The project is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, solicitation number 36C77624B0016, located at the Orlando VA Medical Center Lake Nona Campus. The contractor will provide all tools, equipment, materials, labor, and supervision to complete the construction project in accordance with the attached specifications and drawings. The required building design criteria includes governing building codes, floor live loads, wind loads, demolition requirements, concrete work specifications, and structural framing details for steel, precast concrete, and cold-formed light gauge steel. The project location is at 13800 Veterans Way, Orlando, FL 32827.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING DESIGN CRITERIA:
GOVERNING CODE: FLOIDA BUILDING CODE 7th EDITION (2020) IN CONJUNCTION WITH ASCE 7-16.
RISK CATEGORY: IV
FLOOR LIVE LOADS:
F IRS T F LOOR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10 0 PSF
INTERSTIT IAL SPACE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15 PSF
ACCESSIBLE CEILING ----------------------------------------------------------------------------------------------- 10 PSF
LIVE LOAD REDUCTION ----------------------------------------------------------------------------- NONE
WIND LOAD:
ULTIMATE DESIGN WIND SPEED (Vult): ------------------------------------------------------------------- 149 MPH
NOMINAL DESIGN WIND SPEED (Vasd): ------------------------------------------------------------------ 116 MPH
RISK CATEGORY ------------------------------------------------------------------------------------------------------------- IV
WIND EXPOSURE ------------------------------------------------------------------------------------- C
INTERNAL PRESSURE COEFFICIENT-------------------------------------------------------------- +/-0.18
DEMOLITION:
1. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE DEMOLITION
PROCEDURE AND SEQUENCE TO ENSURE THE SAFETY OF THE EXISTING BUILDING AND ITS
COMPONENT PARTS DURING DEMOLITION AND FUTURE ERECTION. THIS INCLUDES, BUT IS
NOT LIMITED TO, THE ADDITION OF ANY AND ALL TEMPORARY BRACING, GUYS, OR
TIE-DOWNS WHICH MAY BE NECESSARY. SUCH MATERIAL SHALL BE REMOVED, AND SHALL
REMAIN THE PROPERTY OF THE CONTRACTOR AFTER COMPLETION OF THE PROJECT.
2. THE CONTRACTOR SHALL SUPPORT, BRACE, AND SECURE EXISTING STRUCTURE AS
REQUIRED. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY OF THE EXISTING
BUILDING DURING DEMOLITION AND CONSTRUCTION. FIELD VERIFY ALL EXISTING
DIMENSIONS, ELEVATIONS, AND CONDITIONS WHICH AFFECT THE DEMOLITION AND NEW
CONSTRUCTION.
3. THE EXTENT OF THE WORK SHOWN SHALL INCLUDE REMOVAL AND DISPOSAL, OFF SITE, OF
THE ELEMENTS INDICATED WITHIN THESE DEMOLITION DRAWINGS UNO.
4. THE EXISTING STRUCTURE SHALL BE DISASSEMBLED IN A MANNER WHICH DOES NOT
DAMAGE OR DEFORM ANY EXISTING STRUCTURE TO REMAIN. EXISTING SLABS SHALL BE
SAWCUT IN A MANNER WHICH DOES NOT CAUSE THE SLAB SUPPORTING MEMBER TO BE
CUT OR DAMAGED.
5. CONFORM TO ALL APPLICABLE CODES FOR DEMOLITION OF STRUCTURES, SAFETY OF
EXISTING AND ADJACENT STRUCTURES, DUST CONTROL, AND DISPOSAL.
6. USE OF EXPLOSIVES SHALL NOT BE PERMITTED.
7. EXISTING SLABS SHALL BE CORE DRILLED AT RE-ENTRANT CORNERS OF NEW FLOOR
OPENINGS TO PREVENT OVER CUTTING.
8. THE DEMOLISHED STRUCTURE SHALL BE REDUCED TO A WEIGHT AND TRANSPORTED
ACROSS THE EXISTING STRUCTURE IN A MANNER WHICH DOES NOT OVERSTRESS THE
EXISTING BUILDING STRUCTURE.
9. FRAMING SHALL BE REMOVED ONLY AFTER THE LOAD SUPPORTED BY THAT FRAMING IS
REMOVED. THE FRAMING REMOVAL PROCESS SHALL NOT DEFORM OR INDUCE STRESS TO
EXISTING FRAMING TO REMAIN.
CAST-IN-PLACE CONCRETE:
1. CAST-IN-PLACE CONCRETE WORK SHALL CONFORM TO THE AMERICAN CONCRETE
INSTITUTE CODES AND STANDARDS. ACI 301 "STANDARD SPECIFICATIONS FOR
STRUCTURAL CONCRETE" IS HEREBY MADE A PART OF THESE DRAWINGS. ALL CONCRETE
CONSTRUCTION SHALL CONFORM TO ACI 301, EXCEPT AS EXPLICITLY MODIFIED HEREIN.
2. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 318, “THE BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE”.
3. CONCRETE SHALL HAVE THE FOLLOWING MINIMUM COMPRESSIVE STRENGTHS AT 28 DAYS:
a. BEAMS, JOISTS, AND ELEVATED SLABS - 5000 PSI WITHOUT ENTRAINED AIR FOR ALL
CONCRETE WITH A MAXIMUM WATER/CEMENT RATIO = 0.45 UNLESS SPECIFICALLY
NOTED OTHERWISE.
b. COLUMNS - 6000 PSI WITHOUT ENTRAINED AIR FOR ALL CONCRETE WITH A MAXIMUM
WATER/CEMENT RATIO = 0.45 UNLESS SPECIFICALLY NOTED OTHERWISE.
5. WELDED WIRE FABRIC: ASTM A82 AND A185 FOR SMOOTH STEEL WIRE
6. REINFORCING BARS: ASTM 615, GRADE 60 (U.N.O.) WELDING OR TACK WELDING A615 BARS SHALL NOT BE PERMITTED. PROVIDE #5@12"oc EW IN ALL CAST-IN-PLACE CONCRETE UNO.
7. PROVIDE 6x6-W2.9xW2.9 WWF IN ALL SLABS ON GROUND UNO. USE ONLY FLAT SHEETS.
PLACE WELDED WIRE FABRIC IN SLABS ON GRADE AT 1/3 THE SLAB THICKNESS DOWN FROM
TOP OF SLAB, UNLESS NOTED OTHERWISE.
8. ALL WELDED WIRE FABRIC SHALL BE CHAIRED TO ITS PROPER HEIGHT AND MAINTAINED AT
THE PROPER LEVEL THROUGHOUT THE CONCRETE PLACING OPERATION. LIFTING OF
WELDED WIRE FABRIC WITH A HOOK DURING CONCRETE PLACEMENT SHALL NOT BE
PERMITTED.
9. BEND ALL HORIZONTAL WALL AND BEAM BARS AROUND ALL CORNERS, UNLESS OTHERWISE
NOTED. PROVIDE ACI LAP EACH SIDE.
10. REINFORCING BARS REQUIRED FOR PROPER SUPPORT OF PRINCIPAL REINFORCING SHALL
BE DETAILED AND SUPPLIED BY THE CONTRACTOR WHETHER OR NOT THEY ARE INDICATED
ON THE DRAWINGS. THE MINIMUM BAR SIZE SHALL BE #4 AND THE MAXIMUM SPACING
SHALL BE 36" ON CENTER FOR ALL BARS THAT NEED SUPPORT. WELDED WIRE FABRIC
SHALL NOT BE USED FOR THE SUPPORT OF PRINCIPAL REINFORCING.
11. PROVIDE CORROSION RESISTANT ACCESSORIES SUCH AS GRAY PLASTIC CHAIRS OR
CHAIRS WITH PLASTIC COATED TIPS, IN ALL EXPOSED CONCRETE CONSTRUCTION.
PRECAST CONCRETE CUBES OR SAND PLATE CHAIRS SHALL BE USED FOR THE SUPPORT
OF REINFORCING ON GRADE. CONCRETE BLOCK OR CLAY MASONRY BRICK ARE NOT
PERMITTED.
12. NO CONCRETE SHALL BE PLACED UNTIL THE PROPOSED CONCRETE MIX AND TEST HAVE
BEEN SUBMITTED TO AND REVIEWED BY THE ARCHITECT AND AFTER THE CONTRACTOR
HAS RECEIVED WRITTEN ACKNOWLEDGEMENT.
13. ALL CEMENT SHALL BE TYPE I OR TYPE III, BLENDED CEMENTS SHALL NOT BE USED.
14. CONCRETE SHALL BE DISCHARGED AT THE SITE WITHIN 1 1/2 HOURS AFTER WATER HAS
BEEN ADDED TO THE CEMENT AND AGGREGATES, ADDITION OF WATER TO THE MIX AT THE
PROJECT SITE WILL NOT BE PERMITTED. ALL WATER MUST BE ADDED AT THE BATCH
PLANT. SLUMP MAY BE ADJUSTED ONLY THROUGH THE USE OF ADDITIONAL WATER
REDUCING ADMIXTURE OR HIGH RANGE WATER REDUCING ADMIXTURE.
15. ALL CONCRETE SHALL CONTAIN A WATER REDUCING ADMIXTURE CONFORMING TO ASTM
C494, TYPE A, F OR G.
16. CALCIUM CHLORIDE SHALL NOT BE PERMITTED NOR SHALL ANY ADMIXTURE CONTAINING
CALCIUM CHLORIDE BE PERMITTED.
17. PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI 318. SUBMIT DRAWINGS
SHOWING SEQUENCE AND DIRECTION OF POUR TO PERMIT SLAB SHRINKAGE FOR
ENGINEER'S REVIEW.
18. ALL CONSTRUCTION JOINTS BELOW GRADE SHALL HAVE WATERSTOPS, UNLESS NOTED
OTHERWISE.
19. 3/4" CHAMFER FOR EXPOSED EDGES OF CONCRETE UNO.
20. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND EXTENT OF SPECIAL FINISHES OR
TREATMENTS TO CONCRETE.
21. COORDINATE ALL WORK RELATED TO OWNER-SUPPLIED EQUIPMENT OR EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR BY USING ONLY CERTIFIED EQUIPMENT DRAWINGS.
22. PROVIDE SAWCUT CONTROL JOINTS IN ALL SLABS ON GRADE. THE MAXIMUM SPACING OF
JOINTS SHALL BE 36 TIMES THE SLAB THICKNESS IN BOTH DIRECTIONS, UNLESS
OTHERWISE NOTED.
23. PROVIDE BOND BREAKER BETWEEN MASONRY BEARING WALLS AND ALL CAST-IN-PLACE
CONCRETE SLABS UNO.
24. REINFORCING BAR LAP SPLICES AND ANCHORAGE LENGTH SHALL CONFORM WITH TABLE
MINIMUM LAP SPLICE AND ANCHORAGE DIMENSION TABLE AS PROVIDED WITHIN THESE
GENERAL NOTES.
25. TOP LAYER OF REINFORCING STEEL IN SLABS SHALL BE CONSIDERED TOP BARS
REGARDLESS OF THICKNESS OF CONCRETE BELOW THE BARS.
26. CONCRETE SLABS SHALL BEAR A MINIMUM OF 4" ON MASONRY WALLS, UNLESS NOTED
OTHERWISE. CONCRETE BEAMS SHALL BEAR A MINIMUM OF 8" ON MASONRY WALLS,
UNLESS NOTED OTHERWISE.
27. BONDBREAKER MATERIAL SHALL BE 30 POUND FELT PAPER.
28. CONCRETE FIELD QUALITY CONTROL:
a. THE OWNER SHALL EMPLOY A TESTING LABORATORY TO TAKE AND TEST CONCRETE
CYLINDERS, PERFORM SLUMP TESTS, PERFORM TESTS FOR AIR CONTENT, AND TO
PERFORM STRENGTH TESTS IN ACCORDANCE WITH ASTM C39.
b. MINIMUM OF THREE CYLINDERS SHALL BE TAKEN FOR EACH 50 CU YD OF CONCRETE
OR FRACTION THEREOF FOR EACH STRENGTH AND TYPE OF CONCRETE BEING CAST
THAT DAY.
c. NO CONCRETE SHALL BE PLACED THAT DOES NOT MEET SLUMP OR AIR CONTENT
REQUIREMENTS. ALL TESTS FOR AIR CONTENT SHALL BE MADE BY THE PRESSURE
METHOD. SLUMP TESTS SHALL BE TAKEN AT EACH 20 CU YD OF CONCRETE BEING
PLACED.
d. SLUMP EXCEEDING THE SPECIFIED MAXIMUM, WHEN OCCURRING IN 2 CONSECUTIVE
TESTS MADE ON DIFFERENT PORTIONS OF THE SAME SAMPLE, WILL BE CAUSE FOR
REJECTION OF THAT TRUCKLOAD AND SHALL BE REPORTED TO THE A/E
IMMEDIATELY. THE REPLACEMENT OF SUCH CONCRETE WITH THE SPECIFIED
CONCRETE SHALL BE DONE AT NO ADDITIONAL EXPENSE TO THE OWNER.
e. THE CONCRETE TEST REPORTS SHALL CONTAIN THE FOLLOWING INFORMATION:
CONCRETE SUPPLIER, QUANTITY OF CONCRETE REPRESENTED, LOCATION OF ALL
SAMPLES TAKEN, STRENGTH REQUIREMENT IN PSI AT 28 DAYS, LIST OF ALL
MATERIALS USED (QUANTITY, AND BRAND OR SOURCE), ACTUAL SLUMP, ACTUAL AIR
CONTENT PERCENT BY VOLUME, AIR TEMPERATURE, CONCRETE TEMPERATURE,
WEATHER, CYLINDER WEIGHT AS RECEIVED, AIR_DRIED UNIT WEIGHT FOR
LIGHTWEIGHT CONCRETE, DATE MOLDED, NUMBER OF DAYS ON JOB SITE, DATE
TESTED, TEST RESULTS FOR 7 AND 28 DAYS AGE, AND ANY OTHER INFORMATION
NECESSARY TO EVALUATE TESTS. TWO COPIES OF THESE REPORTS SHALL BE SENT
DIRECTLY TO THE A/E OR THE OWNER.
REINFORCING BAR CLEARANCE TABLE
1/3 SLAB THICKNESS
FROM TOP OF SLAB
CONCRETE CAST AGAINST & PERMANENTLY
EXPOSED TO EARTH OR MUD SLAB
CLEARANCELOCATION
SLABS ON GRADE (WWF)
3"
GENERAL CONDITIONS:
1. SEE ARCHITECTURAL DRAWINGS FOR OTHER PERTINENT INFORMATION RELATED TO
STRUCTURAL WORK AND COORDINATE AS REQUIRED. CONTRACTOR SHALL COORDINATE
STRUCTURAL DRAWINGS WITH ALL OTHER DRAWINGS WITHIN THE CONTRACT DOCUMENTS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND CONDITIONS
RELATED TO EXISTING CONSTRUCTION, EXISTING SERVICES, AND THE SITE BEFORE
BEGINNING WORK.
3. CONSTRUCTION LOADS SHALL NOT EXCEED DESIGN LIVE LOADS. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR ALL DESIGN REQUIRED TO SUPPORT CONSTRUCTION EQUIPMENT
USED IN CONSTRUCTING THIS PROJECT. ALL EQUIPMENT SUPPORT DESIGN SHALL BE
PERFORMED BY AN ENGINEER LICENSED IN THE STATE OF THE PROJECT. SHORING AND
RESHORING IS THE RESPONSIBILITY OF THE CONTRACTOR.
4. IF MATERIALS, QUANTITIES, STRENGTHS, OR SIZES INDICATED BY THE DRAWINGS OR
SPECIFICATIONS ARE NOT IN AGREEMENT WITH THESE NOTES, THE BETTER QUALITY
AND/OR GREATER QUANTITY, STRENGTH, OR SIZE INDICATED, SPECIFIED OR NOTED SHALL
BE PROVIDED.
5. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE FOLLOWING ITEMS THAT WILL NOT BE
REVIEWED BY THE OWNER, ARCHITECT OR ENGINEER.
a. DEVIATIONS FROM CONTRACT DOCUMENTS.
b. DIMENSIONS, ELEVATIONS, AND CONDITIONS TO BE CONFIRMED AND CORRELATED AT
THE SITE.
c. FABRICATION PROCESS INFORMATION.
d. MEANS, METHODS, TECHNIQUES, PROCEDURES OF CONSTRUCTION, AND
CONSTRUCTION SAFETY.
e. COORDINATION OF THE WORK OF ALL TRADES.
f. QUALITY ASSURANCE SUBMITTALS.
6. THE INFORMATION SHOWN ON THE ARCHITECTURAL AND STRUCTURAL
CONSTRUCTION DOCUMENTS IS BASED ON ASSUMPTIONS OF THE EXISTING
BUILDING CONSTRUCTION. ORIGINAL CONSTRUCTION DOCUMENTS WERE NOT
AVAILABLE FOR THE PREPARATION OF THESE DOCUMENTS. THE CONTRACTOR IS
TO NOTIFY THE A/E IF CONDITIONS DIFFERING FROM THOSE STATED ARE
UNCOVERED IN THE DEMOLITION PROCESS.
7. ANY CHANGES TO THE STRUCTURAL SYSTEMS SHALL BE REDESIGNED BY A
PROFESSIONAL ENGINEER AT NO COST TO THE OWNER OR THE A/E AND SUBMITTED TO
THE A/E FOR REVIEW. SUBMITTAL SHALL BE ACKNOWLEDGED IN WRITING BEFORE
BEGINNING CONSTRUCTION. IF CHANGES ARE MADE WITHOUT WRITTEN APPROVAL SUCH
CHANGES SHALL BE THE LEGAL AND FINANCIAL RESPONSIBILITY OF THE PARTY MAKING
THE CHANGE TO REPLACE OR REPAIR THE CONDITION AS DIRECTED BY THE A/E.
8. CONTRACTOR IS RESPONSIBLE TO UNCOVER AND VISUALLY FIELD VERIFY THE
EXISTING CONSTRUCTION PRIOR TO THE START OF ANY WORK AFFECTING THE EXISTING
STRUCTURE. CONTRACTOR IS TO REPORT ANY CHANGES OR DISCREPANCIES FROM
THOSE SHOWN TO THE A/E.
STRUCTURAL STEEL:
1. DETAIL, FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE LATEST
AISC AND OTHER RELATED CODES, STANDARDS AND SPECIFICATIONS LISTED IN THE
PROJECT SPECIFICATIONS, EXCEPT AS MODIFIED THEREIN OR ON THE DRAWINGS.
2. THE CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANOUS/ORNAMENTAL STEEL NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
3. STRUCTURAL STEEL:
a. ASTM A992 Fy = 50 KSI FOR ROLLED STEEL WIDE FLANGE SHAPES
b. ASTM A36 Fy = 36 KSI FOR PLATES, BARS, RODS, CHANNELS, ANGLES UNO
c. ASTM A53 TYPE E OR S, GRADE B FOR STEEL PIPE
d. ASTM A500 GRADE C FOR HSS TUBING
4. HIGH STRENGTH BOLTS: ASTM A325 OR A490, 3/4” DIAMETER MINIMUM UNO
5. ANCHOR RODS: ASTM F1554, GRADE 36 UNO
6. WORK STRUCTURAL DRAWINGS WITH ARCHITECTURAL, HVAC, PLUMBING, FIRE
PROTECTION & ELECTRICAL DRAWINGS FOR CLEARANCES, ATTACHMENTS, ETC.
7. ALL FABRICATION AND ERECTION WORK SHALL BE PERFORMED BY AISC CERTIFIED
FABRICATORS AND ERECTORS.
8. WELDED CONNECTIONS SHALL CONFORM TO THE LATEST REVISED CODE OF THE
AMERICAN WELDING SOCIETY, AWS D1.1 AND SHALL BE PERFORMED BY CERTIFIED
WELDERS IN ACCORDANCE WITH THE AMERICAN WELDING SOCIETY STANDARDS.
PROVIDE MINIMUM 1/4" FILLET WELD, UNO.
9. CONTRACTOR SHALL ASSUME THAT ANY MODIFICATIONS TO EXISTING STEEL FRAMING
SHALL REQUIRE AN ABATEMENT OF EXISTING LEAD PAINT IN CONFORMANCE WITH LOCAL
CODES.
10. PROVIDE ANGLE WALL ANCHORS, PER PART 4, AISC MANUAL OF STEEL CONSTRUCTION,
FOR BEAMS BEARING ON MASONRY WALLS. ANGLE ANCHORS SHALL BE WELDED TO
BEAMS.
11. CONNECTIONS: WELD OR BOLT CONNECTIONS, AS INDICATED:
a. CONNECTIONS NOT DETAILED ON THE DRAWINGS SHALL CONFORM TO THE
REQUIREMENTS OF THE CITED AISC SPECIFICATION.
b. WHERE THE REACTION VALUES OF BEAMS ARE NOT SHOWN ON THE DRAWINGS, EACH END CONNECTION SHALL BE DESIGNED TO SUPPORT 55% OF THE TOTAL
UNIFORM LOAD CAPACITY DERIVED FROM THE ASD VALUE OF THE TABLES
AND FORMULA OF THE MAXIMUM TOTAL UNIFORM LOAD IN PART 3, FOURTEENTH
EDITION, OF THE AISC MANUAL OF STEEL CONSTRUCTION FOR THE GIVEN MEMBER
SIZE, SPAN, AND YIELD STRENGTH. COMPOSITE BEAM CONNECTIONS MUST
DEVELOP 75% OF THE TOTAL BEAM ALLOWABLE UNIFORM LOAD CAPACITY, AS
GIVEN IN THE AISC TABLES BASED ON SIZE, SPAN, & YIELD STRENGTH.)
c. THE MINIMUM LENGTH OF CONNECTION ANGLES SHALL BE EQUAL TO ONE-HALF THE
DEPTH OF THE MEMBER TO BE SUPPORTED.
d. ONE-SIDED CONNECTIONS WILL NOT BE PERMITTED, UNLESS SPECIFICALLY
DETAILED ON THE DRAWINGS OR SEALED DESIGN CALCULATIONS ARE SUBMITTED
WITH THE SHOP DRAWINGS.
e. THE MINIMUM NUMBER OF BOLTS IN BOLTED CONNECTIONS SHALL BE TWO (2)
BOLTS.
f. MINIMUM 1/4” FILLET WELD SHALL APPLY UNLESS NOTED OTHERWISE.
g. MINIMUM SIZE OF CLIP ANGLE SHALL BE 3x3x5/16” UNLESS NOTED OTHERWISE.
12. UTILIZE THROUGH PLATES FOR ALL CONNECTIONS TO TUBES AND PIPES UNLESS SHOWN
OTHERWISE.
13. TRUSS AND BRACING MEMBER CONNECTIONS SHALL BE DESIGNED FOR THE FORCES
INDICATED ON THE DRAWINGS.
14. TYPICAL CONNECTION DETAILS INDICATED ON THE STRUCTURAL DESIGN DRAWINGS
SHALL DICTATE THE FORM AND GEOMETRY OF THE CONNECTIONS. THE FABRICATOR
SHALL DETERMINE OR VERIFY TYPE, SIZE AND NUMBER OF BOLTS, PLATE
THICKNESS AND SIZES, WELD SIZES AND LENGTHS, AND ALL REQUIRED INFORMATION NOT
SPECIFIED ON THE TYPICAL CONNECTION DETAILS.
15. THE DESIGN OF ALL STEEL CONNECTIONS (EXCEPT PREDESIGNED CONNECTIONS THAT
HAVE BEEN ENGINEERED ON THESE DRAWINGS) SHALL BE PERFORMED UNDER THE
DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF THE
PROJECT, EMPLOYED BY THE FABRICATOR. THE FABRICATOR'S REGISTERED
PROFESSIONAL ENGINEER SHALL SUBMIT COMPLETE DESIGN CALCULATIONS FOR EACH
CONNECTION. SUCH CALCULATIONS SHALL SHOW DETAILS OF THE ASSEMBLED JOINT
WITH ALL BOLTS AND WELDS REQUIRED.
16. ALL DESIGN CALCULATIONS SHALL BE SEALED BY THE FABRICATOR'S PROFESSIONAL
ENGINEER REGISTERED IN THE STATE OF [OHIO]. SHOP DRAWINGS SUBMITTED WITHOUT
COMPLETE DESIGN CALCULATIONS WILL NOT BE REVIEWED.
17. WELDING ELECTRODES SHALL BE E-70XX OR BETTER. FOR WELDING SYMBOLS WITH NO
LENGTH DIMENSION GIVEN, THE WELDING SHALL BE CONTINUOUS BETWEEN ABRUPT
CHANGES IN DIRECTION.
18. UTILIZE SLIP CRITICAL BOLTS AT ALL MOMENT CONNECTIONS, HANGING CONNECTIONS,
BRACING CONNECTIONS, AND COLUMN SPLICES.
19. CAMBER INDICATED ON DRAWINGS SHALL BE THE AMOUNT OF CAMBER IN THE MEMBER
FOLLOWING ERECTION.
20. ALL STRUCTURAL STEEL MEMBERS EXPOSED TO THE EXTERIOR SHALL BE GALVANIZED
UNLESS NOTED OTHERWISE. THIS INCLUDES BUT IS NOT LIMITED TO MASONRY LINTELS
AND SHELF ANGLES, INCLUDING BEARING PLATES AND ANCHOR BOLTS, AND ANY OTHER
ITEM LISTED ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS.
21. UNLESS NOTED OTHERWISE, ALL PIPE AND TUBE COLUMNS SHALL BE SEAL WELDED WITH
CLOSURE PLATES TO BE AIR TIGHT. ARCHITECTURAL PIPES AND TUBULAR BEAMS SHALL
BE PROVIDED WITH 3/8" DIAMETER WEEP HOLES.
22. LOCATION OF ANCHOR RODS SHALL BE CONFIRMED BY A LICENSED SURVEYOR BEFORE
ERECTION OF STEEL.
23. COLUMNS AND BEAMS WITH BASE, CAP OR END PLATES SHALL HAVE SQUARE CUT OR
MILLED ENDS.
24. THE FRAMING SHALL BE ERECTED TRUE AND PLUMB. TEMPORARY BRACING SHALL BE
PROVIDED AND SHALL REMAIN IN PLACE UNTIL THE LATERAL BRACING SYSTEM IS IN PLACE
AND CONNECTIONS OF ALL MEMBERS ARE FINAL AND ALL DECK IS COMPLETELY ERECTED,
WELDED AND SCREWED IN PLACE.
25. NON-METALLIC, NON-SHRINK, NON-STAINING GROUT UNDER ALL COLUMN BASE PLATES,
BEAM BEARING PLATES, AND EQUIPMENT SHALL CONSIST OF A PREMIXED PRODUCT
COMPLYING WITH ALL REQUIREMENTS OF ASTM C1107, ASTM C827, AND ASTM C109. 8000
PSI MINIMUM COMPRESSIVE STRENGTH.
26. HEADED SHEAR CONNECTORS SHALL BE MADE FORM STEEL CONFORMING TO ASTM A108,
TYPE B, GRADE 1010 THROUGH 1020.
27. STUD TYPE EXPANSION ANCHORS SHALL BE CARBON STEEL (UNLESS NOTED OTHERWISE
ON DRAWINGS) CONFORMING TO THE REQUIREMENTS OF THE MANUFACTURER'S
SPECIFICATIONS AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS. SEE DRAWINGS FOR LOCATIONS AND TYPE.
28. ALL STRUCTURAL STEEL MEMBERS (BEAMS AND COLUMNS) ADJACENT TO OR BUILT INTO
MASONRY CONSTRUCTION SHALL BE PROVIDED WITH 12 GAUGE GALVANIZED WELD-ON
CHANNEL SLOTS AND 3/16 x 1 1/4 HOOKED GALVANIZED ANCHORS, SPACED 16" ON CENTER
VERTICALLY AND 24" ON CENTER HORIZONTALLY, MAXIMUM.
29. ALL DISSIMILAR METALS TO BE SEPARATED BY ELECTROLYTIC SEPARATORS.
30. DO NOT PAINT:
a. SURFACES OF CONNECTIONS INDICATED AS SLIP CRITICAL.
b. SURFACES OF CONNECTIONS TO BE FIELD WELDED.
c. SURFACES TO RECEIVE HEADED SHEAR CONNECTIONS.
d. MEMBERS TO BE EMBEDDED IN CONCRETE OR MASONRY.
e. SURFACES TO RECEIVE SPRAYED ON INSULATION.
f. MEMBERS TO BE GALVANIZED.
31. TESTING OF STRUCTURAL STEEL
a. THE OWNER SHALL ENGAGE AN INDEPENDENT TESTING AND INSPECTION AGENCY, TO INSPECT HIGH-STRENGTH BOLTED CONNECTIONS AND WELDED CONNECTIONS, AND TO PERFORM TESTS AND SUBMIT TEST REPORTS. THE CONTRACTOR SHALL
REMAIN SOLELY RESPONSIBLE FOR ALL WORK PERFORMED, REGARDLESS OF THE
DEGREE OF INSPECTION PROVIDED BY THE OWNER.
b. THE TESTING AGENCY SHALL CONDUCT AND INTERPRET THE TESTS, STATE IN EACH
REPORT WHETHER THE TEST SPECIMENS COMPLY WITH THE CONTRACT
DOCUMENTS, AND SPECIFICALLY STATE ANY DEVIATIONS. REPORTS SHALL BE
DELIVERED TO THE A/E ON A TIMELY SCHEDULE.
c. PROVIDE ACCESS FOR THE TESTING AGENCY TO PLACES WHERE STRUCTURAL
STEEL WORK IS BEING FABRICATED OR PRODUCED AND PROVIDE INFORMATION,
SPACE, AND FACILITIES FOR CHECKING SHOP DRAWINGS SO REQUIRED INSPECTION
AND TESTING CAN BE ACCOMPLISHED. THE STEEL FABRICATOR SHALL INFORM THE
OWNER WHEN FABRICATION IS TO START AND SCHEDULE THE SHOP DRAWINGS TO
FOLLOW IN ORDER OF FABRICATION OF THE MEMBERS.
d. THE TESTING AGENCY MAY INSPECT STRUCTURAL STEEL AT THE PLANT BEFORE
SHIPMENT; HOWEVER, THE A/E RESERVES THE RIGHT TO REJECT MATERIAL NOT
COMPLYING WITH SPECIFIED REQUIREMENTS.
e. CORRECT DEFICIENCIES IN STRUCTURAL STEEL WORK WHICH INSPECTIONS AND
LABORATORY TEST REPORTS INDICATE ARE NOT IN COMPLIANCE WITH
CONSTRUCTION DOCUMENTS. PERFORM ADDITIONAL TESTS, AT CONTRACTOR'S
EXPENSE, AS MAY BE NECESSARY TO RECONFIRM ANY DEVIATION OF THE ORIGINAL
WORK, AND WHICH MAY BE NECESSARY TO SHOW COMPLIANCE OF CORRECTED
WORK.
32. SHOP AND FIELD BOLTED CONNECTIONS
a. INSPECT IN ACCORDANCE WITH AISC SPECIFICATIONS A325.
33. WELDING: SHOP AND FIELD
a. INSPECT AND TEST DURING FABRICATION OF STRUCTURAL STEEL ASSEMBLIES.
b. CERTIFY WELDERS AND CONDUCT INSPECTIONS AND TESTS AS REQUIRED.
RECORD TYPES AND LOCATIONS OF ALL DEFECTS FOUND IN THE WORK. RECORD
WORK REQUIRED AND PERFORMED TO CORRECT DEFICIENCIES. THE SHOP
WELDING SHALL BE INSPECTED AT FIT-UP AS WELL AS AFTER WELDING
COMPLETION.
c. PERFORM VISUAL INSPECTION OF ALL WELDING. SUCH INSPECTION SHALL BE MADE
WHILE THE OPERATORS ARE MAKING THE WELDS AND AGAIN AFTER THE WORK IS
COMPLETED. AFTER THE WELDING IS COMPLETED, WELDS SHALL BE HAND OR
POWER WIRE BRUSHED AND CLEANED BEFORE THE INSPECTOR MAKES THE CHECK
INSPECTION. WELDS SHALL BE INSPECTED WITH MAGNIFIERS UNDER STRONG,
ADEQUATE LIGHT FOR SURFACE CRACKING, POROSITY, SLAG INCLUSIONS,
EXCESSIVE ROUGHNESS, UNFILLED CRATERS, GAS POCKETS, UNDERCUTS,
OVERLAPS, SIZE, SUFFICIENT THROAT AND CONCAVITY. WELD AREAS CONTAINING
DEFECTS SHALL BE REPAIRED AND REINSPECTED AT NO ADDITIONAL EXPENSE TO
THE OWNER.
34. PERFORM TESTS ON FULL PENETRATION WELDS USING ONE OF THE METHODS LISTED
BELOW:
a. LIQUID PENETRANT INSPECTION: ASTM E165.
b. MAGNETIC PARTICLE INSPECTION: ASTM E109; PERFORMED ON THE ROOT PASS
AND ON THE FINISHED WELD. CRACKS OR ZONES OF INCOMPLETE FUSION OR
PENETRATION ARE NOT ACCEPTABLE.
c. RADIOGRAPHIC INSPECTION: ASTM E94 AND ASTM E142; MINIMUM QUALITY LEVEL "2_2T".
d. ULTRASONIC INSPECTION: ASTM E164.
35. IF THE RATE OF ACCEPTABILITY OF WELDS IS POOR OR DECREASES SIGNIFICANTLY
DURING A PROJECT, THE A/E MAY REQUIRE INSPECTION OF WELDS PREVIOUSLY NOT
INSPECTED. THE CONTRACTOR SHALL PROVIDE ACCESS AND REASONABLE CONDITIONS
TO INSPECT SUCH WELDS AT NO EXPENSE TO THE OWNER.
PRECAST CONCRETE:
1. PRECAST CONCRETE SHALL CONFORM TO THE LATEST AMERICAN CONCRETE INSTITUTE
AND THE PRESTRESSED CONCRETE INSTITUTE CODES AND STANDARDS. PCI-MNL 116 AND
THE CONTRACT DOCUMENTS.
2. ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE IN 28 DAYS SHALL BE 5000 PSI.
3. PRECAST UNITS MAY BE EITHER NORMAL WEIGHT CONCRETE OR LIGHT WEIGHT
CONCRETE.
4. ALL CONCRETE USED IN THE PRECAST UNITS SHALL CONTAIN AN AIR ENTRAINING
ADMIXTURE CONFORMING TO ASTM C260. THE AMOUNT SHALL BE 6% ± 1%.
5. ALL CEMENT SHALL BE TYPE I OR TYPE III. CONFORMING TO ASTM C150.
6. WATER REDUCING, RETARDING, ACCELERATING, AND HIGH RANGE WATER REDUCING
ADMIXTURE SHALL CONFORM WITH ASTM C494.
7. AGGREGATES SHALL CONFORM WITH ASTM C33 OR C330. MAXIMUM SIZE OF COARSE
AGGREGATE SHALL BE 1".
8. WATER SHALL BE POTABLE AND FREE FROM FOREIGN MATERIALS HARMFUL TO CONCRETE
AND EMBEDDED STEEL.
9. REINFORCING BARS: A615 GRADE 60 KSI YIELD STRENGTH, UNLESS NOTED OTHERWISE.
WELDING OR TACK WELDING A615 REINFORCING STEEL SHALL NOT BE PERMITTED.
10. REINFORCING BARS FOR WELDED APPLICATION SHALL CONFORM WITH A706, 60KSI YIELD
STRENGTH.
11. PRESTRESSING STRAND: ASTM A416, GRADE 270, UNCOATED, 7 WIRE STRESS RELIEVED
STRAND.
12. WELDED WIRE FABRIC: ASTM A185.
13. GROUT SHALL BE A MIXTURE OF PORTLAND CEMENT, SAND, AND WATER SUFFICIENT FOR
PLACEMENT AND HYDRATION.
14. BEARING PADS: KOROLATH MULTIMONOMER PLASTIC BEARING STRIP FOR PRECAST PLANK
BEARING (OR APPROVED EQUAL).
15. ALL STEEL FOR CONNECTIONS SHALL BE STAINLESS STEEL ASTM A666 TYPE 304.
STAINLESS STEEL BOLTS SHALL BE EQUIVALENT TO A36 IN STRENGTH AND WELDS SHALL
BE IN ACCORDANCE WITH AWS D1.1. CONTINUOUS OR SPOT STRUT TYPE INSERTS
COMPLETE WITH SPRING, NUT AND BOLT SHALL ALL BE STAINLESS STEEL.
16. HEADED STUDS SHALL CONFORM TO ASTM A108 AND MUST BE IN END STUD WELDED TO
STEEL MEMBERS USING A STUD GUN.
17. ALL CONNECTIONS SHALL BE DESIGNED SO AS NOT TO BE EXPOSED TO WEATHER NOR TO
VIEW FROM THE EXTERIOR.
18. MINIMUM WALL REINFORCING SHALL BE IN ACCORDANCE WITH ACI - 318.
19. TOLERANCES FOR THE PRECAST UNITS SHALL CONFORM WITH THE PRESTRESSED
CONCRETE INSTITUTE SPECIFICATIONS.
20. OPENINGS FOR MECHANICAL AND ELECTRICAL ITEMS SHALL BE CORE DRILLED THROUGH
HOLLOW CELLS ONLY, PROVIDE ADDITIONAL REINFORCEMENT AS REQUIRED. COORDINATE
LOCATIONS OF OPENINGS WITH MECHANICAL AND ELECTRICAL CONTRACTORS.
21. PRECAST MANUFACTURER SHALL PROVIDE REQUIRED HEADERS FOR ALL FRAMED
OPENINGS.
22. COMPLY WITH ARCHITECTURAL DRAWINGS FOR LOCATION EXTENT OF SPECIAL FINISHES
AND TREATMENTS TO PRECAST CONCRETE.
23. SUBMIT SHOP DRAWINGS AND CALCULATIONS STAMPED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE OF THE PROJECT FOR REVIEW. SHOP DRAWINGS
FOR ALL MEMBERS AND CONNECTIONS MUST ACCOMPANY THE CALCULATIONS.
24. PRECAST UNITS SHORTER THAN TEN FEET SHALL BE REINFORCED WITH REBAR FOR LOAD
CAPACITY. COORDINATE LOCATION AND SIZE OF ALL OPENINGS REQUIRED FOR
MECHANICAL AND ELECTRICAL TRADES. PRECAST MANUFACTURER SHALL PROVIDE
HEADERS REQUIRED FOR FRAMED OPENINGS AND BLOCKOUTS. PRECAST MANUFACTURER
SHALL SUBMIT CALCULATIONS STAMPED BY AN ENGINEER REGISTERED IN THE STATE OF
OHIO ADDRESSING ALL OPENING CONDITIONS GREATER THAN 12" SQUARE. SEE
MECHANICAL AND ARCHITECTURAL DRAWINGS FOR OPENING LOCATIONS AND SIZES.
25. THE PRECAST CONCRETE MANUFACTURING PLANT SHALL BE CERTIFIED BY THE
PRESTRESSED CONCRETE INSTITUTE, PLANT CERTIFICATION PROGRAM, PRIOR TO THE
START OF PRODUCTION.
26. REINFORCING PATTERNS FOR ALL RAKERS, BEAMS, PLANKS, COLUMNS, WALLS, TUBS,
TREADS AND RISERS MUST BE PROPERLY DESIGNED, SIZED, AND SPACED BY PRECAST
CONTRACTOR. SEE SPECIFICATIONS FOR DESIGN SUBMITTAL REQUIREMENTS.
27. DESIGN CRITERIA: IN ADDITION TO THE OVERALL BUILDING DESIGN LIVE LOADS THE
PRECAST UNITS MUST INCLUDE THE FOLLOWING SUPERIMPOSED LOADS:
a. TOPPING SLABS - [25 PSF]
b. MASONRY WALLS - [SEE PLAN]
c. CONCESSION/TOILET ROOF - [SEE PLAN]
d. MECHANICAL/EQUIPMENT - [SEE PLAN]
SUPERIMPOSED DEAD LOAD AND LIVE LOADS ARE AS SHOWN ON PLANS. TOPPING
THICKNESS HAS BEEN SET AT 2" PLANK END BEARING. TOPPING TAPERS (DUE TO PLANK
CAMBER) TO A MINIMUM OF 1" AT MIDSPAN PRECAST CONCRETE PLANK WITH CAMBER
GREATER THAN 1" WILL BE REJECTED.
28. SEE ARCH, STRUCTURAL, HVAC, PLUMBING & FIRE PROTECTION DWGS FOR THE VARIOUS
LAYOUTS AND LOCATIONS OF SPECIFIC IMPOSED ITEMS.
29. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION AND EXTENT OF SPECIAL FINISHES
OR TREATMENTS TO EXPOSED PRECAST CONCRETE.
30. THE CONTRACTOR SHALL PROVIDE TEMPORARY BRACING, AS REQUIRED, DURING THE
ERECTION OF PRECAST UNITS.
31. EMBEDDED PLATES SHALL BE GALVANIZED ASTM A123 (UNO).
32. THE TOP SURFACE OF PRECAST PLANKS SHALL BE INTENTIONALLY ROUGHENED TO
RECEIVE BONDED TOPPING.
33. FOR BONDED TOPPING SLAB CAST IN PLACE SEE CONCRETE NOTES.
34. FOR PRECAST ROOFS NOT INTENDED TO RECEIVE A TOPPING SLAB, PRECASTER SHALL
PROVIDE A SURFACE SUITABLE FOR ROOFING. PRECASTER SHALL COORDINATE WITH
ROOFING CONTRACTED FOR REQUIREMENTS.
MINIMUM TENSION DEVELOPMENT AND LAP
SPLICE LENGTH SCHEDULE FOR 60KSI
DEFORMED BARS ON 6000PSI NORMAL WEIGHT
CONCRETE
BAR TYPE
BAR SIZE
BEAM & GIRDER OTHER
COLUMN (S > 3db)
COLUMN (2db < S < 3db)
FOUNDATION BOTTOM
FOUNDATION OTHER
BEAM & GIRDER BOTTOM 12''
SLAB OTHER
WALL HORIZONTAL
WALL VERTICAL CATEGORY 1
WALL VERTICAL CATEGORY 2
SLAB BOTTOM
13''
#3
12''
12''
16''
21''
#4
14''
18''
15''
14''
23''
26''
#5
19''
24''
21"
14''
18''
33''
31''
#6
31''
40''
33''
22''
27''
#7
39''
50''
42''
26''
34''
#8
48''
58''
52''
29"
38''
#9
58''
65''
64''
35''
45''
#10
69''
72''
72''
41''
54''
#11
12''
12''
12''
12''
12''
12''
12''
12''
12''
13'' 20'' 26'' 31'' 45'' 51'' 58'' 65''
72''
72''
45'' 51" 58'' 65''
45'' 51" 58'' 65'' 72''
15'' 21" 33'' 42'' 52'' 64'' 72''12''12''
STANDARD HOOK 9'' 11'' 14'' 16'' 18'' 21'' 23'' 27'' 29"
13'' 21'' 26'' 31'' 45'' 51" 58'' 65'' 72''
13'' 21'' 26'' 31'' 45'' 51" 58'' 65'' 72''
1.
2.
3.
4.
5.
6.
7.
8.
9.
NOTES:
MINIMUM TENSION DEVELOPMENT LENGTH CAN BE OBTAIN BY DIVIDING VALUES IN SCHEDULE OVER 1.3
VALUES IN SCHEDULE SHALL BE MULTIPLIED BY 1.2 FOR EPOXY COATED DEFORMED BARS
BOTTOM BAR TYPE IS DEFINED AS:
OTHER BAR TYPE IS DEFINED AS: ANY BAR OTHER THAN BOTTOM BAR
S > 3db IS DEFINED AS:
2db < S < 3db IS DEFINED AS:
IF LAP SPLICE OCCURS ON DIFFERENT BAR SIZES, PROVIDE LAP LENGTH FROM SMALLER
BAR BUT NOT LESS THAN
DEVELOPMENT LENGTH OF LARGER BAR.
REFER TO APPROPRIATE SCHEDULE WHEN CONCRETE STRENGTH OR REINFORCING
STRENGTH IS OTHER THAN PROVIDED
VALUES IN THIS SCHEDULE CAN BE USE FOR HIGHER CONCRETE STRENGTHS
S-001 U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
15 W. Church Street, Suite 201 Orlando, Florida 32801-3350
407-630-6253 ENGINEERING
OSBORN
STRUCTURAL GENERAL
NOTES
AutoCAD SHX Text
INDICATES AREA OF SLAB TO BE RAISED 2" TO MATCH THE EXISTING SLAB HEIGHT
AutoCAD SHX Text
INDICATES EXISTING STRUCTURAL ELEMENTS
AutoCAD SHX Text
INDICATES NEW STRUCTURAL ELEMENTS
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
INDICATES AREAS OUT OF SCOPE
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text strollo & strollo 718 Virginia Drive Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
AutoCAD SHX Text
EXPAND PRIMARY CARE AT LAKE NONA (EAST)
AutoCAD SHX Text
JANUARY 11, 2024
AutoCAD SHX Text 675-100
AutoCAD SHX Text
1 AND 2
AutoCAD SHX Text
KEY PLAN N.T.S.
AutoCAD SHX Text
REFERENCED
AutoCAD SHX Text
BB
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Location
AutoCAD SHX Text
13800 VETERANS WAY, ORLANDO, FL. 32827
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS 100% FINAL SUBMISSION
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text Phase
AutoCAD SHX Text E4
AutoCAD SHX Text E1
AutoCAD SHX Text E2
AutoCAD SHX Text E3
AutoCAD SHX Text D5
AutoCAD SHX Text D4
AutoCAD SHX Text D6
AutoCAD SHX Text D2
AutoCAD SHX Text D1
AutoCAD SHX Text D3
AutoCAD SHX Text C2
AutoCAD SHX Text C1
AutoCAD SHX Text P-W
AutoCAD SHX Text P-E
AutoCAD SHX Text A1
AutoCAD SHX Text A2
AutoCAD SHX Text A3
AutoCAD SHX Text A4
AutoCAD SHX Text B1
AutoCAD SHX Text B2
AutoCAD SHX Text
LEVEL: 3, 4 AND 5
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
TRUE
AutoCAD SHX Text
CDS
4 5 z h
WALL ELEVATION
STEEL JOISTS
1. DETAIL, FABRICATE, AND ERECT STEEL JOISTS IN ACCORDANCE WITH THE LATEST SJI, AISC, AWS, AND OTHER CODES AND STANDARDS AND CONTRACT DOCUMENTS.
2. PROVIDE BRIDGING IN ACCORDANCE WITH THE LATEST SJI SPECIFICATIONS. END OF
BRIDGING LINES SHALL BE ANCHORED TO MASONRY WALLS, CONCRETE WALLS, OR STEEL
BEAMS. ALL BRIDGING SHALL BE WELDED TO JOISTS IN SUCH A MANNER AS TO NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE JOISTS.
3. WELD ALL STEEL JOISTS TO SUPPORTING STRUCTURAL STEEL MEMBERS AS SHOWN ON
THE DRAWINGS, AND ACCORDING TO SJI AS MINIMUM.
4. ALL JOISTS SHALL HAVE STANDARD MINIMUM CAMBER IN ACCORDANCE WITH SJI
STANDARD SPECIFICATIONS.
5. ALL "K" SERIES JOISTS SHALL HAVE A MINIMUM BEARING LENGTH ON STEEL BEAMS OF 3"
AND A MINIMUM BEARING LENGTH ON MASONRY OR CONCRETE OF 4".
6. ALL "LH" SERIES JOISTS SHALL HAVE A MINIMUM BEARING LENGTH ON STEEL BEAMS OF 5"
AND A CAPS BEARING LENGTH ON MASONRY OR CONCRETE OF 6".
7. WHEN THE MINIMUM BEARING LENGTH OF THE JOIST CANNOT BE ACHIEVED DUE TO
BUTTING JOISTS, THE JOISTS SHALL BE STAGGERED.
8. EXTEND ALL JOISTS 2" MINIMUM PAST CENTERLINE OF THE SUPPORTING MEMBER, WHEN
THERE ARE JOISTS ON ONLY ONE SIDE OF THE SUPPORTING MEMBER UNO.
9. THE JOIST PANEL POINTS FOR THE FULL WIDTH OF EACH BAY MUST LINE UP WITH EACH
OTHER WITHIN A TOLERANCE OF 1"±.
10. JOISTS SHALL BE ERECTED STRAIGHT. SWEEPS SHALL BE A MAXIMUM OF 1" MEASURED AT
THE CENTER.
11. NO LOADS SHALL BE HUNG FROM THE JOIST BRIDGING.
12. ANY LOADS SUPPORTED FROM THE JOIST BOTTOM CHORD MUST BE ATTACHED WITHIN 6"
OF A PANEL POINT. (SUCH AS SPRINKLER HANGERS)
13. STEEL JOISTS SHALL BE PRIME PAINTED WITH RUST INHIBITIVE PAINT MEETING FEDERAL
SPECIFICATION TT-P-636. PAINT DRY FILM THICKNESS PER MANUFACTURER STANDARDS.
14. WHERE COLUMNS ARE NOT FRAMED IN AT LEAST TWO DIRECTIONS WITH STRUCTURAL
STEEL MEMBERS, A BAR JOIST WITH BOTTOM CHORD EXTENDED SHALL BE FIELD BOLTED
TOP AND BOTTOM TO COLUMNS TO PROVIDE LATERAL STABILITY.
15. ALL STEEL JOISTS SHALL HAVE A CEILING EXTENSION PROVIDED IN THE AREAS WHERE
CEILINGS ARE HUNG OR DIRECTLY ATTACHED TO THE JOIST.
16. NET UPLIFT = SEE COMPONENTS AND CLADDING TABLE OF THESE GENERAL NOTES. ADD
BOTTOM CHORD BRIDGING AT FIRST PANEL POINT AT EACH END OF JOISTS.
17. PROVIDE FULL BEARING UNDER JOIST SEATS FOR SLOPPING SUPPORT MEMBERS.
PROVIDE SHIMS OR BEARING SEAT UNDER JOIST, AS REQUIRED, TO ACHIEVE FULL JOIST
BEARING.
STEEL DECK
1. DETAIL, FABRICATE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST STEEL
DECK INSTITUTE SPECIFICATIONS, AWS AND CONTRACT DOCUMENTS. DECK SHALL
CONFORM TO "BASIC DESIGN SPECIFICATIONS" AS ADOPTED BY THE STEEL DECK
INSTITUTE.
2. ROOF DECK PROFILE SHALL CONFORM TO FACTORY MUTUAL REQUIREMENTS.
3. ROOF DECK SHALL BE MANUFACTURED FROM STEEL CONFORMING TO ASTM A611 GRADE C,
D OR E, GR 33 OR HIGHER.
4. COMPOSITE FLOOR DECK SHALL BE MANUFACTURED FROM STEEL CONFORMING TO ASTM
A653-94, GR 33 OR HIGHER.
5. COMPOSITE FLOOR DECK SHALL BE GALVANIZED & CONFORM TO ASTM A924-94, CLASS
G-90.
6. ROOF DECK SHALL BE [PRIMER PAINTED] OR [GALVANIZED].
7. ROOF DECK SHALL BE CONNECTED TO SUPPORTING STRUCTURAL STEEL MEMBERS WITH A
[36/4] PATTERN WITH [5/8"] DIAMETER PUDDLE WELDS WITH THE FIRST AND LAST RIBS OF
EACH SHEET WELDED TO THE SUPPORTS. SIDELAPS SHALL BE SCREWED WITH #10 SELF
TAPPING SCREWS AT 36” ON CENTER.
8. COMPOSITE FLOOR DECK SHALL BE CONNECTED TO SUPPORTING STRUCTURAL STEEL
MEMBERS WITH A [36/4] PATTERN WITH [3/4"] DIAMETER PUDDLE WELDS WITH THE FIRST
AND LAST RIB OF EACH SHEET WELDED TO THE SUPPORTS. SIDELAPS SHALL BE SCREWED
WITH #10 SELF TAPPING SCREWS AT 36” ON CENTER.
9. DECK SHALL INCLUDE ANY MISCELLANEOUS CLOSURE PIECES, POUR STOPS, DRAIN SUMP
PANS, REINFORCING AROUND OPENINGS, ETC., REQUIRED TO MAKE A COMPLETE JOB.
MISCELLANEOUS ITEMS SHALL BE GALVANIZED G90.
10. NO LOADS SHALL BE HUNG FROM THE ROOF DECK.
11. ALL DECK LIGHTER THAN 22 GA SHALL USE WELDING WASHERS FOR CONNECTION OF
DECK TO STEEL SUPPORT.
12. PLACE DECK UNITS ON SUPPORTING STEEL FRAMEWORK IN LENGTHS TO SPAN 4 OR MORE
SUPPORTS (3 SPANS). LAP ENDS OF DECK NOT LESS THAN 2". SIDE LAP INTERLOCKS SHALL
NOT BE STRETCHED OR CONTRACTED. DECK SHALL BEAR A MINIMUM OF 3" ON SUPPORTS.
13. MAXIMUM SIZE OF OPENINGS IN DECK WITHOUT STRUCTURAL FRAMING SUPPORT SHALL
NOT EXCEED 10". OPENINGS GREATER THAN 10" MUST HAVE STRUCTURAL SUPPORT ON
ALL SIDES OF THE OPENING.
14. FOR SLOPING DECK PROVIDE CONTINUOUS SHIMS, AS REQUIRED TO ACHIEVE FULL DECK
BEARING ON SUPPORTING MEMBERS.
15. DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
ROOF DECK: FLOOR DECK:
I= 0.155 IN4 I= 0.489 IN4
S= 0.186 IN3 S= 0.409 IN3
16. TESTING OF STEEL DECK AND HEADED STUDS.
a. THE OWNER SHALL ENGAGE AN INDEPENDENT TESTING AND INSPECTION AGENCY
TO CERTIFY THE WELDS BEING PLACED CONFORM TO THE CONTRACT DOCUMENTS.
TO CERTIFY THAT THE WELDS CONFORM, THEY MUST BE MEASURED FOR SIZE, HIT
WITH A HAMMER TO DETERMINE THEIR SOUNDNESS, AND VISUALLY INSPECTED FOR
ANY BURN_OUTS. AS THE PROJECT PROGRESSES, THE TESTING LABORATORY
SHALL SUBMIT WRITTEN REPORTS TO THE A/E OR OWNER ON THE QUALITY OF
WELDING BEING DONE. THE OWNER SHALL PAY FOR THESE REPORTS.
b. HEADED STUD SHEAR CONNECTORS SHALL BE INSPECTED FOR SIZE AND CORRECT
PLACEMENT IN ACCORDANCE WITH CONFORMING SHOP DRAWINGS AND CONTRACT
DOCUMENTS. STUDS SHALL BE VISUALLY INSPECTED FOR FULL FUSION OR A FULL
360 DEG. FLASH (WELD FILLET). IF INSPECTION REVEALS INCORRECT SIZE OR
PLACEMENT, THE STUDS SHALL BE REMOVED AND REPLACED WITH NEW STUDS OF
THE PROPER SIZE AND CORRECTLY PLACED. IF VISUAL INSPECTION REVEALS
STUDS THAT DO NOT SHOW FULL FUSION OR A FULL 360 DEG. FLASH (WELD FILLET)
EACH STUD SHALL BE BENT BY STRIKING WITH A HAMMER OR BY PLACING A PIPE
OVER THE STUD AND MANUALLY BENDING APPROXIMATELY 15 DEG. OFF
PERPENDICULAR IN A DIRECTION OPPOSITE TO MISSING FLASH. IF THE WELD OR
STUDS DO NOT FRACTURE, THE STUD SHALL BE CONSIDERED ACCEPTABLE AND
LEFT BENT. STUDS THAT FAIL THIS TEST SHALL BE REPLACED.
c. ANY WELDING OR STUDS FOUND UNSATISFACTORY SHALL BE CORRECTED BY THE
CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER.
COLD FORMED LIGHT GAGE STEEL FRAMING
1. ALL COLD FORMED FRAMING SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST
AMERICAN IRON AND STEEL INSTITUTE (AISI) “SPECIFICATION FOR DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS”.
2. ALL COLD FORMED STEEL FRAMING SHALL BE GALVANIZED CONFORMING TO ASTM A653.
3. COLD FORM STEEL MEMBER 16 GA. OR THICKER SHALL BE FORMED FROM 50 KSI YIELD
STRENGTH STEEL. COLD FORMED MEMBERS THINNER THAN 16 GA. SHALL BE FORMED
FROM 33KSI YIELD STRENGTH STEEL.
4. SCREW OR WELD ALL CONNECTIONS. TOUCH UP ALL WELDS WITH ASTM A924 ZINC RICH
PAINT.
5. AXIALLY LOADED STUDS SHALL BE INSTALLED SO THE ENDS POSITIONED AGAINST THE
INSIDE OF THE RUNNER TRACK WEB PRIOR TO FASTENING AND SHALL BE ATTACHED TO
BOTH FLANGES OF THE UPPER AND LOWER RUNNER TRACKS.
6. DIAGONAL STRAP BRACING SHALL BE CONNECTED TO ALL CROSSING VERTICAL MEMBERS.
7. SUGGESTED MEMBER SIZES INDICATED ON DRAWINGS ARE BASED ON DIETRICH
INDUSTRIES 1 5/8” FLANGE CSJ SECTION PROPERTIES. ALTERNATE MANUFACTURERS ARE
PERMITTED PROVIDED THEY MATCH OR EXCEED SPANNING DIETRICH SECTION
PROPERTIES AND MEMBER CAPACITIES.
8. THE CONTRACTOR SHALL SUBMIT CALCULATIONS, CONNECTIONS, AND SHOP DRAWINGS
STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE
THE PROJECT IS LOCATED.
9. COLD FORMED LIGHT GAGE STEEL TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH
AISI “COLD FORMED STEEL FRAMING - TRUSS DESIGN”. BOTTOM CHORD OF ROOF TRUSSES
SHALL BE DESIGNED FOR A 10 PSF DEAD LOAD AND A 20 PSF LIVE LOAD IN ATTIC
LOCATIONS.
10. TRUSS LAYOUT AND PROFILES INDICATED ON THE DRAWINGS ARE SHOWN FOR SCHEMATIC
INFORMATION ONLY. ACTUAL DESIGN AND LAYOUT SHALL BE THE RESPONSIBILITY OF THE
TRUSS MANUFACTURER.
11. TRUSS MANUFACTURER SHALL SUBMIT CALCULATIONS, CONNECTIONS, AND SHOP
DRAWINGS STAMPED AND SIGNED BY THE DESIGN ENGINEER REGISTERED IN THE PROJECT
STATE. DESIGN NOTES TO INCLUDE THE RATED LOAD CAPACITY OF THE CONNECTORS
USED TO SECURE THE MEMBERS, SHOP DRAWINGS ARE TO INDICATE LOCATIONS,
CONFIGURATION SPACING, AND SIZES OF MEMBERS TO BE USED.
SPECIAL INSPECTIONS
1. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION AND TESTING PER FBC SECTION
1704 [IBC SECTION 1704]. THIS WORK SHALL BE PERFORMED BY A SPECIAL INSPECTOR
CERTIFIED BY THE GOVERNING MUNICIPALITY WHERE THE PROJECT IS LOCATED TO
PERFORM THE TYPES OF INSPECTIONS AND TESTS SPECIFIED. THE FREQUENCY OF
INSPECTIONS AND TESTING SHALL BE AS OUTLINED IN THE FBC [IBC] TABLE ITEMS
LISTED BELOW. DEFICIENCIES SHALL BE REPORTED DAILY TO THE CONTRACTOR.
SUMMARY REPORTS SHALL BE DISTRIBUTED WEEKLY TO THE OWNER, ARCHITECT,
CONTRACTOR, BUILDING OFFICIAL AND STRUCTURAL ENGINEER. SEE THE SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS FOR SPECIAL INSPECTION AND TESTING.
SECTION 1705.2.1 PER AISC 360 - CHAPTER NSTRUCTURAL STEEL
CONCRETE
MASONRY
ITEMS REQUIRING
VERIFICATION AND INSPECTION
CONSTRUCTION
MATERIAL
TABLE 1705.3
TABLE 1705.4
SOILS TABLE 1705.6 ALL ITEMS
PER TMS 402 / ACI 530 / ASCE5 AND
TMS602 / ACI 530.1 / ACSE6
ALL ITEMS, EXCEPT 9A, 9B, 10 AND 11
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
(PER FBC CHAPTER 17)
APPLICABLE FBC
SECTION/TABLE
SECTION 1705.2.2 PER SDI QA/QCCOLD FORMED STEEL DECK
SECTION 1705.2.3 ALL ITEMSOPEN WEB STEEL JOIST
AND JOIST GIRDERS
SECTION 1705.2.4 ?COLD FORMED STEEL TRUSSES
SPANNING 60 FEET OR GREATER
NOTES 9A, 9B, 10 REFERS TO
PRESTRESSED CONCRETE
NOTE 11 REFERS TO POST
TENSIONED CONCRETE
SECTION 1705.5.2METAL PLATE CONNECTED WOOD
TRUSSES SPANNING 60 FEET OR
GREATER
1 2
3 3
2a 2a 2a
2a
ROOF PLAN
5 5
11 4
2a
2a
2a
S-002U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
15 W. Church Street, Suite 201 Orlando, Florida 32801-3350
407-630-6253 ENGINEERING
OSBORN
STRUCTURAL GENERAL
NOTES
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text strollo & strollo 718 Virginia Drive Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
AutoCAD SHX Text
EXPAND PRIMARY CARE AT LAKE NONA (EAST)
AutoCAD SHX Text
JANUARY 11, 2024
AutoCAD SHX Text 675-100
AutoCAD SHX Text
1 AND 2
AutoCAD SHX Text
KEY PLAN N.T.S.
AutoCAD SHX Text
REFERENCED
AutoCAD SHX Text
BB
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Location
AutoCAD SHX Text
13800 VETERANS WAY, ORLANDO, FL. 32827
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS 100% FINAL SUBMISSION
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text Phase
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E4
AutoCAD SHX Text E1
AutoCAD SHX Text E2
AutoCAD SHX Text E3
AutoCAD SHX Text D5
AutoCAD SHX Text D4
AutoCAD SHX Text D6
AutoCAD SHX Text D2
AutoCAD SHX Text D1
AutoCAD SHX Text D3
AutoCAD SHX Text C2
AutoCAD SHX Text C1
AutoCAD SHX Text P-W
AutoCAD SHX Text P-E
AutoCAD SHX Text A1
AutoCAD SHX Text A2
AutoCAD SHX Text A3
AutoCAD SHX Text A4
AutoCAD SHX Text B1
AutoCAD SHX Text B2
AutoCAD SHX Text
LEVEL: 3, 4 AND 5
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
TRUE
LEVEL 3, AREA B2 PLAN - EXISTING FLOOR FRAMING
1/8" = 1'-0"
S-101
FRAMING PLAN NOTES
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
15 W. Church Street, Suite 201 Orlando, Florida 32801-3350
407-630-6253 ENGINEERING
OSBORN
AutoCAD SHX Text
DA
AutoCAD SHX Text
DB
AutoCAD SHX Text
DC
AutoCAD SHX Text
DD
AutoCAD SHX Text
DE
AutoCAD SHX Text
DF
AutoCAD SHX Text
DG
AutoCAD SHX Text
DH
AutoCAD SHX Text
DJ
AutoCAD SHX Text
DK
AutoCAD SHX Text
DA1
AutoCAD SHX Text D1
AutoCAD SHX Text D2
AutoCAD SHX Text D3
AutoCAD SHX Text D4
AutoCAD SHX Text D5
AutoCAD SHX Text D6
AutoCAD SHX Text D7
AutoCAD SHX Text D8
AutoCAD SHX Text D9
AutoCAD SHX Text D10
AutoCAD SHX Text D11
AutoCAD SHX Text D12
AutoCAD SHX Text D11.7
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text
SCALE 1/8" = 1'-0"
AutoCAD SHX Text
EXISTING EXPANSION JOINT
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CB
AutoCAD SHX Text
EXISTING CONC. JST. TYP.
AutoCAD SHX Text
EXISTING CONC. JST. TYP.
AutoCAD SHX Text
EXISTING CONC. JST. TYP.
AutoCAD SHX Text
EXISTING CONC. JST. TYP.
AutoCAD SHX Text
AutoCAD SHX Text S-400
AutoCAD SHX Text
AutoCAD SHX Text S-400
AutoCAD SHX Text
AutoCAD SHX Text S-401
AutoCAD SHX Text
AutoCAD SHX Text S-401
AutoCAD SHX Text
AutoCAD SHX Text S-402
AutoCAD SHX Text
AutoCAD SHX Text S-402
AutoCAD SHX Text
AutoCAD SHX Text S-403
AutoCAD SHX Text
AutoCAD SHX Text S-403
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
NEW CONC. COLUMN SEE SCHEDULE, S-603, TYP. (3) THIS LEVEL
AutoCAD SHX Text
AutoCAD SHX Text S-602
AutoCAD SHX Text TYPICAL TOP OF SLAB ELEVATION AT LEVEL 3 = +41'-4". ALL OTHER ELEVATIONS ON THIS PLAN ARE REFERENCES AS + OR - FROM THIS TYPICAL TOP OF SLAB ELEVATION
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text UNLESS SHOWN ON PLAN, NO OPENINGS ARE PERMITTED WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
AutoCAD SHX Text PROVIDE EMBED PLATES FOR PRECAST PANELS PER SECTION 1 ON SHEET S-502 AS REQUIRED.
AutoCAD SHX Text PROVIDE EMBEDDED CONTINUOUS ANGLE FOR METAL PANEL AND CURTAIN WALL SYSTEMS PER SECTION 10 ON SHEET S-501 AS REQUIRED.
AutoCAD SHX Text
INDICATES AREA OF SLAB TO BE RAISED 2" TO MATCH THE EXISTING SLAB HEIGHT
AutoCAD SHX Text
ALL STRUCTURAL ITEMS THIS LEVEL ARE EXISTING TO REMAIN
AutoCAD SHX Text
INDICATES EXISTING STRUCTURAL ELEMENTS
AutoCAD SHX Text
INDICATES NEW STRUCTURAL ELEMENTS
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text 7.
AutoCAD SHX Text 2" CONCRETE TOPPING SLAB SHALL BE R/W TUF-STRAND-SF MICROFIBERS (OR APPROVED EQUAL) APPLIED AT A RATE OF 3 LBS/CY.
AutoCAD SHX Text
INDICATES AREAS OUT OF SCOPE
AutoCAD SHX Text
LEVEL 3, AREA B2 FLOOR FRAMING PLAN - RENOVATION - STRUCTURAL
AutoCAD SHX Text S-101
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REFERENCED
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text Office of Construction and Facilities Management
AutoCAD SHX Text strollo & strollo 718 Virginia Drive Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
AutoCAD SHX Text
EXPAND PRIMARY CARE AT LAKE NONA (EAST)
AutoCAD SHX Text
JANUARY 11, 2024
AutoCAD SHX Text 675-100
AutoCAD SHX Text
1 AND 2
AutoCAD SHX Text
KEY PLAN N.T.S.
AutoCAD SHX Text
REFERENCED
AutoCAD SHX Text
BB
AutoCAD SHX Text
STAMP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text
CONSULTANTS:
AutoCAD SHX Text
ARCHITECT/ENGINEERS:
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Approved: Project Director
AutoCAD SHX Text Project Title
AutoCAD SHX Text Location
AutoCAD SHX Text
13800 VETERANS WAY, ORLANDO, FL. 32827
AutoCAD SHX Text Date
AutoCAD SHX Text Checked
AutoCAD SHX Text Drawn
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS 100% FINAL SUBMISSION
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text Phase
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text E4
AutoCAD SHX Text E1
AutoCAD SHX Text E2
AutoCAD SHX Text E3
AutoCAD SHX Text D5
AutoCAD SHX Text D4
AutoCAD SHX Text D6
AutoCAD SHX Text D2
AutoCAD SHX Text D1
AutoCAD SHX Text D3
AutoCAD SHX Text C2
AutoCAD SHX Text C1
AutoCAD SHX Text P-W
AutoCAD SHX Text P-E
AutoCAD SHX Text A1
AutoCAD SHX Text A2
AutoCAD SHX Text A3
AutoCAD SHX Text A4
AutoCAD SHX Text B1
AutoCAD SHX Text B2
AutoCAD SHX Text
LEVEL: 3, 4 AND 5
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
TRUE
AutoCAD SHX Text
TRUE
LEVEL 4, AREA B2 FRAMING PLAN - RENOVATION - STRUCTURAL
S-103
FRAMING PLAN KEY NOTES
FRAMING PLAN NOTES
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
15 W. Church Street, Suite 201 Orlando, Florida 32801-3350
407-630-6253 ENGINEERING
OSBORN
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 16'
AutoCAD SHX Text 32'
AutoCAD SHX Text
SCALE 1/8" = 1'-0"
AutoCAD SHX Text
DB
AutoCAD SHX Text
DC
AutoCAD SHX Text
DD
AutoCAD SHX Text
DE
AutoCAD…