The key details include: the scope of work involves the fabrication and erection of steel joists, steel deck, and cold-formed light gauge steel framing in accordance with applicable industry standards and codes; there are requirements for welding, bridging, bearing lengths, and camber; the steel materials must conform to specific ASTM standards; the deck must meet Factory Mutual requirements; there are requirements for special inspections and testing; and the contractor must submit calculations, connections, and shop drawings sealed by a professional engineer. The related federal contract opportunity is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside solicitation issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the Expand Primary Care Minor Construction at Lake Nona (East) project, with a project location at the Orlando VA Medical Center Lake Nona Campus.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4 5 z h
WALL ELEVATION
STEEL JOISTS
1. DETAIL, FABRICATE, AND ERECT STEEL JOISTS IN ACCORDANCE WITH THE LATEST SJI, AISC, AWS, AND OTHER CODES AND STANDARDS AND CONTRACT DOCUMENTS.
2. PROVIDE BRIDGING IN ACCORDANCE WITH THE LATEST SJI SPECIFICATIONS. END OF
BRIDGING LINES SHALL BE ANCHORED TO MASONRY WALLS, CONCRETE WALLS, OR STEEL
BEAMS. ALL BRIDGING SHALL BE WELDED TO JOISTS IN SUCH A MANNER AS TO NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE JOISTS.
3. WELD ALL STEEL JOISTS TO SUPPORTING STRUCTURAL STEEL MEMBERS AS SHOWN ON
THE DRAWINGS, AND ACCORDING TO SJI AS MINIMUM.
4. ALL JOISTS SHALL HAVE STANDARD MINIMUM CAMBER IN ACCORDANCE WITH SJI
STANDARD SPECIFICATIONS.
5. ALL "K" SERIES JOISTS SHALL HAVE A MINIMUM BEARING LENGTH ON STEEL BEAMS OF 3"
AND A MINIMUM BEARING LENGTH ON MASONRY OR CONCRETE OF 4".
6. ALL "LH" SERIES JOISTS SHALL HAVE A MINIMUM BEARING LENGTH ON STEEL BEAMS OF 5"
AND A CAPS BEARING LENGTH ON MASONRY OR CONCRETE OF 6".
7. WHEN THE MINIMUM BEARING LENGTH OF THE JOIST CANNOT BE ACHIEVED DUE TO
BUTTING JOISTS, THE JOISTS SHALL BE STAGGERED.
8. EXTEND ALL JOISTS 2" MINIMUM PAST CENTERLINE OF THE SUPPORTING MEMBER, WHEN
THERE ARE JOISTS ON ONLY ONE SIDE OF THE SUPPORTING MEMBER UNO.
9. THE JOIST PANEL POINTS FOR THE FULL WIDTH OF EACH BAY MUST LINE UP WITH EACH
OTHER WITHIN A TOLERANCE OF 1"±.
10. JOISTS SHALL BE ERECTED STRAIGHT. SWEEPS SHALL BE A MAXIMUM OF 1" MEASURED AT
THE CENTER.
11. NO LOADS SHALL BE HUNG FROM THE JOIST BRIDGING.
12. ANY LOADS SUPPORTED FROM THE JOIST BOTTOM CHORD MUST BE ATTACHED WITHIN 6"
OF A PANEL POINT. (SUCH AS SPRINKLER HANGERS)
13. STEEL JOISTS SHALL BE PRIME PAINTED WITH RUST INHIBITIVE PAINT MEETING FEDERAL
SPECIFICATION TT-P-636. PAINT DRY FILM THICKNESS PER MANUFACTURER STANDARDS.
14. WHERE COLUMNS ARE NOT FRAMED IN AT LEAST TWO DIRECTIONS WITH STRUCTURAL
STEEL MEMBERS, A BAR JOIST WITH BOTTOM CHORD EXTENDED SHALL BE FIELD BOLTED
TOP AND BOTTOM TO COLUMNS TO PROVIDE LATERAL STABILITY.
15. ALL STEEL JOISTS SHALL HAVE A CEILING EXTENSION PROVIDED IN THE AREAS WHERE
CEILINGS ARE HUNG OR DIRECTLY ATTACHED TO THE JOIST.
16. NET UPLIFT = SEE COMPONENTS AND CLADDING TABLE OF THESE GENERAL NOTES. ADD
BOTTOM CHORD BRIDGING AT FIRST PANEL POINT AT EACH END OF JOISTS.
17. PROVIDE FULL BEARING UNDER JOIST SEATS FOR SLOPPING SUPPORT MEMBERS.
PROVIDE SHIMS OR BEARING SEAT UNDER JOIST, AS REQUIRED, TO ACHIEVE FULL JOIST
BEARING.
STEEL DECK
1. DETAIL, FABRICATE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST STEEL
DECK INSTITUTE SPECIFICATIONS, AWS AND CONTRACT DOCUMENTS. DECK SHALL
CONFORM TO "BASIC DESIGN SPECIFICATIONS" AS ADOPTED BY THE STEEL DECK
INSTITUTE.
2. ROOF DECK PROFILE SHALL CONFORM TO FACTORY MUTUAL REQUIREMENTS.
3. ROOF DECK SHALL BE MANUFACTURED FROM STEEL CONFORMING TO ASTM A611 GRADE C,
D OR E, GR 33 OR HIGHER.
4. COMPOSITE FLOOR DECK SHALL BE MANUFACTURED FROM STEEL CONFORMING TO ASTM
A653-94, GR 33 OR HIGHER.
5. COMPOSITE FLOOR DECK SHALL BE GALVANIZED & CONFORM TO ASTM A924-94, CLASS
G-90.
6. ROOF DECK SHALL BE OR GALVANIZED G90.
7. ROOF DECK SHALL BE CONNECTED TO SUPPORTING STRUCTURAL STEEL MEMBERS WITH A
[36/4] PATTERN WITH [5/8"] DIAMETER PUDDLE WELDS WITH THE FIRST AND LAST RIBS OF
EACH SHEET WELDED TO THE SUPPORTS. SIDELAPS SHALL BE SCREWED WITH #10 SELF
TAPPING SCREWS AT 36” ON CENTER.
8. COMPOSITE FLOOR DECK SHALL BE CONNECTED TO SUPPORTING STRUCTURAL STEEL
MEMBERS WITH A [36/4] PATTERN WITH [3/4"] DIAMETER PUDDLE WELDS WITH THE FIRST
AND LAST RIB OF EACH SHEET WELDED TO THE SUPPORTS. SIDELAPS SHALL BE SCREWED
WITH #10 SELF TAPPING SCREWS AT 36” ON CENTER.
9. DECK SHALL INCLUDE ANY MISCELLANEOUS CLOSURE PIECES, POUR STOPS, DRAIN SUMP
PANS, REINFORCING AROUND OPENINGS, ETC., REQUIRED TO MAKE A COMPLETE JOB.
MISCELLANEOUS ITEMS SHALL BE GALVANIZED G90.
10. NO LOADS SHALL BE HUNG FROM THE ROOF DECK.
11. ALL DECK LIGHTER THAN 22 GA SHALL USE WELDING WASHERS FOR CONNECTION OF
DECK TO STEEL SUPPORT.
12. PLACE DECK UNITS ON SUPPORTING STEEL FRAMEWORK IN LENGTHS TO SPAN 4 OR MORE
SUPPORTS (3 SPANS). LAP ENDS OF DECK NOT LESS THAN 2". SIDE LAP INTERLOCKS SHALL
NOT BE STRETCHED OR CONTRACTED. DECK SHALL BEAR A MINIMUM OF 3" ON SUPPORTS.
13. MAXIMUM SIZE OF OPENINGS IN DECK WITHOUT STRUCTURAL FRAMING SUPPORT SHALL
NOT EXCEED 10". OPENINGS GREATER THAN 10" MUST HAVE STRUCTURAL SUPPORT ON
ALL SIDES OF THE OPENING.
14. FOR SLOPING DECK PROVIDE CONTINUOUS SHIMS, AS REQUIRED TO ACHIEVE FULL DECK
BEARING ON SUPPORTING MEMBERS.
15. DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
ROOF DECK: FLOOR DECK:
I= 0.155 IN4 I= 0.489 IN4
S= 0.186 IN3 S= 0.409 IN3
16. TESTING OF STEEL DECK AND HEADED STUDS.
a. THE OWNER SHALL ENGAGE AN INDEPENDENT TESTING AND INSPECTION AGENCY
TO CERTIFY THE WELDS BEING PLACED CONFORM TO THE CONTRACT DOCUMENTS.
TO CERTIFY THAT THE WELDS CONFORM, THEY MUST BE MEASURED FOR SIZE, HIT
WITH A HAMMER TO DETERMINE THEIR SOUNDNESS, AND VISUALLY INSPECTED FOR
ANY BURN_OUTS. AS THE PROJECT PROGRESSES, THE TESTING LABORATORY
SHALL SUBMIT WRITTEN REPORTS TO THE A/E OR OWNER ON THE QUALITY OF
WELDING BEING DONE. THE OWNER SHALL PAY FOR THESE REPORTS.
b. HEADED STUD SHEAR CONNECTORS SHALL BE INSPECTED FOR SIZE AND CORRECT
PLACEMENT IN ACCORDANCE WITH CONFORMING SHOP DRAWINGS AND CONTRACT
DOCUMENTS. STUDS SHALL BE VISUALLY INSPECTED FOR FULL FUSION OR A FULL
360 DEG. FLASH (WELD FILLET). IF INSPECTION REVEALS INCORRECT SIZE OR
PLACEMENT, THE STUDS SHALL BE REMOVED AND REPLACED WITH NEW STUDS OF
THE PROPER SIZE AND CORRECTLY PLACED. IF VISUAL INSPECTION REVEALS
STUDS THAT DO NOT SHOW FULL FUSION OR A FULL 360 DEG. FLASH (WELD FILLET)
EACH STUD SHALL BE BENT BY STRIKING WITH A HAMMER OR BY PLACING A PIPE
OVER THE STUD AND MANUALLY BENDING APPROXIMATELY 15 DEG. OFF
PERPENDICULAR IN A DIRECTION OPPOSITE TO MISSING FLASH. IF THE WELD OR
STUDS DO NOT FRACTURE, THE STUD SHALL BE CONSIDERED ACCEPTABLE AND
LEFT BENT. STUDS THAT FAIL THIS TEST SHALL BE REPLACED.
c. ANY WELDING OR STUDS FOUND UNSATISFACTORY SHALL BE CORRECTED BY THE
CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER.
COLD FORMED LIGHT GAGE STEEL FRAMING
1. ALL COLD FORMED FRAMING SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST
AMERICAN IRON AND STEEL INSTITUTE (AISI) “SPECIFICATION FOR DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS”.
2. ALL COLD FORMED STEEL FRAMING SHALL BE GALVANIZED CONFORMING TO ASTM A653.
3. COLD FORM STEEL MEMBER 16 GA. OR THICKER SHALL BE FORMED FROM 50 KSI YIELD
STRENGTH STEEL. COLD FORMED MEMBERS THINNER THAN 16 GA. SHALL BE FORMED
FROM 33KSI YIELD STRENGTH STEEL.
4. SCREW OR WELD ALL CONNECTIONS. TOUCH UP ALL WELDS WITH ASTM A924 ZINC RICH
PAINT.
5. AXIALLY LOADED STUDS SHALL BE INSTALLED SO THE ENDS POSITIONED AGAINST THE
INSIDE OF THE RUNNER TRACK WEB PRIOR TO FASTENING AND SHALL BE ATTACHED TO
BOTH FLANGES OF THE UPPER AND LOWER RUNNER TRACKS.
6. DIAGONAL STRAP BRACING SHALL BE CONNECTED TO ALL CROSSING VERTICAL MEMBERS.
7. SUGGESTED MEMBER SIZES INDICATED ON DRAWINGS ARE BASED ON DIETRICH
INDUSTRIES 1 5/8” FLANGE CSJ SECTION PROPERTIES. ALTERNATE MANUFACTURERS ARE
PERMITTED PROVIDED THEY MATCH OR EXCEED SPANNING DIETRICH SECTION
PROPERTIES AND MEMBER CAPACITIES.
8. THE CONTRACTOR SHALL SUBMIT CALCULATIONS, CONNECTIONS, AND SHOP DRAWINGS
STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE
THE PROJECT IS LOCATED.
9. COLD FORMED LIGHT GAGE STEEL TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH
AISI “COLD FORMED STEEL FRAMING - TRUSS DESIGN”. BOTTOM CHORD OF ROOF TRUSSES
SHALL BE DESIGNED FOR A 10 PSF DEAD LOAD AND A 20 PSF LIVE LOAD IN ATTIC
LOCATIONS.
10. TRUSS LAYOUT AND PROFILES INDICATED ON THE DRAWINGS ARE SHOWN FOR SCHEMATIC
INFORMATION ONLY. ACTUAL DESIGN AND LAYOUT SHALL BE THE RESPONSIBILITY OF THE
TRUSS MANUFACTURER.
11. TRUSS MANUFACTURER SHALL SUBMIT CALCULATIONS, CONNECTIONS, AND SHOP
DRAWINGS STAMPED AND SIGNED BY THE DESIGN ENGINEER REGISTERED IN THE PROJECT
STATE. DESIGN NOTES TO INCLUDE THE RATED LOAD CAPACITY OF THE CONNECTORS
USED TO SECURE THE MEMBERS, SHOP DRAWINGS ARE TO INDICATE LOCATIONS,
CONFIGURATION SPACING, AND SIZES OF MEMBERS TO BE USED.
SPECIAL INSPECTIONS
1. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION AND TESTING PER FBC SECTION
1704 [IBC SECTION 1704]. THIS WORK SHALL BE PERFORMED BY A SPECIAL INSPECTOR
CERTIFIED BY THE GOVERNING MUNICIPALITY WHERE THE PROJECT IS LOCATED TO
PERFORM THE TYPES OF INSPECTIONS AND TESTS SPECIFIED. THE FREQUENCY OF
INSPECTIONS AND TESTING SHALL BE AS OUTLINED IN THE FBC [IBC] TABLE ITEMS
LISTED BELOW. DEFICIENCIES SHALL BE REPORTED DAILY TO THE CONTRACTOR.
SUMMARY REPORTS SHALL BE DISTRIBUTED WEEKLY TO THE OWNER, ARCHITECT,
CONTRACTOR, BUILDING OFFICIAL AND STRUCTURAL ENGINEER. SEE THE SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS FOR SPECIAL INSPECTION AND TESTING.
SECTION 1705.2.1 PER AISC 360 - CHAPTER NSTRUCTURAL STEEL
CONCRETE
MASONRY
ITEMS REQUIRING
VERIFICATION AND INSPECTION
CONSTRUCTION
MATERIAL
TABLE 1705.3
TABLE 1705.4
SOILS TABLE 1705.6 ALL ITEMS
PER TMS 402 / ACI 530 / ASCE5 AND
TMS602 / ACI 530.1 / ACSE6
ALL ITEMS, EXCEPT 9A, 9B, 10 AND 11
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
(PER FBC CHAPTER 17)
APPLICABLE FBC
SECTION/TABLE
SECTION 1705.2.2 PER SDI QA/QCCOLD FORMED STEEL DECK
SECTION 1705.2.3 ALL ITEMSOPEN WEB STEEL JOIST
AND JOIST GIRDERS
SECTION 1705.2.4 ?COLD FORMED STEEL TRUSSES
SPANNING 60 FEET OR GREATER
NOTES 9A, 9B, 10 REFERS TO
PRESTRESSED CONCRETE
NOTE 11 REFERS TO POST
TENSIONED CONCRETE
SECTION 1705.5.2METAL PLATE CONNECTED WOOD
TRUSSES SPANNING 60 FEET OR
GREATER
1 2
3 3
2a 2a 2a
2a
ROOF PLAN
5 5
11 4
2a
2a
2a
S-002U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
15 W. Church Street, Suite 201 Orlando, Florida 32801-3350
407-630-6253 ENGINEERING
OSBORN
STRUCTURAL GENERAL
NOTES