589a4-25-102_Addendum 02_260828.pdf

PDF 1 MB Posted

Attached to
Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler Federal contract opportunity
Solicitation number
36C25526R0159
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This is an addendum to contract documents for a federal construction project at Harry S. Truman VA Medical Center in Columbia, Missouri. Addendum No. 02, dated August 28, 2026, modifies the contract for Project 589A4-25-102, "Install Dedicated Pharmacy Air Handler," and makes changes to four drawing pages totaling four 30x42 drawing sheets. The modifications include: (1) Drawing GI001 adds required steel fire protection details; (2) Drawing GI003 incorporates a phasing plan previously issued by the VA; and (3) Drawings AC101 and A-101 replicate the phasing plan from GI003. The phasing plan outlines three phases of work: Phase 1 involves running ductwork and piping during dayshift operations; Phase 2 includes basement compounding work from the new air handling unit (AHU) and hydronic system installation during night shift while maintaining access to sterile processing areas; and Phase 3 includes hydronic line routing to mechanical shafts and ductwork demolition and installation, broken into smaller sub-phases for night shift execution. The document is sealed by an architect registered in Missouri and includes references to applicable codes including the 2024 International Building Code, 2024 NFPA 101 Life Safety Code, ASHRAE standards, and VA seismic design requirements for a facility designated as critical with Risk Category IV in Seismic Design Category D.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--589A4-25-102, Install Dedicated Pharmacy Air Handler, newest first.
File Type Posted
07 81 00 Applied Fireproofing.pdf PDF
36C25526R0159 0004.pdf PDF
Final Drawings Part-2.pdf PDF
PRE-BID SIGN IN ROSTER.pdf PDF
Final Drawings Part-3.pdf PDF
Final Drawings Part-1.pdf PDF
36C25526R0159 0003.docx DOCX document
07_8100-001_Fireproofing_Mfr_Literature.pdf PDF
01 00 00 General Requirements RX.pdf PDF
36C25526R0159 0002.docx DOCX document
Phasing info.pdf PDF
01 32 16-15 Project Schedules RX.pdf PDF
01 91 00 General Commissioning Requirements RX.pdf PDF
finish schedule from specs.pdf PDF
01 00 10 - MEDICAL CENTER REQUIREMENTS RX.pdf PDF
Finish schedule from drawings.pdf PDF
01 33 23- Shop Drawings Product DAta and Samples.pdf PDF
36C25526R0159 0001.docx DOCX document
S02-Final Specifications 1068 pages.pdf PDF
36C25526R0159.docx DOCX document
P09-Final Drawings Part-2 Pages 37.pdf PDF
P09-Final Drawings Part-1 Pages 37.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM

PROJECT NUMBER 589A4-25-102 (2517)

PROJECT NAME Install Dedicated Pharmacy

Air Handler

ADDENDUM NUMBER 02

DATE August 28, 2026 SUBJECT Phasing Plan

A | 312 SW 25th St. Oklahoma City, OK 73109 P | 405.842.6100 E | howdy@spur-design.com W | spur-design.com

THE FOLLOWING MODIFICATIONS, ADDITIONS, AND DELETIONS ARE HEREBY MADE A PART OF THE CONTRACT DOCUMENTS.

SEAL:

GENERAL: This Addendum modifies the following Drawing pages: GI001, GI003, AC131, A-101

Drawings:

• GI001

o Adds Required Steel Fire Protection

• GI003

o Adds Phasing Plan as previously issued by VA.

• AC101

o Replicates Phasing Plan on GI003

• A-101 o Replicates Phasing Plan on GI003

TOTAL: (4) 30x42 Drawing Sheets

END OF ADDENDUM NO. 02

John.Peter Snapshot

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

4' -0

M

A X

T O

B O

T T

O M

4' -0

M

A X

T .O

. S

IN

K

2' -1

0" M

A X

2' -3

M

IN

1'-6" MIN

1. GENERAL CONTRACTOR TO PROVIDE METAL SUPPORT

BLOCKING FOR ALL WALL MOUNTED ACCESSORIES,

FIXTURES, AND EQUIPMENT.

2. PROVIDE ADA SUPPORT BRACKETS PLACED AT ALL OPEN

COUNTERTOPS @ 36"-48" MAX ON CENTER.

3. SPECIFIED MAXIMUMS ARE MEASURED FROM AFTER

FINISHED FLOOR TO THE OPERABLE PART OF THE FIXTURE.

4. FIXTURES SHOWN ARE REPRESENTATIONAL ONLY. NOT ALL

FIXTURES MAY BE USED. REFER TO SPECIFICATIONS FOR

FIXTURE TYPES USED IN THIS PROJECT.

5. FIXTURES MAY OVERLAP WAINSCOT. WHERE APPLICABLE,

BACKING TO BE PROVIDED AS SHIM FOR FLUSH

APPLICATION. SHIM TO MATCH SCHEDULED WALL FINISH.

6" MAX

9" M

IN

SHOWER

VA TOILET ROOM

TURNING RADIUS

DRINKING

FOUNTAIN

PAPER TOWEL

DISPENSER

SANITARY

NAPKIN

DISPENSER

T O

O P

E R

A B

LE

P

A R

T S

4' -0

"M A

X

WASTE

RECEPTACLE

LAVATORY

WITH MIRROR

ON CENTER

WALL

T O

T .O

. P U

S H

B U

T T

O N

4' -0

M

A X

SOAP

DISPENSER

T .O

. S

IN

K

2' -1

0" M

A X

T O

B .O

. R E

F

LE

C T

IV

E

S U

R F

A C

E

3' -4

"M A

X

17 MIN

2' -3

M

IN

T .O

. D R

IN

K

IN

G

O R

IF

A

C E

3' -0

M

A X

1'-6" MIN

WALL

2' -9

3' -0

3' -2

4' -0

2'-0" MIN

8" MIN

WALL

LAVATORY

WITH APRON

1' -5

M

A X

1'-6" MIN

URINAL

WALL

1'-5" - 1'-7" (AMBULATORY)

1'-4" - 1'-6" (WHEELCHAIR)

CLEAR FLOOR

5'-6"

CLEAR FLOOR

6'-0"

3'-0" MIN

T .O

. B A

R

2' -9

3' -0

1'-0" MIN

3'-6" MIN 1'-0"MAX

4'-6" MIN

1' -5

'-7

1' -6

M

IN

A N

S I I

C C

A

7.

1)

1' -3

M

IN

A D

A /A

B A

T .O

. B A

R

2' -9

3' -0

WALL

WALL

WALL HOOK

T .O

. C

LO

C K

7' -0

CLOCK

WALL

FINISHED FLOOR

FIRE EXTINGUISHER

CABINET

WEIGHT > 40LBS

FIRE EXTINGUISHER

CABINET

WEIGHT < 40LBS

T .O

. S

LO

T

4' -0

"M A

X

T .O

. H A

N D

LE

4' -0

M

A X

TOILET SEAT

COVER

DISPENSER

BABY

CHANGING

STATION

CLEAR FLOOR SPACE

@ WATER CLOSET

HANDRAILS AND

BUMPER GUARDS

FIXTURE MOUNTING HEIGHTS AND CLEARANCES

DOOR AND FIXTURE CLEARANCES

MATERIALS LEGEND

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN

VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS. REFERENCE RELEVANT ADDENDA FOR EACH OF THE ADOPTED CODES AND STANDARDS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2024 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2024 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2024 NATIONAL FIRE CODES (NFPA)

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2023 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2024 INTERNATIONAL MECHANICAL CODE

• 2023 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2024 INTERNATIONAL PLUMBING CODE (IPC)

• 2022 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2022 ANSI ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

• 2022 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2023 STEEL CONSTRUCTION MANUAL (16TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND

NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• 2022 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2022 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

• 2024 PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT

NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.

DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES

EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

ASHRAE 90.1 - 2019 EDITION

BUILDING LOCATION: COLUMBIA, MO, BOONE COUNTY

CLIMATE ZONE (TABLE ANNEX 1-1): ZONE 6B

INTERIOR DESIGN CONDITIONS:

THE INTERIOR DESIGN TEMPERATURES FOR HEATING AND COOLING AS DEPICTED IN THE PROJECT DESIGN CONDITIONS SCHEDULE IN THE MECHANICAL CONTROL DRAWINGS SHALL BE THE MAXIMUM

AND MINIMUM VALUES FOR THE ASSOCIATED TEMPERATURE CONTROL ZONES.

BUILDING ENVELOPE REQUIREMENTS (5.5 )

BUILDING ENVELOPE REQUIREMENTS FOR CLIMATE ZONE 4 (A,B,C)

ROOFS REQUIRED DESIGNED

INSULATION: R-30 c.i. R-30 c.i.

METAL BUILDINGS: R-19 + R-11 Ls or R-25 + R-8 Ls N/A

ATTIC AND OTHER: R-49 N/A

WALLS, ABOVE GRADE

MASS: R-9.5 c.i. N/A METAL BUILDING: R-0 + R-15.8 c.i. N/A STEEL-FRAMED: R-13 + R-7.5 c.i. R-13 + R-7.5 c.i WOOD-FRAMED AND OTHER: R-13 + R-3.8 c.i. or R-20 N/A

WALL, BELOW GRADE

BELOW-GRADE WALL: R-7.5 c.i. N/A

FLOORS

MASS: R-14.6 c.i. N/A

STEEL-FRAMED: R-30 N/A

WOOD-FRAMED AND OTHER: R-30 N/A

SLAB-ON-GRADE FLOORS

UNHEATED SLABS: R-15 for 24 in. N/A HEATED SLABS: R-20 for 24 in. N/A

OPAQUE DOORS

SWINGING: U-0.370 U-0.370

NONSWINGING: U-0.310 N/A

FENESTRATION (TABLE 5.5-4):

VERTICAL FENESTRATION, U-FACTOR

FIXED: U-0.36 N/A

OPERABLE: U-0.45 N/A

ENTRANCE DOOR: U-0.63 N/A

DEFINITIONS

c.i = CONTINUOUS INSULATION Ls = LINEAR SYSTEM

NR = NO (INSULATION) REQUIREMENT

ENERGY REQUIREMENTS

N

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL CONFIRM

ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE ENTIRE

DOCUMENT SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY WORK,

TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY DISCREPANCIES TO

THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY ALL DIMENSIONS AND

EXISTING STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT

CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE

CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK

AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN

PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND REPAIR

ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED OR

REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT

PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.

9. APPROPRIATE LIGHT FIXTURES SHALL BE TEMPORARILY SUSPENDED TO PROVIDE

ADEQUATE LIGHTING LEVELS FOR CONSTRUCTION.

10. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER

DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A

WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE AND

OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND

ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS, BUT

DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL DRAWINGS.

CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE OTHER SHEETS

AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION DOCUMENTS THAT REFLECT

WORK REQUIRED TO ACHIEVE A COMPLETE AND OPERATIONAL GOAL. LACK OF

COORDINATION AND REVIEW OF DRAWINGS AND SPECIFICATIONS AS AN ENTIRE

DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS, BEING OBVIOUS AND

TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE DRAWINGS AND SPECIFICATIONS, SHALL

NOT BE IN ANY WAY AN ADDITIONAL COST TO THE GOVERNMENT.

11. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH SERVICES

TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 48 HOURS IN ADVANCE OF

PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE, EXACT TIME OF, AND

APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR INTERRUPTIONS OF ANY

SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60 CALENDAR DAYS PRIOR TO THE

DESIRED TIME AND SHALL BE PERFORMED AS DIRECTED BY THE COR. MAJOR

INTERRUPTIONS SHALL BE COORDINATED WITH OTHER MAJOR INTERRUPTIONS AND MAY

NOT BE SCHEDULED FOR ONE DISCIPLINE MORE THAN TWICE THROUGHOUT THE OVERALL

CONSTRUCTION SCHEDULE UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR.

CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH

OTHER DATE AND/OR TIME SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE

TO OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE

MEDICAL CENTER MAY OCCUR AT TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING

HOURS. SCHEDULE INTERRUPTION MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT

BE AN ADDITIONAL COST TO THE GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT

MAY AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING

THE CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.

12. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING BUILDING MATERIALS

(ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE DESIGNED/SPECIFIED AS BUILDING

MATERIAL IN ANY OF THE CONSTRUCTION DOCUMENTS.

13. REFER TO THE DESIGN BINDER FOR THE ICRA INFORMATION DOCUMENTATION.

GENERAL NOTES

AREA NAME

150 SF

A101

A101

SIM

A

00.0

A101

1 1

A101

LEVEL NAME

00'-00"

00'-00" 4B

3A

FIBERGLASS BATT

INSULATION

RIGID INSULATION

CONCRETE / PRECAST

CONCRETE

EARTH / SOIL

SAND, EIFS FINISH, OR

PLASTER FINISH

GYPSUM BOARD FINISH

BRICK

CONCRETE MASONRY

UNIT

STONE / CAST STONE

GYPSUM BOARD SECTION

EXTERIOR SHEATHING

BOARD SECTION

PLYWOOD SECTION

CLEAN UTILITY

000A

150 SF

/1 A101

X0000

6"

T .O

. R A

IL

2' -1

0"

'-2

ROOM TAG

AREA TAG

SPECIALTY EQUIPMENT TAG

DOOR TAG

KEYED NOTE TAG

WALL TAG

WINDOW TAG

A101

SIM

A

ACB ACOUSTIC CEILING BAFFLE

ACP ACOUSTIC CEILING PANEL

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AF ACCESS FLOORING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

ALUM ALUMINIUM (TRIM)

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AT ACOUSTIC CEILING TILE

AVG AVERAGE

B

BD BOARD

BG BUMPER GUARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CBB CONCRETE BACKER BOARD

C/C CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CH BD CHALKBOARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CPT CARPET/CARPET TILE

CS CONCRETE SEALED

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

DWP DIMENSIONAL WALL PANEL

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EPY EPOXY FLOORING

EQ EQUAL

ETR EXISTING TO REMAIN

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FAB FABRIC

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FP FIRE PROTECTION

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G

GDR GUARDRAIL

GL GLASS/GLAZING

GRAN GRANITE

GR FL GROUND FLOOR

GT GROUT

GSM GALVANIZED SHEET METAL

GYP BD GYPSUM BOARD

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HANDRAIL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LN LINOLEUM

LOC LOCATION

LT LIGHT

LVR LOUVER

LVT LUXURY VINYL TILE

M

MAT CARPET MAT / WALK-OFF MAT

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

P PAINT

PA PUBLIC ADDRESS

PBD PARTICLE BOARD

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRB PROFILE BASE

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PORCELAIN TILE

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

QT QUARRY TILE

REFERENCE SYMBOLS IDENTIFICATION TAGS

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

GRID HEAD AND

LINE

LEVEL INDICATOR

MATCH LINE AND

VIEW REFERENCE

NORTH ARROW W/

PROJECT NORTH

SPOT ELEVATION

DETAIL

SECTION

WALL

SECTION

BUILDING

SECTION

DETAIL

ELEVATION

INTERIOR

ELEVATION

BUILDING

ELEVATION

1 1

6'- 0"

5'- 6"

BARIATRIC TOILET ROOM

TURNING RADIUS

CLEAR FLOOR SPACE

@ ADA LAVATORY

CLEAR FLOOR SPACE @ ADA

DRINKING FOUNTAIN

4"

6"

3"

1' -6

6" MAX

7" - 9" 11" MIN

17" - 25"

(ANSI ICC A117.1)

39"- 41"

(A N

S I I

C C

A

7.

1)

M

IN

(A N

S I I

C C

A

7.

1)

1"

T O

F .E

. H A

N D

LE

3' -6

M

A X

T O

F .E

. H A

N D

LE

5' -0

M

A X

R

RAF RESILIENT ATHLETIC FLOORING

RB RUBBER BASE/RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RES RESINOUS FLOORING

RES-W RESINOUS / EPOXY WALL / CEILING

RF RUBBER FLOORING

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RP RESIN PANEL

RSF RESILIENT SHEET FLOORING

RV ROOF VENT

RWC RIGID VINYL WALLCOVERING

S

SC SPECIALTY COATING

SD STATIC DISSIPATIVE FLOORING/TILE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SM SHEET METAL

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS SOLID SURFACE

ST STONE

STD STANDARD

STOR STORAGE

SV SHEET VINYL (ROLLED OR TILE)

SWC STAINLESS STEEL WALLCOVERING

T

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZZO

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

V/C VA PROVIDED / CONTRACTOR

INSTALLED

VCT VINYL COMPOSITION TILE

VFAT VINYL-FACED ACOUSTICAL TILE

VP VENEERED PLASTER

VT VINYL TILE

V/V VA PROVIDED / VA INSTALLED

VWC VINYL WALLCOVERING

VWF VINYL WALL FABRIC

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WD WOOD

WFAB WALL FABRIC

WPM WATERPROOF MEMBRANE

WSF WELDED SHEET FLOOR

X

X BRACE CROSS BRACE

TRUE

NORTH

18" MIN

M

IN

FRONT APPROACH,

PULL SIDE

36" MIN

M

IN

HINGE APPROACH,

PULL SIDE

HINGE APPROACH,

PULL SIDE

*12" MIN48

M

IN

FRONT APPROACH,

PUSH SIDE

M

IN

HINGE APPROACH,

PUSH SIDE

22" MIN 24" MIN

*4 8"

M

IN

LATCH APPROACH,

PULL SIDE

24" MIN*4

2"

M

IN

LATCH APPROACH,

PUSH SIDE

*IF BOTH CLOSER

AND LATCH ARE

PROVIDED

*54" MIN IF CLOSER

IS PROVIDED

*48" IF CLOSER IS

PROVIDED

FRONT APPROACH,

PUSH SIDE

M

IN

42" MIN

**48" MIN IF BOTH CLOSER

AND LATCH PROVIDED

M

IN

1' -0

1'

-0

1' -0

1'

-0

1' -0

1'

-0

1' -0

2'-6"

8" 4'

-0

1'-6"

5'-6"

6' -0

2'-6"

4' -0

T .O

. H O

O K

4' -0

VA HA 18-8 SEISMIC DESIGN REQUIREMENTS

BUILDING LOCATION: COLUMBIA, MO

FACILITY CRITICALITY DESIGNATION (FCD): CRITICAL

(VA 18-8, 1.4)

RISK CATEGORY: IV

(VA 18-8, 7.0)

SEISMIC DESIGN CATEGORY: D

(ASCE 7)

SEISMIC REQUIREMENTS

A101

SIM

A101

SIM

FIRE RATINGS REQUIRED:

STRUCTURAL STEEL

FLOOR BEAMS

FLOOR DECK

ROOF BEAMS

ROOF DECK

TUBE COLUMNS

WIDE FLANGED COLUMNS

HOURLY RATING

2 HR RESTRAINED

2 HOUR RESTRAINED

1 HOUR

1 HOUR

2 HOUR

2 HOUR

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

/2

/2

:0 :4

P

M

GENERAL INFORMATION

JDM 02 OF 74JP

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

GI001

SPUR #: 2517No. REVISION DESCRIPTION DATE

2 ADDENDUM #2 08/28/2026

UP

UP

KEY PLAN

N

SCOPE AREA

ICRA FLOOR PLAN LEGEND

AREA NOT IN CONTRACT

EXISTING PARTITION TO

REMAIN

NOTE: NOT ALL SYMBOLS MAY BE USED.

TEMPORARY ICRA BARRIER,

WALL TYPE "E"

REF. GI002

TEMPORARY ICRA ACCESSS

DOOR

6 7

8 9

E

D

10 11

C

E.1

D.7

B

6.3

11.5

VESTIBULE

F009A

SHARED OFFICE

F011

JANITOR

F036

STAIR

#11

JANITOR

E013

STORAGE

E001G

PHARMACY

E001

ELEC ROOM

E009

CORRIDOR

CBE2

STORAGE

E002E

NON-HAZARD IV

PREP

E001H

STERILE

PROCESSING

AREA

E001L

IV ROOM

STORAGE

E001F

TEAM ROOM

E001D

OFFICE

E001B

NARCOTIC

VAULT

E001A

OFFICE

E001C

1.01

1.03

MFMR EXEC

OFFICE

E002E

CLINICAL

RESEARCH

E002J

R.C.O. R&D

E002I

OFFICE

E002H

WORK ROOM

E002B

PHASING LEGEND

AREA NOT IN CONTRACT

EXISTING PARTITION TO

REMAIN

NOTE: NOT ALL SYMBOLS MAY BE USED.

TEMPORARY ICRA BARRIER,

WALL TYPE "E"

REF. GI002

TEMPORARY ICRA ACCESSS

DOOR

PHASE 1: RUN DUCTWORK

AND PIPING DURING DAYSHIFT

PHASE 2: RUN BASEMENT

COMPOUNDING FROM NEW

AHU AND RUN HYDRONICS.

NIGHT SHIFT AND ACCESS TO

E001L MUST BE MAINTAINED

PHASE 3: RUN HYDRONICS TO

SHAFT. BREAK INTO SMALLER

PARTS. NIGHSHIFT.

PHASE 3: (NOT SHOWN FOR

CLARITY) DEMO AND INSTALL

DUCTWORK. MUST BE

BROKEN UP INTO SMALLER

SUB PHASES OF WORK. NIGHT

SHIFT.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

/2

/2

:0 :4

P

M

ICRA FLOOR PLAN - BASEMENT LEVEL

JDM 04 OF 74JP

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

GI003

SPUR #: 2517

KEYNOTE LEGEND

1.01 2-HOUR ICRA BARRIER AND DOOR SURROUNDING CEILING WORK AREA IN BASEMENT

PHARMACY; REF. ICRA CONSTRUCTION DETAILS ON SHEET GI002 FOR ADDITIONAL

INFORMATION

1.03 CONTRACTOR TO PROVIDE TEMPORARY CONSTRUCTION BARRIER AND DOOR

N

1/8" = 1'-0"

BASEMENT LEVEL - ICRA FLOOR PLAN1

No. REVISION DESCRIPTION DATE

C B

E

E001

E009

E002B

E002H E002I E002J E002K

E003

C O

R R

E001E

DN

UP

UPDN

F001B

F003*

JAN.

VEST.

CORR.

STAIR

#11

HATCH TO

TUNNEL BELOW

ELEV

#11

ELEV

#10

ELEV

#9

F023A

CBF3

F024

F001A

F004

F021

F018

F020 F019

F017 F016

F015A

F015

F014

C B

F

F005 F010

F012

F013

F011 F036 F009A

F003 F006 F007 F008 F009

CBF5

F001

F002A

F002

CBF1

E010

E008

E007

E006

CBE2

CBE5

CBE2

E004

E005

F037

E001K

E001H

E001L

E002F

E002E

E002D E002C

E002A

E002

A001B037A

CORR-1

F029 F028

F027A

F028A F025

F025A

F027 F026

F034

F034A

F035A

F035

F030 F031 F032 F033

F030A

F023 F022

CBE4

C B

F

A020A

F029A

E001F

E001J

CORR.

CORR.

CORR.

C O

R R

C O

R R

E001BE001D

E001A

OFFICETEAM ROOM

NARCOTIC

VAULT

E001C

OFFICE

STERILE PROCESSING AREA

NON-HAZARD IV PREP

IV STORAGE ROOM

STORAGE

CORRIDOR

HAZARDOUS

DRUG STORAGE

HAZARDOUS

IV PREP

OFFICE

F175

F174C

F174B

F174A

F181

F176

F174

E-1100

E139

E144

E140

F169

E146

E148

E147

C1E8 E145

E143

F179B

F177

F160

F177A F178

F161

F164

F166

F167

F165

F162

F170

E100A

E138

TLT.

CORR

F.M.S. ENG.

F.M.S. ENG.

ENTR.

VEST.

LOBBY

STAIR

#11DN

UP

C1F22

CORR.

F F

UP

FE

FE

FE

FE

FE

FE

UP

FE

C1E33

C1E31

E125F E109 E110

C1E24

E125EE125A E125B E125C E125D

E124

E123

E126

C E

E133

E122 E121 E120

E117

E116

E115

E114

E130 E131

E132

E112

E111

E129

E127

B109 B110 B112 A130

C E

E137

E102G

E102L

C1E35

E102F E102E E102A

F129

F135

C E

E102J E102K

F104

E-1204

F171

F128

F134

C1E13

E108B

F122

C1E21

F171A F150

F101

F125

E102H

E107

E108

C F

F123

F151B

F102

F126

E102

E106

E108C

C F

F124

F151A

C1F7

C1E12

F168

F137A

C1F7

F121

F137

C1E11

C1F1

C1F19

C F

C1F2

C1F21

F136

F118

F117

F163

C1E15

C1F20

F103

C1E9

B144B

F116

C1F6

C F

F115

C1E16

B143

E134

C1E32

C1E10

B137

C F

F109

F108

C F

F146

F179

F131

C1F15

F105

F113 F114A

F127

F130

F103B

F114

F132

F151

F180

F149

C1E17

F119

F107

F106

F112 F155

F147

F152

C F

C F

F144

F138

F153

F138A

F145

F148

F110 F111 F139 F140 F141 F142 F156

C1F12

C F

F133

F157 F158 F159

C1F17

F143 F154

F120

E127A

F103A

A119A A121 A123 A125A

F100

TLT. TLT.

CORR.

SOILED

UTIL.

TLT.

CLEAN UTIL.

C O

R R

TLT.

CORR.

ST. TLT.

CORR.

CLEAN UTIL.

TLT.

SOILED

UTIL.

CORR.

TLT.

CORR.

TLT.

ST. TLT.

TLT.

CORR.

ELEC./

TELE./

MECH.

F.M.S. ENG.

DECONTAMINATION

PT. TLT. H. NURSE/

NOD

ST. TLT.

SOILED

CLEAN

UTIL.

C O

R R

MED.

PT. TLT/

SHR.

CORR.

CORR.

CORR.

CORR.

CORR.

ELEVATOR

LOBBY

ELEVATOR

LOBBY

EQ. STG.

F.M.S. ENG.

VEST.

VEST.

JAN.

ST. TLT.

STAIR

#10

F. TLT.

M. TLT.

CORR. STAIR

#4

ELEV

#11

ELEV

#10

ELEV

#9

TLT.

CORR.

C O

R R

C O

R R

C O

R R

CORR.

TLT.

CORR.

CORR.

C O

R R

E102BE102CE102D

C O

R R

CORR.

CORR.

CORR.

C O

R R

C O

R R

TLT.

ROOF BELOW

AC131

AD131

CORRIDOR

CBE3

MECHANICAL

ROOM

E003

PHARMACY

E001

MECHANICAL

ROOM

E003A

OFFICE

E002H

R.C.O. R&D E002I

CLINICAL

RESEARCH

E002J

WORK ROOM

E002B

ELEC CLOSET

F001B

ELEC ROOM

E009

AE101

AE101

ELEC

F170

GENERAL PLAN NOTES

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT

WALL UNLESS NOTED OTHERWISE.

2. ALL WALLS ARE TYPE K2 PARTITIONS UNLESS OTHERWISE NOTED. REFER TO PARTITION TYPE

SHEET FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION.

7. CONTRACTOR TO LOCATE AND IDENTIFY EXISTING STRUCTURAL MEMBERS AND ROOF

CONDITIONS, AND REPORT ANY DISCREPANCIES TO THE VA BEFORE COMENCING

CONSTRUCTION.

PARTITION LEGEND

NOTE: NOT ALL WALL TYPES MAY BE USED

EXISTING WALL TO REMAIN

EXISTING HORIZONTAL EXIT

(& REFUSE AREA)

FIRE BARRIER

EXISTING BUILDING

SEPARATION: FIRE BARRIER

(FIRE WALL IN IBC)

EXISTING SUBDIVIDED SPACE

SMOKE BARRIER

EXISTING HAZ./INCIDENTAL

USE SMOKE BARRIER

(SPRINKLERED)

NEW PARTITION WALL;

REF. AE001

MECHANICAL

ROOM

E003

MECHANICAL

ROOM

E003A

ACA-AHU-10

23.21

PHASING LEGEND

AREA NOT IN CONTRACT

EXISTING PARTITION TO

REMAIN

NOTE: NOT ALL SYMBOLS MAY BE USED.

TEMPORARY ICRA BARRIER,

WALL TYPE "E"

REF. GI002

TEMPORARY ICRA ACCESSS

DOOR

PHASE 1: RUN DUCTWORK

AND PIPING DURING DAYSHIFT

PHASE 2: RUN BASEMENT

COMPOUNDING FROM NEW

AHU AND RUN HYDRONICS.

NIGHT SHIFT AND ACCESS TO

E001L MUST BE MAINTAINED

PHASE 3: RUN HYDRONICS TO

SHAFT. BREAK INTO SMALLER

PARTS. NIGHSHIFT.

PHASE 3: (NOT SHOWN FOR

CLARITY) DEMO AND INSTALL

DUCTWORK. MUST BE

BROKEN UP INTO SMALLER

SUB PHASES OF WORK. NIGHT

SHIFT.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

/2

/2

:0 :4

P

M

OVERALL REFERENCE PLANS -

BASEMENT AND LEVEL 1

JDM 15 OF 74BKM

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

A-101

SPUR #: 2517

N

3/64" = 1'-0"

BASEMENT LEVEL - OVERALL REFERENCE AND PHASING PLAN2

N

3/64" = 1'-0"

LEVEL 1 - OVERALL REFERENCE PLAN3

N

1" = 20'-0"

SUB-BASEMENT - OVERALL REFERENCE PLAN1

KEYNOTE LEGEND

23.21 AIR HANDLING UNIT (AHU), SUSPENDED FROM CEILING; REF. MECHANICAL DRAWINGS

GENERAL REFLECTED CEILING PLAN NOTES

1. ALL CEILINGS 9'-0" AFF UNO.

2. ALL SURFACES OF SOFFITS TO BE PAINTED XX UNO.

3. WHERE EXISTING CEILINGS ARE TO BE REMOVED AND REPLACED WITH NEW, THE GENERAL

CONTRACTOR SHALL COORDINATE THE REMOVAL AND REINSTALLATION OF ALL CEILING

MOUNTED DEVICES (CUBICLE CURTAIN TRACKS, IV-TRACKS, DETECTORS, SPEAKER, ETC.)

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION ON THE

ROUTING OF THE NEW SERVICES ABOVE THE CEILING.

EXIT LIGHT OR SIGN

REF: LIFE SAFETY

2' x 2' ACOUSTICAL CEILING

GYPSUM BOARD CEILING OR

SOFFIT

2 x 2 LIGHT FIXTURE

REF: ELECTRICAL

CEILING HEIGHT, ABOVE

FINISH FLOOR

RECESSED CAN LIGHT

(CENTER IN TILE U.N.O.)

REF: ELECTRICAL

2 x 4 LIGHT FIXTURE

REF: ELECTRICAL

00'-00"

REFLECTED CEILING PLAN LEGEND

2' x 4' ACOUSTICAL CEILING

RETURN AIR GRILLE

REF: MECHANICAL

SUPPLY AIR DIFFUSER

REF: MECHANICAL

EXHAUST AIR GRILLE

REF: MECHANICAL

SUSPENDED LIGHT FIXTURE

REF: ELECTRICAL

NOTE: ALL SYMBOLS MAY NOT BE USED.

OCCUPANCY SENSOR

REF: ELECTRICAL

AREA NOT IN SCOPE

PARTITION LEGEND

NOTE: NOT ALL WALL TYPES MAY BE USED

EXISTING WALL TO REMAIN

EXISTING HORIZONTAL EXIT

(& REFUSE AREA)

FIRE BARRIER

EXISTING BUILDING

SEPARATION: FIRE BARRIER

(FIRE WALL IN IBC)

EXISTING SUBDIVIDED SPACE

SMOKE BARRIER

EXISTING HAZ./INCIDENTAL

USE SMOKE BARRIER

(SPRINKLERED)

NEW PARTITION WALL;

REF. AE001

3 4 5 6 7 8 9

F

E

D

10 112

C

E.1

D.7

B

6.3 11.5

E002F

CONFERENCE

ROOM

E002E

PROGRAM

SUPPRT R&D

E002C

A.O. RAD

E002D

CORRIDOR

CBE3

MECHANICAL

ROOM

E003

MECHANICAL

ROOM

E003

FREEZER

F030A

REFRIGERATOR

F030

CAMERA DARK

ROOM

F031

MICRO DARK

ROOM

F032

ELEC

CLOSET

F035

WORK ROOM

F002

OFFICE

F003

WORK ROOM

F006

OFFICE

F007

OFFICE

F008

OFFICE

F009

VESTIBULE

F009A

SHARED OFFICE

F011

JANITOR

F036

STAIR

#11

JANITOR

E013

STORAGE

E001G

PHARMACY

E001

TELE / DATA

E006

ELEV MACHINE

ROOM

E007

WOMAN TOILET

E010

MEN TOILET

E008

ELEC ROOM

E009

CORRIDOR

CBE2

CORRIDOR

CBE2

OFFICE

E002A

RESEARCH

SERVICE

CORRIDOR

E002

CORRIDOR

CBF1

CORRIDOR

CBE5

E005

ELEV

#10

ELEV

#9

ELEV

#11

E004CORRIDOR

CBE4

MECHANICAL

ROOM

E003A

9'-0"

9'-0"

9'-0" 9'-0"9'-0"9'-0"

9.170

9.1709.1709.1709.170

9.170

9.170

2.96

OFFICE

E002H

R.C.O. R&D E002I

CLINICAL

RESEARCH

E002J

MFMR EXEC

OFFIC

E002K

WORK ROOM

E002B

9.170

9'-0"

10'-0"

F033

9'-0"

9.170

STORAGE

E002E

NON-HAZARD IV

PREP

E001H

STERILE

PROCESSING

AREA

E001L

IV ROOM

STORAGE

E001F

HAZARDOUS

IV PREP

E001J

HAZARDOUS

DRUG

STORAGE

E001K

TEAM ROOM

E001D

OFFICE

E001B

NARCOTIC

VAULT

E001A

OFFICE

E001C

CHASE

9.170

9.170

9.170

9.170

9.170

9.170

9.170

9.170

9'-0"

KEY PLAN

N

SCOPE AREA

PHASING LEGEND

AREA NOT IN CONTRACT

EXISTING PARTITION TO

REMAIN

NOTE: NOT ALL SYMBOLS MAY BE USED.

TEMPORARY ICRA BARRIER,

WALL TYPE "E"

REF. GI002

TEMPORARY ICRA ACCESSS

DOOR

PHASE 1: RUN DUCTWORK

AND PIPING DURING DAYSHIFT

PHASE 2: RUN BASEMENT

COMPOUNDING FROM NEW

AHU AND RUN HYDRONICS.

NIGHT SHIFT AND ACCESS TO

E001L MUST BE MAINTAINED

PHASE 3: RUN HYDRONICS TO

SHAFT. BREAK INTO SMALLER

PARTS. NIGHSHIFT.

PHASE 3: (NOT SHOWN FOR

CLARITY) DEMO AND INSTALL

DUCTWORK. MUST BE

BROKEN UP INTO SMALLER

SUB PHASES OF WORK. NIGHT

SHIFT.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. A-2012034754 EXP. 12/31/2026

ENGR REG. NO. E-2014031351 EXP. 12/31/2026

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

DRAWING NUMBER

BUILDING NUMBER

CIVIL/STRUCTURAL

H2B ENGINEERING

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

PHYSICAL SECURITY

FORCE PROTECT

4015 VITRUVIAN WAY, UNIT 1212

ADDISON, TX 75001

PHONE NUMBER

MECH/ELEC/PLUMB/TECH ENGINEER

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVE., SUITE H2

EDMOND, OK 73003

(405) 210-5814

/2

/2

:0 :4

P

M

REFLECTED CEILING PLAN - BASEMENT

LEVEL

JDM 23 OF 74JP

100% BID DOCUMENTS

INSTALL DEDICATED

PHARMACY AIR HANDLER

06/11/2026

589A4-25-102

HARRY S. TRUMAN VAMC

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

AC131

SPUR #: 2517

KEYNOTE LEGEND

2.96 EXISTING CEILING OPEN TO STRUCTURE ABOVE

9.170 REINSTALLED CEILING AS SCHEDULED

N

1/8" = 1'-0"

BASEMENT - REFLECTED CEILING PLAN1

File details come from the government source that posted it. Updated .