Final Drawings Part-3.pdf
PDF 2 MB Posted
- Attached to
- Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler Federal contract opportunity
- Solicitation number
- 36C25526R0159
About this file
This document is a 100% Bid set of electrical construction drawings for the "Install Dedicated Pharmacy Air Handler" project at Harry S. Truman VAMC in Columbia, Missouri (Project 589A4-25-102). The drawings were prepared by Spur Design, LLC and are dated June 9, 2026, with a drawing package consisting of 74 sheets.
The project scope involves mechanical controls and electrical systems supporting the installation of a dedicated pharmacy air handler. Key mechanical systems documented include an Exhaust Fan (EF-1) with motorized damper controls that operates in occupied and unoccupied modes, and a Recirculation Pump (RP-X) for water circulation. The electrical work encompasses power distribution, lighting installation, lightning protection bonding, and control circuits throughout multiple building levels (Basement, Levels 2-3, and Roof). New electrical equipment includes panelboards (DP3-D10-480VQ, PP2-D10-120VN2, PP3-D10-120VN), transformers, variable frequency drives (VFD), and associated disconnects and circuit breakers. The electrical design references existing equipment (ETR) and equipment to be demolished (ETD), with specific attention to HVAC equipment connections (ACA-AHU-11, ACA-AHU-12, humidifiers HUM-11 and HUM-12, unit heaters EUH-1 through EUH-4, and pumps HHWP-1 and HHWP-2). Construction must comply with 2023 NEC, NFPA 101, 2024 IBC, VA seismic design standards, and ASHRAE ventilation standards. The electrical demolition plans indicate removal of existing mechanical equipment, circuits, and conduit infrastructure in affected areas, with reestablishment of remaining circuit continuity as required.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 07 81 00 Applied Fireproofing.pdf | ||
| 36C25526R0159 0004.pdf | ||
| Final Drawings Part-1.pdf | ||
| 36C25526R0159 0003.docx | DOCX document | |
| Final Drawings Part-2.pdf | ||
| PRE-BID SIGN IN ROSTER.pdf | ||
| 07_8100-001_Fireproofing_Mfr_Literature.pdf | ||
| 589a4-25-102_Addendum 02_260828.pdf | ||
| 01 00 00 General Requirements RX.pdf | ||
| 36C25526R0159 0002.docx | DOCX document | |
| Finish schedule from drawings.pdf | ||
| 01 33 23- Shop Drawings Product DAta and Samples.pdf | ||
| finish schedule from specs.pdf | ||
| 01 00 10 - MEDICAL CENTER REQUIREMENTS RX.pdf | ||
| Phasing info.pdf | ||
| 01 32 16-15 Project Schedules RX.pdf | ||
| 01 91 00 General Commissioning Requirements RX.pdf | ||
| 36C25526R0159 0001.docx | DOCX document | |
| S02-Final Specifications 1068 pages.pdf | ||
| 36C25526R0159.docx | DOCX document | |
| P09-Final Drawings Part-2 Pages 37.pdf | ||
| P09-Final Drawings Part-1 Pages 37.pdf |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEQUENCE OF OPERATIONS
EXHAUST FAN (EF-1)
GENERAL DESCRIPTION
The exhaust fan provides general exhaust ventilation to the conditioned space(s) as shown on the drawings.
OPERATING MODES
OCCUPIED MODE
The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.
UNOCCUPIED MODE
The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.
COMPONENT CONTROL LOOPS
EXHAUST FAN – ON/OFF
• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.
• When the HOA switch is in off position, the fan shall be off.
• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.
OCCUPIED MODE:
• The exhaust fan shall be enabled after the EA damper has proven operable.
• The exhaust fan shall be commanded to run and shall maintain a user defined constant speed.
UNOCCUPIED MODE:
The exhaust fan shall be off.
MOTORIZED DAMPER
OCCUPIED MODE:
The motorized damper shall be open. The motorized damper shall open 30 sec (adj.)
prior to activation of the exhaust fan.
UNOCCUPIED MODE:
The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.
EA
M
CT
STARTER
N.C.
M
BI
BO
BI
BO
EA DAMPER STATUS
EA DAMPER
EF STATUS
EF START/STOP
SEQUENCE OF OPERATIONS
RECIRCULATION PUMP (RP-X)
GENERAL DESCRIPTION
The inline pump will operate to recirculate water for the fixtures shown on the drawings.
OPERATING MODES
NORMAL OPERATING MODE:
The pump shall be in normal operating mode at all times.
COMPONENT CONTROLS
PUMP
NORMAL OPERATING MODE:
The pump shall operate at the specified flow rate.
CT
M
P1
BI P1 STATUS
HHR / CHR IN HHR / CHR OUT
VFD
BO
AO
BI
P1 VFD START/STOP
P1 VFD SPEED
P1 VFD FAULT
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
/9
/2
:4
:0
A
M
MECHANICAL CONTROLS
DSM 66 OF 73JGD
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE,
COLUMBIA, MO 65201
M-705
SPUR #: 2517No. REVISION DESCRIPTION DATE
NOT TO SCALE
GENERAL EXHAUST FAN (EF-1) TYPICAL CONTROL DIAGRAM2
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.
EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.
EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.
ALARMS DESCRIPTION ALARM ALARM DELAY
EXHAUST AIR DAMPER X X X
EXHAUST AIR DAMPER STATUS X X X
DAMPER
EF START/STOP X X X
EF STATUS X X X
EXHAUST FAN
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-1)
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
PUMP RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.
PUMP IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
PUMP FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
ALARMS DESCRIPTION ALARM ALARM DELAY
PUMP START/STOP X X X
PUMP VFD FAULT X X X
PUMP STATUS X X X
PUMP VFD SPEED X X X
PUMPS
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - HEATING HOT WATER PUMPS (HHWP-X)
12" = 1'-0"
HEATING HOT WATER PUMP (HHWP-X) TYPICAL CONTROL DIAGRAM1
ABBREVIATIONS
LIGHTNING PROTECTION SYMBOLS
STANDARD MOUNTING HEIGHTS
A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE
SCOPE OF WORK, BUT ARE STILL DIAGRAMMATIC IN NATURE.
B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE
CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY
FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.
C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH BUILDING DISCIPLINES.
HOWEVER, COORDINATION WITH OTHER TRADES IS REQUIRED.
D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION REGARDING
SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF
SERVICES.
E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE
BEFORE THE START OF WORK.
F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE SHUTDOWN. COORDINATE
SERVICE SHUTDOWN FOR ALL EQUIPMENT WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE.
G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE COMPLETION OF THE PROJECT.
I. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE CONTRACTOR SHALL DOCUMENT
THE VARIATION AND REPORT IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH
THE ENGINEER OF RECORD.
GENERAL NOTES
1P SINGLE-POLE
1PH SINGLE-PHASE
3P THREE-POLE
3PH THREE-PHASE
3W THREE-WIRE
4W FOUR-WIRE
A
A or AMP AMPERE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, OR
AUTOMATIC FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AIP ABANDONED IN PLACE
ALT ALTERNATE
AMB AMBIENT
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
B
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY-PASS
C
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR CANDELA
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED /
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUED
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CVD CUMULATIVE VOLTAGE DROP
D
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
E
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
ETL EXISTING TO BE RELOCATED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
F
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
G GROUND OR GENERATOR
GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
H
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
I
IC INSULATION CONTACT
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J
JB OR J-BOX JUNCTION BOX
K
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE-HOUR
KVAR KILOVOLT-AMPERE-REACTIVE
KW KILOWATT
KWH KILOWATT-HOUR
KWHM KILOWATT-HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
M
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NC NORMALLY CLOSED
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, OR PULL BOX, OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PNLBD PANELBOARD
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
ANNOTATION LIGHTING SYMBOLS
R
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
RE REFER TO
REC RECESSED
RELO RELOCATED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FEET (FOOT)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SSTV SECURITY SURVEILLANCE TELEVISION
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
T
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
U
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE-REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
W
W WATT
WH WATER HEATER
WP WEATHERPROOF
X
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
ELECTRICAL:
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS (TOP)
ANNUNCIATOR PANELS (TOP)
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
GROUND BAR
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (TOP)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES, EXTERIOR (BOTTOM)
RECEPTACLES, GARAGES (BOTTOM)
RECEPTACLES IN EQUIPMENT ROOMS (TOP)
RECEPTACLES ABOVE COUNTERTOPS (TOP)
REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)
REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)
SAFETY SWITCHES & STARTERS
SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
84" 48" 48" 84" 48" 80" 60"
120" 60" 72" 36" 48" 72" 48"
144" 18" 24" 26" 48" 44" 48"
CEILING
48" 48" 18" 84"
(AFF, AFG UNLESS NOTED OTHERWISE)
1 MECHANICAL KEYNOTE CALL OUT
PLUMBING KEY NOTE CALL OUT
ELECTRICAL KEYNOTE CALL OUT
OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
LIMIT OF DEMOLITION
NEW WORK TO EXISTING WORK CONNECTION POINT
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
LIGHT FIXTURE, CEILING MOUNTED
A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
= ARROW INDICATES AIMING DIRECTION
LIGHTING TRACK WITH TRACK LIGHT FIXTURES
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
EMERGENCY LIGHT FIXTURE, CEILING MOUNTED
A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT
FIXTURE SCHEDULE
a = SWITCHED BY SWITCH "a"
NL = NIGHT LIGHT
EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED
X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT
FIXTURE SCHEDULE
EMERGENCY BATTERY PACK LIGHT FIXTURE,
WALL MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, WALL MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, BOLLARD
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
LIGHT FIXTURE, POLE MOUNTED
A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT
FIXTURE SCHEDULE
CIRCUITING SYMBOLS
HOMERUN TO PANELBOARD
TICK MARKS INDICATE NUMBER OF CONDUCTORS.
DESIGNATIONS ARE PANELBOARD AND
CIRCUIT NUMBERS.
UNSWITCHED HOT CONDUCTORS SHOWN LEADING
NEUTRAL CONDUCTOR
NEUTRAL CONDUCTOR
SWITCHED HOT CONDUCTORS SHOWN TRAILING
GROUND CONDUCTOR
EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY
ISOLATED GROUNDING CONDUCTOR IN RACEWAY
CONCEALED RACEWAY
EXPOSED RACEWAY
RACEWAY TURNING UP
RACEWAY TURNING DOWN
EQUIPMENT TERMINATION
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
UNDERGROUND ELECTRIC LINE
OVERHEAD ELECTRIC LINE
RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO
RECEPTACLE, MOUNTED 6" ABOVE COUNTER,
TYPE AS INDICATED ABOVE
RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT
INTERRUPTER, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, SPECIAL PURPOSE
RECEPTACLE, TWIST-LOCK
RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO
RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO
RECEPTACLE DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER
E = EMERGENCY POWER
GF = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUND
S = SWITCHED
TR = TAMPER RESISTANT
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
XP = EXPLOSION PROOF
MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,
NEMA 5-20R, UNO
WALL SWITCH, SINGLE POLE (LINE VOLTAGE, UNO.)
WALL SWITCH DESIGNATIONS AS FOLLOWS:
2 = TWO-POLE
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER SWITCH
OS# = OCCUPANCY SENSOR TYPE (LINE-VOLTAGE, UNO.)
RE: OCCUPANCY SENSOR AND SWITCH SCHEDULE
P = SINGLE-POLE, SINGLE-THROW, PILOT LIGHT
K = KEYED-TYPE
M = MOTOR RATED
WP = WEATHER PROOF WITH COVER
OCCUPANCY SENSOR, CEILING MOUNTED
OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER
TO OCCUPANCY SENSOR AND SWITCH SCHEDULE
POWER PACK FOR LIGHTING CONTROL
JUNCTION BOX
RECEPTACLE ON EMERGENCY POWER
RECEPTACLE, ISOLATED GROUND TYPE
PUSH BUTTON, TYPE AS NOTED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED
EMERGENCY SHUNT RELAY
WIRING DEVICE SYMBOLS
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CABLE CONNECTION
LIGHTNING PROTECTION GROUND ROD
LIGHTNING PROTECTION CONDUCTOR
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION
PANELBOARD ON HOUSEKEEPING PAD
PANELBOARD, RECESS MOUNTED
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES
AMPERES/POLES, CB = CIRCUIT BREAKER TYPE
DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES
AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE
COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER
100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER
SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,
3-POLE, UNO
CONTACTOR
PHOTOCELL
RELAY
TIME SWITCH
LOW-VOLTAGE TRANSFORMER
VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH
100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,
NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE
CABINET, RECESS MOUNTED
CABINET, SURFACE MOUNTED
POWER EQUIPMENT SYMBOLS
ELECTRICAL ONE-LINE DIAGRAM SYMBOLS
GENERATOR,
SEPARATELY DERIVED
SOURCE, TYPE AND
RATINGS AS INDICATED
GENERATOR, NON-
SEPARATELY DERIVED
SOURCE, TYPE AND
RATINGS AS INDICATED
AUTOMATIC TRANSFER
SWITCH WITH BYPASS TYPE
AND RATINGS AS INDICATED
PANELBOARD,
SINGLE-SECTION,
RATINGS PER
SCHEDULES
PANELBOARD,
MULTI-SECTION,
RATINGS PER
SCHEDULES
TRANSFORMER
TRANSFORMER,
SHIELDED
600AF
500AT
3P
400AS
3P
225AF
LPS-R
DRAWOUT CIRCUIT
BREAKER, RATINGS
AS INDICATED
600AF
500AT
3P
CIRCUIT BREAKER,
RATINGS AS
INDICATED
FUSED DISCONNECT
SWITCH, RATINGS
AS INDICATED
400AS
3P
225AF
LPS-R
NEMA 1
COMBINATION FUSED
SWITCH AND STARTER,
RATINGS AS
INDICATED
GROUND-FAULT RELAY
VARIABLE FREQUENCY
DRIVE WITH
DISCONNECT, RATINGS
AS INDICATED
CONTACT, CLOSED
FEEDER TAGCAPACITOR
COMBINATION CIRCUIT
BREAKER AND
STARTER, RATINGS AS
INDICATED
SHUNT-TRIP RELAY
KIRK-KEY INTERLOCK
SURGE PROTECTION
DEVICE
CURRENT TRANSFORMER
CONTACT, OPEN
HEATER
AMMETERSURGE ARRESTER
VOLTMETER
COMBINATION DIGITAL
AMMETER/VOLTMETER
UTILITY METER
RELAY
GROUND CONNECTION
POTENTIAL TRANSFORMER
GROUND CONNECTION
WITH TEST WELL
MOTOR
200A DEAD-FRONT ELBOW
600A DEAD-FRONT ELBOW
DEAD-FRONT SPLITTER
FAULT INDICATOR
a
A1
GF
OR
PP
J
EPO
ES
EMERGENCY BATTERY PACK LIGHT FIXTURE,
CEILING MOUNTED
Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT
FIXTURE SCHEDULE
AM
VM
DM
ST
KK
GFR
M
SPD
R
E/G 400A/3P
275KW STANDBY
480Y/277V, 3PH, 4W
E/G 400A/3P
275KW STANDBY
480Y/277V, 3PH, 4W
200A 3P
ATS#
200A 3P
ATS#
TX#
TX#
LP1
1,3,5
UE
OE
a
A1
A1E a
X1E
X1E
Y1E
Y1E
A1
A1
A1
OR
OR
T
100/3
100/3/70
100/3/70/1
100/3/CB
C
PC
R
TS
CODES, STANDARDS, AND EXECUTIVE ORDERS
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN VOLUNTARY STANDARD BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS. REFERENCE
RELEVANT ADDENDA FOR EACH OF THE ADOPTED CODES AND STANDARDS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL)
(HTTP://WWW.CFM.VA.GOV/TIL/).
• 2024 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)
• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)
• 2024 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)
• 2024 NATIONAL FIRE CODES (NFPA)
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• 2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• 2024 INTERNATIONAL MECHANICAL CODE
• 2023 NATIONAL ELECTRICAL CODE (NEC), NFPA 70
• 2024 INTERNATIONAL PLUMBING CODE (IPC)
• 2022 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
• ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)
• 2022 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
• 2022 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)
• 2023 STEEL CONSTRUCTION MANUAL (16TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR
PARTS 433, 434 AND 435.
• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS
• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
• 2022 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1
• 2022 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15
• 2024 PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.).
VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY
SYSTEM WIDE.
TRANSFER SWITCH,
RATINGS AS INDICATED
ATS = AUTOMATIC
TRANSFER SWITCH
MTS = MANUAL
TRANSFER SWITCH
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ELECTRICAL LEGEND AND
ABBREVIATIONS
JMF 67 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
E-001
SPUR #: 2517No. REVISION DESCRIPTION DATE
C B
E
E009
E002B
E002H E002I E002J E002K
E003
C O
R R
E001E
DN
UP
UPDN
F001B
F003*
JAN.
VEST.
CORR.
STAIR
#11
HATCH TO
TUNNEL BELOW
ELEV
#11
ELEV
#10
ELEV
#9
F023A
CBF3
F024
F001A
F004
F021
F018
F020 F019
F017 F016
F015A
F015
F014
C B
F
F005 F010
F012
F013
F011 F036 F009A
F003 F006 F007 F008 F009
CBF5
F001
F002A
F002
CBF1
E010
E008
E007
E006
CBE2
CBE5
CBE2
E004
E005
F037
A024A
B042 B048 B051B039AB039
E001K
E001H
E001L
E002F
E002E
E002D E002C
E002A
E002
A001
A002
A003 A007 A009 A010A A010 A019 A020
CORR-1
F029 F028
F027A
F028A F025
F025A
F027 F026
F034
F034A
F035A
F035
F030 F031 F032 F033
F030A
F023 F022
CBE4
A009A
C B
F
A020A
F029A
E001F
E001J
CORR.
CORR.
CORR.
C O
R R
C O
R R
E001BE001D
E001A
OFFICETEAM ROOM
NARCOTIC
VAULT
E001C
OFFICE
STERILE PROCESSING AREA
NON-HAZARD IV PREP
IV STORAGE ROOM
STORAGE
CORRIDOR
HAZARDOUS
DRUG STORAGE
HAZARDOUS
IV PREP
OFFICE
STR #10
DN
ROOF BELOW
ROOF BELOW
F400
F401F402
E305
F396
UP
DN
UP
DN
DN
#10
#11
#9
F315
F312.1
C3F3
E312
E306
E308
E310
E311
E329 E332 E333 E334 E338
E339
E340
E341
E336 E337
E331
E328
E327
E326
E324
E323 E322
E321
E319
C3E2
E320
E318 E317
C3F1
E316
E315 E314 E313
E300
E307
E304
C3F5
E309
F395
S T
R
F397
F300
F303
F302
F322
F304
F307
F
F305
F310 F309
F312
S T
R
F312.2 F311
E325
C E
C3E4
C E
E330
E335
F348 F346 F345 F343 F340 F339 F338 F337
C3F9
F349
F350
F321
F320
F317
F316
C F
F347 F344
F342 F341
F336
F324 F325 F326
F334
F333
F335
F332
F331
F327 F328 F329
F330
F323
F318
F314
C3F7
C F
F319
E A
F361 F359
F364 F360
F363 F362
F386
F372 F371
F375 F376 F377 F378
F382 F381 F380
F389
F391
F392
F393
F390
F385 F383
F358
F352 F353 F354 F355 F356
F357
F366 F367 F368
F370
F379
F369
F388
F398
F365
E253E210
F252
F253
ELECT.
CLOSET
RESTROOM
DN
UP
DN
F
F E
FE
C2E8
C2E7
C2E12
F210 F211 F212 F214 F215 F217 F235
F236 F239 F240 F267 F266 F265
F269
C2F23
F268 F264 F263
F210A C2F3
F204
C2F1
F201
F202
F206C F206D
C2F7
F203
C2E10
F224
C2F8
F206B F206A
F205
F242
F237
F206
F207
C2F20
E201
C2F20
F256
F245
F241
C F
F231
F223
C2F14 F257
F230
F232
F219
F238
F233
C2F16
F234
F243
F246
C F
E207
F209
C2F4
C2F6
F216
F208
C F
F209A
E204 C2E6
F247
F244
C2F17
F225
F228
E205A
C2E3
E226 E225 E223 E222
F218
C2F12
F222
C E
E212A
E224A E214
E213
E205
F221
C2F19
F222A F227
E208
E217
E211
E
C E
C F
F250
F255
C F
F226
E255
E216
C2E1
E220
F211A
F248
F249
C F
F220
E211A
E254
E256
C F
F213A
F213
E221
E219
E218
C F
E215
F271 F260
F270 F261
F262
C F
F273 F258
F272 F259
F229
F200
F274
F
E209A
F275
F213B
E203
E241
E239
E237
E236
C2E9
C2E11
E229
E227E235 E234 E233 E232 E230
E238
C2E16
C2E14
C2E17 E244
E240
E242 E243 E249
C2E18
E245
C E
E246 E247
E248 E250
E231
E228
C2E13
E251 E252
F251
F
F
F
F
E202
F227A
OPEN TO BELOW OPEN TO BELOW
TLT. ALCOVE
CORR.
CORR.
SOILED
UTIL.
ST. TLT.
CLEAN
DISPATCH
CORR.
CORR.
C O
R R
TLT.
ST. WK.
CORR.
C O
R R
C O
R R
TLT.
CLEAN
STORAGE
CORR.
JAN.
C O
R R
SURG.
SUPPLIES
TLT. TLT.
CORR.
SIGNAL
CORR.
CORR.
STERIL.
C O
R R
ALCOVE
ALCOVE
CORR.
SOILED
UTIL.
TLT.
TLT.
CORR.
TELE/ DATA
ELECTRICAL
CORR.
CORR.
TLT.
CORR.
C O
R R
CLEAN UTIL.
CORR.
CORR.
TLT.
TLT.
CORR.
ELEV
#11
ELEV
#10
ELEV
#9
STAIR
#11STAIR
#10
ELEC.
CLOSET
E212
CORR.
C O
R R
C O
R R
C O
R R
CORR.
CORR.
C O
R R
A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED
OTHERWISE.
B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-
ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS
AS REQUIRED TO MAINTAIN OPERATION.
C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION
WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE
VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE
PROPERTY OF THE VA UNLESS NOTED OTHERWISE.
D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE
FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.
E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL
DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND
REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.
F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND
CONDUIT ALL THE WAY BACK TO SOURCE.
G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA
OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM
PANELBOARD.
GENERAL NOTES
H
3 4
6 7 8 9
G
F
E
D
10 112
C
E.1
D.7
B
6.3 11.5 1312
EP401
ED401
EP401
ED401
MECHANICAL ROOM
E003
MAIN ELECTRICAL ROOM
E003A
PHARMACY
E001
ELECTRICAL ROOM
E009
ED401
H
7 8 9
G
F
E
D
10 11
C
E.1
D.7
B
11.5 1312
EL401
MECHANICAL PENTHOUSE
ROOF
H
3 4 5 6 7 8 9
G
F
E
D
10 112
C
E.1
D.7
B
6.3 11.5 1312
EP401
1MECHANICAL PENTHOUSE
F399
ED401
ED401
EL401
H
3 4 5 6 7 8 9
G
F
E
D
10 112
C
E.1
D.7
B
6.3 11.5 1312
EP401
KEY PLAN
N
SCOPE AREA
BLDG 1
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ELECTRICAL REFERENCE PLANS
JMF 68 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
E-101
SPUR #: 2517
N
3/64" = 1'-0"
ELECTRICAL REFERENCE PLAN - BASEMENT1
N
3/64" = 1'-0"
ELECTRICAL REFERENCE PLAN - ROOF4
N
3/64" = 1'-0"
ELECTRICAL REFERENCE PLAN - LEVEL 33
N
3/64" = 1'-0"
ELECTRICAL REFERENCE PLAN - LEVEL 22
No. REVISION DESCRIPTION DATE
DN
F361 F359
F364 F360
F363 F362
F372 F371
F353 F354 F355 F356
F366 F367 F368
F370
F369
F365
E001
E002K
E001K
E001H
E001L
E001F
E001J E001D
TEAM ROOM
STERILE PROCESSING AREA
NON-HAZARD IV PREP
IV STORAGE ROOM
HAZARDOUS
DRUG STORAGE
HAZARDOUS
IV PREP
OFFICE
A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED
OTHERWISE.
B. WHERE PORTIONS OF THE CIRCUIT ARE REMOVED OR ABANDONED, RE-
ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS
AS REQUIRED TO MAINTAIN OPERATION.
C. THE VA SHALL MAINTAIN THE RIGHT OF FIRST REFUSAL TO ALL DEMOLITION
WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE
VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE
PROPERTY OF THE VA UNLESS NOTED OTHERWISE.
D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE
FLUSHED WITH THE NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.
E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL WIRING
DEVICES AND/OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND
REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.
F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND
CONDUIT ALL THE WAY BACK TO SOURCE PANELBOARD.
DEMOLITION GENERAL NOTES
6 7 8 9
D
10 11
C
D.7
B
6.3 11.5
PHARMACY
E001
STORAGE
E001E
MFMR EXEC OFFICE
E002K
CLINICAL RESEARCH
E002J
R.C.O. R&D
E002I
OFFICE
E002H
WORK ROOM
E002B
CORRIDOR
CBE3
WOMAN TOILET
E010
MEN TOILET
E008
1 1 1
CORRIDOR
CBE35
CORRIDOR
CBE3F1
TEAM ROOM
E001D
KEY PLAN
N
SCOPE AREA
BLDG 1
3 4 5 62
B
ACA-AHU-5
(ETD)
MCC
'MCC-B3-480VN'
(ETR)
(ETD)
MECHANICAL ROOM
E003
MAIN ELECTRICAL ROOM
E003A
(ETR)
ACA-AHU-4
E-601
COMPRESSOR
(ETD)
ACA-ET-1ACA-HWP-2
ACA-HX-2
ACA-AHU-17
ACA-AHU-16
(ETR)
(ETR)(ETR)
(ETR)
(ETR)
H
8 9
G
F
3-SH1
3-SH3
3-SH2
(ETD)
(ETD)
(ETD)
78,80
PP3-D10-120VN
82,84
PP3-D10-120VN
74,76
PP3-D10-120VN
INTAKE
F358
PHARMACIST OFFICE
F357
8 9
D
C
B
(ETD)
1-SH1
1-SH3
1-SH2
1-SH4
1-SH5
(ETD)
(ETD)
(ETD)
1-1-TU-1
1-EF-3
(ETD)
(ETD)
(ETL)
20,22
PPB-C8-120VN
17,19
PPB-C8-120VN
21,23
PPB-C8-120VN
25,27
PPB-C8-120VN
24,26
PPB-C8-120VN
31,33,35
PPB-C8-120VC2
STORAGE
E001E
ELECTRICAL ROOM
E009
PHARMACY
E001
CORRIDOR
CBE2
PNL 'PPB-C8-120VN'
(ETR)
REF 3/EP401
MCC
'MCCB-D8-480VQ'
(ETR)
E-601
D
10 11
C
11.5
(EX) EF
(ETD)
MECHANICAL PENTHOUSE
INTERSTITIAL
REF 2/EP401
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ELECTRICAL DEMOLITION PLANS
JMF 69 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
ED401
SPUR #: 2517
ELECTRICAL KEYNOTES
1 EXISTING CEILING SYSTEM SHALL REMAIN.
2 EXISTING CEILING SYSTEMS ARE TO BE DEMOLISHED AS PART OF THIS
PROJECT FOR NEW MECHANICAL WORK. ALL LIGHTING AND LIGHTING
CONTROLS SYSTEMS IN AFFECTED AREA TO REMAIN DURING ALL PHASES OF
CONSTRUCTION. PROTECT AND TEMPORARILY SUPPORT LIGHT FIXTURES
AND DEVICES WHERE NECESSARY. CEILING SHALL BE REINSTALLED ONCE
MECHANICAL WORK IS COMPLETED.
3 EXISTING MECHANICAL EQUIPMENT ABOVE CEILING AND CORRESPONDING
ACCESSORIES ARE TO BE DEMOLISHED AS PART OF THIS PROJECT. REMOVE
ASSOCIATED CIRCUITS, CONDUITS, BOXES, AND SUPPORTS BACK TO THE
TERMINATION POINT AT THE EXISTING FEEDER BREAKER. RELABEL THE
FEEDER BREAKER AS "SPARE".
4 EXISTING EXHAUST FAN TO BE DEMOLISHED. PRESERVE EXISTING CIRCUIT
AND EXTEND OR REROUTE TO NEW LOCATION.
5 MAINTAIN CIRCUITRY AND CORRESPONDING ACCESSORIES OF EXISTING
MECHANICAL EQUIPMENT LOCATED ABOVE CEILING. EXTEND OR REROUTE TO
NEW LOCATION.
10 DISCONNECT AND REMOVE EXISTING CIRCUIT, BACK TO EXISTING MCC.
REMOVE EXISTING DISCONNECT.
22 ALL ACCESSORIES AND ELECTRICAL CONTROLS SERVING EXISTING
COMPRESSOR TO BE DEMOLISHED BACK TO SOURCE.
N
1/8" = 1'-0" REF: 1/ E-101
REFLECTED CEILING DEMOLITION PLAN - BASEMENT1
N
1/8" = 1'-0" REF: 1/ E-101
ENLARGED DEMOLITION PLAN - MECHANICAL RM E003 - BASEMENT3
N
1/8" = 1'-0" REF: 3/ E-101
ENLARGED DEMOLITION PLAN - LEVEL 32
N
1/8" = 1'-0" REF: 1/ E-101
ENLARGED DEMOLITION PLAN - BASEMENT5
N
1/8" = 1'-0" REF: 3/ E-101
ENLARGED DEMOLITION PLAN - EXISTING ROOFTOP - INTERSTITIAL LEVEL4
A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED
OTHERWISE.
B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-
ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS
AS REQUIRED TO MAINTAIN OPERATION.
C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION
WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE
VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE
PROPERTY OF THE VA UNLESS NOTED OTHERWISE.
D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE
FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.
E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL
DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND
REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.
F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND
CONDUIT ALL THE WAY BACK TO SOURCE.
G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA
OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM
PANELBOARD.
GENERAL NOTES
D
10 11
C
11.5
LP3-D2-277VE
MECHANICAL PENTHOUSE
F399
(ETR)
STAFF LOUNGE
E305
(ETR)
(ETR)(ETR)
1-HUM-12
1-HUM-11
EUH-1
HHWP-2
F1E
F1E
ACA-AHU-12
ACA-AHU-11
EUH-2
D
10 11
C
11.5 12
BOND TO EXISTING
SYSTEM ON
ABOVE ROOF
ROOF DRAIN
(RELO)
MECHANICAL PENTHOUSE
ROOF
BOND TO EXISTING
SYSTEM ON
BELOW ROOF
BOND TO EXISTING
SYSTEM ON
ABOVE ROOF
ABOVE ROOF
BELOW ROOF
REA-LV-1
(NEW)
KEY PLAN
N
SCOPE AREA
BLDG 1
E
D
10 11
C
E.1
D.7
11.5 12
D1 D1
D1D1
MECHANICAL PENTHOUSE
INTERSTITIAL
(ETR)
#11
STAIR
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ELECTRICAL LIGHTING PLAN
JMF 70 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
EL401
SPUR #: 2517
N
1/4" = 1'-0" REF: 3/ E-101
ENLARGED LIGHTING PLAN - MECHANICAL PENTHOUSE F399 - LEVEL 32
N
1/4" = 1'-0" REF: 4/ E-101
ENLARGED LIGHTNING PROTECTION PLAN - MECHANICAL PENTHOUSE ROOF1
ELECTRICAL KEYNOTES
7 REUSE POWER FROM EXISTING EGRESS LIGHTING CIRCUIT #18 ON LIFE
SAFETY PANEL 'LP3-D2-277VE' VIA THE NEAREST EXISTING LIGHT FIXTURE
POWERED BY THIS CIRCUIT AS SHOWN ON PLANS.
8 EXISTING LIGHTNING PROTECTION SYSTEM MAY NEED TO BE SHIFTED
DURING CONSTRUCTION OF MECHANICAL PENTHOUSE WALLS. PROTECT
EXISTING SYSTEM DURING CONSTRUCTION. PROVIDE NEW SECTIONS OF
CONDUCTOR OR MOUNTING BRACKETS AS NEEDED.
21 REUSE POWER AND CONTROLS FROM EXISTING LIGHTING CIRCUIT VIA THE
NEAREST LIGHT FIXTURE WITHIN THE INTERSTITIAL SPACE.
No. REVISION DESCRIPTION DATE
N
1/8" = 1'-0"
ENLARGED LIGHTING PLAN - MECHANICAL PENTHOUSE INTERSTITIAL3
DN
A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED
OTHERWISE.
B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-
ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS
AS REQUIRED TO MAINTAIN OPERATION.
C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION
WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE
VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE
PROPERTY OF THE VA UNLESS NOTED OTHERWISE.
D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE
FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.
E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL
DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND
REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.
F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND
CONDUIT ALL THE WAY BACK TO SOURCE.
G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA
OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM
PANELBOARD.
GENERAL NOTES
D
C
ATS 'ATS-3' (ETR)
MCC
'MCCB-D8-480VQ'
(ETR)
ATS 'ATS-1' (ETR)
ATS 'ATS-4' (ETR)
XFMR 'TB-D8-120VE'
(ETR)
PNL 'LPB-C8-120VE'
(ETR)
PNL 'DPB-D8-120VE'
(ETR)
PNL 'PPB-D8-120VC'
(ETR)
XFMR
'TB-D8-120VC-A'
(ETR)
XFMR (ETR)
XFMR 'TB-C8-120VC'
(ETR)
PNL 'LPB-C8-277VC'
(ETR)
PNL 'PPB-C8-120VC'
(ETR)
PNL
'PPB-C8-120VC-A'
(ETR)
PNL 'DPB-D8-277VE'
(ETR)
PNL 'LPB-D8-277VE'
(ETR)
SWBD
'LVB-C8-277VG'
(ETR)
PNL 'DPB-C8-480VQ'
(ETR)
PNL 'PPB-C8-120VN'
(ETR)
PNL 'PPB-C8-120VC2'
(ETR)
GROUNDING BAR
(ETR)
ELECTRICAL ROOM
E009
1-1-TU-1
(RELO)
PHARMACY
E001
REF 5/ED401
D
10 11
C
11.5
2,4,6
DP3-D10-480VQ
1,3,5
DP3-D10-480VQ
PP2-D10-120VN2
MECHANICAL
PENTHOUSE
F399
HHWP-2
14,16,18
DP3-D10-480VQ
ELECTRICAL ROOM
F396
PNL 'DP3-D10-480VQ'
(NEW)
PNL 'PP3-D10-120VC'
(ETR)
PNL 'PP3-D10-120VN'
(ETR)
XFMR 'T3-3-D10'
(ETR)
XFMR 'T3-4-D10'
(ETR)
'DS3-3' (ETR)
'DS3-4' (ETR)
1-HUM-11
1-HUM-12
30/3
60/3
EUH-1
19,21,23
DP3-D10-480VQ
ACA-AHU-12
ACA-AHU-11
7,9,11
DP3-D10-480VQ
8,10,12
DP3-D10-480VQ
30/3
30/3
EUH-2
25,27,29
DP3-D10-480VQ
D.7
PNL 'PP2-D10-120VC'
(ETR)
PNL 'LP2-D10-277VC'
(ETR)
PNL
'PP2-D10-120VN3'
(ETR)
XFMR
'T-PP2-D10-120VN-3'
(ETR)
XFMR 'T2-D10-120VN'
(ETR)
PNL
'PP2-D10-120VN2'
(ETR)
PNL
'PP2-D10-120VN1'
(ETR)
PNL 'LP2-D10-277VN'
(ETR)
200A/3 (ETR)
ELECTRICAL ROOM
F252
KEY PLAN
N
SCOPE AREA
BLDG 1
3 4 5 62
B
MCCB-D8-480VQ
SWBD
'DPB-B3-277VC'
(ETR)
SWBD
'DPB-B3-277VN'
(ETR)
SWBD
'LVB-B3-277VN'
(ETR)
MCC
'MCC-B3-480VN'
(ETR)
ATS 'ATS-2' (ETR)
MAIN ELECTRICAL ROOM
E003A
MECHANICAL ROOM
E003
1-HUM-10 60/3
MCCB-D8-480VQ
(ETR)
ACA-AHU-4
(NEW)
HHWP-1
ACA-AHU-10
(NEW)
(NEW)
MCCB-D8-480VQ
HX-4/HWP-5
(ETR) 12
ACA-ET-1
ACA-HWP-2
ACA-HX-2
ACA-AHU-17
ACA-AHU-16
(ETR)
(ETR)
(ETR)
(ETR)
(ETR)
ACA-HX-1
(ETR)
ACA-HWP-1
(ETR)
D
10 11
C
11.5
ACA-RF-12
ACA-EF-1
(NEW)
MECHANICAL PENTHOUSE
INTERSTITIAL
13,15,17
DP3-D10-480VQ
(NEW)
EUH-4
EUH-3
(NEW)
(NEW)
20,22,24
DP3-D10-480VQ
26,28,30
DP3-D10-480VQ
32,34,36
MPP4-D2-120VQ
REF 4/ED401
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ENLARGED POWER PLANS
JMF 71 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
EP401
SPUR #: 2517
N
1/4" = 1'-0" REF: 1/ E-101
ENLARGED POWER PLAN - ELECTRICAL ROOM E009 - BASEMENT3
N
1/4" = 1'-0" REF: 3/ E-101
ENLARGED POWER PLAN - MECHANICAL PENTHOUSE - LEVEL 31
N
1/4" = 1'-0" REF: 2/ E-101
ENLARGED POWER PLAN - ELECTRICAL ROOM F252 - LEVEL 25
N
1/4" = 1'-0" REF: 1/ E-101
ENLARGED POWER PLAN - MECHANICAL ROOM E003 - BASEMENT4
ELECTRICAL KEYNOTES
9 REROUTE OR EXTEND EXISTING CIRCUIT PREVIOUSLY SERVING FORMER
MECHANICAL EQUIPMENT AT THIS LOCATION FROM EXISTING CONTROL
DEVICE. SEE ONE-LINE DIAGRAMS FOR MODIFICATIONS REQUIRED FOR
CIRCUIT.
12 DISCONNECT TO BE PROVIDED BY DIVISION 23 CONTRACTOR.
No. REVISION DESCRIPTION DATE
N
1/4" = 1'-0"
ENLARGED POWER PLAN - MECHANICAL PENTHOUSE INTERSTITIAL2
SPRING NUT
CONDUIT COMPRESSION
FITTING
JUNCTION BOX (SIZE AS
REQUIRED)
STEEL EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL
15" FLEXIBLE GALVANIZED STEEL
CONDUIT WITH CONDUCTORS & GREEN
INSULATED EQUIPMENT GROUNDING
CONDUCTOR.
CONDUIT,
TYP.
BEAM CLAMP, TYP.
[914mm]
CONDUIT TRAPEZE
PER SD260533-02,
TYP.
JUNCTION BOX, TYP (SIZE
AS REQUIRED)
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
FLOOR OR ROOF STRUCTURE. FIELD
VERIFY ACTUAL CONDITIONS, TYP.
SEISMIC OR EXPANSION
JOINT. FIELD VERIFY
ACTUAL CONDITIONS &
LOCATIONS.
M
IN
IM
U
M
PARAPET WALL
ROOF
AIR TERMINAL
ADHESIVE TYPE AIR TERMINAL
BASE MOUNTED VERTICALLY
LIGHTNING PROTECTION
CONDUCTOR
ADHESIVE STYLE
CABLE FASTENER
LIGHTNING PROTECTION
CONDUCTOR
UNIVERSAL PARALLEL
CABLE SPLICER
BUTT END STRAIGHT
CABLE SPLICER
PARALLEL CABLE
SPLICER
LIGHTNING PROTECTION
BONDING CONDUCTOR
TO BONDS
ADHESIVE STYLE CABLE
FASTENER MOUNTED TO
ROOF
LIGHTNING PROTECTION
CONDUCTOR
CABLE FASTENER WITH
STAINLESS STEEL
HARDWARE, CAULK
PENETRATIONS
BONDING PLATE MOUNTED
WITH STAINLESS STEEL
FASTENERS, CAULK
PENETRATIONS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
VA FORM 08-6231
DRAWING TITLE PROJECT TITLE
LOCATION
DATE CHECKED DRAWN
PROJECT NUMBERCONSULTANTS:
DRAWING #
VA HEALTH CARE SYSTEM APPROVAL:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. A-2012034754 EXP. 12/31/2026
ENGR REG. NO. E-2014031351 EXP. 12/31/2026
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
DRAWING NUMBER
BUILDING NUMBER
MECH/ELEC/PLUMB/TECH ENGINEER
SPUR DESIGN
312 SW 25TH STREET
OKLAHOMA CITY, OK 73109
(405) 842-6100
FIRE PROTECTION ENGINEER
RATED ENGINEERING
609 S. KELLY AVE., SUITE H2
EDMOND, OK 73003
(405) 210-5814
CIVIL/STRUCTURAL
H2B ENGINEERING
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
PHYSICAL SECURITY
FORCE PROTECT
4015 VITRUVIAN WAY, UNIT 1212
ADDISON, TX 75001
PHONE NUMBER
/8
/2
:1
:0
P
M
ELECTRICAL DETAILS
JMF 72 OF 74ES
100% BID DOCUMENTS
INSTALL DEDICATED
PHARMACY AIR HANDLER
06/11/2026
589A4-25-102
HARRY S. TRUMAN VAMC
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
E-501
SPUR #: 2517
NTS
CONDUIT JOINT CROSSING DETAIL4 NTS
TYPICAL PARAPET AIR TERMINAL DETAIL1NTS
SPLICERS/CONDUCTORS DETAIL2NTS
MECHANICAL UNIT BONDING TERMINAL DETAIL3
DM
T O
G R
O U
N D
R O
D S
T O
G R
O U
N D
B A
R A
T M
A
IN
T E
L B
O A
R D
T
T B
T O
W A
T E
R S
E R
V
IC
E
T O
S T
R U
C T
U R
A L S
T E
E L
T O
A B
O V
E G
R O
U N
D M
E T
A L P
IP
IN
G
T O
C O
N C
R E
T E
-E N
C A
S E
D E
L E
C T
R O
D E
U
F E
R
N
G
MBJ
EBJ
E T
R
E T
R
E T
R
E T
R
E T
R
E T
R
3200AF
3200AT
3P
600 AMPS 480V, 3PH, 3W
ELEC RM E009, NEMA 1
MCC 'MCCB-D8-480VQ' (ETR)
E T
R
4000 AMPS 480Y/277V, 3PH, 4W
MAIN ELEC ROOM E003A, NEMA 1
SWBD 'LVB-B3-277VN' (ETR)
DM
1600AF
1200AT
3P
E T
R
2000 AMPS 480Y/277V, 3PH, 4W
ELEC RM E009, NEMA 1
SWBD 'LVB-C8-277VG' (ETR)
800AF
600AT
3P
E T
R
800AF
600AT
3P
E T
R
'ATS-3' (ETR)
3P
600A
G F
R
(N E
W
E L E
C R
M F
P N
L 'D
P -D
-4
V
Q
11504 FCA
M
800AF
300AT
3P
E T
R
250AF
225AT
3P
400AF
400AT
3P
400 AMPS 480Y/277V, 3PH, 4W
MAIN ELEC ROOM E003A, NEMA 1
DIST PNL 'DPB-B3-277VN' (ETR)
E T
R
XFMR 'T2-D10-120VN' (ETR)
45 KVA
480V – 208Y/120V
3PH, 4W
E T
R
E T
R
(E T
R
E L E
C R
M F
P N
L 'P
P -D
-1
V
N
E T
R
(E T
R
E L E
C R
M F
P N
L 'P
P -D
-1
V
N
ETR
(E T
R
E L E
C R
M F
P N
L 'L
P -D
-2
V
N
3358 FCA
200AF
200AT
3P
800AF
400AT
3P
E T
R
800AF
400AT
3P
E T
R
'ATS-4' (ETR)
3P
400A
E T
R
400 AMPS 480Y/277V, 3PH, 4W
ELEC RM E009, NEMA 1
DIST PNL 'DPB-D8-277VE' (ETR)
G F
R
20AF
20AT
3P
100AF
100AT
3P
E T
R
(E T
R
E L E
C R
M F
P N
L 'L
P -D
-2
V
E
20AS
3P
XFMR 'T4-2-D2' (ETR)
75 KVA
480V – 208Y/120V
3PH, 4W
E T
R
E T
R
(E T
R
E L E
C R
M F
P N
L 'M
P P
-D
-1
V
Q
150AF
150AT
3P
E T
R
400AF
400AT
3P
E T
R
400 AMPS 480V, 3PH, 3W
ELEC RM F403, NEMA 1
DIST PNL 'DP4-D2-277VN' (ETR)
XFMR 'T3-4-D10' (ETR)
75 KVA
480V – 208Y/120V
3PH, 4W
E T
R
E T
R
(E T
R
E L E
C R
M F
P N
L 'P
P -D
-1
V
N
E T
R
200AF
150AT
3P
E T
R
150AF
125AT
3P
M
60AF
60AT
3P
60AS
3P
(E T
R
E L E
C R
M F
P N
L 'M
D P
-D
-2
V
Q
6891 FCA
M
3358 FCA
20AF
20AT
3P
30AS
3P
E T
R
DM
3200AF
3200AT
3P
E T
R
4000 AMPS 480Y/277V, 3PH, 4W
MAIN ELEC ROOM E003A, NEMA 1
SWBD 'LVB-B3-277VN' (ETR)
800AF
400AT
3P
E T
R
600 AMPS 480V, 3PH, 3W
MAIN ELEC ROOM E003A, NEMA 1
MCC 'MCC-B3-480VN' (ETR)
(ETR)
3P
DM
1600AF
1200AT
3P
E T
R
2000 AMPS 480Y/277V, 3PH, 4W
ELEC RM E009, NEMA 1
SWBD 'LVB-C8-277VG' (ETR)
800AF
600AT
3P
800AF
600AT
3P
'ATS-3' (ETR)
3P
600A
E T
R
G F
R
ETR ETR
600 AMPS 480V, 3PH, 3W
ELEC RM E009, NEMA 1
MCC 'MCCB-D8-480VQ' (ETR)
(ETD)
3P
ETD
(ETD)
3P
600 AMPS 480V, 3PH, 3W
MAIN ELEC RM E003A, NEMA 1
MCC 'MCC-B3-480VN' (ETR)
600 AMPS 480V, 3PH, 3W
MAIN ELEC RM E009, NEMA 1
MCC 'MCCB-D8-480VQ' (ETR)
A. ELECTRICAL ONE-LINE DIAGRAMS SHOWN MAY NOT REPRESENT THE
ENTIRE ELECTRICAL SYSTEM FOR EACH BUILDING. THE DIAGRAMS ONLY
REPRESENT THE EQUIPMENT BEING AFFECTED BY THIS SCOPE OF WORK.
B. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT MAY REQUIRE
SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL AFFECTED
EQUIPMENT WITH THE CONTRACTING OFFICER'S REPRESENTATIVE NO LESS
THAN 90 DAYS IN ADVANCE OF ANTICIPATED WORK.
C. FAULT CURRENT CALCULATIONS, WHERE SHOWN, ARE PRELIMINARY.
CONTRACTOR SHALL FIELD VERIFY EXACT ROUTINGS AND REQUIRED
LENGTHS. PROVIDE FINAL CALCULATIONS FOR NEW EQUIPMENT IN
ACCORDANCE WITH SPECIFICATION 26 05 73.
D. ONE-LINE DIAGRAMS ARE BASED ON BEST INFORMATION AVAILABLE. VERIFY
ALL INFORMATION IN FIELD AND ALERT ENGINEER TO DISCREPANCIES.
E. WHERE NEW BREAKERS ARE SHOWN TO BE ADDED TO EXISTING
ELECTRICAL EQUIPMENT PROVIDE AIC RATING AND BREAKER STYLE TO
MATCH EXISTING.
ONE-LINE DIAGRAM GENERAL NOTES
NORMAL POWER STANDBY POWER
TO GEN SWBD
'LVB-H14-277VG'
(ETR)
EQUIPMENT BRANCH
TO
'LVB-E2-277VG'
NCB-4 & NCB-5
(ETR)
M E
C H
R M
E
'A C
A -A
H U
-1
(N E
W
LIFE SAFETY BRANCH
'DS3-4' (ETR)
M E
C H
R M
E
'1 -H
U M
-1
(N E
W
22135
13 13 13
M E
C H
R M
E
'H H
W P
-1
(N E
W
NORMAL POWER
MECH RM E003
'AHU-5'
(ETD)
TO
'LVB-E2-277VG'
NCB-4 & NCB-5
(ETR)
TO GEN SWBD
'LVB-H14-277VG'
(ETR)
EQUIPMENT BRANCH
SPARE
STANDBY POWER
SPARE
SPACE
'SF-1'
SUPPLY AIR FAN
AHU-1
(ETR)
DEDICATED
SPACE
DEDICATED
SPACE
TO SWBD
'LVB-B3-277VN'
INCOMING
LINE
'RF-1'
RETURN AIR FAN
AHU-1
(ETR)
'EF-1'
EXHAUST FAN
TOILETS
(ETR)
'EF-3'
EXHAUST FAN
FUME HOOD
(ETR)
'SF-2'
SUPPLY AIR FAN
AHU-2
(ETR)
'RF-2'
RETURN AIR FAN
AHU-2
(ETR)
'EF-4'
EXHAUST FAN
MECH ROOM VENT
(ETR)
'EF-5'
EXHAUST FAN
ELEC ROOM VENT
(ETR)
'HWP-3'
SNOW MELTING
PUMP
(ETR)
'HRP-1'
HOT WATER PUMP
(HEATING)
(ETR)
'SF-3'
SUPPLY AIR FAN
AHU-3
(ETR)
'RF-3'
RETURN AIR FAN
AHU-3
(ETR)
AHU-5
SPARE
(ETR)
'MDP4-D2-277VN'
(ETR)
'SF-4'
SUPPLY AIR FAN
AHU-4 (EMER)
(ETR)
DEDICATED
SPACE
DEDICATED
SPACE
TO ATS
'ATS-3'
INCOMING
LINE
'RF-4'
RETURN AIR FAN
AHU-4 (EMER)
(ETR)
'EF-10'
(ETR)
'PTS-1'
PNEUMATIC TUBE
SYSTEM
(ETR)
'MDP4-D2-277VQ'
(ETR)
DEDICATED
SPACE
SPARE
'EF-6'
EXHAUST FAN
EM PWR SWBD RM
(ETR)
'EF-7'
EXHAUST FAN
AMBULANCE ENTR
(ETR)
'EF-8'
EXHAUST FAN
GENERAL
(ETR)
STEAM COND.
PUMP
E003
(ETR)
SIZE 1
SPARE
(ETR)
'D-12'
DUMBWAITER
(ETR)
SPARE
'DSP-1'
DUPLEX SUMP
PUMP
(ETR)
'HWP-1'
HOT WATER PUMP
(HEATING)
(ETR)
'HWP-2'
HOT WATER PUMP
(HEATING)
(ETR)
'VP-1'
VACUUM PUMP
(DUPLEX)
(ETR)
SUPPLY AIR FAN
'AHU-6' (ETR)
'CLC-DP-BF3-277VQ'
(ETR)
EXISTING LOAD
(ETR)
SPAC…