Palm_Harbor_Rec_Center_-_Electrical_-_Signed_and_Sealed.pdf
PDF 8 MB Posted
- Attached to
- Palm Harbor Recreation Center Addition State and local contract opportunity
- Solicitation number
- 26-0011-ITB-C
- Issued by
- Pinellas County, Clewiston City, Florida
About this file
This is an electrical design document for the Palm Harbor Recreation Center project in Pinellas County, Florida, prepared by Wannemacher Jensen Architects. The document consists of comprehensive electrical plans, schedules, and specifications for a 28,000 square foot, two-story recreation center addition designed to serve dual purposes as a community recreational facility and an at-risk hurricane shelter. The electrical scope includes power distribution systems with a 750 kW diesel generator for emergency backup, comprehensive lighting controls with occupancy sensors and daylight harvesting, fire alarm systems with voice evacuation capabilities, lightning protection systems, and mechanical equipment connections. Key electrical infrastructure encompasses a utility service with pad-mounted transformer, main switchboard with automatic transfer switch, multiple distribution panels throughout the facility, and emergency power systems. The design incorporates 208/120V, three-phase, four-wire service with branch circuit wiring in accordance with the 2020 National Electrical Code, Florida Building Code (2023), and NFPA standards. All devices, equipment, and materials must be new and listed by UL or an approved electrical testing agency, with copper conductors minimum #12 AWG for branch circuits and #3/0 AWG for major feeders. The contractor is responsible for coordinating all electrical work with mechanical, plumbing, fire protection, and technology trades prior to rough-in and installation.
The electrical design specifies detailed requirements for lighting fixtures including recessed troffers, strip fixtures, downlights, and specialty fixtures with integrated 0-10V dimming capability and 4000K color temperature. The lighting control system incorporates contactors, relay modules, occupancy sensors, photocells, and time clocks to achieve Florida Building Code energy conservation compliance. All panelboards and switchgear shall be Schneider Electric equipment with new typewritten directories and phenolic, engraved identification placards. The contractor must provide record drawings, operating manuals, and maintenance manuals within thirty days of system acceptance, including submittal data with equipment ratings and names of qualified service agencies. Equipment grounding shall be wire type bonded to building steel, ground rods, metal water mains, and lightning protection system grounding electrodes. The project includes provisions for electronic submetering at multiple distribution points to track electrical consumption at 15-minute intervals, with data reporting capabilities compatible with building automation systems. Kitchen electrical design incorporates stainless steel enclosures for disconnect switches, GFCI protection where required, and specialized conduit routing for wet location environments. The contractor shall visit the site prior to bidding to verify existing conditions and include all costs for field modifications in the bid price.
View the file
Other files for this state and local contract opportunity
Show all 50
Palm Harbor Recreation Center Addition has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MISCELLANEOUS RECEPTACLE(S) LIGHTING
CODES AND STANDARDS
GENERAL NOTES
SHEET INDEX
SWITCHES
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
NFPA 70
NFPA 72
NFPA 75
NFPA 90A
NFPA 90B
NFPA 101
NFPA 110
NFPA 780
FBC
FBCE
FFPC
ICC 500
NATIONAL ELECTRICAL CODE (2020)
NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
STANDARD FOR THE PROTECTION OF ELECTRONIC
COMPUTER / DATA PROCESSING EQUIPMENT (2024)
STANDARD FOR THE INSTALLATION OF AIR CONDITIONING
AND VENTILATING SYSTEMS (2021)
STANDARD FOR THE INSTALLATION OF WARM AIR
HEATING AND AIR CONDITIONING SYSTEMS (2021)
LIFE SAFETY CODE (2021)
STANDARD FOR EMERGENCY AND STAND-BY POWER
SYSTEMS (2019)
STANDARD FOR THE INSTALLATION OF LIGHTNING
PROTECTION SYSTEMS (2023)
FLORIDA BUILDING CODE (2023)
FLORIDA BUILDING CODE ENERGY CONSERVATION (2023)
FLORIDA FIRE PREVENTION CODE (2023)
ICC/NSSA STANDARD FOR THE DESIGN AND
CONSTRUCTION OF STORM SHELTERS
LOCAL JURISDICITION CODES AND / OR OWNER DESIGN
GUIDELINES
SYMBOL DESCRIPTION
1. THE ELECTRICAL CONTRACT DOCUMENTS ARE SCHEMATIC IN NATURE AND
INDICATE THE GENERAL CONFIGURATION OF SYSTEMS AND WORK. EXAMINE
ARCHITECTURAL, INTERIOR DESIGN, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, PLUMBING, FIRE PROTECTION, TECHNOLOGY, AND FOOD SERVICE
DRAWINGS AND SPECIFICATIONS FOR LOCATIONS AND REQUIREMENTS OF
DEVICES, EQUIPMENT, LUMINARIES, AND SYSTEMS. CONTENT INDICATED ON
THE SPECIFICATIONS BUT NOT THE DRAWINGS, OR CONTENT INDICATED ON
THE DRAWINGS BUT NOT THE SPECIFICATIONS, SHALL BE INTERPRETED AS
BEING PRESENT ON BOTH.
2. PROVIDE ALL DEVICES, EQUIPMENT, ACCESSORIES, MATERIALS, AND LABOR
REQUIRED FOR A COMPLETE, FUNCTIONAL, AND CODE-COMPLIANT ELECTRICAL
SYSTEM. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CODES
AND STANDARDS INDICATED ON THIS SHEET.
3. ALL DEVICES, EQUIPMENT, ACCESSORIES, AND MATERIALS SHALL BE NEW, AND,
WHERE APPLICABLE, SHALL BE LISTED BY U.L. OR ANOTHER APPROVED
ELECTRICAL TESTING AGENCY.
4. COORDINATE LOCATIONS AND REQUIREMENTS OF EQUIPMENT REQUIRING
ELECTRICAL SERVICE (I.E. PRINTERS, APPLIANCES, MOTORIZED PROJECTION
SCREENS, MOTORIZED SHADES, ELEVATORS, TOOLS, ETC.) WITH APPROVED
SHOP DRAWINGS, SPECIFICATION SHEETS, MANUFACTURER’S INSTALLATION
LITERATURE, AND EQUIPMENT NAMEPLATE DATA, PRIOR TO ROUGH-IN AND
INSTALLATION. PROVIDE ELECTRICAL CONNECTIONS (AS REQUIRED).
5. BID SHALL INCLUDE COSTS ASSOCIATED WITH BACKFILLING, CORE DRILLING,
DIRECTIONAL BORING, EXCAVATING, AND REPAIRING OF SURFACES.
6. PAY ALL FEES, TAXES, AND OTHER COSTS ASSOCIATED WITH THE WORK
ENCOMPASSED BY THE ELECTRICAL CONTRACT DOCUMENTS. PROVIDE ALL
REQUIRED NOTICES AND OBTAIN ALL REQUIRED PERMITS.
7. PROVIDE COOPERATION WITH OTHER TRADES AND PROVIDE ANY INFORMATION
REQUIRED TO FACILITATE THE COMPLETION OF THEIR WORK. COORDINATE
DEVICE AND EQUIPMENT LOCATIONS AND MOUNTING HEIGHTS WITH OTHER
TRADES PRIOR TO ROUGH-IN AND INSTALLATION. COORDINATE CONDUIT
ROUTING WITH OTHER TRADES PRIOR TO ROUGH-IN AND INSTALLATION.
8. COORDINATE ALL REQUIREMENTS WITH THE LOCAL UTILITY PRIOR TO ROUGH-
IN AND INSTALLATION. COORDINATE LOCATIONS OF UTILITY HANDHOLES,
AERIAL UTILITY TRANSFORMERS, AND/OR PAD-MOUNTED UTILITY
TRANSFORMERS.
9. PROVIDE TEMPORARY ELECTRICAL SERVICE(S) FOR USE BY OTHER TRADES
DURING PROJECT CONSTRUCTION. UPON COMPLETION OF THE PROJECT, THE
TEMPORARY ELECTRICAL SERVICE(S) SHALL BE REMOVED.
10. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE RECORD
DRAWINGS TO THE OWNER. DRAWINGS SHALL BE COMPRISED OF SINGLE-LINE
DIAGRAMS AND FLOOR PLANS INDICATING THE LOCATIONS AND AREAS SERVED
FOR ALL DISTRIBUTION.
11. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE AN OPERATING
MANUAL AND MAINTENANCE MANUAL TO THE OWNER. THE MANUALS SHALL
INCLUDE THE FOLLOWING INFORMATION: SUBMITTAL DATA WITH EQUIPMENT
RATINGS AND SELECTED OPTIONS, OPERATION AND MAINTENANCE MANUALS
FOR EQUIPMENT REQUIRING MAINTENANCE, NAMES AND ADDRESSES OF A
MINIMUM OF ONE (1) QUALIFIED SERVICE AGENCY.
12. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL WALL-MOUNTED
ELECTRICAL DEVICES AND EQUIPMENT WITH THE ARCHITECTURAL DRAWINGS,
GENERAL CONTRACTOR, CASEWORK/MILLWORK, AND OTHER TRADES PRIOR TO
ROUGH-IN AND INSTALLATION.
13. EQUIPMENT LOCATIONS SHALL SATISFY THE WORKING CLEARANCE
REQUIREMENTS AND DEDICATED SPACE REQUIREMENTS OF NEC ARTICLE 110.
PROVIDE SHOP DRAWINGS, DEMONSTRATING COMPLIANCE AND INTER-
DISCIPLINARY COORDINATION, FOR ENGINEERING REVIEW.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS, SECTIONS, AND
ELEVATIONS FOR LOCATIONS AND/OR MOUNTING HEIGHTS OF LUMINARIES
LOCATED AT CEILINGS AND/OR WALLS. VERIFY THAT CEILING-MOUNTED
LUMINARIES ARE SUITABLE FOR THE FINISHED CEILING SYSTEM INDICATED AND
PROVIDE ACCORDINGLY. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF
WALL-MOUNTED LUMINARIES WITH CASEWORK, FURNITURE, AND
ARCHITECTURAL ELEMENTS. WHERE ARCHITECTURAL REFLECTED CEILING
PLANS INDICATE FIRE-RATED CEILING SYSTEMS, PROVIDE UL-LISTED LUMINAIRE
ENCLOSURES (AS REQUIRED).
SINGLE POWER TOGGLE SWITCH
(LETTER DENOTES FIXTURE CONTROLLED)
THREE-WAY TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
MOTOR SWITCH
FAN SWITCH
THREE POSITION SELECTOR SWITCH
TIMER SWITCH (60 MINUTES)
LOW VOLTAGE SWITCH
HAND-OFF-AUTOMATIC SWITCH
KEY SWITCH
SWITCH - WEATHERPROOF
DUAL TECH WALL SWITCH OCCUPANCY SENSOR
DUAL TECH, DUAL-LEVEL OCCUPANCY SENSOR SWITCH
DUAL TECH OCCUPANCY SENSOR - CEILING MOUNTED
DUAL TECH OCCUPANCY SENSOR - WALL MOUNTED
PHOTOCELL
LIGHTING CONTACTOR
TIME CLOCK
MAGNETIC MOTOR STARTER
ENCLOSED CIRCUIT BREAKER, AS INDICATED
PANELBOARD, 480 / 277V
PANELBOARD, 208 /120V
MANHOLE
HANDHOLE
SURGE PROTECTION DEVICE
ELECTRICAL METER
TRANSFORMER
MOTOR CONNECTION, HP: DENOTES HORSEPOWER RATING
GROUND BUS BAR
PUSHBUTTON
3/4" PLYWOOD TELEPHONE BACKBOARD
CONCRETE ENCASED DUCTBANK
WIRE IN CONDUIT CONCEALED BELOW SLAB OR GRADE
CONDUIT EXPOSED
FLEXIBLE CONDUIT
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT STUB
DISCONNECT SWITCH, NON-FUSIBLE
3 POLE, 60 AMP, NF: NON-FUSED, 3R: NEMA 3R ENCLOSURE
DISCONNECT SWITCH, FUSIBLE
3 POLE, 60 AMP, FUSED AT 50 AMPS, 3R: NEMA 3R ENCLOSURE
COMBINATION STARTER / DISCONNECT SWITCH, FUSIBLE
3 POLE, 60 AMP, NEMA x SIZE, 3R: NEMA 3R ENCLOSURE
HOMERUN TO PANEL INDICATED
NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS
WIRE IN CONDUIT CONCEALED, #12 AWG SIZE WIRE IN
3/4" CONDUIT MINIMUM UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
MOUNTED AT 48" UNLESS NOTED OTHERWISE
QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
MOUNTED AT 48" UNLESS NOTED OTHERWISE
GFI - TYPE DUPLEX RECEPTACLE
(WP: DENOTES WEATHERPROOF COVER)
GFI - DUPLEX RECEPTACLE
MOUNTED AT 48" UNLESS OTHERWISE NOTED
GFI - DOUBLE DUPLEX RECEPTACLE
MOUNTED AT 48" UNLESS OTHERWISE NOTED
SPECIAL PURPOSE RECEPTACLE
(NEMA RATING AS INDICATED)
QUADRAPLEX RECEPTACLE, TICK MARKS
DENOTE EMERGENCY (TYPICAL ALL RECEPTACLES)
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
SINGLE RECEPTACLE, 20 AMP, 120V U.O.N.
GFI - TYPE DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - HALF SWITCHED
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
COORD. TV MOUNTING HEIGHT WITH ARCHITECT / OWNER
FLOOR MOUNTED DUPLEX / QUAD RECEPTACLE. MINIMUM
3/4"C FOR POWER. REFER TO TECH DRAWINGS FOR CONDUIT,
AND DATA/AV DEVICE REQUIREMENTS. COVER AND FINISH BY
ARCHITECT. PROVIDE CORROSION / MOISTURE RESISTANT
COATING FOR BOXES INSTALLED IN SLAB ON GRADE.
PROVIDE A LEGRAND EVOLUTION SERIES OR APPROVED
EQUAL.
POWER POLE
JUNCTION BOX - CEILING MOUNTED
JUNCTION BOX - WALL MOUNTED
JUNCTION BOX - FLOOR / GROUND MOUNTED
CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED
NORMAL POWER
CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED
EMERGENCY POWER
CEILING MOUNTED 1'x4' LUMINAIRE
RECESSED OR SURFACE MOUNTED - NORMAL POWER
CEILING MOUNTED 1'x4' LUMINAIRE
RECESSED OR SURFACE MOUNTED - EMERGENCY POWER
CEILING MOUNTED 1'x4' LUMINAIRE
PENDANT MOUNTED - NORMAL POWER
CEILING MOUNTED 1'x4' LUMINAIRE
PENDANT MOUNTED - EMERGENCY POWER
STRIP LUMINAIRE - NORMAL POWER
STRIP LUMINAIRE - EMERGENCY POWER
DOWNLIGHT LUMINAIRE - NORMAL POWER
DOWNLIGHT LUMINAIRE - EMERGENCY POWER
WALL MOUNTED LUMINAIRE - NORMAL POWER
WALL MOUNTED LUMINAIRE - EMERGENCY POWER
CEILING FAN
TRACK LIGHTING WITH LUMINAIRE
UNDERCOUNTER LUMINAIRE
FLOOD LIGHT LUMINAIRE
POLE LIGHT LUMINAIRE
BOLLARD LUMINAIRE
STEP LIGHT LUMINAIRE
EMERGENCY BATTERY LIGHT UNIT
EXIT LIGHT - SINGLE FACE WITH DIRECTIONAL ARROW
EXIT LIGHT - DOUBLE FACE
EXIT LIGHT - WALL MOUNTED
3P/60A
NF
3R
3P/60A F:50A
3R
3P/60A Nx
3R
MH
HH
SPD
TX
HP
S
3S
4S
MS
FS
3PS
TS
LVS
HOAS
KS
WPS
OSS
DOSS
PC
LC
TC
OS
OS
TV
PP
J
J
J
COMMISSIONING
1. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL SUBMIT
EVIDENCE TO THE REGISTERED DESIGN PROFESSIONAL (ELECTRICAL
ENGINEER-OF-RECORD) OR REGISTERED DESIGN PROFESSIONAL’S
REPRESENTATIVE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN
TESTED TO ENSURE THAT THEY ARE CALIBRATED, ADJUSTED,
PROGRAMMED, AND SATISFY THE INTENT OF THESE CONTRACT
DOCUMENTS AND THE MANUFACTURERS’ WRITTEN INSTRUCTIONS.
FUNCTIONAL TESTING SHALL BE PERFORMED IN ACCORDANCE WITH
FBC C408.3.1.1 (VACANCY / OCCUPANCY SENSOR CONTROLS), FBC
C408.3.1.2 (TIME-SWITCH CONTROLS), AND/OR FBC C408.3.1.3 (DAYLIGHT
RESPONSIVE CONTROLS) (AS REQUIRED).
DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
AUTOMATIC SWITCHED RECEPTACLE
QUADRUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.
HALF-AUTOMATIC SWITCHED RECEPTACLE
VFD
VFD-RATED, REMOTE DISCONNECT SWITCH WITH EARLY-
BREAK, AUXILIARY CONTACTS FOR VFD DECELERATE-TO-
STOP SIGNAL. CONNECT CONTROL WIRING TO ASSOCIATED
VFD (AS REQUIRED).
15. PROVIDE A COMPLETE GROUNDING SYSTEM IN ACCORDANCE WITH APPLICABLE
SECTIONS OF THE NEC AND SPECIFICATIONS. BOND SERVICE ENTRANCE
ELECTRICAL EQUIPMENT TO BUILDING STEEL, GROUND RODS, METAL WATER
MAINS, LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES (WHERE
PRESENT), AND TELECOMMUNICATIONS SYSTEM GROUNDING ELECTRODES (AS
REQUIRED). EQUIPMENT GROUNDING SHALL BE OF THE WIRE TYPE.
16. MINIMUM CONDUIT SIZE SHALL BE 3/4".
17. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. ALL FEEDER AND BRANCH
CIRCUIT CONDUCTORS SHALL BE INSTALLED WITHIN CONDUIT, UNLESS
OTHERWISE INDICATED. ALL CONDUCTORS SHALL BE COPPER, UNLESS
OTHERWISE INDICATED.
18. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTI-WIRE
BRANCH CIRCUITS SHALL BE PROHIBITED.
19. CONNECTIONS TO TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE
MADE WITH FMC OR LFMC, UNLESS OTHERWISE INDICATED.
20. WHERE PRACTICABLE, CONDUITS SHALL BE CONCEALED BELOW SLABS, WITHIN
WALLS, AND ABOVE FINISHED CEILING SYSTEMS. WHERE CONDUITS ARE
EMBEDDED WITHIN CONCRETE SLABS, COORDINATE CONDUIT SIZE LIMITATIONS
AND SPACING REQUIREMENTS WITH THE STRUCTURAL DRAWINGS/ENGINEER
PRIOR TO INSTALLATION.
21. SEAL ALL CONDUIT PENETRATIONS AT FIRE-RATED PARTITIONS. REFER TO
DETAILS FOR FURTHER INFORMATION.
22. COORDINATE ALL CONDUIT PENETRATIONS WITH ARCHITECTURAL DRAWINGS,
STRUCTURAL DRAWINGS, FIELD CONDITIONS, AND OTHER TRADES. PROVIDE
SEALING FITTINGS TO PROHIBIT CONDENSATION AND/OR THE PASSAGE OF
GASES OR VAPORS (AS REQUIRED).
23. INCREASE FEEDER AND BRANCH CIRCUIT CONDUCTOR SIZES AS REQUIRED IN
ORDER TO MAINTAIN A MAXIMUM, CUMULATIVE VOLTAGE DROP OF 5% AT THE
END LOAD. MAXIMUM VOLTAGE DROP SHALL BE DISTRIBUTED AS FOLLOWS: 3%
FOR FEEDERS, 2% FOR BRANCH CIRCUITS. WHERE THE VOLTAGE DROP
REQUIREMENTS OF THE LOCAL ENERGY CODE ARE MORE STRINGENT, THE
REQUIREMENTS OF THE LOCAL ENERGY CODE SHALL TAKE PRECEDENCE.
WHERE PHASE AND NEUTRAL CONDUCTOR SIZES ARE INCREASED FOR
VOLTAGE DROP, THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE
INCREASED PROPORTIONATELY.
24. PROVIDE ALL REQUIRED DISCONNECT SWITCHES, STARTERS, AND
COMBINATION STARTER/DISCONNECT SWITCHES. MAKE CONNECTIONS TO ALL
ELECTRICALLY-DRIVEN DEVICES AND EQUIPMENT PROVIDED BY THE
MECHANICAL, PLUMBING, AND FIRE PROTECTION CONTRACTORS. EXAMINE
EQUIPMENT NAMEPLATE RATINGS PRIOR TO ROUGH-IN AND INSTALLATION.
PROVIDE OVERCURRENT PROTECTION IN ACCORDANCE WITH EQUIPMENT
NAMEPLATE RATINGS. PROVIDE ALL POWER SUPPLIES, CONTROL
TRANSFORMERS, RELAYS, AND OTHER ACCESSORIES REQUIRED TO FACILITATE
THE PROPER OPERATION OF MECHANICAL EQUIPMENT AS DESCRIBED WITHIN
THE MECHANICAL ENGINEER’S SEQUENCE OF OPERATIONS.
25. ALL INTERIOR ELECTRICAL EQUIPMENT SHALL BE OF NEMA 1 CONSTRUCTION,
UNLESS OTHERWISE INDICATED. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL
BE OF NEMA 3R CONSTRUCTION, UNLESS OTHERWISE INDICATED. EQUIPMENT
RATINGS SHALL CORRESPOND TO THEIR INSTALLED ENVIRONMENTS.
26. ALL NEW AND/OR EXISTING PANELBOARDS AND SWITCHBOARDS WITHIN THE
SCOPE OF THIS PROJECT SHALL BE PROVIDED WITH NEW, TYPEWRITTEN
DIRECTORIES. CIRCUIT DESCRIPTIONS SHALL CONTAIN ROOM NAMES AND
ROOM NUMBERS BASED UPON INSTALLED ROOM SIGNAGE.
27. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT ALL
SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, TRANSFORMERS, DISCONNECT
SWITCHES, ENCLOSED CIRCUIT BREAKERS, CABINETS, AND AUTOMATIC
TRANSFER SWITCHES. REFER TO DETAILS FOR FURTHER INFORMATION.
28. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT EACH CIRCUIT
BREAKER WITHIN A DISTRIBUTION PANEL, SWITCHBOARD, OR SWITCHGEAR.
29. PROVIDE TYPEWRITTEN OR ENGRAVED PANEL AND CIRCUIT IDENTIFICATION AT
DEVICE COVER PLATES.
30. PROVIDE HANDWRITTEN PANEL AND CIRCUIT IDENTIFICATION ON THE
EXTERIORS OF ALL JUNCTION BOXES, PULL BOXES, AND WIREWAYS.ELECTRICAL ABBREVIATIONS
SYMBOL DESCRIPTION
A
AC
A/C
AFCI
AHU
AIC
AL
ATS
AWG
C
CATV
CB
C/B
CCTV
CIR
CKT
CU
DC
DIA
EB
EC
EF
EG
ELEV
EM
EMT
EP
EPO
ER
ETR
EWC
EX
F
FA
FAA
FLA
FMC
G, GND
GFCI, GFI
GND
GRC
HOA
HVAC
HZ
IEEE
IG
AMPERES
ALTERNATING CURRENT
AIR CONDITIONING
ARC FAULT CIRCUIT INTERRUPTER
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
CONDUIT
CABLE TELEVISION
CRITICAL BRANCH
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CIRCUIT
COPPER
DIRECT CURRENT
DIAMETER
EQUIPMENT BRANCH
ELECTRICAL CONTRACTOR
EXHAUST FAN
EQUIPMENT GROUND
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
EMERGENCY POWER
EMERGENCY POWER OFF (BUTTON OR SWITCH)
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
ELECTRIC WATER COOLER
EXISTING TO REMAIN
FUSE
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FULL LOAD AMPERES
FLEXIBLE METAL CONDUIT
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
GALVANIZED RIGID METAL CONDUIT
HAND-OFF-AUTOMATIC SWITCH
HEATING, VENTILATION, AIR CONDITIONING
HERTZ
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
ISOLATED GROUND
IMC
KCMIL
KVA
LFMC
LTG
LRA
MC
MCB
MCC
MCP
MLO
MTD
NC
NEC
NEMA
NFPA
NL
NO
P
PB
PNL
PWR
QTY
REQ
RMC
RNC
RTS
RTU
SP
ST
SW
SYM
TEL
TGB
TMCB
TV
TYP
UG
UL
V
VA
VFD
W
WH
WP
XFMR
INTERMEDIATE METAL CONDUIT
THOUSAND CIRCULAR MILS
KILOVOLT - AMPERES
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIGHTING
LOCK ROTOR AMPS
METAL CLAD CABLE
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTION
MAIN LUGS ONLY
MOUNTED
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NIGHT LIGHT
NORMALLY OPEN OR NUMBER
POLE
PUSH BUTTON, PANIC BUTTON OR PULLBOX
PANEL
POWER
QUANTITY
REQUIRED
RIGID METAL CONDUIT
RIGID NON-METALLIC CONDUIT
REMOTE TEST STATION
ROOF TOP UNIT
SPARE
SHUNT-TRIP
SWITCH
SYMMETRICAL
TELEPHONE
TELECOMMUNICATIONS GROUNDING BUSBAR
THERMAL MAGNETIC CIRCUIT BREAKER
TELEVISION
TYPICAL
UNDERGROUND
UNDERWRITERS LABORATORY
VOLT
VOLT - AMPERE
VARIABLE FREQUENCY DRIVE
WATT OR WIRE
WIRE GUARD
WATER HEATER
WEATHERPROOF
TRANSFORMER
SYMBOL DESCRIPTION
DAYLIGHT HARVESTING SENSOR - CEILING MOUNTEDDH
DIMMING SWITCHSD
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING:
RELAY MODULE WITH 0-10V DIMMING OUTPUTPL
PLUG LOAD RELAY PACKPR
FIRE ALARM
SYMBOL DESCRIPTION
FACP: FIRE ALARM CONTROL PANEL
FATC: FIRE ALARM TERMINAL CABINET
FAAP: FIRE ALARM ANNUNCIATOR PANEL
EVAC: FIRE ALARM VOICE / EVAC. UNIT
FIRE ALARM MANUAL PULL STATION
FIRE ALARM SPEAKER DEVICE
FIRE ALARM SPEAKER DEVICE - CEILING MOUNTED
FIRE ALARM HEATER DETECTOR - CEILING MOUNTED
FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED
SB: SOUNDER BASE
I: IONIC
CO: CARBON MONOXIDE
FIRE ALARM SMOKE DETECTOR - WALL MOUNTED
SB: SOUNDER BASE
CO: CARBON MONOXIDE
UF: UNDERFLOOR
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM RELAY
ELECTROMAGNETIC DOOR CONTACT
DOOR HOLDER
FIRE ALARM REMOTE ALARM INDICATOR WITH TEST
SWITCH, FLUSH CEILING MOUNTED, WALL MTD.
CENTER LINE 48" A.F.F. IN MECHANICAL ROOMS
MONITORING MODULE
FIRE ALARM STROBE ONLY DEVICE
MINIMUM 75cd RATING
FIRE ALARM HORN / STROBE ONLY DEVICE
MINIMUM 75cd RATING
FIRE ALARM SPEAKER / STROBE ONLY DEVICE
MINIMUM 75cd RATING
FIRE ALARM STROBE ONLY DEVICE
MINIMUM 75cd RATING - CEILING MOUNTED
FIRE ALARM HORN / STROBE ONLY DEVICE
MINIMUM 75cd RATING - CEILING MOUNTED
FIRE ALARM SPEAKER / STROBE ONLY DEVICE
MINIMUM 75cd RATING - CEILING MOUNTED
FIRE ALARM HORN DEVICE
MINIMUM 75cd RATING
FIRE ALARM HORN DEVICE
MINIMUM 75cd RATING - CEILING MOUNTED
FIRE ALARM DUCT SMOKE DETECTOR
S: SUPPLY.....R: RETURN
P
S
S
S
S
S/R
R
DC
DH
RA
MM
FIRE ALARM KNOX BOXK
FIELD VERIFY ALL LOCATION
1. DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT
THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT
EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL
LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO
EXISTING CONDITIONS.
2. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR
OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND
CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO
MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT,
ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE
IMPLEMENTED AT CONTRACTORS COST.
3. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF
LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS
THE COST FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT
WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT,
ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN
GOVERNING CODES AND DESIGN INTENT.
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
N D
O T
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V E
IN
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
S P
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
R
C
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
A
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
H
X
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
G
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
IT
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
L A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y I
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
F
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B lv d.
ui te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 6:
A
M
E-000
LEGEND - ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
NUMBER NAME
E-000 LEGEND - ELECTRICAL
E-002 SCHEDULES - ELECTRICAL
E-003 SCHEDULES - ELECTRICAL
E-100 SITE PLAN - ELECTRICAL
ED-101 EXISTING BUILDING - FLOOR PLAN - ELECTRICAL
ED-102 EXISTING BUILDING -ONE-LINE - ELECTRICAL
E-201 LEVEL 1 - FLOOR PLAN - POWER
E-202 LEVEL 2 - FLOOR PLAN - POWER
E-203 ROOF PLAN - POWER
E-204 ROOF PLAN - LIGHTNING PROTECTION
E-205 ROOF PLAN - LIGHTNING PROTECTION DETAILS
E-301 LEVEL 1 - RCP - LIGHTING
E-302 LEVEL 2 - RCP - LIGHTING
E-401 ENLARGED FLOOR PLANS - ELECTRICAL
E-402 ENLARGED FLOOR PLANS - KITCHEN ELECTRICAL
E-500 ONE-LINE DIAGRAM NOTES
E-501 ONE-LINE DIAGRAM - ELECTRICAL
E-601 PANEL SCHEDULES - ELECTRICAL
E-602 PANEL SCHEDULES - ELECTRICAL
E-603 PANEL SCHEDULES - ELECTRICAL
E-604 PANEL SCHEDULES - ELECTRICAL
E-700 FIRE ALARM RISER - ELECTRICAL
E-901 DETAILS - ELECTRICAL
E-902 DETAILS - ELECTRICAL
E-903 DETAILS - ELECTRICAL
REV DESCRIPTION DATE
GENERAL NOTES - EL/MECH SCH.
A. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH THE
DIVISION 22 CONTRACTOR, DIVISION 23 CONTRACTOR AND
APPROVED EQUIPMENT SUBMITTALS PRIOR TO ROUGH-IN AND
INSTALLATION. REFER TO MECHANICAL AND PLUMBING
DRAWINGS FOR FURTHER INFORMATION.
B. FOR ALL VFD-DRIVEN EQUIPMENT, PROVIDE A VFD-RATED
CABLE ASSEMBLY BETWEEN THE VFD OUTPUT AND
ASSOCIATED EQUIPMENT AS FOLLOWS; XLPE INSULATION
RATED AT 2,000V, SHIELDED, 100% EQUIPMENT GROUND.
CONDUIT AND CONDUCTORS BETWEEN SOURCE AND VFD
INPUT SHALL BE AS SCHEDULED.
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 6:
A
M
E-002
SCHEDULES -
ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
ELECTRICAL MECHANICAL EQUIPMENT CHILLER SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
CH-1 167100 VA 465 208 V 3 600.4 - REFER TO E-5.01 MSB 7 --- --- --- 800A 3 NEMA 3R 26
ELECTRICAL MECHANICAL EQUIPMENT AIR HANDLER SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
AHU-1 15563 VA 43.2 208 V 3 60.4 - REFER TO E-5.01 LN1MA 1,3,5 --- --- --- 100A 3 NEMA 1 26
AHU-2 10779 VA 29.92 208 V 3 40A - REFER TO E-6xx SHEETS LN1MA 7,9,11 --- --- --- 60A 3 NEMA 1 26
AHU-3 1729 VA 4.8 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 13,15,17 --- --- --- 30A 3 NEMA 3R 26
ELECTRICAL MECHANICAL EQUIPMENT PUMP SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
STARTER TYPE NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
CHWP-1 8700 VA 24.2 208 V 3 35A - REFER TO E-6xx SHEETS LN1MA 2,4,6 VFD --- NEMA 3R 23 --- --- --- ---
CHWP-2 8700 VA 24.2 208 V 3 35A - REFER TO E-6xx SHEETS LN1MA 8,10,12 VFD --- NEMA 3R 23 --- --- --- ---
ELECTRICAL MECHANICAL EQUIPMENT ERV SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
ERV-1 13088 VA 29.04 208 V 3 40A - REFER TO E-6xx SHEETS LN2MA 1,3,5 --- --- --- 60A 3 NEMA 1 26
ELECTRICAL MECHANICAL EQUIPMENT VAV SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
CV-1-5 9400 VA 26 208 V 3 35A - REFER TO E-6xx SHEETS LN1MB 29,31,33 --- --- --- 60A 3 NEMA 1 26
CV-1-6 3700 VA 17.8 208 V 1 25A - REFER TO E-6xx SHEETS LN1MB 35,37 --- --- --- 30A 2 NEMA 1 26
CV-1-8 12500 VA 34.6 208 V 3 45A - REFER TO E-6xx SHEETS LN2MA 7,9,11 --- --- --- 60A 3 NEMA 1 26
CV-1-9 12400 VA 34.4 208 V 3 45A - REFER TO E-6xx SHEETS LN2MB 27,29,31 --- --- --- 60A 3 NEMA 1 26
IWH-1 6240 VA 30 208 V 1 40A - REFER TO E-6xx SHEETS LN1MB 21,23 --- --- --- 30A 3 NEMA 1 26
VAV-1-1 1500 VA 7.2 208 V 1 20A - REFER TO E-6xx SHEETS LN1MA 13,15 --- --- --- 30A 2 NEMA 1 26
VAV-1-2 5400 VA 15 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 6,8,10 --- --- --- 30A 3 NEMA 1 26
VAV-1-3 7500 VA 21 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 12,14,16 --- --- --- 30A 3 NEMA 1 26
VAV-1-4 2100 VA 10 208 V 1 20A - REFER TO E-6xx SHEETS LN1MB 25,27 --- --- --- 30A 2 NEMA 1 26
VAV-1-7 1300 VA 6.25 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 33,35 --- --- --- 30A 2 NEMA 1 26
VAV-1-10 2200 VA 10.6 208 V 1 20A - REFER TO E-6xx SHEETS LN2MA 2,4 --- --- --- 30A 2 NEMA 1 26
VAV-1-11 4600 VA 22 208 V 1 30A - REFER TO E-6xx SHEETS LN2MA 6,8 --- --- --- 30A 3 NEMA 1 26
VAV-1-12 9100 VA 25 208 V 3 35A - REFER TO E-6xx SHEETS LN2MB 1,3,5 --- --- --- 30A 3 NEMA 1 26
VAV-1-13 2700 VA 13 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 18,20 --- --- --- 30A 2 NEMA 1 26
VAV-1-14 1100 VA 5.2 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 30,32 --- --- --- 30A 2 NEMA 1 26
VAV-1-15 2900 VA 13.94 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 22,24 --- --- --- 30A 2 NEMA 1 26
VAV-1-16 2000 VA 9.615 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 26,28 --- --- --- 30A 2 NEMA 1 26
ELECTRICAL MECHANICAL EQUIPMENT FAN SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
EF-1 666 VA 3.2 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 14,16 --- --- --- 30A 2 NEMA 1 26
EF-2 528 VA 4.4 115 V 1 20A - REFER TO E-6xx SHEETS LN1MB 2 --- --- --- 30A 1 NEMA 1 26
KEF-1 1518 VA 7.3 208 V 3 20A - REFER TO E-6xx SHEETS LN2MB 2,4,6 --- --- --- 30A 3 NEMA 3R 26
ELECTRICAL MECHANICAL EQUIPMENT MAKE UP AIR SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
MUA-1 1186 VA 5.7 208 V 3 20A - REFER TO E-6xx SHEETS LN2MB 8,10,12 --- --- --- 30A 3 NEMA 3R 26
ELECTRICAL PLUMBING EQUIPMENT WATER HEATERS
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
EWH-1 36000 VA 173.07 208 V 3 225.4 - REFER TO E-5.01 LN1MB 3,5,7 --- --- --- 200A 3 NEMA 3R 26
EWH-2 4500 VA 21.6 208 V 1 25A - REFER TO E-6xx SHEETS LN1MA 17,19 --- --- --- 30A 2 NEMA 3R 26
ELECTRICAL PLUMBING EQUIPMENT PUMPS
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
BP-1 6720 VA 56 120 V 1 70.4 - REFER TO E-5.01 LN1MA 31 --- NEMA 1 26 100A 1 NEMA 1 26
CP1 1176 VA 9.8 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 11 --- NEMA 1 26 20A 1 NEMA 1 26
CP-2 1176 VA 9.8 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 9 --- NEMA 1 26 20A 1 NEMA 1 26
SP-1 200 VA 1.7 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 1 30A 1 NEMA 3R
ELECTRICAL MECHANICAL DUCT HEATER SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
DH-1 60000 VA 167 208 V 3 200.4 - REFER TO E-5.01 LN1MA 25,27,29 --- --- --- 300A 3 NEMA 1 26
ELECTRICAL CONDENSING UNIT SCHEDULE
TAG LOAD
FLA
(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER
STARTER DISCONNECT
NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)
COOLER 2090 VA 5.8 208 V 3 20A - REFER TO E-6xx SHEETS LK1B1 8,10,12 --- --- --- 30A 3 NEMA 3R 26
CU-1 2300 VA 11.4 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 21,23 --- --- --- 30A 2 NEMA 3R 26
FREEZER 3459 VA 9.6 208 V 3 20A - REFER TO E-6xx SHEETS LK1B1 14,16,18 --- --- --- 30A 3 NEMA 3R 26
GENERAL NOTES - LUMINAIRE SCH.
A. COORDINATE COLORS AND FINISHED WITH ARCHITECT AND /
OR OWNER PRIOR TO ORDERING.
B. COORDINATE LAMP SOURCE COLOR TEMPERATURE WITH
ARCHITECT PRIOR TO ORDERING.
C. WHERE A LUMINAIRE IS AVAILABLE IN TRIM-BASED AND
TRIMLESS CONFIGURATIONS, COORDINATE THE
APPROPRIATE CONFIGURATION WITH THE ARCHITECT PRIOR
TO ORDERING.
D. COORDINATE CEILING TYPES WITH THE ARCHITECT PRIOR TO
ORDERING. ONE (1) LUMINAIRE TYPE MAY BE LOCATED
WITHIN MULTIPLE CEILING TYPES. REFER TO
ARCHITECTURAL REFLECTED CEILING PLANS FOR FURTHER
INFORMATION.
E. PROVIDE INDEPENDENT SUPPORTS TO THE BUILDING
STRUCTURE IN ACCORDANCE WITH THE APPLICABLE
DIVISION 26 SPECIFICATION SECTIONS.
F. WHERE A LUMINAIRE IS EQUIPPED WITH A DIMMABLE DRIVER,
BUT IS NOT DEPICTED AS CONTROLLED VIA A DIMMER
SWITCH ON THE LIGHTING PLANS, TERMINATE THE 0-10V
CONTROL WIRING IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS TO ALLOW FOR ON / OFF SWITCHING.
G. VERIFY COMPATIBILITY BETWEEN DIMMER SWITCHES AND
DIMMABLE DRIVERS PRIOR TO ORDERING.
H. COORDINATE LUMINAIRE LOCATIONS, MOUNTING HEIGHTS
(WHERE APPLICABLE), SUSPENSION HEIGHTS (WHERE
APPLICABLE) AND SUSPENSION METHODS (WHERE
APPLICABLE) WITH ARCHITECT PRIOR TO ORDERING, ROUGH-
IN AND INSTALLATION.
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 7:
A
M
E-003
SCHEDULES -
ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
LIGHTING CONTROL MATRIX
EXTERIOR LIGHTING CONTACTOR
RELAY /
DIMMER
MODULE
NUMBER PANEL
CIRCUIT
NUMBER SWITCH TYPE CONTROLLED BY
SWITCH ID
(ZONE) NOTE Voltage AREA CONTROLLED
1 LEM1A 1 OVERRIDE TIMECLOCK/PHOTOCELL Z1 120 V EXTERIOR SCONCES
2 LEM2B 8 OVERRIDE TIMECLOCK/PHOTOCELL Z2 120 V EXTERIOR DOWNLIGHTS
LUMINAIRE SCHEDULE
Image TYPE DESCRIPTION MANUFACTURER MODEL # LUMENS LAMP TYPE VOLTAGE WATTAGE DIMMING MOUNTING NOTES
A 2X4 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR
WARRANTY
METALUX OR APPROVED EQUAL 24CGTS-L3C3-MID-4000K 5241 lm 80CRI/SET TO 4000K
120-277V 39 VA 0-10V/10% RECESSED
B 2X2 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR
WARRANTY
METALUX OR APPROVED EQUAL 22CGTS-L3C3-MID-4000K 3890 lm 80CRI/SET TO 4000K
120-277V 29 VA 0-10V/10% <varies>
BE 2X2 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR
WARRANTY W/ EMERGENCY 14W BATTERY
METALUX OR APPROVED EQUAL 22CGTS-L3C3-MID-4000K-EL7W 3890 lm 80CRI/SET TO 4000K
120-277V 29 VA 0-10V/10% RECESSED FIXTURE USED IN
EXISTING
BUILDING.
C1 4’ STRIP FIXTURE INTEGRAL FACTORY INSTALLED CONTROLS OPTION ALLOWS MORE ENERGY
SAVINGS, 5 YEAR WARRANTY
METALUX OR APPROVED EQUAL 4SNX-41SL-LW-UNV-L840-CD 3848 lm 80CRI/SET TO 4000K
120-277V 26 VA 0-10V/10% SURFACE/SUSPE
NDED
C2 8' STRIP FIXTURE INTEGRAL FACTORY INSTALLED CONTROLS OPTION ALLOWS MORE ENERGY
SAVINGS, 5 YEAR WARRANTY
METALUX OR APPROVED EQUAL 8TSNX-XXXX-XX-UNV-L8XX-CD1-U 0 lm 80CRI/SET TO 4000K
120-277V 0 VA 0-10V/10% SURFACE/SUSPE
NDED
D 4' VANITY, 4760 LUMENS, ALUMINUM AND STEEL WITH VARIOUS PAINT FINISHES, 50,000 HOUR L70
RATED LIFE, 5 YEAR WARRANTY
KUZCO OR APPROVED EQUAL VL61248-CH 3810 lm 90CRI/SET TO 4000K
120V 59 VA 0-10V SURFACE
E1 6” RECESSED DOWNLIGHT, NEW CONSTRUCTION/REMODEL SERIES; 500 TO 6,000 LUMENS,
UNIVERSAL VOLTAGE 120V-277V; STANDARD 0-10V DRIVER DIMS TO 1%, 5 YEAR WARRANTY
COOPER OR APPROVED EQUAL HC610D010-HM60525835-61WDC 1279 lm 90CRI/SET TO 3500K
120-277V 10 VA 0-10V/1% RECESSED
E2 6” RECESSED DOWNLIGHT, NEW CONSTRUCTION/REMODEL SERIES; 500 TO 6,000 LUMENS,
UNIVERSAL VOLTAGE 120V-277V; STANDARD 0-10V DRIVER DIMS TO 1%, 5 YEAR WARRANTY
COOPER OR APPROVED EQUAL HC620D010-HM60525835-61WDC 2359 lm 90CRI/SET TO 3500K
120-277V 20 VA 0-10V/1% RECESSED
EM EMERGENCY BUG EYE FIXTURES ACTIVATED DURING POWER LOSS ISOLITE OR APPROVED EQUAL BUG-3W-WH-MB 600 lm LED 120-277V 5 VA - SURFACE
F 4' STAIR LIGHT, IK10 RATED, 16 GA CRS, HIGH IMPACT FROSTED LENS, 9800 LUMENS, INTEGRAL
PIR SENSOR, 10W EMERGENCY, 50,000 HOUR L70 RATED LIFE, 5 YEAR WARRANTY
METALUX OR APPROVED EQUAL 4SWLED-48HL-LW-UNV-L840-CD1-U 4899 lm 80CRI/SET TO 4000K
120-277V 45 VA 0-10V/10% SURFACE
G HIGHBAY, SET 18,000 LUMENS, IP65/WET LOCATION LISTED, SWITCHABLE 4000K/5000K, NEMA 4X, IP65 AND NSF RATED, IMPACT PROTECTION RATING IK08 LENS AND IK08 HOUSING, 5 YEAR
WARRANTY
METALUX OR APPROVED EQUAL UHBS-18-MV-L840-U 120V 18353 lm 4000K,80CRI,LED 120-347V 120 VA 0-10V SUSPENDED 26'
AFF
H1 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 4200 lm 80CRI/4000K 120-277V 157 VA 0-10V/10% SUSPENDED
H2 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 3600 lm 80CRI/4000K 120-277V 157 VA 0-10V/10% SUSPENDED
H3 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 3600 lm 80CRI/4000K 120-277V 126 VA 0-10V/10% SUSPENDED
J 8' RECESSED MOUNT IS A HIGH-PERFORMANCE ARCHITECTURAL LINEAR LED FIXTURE
DESIGNED FOR MODERN SPACES THAT REQUIRE BOTH AESTHETIC APPEAL AND EFFICIENCY.
AXIS OR APPROVED EQUAL SCR-500-80-30-FL-4 2005 lm 80CRI/SET TO 4000K
120-277V 23 VA 0-10V/1% RECESSED
K1 1' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5
YEAR WARRANTY
MERCURY ARCHITECTURAL
LIGHTING OR APPROVED EQUAL
MLA-DI-12-1050-1250-30K-HTA-BW-1_-2
C-U-MG
9264 lm 80CRI/4000K 120-277V 88 VA 0-10V/10% SUSPENDED
K2 2' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5
YEAR WARRANTY
MERCURY ARCHITECTURAL
LIGHTING OR APPROVED EQUAL
MLA-DI-24-1050-1250-30K-HTA-BW-1_-2
C-U-MG
9264 lm UNLIT N/A 88 VA N/A SUSPENDED
K2E 2' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5
YEAR WARRANTY
MERCURY ARCHITECTURAL
LIGHTING OR APPROVED EQUAL
MLA-DI-24-1050-1250-30K-HTA-BW-1_-2
C-U-MG
9264 lm UNLIT N/A 88 VA N/A SUSPENDED
K4E 4' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5
YEAR WARRANTY
MERCURY ARCHITECTURAL
LIGHTING OR APPROVED EQUAL
MLA-DI-48-1050-1250-30K-HTA-BW-1_-2
C-U-MG
9264 lm 80CRI/4000K 120-277V 88 VA 0-10V/1% SUSPENDED
L 4" CYLINDER, 2000 LUMENS, 55,000 HOUR L70 RATED LIFE, 5 YEAR WARRANTY HE WILLIAMS OR APPROVED EQUAL CF06XXPC 20L 30K XW XX CL XX 1455 lm 80CRI/4000K 120-277V 13 VA 0-10V/1% SUSPENDED
LP 4' ELEVATOR PIT LIGHTING VAPOR-TIGHT LIGHT WEIGHT LED FIXTURE, 5 YEAR WARRANTY METALUX OR APPROVED EQUAL 4APVTLD-SL3C3 4620 lm 4000K 120-277V 145 VA 0-10V/10% SURFACE
M 2X2 LINEAR HIGHBAY COMPACT, 3 LUMEN OUTPUT, 40/50K CCT SPITZER OR APPROVED EQUAL LHC-14-180LC 15000 lm 80CRI/4000K 120-277V 117 VA 0-10V SURFACE PROVIDE WITH
WIRE GUARD
X LED EXIT LIGHT FIXTURE WITH INTEGRAL LED TEST SWITCH SURE-LITES OR APPROVED EQUAL SCX60G 0 lm N/A 120-277V 5 VA <varies> <varies>
Z COLOR CHANGEABLE CUT-OFF EXTERIOR WALLPACK SPITZER OR APPROVED EQUAL WPFP-XXX-U-CC-XX-C1-XX 0 lm TBD 120-277V 0 VA - SURFACE
MM
A. COORDINATE WITH DUKE ENERGY FOR ELECTRIC UTILITY
SERVICE CONNECTION AND REQUIREMENTS.
B. UNDERGROUND CONDUIT IS DIAGRAMMATIC ONLY. FINAL
ROUTING, QUANTITY, AND SIZE SHALL BE COORDINATED WITH
CIVIL CONTRACTOR.
PROVIDE ASCO 300 GENERATOR
DOCKING STATION. REFER TO
ELECTRICAL ONE-LINE DIAGRAM
(MAIN BUILDING) FOR
FURTHER INFORMATION.
PROVIDE 4" CONCRETE PAD FOR
MOUNTING.
GENERATOR ROOM
PROPOSED LOCATION
OF UTILITY
TRANSFORMER
MAIN ELECTRICAL
ROOM 109
LEVEL 1 ELECTRICAL
ROOM 116
LEVEL 2 ELECTRICAL
ROOM 201
LEVEL 2 ELECTRICAL
ROOM 215
(8) SETS 4#600 CU IN 4"C
PROPOSED LOCATION
OF UTILITY METER
EXISTING
BUILDING
EXISTING
PARKING LOT
NEW PARKING LOT
NOT IN SCOPE
(2) SETS 3#600 CU IN 4"C
COORDINATE TAMPER SWITCH
PLACEMENT WITH PROPOSED NEW
BACKFLOW DEVICE AND FDC LOCATION.
DIESEL PUMP
3P/30A 3R
NF
PROVIDE ICC 500 COMPLIANT ENCLOSURE.
(3) SETS 3#600 CU IN 4"C
LEM1A-4,6
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
GENERAL NOTES
KEY NOTES
KEY PLAN
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 6:
A
M
E-100
SITE PLAN -
ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
0' 15' 30' 60' 120'
SCALE: 1" = 30'-0"
N
1" = 30'-0"
SITE PLAN - ELECTRICAL
A. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE
PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING
CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.
B. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT
AND MAINTAIN THE INTEGRITY OF REMAINING DEVICES AND
EQUIPMENT. ANY SUCH CONNECTIONS SHALL BE CONCEALED
UNLESS LOCATED IN UNFINISHED AREAS.
C. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
REMOVE AND LEGALLY DISPOSE OF DEMOLISHED MATERIALS.
D. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL
SCHEDULED FOR REMOVAL AND SALVAGE ANY ITEMS DEEMED
USEABLE AS SPARE PARTS.
E. EXISTING CONDITIONS INDICATED ON THIS DRAWING ARE TAKEN
FROM FIELD INVESTIGATION. IT IS RECOMMENDED FOR
CONTRACTOR TO VISIT SITE AND VERIFY EXISTING CONDITIONS
PRIOR TO BID.
F. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL
DEVICES, FITTINGS, CONDUITS, ETC. IT IS INTENDED TO PROVIDE
THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING
CONDITIONS WITHIN THE PROJECT AREA.
G. THE CONTRACTOR SHALL INSURE THAT CONDUITS REMAINING
WITHIN THE PROJECT AREA ARE SUPPORTED IN ACCORDANCE
WITH THE SPECIFICATIONS. CONDUITS THAT ARE ATTACHED TO
ITEMS BEING REMOVED DURING DEMOLITION SHALL BE
SUPPORTED FROM THE STRUCTURE PRIOR TO REMOVING ITEM.
H. EXISTING PANEL DIRECTORIES SHALL BE UPDATED TO REFLECT
CURRENT CONDITIONS.
I. CONTRACTOR SHALL PATCH, PAINT, AND MATCH FINISH WITH
EXISTING SURFACES TO REMAIN WHERE ELECTRICAL DEVICES
ARE BEING RELOCATED.
J. DASHED SYMBOLS SHALL BE DEMOLISHED UNLESS OTHERWISE
NOTED.
K. CONTRACTOR SHALL REVIEW FLOOR PLANS FOR DEVICES TO
REMAIN PRIOR TO DEMOLITION.
L. WHERE WORK BY THE CONSTRUCTION MANAGER (WALL
REMOVAL, NEW OR RELOCATED WALL OPENINGS, ETC.)
RESULTS IN THE REMOVAL, RELOCATION OR REFEEDINGS OF
ELECTRICAL DEVICES OR LIGHTING FIXTURES, THE ELECTRICAL
CONTRACTOR SHALL DISCONNECT AND RECONNECT AS
REQUIRED ALL ACTIVE DEVICES REMAINING.
M. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR
FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL
RELOCATE ASSOCIATED ELECTRICAL DEVICES, EQUIPMENT AND
OTHER EXISTING SYSTEMS SERVING ITEMS BEING RELOCATED.
N. COORDINATE MECHANICAL AND PLUMBING DEMOLITION WITH
RESPECTIVE CONTRACTORS. REMOVE POWER CONNECTIONS
FROM ALL DEVICES MARKED FOR DEMOLITION ON MECHANICAL
AND PLUMBING DRAWINGS.
O. ALL CIRCUIT BREAKERS SERVING DEMOLITION DEVICES SHALL
BECOME SPARE AND TURN TO THE OFF POSITION. SERVING
PANELBOARD SCHEDULE SHALL BE UPDATED AND READ 'SPARE'.
P. INSTALL A BLANK COVER PLATE WHERE REQUIRED.
EQUIPMENT TO BE DEMOLISHED
EXISTING TO REMAIN
NEW WORK
LINE STYLE TYPES
(EXISTING) UTILITY XFMR
208 / 120 V
3-PHASE, 4 WIRE
EXISTING ELECTRICAL UTILITY METER
EXISTING DUKE
ENERGY PRIMARY
SERVICE
225A
A
(EXISTING)
M
(EXISTING) MDP
208/120V, 3-PHASE, 4 WIRE
800 A, MLO, FUSED
PANELBOARD
200A
B
(EXISTING)
200A
C
(EXISTING)
200A
D
(EXISTING)
CHILLER
(EXISTING)
PROJECT SCOPE OF
WORK
225AT
400AF
200AT
200AF
200AT
200AF
200AT
200AF
400AT
400AF
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
GENERAL NOTES
KEY NOTES
KEY PLAN
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 7:
A
M
ED-102
EXISTING BUILDING
-ONE-LINE -
ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
0' 4' 12' 24' 42'-8"
SCALE: 3/32" = 1'-0"
N
NTS
EXISTING ONE-LINE DIAGRAM
THIS IS AN EXISTING PANEL.
1- LOCKED BREAKER
2- HACR
PANEL NOTES:
Spare 380 VA 100.00% 380 VA
TOTAL DEMAND VA 380 VA DEM LOAD AMPS 1 A
TOTAL VA 380 VA TOTAL AMPS 1 A
PHASE VA 129 VA 117 VA 134 VA
41 -- LIGHTS 20 A 1 13 VA 0 VA 1 20 A SPACE -- 42
39 -- LIGHTS 20 A 1 6 VA 0 VA 1 20 A SPACE -- 40
37 -- LIGHTS 20 A 1 11 VA 9 VA 38
35 -- RECEPT TEL 20 A 1 6 VA 9 VA
2 20 A SITE LIGHTS --
33 -- RECEPT 20 A 1 9 VA 10 VA 1 20 A RECEPT -- 34
31 -- RECEPT 20 A 1 11 VA 10 VA 1 20 A FACP & SECURITY -- 32 1
29 -- LIGHTS 20 A 1 15 VA 12 VA 1 20 A RECEPT -- 30
27 -- LIGHTS 20 A 1 15 VA 6 VA 1 20 A RECEPT -- 28
25 -- LIGHTS 20 A 1 12 VA 6 VA 1 20 A RECEPT -- 26
23 -- LIGHTS 20 A 1 14 VA 9 VA 1 20 A RECEPT -- 24
1 21 -- ST POWER 20 A 1 7 VA 11 VA 1 20 A LIGHTS -- 22
19 -- SHUNT TRIP 20 A 1 1 VA 10 VA 1 20 A LIGHTS -- 20
17 -- RECEPT 20 A 1 6 VA 11 VA 1 20 A LIGHTS -- 18
15 -- SHUNT TRIP 20 A 1 1 VA 10 VA 1 20 A LIGHTS -- 16
13 -- MAU 20 A 1 7 VA 6 VA 1 20 A AMPLIFIER -- 14
11 22 VA 3 VA 1 20 A HOOD LIGHTS -- 12
-- EWH 4.5 KW 30 A 2
22 VA 6 VA 1 20 A HOOD CONTROL -- 10
7 -- EXHAUST FAN 20 A 1 10 VA 16 VA 1 20 A HOT TABLE -- 8
5 5 VA 10 VA 1 20 A ICE MACHINE -- 6 2
3 5 VA 10 VA 1 20 A REFRIGERATOR -- 4
-- DISPOSER 1 HP 15 A 3
5 VA 15 VA 1 25 A FREEZER -- 2
NOTES
CKT
LOAD
CLASS.
ABBR.
CIRCUIT DESCRIPTION
TRIP
AMPS
BRKR.
POLES
A PHASE
LOAD VA
B PHASE
LOAD VA
C PHASE
LOAD VA
BRKR.
POLES
TRIP
AMPS
CIRCUIT DESCRIPTION
LOAD
CLASS.
ABBR.
CKT
NOTES
3 42 SURFACE NEMA 1 120/208 Wye
MAIN LUGS 200A PHASE CIRCUIT MOUNT NEMA VOLTAGE AIC RATING 22kAIC
MAIN BREAKER BUS RATING 200 A
SUPPLIED FROM
PANEL B
S
S
D H
S
S
S
S
A. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE
PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING
CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.
B. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT
AND MAINTAIN THE INTEGRITY OF REMAINING DEVICES AND
EQUIPMENT. ANY SUCH CONNECTIONS SHALL BE CONCEALED
UNLESS LOCATED IN UNFINISHED AREAS.
C. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO
REMOVE AND LEGALLY DISPOSE OF DEMOLISHED MATERIALS.
D. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL
SCHEDULED FOR REMOVAL AND SALVAGE ANY ITEMS DEEMED
USEABLE AS SPARE PARTS.
E. EXISTING CONDITIONS INDICATED ON THIS DRAWING ARE TAKEN
FROM FIELD INVESTIGATION. IT IS RECOMMENDED FOR
CONTRACTOR TO VISIT SITE AND VERIFY EXISTING CONDITIONS
PRIOR TO BID.
F. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL
DEVICES, FITTINGS, CONDUITS, ETC. IT IS INTENDED TO PROVIDE
THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING
CONDITIONS WITHIN THE PROJECT AREA.
G. THE CONTRACTOR SHALL INSURE THAT CONDUITS REMAINING
WITHIN THE PROJECT AREA ARE SUPPORTED IN ACCORDANCE
WITH THE SPECIFICATIONS. CONDUITS THAT ARE ATTACHED TO
ITEMS BEING REMOVED DURING DEMOLITION SHALL BE
SUPPORTED FROM THE STRUCTURE PRIOR TO REMOVING ITEM.
H. EXISTING PANEL DIRECTORIES SHALL BE UPDATED TO REFLECT
CURRENT CONDITIONS.
I. CONTRACTOR SHALL PATCH, PAINT, AND MATCH FINISH WITH
EXISTING SURFACES TO REMAIN WHERE ELECTRICAL DEVICES
ARE BEING RELOCATED.
J. DASHED SYMBOLS SHALL BE DEMOLISHED UNLESS OTHERWISE
NOTED.
K. CONTRACTOR SHALL REVIEW FLOOR PLANS FOR DEVICES TO
REMAIN PRIOR TO DEMOLITION.
L. WHERE WORK BY THE CONSTRUCTION MANAGER (WALL
REMOVAL, NEW OR RELOCATED WALL OPENINGS, ETC.)
RESULTS IN THE REMOVAL, RELOCATION OR REFEEDINGS OF
ELECTRICAL DEVICES OR LIGHTING FIXTURES, THE ELECTRICAL
CONTRACTOR SHALL DISCONNECT AND RECONNECT AS
REQUIRED ALL ACTIVE DEVICES REMAINING.
M. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR
FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL
RELOCATE ASSOCIATED ELECTRICAL DEVICES, EQUIPMENT AND
OTHER EXISTING SYSTEMS SERVING ITEMS BEING RELOCATED.
N. COORDINATE MECHANICAL AND PLUMBING DEMOLITION WITH
RESPECTIVE CONTRACTORS. REMOVE POWER CONNECTIONS
FROM ALL DEVICES MARKED FOR DEMOLITION ON MECHANICAL
AND PLUMBING DRAWINGS.
O. ALL CIRCUIT BREAKERS SERVING DEMOLITION DEVICES SHALL
BECOME SPARE AND TURN TO THE OFF POSITION. SERVING
PANELBOARD SCHEDULE SHALL BE UPDATED AND READ 'SPARE'.
P. INSTALL A BLANK COVER PLATE WHERE REQUIRED.
EXISTING
ACTIVITY
ROOM
EXISTING
KITCHEN
EXISTING
STORAGE
EXISTING
STORAGE
EXISTING
STORAGE
EXISTING
CUSTODIAL
KITCHEN HOOD
B-6
B-17
B-17
B-17
B-4 B-2
B-26
B-8
B-26
B-24 B-9,11
DISPOSER
B-1,3,5
ELEC WATER
HEATER
D1
D2
D2
D2
(TYP)
B
B
B
B
B
B
BE
(TYP)
NEW STORAGE
NEW CORRIDOR
NEW STORAGE
FIRE RISER ROOM
EXISTING ELEC.
EXISTING CUSTODIAL
TIE-IN TO EXISTING LIGHTING
CIRCUIT AND SWITCH.
X
X
X
B
BE
BE
B
BE
EXISTING
NEW STORAGE
EXISTING PANEL 'B'
B-31
B-31
B-6
B-17
B-26
EX
EX
NEW STORAGE
FIRE RISER ROOM
NEW CORRIDOR
EXISTING CUSTODIAL
EXISTING ELEC.
(TYPICAL)
D3
D4
D5
D3
D5
D5
EXISTING TO REMAIN.
PROTECT IN PLACE
AND MAINTAIN CIRCUIT
CONTINUITY.
REMOVE EXISTING DISCONNECT SWITCH SERVING ELECTRIC
WATER HEATER AND ASSOCIATED CONDUIT AND
CONDUCTORS BACK TO SOURCE. UPDATE SERVING
PANELBOARD SCHEDULE TO READ "SPARE" AND SWITCH
BREAKER TO OFF POSITION.
EXISTING ELECTRICAL DEVICE SHALL BE DEMOLISHED.
EXISTING ELECTRICAL CIRCUIT SHALL REMAIN AND BE
REUSED TO CONNECT NEW ELECTRICAL DEVICES AS SHOWN
ON RENOVATION PLANS. PULL CIRCUIT BACK TO CLOSEST
JUNCTION BOX AND EXTEND AS REQUIRED FOR NEW
CONNECTIONS.
EXISTING LIGHTING FIXTURES SHALL BE DEMOLISHED.
EXISTING ELECTRICAL CIRCUIT SHALL REMAIN AND BE
REUSED TO CONNECT NEW FIXTURES AS SHOWN ON
RENOVATION PLANS. PULL CIRCUIT BACK TO CLOSEST
JUNCTION BOX AND EXTEND AS REQUIRED FOR NEW
CONNECTIONS.
VERIFY CONDITIONS OF EXISTING SWITCH. IF APPROPRIATE,
LEAVE IN PLACE TO REUSE FOR RENOVATION.
EXISTING SWITCHES SHALL BE DEMOLISHED.
KEY NOTES
(DEMOLITION)
1. PROVIDE 120V POWER CONNECTION FROM EXISTING POWER
CIRCUIT LEFT FROM DEMOLITION OF EXISTING DEVICES. SEE
DEMOLITION PLAN FOR APPROXIMATE LOCATION.
D1
D2
D3
D4
D5
T H
E A
R C
H
IT
E C
T 'S
C O
M M
O N
L A
W C
O P
Y R
IG
H
T A
H E
R P
R O
P E
R T
Y R
IG
H
T S
A R
E H
E R
E B
Y R
E S
E R
V
H E
I D
E A
S
D E
S
IG
N S
P L A
N S
D
R A
W
IN
G S
A
E C
IF
IC
A T
IO
N
S P
R O
D U
C E
D B
Y T
H E
A R
C H
IT
E
C T
T H
E S E
I D
E A
S
D E
S
IG
N S
P L A
N S
D R
A W
IN
G
S
A
E C
IF
IC
A T
IO
N
S S
H A
L L N
O T
B E
R E
P R
O D
U C
E D
N V
E Y
E D
I N
A N
Y M
A N
N E
R N
O R
A S
S
IG
N E
D
Y T
H
IR
D P
A R
T Y
W
IT
H O
U T
F
IR
S T
O B
T A
IN
IN
G T
P R
E S S W
R
IT
T E
N P
E R
M
IS
S
IO
N O
F T
C H
IT
E
C T
C
O N
S E
N T
I S
H E
R E
B Y
G R
A N
T E
D
V E
R N
M E
N T
A L A
G E
N C
IE
S
T O
R E
P R
O D
U C
E T
N S T
R U
C T
IO
N
D R
A W
IN
G
S I
N C
O M
P L
IA
N C
E W
E S
T A
T E
S T
A T
U T
E S
T O
T H
E B
E S
T O
F T
C H
IT
E
C T
'S O
F E
N G
IN
E
E R
'S K
N O
W L E
D G
E
T
A
N S
A N
D S
P E
C
IF
IC
A
T
IO
N S C
O M
P L Y
W
IT
H T
P L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S A
N D
T
P L
IC
A B
L E
F
IR
E S
A F
E T
Y S
T A
N D
A R
D S
T E
R M
IN
E
D B
Y T
H E
L O
C A
L A
U T
H O
R
IT
Y
C O
R D
A N
C E
W
IT
H C
H A
P T
E R
S
A N
D
E F
L O
R
ID
A S
T A
T U
T E
S
W J
A rc hi te ct s
A R
(7
2-w .w ja rc
.c om
W an ne m ac he r
Je ns en A rc hi te ct s, In c.
Project number
N . W es ts ho re
B te
T am pa
, F lo rid a
T el : 8
.8
.4
T el
: 8
.8
.9 w w w
.V ol tA irI nc .c om C
O A
P ro je ct
.2
GENERAL NOTES
KEY NOTES
KEY PLAN
A ut od es k D oc s:
//2
P al m
H ar bo r
R ec re at io n
C en te r/
_P al m H ar bo r R ec C nt r_
M E
P _v
.r vt
9/
/2
:0 7:
A
M
ED-101
EXISTING BUILDING -
FLOOR PLAN -
ELECTRICAL
P A
L M
H A
R B
O R
P A
R K
S A
N D
R E
C R
E A
T
IO
N
P
IN
E
LL
A S
C O
U N
T Y
T H
S T
R E
E T
, P A
L M
H A
R B
O R
F L
PERMIT SET 9-15-25
0' 4' 12' 24' 42'-8"
SCALE: 3/32" = 1'-0"
N
3/32" = 1'-0"
EXISTING BUILDING - FLOOR PLAN - ELECTRICAL DEMOLITION
3/32" = 1'-0"
EXISTING BUILDING - RCP - LIGHTING - RENOVATION
3/32" = 1'-0"
EXISTING BUILDING - FLOOR PLAN - POWER - RENOVATION
3/32" = 1'-0"
EXISTING BUILDING - RCP - LIGHTING - DEMOLITION
J
J
J
P
P
P
MMMM
J
J
J
J
J
J
J
J
J
J
J
J J
J J
D H
J
A. ELECTRICAL CONTRACTOR SHALL REFER TO THE ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL DESIGN STANDARDS. THE
ELECTRICAL SPECIFICATIONS ARE A BINDING PART OF THE
CONSTRUCTION DOCUMENTS.
B. ALL WIRE SHALL BE COPPER STRANDED FOR #8 AND LARGER.
C. ALL COVER PLATES SHALL BE PER SPECIFICATIONS.
D. REFER TO ELECTRICAL MECHANICAL EQUIPMENT SCHEDULES
FOR ELECTRICAL INFORMATION PERTAINING TO MECHANICAL,
PLUMBING, FIRE PROTECTION AND / OR VERTICAL
TRANSPORTATION EQUIPMENT.
E. COORDINATE ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT
WITH MANUFACTURER PRIOR TO ROUGH-IN AND
INSTALLATION. ADJUST DEVICE TYPES, SIZES, LOCATIONS
AND BRANCH CIRCUITRY (AS REQUIRED).
F. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL FIRE
PROTECTION EQUIPMENT WITH THE DIVISION 21 CONTRACTOR
PRIOR TO ROUGH-IN AND INSTALLATION.
G. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL
PLUMBING EQUIPMENT WITH THE DIVISION 22 CONTRACTOR
PRIOR TO ROUGH-IN AND INSTALLATION.
H. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL
MECHANICAL EQUIPMENT WITH THE DIVISION 23 CONTRACTOR
PRIOR TO ROUGH-IN AND INSTALLATION.
I. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL
TECHNOLOGY EQUIPMENT WITH THE DIVISION 27
CONTRACTOR PRIOR TO ROUGH-IN AND INSTALLATION.
J. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL
DEVICES WITH ARCHITECTURAL ELEVATIONS, CASEWORK,
FIELD CONDITIONS AND OTHER TRADES, ADJUST (AS
REQUIRED).
K. COORDINATE LOCATIONS OF ALL SMOKE AND / OR FIRE /
SMOKE DAMPERS WITH…