Drawings PC Volume 02 Set - Sealed - 2022-01-11 reduced.pdf

PDF 27 MB Posted

Attached to
Y1DB--675-100 Expand Primary Care Minor Construction at Lake Nona (East)
Solicitation number
36C77624B0016
Issued by

About this file

This document appears to be a set of drawings related to a federal contract opportunity for the Expand Primary Care Minor Construction at Lake Nona (East) project. The solicitation number is 36C77624B0016, and the project is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside. The contractor shall provide all tools, equipment, materials, labor, and supervision to complete the construction project, in accordance with the attached specifications and drawings. The project location is the Orlando VA Medical Center Lake Nona Campus. The Department of Veterans Affairs Technology Acquisition Center Austin is the procuring agency.

View the file

Other files

File Type Posted
36C77624B0016 0007.pdf PDF
36C77624B0016 0006.pdf PDF
36C77624B0016 0005.pdf PDF
Bid opening info.pdf PDF
Construction Wage Rates - Orange 7-12-2024.pdf PDF
09 22 16 Non-Struct Met Frames 100Pct FINAL.pdf PDF
A-621 Precast Section Details-A-621.pdf PDF
A-200 3rd Flr Pln - RCP-A-200.pdf PDF
SnS Transmittal Addendum 2.pdf PDF
A-202 4th Flr Pln - RCP-A-202.pdf PDF
SnS Transmittal Addendum 1.pdf PDF
A-400 Bldg Sec-A-400.pdf PDF
S-501.pdf PDF
A-402 Bldg Sec-A-402.pdf PDF
RFI Responses SOLICITATION 36C77624B0016 Project 675-100.pdf PDF
36C77624B0016 0004.pdf PDF
Pre-Cast Architectural Concrete-Area B Shop Dwgs.pdf PDF
A-109 5th Flr Pln - Dim-A-109.pdf PDF
AD-104 5th Flr Pln - Demo-AD-104.pdf PDF
11 73 00 Ceiling Mtd Patient Lift 100Pct FINAL - REV ADD 2.pdf PDF
S-405.pdf PDF
Additional Lay- Down Area Requirements.pdf PDF
A-108 5th Flr Pln - Arch-A-108.pdf PDF
36C77624B0016 0003.pdf PDF
Lake Nona PC Volume 01 Set - Sealed - 2022-01-11.pdf PDF
Site Visit Sign-In Sheet.pdf PDF
Lake Nona PC Volume 02 Set - Sealed - 2022-01-11.pdf PDF
36C77624B0016 0002.pdf PDF
Addendum 5-21-04 REV 6-04-24.pdf PDF
08 00 01 Blast Requirements- Ammendment to IFB.pdf PDF
Supplement to General Requirements Spec - R2 6-6-24.pdf PDF
36C77624B0016 0001.pdf PDF
Revised sheets 2024-05-28.pdf PDF
Specifications Vol Set 01- 5-23-24.pdf PDF
Construction Wage Rates - Orange 5-10-2024.pdf PDF
IFB 36C77624B0016.pdf PDF
Revised sheets 2024-05-21.pdf PDF
Supplement to General Requirements Spec - R1 4-16-24.pdf PDF
Addendum 2 place holder.pdf PDF
Brand Name Justification - Lake Nona Primary Care.pdf PDF
VAAR 852.219-75 Limitations on Subcontracting.docx DOCX document
Site Visit Instructions.pdf PDF
Addendum 1 5-21-24.pdf PDF
Specifications Vol Set 02- 3-5-24.pdf PDF
Drawings PC Volume 01 Set - Sealed - 2022-01-11 reduced.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF VETERANS AFFAIRS

EXPAND PRIMARY CARE

AT LAKE NONA (EAST)

ORLANDO VA MEDICAL CENTER

13800 VETERANS WAY, ORLANDO FL. 32827

PROJECT NUMBER - 675-100

CONSTRUCTION DOCUMENTS 100% FINAL SUBMISSION

27 441 A1A

PENSACOLA FORT WALTON

BEACH

PANAMA

CITY

TALLAHASSEE

COLUMBIA

UNION

BRADFORD

CLAY

ALACHUA

GAINESVILLE

GILCHRIST

LEVY MARION

PUTNAM

JACKSONVILLE

DAYTONA

BEACH

OCALA

ORLANDO

ORANGE

MELBOURNE

WINTER HAVEN

LAKELAND

NEW PORT

RICHEY

ST

PETERSBURG

SARASOTA

TAMPA

FT

PIERCE

WEST PALM

BEACH

FT

MYERS

NAPLES

FT

LAUDERDALE

MIAMI

MONROE

DADEMONROE

COLLIER BROWARD

COCOA

BRADENTON

ES

CA

M

BI

A

SANTA

ROSA

OKALOOSA WALTON

HOLMES

WASHINGTON

JACKSON

CALHOUN

BAY

GULF

GADSEN

LIBERTY

LEON

WAKULLA

FRANKLIN

JEFFERSON MADISON

TAYLOR

HAMILTON

SUWANNEE

LAFAYETTE

DIXIE

BAKER

NASSAU

DUVAL

ST.

JOHNS

FLAGLER

VOLUSIA

SEMINOLE

LAKECITRUS

HERNANDO

PASCO

SUMTER

BREVARD

OSCEOLA

POLK

PINELLAS

HILLSBOROUGH

MANATEE

SARASOTA

HARDEE

DESOTO

HIGHLANDS

OKEECHOBEE

INDIAN

RIVER

ST.

LUCIE

MARTIN

GLADESCHARLOTTE

LEE HENDRY PALM

BEACH

FLORIDA

KEYS

ANN

FISHER HOUSE

PARKING

19 SPACES

FISHER HOUSE

16BR

FFE=88.0

strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

U.S. Department of Veterans Affairs

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson

COMMISSIONING AGENT:

SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering

JANUARY 11, 2024

VOLUME 2

James P Strollo Digitally signed by James P Strollo Date: 2024.01.08 09:22:25 -05'00' strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

U.S. Department of Veterans Affairs

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson

COMMISSIONING AGENT:

SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering

01-11-2024

Osborn Engineering SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

NOTES AND LEGEND -

MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-001

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 Nicholas Stephenson

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

ROOM AIR CHANGE

CALCULATIONS - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 MN/NPS MN

MH-002

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

SCHEDULES - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-003

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

SCHEDULES - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 MN/NPS MN

MH-004

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 Nicholas Stephenson

3 16

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3, AREA B2 DEMOLITION

PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MD-100

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3, AREA B2 INTERSTITIAL

DEMOLITION PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MD-101

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4, AREA B2 DEMOLITION

PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MD-102

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4, AREA B2 INTERSTITIAL

DEMOLITION PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MD-103

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3, AREA B2 RENOVATION

PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-100

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3 CEILING, AREA B2

RENOVATION PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-100A

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3, AREA B2 INTERSTITIAL

RENO PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-101

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4, AREA B2 RENOVATION

PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-102

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4 CEILING, AREA B2

RENOVATION PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-102A

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4, AREA B2 INTERSTITIAL

RENOVATION PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-103

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 5, AREA B2 RENOVATION

PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-104

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

SECTIONS - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 MN/NPS MN

MH-201

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

EXIST'G ROOF

BELOW

Osborn Engineering SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 3, AREA B2 INTERSTITIAL

PIPING PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS NPS

MP-101

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

LEVEL 4, AREA B2 INTERSTITIAL

PIPING PLAN - MECHANICAL

EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS NPS

MP-102

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

DETAILS - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-501

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

PROVIDE SUPPORTS

TO PREVENT SAG

BETWEEN HANGERS

DUCT COLLAR

CONNECTING

STRAP

DIFFUSER

SUPPLY DUCT

MAIN

MINIMUM OF ONE DUCT DIAMETER

OF STRAIGHT DUCT TO INLET OF

DIFFUSER, OR PROVIDE EQUALIZING

GRID AT DIFFUSER

CONICAL SPIN IN

WITH DAMPER

HARD DUCT

ELBOW

FLEXIBLE DUCT, MAX. 5'-0" LONG.

SECURE INSIDE LINER WITH METAL HOSE

CLAMP RETAINING STRAPS. SECURE

OUTSIDE JACKET WITHNYLON TIE STRAPS. SEE

DIFFUSER TAGS FOR DUCT SIZES.

PIPE OR DUCT

INSULATION SHALL TERMINATE

AT EACH SIDE OF SLEEVE

FULL HEIGHT RATED PARTITION

EXTENDED FLOOR SLEEVE - 1/4" EXPOSED AREAS

AND 2" WET AREAS

VAPOR BARRIER (WHERE REQUIRED) AND INSULATION

TO BE FITTED TIGHT TO SLEEVE. SEAL WITH CONTINUOUS

BEAD OF NON-HARDENING CAULKING

FILL ENTIRE VOID BETWEEN SERVICE AND OPENING

WITH CAULK AND SEALANT AS SPECIFIED

SLEEVE

WALL

FLOOR

SLEEVE WHERE REQUIRED

BLOCK WALL

B

B

B

B

B

B

B

BB

B

B

B

B

B

B

B

B

B

B

B

PROVIDE TRANSITION FROM

TERMINAL TO DUCTWORK

VAV OR CV

TERMINAL

PROVIDE A MINIMUM OF FOUR DUCT

DIAMETERS OF STRAIGHT DUCT

AT EACH FLOOR TAKE-OFF

SU

PP

LY

D

UC

T

MA

IN

LINEAR SLOT, LINEAR BAR

OR FLOW BAR DIFFUSER

SUPPLY DUCT RISER

PROVIDE BALANCING DAMPER

EQUAL LENGTH

BRANCH DUCTS

TO SUPPLY AIR

OUTLETS

SUPPLY DUCT BRANCH

RIGID DUCTFLEX DUCT

(6'-0" MAX)

SUPPLY

GRILLE/

REGISTER

SIZE BY CFM

PROPORTION

NOTES:

1. REFER TO HVAC FLOOR PLANS FOR DUCT SIZES

2. REFER TO SCHEDULES FOR GRILLES, REGISTERS, DIFFUSERS AND TERMINAL SIZES AND TYPES

3. PROVIDE A MANUAL TYPE BALANCING DAMPER FOR EACH SUPPLY OUTLET AND RETURN INLET

4. ALL DUCT RUNOUTS TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK SIZE, UNLESS OTHERWISE

NOTED

5. FLEX DUCT WILL NOT BE ALLOWED ON RETURN OR EXHAUST DUCTWORK SYSTEMS

6. PROVIDE 12" AIR CUSHION AT THE END OF EACH SUPPLY MAIN AND BRANCH DUCT

7. INDIVIDUAL BRANCH BALANCING DAMPERS NOT REQUIRED FOR SUPPLY OR EXHAUST REGISTERS

CEILING

DIFFUSER

SUPPLY DUCT BRANCH

SU

PP

LY

D

UC

T

MA

IN

RETURN DUCT RISER

RE

TU

RN

D

UC

T

MA

INRETURN

DUCT BRANCH

RETURN

GRILLE

CEILING

GRILLE

OPEN ENDED

RETURN AIR

BRANCH DUCT

PROVIDE 1-1/2 RADIUS ELBOWS

FOR ALL DUCTWORK SYSTEMS

WHEREVER SPACE ALLOWS

PROVIDE 90° ELBOWS

WITH TURNING VANES IF

RADIUS ELBOWS WILL NOT FIT

EXHAUST

REGISTER

EX

HA

US

T

DU

CT

M

AI

N

EXHAUST

DUCT BRANCH

EXHAUST DUCT RISER

30° MIN

B

B BALANCING DAMPER

Osborn Engineering SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

DETAILS - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-502

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 o n e e ig h th in c h o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

10987654321

B

A

C

D

E

F

VA FORM 08 - 6231

1 AND 2

Mechanical, Electrical, Fire Protection & Plumbing:

FULLY SPRINKLERED

CONTROLS - MECHANICAL EXPAND PRIMARY CARE AT LAKE

NONA (EAST)

CONSTRUCTION

DOCUMENTS

100% FINAL SUBMISSION

JANUARY 11, 2024 NPS MR/NS

MH-601

675-100

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700

U.S. Department of Veterans Affairs

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson

COMMISSIONING AGENT:

SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering

15 W. Church Street, Suite 201 Orlando, Florida 32801-3350

407-630-6253 ENGINEERING

OSBORN

ELECTRICAL ABBREVIATIONS

A AMP

AA AUTOMATIC ALTERNATOR

AC ALTERNATING CURRENT

ACU AIR CONDITIONER UNIT

AF AMPERAGE FRAME

AFF ABOVE FINISHED FLOOR

ANN ANNUNCIATOR

AS AMMETER SWITCH

AT AMPERE TRIP

AX AUXILIARY DELAY

BKR BREAKER

CB CIRCUIT BREAKER

COL COLUMN

CL CENTERLINE

CKT CIRCUIT

CF(P OR L) CLOSE ON FALLING

(PRESSURE OR LEVEL)

CR(P OR L) CLOSE ON RISING

(PRESSURE OR LEVEL)

CH CONVECTION HEATER

COMPT COMPARTMENT

COND CONDUCTOR

CDT CONDUIT

C-( ) CONTRACT-( ) ID

CPT CONTROL POWER

TRANSFORMER

CR-( ) CONTROL RELAY-( ) ID

I/I CURRENT TO CURRENT

TRANSDUCER

I/P CURRENT TO PNEUMATIC

TRANSDUCER

CT CURRENT TRANSFORMER

D EXISTING TO BE DEMOLISHED

DC DIRECT CURRENT

DDC DIRECT DIGITAL CONTROL

DF DUST FILTER

DIA DIAMETER

DISTR DISTRIBUTION

DP DIFFERENTIAL PRESSURE

DS DISCONNECT SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

E EXISTING TO REMAIN

EBB ELECTRIC BASED BOARD

EC ELECTRICAL CONTRACTOR

ECH ELECTRIC CEILING HEATER

EDH ELECTRIC DUCT HEATER

EF ELECTRIC FAN

EMT ELECTRIC METALLIC TUBING

ER EXISTING TO BE REMOVED AND

RELOCATED

ETM ELAPSED TIME METER

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

F FLOW

FDR FEEDER

FLA FULL LOAD AMPS

FMC FLEXIBLE METALLIC CONDUIT

FOS FAST-OFF-SLOW

F-S FAST-SLOW

FT FEET

F-R FORWARD REVERSE

FR FRAME

FUSS FUSED SAFETY SWITCH

FVNR FULL VOLTAGE

NON-REVERSING

G GREEN

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GPM GALLONS PER MINUTE

GND GROUND

GRV GRAVITY RELIEF VENT

GUH GAS UNIT HEATER

HOA HAND-OFF-AUTOMATIC

HMI HUMAN MACHINE INTERFACE

HP HORSEPOWER

HV HOUSE VACUUM

HZ HERTZ

ID IDENTIFICATION NUMBER

IC INTERRUPTING CAPACITY

IF INFRARED HEATER

IMC INTERMEDIATE METAL

CONDUIT

INF IN LINE FAN

I/O INPUT/OUTPUT

IT INTERCHANGEABLE TRIP OR

INSTANTANEOUS TRIP

JB JUNCTION BOX

kcmil THOUSAND CIRCULAR MILS

KUH/EUH ELECTRIC UNIT HEATER

KVA KILOVOLT AMPERE

KV KILOVOLT

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

L LEVEL

LC LOUVER CONTROLLER

LFMC LIQUID-TIGHT FLEXIBLE

METAL CONDUIT

LM LOUVER MOTOR

LP( )-( ) LIGHTING CIRCUIT ( )

LP( ) LIGHTING PANELBOARD

LS LIMIT SWITCH

LV LOUVER

M MANUAL MOTOR STARTER

mA MILLIAMPERES

MC METAL CLAD CABLE

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MEZZ MEZZANINE

MF-( ) MAIN FEEDER-( ) ID

MGD MILLION GALLONS PER DAY

MS MOTOR STARTER

MTD MOUNTED

MTR MOTORIZED TIMING RELAY

MUAU MAKE UP AIR UNIT

MW MICROWAVE

MX MOTOR AUXILIARY RELAYS

(N) NEW

NAC NOTIFICATION APPLIANCE

CIRCUIT

NP NAMEPLATE

NF NON FUSED

NFSS NON FUSED SAFETY SWITCH

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

No. NUMBER

( )OL OVERLOAD ( ) NUMBER OF

P PRESSURE

( )P POLES ( ) NO OF POLES

Ø or PH PHASE

P/I PNEUMATIC TO CURRENT

TRANSDUCER

PLC PROGRAMMABLE LOGIC

CONTROLLER

PRE POWER ROOF EXHAUSTER

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PTAC PACKAGE TERMINAL

AIR CONDITIONER

PTR PNEUMATIC TIMING RELAY

PVC POLYVINYL CHLORIDE

RIGID CONDUIT

PVC-RSC PVC COATED RIGID

STEEL CONDUIT

PWV POWER WALL VENTILATOR

QTY QUANTITY

R RELOCATED

RAC RIGID ALUMINUM

RECPT RECEPTACLE

REQ REQUIRED

RMS ROOT MEAN SQUARE

RSC RIGID STEEL CONDUIT

RTU REMOTE TERMINAL UNIT

SAF SUPPLY AIR FAN

STP SHIELDED TWISTED PAIR

SL STOP LOCKOUT

SMC SMART MOTOR CONTROLLER

SPDT SINGLE POLE, DOUBLE THROW

SS SELECTOR SWITCH

S/S START/STOP

S/SL START/STOP LOCKOUT

SV SOLENOID VALVE

SYM SYMMETRICAL

T or T'STAT THERMOSTAT

T-( ) TELEPHONE CONDUIT-( )

TCC TIME-CLOSE CONTACT

TEMP TEMPERATURE

TC TEMPERATURE CONTRACTOR

TOC TIME-OPEN CONTACT

TR TIMING RELAY

TRI SHIELDED TRIPLE CABLE

TS TEMPERATURE SWITCH

TSP TWISTED SHIELDED PAIR

TYP TYPICAL

UF UNDERGROUND FEEDER

UH UNIT HEATER

VA VOLT - AMPERE

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

VFD VARIABLE FREQUENCY DRIVE

VS VOLTMETER SWITCH

VT VOLTAGE TRANSFORMER

W WATT

WH WATER HEATER

WP WEATHERPROOF

ELECTRICAL LIGHTING SYMBOLS LEGEND

2X2 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

2X2 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - TYPE AS SPECIFIED

1X4 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

1X4 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - TYPE AS SPECIFIED

4' LINEAR INDUSTRIAL STRIP FIXTURE - TYPE AS SPECIFIED

EXIT SIGN-CEILING MOUNTED - TYPE AS SPECIFIED,

ARROWS AS SHOWN ON PLANS

EXIT SIGN-WALL MOUNTED - TYPE AS SPECIFIED, ARROWS

AS SHOWN ON PLANS

2X2 LIFE SAFETY BRANCH FIXTURE - RECESSED, SURFACE,

OR PENDANT MOUNTED - TYPE AS SPECIFIED

1X4 LIFE SAFETY BRANCH FIXTURE - RECESSED, SURFACE,

OR PENDANT MOUNTED - TYPE AS SPECIFIED

FAN SWITCH (48" AFF)

WALL MOUNTED OCCUPANCY SENSOR SWITCH; DUAL

TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

CEILING MOUNTED OCCUPANCY/VACANCY SENSOR;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

DAYLIGHT SENSOR

LIGHTING RELAY

(UL924 GENERATOR TRANSFER DEVICE)

TIMECLOCK (REFER TO PLANS)

PHOTOCELL (REFER TO PLANS)

ROOM CONTROLLER (REFER TO PLANS)

SINGLE-POLE, DOUBLE-POLE, 3-WAY AND

4-WAY SWITCHES (48" AFF)

LOCAL WALL DIMMER SWITCH (48" AFF)

4' CRITICAL BRANCH LINEAR INDUSTRIAL STRIP FIXTURE -

TYPE AS SPECIFIED

4' LIFESAFETY BRANCH LINEAR INDUSTRIAL STRIP FIXTURE -

TYPE AS SPECIFIED

RECESSED CAN LIGHT - TYPE AS SPECIFIED

RECESSED CRITICAL BRANCH CAN LIGHT - TYPE AS

SPECIFIED

S S S S

S

S

OS VS

DS

RC

LR

T

PC

(REFER TO LIGHTING FIXTURE SCHEDULE FOR MORE INFORMATION)

F

D

DUPLEX RECEPTACLE (18" AFF)

DOUBLE DUPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE -

CEILING MOUNTED

DOUBLE DUPLEX RECEPTACLE -

CEILING MOUNTED

SIMPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE 6" ABOVE COUNTER BACKSPLASH

OR 48" AFF

DUPLEX RECEPTACLE - FLOOR MOUNTED

SPECIAL PURPOSE RECEPTACLE, NEMA TYPE AS NOTED ON

PLANS (18" AFF)

DOUBLE DUPLEX RECEPTACLE - FLOOR MOUNTED

OCCUPANCY CONTROLLED RECEPTACLE

ELECTRICAL POWER SYMBOLS LEGEND

(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)

USB RECEPTACLE COMBINATION

PANELBOARD

TRANSFORMER

MOTOR CONNECTION - HORSE POWER AS NOTED

DISCONNECT SWITCH - FUSED - FRAME/FUSE/POLES/NEMA

AS NOTED ON PLANS, ALL DISCONNECTS SHALL BE HEAVY

DUTY AND NEMA TYPE 1 U.O.N.

DISCONNECT SWITCH - MOTOR/STARTER COMBINATION

NEMA SIZE TO MATCH HP SHOWN ON PLANS AT THE

SPECIFIED VOLTAGE, HEAVY DUTY

VARIABLE FREQUENCY DRIVE - SEE SPECIFICATIONS

JUNCTION BOX OR PULL BOX - SINGLE GANG U.O.N.

WALL MOUNTED JUNCTION BOX OR PULL BOX - SINGLE

GANG U.O.N.

TOP SWITCHED OUTLET, AS NOTED ON PLANS

RANGE OUTLET, 4" AFF TO CENTER. 120/208V, 1 PHASE, 4

WIRE, 50 AMPS

DRYER OUTLET, 48" AFF TO CENTER. 120/208V, 1 PHASE, 4

WIRE, 30 AMPS

TOP AND BOTTOM SWITCHED OUTLET, AS NOTED ON PLANS

VFD

SM

30/15/2/3R

DISCONNECT SWITCH - NON-FUSED -

FRAME/FUSE/POLES/NEMA AS NOTED ON PLANS, ALL

DISCONNECTS SHALL BE HEAVY DUTY AND NEMA TYPE 1

U.O.N.

30/2/3R

MOTOR RATED SWITCH WITH THERMAL OVERLOADS FOR

FRACTIONAL HORSEPOWER MOTORS

FLOOR BOX OR POKE THRU JUNCTION OR PULL BOX

VAV WITH ELECTRIC HEAT - KW AS SHOWN

ELECTRIC DUCT HEATER - KW AS SHOWN

VAV X-X

XX KW

EDH X-X

XX KW

J

J

HP

J

D

R

1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS FOR

REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT APPEAR ON THE

FOLLOWING DRAWINGS.

2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON EXISTING

UTILITIES WITH OWNER REPRESENTATIVES IN ORDER TO MINIMIZE IMPACT TO OTHER

AREAS.

3. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL

CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING

JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING DOCUMENTS AND

CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

4. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE WORK

THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND VERIFY FIELD

CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA

COST TO THE OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE

ATTENTION OF THE ARCHITECT/ENGINEER.

5. ALL WIRING SHALL BE IN CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM

CONDUCTOR SIZE SHALL BE #12 AWG. ALL NEW CIRCUITS SHALL BE PROVIDED WITH AN

INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTOR WITH THE PHASE CONDUCTOR.

6. ALL CONDUITS INSTALLED INTERIOR SHALL BE EMT. ALL CONDUITS INSTALLED EXTERIOR

UNDERGROUND SHALL BE PVC SCHEDULED 40. ALL CONDUITS INSTALLED EXTERIOR AND

EXPOSED SHALL BE RGS.

7. CONDUCTORS #10 AND SMALLER SHALL BE SOLID COPPER. CONDUCTORS #8 AND

LARGER SHALL BE STRANDED COPPER. UNLESS NOTED OTHERWISE, CONDUCTORS

INSULATION SHALL BE DUAL RATED AT THHN/THWN.

8. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY THE

CONTRACTOR UNLESS NOTED OTHERWISE.

9. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER EQUIPMENT AND

DEVICE MANUFACTURER RECOMMENDATIONS.

10. CONTRACTOR SHALL PROVIDE SUBMITTALS TO ARCHITECT/ENGINEER FOR REVIEW AND

APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN THE SUBMITTAL

REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS, DIMENSIONS, WIRING DIAGRAMS,

ACCESSORIES, OPERATION MANUALS, AND ALL NECESSARY INFORMATION FOR

REVIEWER TO MAKE A SOUND EVALUATION.

11. PROVIDE STARTUP OF ALL ELECTRICAL SYSTEMS AND COORDINATE WITH

ARCHITECT/ENGINEER FOR OWNER STARTUP WITNESSING.

12. PROVIDED LAMINATED PLASTIC NAMEPLATES FOR EACH EQUIPMENT ENCLOSURE. EACH

NAMEPLATE IDENTIFY EQUIPMENT FUNCTION, PANELBOARD CONNECTED AND CIRCUIT

NUMBER. NAMEPLATE SHALL BE MELAMINE PLASTIC (0.125 INCHES THICK), WHITE

LETTERS ON BLACK BACKGROUND. MINIMUM SIZE OF LETTERS SHALL BE 2.5 INCHES. IN

ADDITION TO EQUIPMENT TAGGING, CONTRACTOR SHALL PROVIDE ARC-FLASH WARNING

SIGNS FOR PANELBOARDS.

13. PROVIDE COMPUTER PRINTED ON WHITE WRAPAROUND PAPER WITH CLEAR PLASTIC

PROTECTION TAIL FOR ALL WIRE MARKERS. MARKER SHALL STATE PANELBOARD NAME

AND CIRCUIT NUMBER ON ALL WIRES IN JUNCTION/PULL BOXES AND IN EQUIPMENT

TERMINAL BOXES.

14. PROVIDE PUNCHED TAPE LABELS ON ALL WIRING DEVICES FOR IDENTIFICATION. SHALL BE

½” BLACK TAPE WITH WHITE RAISED LETTERS. TAPE LABELS SHALL STATE PANELBOARD

NAME AND CIRCUIT NUMBER.

15. PROVIDE DIRECTORIES ON ALL PANELBOARDS. ALL LOADS SHALL BE BALANCED TO

WITHIN 10%.

16. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET OF RECORD

DRAWINGS TO THE OWNER AT THE END OF THE CONSTRUCTION.

17. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND FREE OF DEFECTS.

ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION (NEMA) STANDARDS AND SHALL BE UL LABELED. ALL

ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A WORKMANLIKE

MANNER.

18. ALL CONNECTORS AND SPLICES FOR CABLE SIZE #10 AWG AND SMALLER SHALL BE

INSULATED, PRESSURE-TYPE. FOR LARGER SIZE CONDUCTORS USE BOLTED CLAMPS

WITH INSULATING TAPE.

19. PROVIDE INSULATION AND CONTINUITY TEST OF ALL 1000V AND LESS WIRES AND CABLES.

USE TESTING PROCEDURES DESCRIBED IN INTERNATIONAL ELECTRICAL TESTING

AGENCY (NETA) STANDARDS. REPLACE ANY CABLES WITH INSULATION RESISTANCE LESS

THAN 100 MEGA OHMS (MOHMS). TEST ALL GROUND FAULT CIRCUIT INTERRUPTING (GFCI)

RECEPTACLES. TEST ALL GROUNDING ELECTRODE SYSTEMS WITH FALL OF POTENTIAL

METHOD. MAKE RESISTANCE MEASUREMENTS 48 HOURS AFTER LAST RAIN FALL.

MAXIMUM RESISTANCE TO GROUND SHALL BE 5 OHMS.

20. PRIOR TO PASSING FINAL INSPECTION, A THIRD PARTY CONTRACTOR SHALL PROVIDE

EVIDENCE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN TESTED TO ENSURE THAT

CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND

IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION

DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS. FUNCTIONAL TESTING SHALL BE IN

ACCORDANCE WITH FLORIDA BUILDING CODE - ENERGY CONSERVATION 6TH EDITION

(2017) - SECTIONS C408.3.1.1 AND C408.3.1.2 FOR THE APPLICABLE CONTROL TYPE.

21. CONTRACTOR SHALL PROVIDE RECORD DOCUMENTS, DRAWINGS AND MANUALS TO

OWNER WITHIN 30 DAYS AFTER SYSTEM ACCEPTANCE PER FLORIDA BUILDING CODE -

ENERGY CONSERVATION 6TH EDITION (2017) - SECTIONS C405.6.4.

22. PANELBOARDS SHALL BE SUPPLIED WITH BOLT-ON CIRCUIT BREAKERS. ALL BUSBARS,

PHASE, NEUTRAL, GROUND IN PANELBOARDS SHALL BE TIN-PLATED ALUMINUM.

GENERAL PROJECT NOTES

FIRE ALARM SYMBOLS LEGEND

MANUAL PULL STATION (46" AFF)

BELL/STROBE LIGHT COMBINATION (80" AFF)

STROBE LIGHT (80" AFF)

HORN (80" AFF)

HORN/STROBE LIGHT COMBINATION (80" AFF)

SPEAKER (80" AFF)

SPEAKER/STROBE COMBINATION (80" AFF)

SMOKE DETECTOR TIED TO FACP -

CEILING MOUNTED; WALL MOUNTED

HEAT DETECTOR TIED TO FACP -

CEILING MOUNTED; WALL MOUNTED

DUCT DETECTOR

TAMPER SWITCH

FLOW SWITCH

MAGNETIC DOOR HOLDER (72" AFF)

FIRE ALARM CONTROL PANEL SURFACE OR RECESSED

FIRE ALARM REMOTE ANNUNCIATOR SURFACE OR

RECESSED

MINI HORN (80" AFF)

COMBO SMOKE/CARBON MONOXIDE DETECTOR TIED TO

FACP - CEILING MOUNTED; WALL MOUNTED

F

S

S

H

H

S

S

M

FS

DH

FACP FACP

FARA FARA

COMMUNICATION SYMBOLS LEGEND

DATA OUTLET (18" AFF)

DATA OUTLET - CEILING MOUNTED

CABLE TV OUTLET (18" AFF); PROVIDE 1 F TYPE CONNECTOR

COMMUNICATION CABLE TRAY MOUNTED ABOVE

SUSPENDED CEILING - SIZE AS NOTED ON PLANS

(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)

ABOVE COUNTER DATA OUTLET (6" ABOVE COUNTER

BACKSPLASH OR 48" AFF)

C

DATA OUTLET - RECESSED FLOOR BOX OR POKE THRU

STAFF TERMINAL (TBD)

CODE BLUE STATION (46" AFF)

TOILET NURSE CALL (46" AFF)

NURSE CALL MASTER

NURSE CALL TERMINAL CABINET W/ BRANCH REGIONAL

CONTROLLERS, POWER SUPPLIES, NETWORK SWITCHES

NURSE CALL SYMBOLS LEGEND

NA

C

MS

FIRE ALARM SYSTEM

FIRE ALARM DEVICES ARE SHOWN FOR REFERENCE ONLY. FULLY FUNCTIONAL FIRE ALARM

SYSTEM TO INCLUDE FIRE CONTROL PANELS, DIALERS, EXPANDER MODULES,

ANNUNCIATION AND NOTIFICATION DEVICES, WIRING, PROGRAMMING, TESTING, WARRANTY

AND COMMISSIONING SHALL BE INCLUDED IN THIS PROJECT BID. CONTRACTOR SHALL

PROVIDE SIGNED AND SEALED SHOP DRAWINGS SHOWING ALL DEVICES, EQUIPMENT,

CIRCUITS AND CALCULATIONS REQUIRED FOR PERMITTING. COORDINATE WITH AHJ IF

SEPARATE PERMIT IS REQUIRED OR SUBMIT UNDER THIS POINT.

BID DEDUCT ALTERNATES:

BID DEDUCT ALTERNATE NO.1:

DO NOT BUILD OUT THE 4TH FLOOR INTERIOR. LEAVE IT AS A

MINIMALLY CONDITIONED SPACE USING 4 VAV’S WITH THEIR POWER AND

HYDRONIC PIPING, AND WITH 2 RUNS OF FLEX-DUCT 20’ MAXIMUM

LENGTH. SET 4TH FLOOR AHU TO MINIMUM SPEED AND CONTROL

HUMIDITY. DO BUILD ELECTRICAL AND PLUMBING, AND THE 4 VAV

SYSTEMS STUBBED UP OR DOWN FROM INTERSTITIAL SPACES SERVING

THE AREA AND DO BUILD MEP SERVICES THAT PASS THROUGH THE 4TH

FLOOR, SUCH AS ROOF DRAINS. DO NOT DEMOLISH EXISTING 4TH

FLOOR AREAS BUT LEAVE AS IS. PLUMBING: DO NOT PROVIDE FIXTURES

OR PIPING EXCEPT TO TAP OFF EXISTING AND CAP. ELECTRICAL:

PROVIDE CODE-MINIMUM LIGHTING AND FIRE ALARM LOCATIONS.

SPRINKLERS: ARRANGE FEEDS AND HEADS AS NEEDED TO COVER THE

ENTIRE OPEN INTERIOR SPACE.

BID DEDUCT ALTERNATE NO. 2:

DO NOT BUILD THE 4TH FLOOR, 4TH INTERSTITIAL FLOOR AND NEW

ROOF SLAB ABOVE THE INTERSTITIAL, INCLUDING COLUMNS, BEAMS

GIRDERS, PRE-CAST CONCRETE EXTERIOR WALLS AND THEIR

EXTERIOR WINDOW FRAMES AND GLASS. THE RESULTANT ROOF OVER

THE NEW 3RD FLOOR INTERSTITIAL AREAS WILL HAVE THE ROOFING

AND PARAPET MATERIALS AND DETAILS AS SHOWN FOR THE 4TH

FLOOR. RETAIN EXISTING 4TH FLOOR INTERIOR SPACES IN THEIR

CURRENT STATES, STRUCTURE, SYSTEMS AND EXTERIOR WALLS,

LOCATING THE MECHANICAL PENTHOUSE EXPANSION AS SHOWN. AT

THE PENTHOUSE ADDITION, DELETE THE EXHAUST FAN(S) ASSOCIATED

WITH THE PROJECT’S 4TH FLOOR WORK INCLUDING POWER FEEDS,

PENETRATIONS THROUGH THE EXISTING ROOF AND THE NEW

PENTHOUSE ADDITION ROOF, AND INTERIOR AND EXTERIOR

DUCTWORK. ALSO DELETE AHU-4 WITH ITS ELECTRICAL AND

HYDRONICS CONNECTIONS, DUCTWORK TO/FROM NEW LOUVERS THAT

SHALL REMAIN (EXCEPT TO CLOSE EACH DUCT OPENING AT EACH

LOUVER), DUCTWORK TO THE EXISTING 4TH FLOOR ROOF, AND

PENETRATIONS THROUGH THE EXISTING 4TH FLOOR ROOF.

BID DEDUCT ALTERNATE NO. 3:

DELETE HANDRAILS AT THE 3RD FLOOR.

BID DEDUCT ALTERNATE NO.4:

DELETE HANDRAILS AT THE 4TH FLOOR IF ALTERNATES 1 OR 2 ARE NOT

INCORPORATED.

BID DEDUCT ALTERNATE NO. 5:

DELETE WALL GUARDS AT THE 3RD FLOOR.

BID DEDUCT ALTERNATE NO. 6:

DELETE WALL GUARDS AT THE 4TH FLOOR IF ALTERNATES 1 OR 2 ARE

NOT INCORPORATED.

BID DEDUCT ALTERNATE NO. 7:

DELETE CORNER GUARDS AT THE 3RD FLOOR.

BID DEDUCT ALTERNATE NO. 8:

DELETE CORNER GUARDS AT THE 4TH FLOOR IF ALTERNATES 1 OR 2

ARE NOT INCORPORATED.

BID ALTERNATE NO. 9:

AT THE 3RD FLOOR, NO DEMOLITION OR NEW CONSTRUCTION AT

EXISTING ROOM CHIEF OFFICE 3J902. IT WILL REMAIN AS IS AND NOT

CHANGE TO LOUNGE, CLINICAL STAFF. FOR RENOVATION WORK,

CHANGE ROOM NAMED WORK STATIONS BETWEEN GRIDS D7 AND D8 TO

BE NAMED LOUNGE, CLINICAL STAFF AND INSTALL ALL THE LOUNGE’S

ITEMS IN THIS LOCATION. REFLECT NAME CHANGE ON THE ROOM FINISH

SCHEDULE.

WAP WIRELESS ACCESS POINT

TO BE DETERMINED BY THE VA/OIT.

DUTY STATION (40" AFF)ND

4 LAMP CEILING MOUNTED ZONE LIGHTZC

4 LAMP CEILING MOUNTED CORRIDOR LIGHTNC

4 LAMP WALL MOUNTED CORRIDOR LIGHT

STAFF ASSIST STATION (40" AFF)NP

TP

NCEC

GENERAL SYMBOLS

KEY NOTE INDICATOR

DRAWING REVISION INDICATORX

X X X X

LINE TYPES

NEW WORK SCOPE OF WORK

EXISTING SCOPE OF WORK

DEMOLITION SCOPE OF WORK

FUTURE SCOPE OF WORK

NOT IN SCOPE OF WORK

Sheet List Table Sheet Number Sheet Title

E-001 ELECTRICAL GENERAL NOTES & LEGENDS

ED-101 LEVEL 3, AREA B2 DEMOLITION PLAN - ELECTRICAL

ED-102 LEVEL 4, AREA B2, DEMOLITION PLAN - ELECTRICAL

EJ-101 LEVEL 5, AREA B2 RENOVATION PLAN - LIGHTNING PROTECTION

EF-100 LEVEL 3, AREA B2 RENOVATION PLAN - FIRE ALARM

EF-101 LEVEL 3, AREA B2 INTERSTITIAL PLAN - FIRE ALARM

EF-102 LEVEL 4, AREA B2 RENOVATION PLAN - FIRE ALARM

EF-103 LEVEL 4, AREA B2 INTERSTITIAL PLAN - FIRE ALARM

EF-104 LEVEL 5, AREA B2 RENOVATION PLAN - FIRE ALARM

EL-100 LEVEL 3, AREA B2 RENOVATION PLAN - LIGHTING

EL-101 LEVEL 3, AREA B2 INTERSTITIAL PLAN - LIGHTING

EL-102 LEVEL 4, AREA B2 RENOVATION PLAN - LIGHTING

EL-103 LEVEL 4, AREA B2 INTERSTITIAL PLAN - LIGHTING

EL-104 LEVEL 5, AREA B2 RENOVATION PLAN - LIGHTING

EP-100 LEVEL 3, AREA B2 RENOVATION PLAN - POWER

EP-101 LEVEL 3, AREA B2 INTERSTITIAL PLAN - POWER

EP-102 LEVEL 4, AREA B2 RENOVATION PLAN - POWER

EP-103 LEVEL 4, AREA B2 INTERSTITIAL PLAN - POWER

EP-104 LEVEL 5, AREA B2 RENOVATION PLAN - POWER

EM-101 LEVEL 3, AREA B2 RENOVATION PLAN - MECHANICAL POWER

EM-102 LEVEL 4, AREA B2 RENOVATION PLAN - MECHANICAL POWER

ET-100 LEVEL 3, AREA B2 RENOVATION PLAN - TELECOMMUNICATIONS

ET-101 LEVEL 3, AREA B2 INTERSTITIAL PLAN - TELECOMMUNICATIONS

ET-102 LEVEL 4, AREA B2 RENOVATION PLAN - TELECOMMUNICATIONS

ET-103 LEVEL 4, AREA B2 INTERSTITIAL PLAN - TELECOMMUNICATIONS

EY-100 LEVEL 3, AREA B2 RENOVATION PLAN - AUXILIARY SYSTEM

EY-101 LEVEL 3, AREA B2 INTERSTITIAL PLAN - AUXILIARY SYSTEM

EY-102 LEVEL 4 AREA B2 RENOVATION PLAN - AUXILIARY SYSTEM

EY-103 LEVEL 4, AREA B2 INTERSTITIAL PLAN - AUXILIARY SYSTEM

E-400 ENLARGED ELECTRICAL AND COMMUNICATION ROOMS

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-503 BASIS OF DESIGN LIGHTING SPEC AND CONTROLS SCHEDULE

E-600 PARTIAL ELECTRICAL RISER DIAGRAM

E-700 ELECTRICAL PANEL SCHEDULES

E-701 ELECTRICAL PANEL SCHEDULES

PUBLIC SAFETY DISTRIBUTED ANTENNA SYSTEM AND UHF

DAS.

DAS

8" CEILING MOUNTED PAGING SPEAKER; PROVIDED WITH

BAFFLE, GRILL AND MATCHING TRANSFORMER

CCTV CAMERA - FIXED

SECURITY/DURESS-ALARM BUTTON WALL MOUNTED 40"

(1000 MM) UNLESS OTHERWISE NOTED.

ELECTRIC STRIKE MORTICED, FAIL SECURE; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER

RING, 3/4" CONDUIT WITH PULL STRING TO DOOR

CONTROLLER.

ELECTRIC MORTICE LOCK; PROVIDE DOUBLE GANG BACK

BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER. ONE HINGE SERVES

AS A WIRE PASS AND A DOOR CLOSER.

CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER RING,

3/4" CONDUIT WITH PULL STRING TO DOOR CONTROLLER

AUTOMATIC DOOR OPENER; PROVIDE DOUBLE GANG BACK

BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

STRING

DOOR POSITION SWITCH; PROVIDE SINGLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH PULL

STRING TO SECURITY PANEL

DB

CCTV CAMERA - MULTIVIEW 360º

360º

CCTV CAMERA - MULTIVIEW 270º

270º

AUXILIARY SYSTEM SYMBOLS LEGEND

ADA HANDICAP DOOR BUTTON, FLUSH MOUNTED AT 42" AFF;

PROVIDE DOUBLE GANG BACK BOX WITH SINGLE GANG

PLASTER RING, 3/4" CONDUIT WITH PULL STRING TO DOOR

CONTROLLER

FSD FIRE SMOKE DAMPER, PROVIDE WITH RELAY MODULE TO BE

TIED TO FACP

T-C3B2LND1

(E)

C-H

PAT TLT

3H311

CODING

3H309

PAT TLT

3H802

SHARED OFFICE

3J219

INTERN SOC

WRK

3J208

SOCIAL WRKR

3J203

SOCIAL WRKR

3J206

CONFERENCE

ROOM

3J209

PRGM SUPP

3J201

STF TLT

3J216

STF TLT

3J218

ELEC

3J202

COMM

3H801

ELEC

3H915

EXAM

3H816

EXAM

3H814

EXAM

3H812

EXAM

3H810

EXAM

3H808

TREATMENT

3H308

CLEAN

3H815

SOILED

3H813

OFFICE

3H811

SECRETARY

3J213

CORR

3HC08

CORR

3JC02

OFFICE

3J903

PROCEDURE

3H807

DIETICIAN

3H805

TLT

3H807A

COPY/SUPPORT

3J214

OFFICE

CLERK/WAIT

3J101

STAIR 3BST2

3HS02

MECH SHAFT

STOR

3J204

OFFICE, CHIEF

3J211

J J

C3CB19/20

PP TV

TV

OS

OS

OS

OS

OS

OS

WAP

WAP

C3B2LN3(E)

C3B2LC1

T-C3B2LND1

C3B2LND1

(E)

(E)

(E)

C3B2LN1(E)

C3B2HN1(E)

RELAY PANEL

C3B2RPN1

(E)

CDBD-N1 (E)

(E)

(E) (E)

(E)

(D)

(D) (D)

(D) (D)

(D)

(D)(D)

(D)

(D)

(D)

(D)

(D) (D) (D) (D)

(D) (D)

(D)

(D) (D)(D)

(D)

(D)

(D)(D)(D) (D)

(D)

(D)

(D) (D)

(D)

(D)

(D)(D)(D)

(D)

(D)(D)

(D) (D)(D)(D)

(D) (D)(D) (D)

(D)

(D)

(D)(D)

(D)

(D)

(D) (D)

(D)(D)

(D)

(D) (D)

(D) (D)

(D)

(D)(D)

(D)

(D) (D)

(D)

(D) (D) (D)

(D)(D)(D) (D)

(D) (D)

(D)

(D) (D) (D)

(D)

(D)(D)

(D)

(E)

(E)

(E)

(E)

(E) (E)

(E)

(E) (E)

(E)

(E)

(E)

(D) (D)

(D)

(D)

(D)

U.S. Department of Veterans Affairs

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson

COMMISSIONING AGENT:

SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering

15 W. Church Street, Suite 201 Orlando, Florida 32801-3350

407-630-6253 ENGINEERING

OSBORN

ED-101

1 LEVEL 3, AREA B2 DEMOLITION PLAN - ELECTRICAL

1/8'' = 1'-0''

LIGHTING DEMO KEYNOTES

3. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL

DETAIL ON PLANNED/REQUIRED DEMOLITION IN THIS AREA OF WORK.

THERE SHALL BE NO DEMOLITION OF ANY LIGHT FIXTURES. CONTRACTOR

SHALL PROVIDE TEMPORARY SUPPORT FOR LIGHT FIXTURES IN CEILING

GRID WHERE ACCESS IS REQUIRED. TRACE EXISTING FIXTURES TO PANEL

AND CIRCUITS AND DISCONNECT ALL WIRING TO EXISTING FIXTURES.

ONCE WORK IN THIS AREA, CORRIDOR EJC02, HAS BEEN COMPLETED,

INSTALL NEW LIGHT FIXTURES IN NEW CEILING TILES AND RE-CONNECT

TO EXISTING CIRCUITS AND SWITCH.

X

GENERAL LIGHTING DEMO NOTES

A. FOR THE THIRD LEVEL,THE DESIGN INTENT IS TO DEMOLISH ALL LIGHTING

FIXTURES AND DEVICES IN AREA OF SCOPE EXCEPT FOR CORRIDOR

EJC02. HOWEVER, DUE TO RE-WORK OF MECHANICAL AND PLUMBING

OVERHEAD IN CEILING OF CORRIDOR EJC02, LIGHT FIXTURES SHALL BE

DISCONNECTED, REMOVED, CLEANED AND STORED IN A SAFE LOCATION

TO BE LATER RE-INSTALLED IN THE EXACT SAME LOCATION ONCE

CONSTRUCTION IS COMPLETED.

B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.

COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH

THE VA/COR.

C. ALL DEMOLISHED LIGHTING FIXTURES AND DEVICES SHALL HAVE BOXES,

DEVICES, CONDUIT AND WIRING REMOVED BACK TO SOURCE.

D. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED WIRING, CONDUITS AND DEVICES BACK TO THE SOURCE.

E. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED

AREAS.

F. PROVIDE WIRE, JUNCTION BOXES, CONDUIT, ETC. AS REQUIRED TO

MAINTAIN CONTINUITY TO EXISTING TO REMAIN EQUIPMENT, DEVICES,

ETC.

G. ALL DEMOLISHED EQUIPMENT, FIXTURES, DEVICES SHALL BE PRESENTED

TO THE VA FOR FIRST RIGHT OF REFUSAL.

H. EXISTING CONDITIONS SHOWN ARE BASED ON 'AS-BUILT' DRAWINGS AND

FIELD OBSERVATION. ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR PRIOR TO

DISTURBING EXISTING INSTALLATION.

I. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS

AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL

EQUIPMENT AND DEVICES SHOWN TO BE DEMOLISHED.

J. ALL EXISTING LIFE SAFETY LIGHTING LOCATED IN AREAS THAT ARE

EXISTING TO REMAIN, SHALL REMAIN OPERATIONAL DURING ALL PAHSES

OF CONSTRUCTION.

GENERAL POWER DEMO NOTES

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.

COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH

THE VA/COR.

B. ALL DEVICES INDICATED ON PLANS SHALL BE DEMOLISHED WITHIN SCOPE

OF WORK, UNLESS OTHERWISE NOTED - EXISTING TO REMAIN (E). ITEMS

BEING DEMOLISHED (D) SHALL HAVE BOXES, DEVICES, CONDUIT AND

WIRING REMOVED BACK TO SOURCE.

C. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED WIRING.

D. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED

AREAS.

E. PROVIDE WIRE, JUNCTION BOXES, CONDUIT, ETC. AS REQUIRED TO

MAINTAIN CONTINUITY TO EXISTING TO REMAIN EQUIPMENT, DEVICES, ETC.

F. ALL DEMOLISHED EQUIPMENT, FIXTURES, DEVICES SHALL BE PRESENTED

TO THE VA FOR FIRST RIGHT OF REFUSAL.

G. EXISTING CONDITIONS SHOWN ARE BASED ON 'AS-BUILT' DRAWINGS AND

FIELD OBSERVATION. ELECTRICAL CONTRACTOR SHALL VERIFY EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR PRIOR TO

DISTURBING EXISTING INSTALLATION.

H. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS

AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL

EQUIPMENT AND DEVICES SHOWN TO BE DEMOLISHED.

I. ALL FIRE ALARM DEVICES IN AREAS THAT ARE EXISTING TO REMAIN SHALL

BE DISABLED AND REMAIN NOT OPERATIONAL IN CONSTRUCTION AREAS

BY EACH PHASE.

J. ALL EXISTING CIRCUIT CONNECTIONS INDICATED IN THIS PLAN SHALL BE

VERIFIED BEFORE DISTURBING ANY ELECTRICAL CONNECTION AND

DEMOLISHING EQUIPMENT.

K. ELECTRICAL CONTRACTOR SHALL INSPECT AND REPLACE ALL DAMAGED

PANEL COVERS.

L. GENERAL CONTRACTOR SHALL INCLUDE WIRING AND CONDUIT TO KEEP

FUNCTIONAL SERVICES ON IN OTHER EXISTING AREAS.

POWER DEMO KEYNOTES

1. ELECTRICAL CONTRACTOR SHALL DEMOLISH ANY DEVICES ALONG DEMO

WALL. MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES

CONNECTED TO ELECTRICAL CIRCUIT. GENERAL CONTRACTOR SHALL

INCLUDE WIRING AND CONDUIT TO KEEP SERVICES FUNCTIONAL IN

EXISTING AREAS NOT IN SCOPE.

2. ALL CEILING DEVICES IN CORRIDOR EJC02 ARE EXISTING TO REMAIN.

ELECTRICAL CONTRACTOR SHALL TEMPORARILY REMOVE AND STORE IN

SAFE LOCATION. DISCONNECT ELECTRICAL DEVICES FROM EXISTING

SOURCE AND MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES.

X

BID DEDUCT ALTERNATES:

THERE ARE NINE (9) DEDUCT ALTERNATES, DESCRIBED IN

SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS AND

E-001. THE DRAWINGS AND SPECIFICATIONS SHOW THE FULL SCOPE

OF THE PROJECT WORK, AND MAY NOT ADDITIONALLY DESCRIBE

THESE ALTERNATES. BIDDERS MUST PROVIDE DEDUCT ALTERNATE

DOLLAR AMOUNTS THAT COINCIDE WITH AND REPRESENT ALL

REDUCED LABOR AND MATERIAL COSTS OF EVERY TRADE AND PARTY

AFFECTED BY EACH DEDUCT ALTERNATE.

LINE TYPES

NEW WORK SCOPE OF WORK

EXISTING SCOPE OF WORK

DEMOLITION SCOPE OF WORK

FUTURE SCOPE OF WORK

NOT IN SCOPE OF WORK

C4CB17/18

OPEN

ROOF

4H217

TRAINEE

LOUNGE

4H901

ELECTRICAL

ROOM

WAP

WAP

OS

WAP

OS

F

OS

WAP

OS

C4B2LN1(E)

T-C4B2LND1

C4B2LC1

C4B2LN3

C4B2HN1

C4B2LND1

(E)

(E)

(E)

(E)

(E)

RELAY

PANEL

C42BRPN1

(E)

CDBD-N1

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E)

(E) (E)

(D) (D) (D) (D)

(D)(D)(D)

(D)

(D)

(D)

(D) (D)(D)(D)

(D) (D)

(D) (D) (D) (D)

(D)(D)

(D)(D)(D)

(D)

(D)

(D) (D) (D)

(D)

(D)

(D)(D)

(D)

(D)

(D) (E)(E)(E) (E)

(D)(D)(D)(D)

(E)

(D)

(E)

(E)

(D)

(D)

(D)(D)(D) (D)

(D) (D)(D) (D)

(D)

(D)

(D)

(D)(D)(D) (D)(D)

(D) (D)

(D)

(D)

(D)(D) (D)(D) (D)

(D)(D)(D) (D)

(D)

(D)

(D) (D)

(D)

(D)

(D)(D)(D)

(D)

(D) (D)

(D) (D) (D)

(D)(D)

(D)

(D)

(D)

(D)(D)

(E)

(D)

4H217

TRAINEE

LOUNGE

4H816

STU/TRAINEE

4H203A

SECRETARY

MECH.

SHAFT

4H213A

SECURE FILE

STOR.

4H213B

OFFICE

4H213C

OFFICE

4H213

OPEN OFFICE

4H213D

OFFICE

4HC02

CORR.

4H215

TOILET

4H213E

OFFICE

4H213F

OFFICE 4H213G

COPIER/SUPPLY

4HS02

STAIR

MECH.

SHAFT

U.S. Department of Veterans Affairs

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson

COMMISSIONING AGENT:

SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering

15 W. Church Street, Suite 201 Orlando, Florida 32801-3350

407-630-6253 ENGINEERING

OSBORN

ED-102

1 LEVEL 4, AREA B2 DEMOLITION PLAN - ELECTRICAL

1/8'' = 1'-0''

LIGHTING DEMO KEYNOTES

3. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL

DETAIL ON PLANNED/REQUIRED DEMOLITION IN THIS AREA OF WORK.

THERE SHALL BE NO DEMOLITION OF ANY LIGHT FIXTURES.

CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR LIGHT

FIXTURES IN CEILING GRID WHERE ACCESS IS REQUIRED. TRACE

EXISTING FIXTURES TO PANEL AND CIRCUITS AND DISCONNECT ALL

WIRING TO EXISTING FIXTURES. ONCE WORK IN THIS AREA, CORRIDOR

4HC08A AND 4H208A, HAS BEEN COMPLETED, INSTALL NEW LIGHT

FIXTURES IN NEW CEILING TILES AND RE-CONNECT TO EXISTING

CIRCUITS AND SWITCH.

X

GENERAL LIGHTING DEMO NOTES

A. FOR THE THIRD LEVEL,THE DESIGN INTENT IS TO DEMOLISH ALL

LIGHTING FIXTURES AND DEVICES IN AREA OF SCOPE EXCEPT FOR

CORRIDOR 4HC08A AND 4H208A. HOWEVER, DUE TO RE-WORK OF

MECHANICAL AND PLUMBING OVERHEAD IN CEILING OF CORRIDOR

4HC08A AND 4H208A, LIGHT FIXTURES SHALL BE DISCONNECTED,

REMOVED, CLEANED AND STORED IN A SAFE LOCATION TO BE LATER

RE-INSTALLED IN THE EXACT SAME LOCATION ONCE CONSTRUCTION IS

COMPLETED.

B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE VA/COR.

C. ALL DEMOLISHED LIGHTING FIXTURES AND DEVICES SHALL HAVE BOXES,

DEVICES, CONDUIT AND WIRING REMOVED BACK TO SOURCE.

D. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED WIRING, CONDUITS AND DEVICES BACK TO THE SOURCE.

E. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED

AREAS.

F. PROVIDE WIRE, JUNCTION BOXES, CONDUIT, ETC. AS REQUIRED TO

MAINTAIN CONTINUITY TO EXISTING TO REMAIN EQUIPMENT, DEVICES,

ETC.

G. ALL DEMOLISHED EQUIPMENT, FIXTURES, DEVICES SHALL BE

PRESENTED TO THE VA FOR FIRST RIGHT OF REFUSAL.

H. EXISTING CONDITIONS SHOWN ARE BASED ON 'AS-BUILT' DRAWINGS AND

FIELD OBSERVATION. ELECTRICAL CONTRACTOR SHALL VERIFY

EXISTING CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

PRIOR TO DISTURBING EXISTING INSTALLATION.

I. ELECTRICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES

DRAWINGS AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF

ALL EQUIPMENT AND DEVICES SHOWN TO BE DEMOLISHED.

J. ALL EXISTING LIFE SAFETY LIGHTING LOCATED IN AREAS THAT ARE

EXISTING TO REMAIN, SHALL REMAIN OPERATIONAL DURING ALL PAHSES

OF CONSTRUCTION.

GENERAL POWER DEMO NOTES

A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE VA/COR.

B. ALL DEVICES INDICATED ON PLANS SHALL BE DEMOLISHED WITHIN

SCOPE OF WORK, UNLESS OTHERWISE NOTED - EXISTING TO REMAIN (E).

ITEMS BEING DEMOLISHED (D) SHALL HAVE BOXES, DEVICES, CONDUIT

AND WIRING REMOVED BACK TO SOURCE.

C. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED WIRING.

D. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED

AREAS.

E. PROVIDE WIRE, JUNCTION BOXES, CONDUIT, ETC. AS REQUIRED TO

MAINTAIN CONTINUITY TO EXISTING TO REMAIN EQUIPMENT, DEVICES,

ETC.

F. ALL DEMOLISHED EQUIPMENT, FIXTURES, DEVICES SHALL BE

PRESENTED TO THE VA FOR FIRST RIGHT OF REFUSAL.

G. EXISTING CONDITIONS SHOWN ARE BASED ON 'AS-BUILT' DRAWINGS AND

FIELD OBSERVATION. ELECTRICAL CONTRACTOR SHALL VERIFY

EXISTING…