P09-Final Drawings Part-2 Pages 37.pdf
PDF 4 MB Posted
- Attached to
- Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler Federal contract opportunity
- Solicitation number
- 36C25526R0159
About this file
This is a comprehensive 100% Construction Documents package for the installation of a dedicated pharmacy air handler system at Harry S. Truman VAMC in Columbia, Missouri (Project 589A4-25-102). The project scope encompasses complete mechanical, plumbing, fire protection, and electrical systems design and demolition work across multiple building levels (basement, Levels 1-3, interstitial space, and penthouse roof).
The mechanical scope includes installation of three new variable air volume (VAV) air handling units (ACA-AHU-10, ACA-AHU-11, and ACA-AHU-12) ranging from 2,300 to 4,300 CFM capacity, along with associated ductwork, terminal units, humidifiers, and control systems. The project requires three hydronic pumps (HHWP-1 and HHWP-2 for heating hot water, plus chilled water circulation), electric unit heaters, and dedicated exhaust/relief fans. Plumbing work includes domestic water distribution (DCW), storm and sanitary drainage systems, and roof drain installations with overflow provisions. Fire protection involves full sprinkler system installation with 2' x 2' ceiling tile integration and proper alignment with architectural features. Electrical work encompasses new power distributions, panelboards (DP3-D10-480VQ, PP3-D10-120VN, PP3-D10-120VC2), lighting fixtures (LED wraparound and vaportight fixtures), and integrated building controls using trim-and-respond static pressure logic. All systems incorporate building automation controls with occupancy sensors, humidity monitoring, and emergency shutdown capabilities. The project document includes detailed specifications, equipment schedules, piping and ductwork diagrams, sequence of operations for three AHU configurations, and extensive mechanical controls documentation. Construction is scheduled to occur after hours and on weekends with mandatory coordination at least 14 days in advance with the VA Contracting Officer's Representative.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 07 81 00 Applied Fireproofing.pdf | ||
| 36C25526R0159 0004.pdf | ||
| Final Drawings Part-2.pdf | ||
| PRE-BID SIGN IN ROSTER.pdf | ||
| Final Drawings Part-3.pdf | ||
| Final Drawings Part-1.pdf | ||
| 36C25526R0159 0003.docx | DOCX document | |
| Phasing info.pdf | ||
| 01 32 16-15 Project Schedules RX.pdf | ||
| 01 91 00 General Commissioning Requirements RX.pdf | ||
| 07_8100-001_Fireproofing_Mfr_Literature.pdf | ||
| 589a4-25-102_Addendum 02_260828.pdf | ||
| 01 00 00 General Requirements RX.pdf | ||
| 36C25526R0159 0002.docx | DOCX document | |
| finish schedule from specs.pdf | ||
| 01 00 10 - MEDICAL CENTER REQUIREMENTS RX.pdf | ||
| Finish schedule from drawings.pdf | ||
| 01 33 23- Shop Drawings Product DAta and Samples.pdf | ||
| 36C25526R0159 0001.docx | DOCX document | |
| P09-Final Drawings Part-1 Pages 37.pdf | ||
| S02-Final Specifications 1068 pages.pdf | ||
| 36C25526R0159.docx | DOCX document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2' - 0"
1' - 0"
DETAIL NOTES:
1. INSTALL SPRINKLERS IN 2' X 2' CEILING TILES AS INDICATED
ABOVE.
2. ALIGN SPRINKLERS AMONGST ADJACENT CEILING TILES WHERE
IN THE SAME FIELD OF VIEW INCLUDING THROUGH OPEN DOORS
AND GLASS PARTITIONS.
3. WHERE SPRINKLERS ARE INSTALLED IN CEILINGS OTHER THAN
2' X 2' CEILING TILES, ALIGN WITH LIGHTS, DIFFUSERS, AND
ARCHITECTURAL FEATURES.
RATEDENGINEERING.COM
MO LIC #2026005125
RATEDENGINEERING.COM
MO LIC #2026005125
RATEDENGINEERING.COM
MO LIC #2026005125
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/2
/2
:5 :1
A
M
FIRE SUPPRESSION DETAILS
JCP 38 OF 73DBN
100% CONSTRUCTION DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
05/28/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
FX501
NTS
FIRE SPRINKLER CEILING TILE INSTALLATION DETAIL1
No. REVISION DESCRIPTION DATE
MA
MV
CO
VEAI
FOV
FOR
FOS
LPG
NPW
NO
O
N
G
MPG
CA
CD
ACD
VAV
AW
ST
OST
GW
SS
SCW
140°ORAL EVACUATION
LABORATORY VACUUM
LABORATORY AIR
INDUSTRIAL AIR
LA
LV
OA
IA
FILTERED COLD WATERFCW
FUEL OIL DISCHARGEFOD
SQUARE FLOOR DRAIN (FD)
ROOF DRAIN (RD), SIZE & TYPESQUARE FLOOR SINK (FS)
CONDENSATE DRAIN
NATURAL GAS
NITROUS OXIDE
LIQUIFIED PETROLEUM GAS
COMPRESSED AIR
NITROGEN
MEDICAL AIR
OXYGEN
DOMESTIC HOT WATER RECIRC.
STORM DRAIN
ACID WASTE
DOMESTIC COLD WATER
DOMESTIC HOT WATER
140° DOMESTIC HOT WATER (140°)
SANITARY SEWER
GREASE WASTE
SOFTENED COLD WATER (SCW)
ACID VENT VENT
WALL CLEANOUT (WCO)
FLOOR CLEANOUT (FCO)
OVERFLOW STORM DRAIN
NON POTABLE WATER (NPW)
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
AUXILIARY CONDENSATE DRAIN
CARBON DIOXIDE
MEDICAL VACUUM
MEDICAL VACUUM EXHAUSTMEDICAL AIR INTAKE
MEDIUM PRESSURE NATURAL GAS
END OF LINE CLEANOUT
PLUMBING EQUIPMENT DESIGNATIONXX-1
A. ALL PIPING SHALL BE COORDINATED WITH CIVIL UTILITY PIPING, FIRE PROTECTION,
DUCTWORK, MECHANICAL PIPING, LIGHTING, STRUCTURAL AND ARCHITECTURAL SYSTEMS.
B. PIPE CLEANOUTS SHALL BE LINE SIZE (6" MAX.). LOCATE 100' APART MAXIMUM FOR SIZES UP
THROUGH 6".
C. PLUMBING VENTS THROUGH ROOF (VTR) SHALL BE 3" MINIMUM. SMALLER VTR'S INDICATED
SHALL INCREASE TO 3" PIPE, 12" BELOW ROOF.
D. ACCESS PANELS SHALL BE PROVIDED FOR ALL WATER HAMMER ARRESTORS LOCATED IN
WALLS TO ACCESS EQUIPMENT. PANEL SHALL BE AS LARGE AS PRACTICAL FOR THE
FUNCTION THEY ARE INTENDED.
E. DO NOT SCALE DRAWINGS, SEE ARCHITECTURAL FLOOR PLAN FOR DIMENSIONS.
F. ALL PLUMBING WORK SHALL COMPLY WITH THE 2009 INTERNATIONAL PLUMBING CODE.
G. PIPE ROUTING IS SCHEMATIC AS SHOWN AND IS NOT INTENDED TO INDICATE EXACT
ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSET AND FITTINGS REQUIRED
FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES.
H. CONCEAL PIPING ABOVE CEILING AND WITHIN WALLS OR CHASES, EXCEPT IN MECHANICAL
SPACES OR WHEN OTHERWISE NOTED.
DHWR
DHW
DCW
ABBREVIATIONS
PLUMBING PIPING TYPES
A/E ARCHITECT / ENGINEER
B
BFP REDUCED PRESSURE BACKFLOW
PREVENTER
BHP BRAKE HORSEPOWER
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
DA
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCW FILTERED COLD WATER
E
ET EXPANSION TANK
FD FLOOR DRAIN
FM FLOW METER
FOP FUEL OIL PUMP
FOV FUEL OIL VENT
G
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GT GREASE TRAP
K
J
J INTENTIONALLY LEFT BLANK
ID INSIDE DIAMETER
H
H&CW HOT & COLD WATER
HB HOSE BIBB
HD HUB DRAIN
HP HORSEPOWER
HWP HOT WATER PUMP
I
L
L/s LITERS PER SECOND (OR LITERS/SECOND)
LA LABORATORY AIR
LBS/HR POUNDS PER HOUR
NTS NOT TO SCALE
N
NC NORMALLY CLOSED
NG NATURAL GAS
M
M METER, SI UNIT
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
P
PP PLUMBING PUMP
PA PASCAL
PD PRESSURE DROP
PG PRESSURE GAGE
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
O
O OXYGEN
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
Q
Q INTENTIONALLY LEFT BLANK
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE, TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TSTAT THERMOSTAT
TWR TEMPERED WATER RETURN
SAN SANITARY SEWER
SCFM STANDARD CUBIC FEET PER MINUTE
SQ FT SQUARE FOOT (FEET)
SS SANITARY SEWER, STAINLESS STEEL
ST STORM SEWER, STORAGE TANK
R
RD ROOF DRAIN
RO REVERSE OSMOSIS
T
X INTENTIONALLY LEFT BLANK
W
W WASTE
WC WATER CLOSET
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VENT
VP VACUUM PUMP
VSD VARIABLE SPEED DRIVE
X
V
DEMOLITION GENERAL NOTES:
PL-100
DETAIL NUMBER
SHEET NUMBER
SHEET NUMBER
SECTION NUMBER
1 OWNER FURNISHED, CONTRACTOR
INSTALLED EQUIPMENT DESIGNATION
EXISTING TO BE DEMOLISHED
EXISTING TO REMAIN
NEW PIPE
CONNECT NEW TO EXISTING
LIMIT OF DEMOLITION
GENERAL PIPING SYMBOLS
GENERAL ANNOTATIONS
AV
STRAINER
FLOAT & THERMOSTATIC
STEAM TRAP
INVERTED BUCKET
STEAM TRAP
FLANGE CONNECTION PIPE DROP
PIPE RISER
TEE DOWN
TEE UP UNION
PRESSURE REDUCING
VALVE
BALL VALVE
ANGLE GLOBE VALVE SAFETY RELIEF VALVE
GLOBE VALVE
MANUAL OR
AUTOMATIC AIR VENT
PRESSURE AND
TEMPERATURE TEST PLUG
FLOW METER
PLUMBING PIPING SYMBOLS
CAP
REDUCER (ECCENTRIC)
Name
XX-XX
ANCHOR
TEE
DIRECTION OF FLOW
S
DIRECTION OF PIPE
PITCH (DOWN)
FM
MV
PLUMBING VALVE SYMBOLS
ROOM TAG
PUMP
REDUCER (CONCENTRIC)
BUTTERFLY VALVE
CHECK VALVE
THERMOMETER
PRESSURE GAUGE
YCO YARD CLEANOUT
Y
Z INTENTIONALLY LEFT BLANK
Z
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AG AIR GAP
AFG ABOVE FINISHED GRADE
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER
ASD ADJUSTABLE SPEED DRIVES
ASD AUTOMATIC SPRINKLER DRAIN
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING
ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
AV ACID VENT
AW ACID WASTE
BSP BLACK STEEL PIPE
C
C CENTIGRADE (CELSIUS)
CFM CUBIC FEET PER MINUTE
CV CONTROL VALVE
CO CLEANOUT
CA COMPRESSED AIR
CGA COMPRESSED GAS ASSOCIATION
CI CAST IRON
CS CLINICAL SINK
DCW DOMESTIC COLD WATER
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DI DEIONIZED WATER
DW DISHWASHER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DN DOWN
DS DOWNSPOUT
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWR DRINKING WATER RETURN
DWS DRINKING WATER SUPPLY
DWV DRAIN WASTE VENT
EX. EXISTING
EWS/SH EYE WASH/ DRENCH SHOWER
EWS EYE WASH STATION
EWH ELECTRIC WATER HEATER
ETR EXISTING TO REMAIN
ESH EMERGENCY SHOWER
ESC ESCUTCHEON
EPACT ENERGY POLICY ACT
EMCS ENERGY MONOSERRAT AND
CENTRAL SYSTEM
EPA ENVIRONMENTAL PROTECTION AGENCY
EL ELEVATION
F
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
GAL GALLONS
GCO GRADE CLEANOUTS
GPS GAS REGULATOR STATION
GVTR GAS VENT THROUGH ROOF
GWH GAS FIRED UNIT HEATER
HX HEAT EXCHANGER
HS HAND SINK
HST HOT WATER STORAGE TANK (DOMESTIC)
HWB HOT WATER BOILER
HWCP HOT WATER CIRCULATING PUMP
HYD HYDRANT
IE INVERT ELEVATION
ICW INDUSTRIAL COLD WATER
IHW INDUSTRIAL HOT WATER
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IRW IRRIGATION WATER
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
IWR INDUSTRIAL WATER RETURN
IWS INDUSTRIAL WATER SUPPLY
kW KILOWATT kWh KILOWATT HOUR
LAV LAVATORY
LCW LABORATORY COLD WATER
LHW LABORATORY HOT WATER
LV LABORATORY VACUUM
LNG LIQUID NATURAL GAS
LOX LIQUID OXYGEN
LW LOW WATER
MED MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MH MANHOLE
MOU MEMORANDUM OF UNDERSTANDING
MSB MOP SERVICE BASIN
MV MEDICAL VACUUM
N2 NITROGEN
N2O NITROUS OXIDE
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
OC ON CENTER
OR OPERATING ROOM
OVFL OVERFLOW
PDI PLUMBING AND DRAINAGE INSTITUTE
PO POTABLE WATER
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RP RECIRCULATION PUMP
RWL RAIN WATER LEADER
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL
ASSOCIATION
SCW SOFTENED COLD WATER
SDMH STORM DRAIN MANHOLE
SMH SANITARY MANHOLE
SP SUMP PUMP
SPR SPRINKLER LINE
SW STORM WATER
TEMP TEMPERATURE
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TWS TEMPERED WATER SUPPLY
TYP TYPICAL
U
U INTENTIONALLY LEFT BLANK
VS VENT STACK
VTR VENT THROUGH ROOF
VAC VACUUM
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
WCO WALL CLEANOUT
WH WALL HYDRANT, WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
YH YARD HYDRANT
BACKFLOW PREVENTER (BFP, RPBP)
NONFREEZE WALL
HYDRANT
PLUMBING CLEANOUT AND DRAIN SYMBOLS
MODULATING CONTROL
VALVE
THERMOSTATIC MIXING
VALVE
M MOTOR OPERATED VALVE
I. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
J. PROVIDE TRAP PROTECTION FOR ALL FLOOR DRAINS.
K. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS.
L. COORDINATE PIPING WITH ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION. ROUTE PIPING
TO AVOID ELECTRICAL EQUIPMENT AND CLEARANCE AREAS.
M. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR THE
PLUMBING EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO
ENSURE COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR PROPER SIZE
ELECTRICAL MATERIAL AND EQUIPMENT AT NO ADDITIONAL COST.
N. PROVIDE SHOCK ARRESTORS PER STANDARD PDI-WH-201.
O. SEAL ALL FIRE AND SMOKE BARRIER PENETRATIONS IN ACCORDANCE WITH THE APPLICABLE
BUILDING CODE, SPECIFICATIONS, AND DETAILS. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATIONS AND RATINGS OF FIRE AND SMOKE WALLS, BARRIERS, AND PARTITIONS.
ROUND FLOOR DRAIN (FD)
GENERAL NOTES:
A. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY GENERAL CONTRACTOR
REGARDING CONFLICTS BEFORE PROCEEDING WITH WORK.
B. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION.
RELOCATE, REMOVE AND ADJUST MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO
COORDINATE WITH NEW WORK.
C. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING
CONDITIONS.
D. COORDINATE DEMOLITION WITH GENERAL CONTRACTOR. NOTIFY GENERAL CONTRACTOR
AND OWNER IF A SHUDTOWN OF UTILITIES IS REQUIRED.
E. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION.
F. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE
WORK.
G. SAWCUT CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE
WITH NEW PLUMBING BEFORE CUTTING ANY FLOOR. CONTRACTOR TO X-RAY FLOORS FOR
ALL STRUCTURAL FLOORS.
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
RPBP REDUCED PRESSURE BACKFLOW PREVENTER
MEDICAL GAS SYMBOLS
O WALL OUTLET - OXYGEN
MA WALL OUTLET - MEDICAL AIR
MV WALL OUTLET - MEDICAL VACUUM
N WALL OUTLET - NITROGEN
NO WALL OUTLET - NITROUS OXIDE
CO WALL OUTLET - CARBON DIOXIDE
LA WALL OUTLET - LABORATORY AIR
LV WALL OUTLET - LABORATORY VACUUM
AREA ALARM PANEL (AAP-X)
MASTER ALARM PANEL (MAP-X)
ZONE VALVE BOX (ZVB-X)
AAP-X
MAP-X
ZVB-X
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/2
/2
:1 :1
P
M
PLUMBING LEGEND
BLB 39 OF 73JGD
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
05/28/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
P-000
SPUR #: 2517No. REVISION DESCRIPTION DATE
E001
E009
E002I E002J E002K E001E
UP
UP
F003*
JAN.
VEST.
STAIR
#11F011 F036
F009A F008 F009
E010
E008
E007
E006
CBE2
F037
E001K
E001H
E001L
E002F
E002C
E001F
E001J E001BE001D
E001A
OFFICETEAM ROOM
NARCOTIC
VAULT
E001C
OFFICE
STERILE PROCESSING AREA
NON-HAZARD IV PREP
IV STORAGE ROOM
STORAGE
CORRIDOR
HAZARDOUS
DRUG STORAGE
HAZARDOUS
IV PREP
OFFICE
F361 F359
F364 F360
F363 F362
F372 F371
F391
F392
F393
F390
F358
F352 F353 F354 F355 F356
F357
F366 F367 F368
F370
F369
F365
UP
8 9
E
D
10 11
C
E.1
D.7
B
11.5
1-SH3
1-SH2
1-SH4
1-SH1
1 1/2" DHW
2 1/2" DCW
3/4" DHWR
1 1/2" DHW
2 1/2" DCW
3/4" DHWR
3/4" DCW
3/4" DHW
1/2" DHWR
1-SH5
D1
D1
D1
D1
D1
H
7 8 9
G
F
3-SH2
3-SH3
3-SH1
D3
D1
D11/2" DCW
1/2" DCW
1/2" DCW
1 1/4" DHW
2" DCW
1 1/4" DHW
2" DCW
3/4" DCW
3/4" DHW
1/2" DCW
KEY PLAN
N
SCOPE AREA
INTERSTITIAL SPACE
8 9
E
D
10 11
C
E.1
D.7
B
11.5 1312
LEVEL 2 ROOFD2
RD-1
OFD-1
D2
4" VTR
8" SD DN.
4" V DN.
4" SD DN.
8" SS
4" V
4" SS
4" S
S
3" S
S
8" S
S th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/2
/2
:1 :1
P
M
DEMOLITION PLUMBING PLAN
BLB 40 OF 73JGD
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
05/28/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PD-101
SPUR #: 2517No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
PLUMBING DEMOLITION PLAN - BASEMENT DOMESTIC WATER1
N
1/8" = 1'-0"
PLUMBING DEMOLITION PLAN - LEVEL 3 DOMESTIC WATER3
N
1/8" = 1'-0"
PLUMBING DEMOLITION PLAN - INTERSTITIAL STORM DRAIN2
DEMOLITION KEYNOTES
D1 DEMOLISH DCW SERVING HUMIDIFIER BACK TO DEMARCATION TO INCLUDE BRANCH TEE AND ALL
HANGERS. REPAIR MAIN AND INSULATE.
D2 DEMOLISH ROOF AND OVERFLOW DRAIN.
D3 DEMOLISH DCW SERVING HUMIDIFIER AND DRAIN COOLER BACK TO DEMARCATION TO INCLUDE
BRANCH TEE AND ALL HANGERS. REPAIR MAIN AND INSULATE.
8 9
E
D
10 11
C
E.1
D.7
B
11.5 1312
6" S
T
6" O
S T
LEVEL 2 ROOF
PENTHOUSE
INTERSTITIAL
INTERSTITIAL
8" SS
4" V
4" SS
8" S
S
4" S
S
3" S
S
4" SS
4" V
2" V
8 9
D
10 11
C
11.5
PENTHOUSE
ACA-AHU-12
ACA-AHU-11
FD-E
FD-E
8" SS
4" SS
4" V
4" SS
4" SS
4" SS
2" V
4" SS 3" SS8" SS
8 9
D
10 11
C
11.5
RD-1
ORD-1 2
PENTHOUSE ROOF
4" VTR
2" VTR
KEY PLAN
N
SCOPE AREA
UNDERDECK CLAMP
NOTE:
CAST INTO CONCRETE ROOF. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
INSULATE ROOF DRAIN SUMP AND PIPE PER SPECIFICATIONS. LOCATE DRAINS WHERE
SHOWN ON ARCHITECTURAL PLANS; VERIFY WITH STRUCTURAL PLANS FOR ROOF
LOW POINTS. COORDINATE WITH STRUCTURAL DRAWINGS REGARDING PROVISION
FOR SUPPLEMENTARY STEEL FRAMING AROUND ROOF OPENING.
LONG RADIUS ELBOWS
PROVIDE PIPE HANGER AS
CLOSE TO JOINT AS POSSIBLE
TO TAKE WEIGHT OFF ROOF
DRAINS.
INSULATED ROOF
STRUCTURE
GRAVEL STOP AND
MEMBRANE CLAMP TO
SECURE FLASHING
OVERFLOW (SECONDARY)
DRAIN. REFER TO PLANS
FOR OUTLET SIZE.
DO NOT OVERLAP
SUMP RECEIVERS
SLOPE HORIZONTAL PIPE AS
INDICATED ON FLOOR PLAN
OR IN SPECIFICATIONS
PRIMARY ROOF DRAIN. REFER
TO PLANS FOR OUTLET SIZE
WEIR - APPROXIMATELY
2" HIGHER THAN
PRIMARY DRAIN
UNDERDECK CLAMP
SUMP RECEIVER
GRAVEL STOP AND MEMBRANE
CLAMP TO SECURE FLASHING
EXTENSION SLEEVE, WITH
HEIGHT AS REQUIRED TO
ACCOMMODATE ROOF
INSULATION THICKNESS
PROVIDE LONG SWEEP ELBOW
AT START OF RUN.
PROVIDE WYE COMBO FITTING
WHERE MORE THAN ONE ROOF
DRAIN IS CONNECTED TO A
SINGLE HORIZONTAL PIPE
ROOF DRAIN OR OVERFLOW
ROOF DRAIN. REFER TO PLANS
FOR OUTLET SIZE.
INSULATED ROOF STRUCTURE
PROVIDE PIPE HANGER AS
CLOSE TO JOINT AS POSSIBLE
TO TAKE WEIGHT OFF ROOF
DRAIN.
HOT PIPECOLD PIPE
REFER TO SPECIFICATIONS FOR INSULATION TYPES, INSULATION
THICKNESSES, HANGER TYPES, HANGER ROD CONNECTIONS TO SRUCTURE
AND HANGER SPACING.
CUT INSULATION TO FIT AROUND
HANGER. SEAL EXPOSED
INSULATION ENDS WITH JOINT
SEALANT.
PROVIDE A SECTION OF HIGH
DENSITY INSULATION OR
STYROFOAM BILLETS AT EACH
HANGER OF COLD INSULATED PIPE.
THREADED STEEL ROD WITH
NUT AND WASHER BOTH
SIDES (TYP.).
CLEVIS HANGER, SHOWN FOR CLARITY.
SIZE HANGER FOR COLD PIPE OUTSIDE
DIAMETER PLUS INSULATION THICKNESS.
DO NOT PENETRATE INSULATION WITHE
HANGER.
CLEVIS HANGER, SHOWN FOR
CLARITY. SIZE HANGER FOR HOT
PIPE OUTSIDE DIAMETER.
SECURE PIPE HANGER TO
STRUCTURE (TYP.)
PROVIDE SHORT INSULATION SHIELD
FOR LAPPING INSULATION JACKET
OVER HIGH DENSITY INSULATION OR
STYROFOAM BILLETS. MAINTAIN
VAPOR BARRIER.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/2
/2
:1 :1
P
M
WASTE, STORM, VENT PLUMBING PLAN
BLB 41 OF 73JGD
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
05/28/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PL-101
SPUR #: 2517No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
PLUMBING PLAN - INTERSTITIAL LEVEL - WASTE, STORM, VENT1
N
1/8" = 1'-0"
PLUMBING PLAN - LEVEL 3 - WASTE, STORM, VENT2
N
1/8" = 1'-0"
PLUMBING PLAN - LEVEL 3 ROOF - WASTE, STORM, VENT3
KEYNOTES
1 CONNECT TO EXISTING 6" STORM SEWER AND ROUTE AS SHOWN ON PLANS.
2 INSTALL ROOF DRAIN AS SHOWN ON PLANS. COORDINATE ALL WORK WITH ROOFING CONTRACTOR.
4 6" STORM SEWER DOWN TO FLOOR BELOW.
5 6" STORM SEWER DOWN FROM FLOOR ABOVE. ROUTE PIPING TIGHT TO STRUCTURE.
6 CONNECT TO EXISTING 4" VENT THRU ROOF AND ROUTE AS SHOW ON PLANS.
7 ROUTE 4" VENT UP THRU ROOF OF PENTHOUSE.
8 ROUTE 2" VENT UP THRU ROOF OF PENTHOUSE.
9 CONNECT 3" DRAIN TO EXISTING 8" SANITARY RISER.
10 4" VENT UP AND DOWN.
11 2" VENT UP AND DOWN.
12 3" DRAIN WITH TRAP UP TO FD-D IN PENTHOUSE.
NTS
ROOF AND OVERFLOW DRAIN DETAIL5 NTS
ROOF DRAIN INSTALLATION DETAIL4NTS
PIPE HANGER DETAIL6
FLOOR DRAINS / CLEANOUT SCHEDULE (FD / CO)
MARK LOCATION
BASIS OF DESIGN OUTLET
SIZE DESCRIPTIONMANUFACTURER MODEL
FD-E Jay R. Smith 2410 Series 4" Floor Drain
RD-1 PENTHOUSE ROOF JAY R. SMITH 1800 6" CAST IRON BODY COMBINED FLASHING CLAMP AND GRAVEL STOP FOR ROOF DRAIN AND 3-1/2" HIGH INTERNAL WATER DAM STANDPIPE FOR OVERFLOW DRAIN.
C B
E
E003
C O
R R
DN
DN
ELEV
#11
F002A
F002
E004
B042 B048 B051B039AB039
F035A
F035
F030 F031 F032 F033
F030A
CBE4
CORR.
KEY PLAN
N
SCOPE AREA
3 4 5 62
C
B
1-HUM-10
ACA-AHU-1ACA-AHU-2ACA-AHU-3
ACA-AHU-6
ACA-AHU-4
1" D
H W
R
1/ 2"
D H
W
4" D
C W
3/4" DCW
BFP
D
10 11
C
11.5
MECHANICAL PENTHOUSE
8 9
D
10 11
C
B
11.5 1312
BFP
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/2
/2
:1 :1
P
M
DOMESTIC WATER PLUMBING PLAN
BLB 42 OF 73JGD
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
05/28/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PP-101
SPUR #: 2517
KEYNOTES
13 CONNECT 3/4" DCW TO EXISTING 4" DCW IN MECHANICAL ROOM. ROUTE DCW TO 1-HUM-10. HUMIDIFIER BY DIV. 23. INSTALL BACKFLOW PREVENTER AND ISOLATION VALVES UPSTREAM AND DOWN STREAM OF BFP.
14 CONNECT 1" DCW TO EXISTING 2" DCW IN INTERSTITIAL SPACE. ROUTE UP TO MECHANICAL PENTHOUSE TO HUMIDIFIERS 1-HUM-11 & 1-HUM-12. HUMIDIFIERS BY DIV. 23. INSTALL BACKFLOW PREVENTER AND ISOLATION VALVES UPSTREAM AND DOWNSTREAM OF BFP. INSTALL SHUTOFF VALVE AT EACH HUMIDIFIER.
15 1" DCW DOWN TO INTERSTITIAL BELOW. ROUTE 3/4" DCW TO EACH HUMIDIFIER AND INSTALL SHUTOFF
VALVE.
No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
PLUMBING PLAN - BASEMENT - DOMESTIC WATER1
N
1/8" = 1'-0"
PLUMBING PLAN - LEVEL 3 - DOMESTIC WATER3
N
1/8" = 1'-0"
PLUMBING PLAN - INTERSTITIAL - DOMESTIC WATER2
LEVEL 2 ROOF
PENTHOUSE
INTERSTITIAL
ABBREVIATIONS
HVAC PIPING TYPES
GENERAL DUCT SYMBOLS
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR COOLED CONDENSER
ACU AIR CONDITIONING UNIT
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERAGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C CENTIGRADE (CELSIUS)
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
A
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
E
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
D
DB DECIBELS
Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
FSD COMBINATION FIRE / SMOKE DAMPER
G
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
J
J INTENTIONALLY LEFT BLANK
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
H
HU HUMIDIFIER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPC HIGH PRESSURE STEAM CONDENSATE RETURN
HPS HIGH PRESSURE STEAM (61-300 PSIG)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HC HOT WATER HEATING COIL
HHP HEATING HOT WATER PUMP
HHR HEATING HOT WATER RETURN
HHS HEATING HOT WATER SUPPLY
HHUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
L
L LITER
L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUID PROPANE GAS
LPC LOW PRESSURE STEAM CONDENSATE RETURN
CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM (0-15 PSIG)
CLPS LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
M
M METER, SI UNIT
M/s METERS PER SECOND
(OR METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPC MEDIUM PRESSURE STEAM CONDENSATE
RETURN
MPS MEDIUM PRESSURE STEAM (16-60 PSIG)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
P
P PUMP
PA PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
O
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OSD ORGANIC SOIL FILTER
Q
Q INTENTIONALLY LEFT BLANK
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
DSD DUCT SMOKE DETECTOR
SD SMOKE DAMPER
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
R
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
RF RETURN FAN
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
T
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
U
X INTENTIONALLY LEFT BLANK
W
W WATTS
WAG WASTE ANESTHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WF WATER FILTER
WFM WATER FLOWMETER
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
X
V
GENERAL NOTES:
A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE
SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.
B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT
DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS
ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS
COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND
NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR
INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.
D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION
"PAINTING".
E. COORDINATE FAN COIL (FCU) AND TERMINAL UNIT (TU/VAV/CV) REHEAT COIL RIGHT OR
LEFT HAND COIL CONNECTIONS WITH PIPING PLANS.
F. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT SHALL BE SIZED BY
THE GAS-FIRED EQUIPMENT MANUFACTURER BASED ON THE SPECIFIC PIPE ROUTING AND
ELEVATIONS FOR THIS PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND
LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND COMBUSTION AIR PIPING
MATERIALS.
G. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT
TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.
H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN
50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)
THROUGHOUT MECHANICAL EQUIPMENT ROOMS. DO THE SAME FOR SUPPORTS OF STEAM
MAINS WITHIN 50' OF BOILER OR PRESSURE REDUCING VALVES.
I. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,
STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
J. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,
SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.
K. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING
INSULATION IS APPLIED.
L. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE
LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS
RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.
M. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED
DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND
COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.
CWR
CWS
CD
LPC
LPS
MPC
MPS
HPC
HPS
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
HIGH PRESSURE STEAM CONDENSATE
HIGH PRESSURE STEAM SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE
MEDIUM PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM CONDENSATE
LOW PRESSURE STEAM SUPPLY
VACUUM RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
VR
CONTINUOUS BLOWDOWN
CHEMICAL FEED
BOILER BLOWOFF BO
CF
CBD
FWPD
FWPS
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE CENTERLINE OF ALL PRESSURE
PIPING AND TO THE INVERT OF ALL GRAVITY PIPING.
C. MAINTAIN A MINIMUM OF 3′-6″ OF GROUND COVER OVER ALL UNDERGROUND HVAC PIPING
(EDIT DEPTH OF GROUND COVER TO SUIT FROST LINE DEPTH AND PROJECT
REQUIREMENTS).
D. UNLESS OTHERWISE NOTED, ALL CHILLED WATER AND HEATING WATER PIPING SHALL BE
3/4" SIZE (EDIT SYSTEM TYPE OR PIPE SIZE TO SUIT PROJECT REQUIREMENTS).
E. PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING WATER, CHILLED
WATER, AND OTHER CLOSED WATER PIPING SYSTEMS (EDIT SYSTEM TYPES TO SUIT
PROJECT REQUIREMENTS). ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END
DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW POINTS.
F. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF
STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
G. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER
APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.
H. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT
OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.
I. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION
INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).
J. PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS MOUNTED
GREATER THAN 7′-0″ ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO 7′-0″ ABOVE FLOOR
LEVEL.
K. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE
BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.
L. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN
BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR
ALTERATION AND REPAIRS.
M. PITCH STEAM PIPING DOWNWARD IN THE DIRECTION OF FLOW 1/4" IN 10' (1" IN 40') MINIMUM.
PITCH ALL STEAM RETURN LINES DOWNWARD IN THE DIRECTION OF CONDENSATE FLOW
1/2" PER 10' (1" IN 20') MINIMUM. WHERE LENGTH OF BRANCH LINES ARE LESS THAN 8', PITCH
BRANCH LINES TOWARD MAINS 1/2" PER FOOT MINIMUM.
N. PITCH UP ALL STEAM AND CONDENSATE RUNOUTS TO RISERS AND EQUIPMENT 1/2" PER
FOOT. WHERE THIS PITCH CANNOT BE OBTAINED, RUNOUTS OVER 8' IN LENGTH SHALL BE
ONE SIZE LARGER THAN NOTED.
O. TAP ALL BRANCH LINES FROM TOP OF STEAM MAINS (45° PREFERRED, 90° ACCEPTABLE).
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME
DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY
FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE
EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
C. IN CORRIDORS WHERE CEILING SPEAKERS AND AIR DIFFUSERS ARE INDICATED BETWEEN
THE SAME LIGHT FIXTURES, INSTALL BOTH DEVICES AT THE QUARTER POINTS BETWEEN
THE SAME FIXTURE.
D. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″
(CENTERLINE) ABOVE FINISHED FLOOR.
E. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
F. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR
DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING
THICKNESS.
G. PROVIDE ALL 90° SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS
OTHERWISE INDICATED. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST
SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1.5 TIMES
THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH
TURNING VANES.
H. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT
MODIFICATIONS TO SUIT.
I. FIELD ERECTED AND FACTORY ASSEMBLED AIR HANDLING UNIT COILS SHALL BE
ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING SUPPORTS.
PROVIDE GALVANIZED STRUCTURAL STEEL SUPPORTS FOR ALL COILS (EXCEPT LOWEST
COIL) IN BANKS OVER TWO COILS HIGH TO PERMIT INDEPENDENT REMOVAL OF ANY COIL.
J. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.
K. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, DUAL DUCT, VARIABLE VOLUME,
CONSTANT VOLUME AND FAN POWERED BOXES, FAN COIL UNITS, CABINET HEATERS, UNIT
HEATERS, UNIT VENTILATORS, COILS, STEAM HUMIDIFIERS, ETC.) FOR UNOBSTRUCTED
ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING.
L. FINNED TUBE RADIATION ENCLOSURES SHALL BE WALL TO WALL UNLESS OTHERWISE
INDICATED.
M. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND
EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE
POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:
EXISTING TO BE DEMOLISHED
LIMIT OF DEMOLITION
CONNECT NEW TO EXISTINGEXISTING TO REMAIN
NEW DUCT (INSIDE DIMENSIONS: W" X D")
RS
RL
REFRIGERANT SUCTION
REFRIGERANT LIQUID
SUPPLY AIR DUCT UP
SUPPLY AIR DUCT DOWN
H
T
H
T
26-P-3
MH-100
PUMP NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (PUMP)
DETAIL NUMBER
SHEET NUMBER
SHEET NUMBER
SECTION NUMBER
THERMOSTAT
HUMIDISTAT
TEMPERATURE SENSOR
HUMIDITY SENSOR
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
26-TU-1-1
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT)
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
SERVED BY AIR HANDLER UNIT NO. 1
TERMINAL UNIT TAG
MECHANICAL EQUIPMENT TAG
1 OWNER FURNISHED, CONTRACTOR
INSTALLED EQUIPMENT DESIGNATION
EXISTING TO BE DEMOLISHED
EXISTING TO REMAIN
NEW PIPE
CONNECT NEW TO EXISTING
LIMIT OF DEMOLITION
GENERAL PIPING SYMBOLS
GENERAL ANNOTATIONS
AV
STRAINERFLOAT & THERMOSTATIC
STEAM TRAP
INVERTED BUCKET
STEAM TRAP
FLANGE CONNECTION PIPE DROP
PIPE RISER TEE DOWN
TEE UP
UNION
PRESSURE REDUCING
VALVE
BALL VALVE
ANGLE GLOBE VALVE
SAFETY RELIEF VALVE
GLOBE VALVE
MANUAL OR
AUTOMATIC AIR VENT
EXPANSION JOINT
EJ
PRESSURE AND
TEMPERATURE TEST PLUG
QUICK-COUPLE HOSE
CONNECTOR
FLOW METER
HVAC PIPING SYMBOLS
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHR
CHS
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
HHR
HHS QV CRYOGEN VENT
DR DRIP RETURN
CAP
REDUCER (ECCENTRIC)
TYPE
AIRFLOW (CFM)
SD-1
TYPE
AIRFLOW (CFM)
RG-1
TYPE
AIRFLOW (CFM)
EG-1
SQUARE TO ROUND TRANSITION
ELBOW WITH TURNING
VANES
ROUND ELBOW
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT DOWN
EXHAUST, RELIEF, MAKE UP, OR
OUTSIDE AIR DUCT UP
RETURN DUCT DOWN
RETURN DUCT UP
BRANCH DUCT WITH HIGH EFFICIENCY
TAKE-OFF (HETO) BRANCH FITTING &
MANUAL VOLUME DAMPER
BRANCH DUCT WITH CONICAL
FITTING & MANUAL VOLUME
DAMPER
DAMPERS: (BD, FD, FSD, MD, SD, VD)
BD
XX-XX
ANCHOR
TEEDIRECTION OF FLOW
S
N. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND
LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL
BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.
CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. IT
SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE SIZE
AND LOCATION OF CONCRETE HOUSEKEEPING PADS.
O. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, ETC.) IS SUB-CONTRACTED, IT
SHALL BE THE MECHANICAL CONTRACTOR’S RESPONSIBILITY TO COORDINATE
SUBCONTRACTORS AND THE ASSOCIATED CONTRACTS. WHEN DISCREPANCIES ARISE
PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR ITEM OF THE MECHANICAL
CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL CONNECTIONS FOR A PARTICULAR
ITEM OF THE MECHANICAL CONTRACT, IT SHALL BE BROUGHT TO THE ATTENTION OF THE
MECHANICAL CONTRACTOR, WHOSE DECISION SHALL BE FINAL.
P. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE
SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE
ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND
RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE
APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.
Q. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN
IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL
BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
R. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED
TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED
MECHANICAL EQUIPMENT.
S. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL
BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR
JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS
MEETING MSS STANDARDS.WELDING TO STRUCTURAL MEMBERS SHALL NOT BE
PERMITTED. THE USE OF C-CLAMPS SHALL NOT BE PERMITTED.
T. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL
CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE
INSTALLATION WITH GENERAL CONTRACTOR.
U. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE
COORDINATED WITH ALL OTHER TRADES INVOLVED.
V. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE
STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.
W. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND
ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND
PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR
CONDITIONING CONDENSATE TRAP.
X. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
P. PROVIDE AN END OF MAIN DRIP AT EACH RISE IN THE STEAM MAIN. PROVIDE CONDENSATE
DRIPS AT THE BOTTOM OF ALL STEAM RISERS, DOWNFED RUNOUTS TO EQUIPMENT,
RADIATORS, ETC., AT END OF MAINS AND LOW POINTS, AND AHEAD OF ALL PRESSURE
REGULATORS, CONTROL VALVES, ISOLATION VALVES, AND EXPANSION JOINTS.
Q. ON STRAIGHT STEAM PIPING RUNS WITH NO NATURAL DRAINAGE POINTS, INSTALL DRIP
LEGS AT INTERVALS NOT EXCEEDING 200' WHERE PIPE IS PITCHED DOWNWARD IN THE
DIRECTION OF STEAM FLOW AND A MAXIMUM OF 100' WHERE THE PIPE IS PITCHED UP SO
THAT CONDENSATE FLOW IS OPPOSITE OF STEAM FLOW.
R. STEAM TRAPS SHALL BE MINIMUM 3/4″ IN SIZE.
S. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.
T. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.
U. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.
V. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE
OWNER.
W. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,
CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION
ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE
TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.
X. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID
LINES MAY BE INSTALLED LEVEL.
Y. INSTALL HORIZONTAL REFRIGERANT HOT GAS DISCHARGE PIPING WITH 1/2″ PER 10'
DOWNWARD SLOPE AWAY FROM THE COMPRESSOR.
Z. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE
TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO
SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING
SLUGS.
AA. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR
RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER
DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.
BB. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF
VALVE ON EACH SIDE OF STRAINER.
CC. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS
USING HERMETIC COMPRESSORS.
DD. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS A
ASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.
EE. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN
RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.
N. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF
THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.
M. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' MAXIMUM LENGTH.
O. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN
DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
P. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE
DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,
AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR
INSPECTION.
Q. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND
MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.
R. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE
COPPER GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO
BOTH THE EQUIPMENT AND THE DUCT.
S. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR.
THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE
DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH
MANUFACTURER’S PRINTED INSTRUCTIONS.
T. TERMINATE GAS VENTS FOR UNIT HEATERS, WATER HEATERS, HIGH PRESSURE PARTS
WASHER, HIGH PRESSURE CLEANER, AND OTHER GAS APPLIANCES A MINIMUM OF 3′-0″
ABOVE ROOF WITH RAIN CAP (NOTE TO DESIGNER: EDIT APPLIANCES AND HEIGHT ABOVE
ROOF TO MEET CODE AND TO SUIT PROJECT REQUIREMENTS).
U. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER
REQUIREMENTS.
V. LOUVER SIZES, LOCATIONS, MOUNTING, AND DETAILS SHALL BE COORDINATED WITH
OTHER TRADES INVOLVED. REFER TO ARCHITECTURAL SPECIFICATIONS FOR DETAILED
DESCRIPTIONS.
DIRECTION OF PIPE
PITCH (DOWN)
FM
MV
HVAC VALVE SYMBOLS
PC PUMPED CONDENSATE
SPACE TAG
FLEXIBLE CONNECTOR
PUMP
REDUCER (CONCENTRIC)
GATE VALVE
BUTTERFLY VALVE
CHECK VALVE
THERMOMETER
PRESSURE GAUGE
STRAINER WITH BLOWOFF
AND HOSE CONNECTION
YR YEAR
Y
Z INTENTIONALLY LEFT BLANK
Z
M
CONTROL VALVE
CONTROL VALVE, THREE WAY
MOTOR CONTROLLED
VALVE
M
M
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.
B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP
NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,
STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND COR.
C. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO
COMPLETION DEMOLITION WORK.
D. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT WILL REQUIRE CAPPING AND SEALING EXISTING MAINS OR BRANCHES, WITHOUT LEAVING DEAD LEGS, TO KEEP REMAINING SYSTEMS IN OPERATION. THE CONTRACTOR SHALL PROVIDE PROTECTIVE MEASURES TO PROTECT THE EXISTING
OCCUPIED AREAS AND EQUIPMENT DURING THE CONSTRUCTION WORK. THE CONTRACTOR SHALL
CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.
E. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED AND PROPERLY VENTED BY THE
CONTRACTOR ONCE NEW WORK HAS BEEN COMPLETED.
F. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.
REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.
G. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING
WHERE WATER CAN SIT AND BECOME STAGNANT.
H. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE
REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.
I. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.
J. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS
POSSIBLE.
K. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED
OF.
L. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO
EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.
GENERAL DEMOLITION NOTES:
B-100
SPACE…
This is the start of the file's text. The full file is on GovTribe.