The document provided appears to be a set of drawings related to a federal contract opportunity. The associated federal contract opportunity is a solicitation for a project titled "Y1DB--675-100 Expand Primary Care Minor Construction at Lake Nona (East)". This is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside solicitation issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The contractor will be responsible for providing all tools, equipment, materials, labor, and supervision to complete the project of expanding the primary care facility at the Orlando VA Medical Center Lake Nona Campus. The project location is 13800 Veterans Way, Orlando, FL 32827.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF VETERANS AFFAIRS
EXPAND PRIMARY CARE
AT LAKE NONA (EAST)
ORLANDO VA MEDICAL CENTER
13800 VETERANS WAY, ORLANDO FL. 32827
PROJECT NUMBER - 675-100
27 441 A1A
PENSACOLA FORT WALTON
BEACH
PANAMA
CITY
TALLAHASSEE
COLUMBIA
UNION
BRADFORD
CLAY
ALACHUA
GAINESVILLE
GILCHRIST
LEVY MARION
PUTNAM
JACKSONVILLE
DAYTONA
BEACH
OCALA
ORLANDO
ORANGE
MELBOURNE
WINTER HAVEN
LAKELAND
NEW PORT
RICHEY
ST
PETERSBURG
SARASOTA
TAMPA
FT
PIERCE
WEST PALM
BEACH
FT
MYERS
NAPLES
FT
LAUDERDALE
MIAMI
MONROE
DADEMONROE
COLLIER BROWARD
COCOA
BRADENTON
ES
CA
M
BI
A
SANTA
ROSA
OKALOOSA WALTON
HOLMES
WASHINGTON
JACKSON
CALHOUN
BAY
GULF
GADSEN
LIBERTY
LEON
WAKULLA
FRANKLIN
JEFFERSON MADISON
TAYLOR
HAMILTON
SUWANNEE
LAFAYETTE
DIXIE
BAKER
NASSAU
DUVAL
ST.
JOHNS
FLAGLER
VOLUSIA
SEMINOLE
LAKECITRUS
HERNANDO
PASCO
SUMTER
BREVARD
OSCEOLA
POLK
PINELLAS
HILLSBOROUGH
MANATEE
SARASOTA
HARDEE
DESOTO
HIGHLANDS
OKEECHOBEE
INDIAN
RIVER
ST.
LUCIE
MARTIN
GLADESCHARLOTTE
LEE HENDRY PALM
BEACH
FLORIDA
KEYS
ANN
FISHER HOUSE
PARKING
19 SPACES
FISHER HOUSE
16BR
FFE=88.0
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
VOLUME 1
CONSTRUCTION DOCUMENTS 100% FINAL SUBMISSION
JANUARY 11, 2024
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
FISHER HOUSE
PARKING
19 SPACES
FISHER HOUSE
16BRFFE=88.0
CLINIC
PARKING PARKING
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
C-F
C-H
C-G
SERVICE D
C-D
C-B
C-A
STORAGE
(PARKING)
BUSINESS
OCCUPANCY
STORAGE
(PARKING)
BUSINESS
OCCUPANCY
STORAGE
3A508
OFFICE
3B101
STORAGE
STORAGE
STORAGE CLEAN
STORAGE
SOILED
UTILITY
3J204
STORAGE
STORAGE
CLEAN
STORAGE
HAC
SOILED
UTILITY
CLEAN
UTILITY
3D304C
EMPLOYEE
BREAKROOM
SOILED
UTILITY
MECH
SHAFT
MECH
SHAFT
C-F
C-H
C-G
SERVICE D
C-D
C-B
C-A
MECH
SHAFT
MECH
SHAFT
OVERALL LEVEL 3 INTERSTITIAL PLAN
1" = 30'
G-101 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
C-B
C-C
C-D
PARKING/
STORAGE
OCCUPANCY
BUSINESS
OCCUPANCY
BUSINESS
OCCUPANCY
PARKING/
STORAGE
OCCUPANCY
4H217
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
47112
ELECTRICAL
ROOM47110-C
IT
4E801
4E803
4F903
KITCHEN
4F301C
STORAGE
4F918
4G906
AUDITORIUM
4E804
GME
OFFICE
HAC
4E903
CONFERENCE
ROOM
4E901
WOMENS
LOCKERS
4D204
EL
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
TREATMENT
STORAGE
STORAGE
STORAGE
SOILED
UTILITY
HAC
4C908
EL
4B906
STAFF
LOUNGE
4A901
ELECTRICAL
ROOM
4A206
TOILET
4A202
ELEC
ROOM 4A308
CONFERENCE
ROOM
4A903A
1 2
MECH.
SHAFT
4H213
OPEN OFFICE
MECH.
SHAFT
NEW
SHAFT
4H816
STU/TRAINEE
C-B
C-C
C-D
C-H
MECH.
SHAFT
MECH.
SHAFT
NEW
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MEMBRANE
ROOFINGRDR
ODR
RDR
ODR
TYP
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
UP
DN
UP
UP
UP
UP
DN
DN
UP
UP
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
STAIR 5BST25HS02
MECH
SHAFT
MECH5A105
MECH
SHAFT
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
NEW
SHAFT
5A112
MECH
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
PAT TLT
3H311
CODING
3H309
PAT TLT
3H802
INTERN SOC
WRK
3J208
SOCIAL WRKR
3J206
STF TLT
3J216
STF TLT
3J218
EXAM
3H816
EXAM
3H814
EXAM
3H812
EXAM
3H810
EXAM
3H808
TREATMENT
3H308
CLEAN
3H815
SOILED
3H813
OFFICE
3H811
CORR
3HC08
PROCEDURE
3H807
DIETICIAN
3H805
TLT
3H807A
COPY/SUPPORT
3J214
STAIR 3BST2
3HS02
MECH
SHAFT
STOR
3J204
MECH
SHAFT HZ
HZ
S
S
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S
SD
S
SD
* NOTE
System No. C-AJ-1429 May 18, 2005 F Rating - 2 Hr T Rating - 0 Hr
W Rating - Class I (See Item 3)
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening 240 sq in. (1548 sq cm) with a max dimension of 30 in.
(762 mm).Max area of opening in floors constructed of hollow-core concrete is 49 sq in.
(316 sq cm) with a max dimension of 7 in. (178 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in Fire Resistance Directory for names of manufacturers.
2. Through Penetrant - One or more metallic pipes, conduits, tubes or flexible metal pipes installed concentrically or eccentrically within opening. Annular space between penetrants and periphery of opening shall be min of 0 in. (point contact) to max 2 in. (0 mm to max 51 mm) Space between penetrants shall be min of 1/4 in. to max 2 in. (6 mm to max 51 mm). Penetrants to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of penetrants may be used:
A. Steel Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102
mm) diam (or smaller) steel electrical metallic tubing.
D. Copper Tubing - Nom 3 in. (76 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe - Nom 3 in. (76 mm) diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:
1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
OMEGA FLEX INC.
2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
TITEFLEX CORP, A BUNDY CO.
3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly.
WARD MFG INC.
3. Firestop System - The details of the firestop system shall be as follows:
A. Packing Material - Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. In floors constructed of hollow-core concrete, packing material to be recessed from top and bottom surfaces of floor as required to accommodate the required thickness of fill material.
B. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top surface of floor or with both surfaces of wall. In floors constructed of hollow-core concrete, min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top and bottom surfaces of floor. Min 1/4 in. (6 mm) diam bead of caulk applied to the penetrant/concrete interface at the point contact location on the top surface of floor or both surfaces of wall or hollow-core concrete.
3M COMPANY - IC 15WB+, CP 25WB+ caulk or FB-3000 WT sealant.
(Note: W Rating applies only when FB-3000 WT is used.)
* Bearing the UL Classification Marking
SECTION A-A
System No. C-AJ-7081 May 19, 2005 F Rating - 2 Hr T Rating - 0 Hr
W Rating - Class I (See Item 3)
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600- 2400 kg/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 18 in. (457 mm) Max diam of openings in floors constructed of hollow-core concrete is 7 in. (178 mm).
See Concrete Blocks (CAZT) categories in Fire Resistance Directory for names of manufacturers.
2. Through Penetrant - One steel duct to be installed either concentrically or eccentrically within the firestop system. An annular space of min 1/2 in. to max 1-1/2 in.
(13 mm to max 38 mm) is required within the firestop system. Steel duct to be rigidly supported on both sides of floor or wall assembly. The following sizes of steel ducts may be used:
A. Steel Duct - Nom 16 in. (406 mm) diam (or smaller) No. 24 gauge (or heavier) spiral wound galv steel duct.
B. Steel Vent Duct - Nom 10 in. (254 mm) diam (or smaller) No. 28 gauge (or heavier) galv steel vent duct.
3. Firestop System - The firestop system shall consist of the following:
A. Packing Material - Min 3-1/2 in. (89 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall to accommodate the required thickness of fill material. In floors constructed of hollow-core concrete, packing material to be recessed from top and bottom surfaces of floor as required to accommodate the required thickness of fill material.
B. Fill Void or Cavity Materials* - Caulk or Sealant - Min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top surface of floor or with both surfaces of wall. In floors constructed of hollow-core concrete, min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top and bottom surfaces of floor. resistance of through penetrant (Item 2) must be considered in addition 3M COMPANY - CP 25WB+, IC 15WB+ caulk or FB-3000 WT sealant.
(Note: W Rating applies only when FB-3000 WT sealant is used. Water resistance of throughpenetrant (Item 2) must be considered in addition to water resistance of firestop system.)
*Bearing the UL Classification Mark
* NOTE
System No.W-L-7091 May 19, 2005
F Ratings - 1 & 2 Hr (See Item 1) T Rating - 0 Hr
1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of steel channel studs to be min 3-1/2 in.
(89 mm) wide and spaced max 24 in. (610 mm) OC. Additional 3-1/2 in. (89
mm) wide steel studs shall be used to completely frame opening.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Max size of opening to be 640 sq in. (4129 cm2) with a max dimension of 32 in. (813 mm)
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Steel Duct - Nom 30 in. by 18 in. (762 mm by 457 mm) (or smaller) No. 24 gauge (or heavier) galv steel duct installed concentrically or eccentrically within opening.
Annular space between duct and periphery of opening to be min 0 in. (point contact) to max 2 in. (0 mm to max 51 mm). Duct to be rigidly supported on both sides of wall assembly.
3. Firestop System - The firestop system shall consist of the following:
A. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8 in. (16 mm) thickness of caulk applied within annulus, flush with both surfaces of wall.
3M COMPANY - CP 25WB+, IC 15WB+ caulk or FB-3000 WT sealant
B. Retaining Angles - Min 16 gauge galv steel angles sized to lap duct a min of 2 in. (51 mm) and lap wall surfaces a min of 1 in. (25 mm). Angles attached to duct on both sides of wall with min 1/2 in. (13 mm) long, No. 10 (or larger) sheet metal screws spaced a max 1 in. (25 mm) from each end and spaced a max 6 in. (152 mm) OC.
*Bearing the UL Classification Marking
SECTION A-A
SECTION A-A
System No.W-L-2299 May 19, 2005
F Ratings - 1 & 2 Hr (See Item 1) T Rating - 0 Hr
1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs.
Wood studs to consist of nom 2 in. by 4 in. (51 mm by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. wide (89 mm) spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3-1/2 in. (89 mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants - One nonmetallic pipe or conduit installed eccentrically or concentrically within opening. Annular space between penetrant and periphery of opening to be min 0 in. (point contact) to max 1-1/8 in. (0 mm to max 29 mm).
Penetrant to be rigidly supported on both sides of wall. The following types and sizes of penetrants may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70).
D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
E. Electrical Nonmetallic Tubing (ENT)+ - Nom 1-1/4 in (32 mm) diam (or smaller) ENT installed in accordance with Article 331 of the National Electrical Code (NFPA No. 70).
See Electrical Nonmetallic Tubing (FKHU) category in the Electrical Construction Materials Directory for names of manufacturers.
3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8 in. (16 mm) thickness of caulk applied within annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.
3M COMPANY - IC 15WB+, CP 25WB+ caulk or FB-3000 WT sealant (Note: CP 25WB+ not suitable for use with CPVC pipes.)
*Bearing the UL Classification Marking +Bearing the UL Listing Mark
6-1/8"
System Performance 2 HR Fire
UL Design No. U412
4-7/8"
System Performance 1 HR Fire
UL Design No. U419
Shaftwall 2 HR Fire strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814
HZ
STAIR 3BST2
MECH
SHAFT
MECH
SHAFT
S S
S S
S strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
4H217
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
4H816
STU/TRAINEE
4H203A
SECRETARY
MECH.
SHAFT
4H213A
SECURE FILE
STOR.
4H213B
OFFICE
4H213C
OFFICE
4H213
OPEN OFFICE
4H213D
OFFICE
4HC02
CORR.
4H215
TOILET
4H213E
OFFICE
4H213F
OFFICE 4H213G
COPIER/SUPPLY
4HS02
STAIR
MECH.
SHAFT
NEW
SHAFT
4HCO1
CORRIDOR
HZ
S
S
S
S
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S
S
S strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814
HZ
MECH.
SHAFT
MECH.
SHAFTSTAIR 4BiST2
4HiS02
NEW
SHAFT
S S
S S
S strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
STAIR 5BST2
5HS02
MECH
SHAFT
MECH
5A105
MECH
SHAFT
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
NEW
SHAFT
5A112
MECH
DD
DD
DD
S
S
S
DD
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
3H311
CODING
3H309
PAT TLT
3H802
SHARED OFFICE
3J219
INTERN SOC
WRK
3J208
SOCIAL WRKR
3J203
SOCIAL WRKR
3J206
CONFERENCE
ROOM
3J209
PRGM SUPP
3J201
STF TLT
3J216
STF TLT
3J218
ELEC
3J202
COMM
3H801
ELEC
3H915
EXAM
3H816
EXAM
3H814
EXAM
3H812
EXAM
3H810
EXAM
3H808
TREATMENT
3H308
CLEAN
3H815
SOILED
3H813
OFFICE
3H811
SECRETARY
3J213
CORR
3HC08
CORR
3JC02
OFFICE
3J903
PROCEDURE
3H807
DIETICIAN
3H805
TLT
3H807A
COPY/SUPPORT
3J214
OFFICE
CLERK/WAIT
3J101
STAIR 3BST2
3HS02
MECH SHAFT
STOR
3J204
3J902
CHIEF OFFICE
OFFICE, CHIEF
3J211
MECH.
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
ROOF
4H217
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
OFFICE
4H815
CAC SHARED
OFFICE
4H817
CORR.
4GC09A
4H816
STU/TRAINEE
CORR.
4HC08A
OFFICE
4H813
OFFICE
4H811
OFFICE
4H809
OFFICE
4H807
OFFICE
4H805
OFFICE
4H803
OFFICE
4H801
CORR.
4HC08
CORR.
4HC01
DEO
4H201
4H203A
SECRETARY
4H102
COMM.
4H802
ELEC.
MECH.
SHAFT
4H213A
SECURE FILE
STOR.
4H213B
OFFICE
4H213C
OFFICE
4H213
OPEN OFFICE
4H213D
OFFICE
4HC02
CORR.
4H215
TOILET
4H213E
OFFICE
4H213F
OFFICE 4H213G
COPIER/SUPPLY
4HS02
STAIR
MECH.
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
SHAFT
MECH.
SHAFTSTAIR 4BiST2
4HiS02 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
SHAFT
MECH.
SHAFT
STAIR 5BST2
5HS02
MECH
5A112
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
5A105
MECH
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
3H311
CODING
3H309
PAT TLT
3H802
INTERN SOC
WRK
3J208
SOCIAL WRKR
3J206
STF TLT
3J216
STF TLT
3J218
EXAM
3H816
EXAM
3H814
EXAM
3H812
EXAM
3H810
EXAM
3H808
TREATMENT
3H308
CLEAN
3H815
SOILED
3H813
OFFICE
3H811
CORR
3HC08
PROCEDURE
3H807
DIETICIAN
3H805
TLT
3H807A
COPY/SUPPORT
3J214
STAIR 3BST2
3HS02
MECH
SHAFT
STOR
3J204
MECH
SHAFT
south wall materialmaterial finish room number space name floor material material material- finishfinish finish
ROOM FINISH SCHEDULE - LEVEL 3
base north wall east wall material materialfinish finishfinish west wall ceiling ceiling height remarks notes &
APC = ACOUSTICAL PANEL CEILING
BG = BUMPER GUARD (SEE DETAIL ON SHEET AI-610)
B.O.S. = BOTTOM OF STRUCTURE
CONC = CONCRETE
CR = CHAIR RAIL (SEE DETAIL ON SHEET AI-610)
CT = CERAMIC TILE
CG = CORNER GUARD (SEE DETAIL ON SHEET AI-610)
CPT = CARPET
FACT = FACTORY FINISH
GYP = GYPSUM WALLBOARD
HR = HAND RAIL (SEE DETAIL ON SHEET AI-610)
N/A = NOT APPLICABLE
P = PAINT
PPT = PORCELAIN TILE
RB = RUBBER BASE
RF = RESILIENT FLOORING
SEALER = SEALER
TST = THIN SET TERRAZZO 3 8" MIN. THICKNESS
WD = WOOD
WSCT = WAINSCOT
WSF = WELDED SHEET FLOORING
1. CT TO BE WAINSCOT HEIGHT. SEE INTERIOR ELEVATIONS.
2. HANDRAILS/CORNER GUARDS. SEE DETAIL ON SHEET AI-610. SEE FLOOR
PLAN FOR LOCATIONS.
3. MARBLE THRESHOLD.
4. WALL GUARDS. SEE DETAIL ON SHEET AI-610. SEE FLOOR PLAN FOR
LOCATIONS.
5. INSTALL CURTAIN TRACK.
6. EC-2 ON WALL WITH PPT-1B, 1C TILE.
7. GL-1 LOCATED IN DIVIDER PANEL AT RECEPTION DESK.
3K300 WAITING CONC TST-1,2,3,4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2, 7
3K302 CONF./GROUP CARE/CLASSRM. CONC CPT-1 GYP RB GYP P-1 GYP P-8 GYP P-1 GYP P-1 APC FACT SEE RCP 2 3K303 PATIENT TOILET CONC PPT-1 GYP PPT-1A GYP PPT-1B, 1C GYP PPT-1D, 1E GYP PPT-1B, 1C GYP PPT-1B, 1C APC FACT SEE RCP 1, 3, 6
3K305 PATIENT TOILET CONC PPT-1 GYP PPT-1A GYP PPT-1B, 1C GYP PPT-1B, 1C GYP PPT-1B, 1C GYP PPT-1D, 1E APC FACT SEE RCP 1, 3, 6 3K306 RECEPTION CONC CPT-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-8 APC/GYP FACT/P SEE RCP 7
3K309 NURSE MANAGER OFFICE CONC CPT-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
3K312 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
3K315 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
3K319 SOILED UTILITY CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP - 3K320 CLEAN UTILITY CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
3K322 CLEAN STORAGE CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
3KC05 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2 3K325 WORK STATION CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP - 3K326 LOUNGE, CLINICAL STAFF CONC RF-1 GYP RB GYP P-9 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP - 3K327 WORK STATION CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2
3K329 PROCEDURE (ISOLATION) CONC WSF-2 GYP RB GYP P-1 GYP P-1 GYP P-8 GYP P-1 APC FACT SEE RCP 2, 4, 5 3K330 TREATMENT ROOM CONC WSF-2 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2, 4, 5
3JC02 CORRIDOR CONC RF-3 GYP RB EXIST P-1 GYP P-1 GYP P-1 EXIST P-1 EXIST EXIST SEE RCP 2
3KC01 CORRIDOR CONC TST-1,2,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT SEE RCP 2
3K300A PATIENT CHECK-IN KIOSK CONC TST-1,2,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2 3K300B PATIENT ED. WORK STATION CONC TST-1,2,3,4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2 3K300C MOBILITY DEVICES CONC TST-1,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2
304A HT./WT. STN CONC RF-1, 2, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-8 APC FACT SEE RCP 2, 4
3K327A ALCOVE, MEDICATIONS CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
3K314 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
3K316 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
3K318 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
3K321 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
3K323 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
3K331 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5 3K332 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5 3K333 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5 3K334 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5 3K335 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
3KC07 CORRIDOR CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
3KC04 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
3KC03 CORRIDOR CONC RF-1, 2, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
3KC02 CORRIDOR CONC TST-2 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
3KC06 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
3K313 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
3K310 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP - 3K311 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
3K308 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
3K317 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
REFER TO SHEET AI-900 FOR FINISH KEY CALL OUTS.
NOTE:
SEE SPECIFICATIONS SECTION 10 14 00 SIGNAGE FOR SIGN
REQUIREMENTS AND THE SIGN SCHEDULE. THIS SCHEDULE
DEFINES SIGN LOCATIONS FOR EACH SIGN TYPE INDICATED.
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
3H311
CODING
3H309
PAT TLT
3H802
INTERN SOC
WRK
3J208
SOCIAL WRKR
3J206
STF TLT
3J216
STF TLT
3J218
EXAM
3H816
EXAM
3H814
EXAM
3H812
EXAM
3H810
EXAM
3H808
TREATMENT
3H308
CLEAN
3H815
SOILED
3H813
OFFICE
3H811
CORR
3HC08
PROCEDURE
3H807
DIETICIAN
3H805
TLT
3H807A
COPY/SUPPORT
3J214
STAIR 3BST2
3HS02
MECH
SHAFT
STOR
3J204
MECH
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
SHAFT
south wall materialmaterial finish room number space name floor material material material- finishfinish finish
ROOM FINISH SCHEDULE - LEVEL 3 INTERSTITIAL
base north wall east wall material materialfinish finishfinish west wall ceiling ceiling height remarks notes &
B.O.S. = BOTTOM OF STRUCTURE
CONC = CONCRETE
GYP = GYPSUM WALLBOARD
N/A = NOT APPLICABLE
P = PAINT
RB = RUBBER BASE
SEALER = SEALER
1.
3Fi01 UTILITY PLATFORM CONC SEALER RB NA GYP/CONC P GYP/CONC P GYP/CONC P NA NA B.O.S. P SEE RCP -
REFER TO SHEET AI-900 FOR FINISH KEY CALL OUTS.
NOTE:
SEE SPECIFICATIONS SECTION 10 14 00 SIGNAGE FOR SIGN
REQUIREMENTS AND THE SIGN SCHEDULE. THIS SCHEDULE
DEFINES SIGN LOCATIONS FOR EACH SIGN TYPE INDICATED.
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
4H816
STU/TRAINEE
4H203A
SECRETARY
MECH.
SHAFT
4H213A
SECURE FILE
STOR.
4H213B
OFFICE
4H213C
OFFICE
4H213
OPEN OFFICE
4H213D
OFFICE
4HC02
CORR.
4H215
TOILET
4H213E
OFFICE
4H213F
OFFICE 4H213G
COPIER/SUPPLY
4HS02
STAIR
MECH.
SHAFT
NEW
SHAFT
4HCO1
CORRIDOR
south wall materialmaterial finish room number space name floor material material material- finishfinish finish
ROOM FINISH SCHEDULE - LEVEL 4
base north wall east wall material materialfinish finishfinish west wall ceiling ceiling height remarks notes &
4J400 WAITING CONC TST-1,2,3,4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2, 7
4J402 CONF./GROUP CARE/CLASSRM. CONC CPT-1 GYP RB GYP P-1 GYP P-8 GYP P-1 GYP P-1 APC FACT SEE RCP 2 4J403 PATIENT TOILET CONC PPT-1 GYP PPT-1A GYP PPT-1B, 1C GYP PPT-1D, 1E GYP PPT-1B, 1C GYP PPT-1B, 1C APC FACT SEE RCP 1, 3, 6
4J405 PATIENT TOILET CONC PPT-1 GYP PPT-1A GYP PPT-1B, 1C GYP PPT-1B, 1C GYP PPT-1B, 1C GYP PPT-1D, 1E APC FACT SEE RCP 1, 3, 6 4J406 RECEPTION CONC CPT-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-8 APC/GYP FACT/P SEE RCP 7
4J409 ASSISTANT CHIEF OFFICE CONC CPT-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
4J412 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
4J415 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
4J419 SOILED UTILITY CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP - 4J420 CLEAN UTILITY CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
4J422 CLEAN STORAGE CONC WSF-1 GYP WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
4JC05 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2 4J425 WORK STATION CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP - 4J426 LOUNGE, CLINICAL STAFF CONC RF-1 GYP RB GYP P-9 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP - 4J427 WORK STATION CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2
4J429 PROCEDURE (ISOLATION) CONC WSF-2 GYP RB GYP P-1 GYP P-1 GYP P-8 GYP P-1 APC FACT SEE RCP 2, 4, 5 4J430 TREATMENT ROOM CONC WSF-2 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2, 4, 5
4JC01 CORRIDOR CONC TST-1,2,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT SEE RCP 2
4J400A PATIENT CHECK-IN KIOSK CONC TST-1,2,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2 4J400B PATIENT ED. WORK STATION CONC TST-1,2,3,4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2 4J400C MOBILITY DEVICES CONC TST-1,3 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC/GYP FACT/P SEE RCP 2
4J404A HT./WT. STN CONC RF-1, 2, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-8 APC FACT SEE RCP 2, 4
4J427A ALCOVE, MEDICATIONS CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
4J414 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
4J416 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
4J418 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5
4J421 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
4J423 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
4J431 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5 4J432 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5 4J433 EXAM ROOM CONC RF-1 GYP RB GYP P-7 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 5 4J434 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5 4J435 EXAM ROOM CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-7 GYP P-1 APC FACT SEE RCP 5
4J428 CORRIDOR CONC RF-1 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP -
4JC04 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
4JC03 CORRIDOR CONC RF-1, 2, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
4JC02 CORRIDOR CONC TST-2 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
4JC06 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
4J413 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
4J410 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP - 4J411 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
4J408 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
4J417 CONSULTANT ROOM CONC CPT-1 GYP RB GYP P-2 GYP P-2 GYP P-2 GYP P-2 APC FACT SEE RCP -
4H213 OPEN OFFICE CONC CARPET GYP RB GYP P-1 GYP P-1 GYP P-1 EXIST P-1 EXIST EXIST SEE RCP 2
4JC07 CORRIDOR CONC RF-1, 3, 4 GYP RB GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP 2
APC = ACOUSTICAL PANEL CEILING
BG = BUMPER GUARD (SEE DETAIL ON SHEET AI-610)
B.O.S. = BOTTOM OF STRUCTURE
CONC = CONCRETE
CR = CHAIR RAIL (SEE DETAIL ON SHEET AI-610)
CT = CERAMIC TILE
CG = CORNER GUARD (SEE DETAIL ON SHEET AI-610)
CPT = CARPET
FACT = FACTORY FINISH
GYP = GYPSUM WALLBOARD
HR = HAND RAIL (SEE DETAIL ON SHEET AI-610)
N/A = NOT APPLICABLE
P = PAINT
PPT = PORCELAIN TILE
RB = RUBBER BASE
RF = RESILIENT FLOORING
SEALER = SEALER
TST = THIN SET TERRAZZO 3 8" MIN. THICKNESS
WD = WOOD
WSCT = WAINSCOT
WSF = WELDED SHEET FLOORING
1. CT TO BE WAINSCOT HEIGHT. SEE INTERIOR ELEVATIONS.
2. HANDRAILS/CORNER GUARDS. SEE DETAIL ON SHEET AI-610 FOR. SEE
FLOOR PLAN FOR LOCATIONS.
3. MARBLE THRESHOLD.
4. WALL GUARDS. SEE DETAIL ON SHEET AI-610. SEE FLOOR PLAN FOR
LOCATIONS.
5. INSTALL CURTAIN TRACK.
6. EC-2 ON WALL WITH PPT-1B, 1C TILE.
7. GL-1 LOCATED IN DIVIDER PANEL AT RECEPTION DESK.
8. SECRETARY 4H203A IS AN EXISTING ROOM TO REMAIN AS IS WITH THE
EXCEPTION OF AN EXISTING OPENING INTO CORRIDOR 4HC01. THIS
OPENING IS TO BE CLOSED TO MATCH EXISTING WALL CONSTRUCTION
AND FINISHES. (BASE, PAINT ETC.)
REFER TO SHEET AI-900 FOR FINISH KEY CALL OUTS.
4J439 H.A.C. CONC WSF-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 GYP P-1 APC FACT SEE RCP - 4J438 STAFF TOILET CONC PPT-1 GYP PPT-1A GYP PPT-1B, 1C GYP PPT-1D, 1E GYP PPT-1B, 1C GYP PPT-1B, 1C APC FACT SEE RCP 1, 3, 6
4H203A EXISTING SECRETARY EXIST EXIST GYP RB EXIST EXIST EXIST EXIST GYP P EXIST EXIST EXIST EXIST EXIST 8
NOTE:
SEE SPECIFICATIONS SECTION 10 14 00 SIGNAGE FOR SIGN REQUIREMENTS AND THE SIGN
SCHEDULE. THIS SCHEDULE DEFINES SIGN LOCATIONS FOR EACH SIGN TYPE INDICATED.
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
4H816
STU/TRAINEE
4H203A
SECRETARY
MECH.
SHAFT
4H213A
SECURE FILE
STOR.
4H213B
OFFICE
4H213C
OFFICE
4H213
OPEN OFFICE
4H213D
OFFICE
4HC02
CORR.
4H215
TOILET
4H213E
OFFICE
4H213F
OFFICE 4H213G
COPIER/SUPPLY
4HS02
STAIR
MECH.
SHAFT
NEW
SHAFT
4HCO1
CORRIDOR
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
SHAFT
MECH.
SHAFTSTAIR 4BiST2
4HiS02
NEW
SHAFT
south wall materialmaterial finish room number space name floor material material material- finishfinish finish
ROOM FINISH SCHEDULE - LEVEL 4 INTERSTITIAL
base north wall east wall material materialfinish finishfinish west wall ceiling ceiling height remarks notes &
B.O.S. = BOTTOM OF STRUCTURE
CONC = CONCRETE
GYP = GYPSUM WALLBOARD
N/A = NOT APPLICABLE
P = PAINT
RB = RUBBER BASE
SEALER = SEALER
1.
4Fi01 UTILITY PLATFORM CONC SEALER RB NA GYP/CONC P GYP/CONC P GYP/CONC P NA NA B.O.S. P SEE RCP -
REFER TO SHEET AI-900 FOR FINISH KEY CALL OUTS.
NOTE:
SEE SPECIFICATIONS SECTION 10 14 00 SIGNAGE FOR SIGN
REQUIREMENTS AND THE SIGN SCHEDULE. THIS SCHEDULE
DEFINES SIGN LOCATIONS FOR EACH SIGN TYPE INDICATED.
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
SHAFT
MECH.
SHAFTSTAIR 4BiST2
4HiS02
NEW
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
5A105
MECH
SHAFT
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
NEW
SHAFT
5A112
MECH
south wall materialmaterial finish room number space name floor material material material- finishfinish finish
ROOM FINISH SCHEDULE - LEVEL 5 - MECHANICAL
base north wall east wall material materialfinish finishfinish west wall ceiling ceiling height remarks notes &
B.O.S. = BOTTOM OF STRUCTURE
FACT = FACTORY FINISH
N/A = NOT APPLICABLE
P = PAINT
PAN = INSULATED METAL PANELS
1. BACK SIDE OF METAL INSULATED PANELS OVER METAL FRAMING.
5B500 MECHANICAL METAL FACT NA NA PAN P PAN P PAN P NA NA B.O.S. P SEE RCP 1
REFER TO SHEET AI-900 FOR FINISH KEY CALL OUTS.
NOTE:
SEE SPECIFICATIONS SECTION 10 14 00 SIGNAGE FOR SIGN
REQUIREMENTS AND THE SIGN SCHEDULE. THIS SCHEDULE
DEFINES SIGN LOCATIONS FOR EACH SIGN TYPE INDICATED.
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
5A105
MECH
SHAFT
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
NEW
SHAFT
5A112
MECH
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
3H311
CODING
3H309
PAT TLT
3H802
INTERN SOC
WRK
3J208
SOCIAL WRKR
3J206
STF TLT
3J216
STF TLT
3J218
EXAM
3H816
EXAM
3H814
EXAM
3H812
EXAM
3H810
EXAM
3H808
TREATMENT
3H308
CLEAN
3H815
SOILED
3H813
OFFICE
3H811
CORR
3HC08
PROCEDURE
3H807
DIETICIAN
3H805
TLT
3H807A
COPY/SUPPORT
3J214
STAIR 3BST2
3HS02
MECH
SHAFT
STOR
3J204
MECH
SHAFT
8'-0"
SOFFIT
9'-0"
CEILING
13-5"
CONC. DECK
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
TRAINEE
LOUNGE
4H901
ELECTRICAL
ROOM
4H816
STU/TRAINEE
4H203A
SECRETARY
MECH.
SHAFT
4H213A
SECURE FILE
STOR.
4H213B
OFFICE
4H213C
OFFICE
4H213
OPEN OFFICE
4H213D
OFFICE
4HC02
CORR.
4H215
TOILET
4H213E
OFFICE
4H213F
OFFICE 4H213G
COPIER/SUPPLY
4HS02
STAIR
MECH.
SHAFT
NEW
SHAFT
4HCO1
CORRIDOR
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
SHAFT
MECH.
SHAFTSTAIR 4BiST2
4HiS02
NEW
SHAFT
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
MECH
SHAFT
MECH
5A105
MECH
SHAFT
EXISTING
ROOF
EXISTING
ROOF
EXISTING
ROOF
NEW
SHAFT
5A112
MECH
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
A A-401
A A-400 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
A-500 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
3K306
NURSE
MANAGER
OFFICE
3K310
CONSULTANT
3K300A
PATIENT
CHECK-IN
KIOSK
3K311
CONSULTANT
3K313
CONSULTANT
3K315
CONSULTANT
3K315
CONSULTANT 3K319
SOILED
UTILITY
3K320
CLEAN
UTILITY
3K322
CLEAN
STORAGE
3K325
WORK
STATIONS
4JC05
4J406
NURSE
MANAGER
OFFICE
4J410
CONSULTANT
4J400A
PATIENT
CHECK-IN
KIOSK
4J411
CONSULTANT
4J413
CONSULTANT
4J415
CONSULTANT
4J415
CONSULTANT 4J419
SOILED
UTILITY
4J420
CLEAN
UTILITY
4J422
CLEAN
STORAGE
4J425
WORK
STATIONS
5B500
MECHANICAL
A-402 A
Fg
F
EXISTG
3Fi01
UTILITY
PLATFORM
4Fi01
UTILITY
PLATFORM
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
4J412B
4J406
RECEPTION
4J414B 4J414B 4J418B 4J421B 4J423B
4J404A
HT./WT. STN.
4JC05
CORRIDOR
4JC07
CORRIDOR
4J400
WAITING
3K312B
3K306
RECEPTION
3K314B 3K314B 3K318B 3K321B 323B
3K304A
HT./WT. STN.
3KC05
CORRIDOR
3KC07
CORRIDOR
3K300
WAITING
A-402 A
AgAg
AA
EXISTG
4J427
WORK
STATIONS
3K327
WORK
STATIONS
4JC05
3Fi01
UTILITY
PLATFORM
4Fi01
UTILITY
PLATFORM
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
A-400
A-401 A
Dg
D
A A
AgAg
3K334B
3K334
EXAM ROOM
3K327
WORK
STATION
3K321
EXAM ROOM
3K321A3KC04B3K320
3K320
CLEAN
UTILITY
3K334A
3KC04
CORRIDOR
4JC06
4J434
EXAM ROOM
4J427
WORK
STATION
4J421
EXAM ROOM
4J421A4JC04B4J420
4J420
CLEAN
UTILITY
4J434A
4JC04
CORRIDOR
EXISTG
4JC06
CORRIDOR
3KC06
CORRIDOR
3K321B
4J421B
3KC06
3Fi01
UTILITY
PLATFORM
4J434B
4Fi01
UTILITY
PLATFORM
5B500
MECHANICAL
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
PRECAST DETAIL
1 1/2" = 1'-0"
A-610
PRECAST DETAIL
1 1/2" = 1'-0"
A-610
PRECAST DETAIL
1 1/2" = 1'-0"
A-610
PRECAST DETAIL
1 1/2" = 1'-0"
A-610
PRECAST DETAIL
1 1/2" = 1'-0"
A-610
PRECAST DETAIL
1 1/2" = 1'-0"
A-610 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
PRECAST DETAIL
1 1/2" = 1'-0"
A-611
PRECAST DETAIL
1 1/2" = 1'-0"
A-611
PRECAST DETAIL
1 1/2" = 1'-0"
A-611
PRECAST DETAIL
1 1/2" = 1'-0"
A-611 strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-620
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-620
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-620
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-620
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-620
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane Orlando, FL 32814 t: (407) 767-5188 f: (407) 767-5772 Osborn Engineering
CURB @ LOUVER
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-621
LOUVER -
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-621
ROOF EDGE OVERHANG
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-621
CMU CURB SECTION DETAIL @ PENTHOUSE
1 1/2" = 1'-0"
A-621
WALL PANEL SECTION DETAIL
1 1/2" = 1'-0"
A-621
PRECAST SECTION DETAIL
1 1/2" = 1'-0"
A-621
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane
VAO
VAO
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
U.S. Department of Veterans Affairs
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 t: (813) 289-4700 Nicholas Stephenson
COMMISSIONING AGENT:
SGM Engineering 935 Lake Baldwin Lane door, frame and glazingopening hardware re ma rks / n ote s ke y s ide ke y m ar k ke y t yp e loc k a cc es s gla zin g t yp e fra me fin ish fra me m ate ria l fra me ty pe do or fin ish do or m ate ria l do or ty pe fire ra tin g no mi na l s ize s do or nu mb er
DOOR SCHEDULE - LEVEL 3
ja mb de tai l he ad de tai l sil l d eta il gla zin g s top si de ha rd wa re se t
W = WOOD
AL = ALUMINUM
DOOR MATERIAL:
DOOR FINISH
S = STAIN
M = MANUFACTURE'S FINISH
FRAME TYPE
SEE ELEVATIONS FOR TYPES.
AL = ALUMINUM
S = STANDARD
SLG = SLIDING DOOR
FRAME MATERIAL:
HM = STD HOLLOW METAL (08 11 13)
AL = ALUMINUM
FRAME FINISH:
P = PAINT
M = MANUFACTURE'S FINISH
HARDWARE SETS:
REFER TO SPEC SECTION 08 71 00
DOOR TYPE:
SEE ELEVATIONS FOR TYPES.
AL = ALUMINUM
F = FLUSH
FG = FULL GLASS
NL = NARROW LIGHT
SLG = SLIDING DOOR
NOTES:
1. SINGLE SLIDING DOOR. HARDWARE AND FRAME BY
MANUFACTURER. C.O. IS CLEAR OPENING WHEN
DOOR IS OPEN. C.O. IS NOT THE DOOR SIZE. SEE
DETAIL.
2. DOUBLE EGRESS DOOR.
3. GLAZING .25 T = 14" CLEAR TEMPERED GLASS
GLAZING FR = FIRE RATED GLASS
4. THE ABBREVIATION "NA" MEANS " NOT APPLICABLE "
WHERE NOTED ON THE SCHEDULE.
5. SEE WINDOW TYPES FOR DOOR FRAME.
6. MATCH ADJACENT EXTERIOR WINDOW GLASS.
3KC02 1'-0"/4'-0"X7'-0" - NL2 W S S1 HM P .25T NA 2/A-900 1/A-900 - 8 NA NA NA NA -
3K303 4'-0"X7'-0" - F W S S1 HM P - NA 2/A-900 1/A-900 4/AI-600 10 NA NA NA NA -
3K312A C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1 door, frame and glazingopening hardware re ma rks / n ote s ke y s ide ke y m ar k ke y t yp e loc k a cc es s gla zin g t yp e fra me fin ish fra me m ate ria l fra me ty pe do or fin ish do or m ate ria l do or ty pe fire ra tin g no mi na l s ize s do or nu mb er
DOOR SCHEDULE - LEVEL 4
ja mb de tai l he ad de tai l sil l d eta il gla zin g s top si de ha rd wa re se t
3KC07 3'-6"X7'-0" - NL1 W S S1 HM P .25T NA 6&7/A-900 5/A-900 - 12 NA NA NA NA -
3K306 3'-6"X7'-0" - F W S S1 HM P - NA 2/A-900 1/A-900 - 12 NA NA NA NA -
3K308 3'-6"X7'-0" - NL1 W S S1 HM P .25T NA 2/A-900 1/A-900 - 11 NA NA NA NA -
3KC04A 1'-0"/4'-0"X7'-0" - NL2 W S S1 HM P .25T NA 2/A-900 1/A-900 - 8 NA NA NA NA -
3K302 3'-6"X7'-0" - F W S AL2 AL M .25T NA 6&7/A-900 5/A-900 - 5 NA NA NA NA -
3K312B C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1
3K314A C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1 3K314B C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1
3K316A C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1 3K316B C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1
3K318A C.O. 4'-4"X7'-0" - F / SLG W S SLG1 - - - NA 13/A-900 12/A-900 14/A-900 1.00 NA NA NA NA 1 3K318B C.O.