" = 1'-0"

B32 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 511

N

1/4" = 1'-0"

B36 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1012

N

1/4" = 1'-0"

B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1064

N

1/4" = 1'-0"

B7 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1485

N

1/4" = 1'-0"

B7 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 233B6

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

SPRINKLERS.

2 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE

BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER

SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA

IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT

REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.

5A-37

BREAKROOM

5A-37

114-46

TR

114-46

214-46

TR

214-46

9A-66

TR

9A-66

125-66

TR

125-66

226-66

TR

226-66

103-92

TE

103-92

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :4

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 105 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX403

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B37 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 51

N

1/4" = 1'-0"

B46 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1142

N

1/4" = 1'-0"

B46 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2143

N

1/4" = 1'-0"

B66 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - 9A4

N

1/4" = 1'-0"

B66 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1255

N

1/4" = 1'-0"

B66 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2266

N

1/4" = 1'-0"

B92 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1037

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

SPRINKLERS.

1H-131

1H-131 1

101B-131

TR

101B-131 1

207-131

TR

207-131 1

302-131

TR

302-131 1

402A-131

TR

402A-131

BC113-133

TR

BC113-133

BD129-133

TR

BD129-133

BD139-133

TR

BD139-133

BD105-133

TR

BD105-133

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :5

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 106 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX404

SPUR #: 2113

N

1/4" = 1'-0"

B131 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - 1H1

N

1/4" = 1'-0"

B131 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 101B2

N

1/4" = 1'-0"

B131 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2073

N

1/4" = 1'-0"

B131 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3024

N

1/4" = 1'-0"

B131 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 402A5

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BC1136

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1297

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1398

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BD1059

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

BA140-133

TR

BA140-133

BB101H-133

TELECOM

BB101H-133

BE215-133

TR

BE215-133 1

BF117-133

TR

BF117-133 1BF329-133

TR

BF329-133 1

BE405-133

TR

BE405-133

1A143-133

TR

1A143-133

1A120A-133

TR

1A120A-133 1

BA130B-133

TR

BA130B-133

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :0

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 107 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX405

SPUR #: 2113

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BA1401

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BB101H2

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BE2154

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BF1175

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BF3296

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BE4047

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E107A8

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1A120A9

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B133 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - BA130B3

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

1B117A-133

1B117A-133

1D225-133

TR

1D225-133

11D226-133

TR

1D226-133

1D117-133

TR

1D117-133 1 1E226-133

TR

1E226-133 1

1E104-133

TR

1E104-133

1F347-133

TR

1F347-133 1 1F101F-133

TR

1F101F-133 11E344-133

TR

1E344-133 1

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :0

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 108 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX406

SPUR #: 2113

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1B117A1

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D2252

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D2263

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1D1174

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E2265

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E1046

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1F3477

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1F101F8

N

1/4" = 1'-0"

B133 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1E3449

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

2B117A-133

2B117A-133

2A106-133

TR

2A106-133

2D129-133

TR

2D129-133

2D146-133

TR

2D146-133 1

2D174-133

TR

2D174-133 1

2E224-133

TR

2E224-133 1

2F311-133

TR

2F311-133 1 2F123-133

TR

2F123-133 12E408-133

TR

2E408-133 1

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :1

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 109 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX407

SPUR #: 2113

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2B1171

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2A1062

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D129A3

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D1464

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2D1745

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2E2246

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2F3117

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2F1238

N

1/4" = 1'-0"

B133 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 2E4089

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

3A148-133

3A148-133

13D111-133

TR

3D111-133

3D126-133

TR

3D126-133

3D100-133

TR

3D100-133 13F119-133

TR

3F119-133

3F323-133

TR

3F323-133

4A115-133

TR

4A115-133

4B117-133

TR

4B117-133

3B123-133

TR

3B123-133

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :2

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 110 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX408

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3A1471

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D111A2

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D126A4

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3D1005

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3F1196

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3F3237

N

1/4" = 1'-0"

B133 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 4A1139

N

1/4" = 1'-0"

B133 - LEVEL FOUR - ENLARGED FIRE SUPPRESSION PLAN - 4B11710

N

1/4" = 1'-0"

B133 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - 3B1233

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

A104-134

A104-134

A206-134

TR

A206-134

1B216-134

TR

B216-134

A305-134

TR

A305-134

B116-134

TE ROOM

B116-134

B318-134

TR

B318-134

A02-135

IT ROOM

A02-135

A29A-135

TR

A29A-135

108-135

TR

108-135

142A-135

TR

142A-135

208-135

TR

208-135

242A-135

TR

242A-135

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :3

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 111 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX409

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B134 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - A1041

N

1/4" = 1'-0"

B134 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - A2062

N

1/4" = 1'-0"

B134 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - B2164

N

1/4" = 1'-0"

B134 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - A3055

N

1/4" = 1'-0"

B134 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - B1163

N

1/4" = 1'-0"

B134 - LEVEL THREE - ENLARGED FIRE SUPPRESSION PLAN - B3186

N

1/4" = 1'-0"

B135 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - A027

N

1/4" = 1'-0"

B135 - BASEMENT - ENLARGED FIRE SUPPRESSION PLAN - A29A8

N

1/4" = 1'-0"

B135 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1089

N

1/4" = 1'-0"

B135 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 142A10

N

1/4" = 1'-0"

B135 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 20811

N

1/4" = 1'-0"

B135 - LEVEL TWO - ENLARGED FIRE SUPPRESSION PLAN - 242A12

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

122-195

122-195

114-195

TR

114-195 2

128-201

TR

128-201 1128-202

TR

128-202 1

132-205

TR

132-205 1 132-206

TR

132-2061

102-188

TR

102-188

06-187

IRM RACK

ROOM

06-18707-187

UTILITY

07-187

03-140

TR

03-140

02-140

DISPATCH

02-140

K1-138

TR

K1-138

HAZARD CLASSIFICATION LEGEND

OUT OF SCOPE AREA

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

RATED WALL LEGEND

AREA NOT IN CONTRACT

EXISTING WALLS TO REMAIN

NOTE: WALL RATINGS ARE REFERENCED FROM LIFE SAFETY SHEETS DEVELOPED BY SPUR.

EXISTING 2 HOUR FIRE WALL

EXISTING 1 HOUR FIRE WALL

EXISTING 30 MINUTE SMOKE BARRIER

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. SETH CAVIN, #001.023503 EXP. 11/30/2022

MECH REG. ROSS MYLES, #062.071715 EXP. 11/30/2023

ELEC REG. BEN NOE, #062.072296 EXP. 11/30/2023

CIVIL ENGINEER

OLSSON

550 E. ST. LOUIS ST,

SPRINGFIELD, MO 65806

(417) 885-1736

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING ST., SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

STRUCTURAL ENGINEER

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST., STE 300

ST. LOUIS, MO 63101

(713) 864-2900

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 85712

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.,

OLATHE, KANSAS 66062

(913) 829-8690

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L A

S S

IF

IE

D I N

F O

R M

A T

IO

N

C

U I)

/2

/2

:5 :3

P

M

ENLARGED FIRE SUPPRESSION PLANS

SAB 112 OF 348BLS

ISSUED FOR BID & CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES, WEST CAMPUS -

NORTH CHICAGO

12/08/2022

556-21-701

3001 GREEN BAY ROAD

NORTH CHICAGO, ILLINOIS 60064

FX410

SPUR #: 2113

4 69

KEY PLAN

G R

E E

N B

A Y

R O

A D

BUCKLEY ROAD

N

202 201

205206

N

1/4" = 1'-0"

B195 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1225

N

1/4" = 1'-0"

B195 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1146

N

1/4" = 1'-0"

B201 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1287

N

1/4" = 1'-0"

B202 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1288

N

1/4" = 1'-0"

B205 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1329

N

1/4" = 1'-0"

B206 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 13210

N

1/4" = 1'-0"

B188 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 1024

N

1/4" = 1'-0"

B187 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 063

N

1/4" = 1'-0"

B140 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - 032

N

1/4" = 1'-0"

B138 - LEVEL ONE - ENLARGED FIRE SUPPRESSION PLAN - K11

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A

QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE

INSTALLED TO PROTECT THIS SPACE. THE SPACE IS

CURRENTLY PROTECTED WITH QUICK-RESPONSE

SPRINKLERS.

2 THIS TELECOMMUNICATION SPACE HAS BEEN

DESIGNATED AS AN ANSI/TIA-942-B RATING 1

SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA

FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. THE

BUILDING CURRENTLY DOES NOT HAVE A FIRE SPRINKLER

SYSTEM INSTALLED, THE DIRECTION PROVIDED BY THE VA

IS THAT A NEW FIRE SPRINKLER SYSTEM IS NOT

REQUIRED TO BE INSTALLED TO PROTECT THIS SPACE.

ABBREVIATIONS

HVAC PIPING TYPES

GENERAL DUCT SYMBOLS

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION

INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

A

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

ETR EXISTING TO REMAIN

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

D

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

FSD COMBINATION FIRE / SMOKE DAMPER

G

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

J

J INTENTIONALLY LEFT BLANK

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

H

HU HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPC HIGH PRESSURE STEAM CONDENSATE RETURN

HPS HIGH PRESSURE STEAM (61-300 PSIG)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HC HOT WATER HEATING COIL

HHP HEATING HOT WATER PUMP

HHR HEATING HOT WATER RETURN

HHS HEATING HOT WATER SUPPLY

HHUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

L

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPC LOW PRESSURE STEAM CONDENSATE RETURN

CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM (0-15 PSIG)

CLPS LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

M

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPC MEDIUM PRESSURE STEAM CONDENSATE

RETURN

MPS MEDIUM PRESSURE STEAM (16-60 PSIG)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

P

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

O

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OSD ORGANIC SOIL FILTER

Q

Q INTENTIONALLY LEFT BLANK

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

DSD DUCT SMOKE DETECTOR

SD SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

R

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

T

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

U

X INTENTIONALLY LEFT BLANK

W

W WATTS

WAG WASTE ANESTHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFM WATER FLOWMETER

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

X

V

GENERAL NOTES:

A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT

DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS

ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS

COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR

INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.

D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION

"PAINTING".

E. PROVIDE VIBRATION ISOLATION AS RECOMMENDED BY THE MANUFACTURER FOR ALL

MOTORIZED…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .