Palm_Harbor_Rec_Center_-_Mechanical_-_Combined.pdf

PDF 4 MB Posted

Attached to
Palm Harbor Recreation Center Addition State and local contract opportunity
Solicitation number
26-0011-ITB-C
Issued by
Pinellas County, Clewiston City, Florida

About this file

These documents are mechanical HVAC design plans for the Palm Harbor Parks and Recreation Center located at 1500 16th Street, Palm Harbor, Florida, prepared by WJ Architects and VoltAir Inc. The project is a comprehensive mechanical system renovation involving multiple air handling units (AHU-1, AHU-2, AHU-3), an energy recovery ventilator (ERV-1), exhaust fans, and a chilled water system. The plans are a permit set dated September 15, 2025, covering detailed mechanical system designs for a two-level recreation center, including spaces such as a gymnasium, offices, dance studios, restrooms, and various program rooms.

The mechanical system design includes an air-cooled chiller (CH-1) with variable speed pumps, multiple air handling units with electronically commutated motors, and a complex control system utilizing BACnet communication protocols. The system is designed with energy efficiency in mind, incorporating demand control ventilation, CO2 sensors, and dynamic setpoint reset strategies. The project includes specific provisions for emergency shelter capabilities, with mechanical systems configured to meet ICC 500 standards for mechanical ventilation and natural ventilation requirements. The design emphasizes flexibility, with systems capable of operating in both normal and emergency modes, and includes comprehensive control sequences for optimizing energy performance and maintaining indoor environmental quality.

View the file

Other files for this state and local contract opportunity

Other files attached to Palm Harbor Recreation Center Addition, newest first.
File Type Posted
Site_visit_sign_in_sheet.pdf PDF
Palm_Harbor_Recreation_Center_Addition_(Addendum_#5_Revision).pdf PDF
Palm_Harbor_Recreation_Center_Addition_(Addendum_#2_Revision).pdf PDF
Pricing_Proposal26-0011(reference_only).pdf PDF
Pricing_Proposal26-0011(reference_only).pdf PDF
250070-AS_Palm_Harbor_Parks_Rec_Building_2_Asbestos_Survey_Report.pdf PDF
250070-AS_Palm_Harbor_Parks_Rec_Building_2_Asbestos_Survey_Report.pdf PDF
26-0011_-_Insurance_Requirements_-_Palm_Harbor_Recreation_Center_Addition_VE.docx DOCX document
PH_REC_CENTER_SPECIFICATIONS_-_VOL_2.pdf PDF
Palm_Harbor_Rec_Center_-_Mechanical_-_Rev_1.pdf PDF
Palm_Harbor_Rec_Center_-_Mechanical_-_Rev_1.pdf PDF
APPENDIX_7_-_SBE_COMPLIANCE_FORM.pdf PDF
APPENDIX_7_-_SBE_COMPLIANCE_FORM.pdf PDF
SBE_Compliance_Form.pdf PDF
QUALIFICATION_SUBMITTAL_FORM_Non_FDOT.pdf PDF
Agreement-26-0011.pdf PDF
Palm_Harbor_Rec_Center_-_Technology_-_Combined.pdf PDF
Palm_Harbor_Rec_Center_-_Technology_-_Combined.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_ARCHITECTURAL_ESS.pdf PDF
Palm_Harbor_Eng_Design_Rpt.pdf PDF
Palm_Harbor_Eng_Design_Rpt.pdf PDF
PH_REC_CENTER_SPECIFICATIONS_-_VOL_1.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_STRUCTURAL_S&S.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_STRUCTURAL_S&S.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_FOOD_SERVICE.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_LANDSCAPE.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_LANDSCAPE.pdf PDF
Palm_Harbor_Rec_Center_-_Electrical_-_Signed_and_Sealed.pdf PDF
Palm_Harbor_Rec_Center_-_Electrical_-_Signed_and_Sealed.pdf PDF
Palm_Harbor_Rec_Center_-_Plumbing_-_Combined.pdf PDF
Civil_Site_Permit_Set_S&S_09-15-25.pdf PDF
Palm_Harbor_Rec_Center_-_Fire_Protection_-_Signed_and_Sealed.pdf PDF
Palm_Harbor_Rec_Center_-_Fire_Protection_-_Signed_and_Sealed.pdf PDF
Airport_Security_Program.pdf PDF
Affdavit_of_Release_and_Guarantee.pdf PDF
E-Verify_Affidavit.pdf PDF
Florida_Trench_Safety_Form.pdf PDF
Performance_and_Payment_Bonds.pdf PDF
Affdavit_of_Release_and_Guarantee.pdf PDF
E-Verify_Affidavit.pdf PDF
Non-Competitive_Oversight_Committee_Justification_Form.docx DOCX document
OpenGov_Fillable-_Final.pdf PDF
Airport_Security_Program.pdf PDF
OpenGov_Fillable-_Final.pdf PDF
Sample_Application_for_Payment.pdf PDF
Bid_Submittal_Form-JOC.pdf PDF
Notice_of_Intent_to_Sole_Source_07-25-2023.pdf PDF
Sample_Application_for_Payment.pdf PDF
Notice_of_Intent_to_Sole_Source_07-25-2023.pdf PDF
Sample_Change_Order.pdf PDF
Show all 50

Palm Harbor Recreation Center Addition has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A (XXX)

GENERAL NOTES ABBREVIATIONS - HVAC

SYMBOL DESCRIPTION

AD

AFF

AFR

AHU

AP

BD

BOD

BOP

BHP

BTU

CD

CFM

CHWR

CHWS

CR

CT

CU

CWS

CWR

DDC

DN

(E)

EA

EAT

EDH

EF

ESP

ETR

EWT

FCU

FF

FLA

FOB

FOT

FPM

GPM

HHWR

HHWS

KW

LAT

LWT

MBH

MCA

MD

MOCP

NC

NIC

NO

NTS

OA

PRV

PSI

PSIG

PTAC

RA

RHC

RPM

RTU

SA

SP

TA

TEMP

TSP

UNO

V / PH

VAV

VFD

AIR DEVICE

ABOVE FINISHED FLOOR

ABOVE FINISHED ROOF

AIR HANDLING UNIT

ACCESS PANEL

BACKDRAFT DAMPER

BASIS OF DESIGN

BOTTOM OF PIPE

BRAKE HORSEPOWER

BRITISH THERMAL UNIT

CONDENSATE

CUBIC FEET PER MINUTE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE RETURN

COOLING TOWER

CONDENSING UNIT

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

DIRECT DIGITAL CONTROLS

DOWN

EXISTING

EXHAUST AIR

ENTERING AIR TEMPERATURE

ELECTRIC DUCT HEATER

EXHAUST FAN

EXTERNAL STATIC PRESSURE

EXISTING TO REMAIN

ENTERING WATER TEMPERATURE

FAN COIL UNIT

FINAL FILTERS

FULL LOAD AMPS

FLAT ON BOTTOM

FLAT ON TOP

FEET PER MINUTE

GALLONS PER MINUTE

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

KILOWATT

LEAVING AIR TEMPERATURE

LEAVING WATER TEMPERATURE

THOUSAND BTUs PER HOUR

MINIMUM CIRCUIT AMPACITY

MOTORIZED DAMPER

MAXIMUM OVER CURRENT PROTECTION

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

OUTSIDE AIR

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH

PSI GAUGE

PACKAGED TERMINAL AIR CONDITIONER

RETURN AIR

REHEAT COIL

REVOLUTIONS PER MINUTE

ROOFTOP UNIT

SUPPLY AIR

STATIC PRESSURE

TRANSFER AIR

TEMPERATURE

TOTAL STATIC PRESSURE

UNLESS NOTED OTHERWISE

VOLTS / PHASE

VARIABLE AIR VOLUME

VARIABLE FREQUENCY DRIVE

LEGEND - HVAC

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SYMBOL DESCRIPTIONSYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

SYMBOL DESCRIPTION

LIFE SAFETY

DUCTWORKCONTROLS

AIR DISTRIBUTION

GENERAL TAGS

DUCT ACCESSORIES COMMISSIONING NOTES CODE COMPLIANCE

SHEET INDEX

1. ENLIST A COMMISSIONING AGENT TO PROVIDE BUILDING

COMMISSIONING SERVICES IN ACCORDANCE WITH THE FLORIDA

BUILDING CODE 2023, 8th EDITION - ENERGY EFFICIENCY (FBC -

ENERGY).

2. PER FBC - ENERGY SECTION C408.2.5, ALL DOCUMENTS DESCRIBED IN

SECTION C408.2 SHALL BE PROVIDED TO THE BUILDING OWNER OR

OWNER'S AUTHORIZED AGENT AND PROVIDED TO THE CODE OFFICIAL

WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF

OCCUPANCY.

3. ENSURE CODE OFFICIAL HAS RECEIVED THE PRELIMINARY

COMMISSIONING REPORT AND A LETTER OF TRANSMITTAL FROM THE

BUILDING OWNER ACKNOWLEDGING THAT THE BUILDING OWNER HAS

RECEIVED THE PRELIMINARY COMMISSIONING REPORT AS REQUIRED IN

SECTION C408.2.4 PRIOR TO FINAL INSPECTION.

1. TO THE BEST OF OUR KNOWLEDGE, THESE PLANS AND SPECIFICATIONS

ARE COMPLETE AND COMPLY WITH THE FLORIDA BUILDING CODE 8th

EDITION (2023), BUILDING, MECHANICAL, ENERGY CONSERVATION,

FLORIDA FIRE PREVENTION CODE, LOCAL MUNICIPALITY AMENDMENTS

AND THE CODES REFERENCED WITHIN.

NEW DUCTWORK TO BE PROVIDED24x12

EXISTING DUCTWORK TO REMAIN24x12

EXISTING DUCTWORK TO BE REMOVED24x12

NEW PIPING TO BE PROVIDED

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

CONNECT TO EXISTING

DEMOLISH TO POINT INDICATED

VALVES

ELBOW, TURNED DOWN

ELBOW, TURNED UP

TEE, OUTLET DOWN

TEE, OUTLET UP

M

THERMOSTAT / TEMPERATURE SENSOR

HUMIDISTAT / HUMIDITY SENSOR

MOTORIZED CONTROL DAMPER

CO2 SENSOR

AIR DISTRIBUTION DEVICE: SUPPLY

(4-WAY BLOW UNLESS INDICATED BY ARROWS)

AIR DISTRIBUTION DEVICE: RETURN

AIR DISTRIBUTION TAG:

A: TYPE, (XXX): CFM

AIR TERMINAL DEVICE: SIDEWALL MOUNTED

DOOR GRILLE

SEE ARCHITECTURAL DRAWINGS

UNDERCUT DOOR:

SEE ARCHITECTURAL DRAWINGS

UC

AHU-X AIR HANDLING UNIT

EF-X EXHAUST FAN

RTU-X ROOF TOP UNIT

CU-X CONDENSING UNIT

VAV-X VARIABLE AIR VOLUME TERMINAL UNIT

CH-X CHILLER

EDH-X ELECTRIC DUCT HEATER

P-X PUMP

REVISION REFERENCE

DETAIL REFERENCE: TOP: DETAIL NO.

BOTTOM: DRAWING NO. DETAIL SHOWN ON

KEY NOTE

Mx

FIRE AND SMOKE DAMPER

WITH ACCESS DOOR PANEL

SMOKE DAMPER

WITH ACCESS DOOR PANEL

FIRE DAMPER

WITH ACCESS DOOR PANEL

EXISTING FIRE DAMPER TO REMAIN WITH

ACCESS DOOR PANEL, UNLESS OTHERWISE NOTED

EXISTING SMOKE DAMPER TO REMAIN WITH

ACCESS DOOR PANEL, UNLESS OTHERWISE NOTED

EXISTING FIRE AND SMOKE DAMPER TO REMAIN

WITH ACCESS PANEL, UNLESS OTHERWISE NOTED

DUCT SMOKE DETECTOR

NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN

PROVIDE EXTERNALLY INSULATED SHEET-METAL

DUCT ELBOW

POSITIVE PRESSURE (SUPPLY)

DUCT ELBOW

NEGATIVE PRESSURE (EXHAUST)

DUCT ELBOW

NEGATIVE PRESSURE (RETURN)

CHANGE OF ELEVATION

FLEXIBLE DUCT

TRANSITION, CONCENTRIC

TRANSITION, ECCENTRIC

TRANSITION, SQUARE TO ROUND

SQUARE THROAT ELBOW WITH TURNING VANES

RADIUS ELBOW

RECTANGULAR / ROUND BRANCH TAKE-OFF OR

ROUND / ROUND BRANCH TAKE-OFF

RECTANGULAR DUCTWORK

FLAT OVAL DUCTWORK

ROUND DUCTWORK

24x12

24"x12"

24"/12"

8"ø

DN UP

DN UP

DN UP

UP DN

8"ø10"x8"

SAD-1

M

BD

SOUND ATTENUATION DEVICE

MOTOR OPERATED CONTROL DAMPER (MOD)

AIR FLOW MEASURING STATION

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

FM

AIR DISTRIBUTION DEVICE: EXHAUST

1. SCOPE

WORK SHALL INCLUDE ALL MATERIALS, EQUIPMENT AND LABOR NECESSARY

FOR A COMPLETE AND PROPERLY FUNCTIONING MECHANICAL INSTALLATION

IN ACCORDANCE WITH ALL APPLICABLE CODES, AND CONTRACT DRAWINGS

AND SPECIFICATIONS. WORK SHALL INCLUDE ALL WORK NORMALLY SPECIFIED

IN DIVISION 23.

PAY FOR ALL REQUIRED LICENSES, FEES, INSPECTIONS AND PERMITS.

2. CODES

INSTALL ALL WORK IN ACCORDANCE WITH THE LATEST EDITION OF ALL

APPLICABLE REGULATIONS AND GOVERNING CODES, INCLUDING THE

REGULATIONS OF THE UTILITY COMPANIES SERVING THE PROJECT. WHERE A

CONFLICT IN CODE REQUIREMENTS OCCURS THE MORE STRINGENT

REQUIREMENT SHALL GOVERN.

3. STANDARDS

1. ALL EQUIPMENT AND DEVICES SHALL BEAR U.L. LABEL, THE LABEL OF

AN INDUSTRY RECOGNIZED APPROVED TESTING AGENCY FOR SAID

ITEM OF EQUIPMENT OR DEVICE.

2. ALL ELECTRICAL DEVICES MUST BE U.L. LISTED

3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST

EDITION OF THE SMACNA HVAC DUCT CONSTRUCTION STANDARD.

4. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK,

PIPING, EQUIPMENT, ETC. AND ALL FIRE RATED AND FIRE/SMOKE

RATED PARTITIONS TO ALLOW FOR INSPECTIONS OF RATED WALLS.

5. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10'-0" CLEAR FROM

ALL PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS.

LOWEST POINT OF EACH OUTSIDE AIR INTAKE ON ROOF SHALL BE A

MINIMUM OF 24" ABOVE ROOF.

6. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS

DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS

REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.

7. ALL PRODUCTS USED INDOORS SHALL BE OF THE LOW VOLATILE

ORGANIC COMPOUNDS (LOW-VOC) TYPE. INCLUDING BUT NOT

LIMITED TO PAINTS, SEALANTS, ADHESIVES AND MASTICS, ETC.

8. PRIOR TO START UP OF AIR HANDLING SYSTEMS AND EXHAUST

SYSTEMS, INSTALL AND MAINTAIN TEMPORARY FILTERS OVER ALL

RETURN, EXHAUST AND RELIEF GRILLES AND OPENINGS. FILTRATION

MEDIUM SHALL HAVE A RATING OF MERV 8 OR BETTER.

4. DRAWINGS

DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT

AND EXTENT OF WORK. EXACT LOCATIONS AND ARRANGEMENT OF

MATERIALS AND EQUIPMENT SHALL BE DETERMINED, WITH THE ACCEPTANCE

OF THE ARCHITECT/ENGINEER, AS CONSTRUCTION PROGRESSES TO

CONFORM IN THE BEST POSSIBLE MANNER WITH THE SURROUNDINGS AND

WITH THE ADJOINING WORK OF OTHER TRADES. WHERE LOCATIONS OF

EQUIPMENT, DEVICES OR FIXTURES ARE CONTROLLED BY ARCHITECTURAL

FEATURES, ESTABLISH SUCH LOCATIONS BY REFERRING TO DIMENSIONS ON

ARCHITECTURAL DRAWINGS AND NOT BY SCALING DRAWINGS. THE

FOLLOWING ITEMS ARE UNDERSTOOD TO BE INCLUDED AS PART OF THE

DRAWINGS UNLESS NOTED OTHERWISE:

1. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

2. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE

ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC. TO

ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL

TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES

UPSTREAM OF SPLIT.

3. PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN CHILLED WATER

AND HEATING HOT WATER PIPING.

4. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF

EQUIPMENT.

5. DISCREPANCIES

IN CASE OF DIFFERENCES BETWEEN DRAWINGS AND SPECIFICATIONS, OR

WHERE DRAWINGS AND SPECIFICATIONS ARE NOT CLEAR OR DEFINITE, THE

SUBJECT SHALL BE REFERRED TO ARCHITECT/ENGINEER FOR CLARIFICATION

AND INSTRUCTIONS.

6. ELECTRICAL PROVISIONS

WORK INCLUDES VARIOUS ELECTRICAL REQUIREMENTS (A) WHICH

INCORPORATE SPECIFIC ELECTRICAL FEATURES AND COMPONENTS WHICH

ARE REQUIRED TO BE PHYSICALLY INTEGRAL WITH MECHANICAL EQUIPMENT,

OR (B) WHICH REQUIRE NECESSARY ELECTRICAL INTERCONNECTING

COMPONENTS FOR THE MECHANICAL SYSTEMS.

DEFINITIONS:

A. "FURNISH" MEANS TO PROCURE AN ITEM AND TO DELIVER IT TO THE

PROJECT FOR INSTALLATION.

B. "INSTALL" MEANS TO DETERMINE (IN COORDINATION WITH OTHERS AS

NECESSARY) THE APPROPRIATE INTENDED LOCATION OF AN ITEM

AND TO SET AND CONNECT IT IN PLACE.

C. "PROVIDE" MEANS TO BOTH FURNISH AND INSTALL.

D. COORDINATE WITH OTHER ASSOCIATED TRADES FOR DUCT

MOUNTED FIRE ALARM DEVICES.

7. AUXILIARIES AND ACCESSORIES

INCLUDE ALL AUXILIARIES AND ACCESSORIES FOR COMPLETE AND PROPERLY

OPERATING SYSTEMS.

1. PROVIDE AIR TURNING VANES IN ALL 45 AND 90 DEGREE

RECTANGULAR DUCT ELBOWS.

2. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH DUCTS FROM

MAIN DUCT TO AIR DEVICES. POSITION DAMPERS IN ACCESSIBLE

LOCATION. IF NOT ACCESSIBLE PROVIDE A REMOTELY-OPERATED

VOLUME DAMPER AT ACCESSIBLE LOCATION.

3. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK

CONNECTING TO EACH FAN, AIR HANDLING UNIT, FAN COIL UNIT, AND

ANY EQUIPMENT WITH ROTATING OR POTENTIALLY VIBRATION-

CAUSING COMPONENTS.

4. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES,

REGISTERS, AND DIFFUSERS SHALL BE PAINTED FLAT BLACK.

5. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS

SHALL BE INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST

PLUMBING DRAIN.

6. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-

MOUNTED EQUIPMENT.

7. PROVIDE ALL REQUIRED OPENINGS TO ACCOMPLISH THE WORK.

PROVIDE SLEEVES OR OTHER APPROVED METHODS TO ALLOW

PASSAGE OF ITEMS INSTALLED. SEAL ALL OPENINGS AFTER

INSTALLATION OF PIPE, DUCT, ETC. TO MATCH RATING OF THE

PENETRATED SURFACE.

8. COORDINATION

1. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE

MECHANICAL WORK INTERFACES DIRECTLY OR INDIRECTLY WITH

WORK OF ANY TRADES. PROVIDE A COORDINATED SET OF SHOP

DRAWINGS THAT INCLUDE ALL OTHER TRADES WITHIN THE BUILDING

TO ENSURE THAT THE INSTALLATION OF THE MECHANICAL ITEMS

DOES NOT CONFLICT WITH ANY OTHER TRADE.

2. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH

MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL

EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT

FURNISHED.

3. DIMENSIONS AND CODE/MANUFACTURER REQUIRED CLEARANCES

SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO

PROCUREMENT OR FABRICATION. COORDINATE THE WORK WITH

OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS

IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED

DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT

NO ADDITIONAL COST.

4. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION

SHALL SUIT EQUIPMENT FURNISHED.

5. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED

WHERE REQUIRED FOR OPERATION, BALANCING, OR MAINTENANCE

OF ALL MECHANICAL EQUIPMENT.

6. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES,

REGISTERS, DIFFUSERS, LOUVERS, AND OTHER AIR DISTRIBUTION

DEVICES.

7. COORDINATE DIFFUSER, GRILLE, AND REGISTER LOCATIONS WITH

ARCHITECTURAL REFLECTED CEILING PLANS AND EQUIPMENT OF ALL

TRADES.

8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS,

AND HUMIDITY SENSORS AT 48" ABOVE FINISHED FLOOR UNLESS

NOTED OTHERWISE. COORDINATE LOCATIONS WITH DOOR SWINGS,

FURNITURE, AND OTHER EQUIPMENT. DO NOT LOCATE ON EXTERIOR

WALL NOWHERE DIRECT SUNLIGHT OR HVAC AIR WILL STRIKE

SENSOR.

9. ANY INTERRUPTION OF EXISTING MECHANICAL AND ELECTRICAL

SERVICES SHALL BE COORDINATED IN ADVANCE WITH THE OWNER'S

REPRESENTATIVE. THIS INCLUDES, BUT IS NOT LIMITED TO,

SERVICES PROVIDING CHILLED WATER, ELECTRICITY OR OTHER

CRITICAL SYSTEMS AS MAY BE PERTINENT TO THIS PROJECT.

SERVICE INTERRUPTION TIMES AND DURATION OF INTERRUPTION OF

SERVICES SHALL BE DECIDED BY THE OWNER. PROVIDE

APPROPRIATE PROVISIONS (E.G., ISOLATION SHUT-OFF VALVES,

DAMPERS, END CAPS AND SIMILAR ITEMS) AS NECESSARY TO

ACCOMMODATE THE REQUIRED SERVICE INTERRUPTIONS. IF

SHUTDOWNS CANNOT BE ACCOMMODATED, PROVIDE MEANS FOR

'WET' TAPPING OR 'HOT' TAPPING OF PIPING SYSTEMS.

10. UNLESS OTHERWISE SPECIFIED, ALL REFRIGERANT PIPING BETWEEN

INDOOR AND OUTDOOR UNITS SHALL BE INSTALLED USING HARD-

DRAWN COPPER WITH BRAZED JOINTS. THE USE OF SOFT-DRAWN

COPPER IS PROHIBITED.

CONTROL VALVE

DG

CO2

H

T

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

N D

O T

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V E

IN

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

S P

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

R

C

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

A

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

H

X

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

G

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

IT

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

L A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y I

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

F

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B lv d.

ui te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 3:

A

M

M-000

LEGEND - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

SHEET NUMBER SHEET NAME

M-000 LEGEND - HVAC

MD-101 EXISTING BUILDING - FLOOR PLAN - HVAC

M-201 LEVEL 1 - FLOOR PLAN - HVAC

M-202 LEVEL 2 - FLOOR PLAN - HVAC

M-203 ROOF PLAN - HVAC

M-401 ENLARGED FLOOR PLANS - HVAC

M-402 ENLARGED FLOOR PLANS - HVAC

M-601 AIR SYSTEM SCHEMATICS - HVAC

M-701 CONTROLS - HVAC

M-702 CONTROLS - HVAC

M-703 CONTROLS - HVAC

M-704 CONTROLS - HVAC

M-801 SCHEDULES - HVAC

M-802 SCHEDULES - HVAC

M-901 DETAILS - HVAC

M-902 DETAILS - HVAC

M-903 DETAILS - HVAC

M-904 DETAILS - HVAC

REV DESCRIPTION DATE

EXISTING CONDITIONS

THE EXISTING MECHANICAL SYSTEMS INDICATED ON THESE

DRAWINGS WAS COMPILED FROM ORIGINAL CONSTRUCTION

DRAWINGS, AS-BUILT DRAWINGS AND ENGINEERS’ FIELD

OBSERVATIONS. THE EXISTING SYSTEMS INDICATED REPRESENT A

BEST FAITH EFFORT BY THE ENGINEER TO DEMONSTRATE THE

CONDITIONS UNDER WHICH THE WORK IS TO BE EXECUTED.

VISIT THE SITE AND FAMILIARIZE YOURSELF WITH THE EXISTING

CONDITIONS AND SATISFY YOURSELF AS TO THE NATURE AND

SCOPE OF THE WORK AND DIFFICULTIES ASSOCIATED WITH THE

EXECUTION OF THE DRAWINGS. ALL DISCREPANCIES OR POTENTIAL

CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE

ARCHITECT/ENGINEER PRIOR TO BIDDING IN WRITING.

GENERAL HVAC DEMOLITION NOTES

A. ALL ITEMS TO BE DEMOLISHED SHALL BE REMOVED FROM THE

PREMISES AND DISPOSED OF IN A SAFE WAY AND MEETING ALL

LEGAL REQUIREMENTS. THE OWNER SHALL HAVE THE FIRST

RIGHT OF REFUSAL TO ALL ITEMS BEING DISPOSED.

B. DEMOLISH EXISTING MECHANICAL EQUIPMENT AS INDICATED.

COORDINATE THE DEMOLITION OF ALL APPURTENANCES

ASSOCIATED WITH EQUIPMENT INCLUDING BUT NOT LIMITED TO

CONTROLS, POWER CONDUITS, DUCTWORK, PIPING, HANGERS,

SUPPORTS AND ALL OTHER APPURTENANCES.

C. DEMOLISH ALL EXISTING HVAC DIFFUSERS, REGISTERS, GRILLES

AND AIR DISTRIBUTION DEVICES AND APPURTENANCES AS

INDICATED.

D. DEMOLISH EXISTING DUCTWORK, DAMPERS AND

APPURTENANCES, LOCATED WITHIN THE SPACE AS INDICATED

ON THE PLANS.

E. ALL MECHANICAL PENETRATIONS SHALL BE SEALED

WEATHERTIGHT.

F. REPORT ANY EXISTING ITEMS TO BE REUSED WHICH ARE IN

POOR SHAPE TO BE REUSED, NOT PROPERLY SUPPORTED, AND

NOT INSTALLED PROPERLY. EXISTING ITEMS TO BE REUSED ARE

EXPECTED TO BE SATISFACTORY DURING THE SUBSTANTIAL

INSPECTION.

G. INTERRUPTION OF EXISTING SERVICES: ANY INTERRUPTION OF

EXISTING MECHANICAL SERVICES SHALL BE COORDINATED IN

ADVANCE WITH THE OWNER'S REPRESENTATIVE. THIS

INCLUDES, BUT IS NOT LIMITED TO, SERVICES PROVIDING

CHILLED WATER, ELECTRICITY OR OTHER CRITICAL SYSTEMS AS

MAY BE PERTINENT TO THIS PARTICULAR PROJECT. SERVICE

INTERRUPTION TIMES AND DURATION OF INTERRUPTION OF

SERVICES SHALL BE DECIDED BY THE OWNER. PROVIDE

APPROPRIATE PROVISIONS (E.G., ISOLATION SHUT-OFF VALVES,

DAMPERS, END CAPS AND SIMILAR ITEMS) AS NECESSARY TO

ACCOMMODATE THE REQUIRED SERVICE INTERRUPTIONS. IF

SHUTDOWNS CANNOT BE ACCOMMODATED, PROVIDE MEANS

FOR CONNECTIONS INTO THE CURRENTLY OPERATIONAL

SYSTEMS. COORDINATE WITH OWNER THE REQUIREMENTS FOR

TEMPORARY COOLING WITHIN THE FACILITY IF THE SYSTEM WILL

REMAIN NON-OPERATIONAL.

H. PATCH TO MATCH EXISTING FLOORS, WALLS, CEILINGS, AND / OR

ROOF MATERIALS WHEN REMOVING ANY MECHANICAL SYSTEMS.

12 14 16 17

B A

9 15

EXISTING

ACTIVITY

ROOM

EXISTING

KITCHEN

EXISTING

STORAGE

EXISTING

STORAGE

EXISTING

STORAGE

EXISTING

CUSTODIAL

14"x8" 10"ø

12 14 16 17

B A

9 15

EXISTING OFFICE

EXISTING ACTIVITY ROOM

EXISTING EXERCISE

EXISTING MECH. ROOM

EXISTING STORAGE

NEW STORAGE

12"x10"

NEW CORRIDOR

FIRE RISER ROOM

021?

A (60)

A (40)

A (40)

A (150)

A (150)

A (160)

"x

8"

10"ø

6" x8

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 3:

A

M

MD-101

EXISTING BUILDING -

FLOOR PLAN - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N 3/32" = 1'-0"

EXISTING BUILDING - FLOOR PLAN - HVAC DEMOLITION

3/32" = 1'-0"

EXISTING BUILDING - FLOOR PLAN - HVAC

1 REMOVE EXISTING KITCHEN HOOD, ACCESSORIES, AND

ASSOCIATED WALL-MOUNTED EXHAUST FAN.

A. PROVIDE VOLUME DAMPERS AT ALL BRANCH TAKEOFFS

SERVING SINGLE DIFFUSERS, GRILLE OR REGISTER.

B. PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS.

C. MAINTAIN MINIMUM 6" CLEARANCE BETWEEN DUCTWORK AND

RATED WALLS.

D. COORDINATE DUCTWORK WITH STRUCTURE. PREPARE

COORDINATION DRAWINGS AS SPECIFIED. REFER TO

STRUCTURAL DRAWINGS FOR ALL PENETRATIONS THROUGH

STRUCTURAL WALLS (CMU, TILT, ETC.)

E. PROVIDE REMOTE DAMPER OPERATIONS FOR VOLUME

DAMPERS LOCATED ABOVE IN-ACCESSIBLE CEILINGS. DO NOT

PROVIDE ACCESS PANELS WITHIN HARD CEILINGS FOR

ACCESS TO MANUAL BALANCING DAMPERS.

F. PROVIDE ALL CODE REQUIRED AND MANUFACTURED

RECOMMENDED CLEARANCES FOR ALL EQUIPMENT.

G. UNLESS SHOWN ON FLOOR PLAN, REFER TO SCHEDULES FOR

DUCT SIZES FROM DUCT MAIN TO AIR TERMINAL UNIT FOR

BRANCH DUCTS TO AIR DEVICES.

H. COORDINATE ALL LOUVER LOCATIONS WITH ARCHITECTURAL

PLANS.

12 14 16 17

R

Q

K

J

F

P

N

M

L

G

E

D

C

B

A

H

9 1915 18

EXISTING ACTIVITY ROOM

KITCHEN

CUSTODIAL

MDF

MEN'S RESTROOM

WOMEN'S RESTROOM

OFFICES

MULTIPURPOSE ROOM B

MULTIPURPOSE ROOM A

STORAGE

MECH

ELEC

STORAGE

108A

GYM

LOBBY

RECEPTION

101A

CORRIDOR

CH-1

AHU-1

26"x18"

"x

1/

4" C

H W

S

1/

4" C

H W

R

3" CHWS

3" CHWR

AS-1

18"x12"

VAV-1-2

VAV-1-3

"x

"x

AHU-2

A (270)

A (305)

A (305)

B (540)

B (535)

B (100)

B (160) B (160)

B (160)

B (160) A (145)

A (140)

B (-)

B (-)

10"x10"

8"x10"

14"x10"

B (-)

B (-)

12"x8"

12"x8"

A (300)

A (275)

A (300) A (275)

A (560)

16"x14"

10"x8"

CV-1-5

B (510)

B (510)

VAV-1-1

B (515)

B (515)

A (240)

B (240)

"x

"x

A (290)

A (295)

A (260)

A (260)

20"x12"

B (-)

MECH

M-401

M-401

20"x14"

16"x6"

10"x10"

A (155)

A (120)

A (405)

A (345)

A (345)

A (405)

16"x14"

B (200)

B (200)

EF-2

10"x10"

CV-1-6

D (1500) 10"x10"

AC-1

CHWP-2

CHWP-1

F (5435)

A (100)

T

T

T

T

T

TVAV-1-11

T AHU-2

T AHU-3

CO2 CO2

CO2

CO2

18"x12"

32"x10"

24"x10"

ARTS AND CRAFTS

ELEC

T

D (135)

C (135)

"ø

V A

V -1

-4

B (560)

"x

4" CHWR

4" CHWS

A (270)

4" C

H W

R

4" C

H W

S

AHU-3

B (-)

B (-)

B (-)

ET-1

DH-1

EMERGENCY ELEC. AND

GENERATOR

108B

EF-3

16"x10"

16"x16"

D (775)

BAS

VFD

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 3:

A

M

M-201

LEVEL 1 - FLOOR PLAN

- HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

3/32" = 1'-0"

LEVEL 1 - FLOOR PLAN - HVAC

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER WITH FREE AREA OF AT LEAST 190 SQ. IN. ON

LOW WALL BELOW WINDOW. MAXIMUM HEIGHT OF LOW

LOUVERS TO BE 46" A.F.F. PER ICC 500. PROVIDE

MOTORIZED DAMPER ON THE BACK OF THE LOUVER

INTERLOCKED WITH WALL-MOUNTED SWITCH TO OPEN

& CLOSE. BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER WITH FREE AREA OF AT LEAST 568 SQ. IN. ON

WALL ABOVE THE CEILING LEVEL. PROVIDE MOTORIZED

DAMPER ON THE BACK OF THE LOUVER INTERLOCKED

WITH WALL-MOUNTED SWITCH TO OPEN & CLOSE.

BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER(S) WITH TOTAL FREE AREA OF AT LEAST 295

SQ. IN. ON LOW WALL BEHIND BLEACHERS. MAXIMUM

HEIGHT OF LOW LOUVERS TO BE 46" A.F.F. PER ICC 500.

PROVIDE MOTORIZED DAMPER ON THE BACK OF THE

LOUVER INTERLOCKED WITH WALL-MOUNTED SWITCH

TO OPEN & CLOSE. BASIS OF DESIGN: GREENHECK

AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED INTAKE

LOUVER WITH FREE AREA OF AT LEAST 6.0 SF. BASIS OF

DESIGN: GREENHECK AFL-610

ROUTE MAKEUP AIR DUCT FROM MUA-1 ON ROOF TO

KH-1 WITHIN DUCT CHASE.

ROUTE 16" ROUND GREASE EXHAUST DUCT FROM KH-1

UP TO KEF-1 ON ROOF WITHIN DUCT CHASE. PROVIDE

UL LISTED GREASE EXHAUST DUCT (BASIS OF DESIGN:

SCHEBLER FYREGUARD).

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

EXHAUST LOUVER WITH FREE AREA OF AT LEAST 0.7

SF. BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE 4" ROUND DRYER EXHAUST DUCTWORK AND

ROUTE TO EXTERIOR. PROVIDE WALL CAP FOR DRYER

EXHAUST.

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

EXHAUST LOUVER WITH FREE AREA OF AT LEAST 31.2

SF. BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED INTAKE

LOUVER WITH FREE AREA OF AT LEAST 41.7 SF. BASIS

OF DESIGN: GREENHECK AFL-610

PROVIDE GENERATOR EXHAUST FLUE. SEE DETAIL 1 ON

SHEET M-904 AND MANUFACTURER'S INSTALLATION

INSTRUCTIONS FOR FURTHER INFORMATION.

B. PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS.

C. MAINTAIN MINIMUM 6" CLEARANCE BETWEEN DUCTWORK AND

RATED WALLS.

D. COORDINATE DUCTWORK WITH STRUCTURE. PREPARE

COORDINATION DRAWINGS AS SPECIFIED. REFER TO

STRUCTURAL DRAWINGS FOR ALL PENETRATIONS THROUGH

STRUCTURAL WALLS (CMU, TILT, ETC.)

E. PROVIDE REMOTE DAMPER OPERATIONS FOR VOLUME

DAMPERS LOCATED ABOVE IN-ACCESSIBLE CEILINGS. DO NOT

PROVIDE ACCESS PANELS WITHIN HARD CEILINGS FOR

ACCESS TO MANUAL BALANCING DAMPERS.

F. PROVIDE ALL CODE REQUIRED AND MANUFACTURED

RECOMMENDED CLEARANCES FOR ALL EQUIPMENT.

G. UNLESS SHOWN ON FLOOR PLAN, REFER TO SCHEDULES FOR

DUCT SIZES FROM DUCT MAIN TO AIR TERMINAL UNIT FOR

BRANCH DUCTS TO AIR DEVICES.

H. COORDINATE ALL LOUVER LOCATIONS WITH ARCHITECTURAL

PLANS.

12 14 16 17

R

Q

K

J

F

P

N

M

L

G

E

D

C

B

A

H

9 1915 18

OFFICE

OFFICE

ADA STAFF RESTROOM

STAFF RESTROOM

MEN'S RESTROOM

WOMEN'S RESTROOM

DANCE STUDIO A

DANCE STUDIO B

SMALL PROGRAM ROOM

CONFERENCE ROOM

MECH

ELEC

STORAGE

ELEVATED TRACK

CORRIDOR

"ø

"x

ERV-1

"x

"x

A (240)

A (240) A (305)

A (300)

A (225)

B (225)

B (335)

B (335)

B (335)

B (340)

B (340)

B (335)

"x

A (285)

A (225)

A (285)

A (220)

CV-1-8

CV-1-9

16"x12"

16"x12" 14"x10"

C (145)

C (145)

16"ø

26"x10"

24"x16"

30"/14"

30"/16"

"x

22"/14"

18"/12"

18"/12" G (370)

G (375)

G (375)

G (435)

G (435)

G (375)

VAV-1-12

C (290)

D (290)

8"x8"

14"x10" 10"x10"

B (120)

B (120)

B (120)

A (140)

A (140)

VAV-1-13

12"x8"

B (210)

B (255)

A (295) A (240)

B (180)

A (210)

M-402

OFFICE

CORRIDOR 201B

CUSTODIAL

B (100)

B (80) B (80)

V A

V -1

-1

V A

V -1

-1

A (50) A (50)

18"x10"

"x

D (490)

12"x10"

D (490)

D (980)

18"x10"

VAV-1-11

A (385)

A (390)B (390)

B (385)

C (160)

V A

V -1

-1

A (290)

A (285)

B (575)

"x

VAV-1-7

V A

V -1

-1

FD

G (535) G (535) G (535) G (535)

G (535)G (535)G (535)G (535)

G (535) G (540) G (540) G (540)

G (540) G (540) G (540) G (540)

A (130)

E (160)

T

T

T

T

T

T

T

T T

ELEC.

C (145)

D (145)

30"/14"

10"x10"

18"x12"

"x

16"ø16"ø

16"ø16"ø

16"ø16"ø

16"ø16"ø

"ø

"ø

"ø

B (-)

B (-)

B (-)

14"x10"

EF-1

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 3:

A

M

M-202

LEVEL 2 - FLOOR PLAN

- HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

3/32" = 1'-0"

LEVEL 2 - FLOOR PLAN - HVAC

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER WITH FREE AREA OF AT LEAST 190 SQ. IN. ON

LOW WALL BELOW WINDOW. MAXIMUM HEIGHT OF LOW

LOUVERS TO BE 46" A.F.F. PER ICC 500. PROVIDE

MOTORIZED DAMPER ON THE BACK OF THE LOUVER

INTERLOCKED WITH WALL-MOUNTED SWITCH TO OPEN

& CLOSE. BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER WITH FREE AREA OF AT LEAST 568 SQ. IN. ON

WALL ABOVE THE CEILING LEVEL. PROVIDE MOTORIZED

DAMPER ON THE BACK OF THE LOUVER INTERLOCKED

WITH WALL-MOUNTED SWITCH TO OPEN & CLOSE.

BASIS OF DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

LOUVER WITH FREE AREA OF AT LEAST 890 SQ. IN. ON

HIGH WALL. PROVIDE MOTORIZED DAMPER ON THE

BACK OF THE LOUVER INTERLOCKED WITH WALL-

MOUNTED SWITCH TO OPEN & CLOSE. BASIS OF

DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED RELIEF

LOUVER WITH FREE AREA OF AT LEAST 3.3 SF. PROVIDE

BAROMETRIC RELIEF DAMPER IN DUCTWORK ON THE

BACK OF THE LOUVER. BASIS OF DESIGN: GREENHECK

AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED INTAKE

LOUVER WITH FREE AREA OF AT LEAST 8.6 SF. BASIS OF

DESIGN: GREENHECK AFL-610

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

EXHAUST LOUVER WITH FREE AREA OF AT LEAST 5.5

SF. BASIS OF DESIGN: GREENHECK AFL-610

ROUTE 32"x10" MAKEUP AIR DUCT FROM MUA-1 ON

ROOF TO KH-1 WITHIN DUCT CHASE.

ROUTE 16" ROUND GREASE EXHAUST DUCT FROM KH-1

UP TO KEF-1 ON ROOF WITHIN DUCT CHASE. PROVIDE

UL LISTED GREASE EXHAUST DUCT (BASIS OF DESIGN:

SCHEBLER FYREGUARD).

PROVIDE AMCA 550 LISTED AND ICC 500 TESTED

EXHAUST LOUVER WITH FREE AREA OF AT LEAST 0.74

SF. BASIS OF DESIGN: GREENHECK AFL-610

B. PROVIDE TURNING VANES IN ALL RECTANGULAR ELBOWS.

C. MAINTAIN MINIMUM 6" CLEARANCE BETWEEN DUCTWORK AND

RATED WALLS.

D. COORDINATE DUCTWORK WITH STRUCTURE. PREPARE

COORDINATION DRAWINGS AS SPECIFIED. REFER TO

STRUCTURAL DRAWINGS FOR ALL PENETRATIONS THROUGH

STRUCTURAL WALLS (CMU, TILT, ETC.)

E. PROVIDE REMOTE DAMPER OPERATIONS FOR VOLUME

DAMPERS LOCATED ABOVE IN-ACCESSIBLE CEILINGS. DO NOT

PROVIDE ACCESS PANELS WITHIN HARD CEILINGS FOR

ACCESS TO MANUAL BALANCING DAMPERS.

F. PROVIDE ALL CODE REQUIRED AND MANUFACTURED

RECOMMENDED CLEARANCES FOR ALL EQUIPMENT.

G. UNLESS SHOWN ON FLOOR PLAN, REFER TO SCHEDULES FOR

DUCT SIZES FROM DUCT MAIN TO AIR TERMINAL UNIT FOR

BRANCH DUCTS TO AIR DEVICES.

H. COORDINATE ALL LOUVER LOCATIONS WITH ARCHITECTURAL

PLANS.

12 14 16 17

R

Q

K

J

F

P

N

M

L

G

E

D

C

B

A

H

9 1915 18

KEF-1

CU-1

MUA-1

2 3

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 3:

A

M

M-203

ROOF PLAN - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

3/32" = 1'-0"

ROOF PLAN - HVAC

LOCATE KEF-1 AT LEAST 10'-0" FROM THE ROOF EDGE

AND MUA-1'S OUTSIDE AIR INTAKE.

PROVIDE ROOFTOP CONDENSING UNIT STAND WITH

MIAMI-DADE NOA. BASIS OF DESIGN: MIAMI TECH

MODEL AS14. ROUTE REFRIGERANT PIPING FROM CU-1

DOWN TO LEVEL 1 VIA MECHANICAL DUCT CHASE.

PROVIDE ROOFTOP CONDENSING UNIT STANDS WITH

MIAMI-DADE NOA FOR THE WALK-IN FREEZER AND

WALK-IN COOLER CONDENSING UNITS. SEE FOOD

SERVICE DRAWINGS FOR INFORMATION ON THESE

UNITS. BASIS OF DESIGN: MIAMI TECH MODEL AS14.

ROUTE REFRIGERANT PIPING FROM THESE

CONDENSING UNITS DOWN TO LEVEL 1 VIA

MECHANICAL DUCT CHASE.

A. PROPERLY COORDINATE DUCTWORK AND EQUIPMENT

LAYOUT TO PROVIDE ACCESS TO ALL NEC AND

MAINTENANCE CLEARANCES. ENSURE PROPER PATH OF

TRAVEL TO ALL EQUIPMENT WITHIN ROOM FOR

MAINTENANCE AND FUTURE REPLACEMENT. PROVIDE

COORDINATED SHOP DRAWINGS OF EACH MECHANICAL

ROOM SHOWING ALL TRADES TO BE INSTALLED WITHIN

ROOM.

B. PROVIDE DDC PANEL ON WALL ADJACENT TO VFD's.

C. PROVIDE PROPER ACCESS TO ALL FIRE DAMPER, FIRE /

SMOKE DAMPER, SMOKE DETECTOR, AIRFLOW MEASURING

STATION, ETC. ACCESS PANELS.

2 3

P

N

RETURN AIR FROM

FIRST FLOOR

SUPPLY AIR TO

FIRST FLOOR

EXHAUST AIR FROM

FIRST FLOOR

SUPPLY AIR UP THROUGH

SECOND FLOOR TO

SERVE SECOND FLOOR

EXHAUST AIR UP THROUGH

SECOND FLOOR

PRE-TREATED OA

FROM SECOND FLOOR

28"x30"

26"x16"

"x

"x

VAV-1-1

3" CHWR

3" CHWS

RETURN AIR FROM

SECOND FLOOR

AHU-1

BAS

DUCT SMOKE DETECTOR

HOLD DUCT AS HIGH ABOVE GRADE

AS POSSIBLE TO MAINTAIN ACCESS

TO BACKSIDE OF UNIT

34"x20"

12 14

R

Q

SUPPLY DUCT UP

THROUGH DECK

RETURN DUCT ABOVE

CEILING IN STORAGE ROOM

36"x24"

AHU-2

D (240)

"x

12"x20"

C (150)

C (1175)

D (1075) 16"x12"

3" CHWS

3" CHWR

C (240)

BAS

DUCT SMOKE

DETECTOR

F M

CONTROL DAMPER

24"x20"

DH-1

RETURN DUCT THROUGH

WALL TO STORAGE ROOM

SUPPLY DUCT UP

THROUGH DECK

OUTSIDE AIR DUCT TO CONNECT

TO ARCHITECTURAL LOUVER.

(MIN 5.0 SQFT. FREE AREA)

36"x24"

24"x20"

AHU-2

3" CHWR

3" CHWS

16"x12"

C (1175)

D (1075)

12"x20"

C (240)

16"x12"

D (240)

BAS

DUCT SMOKE

DETECTOR IN

SUPPLY AIR DUCT

DH-1

"x

24"x20"

AHU-2

3" CHWS

3" CHWR

SUPPLY DUCT UP

THROUGH DECK

RETURN DUCT THROUGH

WALL TO STORAGE ROOM

OUTSIDE AIR DUCT TO CONNECT TO

ARCHITECTURAL LOUVER.

(MIN 5.0 SQFT. FREE AREA)

36"x26"

C (1175)

C (150)

12"x20"

D (240)

16"x12"

36"x24"

C (240)

D (1075)

8"x8"

DH-1

RETURN AIR FROM

FIRST FLOOR

RETURN AIR FROM

SECOND FLOOR

PRE-TREATED OA

FROM SECOND FLOOR

SUPPLY AIR TO

FIRST FLOOR

AHU-1EXHAUST AIR TO

FIRST FLOOR

EXHAUST AIR UP

THROUGH SECOND FLOOR

VAV-1-1

SUPPLY AIR UP THROUGH SECOND

FLOOR TO SERVE SECOND FLOOR

3" CHWS

3" CHWR

28"x30"

"x

DUCT SMOKE

DETECTOR IN

SUPPLY AIR DUCT

"x

"26"x16"

"x

BAS

3" CHWR

3" CHWS

AHU-1

VAV-1-1

"x

"x

34"x20"

"x

26"x16"

26"x18"

28"x30"

EXHAUST AIR UP

THROUGH FLOOR

SUPPLY AIR UP THROUGH FLOOR

TO SERVE SECOND FLOOR

EXHAUST AIR FROM

FIRST FLOOR

RETURN AIR FROM

SECOND FLOOR

RETURN AIR FROM

FIRST FLOOR

SUPPLY AIR TO

FIRST FLOOR

PRE-TREATED OA

FROM SECOND FLOOR

20"x16"

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 4:

A

M

M-401

ENLARGED FLOOR

PLANS - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 2' 4' 8' 16'

SCALE: 1/4" = 1'-0"

N

1/4" = 1'-0"

MECH 107 ENLARGED PLAN - MECHANICAL

1/4" = 1'-0"

MECH 110 ENLARGED PLAN - MECHANICAL

MECH 110 ISOMETRIC - MECHANICAL - SE

MECH 110 ISOMETRIC - MECHANICAL - NW

MECH 107 ISOMETRIC - MECHANICAL - SE

MECH 107 ISOMETRIC - MECHANICAL - NW

A. PROPERLY COORDINATE DUCTWORK AND EQUIPMENT

LAYOUT TO PROVIDE ACCESS TO ALL NEC AND

MAINTENANCE CLEARANCES. ENSURE PROPER PATH OF

TRAVEL TO ALL EQUIPMENT WITHIN ROOM FOR

MAINTENANCE AND FUTURE REPLACEMENT. PROVIDE

COORDINATED SHOP DRAWINGS OF EACH MECHANICAL

ROOM SHOWING ALL TRADES TO BE INSTALLED WITHIN

ROOM.

B. PROVIDE DDC PANEL ON WALL ADJACENT TO VFD's.

C. PROVIDE PROPER ACCESS TO ALL FIRE DAMPER, FIRE /

SMOKE DAMPER, SMOKE DETECTOR, AIRFLOW MEASURING

STATION, ETC. ACCESS PANELS.

2 3

P

N

MECH

ERV-1

VAV-1-7

"x

"x

"x

34"x20"

18"x18"

30"x28"

EXHAUST AIR FROM

BELOW THROUGH SLAB

SUPPLY AIR FROM

BELOW THROUGH SLAB

PRE-TREATED

OA TO BELOW

THROUGH SLAB

SUPPLY AIR TO

SECOND FLOOR

EXHAUST AIR FROM

SECOND FLOOR

RETURN AIR FROM

SECOND FLOOR

C (340)

12"x10"

BAS

DUCT SMOKE

DETECTOR

28"x26"

EXHAUST AIR FROM

SECOND FLOOR

RETURN AIR FROM

SECOND FLOOR

RETURN AIR TO BELOW

THROUGH SLAB

PRE-TREATED OA TO

BELOW THROUGH SLAB

SUPPLY AIR FROM

BELOW THROUGH SLAB

EXHAUST AIR FROM

BELOW THROUGH SLAB

"x

20"x16" 18"x18"

"x

"x

"x

"x

C (340)

BAS

FM

34"x20"

38"x16"

D (340)

EXHAUST AIR FROM

SECOND FLOOR

RETURN AIR FROM

SECOND FLOOR

SUPPLY AIR TO

SECOND FLOOR

"x

EXHAUST AIR FROM

BELOW THROUGH SLAB

ERV-1

38"x16"

20"x16"

RETURN AIR TO BELOW

THROUGH SLAB

"x

"x

"x

C (340)

CONTROL DAMPER

CONTROL DAMPER

FM

28"x26"

34"x20"

18"x18" 18"x18"

32"x18"

12"x10"

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 4:

A

M

M-402

ENLARGED FLOOR

PLANS - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NOTES

0' 2' 4' 8' 16'

SCALE: 1/4" = 1'-0"

N

1/4" = 1'-0"

MECH 207 ENLARGED PLAN - MECHANICAL

MECH 207 ISOMETRIC - MECHANICAL - SE

MECH 207 ISOMETRIC - MECHANICAL - NW

LINE TYPE LEGEND

BUILDING

EXHAUST AIR

OUTDOOR AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

AHU-2

10,250 CFM

6,750 CFM

3,500 CFM

BUILDING AIR BALANCE

EQUIPMENT TAG EA CFM OA CFM (VIA ERV) ZONE PRESSURE TOTAL

AHU-2 (GYMNASIUM) -- 3,500

+2,120 CFMAHU-1 (REC CENTER) 3,745 (VIA ERV) 5,865

AHU-3 (KITCHEN) -- --

+3,500 CFM

1. ALL VALUES ARE CALCULATED UNDER FULL FLOW CONDITIONS FOR THE KITCHEN HOOD EQUIPMENT AND WITH RELIEF

BEING FULLY UTILIZED. ACTUAL CONDITIONS MAY VARY BASED ON KITCHEN EQUIPMENT OPERATING CONDITIONS.

+0 CFM

BUILDING TOTAL 7,085 11,565 +4,480 CFM

EF-1 (AHU-1) 740 -- -740 CFM

GYMNASIUM

2,850 CFM (RELIEF VIA BAROMETRIC RELIEF IN GYM)

AHU-1

13,910 CFM

8,045 CFM

5,865 CFM

ERV-1

3,745 CFM

3,745 CFM

5,865 CFM

RECREATION CENTER

980 CFM

AHU-3

1,500 CFM

1,500 CFM

400 CFM

KITCHEN

MUA-1 KEF-1

2,200 CFM 2,600 CFM

DOAS-1 (KITCHEN) -- 2,200 +2,200 CFM

KEF-1 (KITCHEN) 2,600 -- -2,600 CFM

3,500 CFM

650 CFM (RELIEF THROUGH EXTERIOR DOORS)

740 CFM EF-1

400 CFM

EF-2 (ONLY RUNS WHILE KEF-1 IS OFF)

ICC 500 MECHANICAL VENTILATION CALCULATION

COMMUNITY SHELTER AREA OCCUPANT CAPACITY CFM/OCCUPANT OUTSIDE AIR REQUIRED

REC CENTER LEVEL 2 63 5.0

310 CFMREC CENTER LEVEL 1 62 5.0

GYMNASIUM 393 5.0

1. MECHANICAL VENTILATION RATE REQUIREMENTS ARE BASED ON THE ICC 500 2020, SECTION 7.03.6 VENTILATION.

315 CFM

1,965 CFM

2,205 CFM

3,660 CFM

3,500 CFM

OUTSIDE AIR PROVIDED VIA

MECHANICAL SYSTEM

ICC 500 NATURAL VENTILATION CALCULATION

COMMUNITY SHELTER AREA OCCUPANT CAPACITY

VENTING AREA PER

OCCUPANT

TOTAL MINIMUM VENTING

AREA REQUIRED

REC CENTER LEVEL 2 63 12.0 SQUARE INCHES

744 SQUARE INCHESREC CENTER LEVEL 1 62 12.0 SQUARE INCHES

GYMNASIUM 393 12.0 SQUARE INCHES

1. NATURAL VENTILATION AREA REQUIREMENTS ARE BASED ON THE ICC 500 2020, SECTION 7.03.6 VENTILATION.

756 SQUARE INCHES

4,716 SQUARE INCHES

201.6 SQUARE INCHES

201.6 SQUARE INCHES

1,267 SQUARE INCHES

VENTING AREA PROVIDED

WITHIN 46" A.F.F.

590.4 SQUARE INCHES

590.4 SQUARE INCHES

5,011 SQUARE INCHES

VENTING AREA PROVIDED

AT LEAST 72" A.F.F.

792 SQUARE INCHES

792 SQUARE INCHES

6,278 SQUARE INCHES

TOTAL VENTING AREA

PROVIDED

2. VENTING AREAS PROVIDED ARE BASED ON THE FREE AREA OF THE BASIS OF DESIGN LOUVER: GREENHECK AFL-601. ACTUAL LOUVER DIMENSIONS SHOWN ON ARCHITECTURAL PLANS.

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 4:

A

M

M-601

AIR SYSTEM

SCHEMATICS - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

AI

1. APPLICATION SPECIFIC CONTROLLERS (ASC) SHALL BE PROVIDED WITH A GATEWAY

INTERFACE CARD CAPABLE OF INTERFACING WITH THE BUILDING LEVEL CONTROLS. THE

BUILDING LEVEL CONTROL SYSTEM SHALL BE CAPABLE OF MONITORING INPUTS AND OUTPUTS

OF THE ASC CONTROLLER AND REMOTE SETPOINT ADJUSTMENT.

2. 110VAC TO GLOBAL CONTROLLERS SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR.

CONTROL CONTRACTOR TO PROVIDE SURGE SUPPRESSORS TO INCOMING LINE VOLTAGE.

3. THE OWNER AND THE CONTRACTOR MUST COORDINATE TO OBTAIN ALL THE PROPER

INTERNET PROTOCOLS NECESSARY FOR DATA OUTLETS TO BE LIVE (DNX RECORDS, MAC

ADDRESS, IP ADDRESS ETC.).

GENERAL NOTES:

GLOBAL CONTROLLER

PROVIDE TWO CAT 5

JACKS IN MECH RM

(TYP OF 2)

NEW ETHERNET.

1CONTROLS LEGEND

2DDC RISER

4EXHAUST FAN CONTROL (ECM CONSTANT SPEED)

5MINI-SPLIT CONTROL

3VARIABLE AIR VOLUME TERMINAL UNIT CONTROL

ELECTRIC/ELECTRONIC WIRE

HUMIDITY SENSORHS

TEMPERATURE SENSOR

CONTROL VALVE

DIGITAL INPUT

DIGITAL OUTPUT

ANALOG INPUT

ANALOG OUTPUT

TS

CV

DI

DO

AI

AO

VELOCITY PRESSURE SENSORVP

ELECTRIC PNUEMATICEP

SMOKE DETECTOR

WATER FLOW TRANSMITTERFT-XX

DIFFERENTIAL PRESSURE SENSORDPT-XX

SMOKE DAMPER ACTUATOR

SDM-XX

DM-XX

DPS-XX

FM-XX

TS-XX

HS-XX

FZ-XX

SP-XX

CONTROL DAMPER ACTUATOR

AIR FLOW MEASURING STATION

SPACE TEMPERATURE SENSOR

HUMIDITY SENSOR

FREEZESTAT

STATIC PRESSURE SENSOR

DIFFERENTIAL PRESSURE SWITCH

TS-XX

DUCT TEMPERATURE SENSOR

IMMERSION TEMPERATURE SENSORTS-XX

(AVERAGING)

CONTROL VALVE

DDC CONTROL PANEL

INPUT/OUTPUT POINT TO

V-1

AI

AO

CT CURRENT RELAY (ADJ. TRIP FOR BELT

DRIVEN APPLICATIONS)

DDC CONTROLLERS (TYP)

APPLICATION SPECIFIC

ERV-X

ASC-1

AHU-X

24 VDC.

ASC-2

24 VDC.

COMMUNICATION

TRUNK LINE

110 VAC.

INDOOR WALL MOUNT UNIT

24V LEAD TO ROOM.

T'STAT PROVIDED BY

UNIT MFGR.

SA

RA

OUTDOOR CONDENSING UNIT

TS-XX

SPACE TEMPERATURE

SENSOR WITH LCD

INTERFACE.

SEQUENCE OF OPERATION

INDOOR UNIT AND CORRESPONDING CONDENSING UNIT SHALL MODULATE AIRFLOW

AND COOLING TO MAINTAIN SPACE TEMPERATURE OF 75 DEG F (ADJUSTABLE).

BAS

BACNET

MSTP

TS-2

FACTORY MOUNTED ON BOX.

WITH PILOT TUBES

FROM AHU

SUPPLY AIR

TERMINAL UNIT CONTROLLER

STAND-ALONE DDC

FACTORY MOUNTED

BOX DAMPER

ACTUATOR ELECTRIC HEAT

AI

TS-1

FURNISH

AS SHOWN ON

PLAN.

POINTS LIST

TAG POINT TYPE DESCRIPTION

SETPOINT (ALL

SETPOINTS ADJ.)

- AI AIR TERMINAL AIRFLOW -

- AI AIR TERMINAL DAMPER POSITION -

- AO AIR TERMINAL DAMPER CONTROL -

TS-1 AI REHEAT COIL SUPPLY TEMP AS SCHEDULED

TS-2 AI SPACE TEMPERATURE 75°F / 70°F

- AI SPACE TEMPERATURE SETPOINT

HS-1 AI SPACE HUMIDITY SENSOR -

EDH-1 AO SCR REHEAT COIL CONTROL -

EDH-1

HS-2

DO

RELAY

INTERLOCK

R-X

START EXHAUST FAN

WIRE TO

EXHAUST

AIR

EXHAUST FAN

N.C.

DI

AO CONTROL

ECM

FM

POINTS LIST

TAG POINT TYPE DESCRIPTION

- DO FAN START

- DI FAN STATUS

AO FAN SPEED CONTROL

FM-1 RELIEF AIR FLOW AS SCHEDULED

STATUS

CO₂ CARBON DIOXIDE SENSOR

SPACE TEMPERATURE SENSOR

W/JACK FOR

PORTABLE COMPUTER TIE-IN

AND WITH LCD DISPLAY. HS+TS

IN

SAME BOX COORDINATE COLOR

AND HEIGHT WITH ELECTRICAL

AND ARCHITECT.

AIR TERMINAL UNIT CONTROL:

THE BAS SHALL MODULATE THE AIR TERMINAL UNIT CFM FROM ITS MINIMUM TO MAXIMUM SCHEDULED VALUE

TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.

THE SCR REHEAT CONTROL SHALL MODULATE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT IF THE SETPOINT IS NOT MET BY THE AIR TERMINAL UNIT'S MINIMUM SCHEDULED CFM VALUE. SUPPLY AIR

TEMPERATURE SHALL BE LIMITED TO LESS THAN 15 DEG. F ABOVE SPACE TEMPERATURE IN THE

REHEATING/HEATING MODE.

SPACE TEMPERATURE SETPOINTS SHALL BE RESET TO AN ADJUSTABLE NIGHT SETBACK SETPOINT WHEN

INDEXED BY BAS OR BY OCCUPANCY SENSOR.

HIGH AND LOW TEMPERATURE AND CFM ALARMS SHALL BE INDICATED AT THE BAS FRONT END.

EXHAUST FAN CONTROL:

EF-1 SHALL BE INTERLOCKED WITH ITS RESPECTIVE AHU'S

OUTSIDE AIR DAMPER AND AHU FAN STATUS. STATUS ALARMS

SHALL BE INDICATED AT THE BAS FRONT

END.

EF-2 SHALL BE ENERGIZED WHEN ASSOCIATED AHU FAN AND

DAMPER STATUS IS ENABLED AND KITCHEN HOOD FAN IS

DISABLED.

FAN SPEED SHALL MODULATE AS REQUIRED TO MAINTAIN

EXHAUST AIRFLOW (AS SENSED BY RELIEF AIR AIRFLOW

MONITORING STATION) EQUAL TO SCHEDULED EXHAUST FLOW.

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:5 4:

A

M

M-701

CONTROLS - HVAC

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

ENERGY CORE

CONSTANT VOLUME ENERGY RECOVERY VENTILATOR CONTROL - TYPICAL OF ERV-1 2

VARIABLE VOLUME CHILLED WATER AIR HANDLING UNIT WITH ECM CONTROL - TYPICAL OF AHU-1 1

OUTSIDE AIR

EXHAUST AIR

RELIEF AIR

POINTS LIST

TAG POINT TYPE DESCRIPTION SETPOINT (ALL SETPOINTS ADJ.)

MD-1 AO OUTSIDE AIR DAMPER CONTROL -

MD-1 AI OUTSIDE AIR DAMPER FEEDBACK -

DPS-1 AI FILTER STATUS

PER FILTER MANUF.'S

RECOMMENDATIONS

TS-1 AI OUTSIDE AIR TEMPERATURE SENSOR -

HS-1 AI OUTSIDE AIR HUMIDITY SENSOR -

HS-2 AI LVG CORE OA HUMIDITY SENSOR -

TS-2 AI LVG CORE OA TEMP SENSOR -

- DI *SA ECM FAN STATUS -

- AO SA ECM FAN SYSTEM CONTROL -

FM-1 AI SUPPLY AIR FLOW AS SCHEDULED

HS-3 AI RELIEF AIR HUMIDITY SENSOR -

TS-3 AI RELIEF AIR TEMPERATURE SENSOR -

FM-2 AI RELIEF AIR FLOW AS SCHEDULED

DPS-2 AI FILTER STATUS

PER FILTER MANUF.'S

RECOMMENDATIONS

HS-4 AI LVG CORE EA HUMIDITY SENSOR -

TS-4 AI LVG CORE EA TEMP SENSOR -

- DI *EA ECM FAN STATUS -

- AO EA ECM FAN SYSTEM CONTROL -

MD-2 AO EXHAUST AIR DAMPER CONTROL -

MD-2 AI EXHAUST AIR DAMPER FEEDBACK -

HSP-1

HS-3

AI

TS-3

AI

AI

HS-1

AI

AO

N.C.

MD-1

AI

FM-1

AI

TS-1

AI

TS-2

AI

HS-2

AI

DI

AO

CONTROL

ECM

DI

AO

CONTROL

ECM

TS-4

AI

HS-4

AI

FM-2

AI

AO

N.C.

MD-2

DPS-1DPS-2

AI

AI

*ONE PER FAN, REFER TO AHU SCHEDULES FOR FAN QUANTITY.

ENERGY RECOVERY VENTILATOR CONTROL:

ERV SYSTEM CONSISTS OF ECM SUPPLY AND EXHAUST FAN(S) AND TOTAL ENTHALPY ENERGY CORE.

OCCUPIED MODE:

ERV WILL ENTER THE OCCUPIED MODE WHEN SCHEDULED BY THE BUILDING AUTOMATION SYSTEM (BAS) AND SHALL BE

INTERLOCKED TO THE AHU IT IS SERVING. IN THIS OCCUPIED MODE THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL

MODULATE OPEN AND SUPPLY AND EXHAUST FANS SHALL ENABLE.

THE SUPPLY FAN SHALL MODULATE TO MAINTAIN THE OUTSIDE AIR CFM SETPOINT (ADJ.) AS SENSED BY THE SUPPLY

AIRFLOW MONITORING STATION. THE EXHAUST FAN SHALL MODULATE TO MAINTAIN THE RELIEF AIR CFM SETPOINT (ADJ.)

AS SENSED BY THE RELIEF AIRFLOW MONITORING STATION.

UNOCCUPIED MODE

THE ERV SHALL BE DE-ENERGIZED AND OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL CLOSE.

GENERAL NOTES:

HIGH AND LOW TEMPERATURE, AIRFLOW (IF OA OR EA DEVIATES BY 10% OF DESIGN OR CALCULATED VALUE), FILTER

STATUS ALARMS, DAMPER POSITION ALARMS, AND FAN STATUS ALARMS SHALL BE INDICATED AT THE BAS FRONT END.

SUPPLY

AIR

DPS-1

AI

FILTER(S)

CHWR

CHWS

AO

N.O.

C

C

RETURN AIR

V-1

AO

HS-1

AI

NO

TS-3

AI

AI

SUPPLY

AIR

STATIC PRESSURE

SENSOR LOC. 2/3

DOWNSTREAM

LONGEST RUN

OUTSIDE AIR FROM ERV-1

POINTS LIST

TAG POINT TYPE DESCRIPTION SETPOINT (ALL SETPOINTS ADJ.)

HS-1 AI RETURN AIR HUMIDITY -

TS-1 AI RETURN AIR TEMP -

MD-1 AO RETURN AIR DAMPER CONTROL -

TS-2 AI MIXED AIR TEMP -

DPS-1 AI FILTER STATUS

PER FILTER MANUF.'S

RECOMMENDATIONS

V-1 AO CHW CONTROL VALVE CONTROL -

V-1 AI CHW CONTROL VALVE FEEDBACK -

TS-3 AI COOLING COIL LEAVING AIR TEMP AS SCHEDULED

- DI *AHU ECM FAN STATUS -

- AO AHU ECM FAN SYSTEM CONTROL -

TS-4 AI SUPPLY AIR TEMP -

SP-1 AI SUPPLY AIR STATIC PRESSURE SET BY TAB

*ONE PER FAN, REFER TO AHU SCHEDULES FOR FAN QUANTITY.

MD-1

TS-1

AI

TS-2

AI

AI

TS-4

AI

HSP-1

SP-1

VAV AHU CONTROL:

AHU SYSTEM CONSISTS OF ECM SUPPLY FAN(S) AND COOLING COIL(S) WITH

MODULATING CONTROL VALVE(S).

OCCUPIED MODE:

AHU WILL ENTER THE OCCUPIED MODE WHEN SCHEDULED BY THE BUILDING

AUTOMATION SYSTEM (BAS). IN THE OCCUPIED MODE, THE CHILLED WATER

CONTROL VALVE SHALL MODULATE TO MAINTAIN THE SCHEDULED COOLING COIL

LEAVING AIR TEMPERATURE SETPOINT (ADJ.).

THE SUPPLY FANS SHALL MODULATE TO MAINTAIN THE DUCT STATIC PRESSURE

SETPOINT SET BY TAB. RESPECTIVE ERV FANS SHALL BE INTERLOCKED TO AHU

SUPPLY FAN TO OPERATE WHENEVER THE AHU IS IN THE OCCUPIED

MODE.

BAS SHALL POLL THE DAMPER POSITION OF ALL AIR TERMINAL BOXES. IF ALL

DAMPERS ARE BELOW 60% AS INDICATED BY COMMAND SIGNAL, THE BAS SHALL

RESET THE STATIC PRESSURE SET-POINT DOWN AT A RATE OF -0.1" WG. IF ANY AIR

TERMINAL DAMPER COMMAND SIGNAL IS ABOVE 90%, THE BAS SHALL RESET

STATIC PRESSURE SET-POINT UP AT A RATE OF +0.25" WG. THE BAS SHALL POLL

ALL AIR TERMINALS CONTINUOUSLY AND LIMIT RESET FREQUENCY TO NO MORE

THAN

ONCE EVERY 15 MINUTES.

SPACE HUMIDITY IN ALL ZONES SHALL BE MONITORED. IF HUMIDITY IS WITHIN

SETPOINT (MAXIMUM OF 60% RH, ADJ.) AND ZONE TEMPERATURE IS SATISFIED,

THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL INCREASE BY 2° F (ADJ.)

EVERY 15 MINUTES (ADJ.). IF RETURN AIR HUMIDITY EXCEEDS SETPOINT, OR ZONE

TEMPERATURE IS NO LONGER SATISFIED, THEN THE SUPPLY AIR…

This is the start of the file's text. The full file is on GovTribe.