Final Drawings Part-3.pdf

PDF 2 MB Posted

Attached to
Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler Federal contract opportunity
Solicitation number
36C25526R0159
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document is a 100% Bid set of electrical construction drawings for the "Install Dedicated Pharmacy Air Handler" project at Harry S. Truman VAMC in Columbia, Missouri (Project 589A4-25-102). The drawings were prepared by Spur Design, LLC and are dated June 9, 2026, with a drawing package consisting of 74 sheets.

The project scope involves mechanical controls and electrical systems supporting the installation of a dedicated pharmacy air handler. Key mechanical systems documented include an Exhaust Fan (EF-1) with motorized damper controls that operates in occupied and unoccupied modes, and a Recirculation Pump (RP-X) for water circulation. The electrical work encompasses power distribution, lighting installation, lightning protection bonding, and control circuits throughout multiple building levels (Basement, Levels 2-3, and Roof). New electrical equipment includes panelboards (DP3-D10-480VQ, PP2-D10-120VN2, PP3-D10-120VN), transformers, variable frequency drives (VFD), and associated disconnects and circuit breakers. The electrical design references existing equipment (ETR) and equipment to be demolished (ETD), with specific attention to HVAC equipment connections (ACA-AHU-11, ACA-AHU-12, humidifiers HUM-11 and HUM-12, unit heaters EUH-1 through EUH-4, and pumps HHWP-1 and HHWP-2). Construction must comply with 2023 NEC, NFPA 101, 2024 IBC, VA seismic design standards, and ASHRAE ventilation standards. The electrical demolition plans indicate removal of existing mechanical equipment, circuits, and conduit infrastructure in affected areas, with reestablishment of remaining circuit continuity as required.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler, newest first.
File Type Posted
07 81 00 Applied Fireproofing.pdf PDF
36C25526R0159 0004.pdf PDF
Final Drawings Part-1.pdf PDF
36C25526R0159 0003.docx DOCX document
Final Drawings Part-2.pdf PDF
PRE-BID SIGN IN ROSTER.pdf PDF
07_8100-001_Fireproofing_Mfr_Literature.pdf PDF
589a4-25-102_Addendum 02_260828.pdf PDF
01 00 00 General Requirements RX.pdf PDF
36C25526R0159 0002.docx DOCX document
Finish schedule from drawings.pdf PDF
01 33 23- Shop Drawings Product DAta and Samples.pdf PDF
finish schedule from specs.pdf PDF
01 00 10 - MEDICAL CENTER REQUIREMENTS RX.pdf PDF
Phasing info.pdf PDF
01 32 16-15 Project Schedules RX.pdf PDF
01 91 00 General Commissioning Requirements RX.pdf PDF
36C25526R0159 0001.docx DOCX document
S02-Final Specifications 1068 pages.pdf PDF
36C25526R0159.docx DOCX document
P09-Final Drawings Part-2 Pages 37.pdf PDF
P09-Final Drawings Part-1 Pages 37.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEQUENCE OF OPERATIONS

EXHAUST FAN (EF-1)

GENERAL DESCRIPTION

The exhaust fan provides general exhaust ventilation to the conditioned space(s) as shown on the drawings.

OPERATING MODES

OCCUPIED MODE

The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.

UNOCCUPIED MODE

The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.

COMPONENT CONTROL LOOPS

EXHAUST FAN – ON/OFF

• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.

• When the HOA switch is in off position, the fan shall be off.

• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.

OCCUPIED MODE:

• The exhaust fan shall be enabled after the EA damper has proven operable.

• The exhaust fan shall be commanded to run and shall maintain a user defined constant speed.

UNOCCUPIED MODE:

The exhaust fan shall be off.

MOTORIZED DAMPER

OCCUPIED MODE:

The motorized damper shall be open. The motorized damper shall open 30 sec (adj.)

prior to activation of the exhaust fan.

UNOCCUPIED MODE:

The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.

EA

M

CT

STARTER

N.C.

M

BI

BO

BI

BO

EA DAMPER STATUS

EA DAMPER

EF STATUS

EF START/STOP

SEQUENCE OF OPERATIONS

RECIRCULATION PUMP (RP-X)

GENERAL DESCRIPTION

The inline pump will operate to recirculate water for the fixtures shown on the drawings.

OPERATING MODES

NORMAL OPERATING MODE:

The pump shall be in normal operating mode at all times.

COMPONENT CONTROLS

PUMP

NORMAL OPERATING MODE:

The pump shall operate at the specified flow rate.

CT

M

P1

BI P1 STATUS

HHR / CHR IN HHR / CHR OUT

VFD

BO

AO

BI

P1 VFD START/STOP

P1 VFD SPEED

P1 VFD FAULT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

/9

/2

:4

:0

A

M

MECHANICAL CONTROLS

DSM 66 OF 73JGD

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE,

COLUMBIA, MO 65201

M-705

SPUR #: 2517No. REVISION DESCRIPTION DATE

NOT TO SCALE

GENERAL EXHAUST FAN (EF-1) TYPICAL CONTROL DIAGRAM2

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.

EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.

EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.

ALARMS DESCRIPTION ALARM ALARM DELAY

EXHAUST AIR DAMPER X X X

EXHAUST AIR DAMPER STATUS X X X

DAMPER

EF START/STOP X X X

EF STATUS X X X

EXHAUST FAN

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-1)

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

PUMP RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.

PUMP IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

PUMP FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

ALARMS DESCRIPTION ALARM ALARM DELAY

PUMP START/STOP X X X

PUMP VFD FAULT X X X

PUMP STATUS X X X

PUMP VFD SPEED X X X

PUMPS

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - HEATING HOT WATER PUMPS (HHWP-X)

12" = 1'-0"

HEATING HOT WATER PUMP (HHWP-X) TYPICAL CONTROL DIAGRAM1

ABBREVIATIONS

LIGHTNING PROTECTION SYMBOLS

STANDARD MOUNTING HEIGHTS

A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK, BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS WITH BUILDING DISCIPLINES.

HOWEVER, COORDINATION WITH OTHER TRADES IS REQUIRED.

D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION REGARDING

SCHEDULE AND PHASING REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF

SERVICES.

E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE

BEFORE THE START OF WORK.

F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE SHUTDOWN. COORDINATE

SERVICE SHUTDOWN FOR ALL EQUIPMENT WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE COMPLETION OF THE PROJECT.

I. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE CONTRACTOR SHALL DOCUMENT

THE VARIATION AND REPORT IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH

THE ENGINEER OF RECORD.

GENERAL NOTES

1P SINGLE-POLE

1PH SINGLE-PHASE

3P THREE-POLE

3PH THREE-PHASE

3W THREE-WIRE

4W FOUR-WIRE

A

A or AMP AMPERE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, OR

AUTOMATIC FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

AIP ABANDONED IN PLACE

ALT ALTERNATE

AMB AMBIENT

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

B

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY-PASS

C

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS OR CANDELA

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED /

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAXIAL CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUED

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CVD CUMULATIVE VOLTAGE DROP

D

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

E

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

ETL EXISTING TO BE RELOCATED

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

F

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

G GROUND OR GENERATOR

GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

H

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

I

IC INSULATION CONTACT

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J

JB OR J-BOX JUNCTION BOX

K

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAH KILOVOLT-AMPERE-HOUR

KVAR KILOVOLT-AMPERE-REACTIVE

KW KILOWATT

KWH KILOWATT-HOUR

KWHM KILOWATT-HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTCP LOCAL TEMPERATURE CONTROL PANEL

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

M

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

N

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NC NORMALLY CLOSED

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, OR PULL BOX, OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PNLBD PANELBOARD

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

ANNOTATION LIGHTING SYMBOLS

R

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

RE REFER TO

REC RECESSED

RELO RELOCATED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SES SERVICE ENTRANCE SECTION

SF SQUARE FEET (FOOT)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SSTV SECURITY SURVEILLANCE TELEVISION

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

U

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V

V VOLT

VA VOLT-AMPERE

VAR VOLT-AMPERE-REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

W

W WATT

WH WATER HEATER

WP WEATHERPROOF

X

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

ELECTRICAL:

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS (TOP)

ANNUNCIATOR PANELS (TOP)

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

GROUND BAR

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (TOP)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES, EXTERIOR (BOTTOM)

RECEPTACLES, GARAGES (BOTTOM)

RECEPTACLES IN EQUIPMENT ROOMS (TOP)

RECEPTACLES ABOVE COUNTERTOPS (TOP)

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)

SAFETY SWITCHES & STARTERS

SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

84" 48" 48" 84" 48" 80" 60"

120" 60" 72" 36" 48" 72" 48"

144" 18" 24" 26" 48" 44" 48"

CEILING

48" 48" 18" 84"

(AFF, AFG UNLESS NOTED OTHERWISE)

1 MECHANICAL KEYNOTE CALL OUT

PLUMBING KEY NOTE CALL OUT

ELECTRICAL KEYNOTE CALL OUT

OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

LIMIT OF DEMOLITION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

EP-101

EP-101

LIGHT FIXTURE, CEILING MOUNTED

A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

= ARROW INDICATES AIMING DIRECTION

LIGHTING TRACK WITH TRACK LIGHT FIXTURES

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

EMERGENCY LIGHT FIXTURE, CEILING MOUNTED

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EMERGENCY BATTERY PACK LIGHT FIXTURE,

WALL MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

LIGHT FIXTURE, WALL MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

LIGHT FIXTURE, BOLLARD

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

LIGHT FIXTURE, POLE MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

CIRCUITING SYMBOLS

HOMERUN TO PANELBOARD

TICK MARKS INDICATE NUMBER OF CONDUCTORS.

DESIGNATIONS ARE PANELBOARD AND

CIRCUIT NUMBERS.

UNSWITCHED HOT CONDUCTORS SHOWN LEADING

NEUTRAL CONDUCTOR

NEUTRAL CONDUCTOR

SWITCHED HOT CONDUCTORS SHOWN TRAILING

GROUND CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY

ISOLATED GROUNDING CONDUCTOR IN RACEWAY

CONCEALED RACEWAY

EXPOSED RACEWAY

RACEWAY TURNING UP

RACEWAY TURNING DOWN

EQUIPMENT TERMINATION

LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)

UNDERGROUND ELECTRIC LINE

OVERHEAD ELECTRIC LINE

RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, MOUNTED 6" ABOVE COUNTER,

TYPE AS INDICATED ABOVE

RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT

INTERRUPTER, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, TWIST-LOCK

RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO

RECEPTACLE DESIGNATIONS AS FOLLOWS:

C = CLOCK HANGER

E = EMERGENCY POWER

GF = GROUND FAULT CIRCUIT INTERRUPTER

IG = ISOLATED GROUND

S = SWITCHED

TR = TAMPER RESISTANT

WP = WEATHER PROOF COVER

WR = WEATHER RESISTANT

XP = EXPLOSION PROOF

MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,

NEMA 5-20R, UNO

WALL SWITCH, SINGLE POLE (LINE VOLTAGE, UNO.)

WALL SWITCH DESIGNATIONS AS FOLLOWS:

2 = TWO-POLE

3 = THREE-WAY

4 = FOUR-WAY

D = DIMMER SWITCH

OS# = OCCUPANCY SENSOR TYPE (LINE-VOLTAGE, UNO.)

RE: OCCUPANCY SENSOR AND SWITCH SCHEDULE

P = SINGLE-POLE, SINGLE-THROW, PILOT LIGHT

K = KEYED-TYPE

M = MOTOR RATED

WP = WEATHER PROOF WITH COVER

OCCUPANCY SENSOR, CEILING MOUNTED

OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER

TO OCCUPANCY SENSOR AND SWITCH SCHEDULE

POWER PACK FOR LIGHTING CONTROL

JUNCTION BOX

RECEPTACLE ON EMERGENCY POWER

RECEPTACLE, ISOLATED GROUND TYPE

PUSH BUTTON, TYPE AS NOTED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED

EMERGENCY SHUNT RELAY

WIRING DEVICE SYMBOLS

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CABLE CONNECTION

LIGHTNING PROTECTION GROUND ROD

LIGHTNING PROTECTION CONDUCTOR

SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION

PANELBOARD ON HOUSEKEEPING PAD

PANELBOARD, RECESS MOUNTED

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES

AMPERES/POLES, CB = CIRCUIT BREAKER TYPE

DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES

AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE

COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER

100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER

SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,

3-POLE, UNO

CONTACTOR

PHOTOCELL

RELAY

TIME SWITCH

LOW-VOLTAGE TRANSFORMER

VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH

100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,

NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

CABINET, RECESS MOUNTED

CABINET, SURFACE MOUNTED

POWER EQUIPMENT SYMBOLS

ELECTRICAL ONE-LINE DIAGRAM SYMBOLS

GENERATOR,

SEPARATELY DERIVED

SOURCE, TYPE AND

RATINGS AS INDICATED

GENERATOR, NON-

SEPARATELY DERIVED

SOURCE, TYPE AND

RATINGS AS INDICATED

AUTOMATIC TRANSFER

SWITCH WITH BYPASS TYPE

AND RATINGS AS INDICATED

PANELBOARD,

SINGLE-SECTION,

RATINGS PER

SCHEDULES

PANELBOARD,

MULTI-SECTION,

RATINGS PER

SCHEDULES

TRANSFORMER

TRANSFORMER,

SHIELDED

600AF

500AT

3P

400AS

3P

225AF

LPS-R

DRAWOUT CIRCUIT

BREAKER, RATINGS

AS INDICATED

600AF

500AT

3P

CIRCUIT BREAKER,

RATINGS AS

INDICATED

FUSED DISCONNECT

SWITCH, RATINGS

AS INDICATED

400AS

3P

225AF

LPS-R

NEMA 1

COMBINATION FUSED

SWITCH AND STARTER,

RATINGS AS

INDICATED

GROUND-FAULT RELAY

VARIABLE FREQUENCY

DRIVE WITH

DISCONNECT, RATINGS

AS INDICATED

CONTACT, CLOSED

FEEDER TAGCAPACITOR

COMBINATION CIRCUIT

BREAKER AND

STARTER, RATINGS AS

INDICATED

SHUNT-TRIP RELAY

KIRK-KEY INTERLOCK

SURGE PROTECTION

DEVICE

CURRENT TRANSFORMER

CONTACT, OPEN

HEATER

AMMETERSURGE ARRESTER

VOLTMETER

COMBINATION DIGITAL

AMMETER/VOLTMETER

UTILITY METER

RELAY

GROUND CONNECTION

POTENTIAL TRANSFORMER

GROUND CONNECTION

WITH TEST WELL

MOTOR

200A DEAD-FRONT ELBOW

600A DEAD-FRONT ELBOW

DEAD-FRONT SPLITTER

FAULT INDICATOR

a

A1

GF

OR

PP

J

EPO

ES

EMERGENCY BATTERY PACK LIGHT FIXTURE,

CEILING MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

AM

VM

DM

ST

KK

GFR

M

SPD

R

E/G 400A/3P

275KW STANDBY

480Y/277V, 3PH, 4W

E/G 400A/3P

275KW STANDBY

480Y/277V, 3PH, 4W

200A 3P

ATS#

200A 3P

ATS#

TX#

TX#

LP1

1,3,5

UE

OE

a

A1

A1E a

X1E

X1E

Y1E

Y1E

A1

A1

A1

OR

OR

T

100/3

100/3/70

100/3/70/1

100/3/CB

C

PC

R

TS

CODES, STANDARDS, AND EXECUTIVE ORDERS

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS. REFERENCE

RELEVANT ADDENDA FOR EACH OF THE ADOPTED CODES AND STANDARDS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL)

(HTTP://WWW.CFM.VA.GOV/TIL/).

• 2024 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2024 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2024 NATIONAL FIRE CODES (NFPA)

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2024 INTERNATIONAL MECHANICAL CODE

• 2023 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2024 INTERNATIONAL PLUMBING CODE (IPC)

• 2022 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2022 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

• 2022 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2023 STEEL CONSTRUCTION MANUAL (16TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR

PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION SPECIFICATION.

• 2022 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2022 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

• 2024 PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.).

VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY

SYSTEM WIDE.

TRANSFER SWITCH,

RATINGS AS INDICATED

ATS = AUTOMATIC

TRANSFER SWITCH

MTS = MANUAL

TRANSFER SWITCH

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ELECTRICAL LEGEND AND

ABBREVIATIONS

JMF 67 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

E-001

SPUR #: 2517No. REVISION DESCRIPTION DATE

C B

E

E009

E002B

E002H E002I E002J E002K

E003

C O

R R

E001E

DN

UP

UPDN

F001B

F003*

JAN.

VEST.

CORR.

STAIR

#11

HATCH TO

TUNNEL BELOW

ELEV

#11

ELEV

#10

ELEV

#9

F023A

CBF3

F024

F001A

F004

F021

F018

F020 F019

F017 F016

F015A

F015

F014

C B

F

F005 F010

F012

F013

F011 F036 F009A

F003 F006 F007 F008 F009

CBF5

F001

F002A

F002

CBF1

E010

E008

E007

E006

CBE2

CBE5

CBE2

E004

E005

F037

A024A

B042 B048 B051B039AB039

E001K

E001H

E001L

E002F

E002E

E002D E002C

E002A

E002

A001

A002

A003 A007 A009 A010A A010 A019 A020

CORR-1

F029 F028

F027A

F028A F025

F025A

F027 F026

F034

F034A

F035A

F035

F030 F031 F032 F033

F030A

F023 F022

CBE4

A009A

C B

F

A020A

F029A

E001F

E001J

CORR.

CORR.

CORR.

C O

R R

C O

R R

E001BE001D

E001A

OFFICETEAM ROOM

NARCOTIC

VAULT

E001C

OFFICE

STERILE PROCESSING AREA

NON-HAZARD IV PREP

IV STORAGE ROOM

STORAGE

CORRIDOR

HAZARDOUS

DRUG STORAGE

HAZARDOUS

IV PREP

OFFICE

STR #10

DN

ROOF BELOW

ROOF BELOW

F400

F401F402

E305

F396

UP

DN

UP

DN

DN

#10

#11

#9

F315

F312.1

C3F3

E312

E306

E308

E310

E311

E329 E332 E333 E334 E338

E339

E340

E341

E336 E337

E331

E328

E327

E326

E324

E323 E322

E321

E319

C3E2

E320

E318 E317

C3F1

E316

E315 E314 E313

E300

E307

E304

C3F5

E309

F395

S T

R

F397

F300

F303

F302

F322

F304

F307

F

F305

F310 F309

F312

S T

R

F312.2 F311

E325

C E

C3E4

C E

E330

E335

F348 F346 F345 F343 F340 F339 F338 F337

C3F9

F349

F350

F321

F320

F317

F316

C F

F347 F344

F342 F341

F336

F324 F325 F326

F334

F333

F335

F332

F331

F327 F328 F329

F330

F323

F318

F314

C3F7

C F

F319

E A

F361 F359

F364 F360

F363 F362

F386

F372 F371

F375 F376 F377 F378

F382 F381 F380

F389

F391

F392

F393

F390

F385 F383

F358

F352 F353 F354 F355 F356

F357

F366 F367 F368

F370

F379

F369

F388

F398

F365

E253E210

F252

F253

ELECT.

CLOSET

RESTROOM

DN

UP

DN

F

F E

FE

C2E8

C2E7

C2E12

F210 F211 F212 F214 F215 F217 F235

F236 F239 F240 F267 F266 F265

F269

C2F23

F268 F264 F263

F210A C2F3

F204

C2F1

F201

F202

F206C F206D

C2F7

F203

C2E10

F224

C2F8

F206B F206A

F205

F242

F237

F206

F207

C2F20

E201

C2F20

F256

F245

F241

C F

F231

F223

C2F14 F257

F230

F232

F219

F238

F233

C2F16

F234

F243

F246

C F

E207

F209

C2F4

C2F6

F216

F208

C F

F209A

E204 C2E6

F247

F244

C2F17

F225

F228

E205A

C2E3

E226 E225 E223 E222

F218

C2F12

F222

C E

E212A

E224A E214

E213

E205

F221

C2F19

F222A F227

E208

E217

E211

E

C E

C F

F250

F255

C F

F226

E255

E216

C2E1

E220

F211A

F248

F249

C F

F220

E211A

E254

E256

C F

F213A

F213

E221

E219

E218

C F

E215

F271 F260

F270 F261

F262

C F

F273 F258

F272 F259

F229

F200

F274

F

E209A

F275

F213B

E203

E241

E239

E237

E236

C2E9

C2E11

E229

E227E235 E234 E233 E232 E230

E238

C2E16

C2E14

C2E17 E244

E240

E242 E243 E249

C2E18

E245

C E

E246 E247

E248 E250

E231

E228

C2E13

E251 E252

F251

F

F

F

F

E202

F227A

OPEN TO BELOW OPEN TO BELOW

TLT. ALCOVE

CORR.

CORR.

SOILED

UTIL.

ST. TLT.

CLEAN

DISPATCH

CORR.

CORR.

C O

R R

TLT.

ST. WK.

CORR.

C O

R R

C O

R R

TLT.

CLEAN

STORAGE

CORR.

JAN.

C O

R R

SURG.

SUPPLIES

TLT. TLT.

CORR.

SIGNAL

CORR.

CORR.

STERIL.

C O

R R

ALCOVE

ALCOVE

CORR.

SOILED

UTIL.

TLT.

TLT.

CORR.

TELE/ DATA

ELECTRICAL

CORR.

CORR.

TLT.

CORR.

C O

R R

CLEAN UTIL.

CORR.

CORR.

TLT.

TLT.

CORR.

ELEV

#11

ELEV

#10

ELEV

#9

STAIR

#11STAIR

#10

ELEC.

CLOSET

E212

CORR.

C O

R R

C O

R R

C O

R R

CORR.

CORR.

C O

R R

A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED

OTHERWISE.

B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-

ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS

AS REQUIRED TO MAINTAIN OPERATION.

C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION

WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE

VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE

PROPERTY OF THE VA UNLESS NOTED OTHERWISE.

D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE

FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.

E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL

DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND

REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.

F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND

CONDUIT ALL THE WAY BACK TO SOURCE.

G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA

OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM

PANELBOARD.

GENERAL NOTES

H

3 4

6 7 8 9

G

F

E

D

10 112

C

E.1

D.7

B

6.3 11.5 1312

EP401

ED401

EP401

ED401

MECHANICAL ROOM

E003

MAIN ELECTRICAL ROOM

E003A

PHARMACY

E001

ELECTRICAL ROOM

E009

ED401

H

7 8 9

G

F

E

D

10 11

C

E.1

D.7

B

11.5 1312

EL401

MECHANICAL PENTHOUSE

ROOF

H

3 4 5 6 7 8 9

G

F

E

D

10 112

C

E.1

D.7

B

6.3 11.5 1312

EP401

1MECHANICAL PENTHOUSE

F399

ED401

ED401

EL401

H

3 4 5 6 7 8 9

G

F

E

D

10 112

C

E.1

D.7

B

6.3 11.5 1312

EP401

KEY PLAN

N

SCOPE AREA

BLDG 1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ELECTRICAL REFERENCE PLANS

JMF 68 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

E-101

SPUR #: 2517

N

3/64" = 1'-0"

ELECTRICAL REFERENCE PLAN - BASEMENT1

N

3/64" = 1'-0"

ELECTRICAL REFERENCE PLAN - ROOF4

N

3/64" = 1'-0"

ELECTRICAL REFERENCE PLAN - LEVEL 33

N

3/64" = 1'-0"

ELECTRICAL REFERENCE PLAN - LEVEL 22

No. REVISION DESCRIPTION DATE

DN

F361 F359

F364 F360

F363 F362

F372 F371

F353 F354 F355 F356

F366 F367 F368

F370

F369

F365

E001

E002K

E001K

E001H

E001L

E001F

E001J E001D

TEAM ROOM

STERILE PROCESSING AREA

NON-HAZARD IV PREP

IV STORAGE ROOM

HAZARDOUS

DRUG STORAGE

HAZARDOUS

IV PREP

OFFICE

A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED

OTHERWISE.

B. WHERE PORTIONS OF THE CIRCUIT ARE REMOVED OR ABANDONED, RE-

ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS

AS REQUIRED TO MAINTAIN OPERATION.

C. THE VA SHALL MAINTAIN THE RIGHT OF FIRST REFUSAL TO ALL DEMOLITION

WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE

VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE

PROPERTY OF THE VA UNLESS NOTED OTHERWISE.

D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE

FLUSHED WITH THE NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.

E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL WIRING

DEVICES AND/OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND

REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.

F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND

CONDUIT ALL THE WAY BACK TO SOURCE PANELBOARD.

DEMOLITION GENERAL NOTES

6 7 8 9

D

10 11

C

D.7

B

6.3 11.5

PHARMACY

E001

STORAGE

E001E

MFMR EXEC OFFICE

E002K

CLINICAL RESEARCH

E002J

R.C.O. R&D

E002I

OFFICE

E002H

WORK ROOM

E002B

CORRIDOR

CBE3

WOMAN TOILET

E010

MEN TOILET

E008

1 1 1

CORRIDOR

CBE35

CORRIDOR

CBE3F1

TEAM ROOM

E001D

KEY PLAN

N

SCOPE AREA

BLDG 1

3 4 5 62

B

ACA-AHU-5

(ETD)

MCC

'MCC-B3-480VN'

(ETR)

(ETD)

MECHANICAL ROOM

E003

MAIN ELECTRICAL ROOM

E003A

(ETR)

ACA-AHU-4

E-601

COMPRESSOR

(ETD)

ACA-ET-1ACA-HWP-2

ACA-HX-2

ACA-AHU-17

ACA-AHU-16

(ETR)

(ETR)(ETR)

(ETR)

(ETR)

H

8 9

G

F

3-SH1

3-SH3

3-SH2

(ETD)

(ETD)

(ETD)

78,80

PP3-D10-120VN

82,84

PP3-D10-120VN

74,76

PP3-D10-120VN

INTAKE

F358

PHARMACIST OFFICE

F357

8 9

D

C

B

(ETD)

1-SH1

1-SH3

1-SH2

1-SH4

1-SH5

(ETD)

(ETD)

(ETD)

1-1-TU-1

1-EF-3

(ETD)

(ETD)

(ETL)

20,22

PPB-C8-120VN

17,19

PPB-C8-120VN

21,23

PPB-C8-120VN

25,27

PPB-C8-120VN

24,26

PPB-C8-120VN

31,33,35

PPB-C8-120VC2

STORAGE

E001E

ELECTRICAL ROOM

E009

PHARMACY

E001

CORRIDOR

CBE2

PNL 'PPB-C8-120VN'

(ETR)

REF 3/EP401

MCC

'MCCB-D8-480VQ'

(ETR)

E-601

D

10 11

C

11.5

(EX) EF

(ETD)

MECHANICAL PENTHOUSE

INTERSTITIAL

REF 2/EP401

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ELECTRICAL DEMOLITION PLANS

JMF 69 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

ED401

SPUR #: 2517

ELECTRICAL KEYNOTES

1 EXISTING CEILING SYSTEM SHALL REMAIN.

2 EXISTING CEILING SYSTEMS ARE TO BE DEMOLISHED AS PART OF THIS

PROJECT FOR NEW MECHANICAL WORK. ALL LIGHTING AND LIGHTING

CONTROLS SYSTEMS IN AFFECTED AREA TO REMAIN DURING ALL PHASES OF

CONSTRUCTION. PROTECT AND TEMPORARILY SUPPORT LIGHT FIXTURES

AND DEVICES WHERE NECESSARY. CEILING SHALL BE REINSTALLED ONCE

MECHANICAL WORK IS COMPLETED.

3 EXISTING MECHANICAL EQUIPMENT ABOVE CEILING AND CORRESPONDING

ACCESSORIES ARE TO BE DEMOLISHED AS PART OF THIS PROJECT. REMOVE

ASSOCIATED CIRCUITS, CONDUITS, BOXES, AND SUPPORTS BACK TO THE

TERMINATION POINT AT THE EXISTING FEEDER BREAKER. RELABEL THE

FEEDER BREAKER AS "SPARE".

4 EXISTING EXHAUST FAN TO BE DEMOLISHED. PRESERVE EXISTING CIRCUIT

AND EXTEND OR REROUTE TO NEW LOCATION.

5 MAINTAIN CIRCUITRY AND CORRESPONDING ACCESSORIES OF EXISTING

MECHANICAL EQUIPMENT LOCATED ABOVE CEILING. EXTEND OR REROUTE TO

NEW LOCATION.

10 DISCONNECT AND REMOVE EXISTING CIRCUIT, BACK TO EXISTING MCC.

REMOVE EXISTING DISCONNECT.

22 ALL ACCESSORIES AND ELECTRICAL CONTROLS SERVING EXISTING

COMPRESSOR TO BE DEMOLISHED BACK TO SOURCE.

N

1/8" = 1'-0" REF: 1/ E-101

REFLECTED CEILING DEMOLITION PLAN - BASEMENT1

N

1/8" = 1'-0" REF: 1/ E-101

ENLARGED DEMOLITION PLAN - MECHANICAL RM E003 - BASEMENT3

N

1/8" = 1'-0" REF: 3/ E-101

ENLARGED DEMOLITION PLAN - LEVEL 32

N

1/8" = 1'-0" REF: 1/ E-101

ENLARGED DEMOLITION PLAN - BASEMENT5

N

1/8" = 1'-0" REF: 3/ E-101

ENLARGED DEMOLITION PLAN - EXISTING ROOFTOP - INTERSTITIAL LEVEL4

A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED

OTHERWISE.

B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-

ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS

AS REQUIRED TO MAINTAIN OPERATION.

C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION

WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE

VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE

PROPERTY OF THE VA UNLESS NOTED OTHERWISE.

D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE

FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.

E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL

DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND

REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.

F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND

CONDUIT ALL THE WAY BACK TO SOURCE.

G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA

OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM

PANELBOARD.

GENERAL NOTES

D

10 11

C

11.5

LP3-D2-277VE

MECHANICAL PENTHOUSE

F399

(ETR)

STAFF LOUNGE

E305

(ETR)

(ETR)(ETR)

1-HUM-12

1-HUM-11

EUH-1

HHWP-2

F1E

F1E

ACA-AHU-12

ACA-AHU-11

EUH-2

D

10 11

C

11.5 12

BOND TO EXISTING

SYSTEM ON

ABOVE ROOF

ROOF DRAIN

(RELO)

MECHANICAL PENTHOUSE

ROOF

BOND TO EXISTING

SYSTEM ON

BELOW ROOF

BOND TO EXISTING

SYSTEM ON

ABOVE ROOF

ABOVE ROOF

BELOW ROOF

REA-LV-1

(NEW)

KEY PLAN

N

SCOPE AREA

BLDG 1

E

D

10 11

C

E.1

D.7

11.5 12

D1 D1

D1D1

MECHANICAL PENTHOUSE

INTERSTITIAL

(ETR)

#11

STAIR

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ELECTRICAL LIGHTING PLAN

JMF 70 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

EL401

SPUR #: 2517

N

1/4" = 1'-0" REF: 3/ E-101

ENLARGED LIGHTING PLAN - MECHANICAL PENTHOUSE F399 - LEVEL 32

N

1/4" = 1'-0" REF: 4/ E-101

ENLARGED LIGHTNING PROTECTION PLAN - MECHANICAL PENTHOUSE ROOF1

ELECTRICAL KEYNOTES

7 REUSE POWER FROM EXISTING EGRESS LIGHTING CIRCUIT #18 ON LIFE

SAFETY PANEL 'LP3-D2-277VE' VIA THE NEAREST EXISTING LIGHT FIXTURE

POWERED BY THIS CIRCUIT AS SHOWN ON PLANS.

8 EXISTING LIGHTNING PROTECTION SYSTEM MAY NEED TO BE SHIFTED

DURING CONSTRUCTION OF MECHANICAL PENTHOUSE WALLS. PROTECT

EXISTING SYSTEM DURING CONSTRUCTION. PROVIDE NEW SECTIONS OF

CONDUCTOR OR MOUNTING BRACKETS AS NEEDED.

21 REUSE POWER AND CONTROLS FROM EXISTING LIGHTING CIRCUIT VIA THE

NEAREST LIGHT FIXTURE WITHIN THE INTERSTITIAL SPACE.

No. REVISION DESCRIPTION DATE

N

1/8" = 1'-0"

ENLARGED LIGHTING PLAN - MECHANICAL PENTHOUSE INTERSTITIAL3

DN

A. DASHED DEVICES INDICATE DEVICES TO BE DEMOLISHED UNLESS NOTED

OTHERWISE.

B. WHERE PORTIONS OF CIRCUIT ARE REMOVED OR ABANDONED, RE-

ESTABLISH CIRCUIT CONTINUITY FOR REMAINING PORTIONS OF CIRCUITS

AS REQUIRED TO MAINTAIN OPERATION.

C. THE VA SHALL MAINTAIN RIGHT TO FIRST REFUSAL TO ALL DEMOLITION

WASTE TO BE REMOVED. ALL OTHER ITEMS OF INTEREST OR VALUE TO THE

VA THAT MAY BE UNCOVERED DURING DEMOLITION SHALL REMAIN THE

PROPERTY OF THE VA UNLESS NOTED OTHERWISE.

D. FOR ELECTRICAL DEVICES INDICATED TO REMAIN, EXTEND BOXES TO BE

FLUSHED WITH NEW FINISH ON EXISTING WALLS, WHERE REQUIRED.

E. COORDINATE REMOVAL OF ALL EXISTING CONDUIT AND ELECTRICAL

DEVICES AND/ OR EQUIPMENT IN WALLS TO BE REMOVED. PATCH AND

REPAIR ALL OPENINGS IN GYPSUM BOARD THAT ARE EXISTING TO REMAIN.

F. FOR CIRCUITS BEING COMPLETELY DEMOLISHED, REMOVE CABLE AND

CONDUIT ALL THE WAY BACK TO SOURCE.

G. ALL RECEPTACLES, UPS SYSTEMS, AND PDUS TO BE DEMOLISHED IN AREA

OF WORK. REMOVE CONDUIT AND CONDUCTORS BACK TO UPSTREAM

PANELBOARD.

GENERAL NOTES

D

C

ATS 'ATS-3' (ETR)

MCC

'MCCB-D8-480VQ'

(ETR)

ATS 'ATS-1' (ETR)

ATS 'ATS-4' (ETR)

XFMR 'TB-D8-120VE'

(ETR)

PNL 'LPB-C8-120VE'

(ETR)

PNL 'DPB-D8-120VE'

(ETR)

PNL 'PPB-D8-120VC'

(ETR)

XFMR

'TB-D8-120VC-A'

(ETR)

XFMR (ETR)

XFMR 'TB-C8-120VC'

(ETR)

PNL 'LPB-C8-277VC'

(ETR)

PNL 'PPB-C8-120VC'

(ETR)

PNL

'PPB-C8-120VC-A'

(ETR)

PNL 'DPB-D8-277VE'

(ETR)

PNL 'LPB-D8-277VE'

(ETR)

SWBD

'LVB-C8-277VG'

(ETR)

PNL 'DPB-C8-480VQ'

(ETR)

PNL 'PPB-C8-120VN'

(ETR)

PNL 'PPB-C8-120VC2'

(ETR)

GROUNDING BAR

(ETR)

ELECTRICAL ROOM

E009

1-1-TU-1

(RELO)

PHARMACY

E001

REF 5/ED401

D

10 11

C

11.5

2,4,6

DP3-D10-480VQ

1,3,5

DP3-D10-480VQ

PP2-D10-120VN2

MECHANICAL

PENTHOUSE

F399

HHWP-2

14,16,18

DP3-D10-480VQ

ELECTRICAL ROOM

F396

PNL 'DP3-D10-480VQ'

(NEW)

PNL 'PP3-D10-120VC'

(ETR)

PNL 'PP3-D10-120VN'

(ETR)

XFMR 'T3-3-D10'

(ETR)

XFMR 'T3-4-D10'

(ETR)

'DS3-3' (ETR)

'DS3-4' (ETR)

1-HUM-11

1-HUM-12

30/3

60/3

EUH-1

19,21,23

DP3-D10-480VQ

ACA-AHU-12

ACA-AHU-11

7,9,11

DP3-D10-480VQ

8,10,12

DP3-D10-480VQ

30/3

30/3

EUH-2

25,27,29

DP3-D10-480VQ

D.7

PNL 'PP2-D10-120VC'

(ETR)

PNL 'LP2-D10-277VC'

(ETR)

PNL

'PP2-D10-120VN3'

(ETR)

XFMR

'T-PP2-D10-120VN-3'

(ETR)

XFMR 'T2-D10-120VN'

(ETR)

PNL

'PP2-D10-120VN2'

(ETR)

PNL

'PP2-D10-120VN1'

(ETR)

PNL 'LP2-D10-277VN'

(ETR)

200A/3 (ETR)

ELECTRICAL ROOM

F252

KEY PLAN

N

SCOPE AREA

BLDG 1

3 4 5 62

B

MCCB-D8-480VQ

SWBD

'DPB-B3-277VC'

(ETR)

SWBD

'DPB-B3-277VN'

(ETR)

SWBD

'LVB-B3-277VN'

(ETR)

MCC

'MCC-B3-480VN'

(ETR)

ATS 'ATS-2' (ETR)

MAIN ELECTRICAL ROOM

E003A

MECHANICAL ROOM

E003

1-HUM-10 60/3

MCCB-D8-480VQ

(ETR)

ACA-AHU-4

(NEW)

HHWP-1

ACA-AHU-10

(NEW)

(NEW)

MCCB-D8-480VQ

HX-4/HWP-5

(ETR) 12

ACA-ET-1

ACA-HWP-2

ACA-HX-2

ACA-AHU-17

ACA-AHU-16

(ETR)

(ETR)

(ETR)

(ETR)

(ETR)

ACA-HX-1

(ETR)

ACA-HWP-1

(ETR)

D

10 11

C

11.5

ACA-RF-12

ACA-EF-1

(NEW)

MECHANICAL PENTHOUSE

INTERSTITIAL

13,15,17

DP3-D10-480VQ

(NEW)

EUH-4

EUH-3

(NEW)

(NEW)

20,22,24

DP3-D10-480VQ

26,28,30

DP3-D10-480VQ

32,34,36

MPP4-D2-120VQ

REF 4/ED401

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ENLARGED POWER PLANS

JMF 71 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

EP401

SPUR #: 2517

N

1/4" = 1'-0" REF: 1/ E-101

ENLARGED POWER PLAN - ELECTRICAL ROOM E009 - BASEMENT3

N

1/4" = 1'-0" REF: 3/ E-101

ENLARGED POWER PLAN - MECHANICAL PENTHOUSE - LEVEL 31

N

1/4" = 1'-0" REF: 2/ E-101

ENLARGED POWER PLAN - ELECTRICAL ROOM F252 - LEVEL 25

N

1/4" = 1'-0" REF: 1/ E-101

ENLARGED POWER PLAN - MECHANICAL ROOM E003 - BASEMENT4

ELECTRICAL KEYNOTES

9 REROUTE OR EXTEND EXISTING CIRCUIT PREVIOUSLY SERVING FORMER

MECHANICAL EQUIPMENT AT THIS LOCATION FROM EXISTING CONTROL

DEVICE. SEE ONE-LINE DIAGRAMS FOR MODIFICATIONS REQUIRED FOR

CIRCUIT.

12 DISCONNECT TO BE PROVIDED BY DIVISION 23 CONTRACTOR.

No. REVISION DESCRIPTION DATE

N

1/4" = 1'-0"

ENLARGED POWER PLAN - MECHANICAL PENTHOUSE INTERSTITIAL2

SPRING NUT

CONDUIT COMPRESSION

FITTING

JUNCTION BOX (SIZE AS

REQUIRED)

STEEL EXPANSION

ANCHOR

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

15" FLEXIBLE GALVANIZED STEEL

CONDUIT WITH CONDUCTORS & GREEN

INSULATED EQUIPMENT GROUNDING

CONDUCTOR.

CONDUIT,

TYP.

BEAM CLAMP, TYP.

[914mm]

CONDUIT TRAPEZE

PER SD260533-02,

TYP.

JUNCTION BOX, TYP (SIZE

AS REQUIRED)

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

SEISMIC OR EXPANSION

JOINT. FIELD VERIFY

ACTUAL CONDITIONS &

LOCATIONS.

M

IN

IM

U

M

PARAPET WALL

ROOF

AIR TERMINAL

ADHESIVE TYPE AIR TERMINAL

BASE MOUNTED VERTICALLY

LIGHTNING PROTECTION

CONDUCTOR

ADHESIVE STYLE

CABLE FASTENER

LIGHTNING PROTECTION

CONDUCTOR

UNIVERSAL PARALLEL

CABLE SPLICER

BUTT END STRAIGHT

CABLE SPLICER

PARALLEL CABLE

SPLICER

LIGHTNING PROTECTION

BONDING CONDUCTOR

TO BONDS

ADHESIVE STYLE CABLE

FASTENER MOUNTED TO

ROOF

LIGHTNING PROTECTION

CONDUCTOR

CABLE FASTENER WITH

STAINLESS STEEL

HARDWARE, CAULK

PENETRATIONS

BONDING PLATE MOUNTED

WITH STAINLESS STEEL

FASTENERS, CAULK

PENETRATIONS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

/8

/2

:1

:0

P

M

ELECTRICAL DETAILS

JMF 72 OF 74ES

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

E-501

SPUR #: 2517

NTS

CONDUIT JOINT CROSSING DETAIL4 NTS

TYPICAL PARAPET AIR TERMINAL DETAIL1NTS

SPLICERS/CONDUCTORS DETAIL2NTS

MECHANICAL UNIT BONDING TERMINAL DETAIL3

DM

T O

G R

O U

N D

R O

D S

T O

G R

O U

N D

B A

R A

T M

A

IN

T E

L B

O A

R D

T

T B

T O

W A

T E

R S

E R

V

IC

E

T O

S T

R U

C T

U R

A L S

T E

E L

T O

A B

O V

E G

R O

U N

D M

E T

A L P

IP

IN

G

T O

C O

N C

R E

T E

-E N

C A

S E

D E

L E

C T

R O

D E

U

F E

R

N

G

MBJ

EBJ

E T

R

E T

R

E T

R

E T

R

E T

R

E T

R

3200AF

3200AT

3P

600 AMPS 480V, 3PH, 3W

ELEC RM E009, NEMA 1

MCC 'MCCB-D8-480VQ' (ETR)

E T

R

4000 AMPS 480Y/277V, 3PH, 4W

MAIN ELEC ROOM E003A, NEMA 1

SWBD 'LVB-B3-277VN' (ETR)

DM

1600AF

1200AT

3P

E T

R

2000 AMPS 480Y/277V, 3PH, 4W

ELEC RM E009, NEMA 1

SWBD 'LVB-C8-277VG' (ETR)

800AF

600AT

3P

E T

R

800AF

600AT

3P

E T

R

'ATS-3' (ETR)

3P

600A

G F

R

(N E

W

E L E

C R

M F

P N

L 'D

P -D

-4

V

Q

11504 FCA

M

800AF

300AT

3P

E T

R

250AF

225AT

3P

400AF

400AT

3P

400 AMPS 480Y/277V, 3PH, 4W

MAIN ELEC ROOM E003A, NEMA 1

DIST PNL 'DPB-B3-277VN' (ETR)

E T

R

XFMR 'T2-D10-120VN' (ETR)

45 KVA

480V – 208Y/120V

3PH, 4W

E T

R

E T

R

(E T

R

E L E

C R

M F

P N

L 'P

P -D

-1

V

N

E T

R

(E T

R

E L E

C R

M F

P N

L 'P

P -D

-1

V

N

ETR

(E T

R

E L E

C R

M F

P N

L 'L

P -D

-2

V

N

3358 FCA

200AF

200AT

3P

800AF

400AT

3P

E T

R

800AF

400AT

3P

E T

R

'ATS-4' (ETR)

3P

400A

E T

R

400 AMPS 480Y/277V, 3PH, 4W

ELEC RM E009, NEMA 1

DIST PNL 'DPB-D8-277VE' (ETR)

G F

R

20AF

20AT

3P

100AF

100AT

3P

E T

R

(E T

R

E L E

C R

M F

P N

L 'L

P -D

-2

V

E

20AS

3P

XFMR 'T4-2-D2' (ETR)

75 KVA

480V – 208Y/120V

3PH, 4W

E T

R

E T

R

(E T

R

E L E

C R

M F

P N

L 'M

P P

-D

-1

V

Q

150AF

150AT

3P

E T

R

400AF

400AT

3P

E T

R

400 AMPS 480V, 3PH, 3W

ELEC RM F403, NEMA 1

DIST PNL 'DP4-D2-277VN' (ETR)

XFMR 'T3-4-D10' (ETR)

75 KVA

480V – 208Y/120V

3PH, 4W

E T

R

E T

R

(E T

R

E L E

C R

M F

P N

L 'P

P -D

-1

V

N

E T

R

200AF

150AT

3P

E T

R

150AF

125AT

3P

M

60AF

60AT

3P

60AS

3P

(E T

R

E L E

C R

M F

P N

L 'M

D P

-D

-2

V

Q

6891 FCA

M

3358 FCA

20AF

20AT

3P

30AS

3P

E T

R

DM

3200AF

3200AT

3P

E T

R

4000 AMPS 480Y/277V, 3PH, 4W

MAIN ELEC ROOM E003A, NEMA 1

SWBD 'LVB-B3-277VN' (ETR)

800AF

400AT

3P

E T

R

600 AMPS 480V, 3PH, 3W

MAIN ELEC ROOM E003A, NEMA 1

MCC 'MCC-B3-480VN' (ETR)

(ETR)

3P

DM

1600AF

1200AT

3P

E T

R

2000 AMPS 480Y/277V, 3PH, 4W

ELEC RM E009, NEMA 1

SWBD 'LVB-C8-277VG' (ETR)

800AF

600AT

3P

800AF

600AT

3P

'ATS-3' (ETR)

3P

600A

E T

R

G F

R

ETR ETR

600 AMPS 480V, 3PH, 3W

ELEC RM E009, NEMA 1

MCC 'MCCB-D8-480VQ' (ETR)

(ETD)

3P

ETD

(ETD)

3P

600 AMPS 480V, 3PH, 3W

MAIN ELEC RM E003A, NEMA 1

MCC 'MCC-B3-480VN' (ETR)

600 AMPS 480V, 3PH, 3W

MAIN ELEC RM E009, NEMA 1

MCC 'MCCB-D8-480VQ' (ETR)

A. ELECTRICAL ONE-LINE DIAGRAMS SHOWN MAY NOT REPRESENT THE

ENTIRE ELECTRICAL SYSTEM FOR EACH BUILDING. THE DIAGRAMS ONLY

REPRESENT THE EQUIPMENT BEING AFFECTED BY THIS SCOPE OF WORK.

B. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT MAY REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL AFFECTED

EQUIPMENT WITH THE CONTRACTING OFFICER'S REPRESENTATIVE NO LESS

THAN 90 DAYS IN ADVANCE OF ANTICIPATED WORK.

C. FAULT CURRENT CALCULATIONS, WHERE SHOWN, ARE PRELIMINARY.

CONTRACTOR SHALL FIELD VERIFY EXACT ROUTINGS AND REQUIRED

LENGTHS. PROVIDE FINAL CALCULATIONS FOR NEW EQUIPMENT IN

ACCORDANCE WITH SPECIFICATION 26 05 73.

D. ONE-LINE DIAGRAMS ARE BASED ON BEST INFORMATION AVAILABLE. VERIFY

ALL INFORMATION IN FIELD AND ALERT ENGINEER TO DISCREPANCIES.

E. WHERE NEW BREAKERS ARE SHOWN TO BE ADDED TO EXISTING

ELECTRICAL EQUIPMENT PROVIDE AIC RATING AND BREAKER STYLE TO

MATCH EXISTING.

ONE-LINE DIAGRAM GENERAL NOTES

NORMAL POWER STANDBY POWER

TO GEN SWBD

'LVB-H14-277VG'

(ETR)

EQUIPMENT BRANCH

TO

'LVB-E2-277VG'

NCB-4 & NCB-5

(ETR)

M E

C H

R M

E

'A C

A -A

H U

-1

(N E

W

LIFE SAFETY BRANCH

'DS3-4' (ETR)

M E

C H

R M

E

'1 -H

U M

-1

(N E

W

22135

13 13 13

M E

C H

R M

E

'H H

W P

-1

(N E

W

NORMAL POWER

MECH RM E003

'AHU-5'

(ETD)

TO

'LVB-E2-277VG'

NCB-4 & NCB-5

(ETR)

TO GEN SWBD

'LVB-H14-277VG'

(ETR)

EQUIPMENT BRANCH

SPARE

STANDBY POWER

SPARE

SPACE

'SF-1'

SUPPLY AIR FAN

AHU-1

(ETR)

DEDICATED

SPACE

DEDICATED

SPACE

TO SWBD

'LVB-B3-277VN'

INCOMING

LINE

'RF-1'

RETURN AIR FAN

AHU-1

(ETR)

'EF-1'

EXHAUST FAN

TOILETS

(ETR)

'EF-3'

EXHAUST FAN

FUME HOOD

(ETR)

'SF-2'

SUPPLY AIR FAN

AHU-2

(ETR)

'RF-2'

RETURN AIR FAN

AHU-2

(ETR)

'EF-4'

EXHAUST FAN

MECH ROOM VENT

(ETR)

'EF-5'

EXHAUST FAN

ELEC ROOM VENT

(ETR)

'HWP-3'

SNOW MELTING

PUMP

(ETR)

'HRP-1'

HOT WATER PUMP

(HEATING)

(ETR)

'SF-3'

SUPPLY AIR FAN

AHU-3

(ETR)

'RF-3'

RETURN AIR FAN

AHU-3

(ETR)

AHU-5

SPARE

(ETR)

'MDP4-D2-277VN'

(ETR)

'SF-4'

SUPPLY AIR FAN

AHU-4 (EMER)

(ETR)

DEDICATED

SPACE

DEDICATED

SPACE

TO ATS

'ATS-3'

INCOMING

LINE

'RF-4'

RETURN AIR FAN

AHU-4 (EMER)

(ETR)

'EF-10'

(ETR)

'PTS-1'

PNEUMATIC TUBE

SYSTEM

(ETR)

'MDP4-D2-277VQ'

(ETR)

DEDICATED

SPACE

SPARE

'EF-6'

EXHAUST FAN

EM PWR SWBD RM

(ETR)

'EF-7'

EXHAUST FAN

AMBULANCE ENTR

(ETR)

'EF-8'

EXHAUST FAN

GENERAL

(ETR)

STEAM COND.

PUMP

E003

(ETR)

SIZE 1

SPARE

(ETR)

'D-12'

DUMBWAITER

(ETR)

SPARE

'DSP-1'

DUPLEX SUMP

PUMP

(ETR)

'HWP-1'

HOT WATER PUMP

(HEATING)

(ETR)

'HWP-2'

HOT WATER PUMP

(HEATING)

(ETR)

'VP-1'

VACUUM PUMP

(DUPLEX)

(ETR)

SUPPLY AIR FAN

'AHU-6' (ETR)

'CLC-DP-BF3-277VQ'

(ETR)

EXISTING LOAD

(ETR)

SPAC…