Palm_Harbor_Rec_Center_-_Electrical_-_Signed_and_Sealed.pdf

PDF 8 MB Posted

Attached to
Palm Harbor Recreation Center Addition State and local contract opportunity
Solicitation number
26-0011-ITB-C
Issued by
Pinellas County, Clewiston City, Florida

About this file

These are electrical design and construction documents for the Palm Harbor Parks and Recreation Center project located at 1500 16th Street, Palm Harbor, Florida 34683, prepared by WJ Architects and Volt Air Inc. for Pinellas County. The permit set is dated September 15, 2025, and includes comprehensive electrical system design drawings covering multiple aspects such as site electrical plans, power distribution, lighting, fire alarm systems, panel schedules, and detailed electrical installation specifications. The documents follow multiple national and local building codes including the National Electrical Code (2020), Florida Building Code (2023), and various NFPA standards.

The electrical design encompasses a 750kW diesel generator with a 208/120V, 3-phase power system, multiple electrical rooms and distribution panels across two building levels, and detailed specifications for lighting, receptacles, and fire alarm systems. The project includes emergency power systems, lightning protection, comprehensive grounding systems, and intricate electrical load calculations. The design integrates sophisticated electrical infrastructure with considerations for energy efficiency, including daylight harvesting sensors and carefully planned circuit distributions. Electrical systems are designed to serve various building spaces including a gym, multipurpose rooms, offices, restrooms, and support areas, with extensive attention to code compliance, safety standards, and precise electrical load management.

View the file

Other files for this state and local contract opportunity

Other files attached to Palm Harbor Recreation Center Addition, newest first.
File Type Posted
Site_visit_sign_in_sheet.pdf PDF
unlocked_Arch_and_Structural-Palm_Harbor.pdf PDF
Palm_Harbor_Recreation_Center_Addition_(Addendum_#5_Revision).pdf PDF
Palm_Harbor_Recreation_Center_Addition_(Addendum_#2_Revision).pdf PDF
Pricing_Proposal26-0011(reference_only).pdf PDF
Pricing_Proposal26-0011(reference_only).pdf PDF
250070-AS_Palm_Harbor_Parks_Rec_Building_2_Asbestos_Survey_Report.pdf PDF
250070-AS_Palm_Harbor_Parks_Rec_Building_2_Asbestos_Survey_Report.pdf PDF
26-0011_-_Insurance_Requirements_-_Palm_Harbor_Recreation_Center_Addition_VE.docx DOCX document
Palm_Harbor_Rec_Center_-_Mechanical_-_Rev_1.pdf PDF
PH_REC_CENTER_SPECIFICATIONS_-_VOL_2.pdf PDF
Palm_Harbor_Rec_Center_-_Mechanical_-_Rev_1.pdf PDF
Palm_Harbor_Rec_Center_-_Mechanical_-_Combined.pdf PDF
APPENDIX_7_-_SBE_COMPLIANCE_FORM.pdf PDF
APPENDIX_7_-_SBE_COMPLIANCE_FORM.pdf PDF
QUALIFICATION_SUBMITTAL_FORM_Non_FDOT.pdf PDF
SBE_Compliance_Form.pdf PDF
Agreement-26-0011.pdf PDF
Palm_Harbor_Rec_Center_-_Technology_-_Combined.pdf PDF
Palm_Harbor_Rec_Center_-_Technology_-_Combined.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_ARCHITECTURAL_ESS.pdf PDF
Palm_Harbor_Eng_Design_Rpt.pdf PDF
Palm_Harbor_Eng_Design_Rpt.pdf PDF
PH_REC_CENTER_SPECIFICATIONS_-_VOL_1.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_STRUCTURAL_S&S.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_STRUCTURAL_S&S.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_FOOD_SERVICE.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_LANDSCAPE.pdf PDF
250915_PERMIT_SET_-_PH_REC_CENTER_-_LANDSCAPE.pdf PDF
Palm_Harbor_Rec_Center_-_Electrical_-_Signed_and_Sealed.pdf PDF
Palm_Harbor_Rec_Center_-_Plumbing_-_Combined.pdf PDF
Civil_Site_Permit_Set_S&S_09-15-25.pdf PDF
Palm_Harbor_Rec_Center_-_Fire_Protection_-_Signed_and_Sealed.pdf PDF
Palm_Harbor_Rec_Center_-_Fire_Protection_-_Signed_and_Sealed.pdf PDF
Airport_Security_Program.pdf PDF
Affdavit_of_Release_and_Guarantee.pdf PDF
E-Verify_Affidavit.pdf PDF
Florida_Trench_Safety_Form.pdf PDF
Performance_and_Payment_Bonds.pdf PDF
Bid_Submittal_Form-JOC.pdf PDF
Notice_of_Intent_to_Sole_Source_07-25-2023.pdf PDF
Sample_Application_for_Payment.pdf PDF
Notice_of_Intent_to_Sole_Source_07-25-2023.pdf PDF
Sample_Change_Order.pdf PDF
Affdavit_of_Release_and_Guarantee.pdf PDF
E-Verify_Affidavit.pdf PDF
Non-Competitive_Oversight_Committee_Justification_Form.docx DOCX document
OpenGov_Fillable-_Final.pdf PDF
Airport_Security_Program.pdf PDF
OpenGov_Fillable-_Final.pdf PDF
Show all 50

Palm Harbor Recreation Center Addition has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MISCELLANEOUS RECEPTACLE(S) LIGHTING

CODES AND STANDARDS

GENERAL NOTES

SHEET INDEX

SWITCHES

SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

NFPA 70

NFPA 72

NFPA 75

NFPA 90A

NFPA 90B

NFPA 101

NFPA 110

NFPA 780

FBC

FBCE

FFPC

ICC 500

NATIONAL ELECTRICAL CODE (2020)

NATIONAL FIRE ALARM AND SIGNALING CODE (2019)

STANDARD FOR THE PROTECTION OF ELECTRONIC

COMPUTER / DATA PROCESSING EQUIPMENT (2024)

STANDARD FOR THE INSTALLATION OF AIR CONDITIONING

AND VENTILATING SYSTEMS (2021)

STANDARD FOR THE INSTALLATION OF WARM AIR

HEATING AND AIR CONDITIONING SYSTEMS (2021)

LIFE SAFETY CODE (2021)

STANDARD FOR EMERGENCY AND STAND-BY POWER

SYSTEMS (2019)

STANDARD FOR THE INSTALLATION OF LIGHTNING

PROTECTION SYSTEMS (2023)

FLORIDA BUILDING CODE (2023)

FLORIDA BUILDING CODE ENERGY CONSERVATION (2023)

FLORIDA FIRE PREVENTION CODE (2023)

ICC/NSSA STANDARD FOR THE DESIGN AND

CONSTRUCTION OF STORM SHELTERS

LOCAL JURISDICITION CODES AND / OR OWNER DESIGN

GUIDELINES

SYMBOL DESCRIPTION

1. THE ELECTRICAL CONTRACT DOCUMENTS ARE SCHEMATIC IN NATURE AND

INDICATE THE GENERAL CONFIGURATION OF SYSTEMS AND WORK. EXAMINE

ARCHITECTURAL, INTERIOR DESIGN, CIVIL, LANDSCAPE, STRUCTURAL,

MECHANICAL, PLUMBING, FIRE PROTECTION, TECHNOLOGY, AND FOOD SERVICE

DRAWINGS AND SPECIFICATIONS FOR LOCATIONS AND REQUIREMENTS OF

DEVICES, EQUIPMENT, LUMINARIES, AND SYSTEMS. CONTENT INDICATED ON

THE SPECIFICATIONS BUT NOT THE DRAWINGS, OR CONTENT INDICATED ON

THE DRAWINGS BUT NOT THE SPECIFICATIONS, SHALL BE INTERPRETED AS

BEING PRESENT ON BOTH.

2. PROVIDE ALL DEVICES, EQUIPMENT, ACCESSORIES, MATERIALS, AND LABOR

REQUIRED FOR A COMPLETE, FUNCTIONAL, AND CODE-COMPLIANT ELECTRICAL

SYSTEM. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CODES

AND STANDARDS INDICATED ON THIS SHEET.

3. ALL DEVICES, EQUIPMENT, ACCESSORIES, AND MATERIALS SHALL BE NEW, AND,

WHERE APPLICABLE, SHALL BE LISTED BY U.L. OR ANOTHER APPROVED

ELECTRICAL TESTING AGENCY.

4. COORDINATE LOCATIONS AND REQUIREMENTS OF EQUIPMENT REQUIRING

ELECTRICAL SERVICE (I.E. PRINTERS, APPLIANCES, MOTORIZED PROJECTION

SCREENS, MOTORIZED SHADES, ELEVATORS, TOOLS, ETC.) WITH APPROVED

SHOP DRAWINGS, SPECIFICATION SHEETS, MANUFACTURER’S INSTALLATION

LITERATURE, AND EQUIPMENT NAMEPLATE DATA, PRIOR TO ROUGH-IN AND

INSTALLATION. PROVIDE ELECTRICAL CONNECTIONS (AS REQUIRED).

5. BID SHALL INCLUDE COSTS ASSOCIATED WITH BACKFILLING, CORE DRILLING,

DIRECTIONAL BORING, EXCAVATING, AND REPAIRING OF SURFACES.

6. PAY ALL FEES, TAXES, AND OTHER COSTS ASSOCIATED WITH THE WORK

ENCOMPASSED BY THE ELECTRICAL CONTRACT DOCUMENTS. PROVIDE ALL

REQUIRED NOTICES AND OBTAIN ALL REQUIRED PERMITS.

7. PROVIDE COOPERATION WITH OTHER TRADES AND PROVIDE ANY INFORMATION

REQUIRED TO FACILITATE THE COMPLETION OF THEIR WORK. COORDINATE

DEVICE AND EQUIPMENT LOCATIONS AND MOUNTING HEIGHTS WITH OTHER

TRADES PRIOR TO ROUGH-IN AND INSTALLATION. COORDINATE CONDUIT

ROUTING WITH OTHER TRADES PRIOR TO ROUGH-IN AND INSTALLATION.

8. COORDINATE ALL REQUIREMENTS WITH THE LOCAL UTILITY PRIOR TO ROUGH-

IN AND INSTALLATION. COORDINATE LOCATIONS OF UTILITY HANDHOLES,

AERIAL UTILITY TRANSFORMERS, AND/OR PAD-MOUNTED UTILITY

TRANSFORMERS.

9. PROVIDE TEMPORARY ELECTRICAL SERVICE(S) FOR USE BY OTHER TRADES

DURING PROJECT CONSTRUCTION. UPON COMPLETION OF THE PROJECT, THE

TEMPORARY ELECTRICAL SERVICE(S) SHALL BE REMOVED.

10. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE RECORD

DRAWINGS TO THE OWNER. DRAWINGS SHALL BE COMPRISED OF SINGLE-LINE

DIAGRAMS AND FLOOR PLANS INDICATING THE LOCATIONS AND AREAS SERVED

FOR ALL DISTRIBUTION.

11. WITHIN THIRTY (30) DAYS OF SYSTEM ACCEPTANCE, PROVIDE AN OPERATING

MANUAL AND MAINTENANCE MANUAL TO THE OWNER. THE MANUALS SHALL

INCLUDE THE FOLLOWING INFORMATION: SUBMITTAL DATA WITH EQUIPMENT

RATINGS AND SELECTED OPTIONS, OPERATION AND MAINTENANCE MANUALS

FOR EQUIPMENT REQUIRING MAINTENANCE, NAMES AND ADDRESSES OF A

MINIMUM OF ONE (1) QUALIFIED SERVICE AGENCY.

12. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL WALL-MOUNTED

ELECTRICAL DEVICES AND EQUIPMENT WITH THE ARCHITECTURAL DRAWINGS,

GENERAL CONTRACTOR, CASEWORK/MILLWORK, AND OTHER TRADES PRIOR TO

ROUGH-IN AND INSTALLATION.

13. EQUIPMENT LOCATIONS SHALL SATISFY THE WORKING CLEARANCE

REQUIREMENTS AND DEDICATED SPACE REQUIREMENTS OF NEC ARTICLE 110.

PROVIDE SHOP DRAWINGS, DEMONSTRATING COMPLIANCE AND INTER-

DISCIPLINARY COORDINATION, FOR ENGINEERING REVIEW.

14. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS, SECTIONS, AND

ELEVATIONS FOR LOCATIONS AND/OR MOUNTING HEIGHTS OF LUMINARIES

LOCATED AT CEILINGS AND/OR WALLS. VERIFY THAT CEILING-MOUNTED

LUMINARIES ARE SUITABLE FOR THE FINISHED CEILING SYSTEM INDICATED AND

PROVIDE ACCORDINGLY. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF

WALL-MOUNTED LUMINARIES WITH CASEWORK, FURNITURE, AND

ARCHITECTURAL ELEMENTS. WHERE ARCHITECTURAL REFLECTED CEILING

PLANS INDICATE FIRE-RATED CEILING SYSTEMS, PROVIDE UL-LISTED LUMINAIRE

ENCLOSURES (AS REQUIRED).

SINGLE POWER TOGGLE SWITCH

(LETTER DENOTES FIXTURE CONTROLLED)

THREE-WAY TOGGLE SWITCH

FOUR-WAY TOGGLE SWITCH

MOTOR SWITCH

FAN SWITCH

THREE POSITION SELECTOR SWITCH

TIMER SWITCH (60 MINUTES)

LOW VOLTAGE SWITCH

HAND-OFF-AUTOMATIC SWITCH

KEY SWITCH

SWITCH - WEATHERPROOF

DUAL TECH WALL SWITCH OCCUPANCY SENSOR

DUAL TECH, DUAL-LEVEL OCCUPANCY SENSOR SWITCH

DUAL TECH OCCUPANCY SENSOR - CEILING MOUNTED

DUAL TECH OCCUPANCY SENSOR - WALL MOUNTED

PHOTOCELL

LIGHTING CONTACTOR

TIME CLOCK

MAGNETIC MOTOR STARTER

ENCLOSED CIRCUIT BREAKER, AS INDICATED

PANELBOARD, 480 / 277V

PANELBOARD, 208 /120V

MANHOLE

HANDHOLE

SURGE PROTECTION DEVICE

ELECTRICAL METER

TRANSFORMER

MOTOR CONNECTION, HP: DENOTES HORSEPOWER RATING

GROUND BUS BAR

PUSHBUTTON

3/4" PLYWOOD TELEPHONE BACKBOARD

CONCRETE ENCASED DUCTBANK

WIRE IN CONDUIT CONCEALED BELOW SLAB OR GRADE

CONDUIT EXPOSED

FLEXIBLE CONDUIT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB

DISCONNECT SWITCH, NON-FUSIBLE

3 POLE, 60 AMP, NF: NON-FUSED, 3R: NEMA 3R ENCLOSURE

DISCONNECT SWITCH, FUSIBLE

3 POLE, 60 AMP, FUSED AT 50 AMPS, 3R: NEMA 3R ENCLOSURE

COMBINATION STARTER / DISCONNECT SWITCH, FUSIBLE

3 POLE, 60 AMP, NEMA x SIZE, 3R: NEMA 3R ENCLOSURE

HOMERUN TO PANEL INDICATED

NUMBER OF ARROWS INDICATE NUMBER OF CIRCUITS

WIRE IN CONDUIT CONCEALED, #12 AWG SIZE WIRE IN

3/4" CONDUIT MINIMUM UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

MOUNTED AT 48" UNLESS NOTED OTHERWISE

QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

MOUNTED AT 48" UNLESS NOTED OTHERWISE

GFI - TYPE DUPLEX RECEPTACLE

(WP: DENOTES WEATHERPROOF COVER)

GFI - DUPLEX RECEPTACLE

MOUNTED AT 48" UNLESS OTHERWISE NOTED

GFI - DOUBLE DUPLEX RECEPTACLE

MOUNTED AT 48" UNLESS OTHERWISE NOTED

SPECIAL PURPOSE RECEPTACLE

(NEMA RATING AS INDICATED)

QUADRAPLEX RECEPTACLE, TICK MARKS

DENOTE EMERGENCY (TYPICAL ALL RECEPTACLES)

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

QUADRAPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

SINGLE RECEPTACLE, 20 AMP, 120V U.O.N.

GFI - TYPE DOUBLE DUPLEX RECEPTACLE

DUPLEX RECEPTACLE - HALF SWITCHED

DUPLEX RECEPTACLE - CEILING MOUNTED

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

COORD. TV MOUNTING HEIGHT WITH ARCHITECT / OWNER

FLOOR MOUNTED DUPLEX / QUAD RECEPTACLE. MINIMUM

3/4"C FOR POWER. REFER TO TECH DRAWINGS FOR CONDUIT,

AND DATA/AV DEVICE REQUIREMENTS. COVER AND FINISH BY

ARCHITECT. PROVIDE CORROSION / MOISTURE RESISTANT

COATING FOR BOXES INSTALLED IN SLAB ON GRADE.

PROVIDE A LEGRAND EVOLUTION SERIES OR APPROVED

EQUAL.

POWER POLE

JUNCTION BOX - CEILING MOUNTED

JUNCTION BOX - WALL MOUNTED

JUNCTION BOX - FLOOR / GROUND MOUNTED

CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED

NORMAL POWER

CEILING MOUNTED 2'x2' / 2'x4' LUMINAIRE - RECESSED

EMERGENCY POWER

CEILING MOUNTED 1'x4' LUMINAIRE

RECESSED OR SURFACE MOUNTED - NORMAL POWER

CEILING MOUNTED 1'x4' LUMINAIRE

RECESSED OR SURFACE MOUNTED - EMERGENCY POWER

CEILING MOUNTED 1'x4' LUMINAIRE

PENDANT MOUNTED - NORMAL POWER

CEILING MOUNTED 1'x4' LUMINAIRE

PENDANT MOUNTED - EMERGENCY POWER

STRIP LUMINAIRE - NORMAL POWER

STRIP LUMINAIRE - EMERGENCY POWER

DOWNLIGHT LUMINAIRE - NORMAL POWER

DOWNLIGHT LUMINAIRE - EMERGENCY POWER

WALL MOUNTED LUMINAIRE - NORMAL POWER

WALL MOUNTED LUMINAIRE - EMERGENCY POWER

CEILING FAN

TRACK LIGHTING WITH LUMINAIRE

UNDERCOUNTER LUMINAIRE

FLOOD LIGHT LUMINAIRE

POLE LIGHT LUMINAIRE

BOLLARD LUMINAIRE

STEP LIGHT LUMINAIRE

EMERGENCY BATTERY LIGHT UNIT

EXIT LIGHT - SINGLE FACE WITH DIRECTIONAL ARROW

EXIT LIGHT - DOUBLE FACE

EXIT LIGHT - WALL MOUNTED

3P/60A

NF

3R

3P/60A F:50A

3R

3P/60A Nx

3R

MH

HH

SPD

TX

HP

S

3S

4S

MS

FS

3PS

TS

LVS

HOAS

KS

WPS

OSS

DOSS

PC

LC

TC

OS

OS

TV

PP

J

J

J

COMMISSIONING

1. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL SUBMIT

EVIDENCE TO THE REGISTERED DESIGN PROFESSIONAL (ELECTRICAL

ENGINEER-OF-RECORD) OR REGISTERED DESIGN PROFESSIONAL’S

REPRESENTATIVE THAT THE LIGHTING CONTROL SYSTEMS HAVE BEEN

TESTED TO ENSURE THAT THEY ARE CALIBRATED, ADJUSTED,

PROGRAMMED, AND SATISFY THE INTENT OF THESE CONTRACT

DOCUMENTS AND THE MANUFACTURERS’ WRITTEN INSTRUCTIONS.

FUNCTIONAL TESTING SHALL BE PERFORMED IN ACCORDANCE WITH

FBC C408.3.1.1 (VACANCY / OCCUPANCY SENSOR CONTROLS), FBC

C408.3.1.2 (TIME-SWITCH CONTROLS), AND/OR FBC C408.3.1.3 (DAYLIGHT

RESPONSIVE CONTROLS) (AS REQUIRED).

DUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

AUTOMATIC SWITCHED RECEPTACLE

QUADRUPLEX RECEPTACLE, 20 AMP, 120V U.O.N.

HALF-AUTOMATIC SWITCHED RECEPTACLE

VFD

VFD-RATED, REMOTE DISCONNECT SWITCH WITH EARLY-

BREAK, AUXILIARY CONTACTS FOR VFD DECELERATE-TO-

STOP SIGNAL. CONNECT CONTROL WIRING TO ASSOCIATED

VFD (AS REQUIRED).

15. PROVIDE A COMPLETE GROUNDING SYSTEM IN ACCORDANCE WITH APPLICABLE

SECTIONS OF THE NEC AND SPECIFICATIONS. BOND SERVICE ENTRANCE

ELECTRICAL EQUIPMENT TO BUILDING STEEL, GROUND RODS, METAL WATER

MAINS, LIGHTNING PROTECTION SYSTEM GROUNDING ELECTRODES (WHERE

PRESENT), AND TELECOMMUNICATIONS SYSTEM GROUNDING ELECTRODES (AS

REQUIRED). EQUIPMENT GROUNDING SHALL BE OF THE WIRE TYPE.

16. MINIMUM CONDUIT SIZE SHALL BE 3/4".

17. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG. ALL FEEDER AND BRANCH

CIRCUIT CONDUCTORS SHALL BE INSTALLED WITHIN CONDUIT, UNLESS

OTHERWISE INDICATED. ALL CONDUCTORS SHALL BE COPPER, UNLESS

OTHERWISE INDICATED.

18. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTI-WIRE

BRANCH CIRCUITS SHALL BE PROHIBITED.

19. CONNECTIONS TO TRANSFORMERS AND MECHANICAL EQUIPMENT SHALL BE

MADE WITH FMC OR LFMC, UNLESS OTHERWISE INDICATED.

20. WHERE PRACTICABLE, CONDUITS SHALL BE CONCEALED BELOW SLABS, WITHIN

WALLS, AND ABOVE FINISHED CEILING SYSTEMS. WHERE CONDUITS ARE

EMBEDDED WITHIN CONCRETE SLABS, COORDINATE CONDUIT SIZE LIMITATIONS

AND SPACING REQUIREMENTS WITH THE STRUCTURAL DRAWINGS/ENGINEER

PRIOR TO INSTALLATION.

21. SEAL ALL CONDUIT PENETRATIONS AT FIRE-RATED PARTITIONS. REFER TO

DETAILS FOR FURTHER INFORMATION.

22. COORDINATE ALL CONDUIT PENETRATIONS WITH ARCHITECTURAL DRAWINGS,

STRUCTURAL DRAWINGS, FIELD CONDITIONS, AND OTHER TRADES. PROVIDE

SEALING FITTINGS TO PROHIBIT CONDENSATION AND/OR THE PASSAGE OF

GASES OR VAPORS (AS REQUIRED).

23. INCREASE FEEDER AND BRANCH CIRCUIT CONDUCTOR SIZES AS REQUIRED IN

ORDER TO MAINTAIN A MAXIMUM, CUMULATIVE VOLTAGE DROP OF 5% AT THE

END LOAD. MAXIMUM VOLTAGE DROP SHALL BE DISTRIBUTED AS FOLLOWS: 3%

FOR FEEDERS, 2% FOR BRANCH CIRCUITS. WHERE THE VOLTAGE DROP

REQUIREMENTS OF THE LOCAL ENERGY CODE ARE MORE STRINGENT, THE

REQUIREMENTS OF THE LOCAL ENERGY CODE SHALL TAKE PRECEDENCE.

WHERE PHASE AND NEUTRAL CONDUCTOR SIZES ARE INCREASED FOR

VOLTAGE DROP, THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE

INCREASED PROPORTIONATELY.

24. PROVIDE ALL REQUIRED DISCONNECT SWITCHES, STARTERS, AND

COMBINATION STARTER/DISCONNECT SWITCHES. MAKE CONNECTIONS TO ALL

ELECTRICALLY-DRIVEN DEVICES AND EQUIPMENT PROVIDED BY THE

MECHANICAL, PLUMBING, AND FIRE PROTECTION CONTRACTORS. EXAMINE

EQUIPMENT NAMEPLATE RATINGS PRIOR TO ROUGH-IN AND INSTALLATION.

PROVIDE OVERCURRENT PROTECTION IN ACCORDANCE WITH EQUIPMENT

NAMEPLATE RATINGS. PROVIDE ALL POWER SUPPLIES, CONTROL

TRANSFORMERS, RELAYS, AND OTHER ACCESSORIES REQUIRED TO FACILITATE

THE PROPER OPERATION OF MECHANICAL EQUIPMENT AS DESCRIBED WITHIN

THE MECHANICAL ENGINEER’S SEQUENCE OF OPERATIONS.

25. ALL INTERIOR ELECTRICAL EQUIPMENT SHALL BE OF NEMA 1 CONSTRUCTION,

UNLESS OTHERWISE INDICATED. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL

BE OF NEMA 3R CONSTRUCTION, UNLESS OTHERWISE INDICATED. EQUIPMENT

RATINGS SHALL CORRESPOND TO THEIR INSTALLED ENVIRONMENTS.

26. ALL NEW AND/OR EXISTING PANELBOARDS AND SWITCHBOARDS WITHIN THE

SCOPE OF THIS PROJECT SHALL BE PROVIDED WITH NEW, TYPEWRITTEN

DIRECTORIES. CIRCUIT DESCRIPTIONS SHALL CONTAIN ROOM NAMES AND

ROOM NUMBERS BASED UPON INSTALLED ROOM SIGNAGE.

27. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT ALL

SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, TRANSFORMERS, DISCONNECT

SWITCHES, ENCLOSED CIRCUIT BREAKERS, CABINETS, AND AUTOMATIC

TRANSFER SWITCHES. REFER TO DETAILS FOR FURTHER INFORMATION.

28. PROVIDE PHENOLIC, ENGRAVED IDENTIFICATION PLACARDS AT EACH CIRCUIT

BREAKER WITHIN A DISTRIBUTION PANEL, SWITCHBOARD, OR SWITCHGEAR.

29. PROVIDE TYPEWRITTEN OR ENGRAVED PANEL AND CIRCUIT IDENTIFICATION AT

DEVICE COVER PLATES.

30. PROVIDE HANDWRITTEN PANEL AND CIRCUIT IDENTIFICATION ON THE

EXTERIORS OF ALL JUNCTION BOXES, PULL BOXES, AND WIREWAYS.ELECTRICAL ABBREVIATIONS

SYMBOL DESCRIPTION

A

AC

A/C

AFCI

AHU

AIC

AL

ATS

AWG

C

CATV

CB

C/B

CCTV

CIR

CKT

CU

DC

DIA

EB

EC

EF

EG

ELEV

EM

EMT

EP

EPO

ER

ETR

EWC

EX

F

FA

FAA

FLA

FMC

G, GND

GFCI, GFI

GND

GRC

HOA

HVAC

HZ

IEEE

IG

AMPERES

ALTERNATING CURRENT

AIR CONDITIONING

ARC FAULT CIRCUIT INTERRUPTER

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

CONDUIT

CABLE TELEVISION

CRITICAL BRANCH

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CIRCUIT

COPPER

DIRECT CURRENT

DIAMETER

EQUIPMENT BRANCH

ELECTRICAL CONTRACTOR

EXHAUST FAN

EQUIPMENT GROUND

ELEVATOR

EMERGENCY

ELECTRICAL METALLIC TUBING

EMERGENCY POWER

EMERGENCY POWER OFF (BUTTON OR SWITCH)

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

ELECTRIC WATER COOLER

EXISTING TO REMAIN

FUSE

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FULL LOAD AMPERES

FLEXIBLE METAL CONDUIT

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

GROUND

GALVANIZED RIGID METAL CONDUIT

HAND-OFF-AUTOMATIC SWITCH

HEATING, VENTILATION, AIR CONDITIONING

HERTZ

INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

ISOLATED GROUND

IMC

KCMIL

KVA

LFMC

LTG

LRA

MC

MCB

MCC

MCP

MLO

MTD

NC

NEC

NEMA

NFPA

NL

NO

P

PB

PNL

PWR

QTY

REQ

RMC

RNC

RTS

RTU

SP

ST

SW

SYM

TEL

TGB

TMCB

TV

TYP

UG

UL

V

VA

VFD

W

WH

WP

XFMR

INTERMEDIATE METAL CONDUIT

THOUSAND CIRCULAR MILS

KILOVOLT - AMPERES

LIQUID TIGHT FLEXIBLE METAL CONDUIT

LIGHTING

LOCK ROTOR AMPS

METAL CLAD CABLE

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTION

MAIN LUGS ONLY

MOUNTED

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NIGHT LIGHT

NORMALLY OPEN OR NUMBER

POLE

PUSH BUTTON, PANIC BUTTON OR PULLBOX

PANEL

POWER

QUANTITY

REQUIRED

RIGID METAL CONDUIT

RIGID NON-METALLIC CONDUIT

REMOTE TEST STATION

ROOF TOP UNIT

SPARE

SHUNT-TRIP

SWITCH

SYMMETRICAL

TELEPHONE

TELECOMMUNICATIONS GROUNDING BUSBAR

THERMAL MAGNETIC CIRCUIT BREAKER

TELEVISION

TYPICAL

UNDERGROUND

UNDERWRITERS LABORATORY

VOLT

VOLT - AMPERE

VARIABLE FREQUENCY DRIVE

WATT OR WIRE

WIRE GUARD

WATER HEATER

WEATHERPROOF

TRANSFORMER

SYMBOL DESCRIPTION

DAYLIGHT HARVESTING SENSOR - CEILING MOUNTEDDH

DIMMING SWITCHSD

ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING:

RELAY MODULE WITH 0-10V DIMMING OUTPUTPL

PLUG LOAD RELAY PACKPR

FIRE ALARM

SYMBOL DESCRIPTION

FACP: FIRE ALARM CONTROL PANEL

FATC: FIRE ALARM TERMINAL CABINET

FAAP: FIRE ALARM ANNUNCIATOR PANEL

EVAC: FIRE ALARM VOICE / EVAC. UNIT

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER DEVICE

FIRE ALARM SPEAKER DEVICE - CEILING MOUNTED

FIRE ALARM HEATER DETECTOR - CEILING MOUNTED

FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED

SB: SOUNDER BASE

I: IONIC

CO: CARBON MONOXIDE

FIRE ALARM SMOKE DETECTOR - WALL MOUNTED

SB: SOUNDER BASE

CO: CARBON MONOXIDE

UF: UNDERFLOOR

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM RELAY

ELECTROMAGNETIC DOOR CONTACT

DOOR HOLDER

FIRE ALARM REMOTE ALARM INDICATOR WITH TEST

SWITCH, FLUSH CEILING MOUNTED, WALL MTD.

CENTER LINE 48" A.F.F. IN MECHANICAL ROOMS

MONITORING MODULE

FIRE ALARM STROBE ONLY DEVICE

MINIMUM 75cd RATING

FIRE ALARM HORN / STROBE ONLY DEVICE

MINIMUM 75cd RATING

FIRE ALARM SPEAKER / STROBE ONLY DEVICE

MINIMUM 75cd RATING

FIRE ALARM STROBE ONLY DEVICE

MINIMUM 75cd RATING - CEILING MOUNTED

FIRE ALARM HORN / STROBE ONLY DEVICE

MINIMUM 75cd RATING - CEILING MOUNTED

FIRE ALARM SPEAKER / STROBE ONLY DEVICE

MINIMUM 75cd RATING - CEILING MOUNTED

FIRE ALARM HORN DEVICE

MINIMUM 75cd RATING

FIRE ALARM HORN DEVICE

MINIMUM 75cd RATING - CEILING MOUNTED

FIRE ALARM DUCT SMOKE DETECTOR

S: SUPPLY.....R: RETURN

P

S

S

S

S

S/R

R

DC

DH

RA

MM

FIRE ALARM KNOX BOXK

FIELD VERIFY ALL LOCATION

1. DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT

THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT

EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL

LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO

EXISTING CONDITIONS.

2. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR

OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND

CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO

MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT,

ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE

IMPLEMENTED AT CONTRACTORS COST.

3. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF

LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS

THE COST FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH

GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT

WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT,

ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN

GOVERNING CODES AND DESIGN INTENT.

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

N D

O T

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V E

IN

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

S P

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

R

C

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

A

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

H

X

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

G

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

IT

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

L A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y I

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

F

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B lv d.

ui te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 6:

A

M

E-000

LEGEND - ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

NUMBER NAME

E-000 LEGEND - ELECTRICAL

E-002 SCHEDULES - ELECTRICAL

E-003 SCHEDULES - ELECTRICAL

E-100 SITE PLAN - ELECTRICAL

ED-101 EXISTING BUILDING - FLOOR PLAN - ELECTRICAL

ED-102 EXISTING BUILDING -ONE-LINE - ELECTRICAL

E-201 LEVEL 1 - FLOOR PLAN - POWER

E-202 LEVEL 2 - FLOOR PLAN - POWER

E-203 ROOF PLAN - POWER

E-204 ROOF PLAN - LIGHTNING PROTECTION

E-205 ROOF PLAN - LIGHTNING PROTECTION DETAILS

E-301 LEVEL 1 - RCP - LIGHTING

E-302 LEVEL 2 - RCP - LIGHTING

E-401 ENLARGED FLOOR PLANS - ELECTRICAL

E-402 ENLARGED FLOOR PLANS - KITCHEN ELECTRICAL

E-500 ONE-LINE DIAGRAM NOTES

E-501 ONE-LINE DIAGRAM - ELECTRICAL

E-601 PANEL SCHEDULES - ELECTRICAL

E-602 PANEL SCHEDULES - ELECTRICAL

E-603 PANEL SCHEDULES - ELECTRICAL

E-604 PANEL SCHEDULES - ELECTRICAL

E-700 FIRE ALARM RISER - ELECTRICAL

E-901 DETAILS - ELECTRICAL

E-902 DETAILS - ELECTRICAL

E-903 DETAILS - ELECTRICAL

REV DESCRIPTION DATE

GENERAL NOTES - EL/MECH SCH.

A. COORDINATE ALL ELECTRICAL REQUIREMENTS WITH THE

DIVISION 22 CONTRACTOR, DIVISION 23 CONTRACTOR AND

APPROVED EQUIPMENT SUBMITTALS PRIOR TO ROUGH-IN AND

INSTALLATION. REFER TO MECHANICAL AND PLUMBING

DRAWINGS FOR FURTHER INFORMATION.

B. FOR ALL VFD-DRIVEN EQUIPMENT, PROVIDE A VFD-RATED

CABLE ASSEMBLY BETWEEN THE VFD OUTPUT AND

ASSOCIATED EQUIPMENT AS FOLLOWS; XLPE INSULATION

RATED AT 2,000V, SHIELDED, 100% EQUIPMENT GROUND.

CONDUIT AND CONDUCTORS BETWEEN SOURCE AND VFD

INPUT SHALL BE AS SCHEDULED.

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 6:

A

M

E-002

SCHEDULES -

ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

ELECTRICAL MECHANICAL EQUIPMENT CHILLER SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

CH-1 167100 VA 465 208 V 3 600.4 - REFER TO E-5.01 MSB 7 --- --- --- 800A 3 NEMA 3R 26

ELECTRICAL MECHANICAL EQUIPMENT AIR HANDLER SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

AHU-1 15563 VA 43.2 208 V 3 60.4 - REFER TO E-5.01 LN1MA 1,3,5 --- --- --- 100A 3 NEMA 1 26

AHU-2 10779 VA 29.92 208 V 3 40A - REFER TO E-6xx SHEETS LN1MA 7,9,11 --- --- --- 60A 3 NEMA 1 26

AHU-3 1729 VA 4.8 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 13,15,17 --- --- --- 30A 3 NEMA 3R 26

ELECTRICAL MECHANICAL EQUIPMENT PUMP SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

STARTER TYPE NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

CHWP-1 8700 VA 24.2 208 V 3 35A - REFER TO E-6xx SHEETS LN1MA 2,4,6 VFD --- NEMA 3R 23 --- --- --- ---

CHWP-2 8700 VA 24.2 208 V 3 35A - REFER TO E-6xx SHEETS LN1MA 8,10,12 VFD --- NEMA 3R 23 --- --- --- ---

ELECTRICAL MECHANICAL EQUIPMENT ERV SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

ERV-1 13088 VA 29.04 208 V 3 40A - REFER TO E-6xx SHEETS LN2MA 1,3,5 --- --- --- 60A 3 NEMA 1 26

ELECTRICAL MECHANICAL EQUIPMENT VAV SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

CV-1-5 9400 VA 26 208 V 3 35A - REFER TO E-6xx SHEETS LN1MB 29,31,33 --- --- --- 60A 3 NEMA 1 26

CV-1-6 3700 VA 17.8 208 V 1 25A - REFER TO E-6xx SHEETS LN1MB 35,37 --- --- --- 30A 2 NEMA 1 26

CV-1-8 12500 VA 34.6 208 V 3 45A - REFER TO E-6xx SHEETS LN2MA 7,9,11 --- --- --- 60A 3 NEMA 1 26

CV-1-9 12400 VA 34.4 208 V 3 45A - REFER TO E-6xx SHEETS LN2MB 27,29,31 --- --- --- 60A 3 NEMA 1 26

IWH-1 6240 VA 30 208 V 1 40A - REFER TO E-6xx SHEETS LN1MB 21,23 --- --- --- 30A 3 NEMA 1 26

VAV-1-1 1500 VA 7.2 208 V 1 20A - REFER TO E-6xx SHEETS LN1MA 13,15 --- --- --- 30A 2 NEMA 1 26

VAV-1-2 5400 VA 15 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 6,8,10 --- --- --- 30A 3 NEMA 1 26

VAV-1-3 7500 VA 21 208 V 3 20A - REFER TO E-6xx SHEETS LN1MB 12,14,16 --- --- --- 30A 3 NEMA 1 26

VAV-1-4 2100 VA 10 208 V 1 20A - REFER TO E-6xx SHEETS LN1MB 25,27 --- --- --- 30A 2 NEMA 1 26

VAV-1-7 1300 VA 6.25 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 33,35 --- --- --- 30A 2 NEMA 1 26

VAV-1-10 2200 VA 10.6 208 V 1 20A - REFER TO E-6xx SHEETS LN2MA 2,4 --- --- --- 30A 2 NEMA 1 26

VAV-1-11 4600 VA 22 208 V 1 30A - REFER TO E-6xx SHEETS LN2MA 6,8 --- --- --- 30A 3 NEMA 1 26

VAV-1-12 9100 VA 25 208 V 3 35A - REFER TO E-6xx SHEETS LN2MB 1,3,5 --- --- --- 30A 3 NEMA 1 26

VAV-1-13 2700 VA 13 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 18,20 --- --- --- 30A 2 NEMA 1 26

VAV-1-14 1100 VA 5.2 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 30,32 --- --- --- 30A 2 NEMA 1 26

VAV-1-15 2900 VA 13.94 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 22,24 --- --- --- 30A 2 NEMA 1 26

VAV-1-16 2000 VA 9.615 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 26,28 --- --- --- 30A 2 NEMA 1 26

ELECTRICAL MECHANICAL EQUIPMENT FAN SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

EF-1 666 VA 3.2 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 14,16 --- --- --- 30A 2 NEMA 1 26

EF-2 528 VA 4.4 115 V 1 20A - REFER TO E-6xx SHEETS LN1MB 2 --- --- --- 30A 1 NEMA 1 26

KEF-1 1518 VA 7.3 208 V 3 20A - REFER TO E-6xx SHEETS LN2MB 2,4,6 --- --- --- 30A 3 NEMA 3R 26

ELECTRICAL MECHANICAL EQUIPMENT MAKE UP AIR SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

MUA-1 1186 VA 5.7 208 V 3 20A - REFER TO E-6xx SHEETS LN2MB 8,10,12 --- --- --- 30A 3 NEMA 3R 26

ELECTRICAL PLUMBING EQUIPMENT WATER HEATERS

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

EWH-1 36000 VA 173.07 208 V 3 225.4 - REFER TO E-5.01 LN1MB 3,5,7 --- --- --- 200A 3 NEMA 3R 26

EWH-2 4500 VA 21.6 208 V 1 25A - REFER TO E-6xx SHEETS LN1MA 17,19 --- --- --- 30A 2 NEMA 3R 26

ELECTRICAL PLUMBING EQUIPMENT PUMPS

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

BP-1 6720 VA 56 120 V 1 70.4 - REFER TO E-5.01 LN1MA 31 --- NEMA 1 26 100A 1 NEMA 1 26

CP1 1176 VA 9.8 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 11 --- NEMA 1 26 20A 1 NEMA 1 26

CP-2 1176 VA 9.8 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 9 --- NEMA 1 26 20A 1 NEMA 1 26

SP-1 200 VA 1.7 120 V 1 20A - REFER TO E-6xx SHEETS LN1MB 1 30A 1 NEMA 3R

ELECTRICAL MECHANICAL DUCT HEATER SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

DH-1 60000 VA 167 208 V 3 200.4 - REFER TO E-5.01 LN1MA 25,27,29 --- --- --- 300A 3 NEMA 1 26

ELECTRICAL CONDENSING UNIT SCHEDULE

TAG LOAD

FLA

(AMPS) VOLTAGE PHASE CONDUIT/WIRE (AWG) PANEL CIRCUIT NUMBER

STARTER DISCONNECT

NEMA SIZE ENCLOS. TYPE FURN. BY (DIV.) SWITCH SIZE NO. OF POLES ENCLOS. TYPE FURN. BY (DIV.)

COOLER 2090 VA 5.8 208 V 3 20A - REFER TO E-6xx SHEETS LK1B1 8,10,12 --- --- --- 30A 3 NEMA 3R 26

CU-1 2300 VA 11.4 208 V 1 20A - REFER TO E-6xx SHEETS LN2MB 21,23 --- --- --- 30A 2 NEMA 3R 26

FREEZER 3459 VA 9.6 208 V 3 20A - REFER TO E-6xx SHEETS LK1B1 14,16,18 --- --- --- 30A 3 NEMA 3R 26

GENERAL NOTES - LUMINAIRE SCH.

A. COORDINATE COLORS AND FINISHED WITH ARCHITECT AND /

OR OWNER PRIOR TO ORDERING.

B. COORDINATE LAMP SOURCE COLOR TEMPERATURE WITH

ARCHITECT PRIOR TO ORDERING.

C. WHERE A LUMINAIRE IS AVAILABLE IN TRIM-BASED AND

TRIMLESS CONFIGURATIONS, COORDINATE THE

APPROPRIATE CONFIGURATION WITH THE ARCHITECT PRIOR

TO ORDERING.

D. COORDINATE CEILING TYPES WITH THE ARCHITECT PRIOR TO

ORDERING. ONE (1) LUMINAIRE TYPE MAY BE LOCATED

WITHIN MULTIPLE CEILING TYPES. REFER TO

ARCHITECTURAL REFLECTED CEILING PLANS FOR FURTHER

INFORMATION.

E. PROVIDE INDEPENDENT SUPPORTS TO THE BUILDING

STRUCTURE IN ACCORDANCE WITH THE APPLICABLE

DIVISION 26 SPECIFICATION SECTIONS.

F. WHERE A LUMINAIRE IS EQUIPPED WITH A DIMMABLE DRIVER,

BUT IS NOT DEPICTED AS CONTROLLED VIA A DIMMER

SWITCH ON THE LIGHTING PLANS, TERMINATE THE 0-10V

CONTROL WIRING IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS TO ALLOW FOR ON / OFF SWITCHING.

G. VERIFY COMPATIBILITY BETWEEN DIMMER SWITCHES AND

DIMMABLE DRIVERS PRIOR TO ORDERING.

H. COORDINATE LUMINAIRE LOCATIONS, MOUNTING HEIGHTS

(WHERE APPLICABLE), SUSPENSION HEIGHTS (WHERE

APPLICABLE) AND SUSPENSION METHODS (WHERE

APPLICABLE) WITH ARCHITECT PRIOR TO ORDERING, ROUGH-

IN AND INSTALLATION.

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 7:

A

M

E-003

SCHEDULES -

ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

LIGHTING CONTROL MATRIX

EXTERIOR LIGHTING CONTACTOR

RELAY /

DIMMER

MODULE

NUMBER PANEL

CIRCUIT

NUMBER SWITCH TYPE CONTROLLED BY

SWITCH ID

(ZONE) NOTE Voltage AREA CONTROLLED

1 LEM1A 1 OVERRIDE TIMECLOCK/PHOTOCELL Z1 120 V EXTERIOR SCONCES

2 LEM2B 8 OVERRIDE TIMECLOCK/PHOTOCELL Z2 120 V EXTERIOR DOWNLIGHTS

LUMINAIRE SCHEDULE

Image TYPE DESCRIPTION MANUFACTURER MODEL # LUMENS LAMP TYPE VOLTAGE WATTAGE DIMMING MOUNTING NOTES

A 2X4 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR

WARRANTY

METALUX OR APPROVED EQUAL 24CGTS-L3C3-MID-4000K 5241 lm 80CRI/SET TO 4000K

120-277V 39 VA 0-10V/10% RECESSED

B 2X2 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR

WARRANTY

METALUX OR APPROVED EQUAL 22CGTS-L3C3-MID-4000K 3890 lm 80CRI/SET TO 4000K

120-277V 29 VA 0-10V/10% <varies>

BE 2X2 TROFFER, CULUS LISTED FOR 25C AMBIENT ENVIRONMENTS, INDOOR APPLICATIONS, 5 YEAR

WARRANTY W/ EMERGENCY 14W BATTERY

METALUX OR APPROVED EQUAL 22CGTS-L3C3-MID-4000K-EL7W 3890 lm 80CRI/SET TO 4000K

120-277V 29 VA 0-10V/10% RECESSED FIXTURE USED IN

EXISTING

BUILDING.

C1 4’ STRIP FIXTURE INTEGRAL FACTORY INSTALLED CONTROLS OPTION ALLOWS MORE ENERGY

SAVINGS, 5 YEAR WARRANTY

METALUX OR APPROVED EQUAL 4SNX-41SL-LW-UNV-L840-CD 3848 lm 80CRI/SET TO 4000K

120-277V 26 VA 0-10V/10% SURFACE/SUSPE

NDED

C2 8' STRIP FIXTURE INTEGRAL FACTORY INSTALLED CONTROLS OPTION ALLOWS MORE ENERGY

SAVINGS, 5 YEAR WARRANTY

METALUX OR APPROVED EQUAL 8TSNX-XXXX-XX-UNV-L8XX-CD1-U 0 lm 80CRI/SET TO 4000K

120-277V 0 VA 0-10V/10% SURFACE/SUSPE

NDED

D 4' VANITY, 4760 LUMENS, ALUMINUM AND STEEL WITH VARIOUS PAINT FINISHES, 50,000 HOUR L70

RATED LIFE, 5 YEAR WARRANTY

KUZCO OR APPROVED EQUAL VL61248-CH 3810 lm 90CRI/SET TO 4000K

120V 59 VA 0-10V SURFACE

E1 6” RECESSED DOWNLIGHT, NEW CONSTRUCTION/REMODEL SERIES; 500 TO 6,000 LUMENS,

UNIVERSAL VOLTAGE 120V-277V; STANDARD 0-10V DRIVER DIMS TO 1%, 5 YEAR WARRANTY

COOPER OR APPROVED EQUAL HC610D010-HM60525835-61WDC 1279 lm 90CRI/SET TO 3500K

120-277V 10 VA 0-10V/1% RECESSED

E2 6” RECESSED DOWNLIGHT, NEW CONSTRUCTION/REMODEL SERIES; 500 TO 6,000 LUMENS,

UNIVERSAL VOLTAGE 120V-277V; STANDARD 0-10V DRIVER DIMS TO 1%, 5 YEAR WARRANTY

COOPER OR APPROVED EQUAL HC620D010-HM60525835-61WDC 2359 lm 90CRI/SET TO 3500K

120-277V 20 VA 0-10V/1% RECESSED

EM EMERGENCY BUG EYE FIXTURES ACTIVATED DURING POWER LOSS ISOLITE OR APPROVED EQUAL BUG-3W-WH-MB 600 lm LED 120-277V 5 VA - SURFACE

F 4' STAIR LIGHT, IK10 RATED, 16 GA CRS, HIGH IMPACT FROSTED LENS, 9800 LUMENS, INTEGRAL

PIR SENSOR, 10W EMERGENCY, 50,000 HOUR L70 RATED LIFE, 5 YEAR WARRANTY

METALUX OR APPROVED EQUAL 4SWLED-48HL-LW-UNV-L840-CD1-U 4899 lm 80CRI/SET TO 4000K

120-277V 45 VA 0-10V/10% SURFACE

G HIGHBAY, SET 18,000 LUMENS, IP65/WET LOCATION LISTED, SWITCHABLE 4000K/5000K, NEMA 4X, IP65 AND NSF RATED, IMPACT PROTECTION RATING IK08 LENS AND IK08 HOUSING, 5 YEAR

WARRANTY

METALUX OR APPROVED EQUAL UHBS-18-MV-L840-U 120V 18353 lm 4000K,80CRI,LED 120-347V 120 VA 0-10V SUSPENDED 26'

AFF

H1 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 4200 lm 80CRI/4000K 120-277V 157 VA 0-10V/10% SUSPENDED

H2 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 3600 lm 80CRI/4000K 120-277V 157 VA 0-10V/10% SUSPENDED

H3 BEAM 3 DIRECT,MINIMUM 50,000 HOURS LIFESPAN, 5 YEAR WARRANTY AXIS OR APPROVED EQUAL TB3DLED-500-80-30-SO 3600 lm 80CRI/4000K 120-277V 126 VA 0-10V/10% SUSPENDED

J 8' RECESSED MOUNT IS A HIGH-PERFORMANCE ARCHITECTURAL LINEAR LED FIXTURE

DESIGNED FOR MODERN SPACES THAT REQUIRE BOTH AESTHETIC APPEAL AND EFFICIENCY.

AXIS OR APPROVED EQUAL SCR-500-80-30-FL-4 2005 lm 80CRI/SET TO 4000K

120-277V 23 VA 0-10V/1% RECESSED

K1 1' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5

YEAR WARRANTY

MERCURY ARCHITECTURAL

LIGHTING OR APPROVED EQUAL

MLA-DI-12-1050-1250-30K-HTA-BW-1_-2

C-U-MG

9264 lm 80CRI/4000K 120-277V 88 VA 0-10V/10% SUSPENDED

K2 2' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5

YEAR WARRANTY

MERCURY ARCHITECTURAL

LIGHTING OR APPROVED EQUAL

MLA-DI-24-1050-1250-30K-HTA-BW-1_-2

C-U-MG

9264 lm UNLIT N/A 88 VA N/A SUSPENDED

K2E 2' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5

YEAR WARRANTY

MERCURY ARCHITECTURAL

LIGHTING OR APPROVED EQUAL

MLA-DI-24-1050-1250-30K-HTA-BW-1_-2

C-U-MG

9264 lm UNLIT N/A 88 VA N/A SUSPENDED

K4E 4' LINEAR DIRECT, ACOUSTIC BATTING 1.1 NCR, 500 LUMENS/FT, 60,000 HOUR L70 RATED LIFE, 5

YEAR WARRANTY

MERCURY ARCHITECTURAL

LIGHTING OR APPROVED EQUAL

MLA-DI-48-1050-1250-30K-HTA-BW-1_-2

C-U-MG

9264 lm 80CRI/4000K 120-277V 88 VA 0-10V/1% SUSPENDED

L 4" CYLINDER, 2000 LUMENS, 55,000 HOUR L70 RATED LIFE, 5 YEAR WARRANTY HE WILLIAMS OR APPROVED EQUAL CF06XXPC 20L 30K XW XX CL XX 1455 lm 80CRI/4000K 120-277V 13 VA 0-10V/1% SUSPENDED

LP 4' ELEVATOR PIT LIGHTING VAPOR-TIGHT LIGHT WEIGHT LED FIXTURE, 5 YEAR WARRANTY METALUX OR APPROVED EQUAL 4APVTLD-SL3C3 4620 lm 4000K 120-277V 145 VA 0-10V/10% SURFACE

M 2X2 LINEAR HIGHBAY COMPACT, 3 LUMEN OUTPUT, 40/50K CCT SPITZER OR APPROVED EQUAL LHC-14-180LC 15000 lm 80CRI/4000K 120-277V 117 VA 0-10V SURFACE PROVIDE WITH

WIRE GUARD

X LED EXIT LIGHT FIXTURE WITH INTEGRAL LED TEST SWITCH SURE-LITES OR APPROVED EQUAL SCX60G 0 lm N/A 120-277V 5 VA <varies> <varies>

Z COLOR CHANGEABLE CUT-OFF EXTERIOR WALLPACK SPITZER OR APPROVED EQUAL WPFP-XXX-U-CC-XX-C1-XX 0 lm TBD 120-277V 0 VA - SURFACE

MM

A. COORDINATE WITH DUKE ENERGY FOR ELECTRIC UTILITY

SERVICE CONNECTION AND REQUIREMENTS.

B. UNDERGROUND CONDUIT IS DIAGRAMMATIC ONLY. FINAL

ROUTING, QUANTITY, AND SIZE SHALL BE COORDINATED WITH

CIVIL CONTRACTOR.

PROVIDE ASCO 300 GENERATOR

DOCKING STATION. REFER TO

ELECTRICAL ONE-LINE DIAGRAM

(MAIN BUILDING) FOR

FURTHER INFORMATION.

PROVIDE 4" CONCRETE PAD FOR

MOUNTING.

GENERATOR ROOM

PROPOSED LOCATION

OF UTILITY

TRANSFORMER

MAIN ELECTRICAL

ROOM 109

LEVEL 1 ELECTRICAL

ROOM 116

LEVEL 2 ELECTRICAL

ROOM 201

LEVEL 2 ELECTRICAL

ROOM 215

(8) SETS 4#600 CU IN 4"C

PROPOSED LOCATION

OF UTILITY METER

EXISTING

BUILDING

EXISTING

PARKING LOT

NEW PARKING LOT

NOT IN SCOPE

(2) SETS 3#600 CU IN 4"C

COORDINATE TAMPER SWITCH

PLACEMENT WITH PROPOSED NEW

BACKFLOW DEVICE AND FDC LOCATION.

DIESEL PUMP

3P/30A 3R

NF

PROVIDE ICC 500 COMPLIANT ENCLOSURE.

(3) SETS 3#600 CU IN 4"C

LEM1A-4,6

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 6:

A

M

E-100

SITE PLAN -

ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

0' 15' 30' 60' 120'

SCALE: 1" = 30'-0"

N

1" = 30'-0"

SITE PLAN - ELECTRICAL

A. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE

PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

B. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT

AND MAINTAIN THE INTEGRITY OF REMAINING DEVICES AND

EQUIPMENT. ANY SUCH CONNECTIONS SHALL BE CONCEALED

UNLESS LOCATED IN UNFINISHED AREAS.

C. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO

REMOVE AND LEGALLY DISPOSE OF DEMOLISHED MATERIALS.

D. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL

SCHEDULED FOR REMOVAL AND SALVAGE ANY ITEMS DEEMED

USEABLE AS SPARE PARTS.

E. EXISTING CONDITIONS INDICATED ON THIS DRAWING ARE TAKEN

FROM FIELD INVESTIGATION. IT IS RECOMMENDED FOR

CONTRACTOR TO VISIT SITE AND VERIFY EXISTING CONDITIONS

PRIOR TO BID.

F. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL

DEVICES, FITTINGS, CONDUITS, ETC. IT IS INTENDED TO PROVIDE

THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING

CONDITIONS WITHIN THE PROJECT AREA.

G. THE CONTRACTOR SHALL INSURE THAT CONDUITS REMAINING

WITHIN THE PROJECT AREA ARE SUPPORTED IN ACCORDANCE

WITH THE SPECIFICATIONS. CONDUITS THAT ARE ATTACHED TO

ITEMS BEING REMOVED DURING DEMOLITION SHALL BE

SUPPORTED FROM THE STRUCTURE PRIOR TO REMOVING ITEM.

H. EXISTING PANEL DIRECTORIES SHALL BE UPDATED TO REFLECT

CURRENT CONDITIONS.

I. CONTRACTOR SHALL PATCH, PAINT, AND MATCH FINISH WITH

EXISTING SURFACES TO REMAIN WHERE ELECTRICAL DEVICES

ARE BEING RELOCATED.

J. DASHED SYMBOLS SHALL BE DEMOLISHED UNLESS OTHERWISE

NOTED.

K. CONTRACTOR SHALL REVIEW FLOOR PLANS FOR DEVICES TO

REMAIN PRIOR TO DEMOLITION.

L. WHERE WORK BY THE CONSTRUCTION MANAGER (WALL

REMOVAL, NEW OR RELOCATED WALL OPENINGS, ETC.)

RESULTS IN THE REMOVAL, RELOCATION OR REFEEDINGS OF

ELECTRICAL DEVICES OR LIGHTING FIXTURES, THE ELECTRICAL

CONTRACTOR SHALL DISCONNECT AND RECONNECT AS

REQUIRED ALL ACTIVE DEVICES REMAINING.

M. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR

FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL

RELOCATE ASSOCIATED ELECTRICAL DEVICES, EQUIPMENT AND

OTHER EXISTING SYSTEMS SERVING ITEMS BEING RELOCATED.

N. COORDINATE MECHANICAL AND PLUMBING DEMOLITION WITH

RESPECTIVE CONTRACTORS. REMOVE POWER CONNECTIONS

FROM ALL DEVICES MARKED FOR DEMOLITION ON MECHANICAL

AND PLUMBING DRAWINGS.

O. ALL CIRCUIT BREAKERS SERVING DEMOLITION DEVICES SHALL

BECOME SPARE AND TURN TO THE OFF POSITION. SERVING

PANELBOARD SCHEDULE SHALL BE UPDATED AND READ 'SPARE'.

P. INSTALL A BLANK COVER PLATE WHERE REQUIRED.

EQUIPMENT TO BE DEMOLISHED

EXISTING TO REMAIN

NEW WORK

LINE STYLE TYPES

(EXISTING) UTILITY XFMR

208 / 120 V

3-PHASE, 4 WIRE

EXISTING ELECTRICAL UTILITY METER

EXISTING DUKE

ENERGY PRIMARY

SERVICE

225A

A

(EXISTING)

M

(EXISTING) MDP

208/120V, 3-PHASE, 4 WIRE

800 A, MLO, FUSED

PANELBOARD

200A

B

(EXISTING)

200A

C

(EXISTING)

200A

D

(EXISTING)

CHILLER

(EXISTING)

PROJECT SCOPE OF

WORK

225AT

400AF

200AT

200AF

200AT

200AF

200AT

200AF

400AT

400AF

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 7:

A

M

ED-102

EXISTING BUILDING

-ONE-LINE -

ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

NTS

EXISTING ONE-LINE DIAGRAM

THIS IS AN EXISTING PANEL.

1- LOCKED BREAKER

2- HACR

PANEL NOTES:

Spare 380 VA 100.00% 380 VA

TOTAL DEMAND VA 380 VA DEM LOAD AMPS 1 A

TOTAL VA 380 VA TOTAL AMPS 1 A

PHASE VA 129 VA 117 VA 134 VA

41 -- LIGHTS 20 A 1 13 VA 0 VA 1 20 A SPACE -- 42

39 -- LIGHTS 20 A 1 6 VA 0 VA 1 20 A SPACE -- 40

37 -- LIGHTS 20 A 1 11 VA 9 VA 38

35 -- RECEPT TEL 20 A 1 6 VA 9 VA

2 20 A SITE LIGHTS --

33 -- RECEPT 20 A 1 9 VA 10 VA 1 20 A RECEPT -- 34

31 -- RECEPT 20 A 1 11 VA 10 VA 1 20 A FACP & SECURITY -- 32 1

29 -- LIGHTS 20 A 1 15 VA 12 VA 1 20 A RECEPT -- 30

27 -- LIGHTS 20 A 1 15 VA 6 VA 1 20 A RECEPT -- 28

25 -- LIGHTS 20 A 1 12 VA 6 VA 1 20 A RECEPT -- 26

23 -- LIGHTS 20 A 1 14 VA 9 VA 1 20 A RECEPT -- 24

1 21 -- ST POWER 20 A 1 7 VA 11 VA 1 20 A LIGHTS -- 22

19 -- SHUNT TRIP 20 A 1 1 VA 10 VA 1 20 A LIGHTS -- 20

17 -- RECEPT 20 A 1 6 VA 11 VA 1 20 A LIGHTS -- 18

15 -- SHUNT TRIP 20 A 1 1 VA 10 VA 1 20 A LIGHTS -- 16

13 -- MAU 20 A 1 7 VA 6 VA 1 20 A AMPLIFIER -- 14

11 22 VA 3 VA 1 20 A HOOD LIGHTS -- 12

-- EWH 4.5 KW 30 A 2

22 VA 6 VA 1 20 A HOOD CONTROL -- 10

7 -- EXHAUST FAN 20 A 1 10 VA 16 VA 1 20 A HOT TABLE -- 8

5 5 VA 10 VA 1 20 A ICE MACHINE -- 6 2

3 5 VA 10 VA 1 20 A REFRIGERATOR -- 4

-- DISPOSER 1 HP 15 A 3

5 VA 15 VA 1 25 A FREEZER -- 2

NOTES

CKT

LOAD

CLASS.

ABBR.

CIRCUIT DESCRIPTION

TRIP

AMPS

BRKR.

POLES

A PHASE

LOAD VA

B PHASE

LOAD VA

C PHASE

LOAD VA

BRKR.

POLES

TRIP

AMPS

CIRCUIT DESCRIPTION

LOAD

CLASS.

ABBR.

CKT

NOTES

3 42 SURFACE NEMA 1 120/208 Wye

MAIN LUGS 200A PHASE CIRCUIT MOUNT NEMA VOLTAGE AIC RATING 22kAIC

MAIN BREAKER BUS RATING 200 A

SUPPLIED FROM

PANEL B

S

S

D H

S

S

S

S

A. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE

PRIOR TO CONSTRUCTION TO ASCERTAIN THE EXISTING

CONDITIONS AND LIMITS OF DEMOLITION AND CONSTRUCTION.

B. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT

AND MAINTAIN THE INTEGRITY OF REMAINING DEVICES AND

EQUIPMENT. ANY SUCH CONNECTIONS SHALL BE CONCEALED

UNLESS LOCATED IN UNFINISHED AREAS.

C. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO

REMOVE AND LEGALLY DISPOSE OF DEMOLISHED MATERIALS.

D. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL

SCHEDULED FOR REMOVAL AND SALVAGE ANY ITEMS DEEMED

USEABLE AS SPARE PARTS.

E. EXISTING CONDITIONS INDICATED ON THIS DRAWING ARE TAKEN

FROM FIELD INVESTIGATION. IT IS RECOMMENDED FOR

CONTRACTOR TO VISIT SITE AND VERIFY EXISTING CONDITIONS

PRIOR TO BID.

F. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL

DEVICES, FITTINGS, CONDUITS, ETC. IT IS INTENDED TO PROVIDE

THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING

CONDITIONS WITHIN THE PROJECT AREA.

G. THE CONTRACTOR SHALL INSURE THAT CONDUITS REMAINING

WITHIN THE PROJECT AREA ARE SUPPORTED IN ACCORDANCE

WITH THE SPECIFICATIONS. CONDUITS THAT ARE ATTACHED TO

ITEMS BEING REMOVED DURING DEMOLITION SHALL BE

SUPPORTED FROM THE STRUCTURE PRIOR TO REMOVING ITEM.

H. EXISTING PANEL DIRECTORIES SHALL BE UPDATED TO REFLECT

CURRENT CONDITIONS.

I. CONTRACTOR SHALL PATCH, PAINT, AND MATCH FINISH WITH

EXISTING SURFACES TO REMAIN WHERE ELECTRICAL DEVICES

ARE BEING RELOCATED.

J. DASHED SYMBOLS SHALL BE DEMOLISHED UNLESS OTHERWISE

NOTED.

K. CONTRACTOR SHALL REVIEW FLOOR PLANS FOR DEVICES TO

REMAIN PRIOR TO DEMOLITION.

L. WHERE WORK BY THE CONSTRUCTION MANAGER (WALL

REMOVAL, NEW OR RELOCATED WALL OPENINGS, ETC.)

RESULTS IN THE REMOVAL, RELOCATION OR REFEEDINGS OF

ELECTRICAL DEVICES OR LIGHTING FIXTURES, THE ELECTRICAL

CONTRACTOR SHALL DISCONNECT AND RECONNECT AS

REQUIRED ALL ACTIVE DEVICES REMAINING.

M. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR

FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL

RELOCATE ASSOCIATED ELECTRICAL DEVICES, EQUIPMENT AND

OTHER EXISTING SYSTEMS SERVING ITEMS BEING RELOCATED.

N. COORDINATE MECHANICAL AND PLUMBING DEMOLITION WITH

RESPECTIVE CONTRACTORS. REMOVE POWER CONNECTIONS

FROM ALL DEVICES MARKED FOR DEMOLITION ON MECHANICAL

AND PLUMBING DRAWINGS.

O. ALL CIRCUIT BREAKERS SERVING DEMOLITION DEVICES SHALL

BECOME SPARE AND TURN TO THE OFF POSITION. SERVING

PANELBOARD SCHEDULE SHALL BE UPDATED AND READ 'SPARE'.

P. INSTALL A BLANK COVER PLATE WHERE REQUIRED.

EXISTING

ACTIVITY

ROOM

EXISTING

KITCHEN

EXISTING

STORAGE

EXISTING

STORAGE

EXISTING

STORAGE

EXISTING

CUSTODIAL

KITCHEN HOOD

B-6

B-17

B-17

B-17

B-4 B-2

B-26

B-8

B-26

B-24 B-9,11

DISPOSER

B-1,3,5

ELEC WATER

HEATER

D1

D2

D2

D2

(TYP)

B

B

B

B

B

B

BE

(TYP)

NEW STORAGE

NEW CORRIDOR

NEW STORAGE

FIRE RISER ROOM

EXISTING ELEC.

EXISTING CUSTODIAL

TIE-IN TO EXISTING LIGHTING

CIRCUIT AND SWITCH.

X

X

X

B

BE

BE

B

BE

EXISTING

NEW STORAGE

EXISTING PANEL 'B'

B-31

B-31

B-6

B-17

B-26

EX

EX

NEW STORAGE

FIRE RISER ROOM

NEW CORRIDOR

EXISTING CUSTODIAL

EXISTING ELEC.

(TYPICAL)

D3

D4

D5

D3

D5

D5

EXISTING TO REMAIN.

PROTECT IN PLACE

AND MAINTAIN CIRCUIT

CONTINUITY.

REMOVE EXISTING DISCONNECT SWITCH SERVING ELECTRIC

WATER HEATER AND ASSOCIATED CONDUIT AND

CONDUCTORS BACK TO SOURCE. UPDATE SERVING

PANELBOARD SCHEDULE TO READ "SPARE" AND SWITCH

BREAKER TO OFF POSITION.

EXISTING ELECTRICAL DEVICE SHALL BE DEMOLISHED.

EXISTING ELECTRICAL CIRCUIT SHALL REMAIN AND BE

REUSED TO CONNECT NEW ELECTRICAL DEVICES AS SHOWN

ON RENOVATION PLANS. PULL CIRCUIT BACK TO CLOSEST

JUNCTION BOX AND EXTEND AS REQUIRED FOR NEW

CONNECTIONS.

EXISTING LIGHTING FIXTURES SHALL BE DEMOLISHED.

EXISTING ELECTRICAL CIRCUIT SHALL REMAIN AND BE

REUSED TO CONNECT NEW FIXTURES AS SHOWN ON

RENOVATION PLANS. PULL CIRCUIT BACK TO CLOSEST

JUNCTION BOX AND EXTEND AS REQUIRED FOR NEW

CONNECTIONS.

VERIFY CONDITIONS OF EXISTING SWITCH. IF APPROPRIATE,

LEAVE IN PLACE TO REUSE FOR RENOVATION.

EXISTING SWITCHES SHALL BE DEMOLISHED.

KEY NOTES

(DEMOLITION)

1. PROVIDE 120V POWER CONNECTION FROM EXISTING POWER

CIRCUIT LEFT FROM DEMOLITION OF EXISTING DEVICES. SEE

DEMOLITION PLAN FOR APPROXIMATE LOCATION.

D1

D2

D3

D4

D5

T H

E A

R C

H

IT

E C

T 'S

C O

M M

O N

L A

W C

O P

Y R

IG

H

T A

H E

R P

R O

P E

R T

Y R

IG

H

T S

A R

E H

E R

E B

Y R

E S

E R

V

H E

I D

E A

S

D E

S

IG

N S

P L A

N S

D

R A

W

IN

G S

A

E C

IF

IC

A T

IO

N

S P

R O

D U

C E

D B

Y T

H E

A R

C H

IT

E

C T

T H

E S E

I D

E A

S

D E

S

IG

N S

P L A

N S

D R

A W

IN

G

S

A

E C

IF

IC

A T

IO

N

S S

H A

L L N

O T

B E

R E

P R

O D

U C

E D

N V

E Y

E D

I N

A N

Y M

A N

N E

R N

O R

A S

S

IG

N E

D

Y T

H

IR

D P

A R

T Y

W

IT

H O

U T

F

IR

S T

O B

T A

IN

IN

G T

P R

E S S W

R

IT

T E

N P

E R

M

IS

S

IO

N O

F T

C H

IT

E

C T

C

O N

S E

N T

I S

H E

R E

B Y

G R

A N

T E

D

V E

R N

M E

N T

A L A

G E

N C

IE

S

T O

R E

P R

O D

U C

E T

N S T

R U

C T

IO

N

D R

A W

IN

G

S I

N C

O M

P L

IA

N C

E W

E S

T A

T E

S T

A T

U T

E S

T O

T H

E B

E S

T O

F T

C H

IT

E

C T

'S O

F E

N G

IN

E

E R

'S K

N O

W L E

D G

E

T

A

N S

A N

D S

P E

C

IF

IC

A

T

IO

N S C

O M

P L Y

W

IT

H T

P L

IC

A B

L E

M

IN

IM

U

M B

U

IL

D

IN

G C

O D

E S A

N D

T

P L

IC

A B

L E

F

IR

E S

A F

E T

Y S

T A

N D

A R

D S

T E

R M

IN

E

D B

Y T

H E

L O

C A

L A

U T

H O

R

IT

Y

C O

R D

A N

C E

W

IT

H C

H A

P T

E R

S

A N

D

E F

L O

R

ID

A S

T A

T U

T E

S

W J

A rc hi te ct s

A R

(7

2-w .w ja rc

.c om

W an ne m ac he r

Je ns en A rc hi te ct s, In c.

Project number

N . W es ts ho re

B te

T am pa

, F lo rid a

T el : 8

.8

.4

T el

: 8

.8

.9 w w w

.V ol tA irI nc .c om C

O A

P ro je ct

.2

GENERAL NOTES

KEY NOTES

KEY PLAN

A ut od es k D oc s:

//2

P al m

H ar bo r

R ec re at io n

C en te r/

_P al m H ar bo r R ec C nt r_

M E

P _v

.r vt

9/

/2

:0 7:

A

M

ED-101

EXISTING BUILDING -

FLOOR PLAN -

ELECTRICAL

P A

L M

H A

R B

O R

P A

R K

S A

N D

R E

C R

E A

T

IO

N

P

IN

E

LL

A S

C O

U N

T Y

T H

S T

R E

E T

, P A

L M

H A

R B

O R

F L

PERMIT SET 9-15-25

0' 4' 12' 24' 42'-8"

SCALE: 3/32" = 1'-0"

N

3/32" = 1'-0"

EXISTING BUILDING - FLOOR PLAN - ELECTRICAL DEMOLITION

3/32" = 1'-0"

EXISTING BUILDING - RCP - LIGHTING - RENOVATION

3/32" = 1'-0"

EXISTING BUILDING - FLOOR PLAN - POWER - RENOVATION

3/32" = 1'-0"

EXISTING BUILDING - RCP - LIGHTING - DEMOLITION

J

J

J

P

P

P

MMMM

J

J

J

J

J

J

J

J

J

J

J

J J

J J

D H

J

A. ELECTRICAL CONTRACTOR SHALL REFER TO THE ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL DESIGN STANDARDS. THE

ELECTRICAL SPECIFICATIONS ARE A BINDING PART OF THE

CONSTRUCTION DOCUMENTS.

B. ALL WIRE SHALL BE COPPER STRANDED FOR #8 AND LARGER.

C. ALL COVER PLATES SHALL BE PER SPECIFICATIONS.

D. REFER TO ELECTRICAL MECHANICAL EQUIPMENT SCHEDULES

FOR ELECTRICAL INFORMATION PERTAINING TO MECHANICAL,

PLUMBING, FIRE PROTECTION AND / OR VERTICAL

TRANSPORTATION EQUIPMENT.

E. COORDINATE ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT

WITH MANUFACTURER PRIOR TO ROUGH-IN AND

INSTALLATION. ADJUST DEVICE TYPES, SIZES, LOCATIONS

AND BRANCH CIRCUITRY (AS REQUIRED).

F. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL FIRE

PROTECTION EQUIPMENT WITH THE DIVISION 21 CONTRACTOR

PRIOR TO ROUGH-IN AND INSTALLATION.

G. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL

PLUMBING EQUIPMENT WITH THE DIVISION 22 CONTRACTOR

PRIOR TO ROUGH-IN AND INSTALLATION.

H. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL

MECHANICAL EQUIPMENT WITH THE DIVISION 23 CONTRACTOR

PRIOR TO ROUGH-IN AND INSTALLATION.

I. COORDINATE LOCATIONS AND REQUIREMENTS OF ALL

TECHNOLOGY EQUIPMENT WITH THE DIVISION 27

CONTRACTOR PRIOR TO ROUGH-IN AND INSTALLATION.

J. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL

DEVICES WITH ARCHITECTURAL ELEVATIONS, CASEWORK,

FIELD CONDITIONS AND OTHER TRADES, ADJUST (AS

REQUIRED).

K. COORDINATE LOCATIONS OF ALL SMOKE AND / OR FIRE /

SMOKE DAMPERS WITH…