P09 Drawings 09 LV FIREALARM 100 BID - 9 pages.pdf

PDF 3 MB Posted

Attached to
Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
Solicitation number
36C25520R0040_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This federal solicitation requests construction services for a surgical suite addition project at a Department of Veterans Affairs medical center. The scope of work involves constructing three new operating rooms, supporting inpatient and ambulatory surgical services on the second floor of an existing building. Infrastructure upgrades will include UPS power systems to meet VA requirements. The completed project will provide the VA with a fully operational three operating room inpatient surgical and endovascular services suite as well as an ambulatory surgical service.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - 2-4 PR UTP

DATA OUTLET - 1-4 PR UTP

TELCO OUTLET - 1-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

18"

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD)

48"CR

ES

DC

RX

48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)

WIRELESS ACCESS POINT - 2-4 PR UTP

WALL PHONEW

N

S

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET WELL)

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

P

NURSE CALL PATIENT BED INTERFACE RECEPTACLE

B NURSE CALL CODE BLUE STATION

E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN

RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)

D

NURSE CALL DUTY STATION

M

NURSE CALL MASTER STATION/CONSOLE

NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

IC

INTERCOM WITH CAMERA

IC

INTERCOM MASTER WITH PUSH TO RELEASE DOORM

NURSE CALL WIRELESS ANTENNASNW

DATA OUTLET - 4-4 PR UTP18"

TV OUTLET WALL MOUNTED

48"

54"

DESK

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST OIT EQUIPMENT RACK

OIT EQUIPMENT CABINET

NURSE CALL EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

NCE

MATV

CCTV

LADDER CABLE TARY

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

HEADWALL

18"

HEADWALL

/40"

40",72"

18"

60"

CEILING

CEILING

6' TO TOP

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

HANDWAVE

T

C

NURSE CALL STAFF TERMINAL

NURSE CALL PATIENT STATION WITH CALL CORD.

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

48"

HEADWALL

W WIRELESS PENDANT

L

KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"

PATIENT ROAM ALERT ANTENNACEILING

GROUND BUS

CEILING

DOOR

DOOR

48"

ABOVE

DOOR

NURSE CALL DOME LIGHT

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

DATA OUTLET - 6-4 PR UTP18"6

N

M

PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)

88" MOTION DETECTOR

MD

FLOOR TWO POST OIT EQUIPMENT RACK

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

AREA OF REFUGE PANEL6' TO TOP

AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP

AOF

AOFA

IC AREA OF REFUGE INTERCOM48"

AREA OF REFUGE STROBE LIGHTCEILINGSL

DP

DPP

DURESS PANIC ALARM PUSH BUTTON48"

DURESS PANIC ALARM PANEL6' TO TOP

N

DATA OUTLET - 3-4 PR UTP18"3

R

CEILING

CEILING

TELEMETRY ANTENNA, 2-4 PR UTP

ROBOT PHARMACY ANTENNA, 1-4 PR UTP

CEILING ANTENNA

GENERAL TECHNOLOGY NOTES

1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT

SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL

LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.

4. PROVIDE CABLING THAT COMPLIES WITH LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION

METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

5. COMPLY WITH LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

6. COMPLY WITH LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING

STANDARD.

7. COMPLY WITH LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

8. COMPLY WITH LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

9. COMPLY WITH LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

10. COMPLY WITH LATEST NFPA 101 LIFE SAFETY CODE.

11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY

AMERICAN ACT".

13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS

NOTED OTHERWISE.

14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY

TESTING AGENCY.

16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE

MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

17. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.

18. PROVIDE TIA/EIA CAT 6 COPPER OUTLETS AND CONNECTORS.

19. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED

BY THE VA COR.

20. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS

SET FORTH BY THE VA HOSPITAL OIT.

21. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.

22. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND

EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.

23. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

ADO AUTOMATIC DOOR OPERATOR

AFF ABOVE FINISH FLOOR

BOD BASIS OF DESIGN

CCTV CLOSED CIRCUIT TELEVISION

COAX COAXIAL CABLE

COMM COMMUNICATION

COR CONRACTING OFFICER REPRESENTATIVE

DC DOOR CONTACT SWITCH

DN DOWN

DO DOOR OPERATOR

DVR DIGITAL VIDEO RECORDER

DVC DIGITAL VOICE COMMAND

E EXISTING DEVICES

EEB EMERGENCY EXIT BUTTON

EL ELECTRICAL STRIKE

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR

PANEL

FO FIBER OPTIC

IT INTERCOMMUNICATION ROOM

MATV MASTER ANTENNA TELEVISION

MM MULTI MODE FIBER

NAC NETWORK APPLIANCES CONTROL PANEL

N NEW DEVICES

NCA NETWORK CONTROL ANNUNCIATOR

NCE NURSE CALL EQUIPMENT CABINET

NS NO SCALE

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

TECHNOLOGY ABBREVIATIONS LIST

OC ON CENTER

OIT OFFICE OF INFORMATION TECHNOLOGY

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM

PB PUSH BUTTON

PDU RACK POWER DISTRIBUTION UNITS

POE POWER OVER ETHERNET

PR PAIR

RX REQUEST TO EXIT

SEP SERVICE ENTRANCE PROTECTION

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE FIBER

TEL TELEPHONE

TGB TELECOMM GROUND BUS BAR

TM TELEMONITORING

TMGB TELECOMM MAIN GROUND BUS BAR

TP TWISTED PAIR

TR TELECOMM ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

WAP WIRELESS ACCESS POINT

WM WIRE MANAGEMENT

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:5

P M

TK001

TECHNOLOGY GENERAL NOTES,

SYMBOL LEGEND, AND

ABBREVIATIONS

1 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

DocuSign Envelope ID: 4F810D56-F7FC-4A6F-92E9-37BF1FEFC9E6

11/14/2019

F S

1/

W

C d

F

S

1/2 W 75 Cd

S

S

S

S

S

S

S

F

S

F

S

1/2 W 75 Cd RX

CR

RX

C R

F S

1/

W

C d

F

S

1/2 W 75 Cd F

S

1/2 W 75 Cd

S

S

S S S

S

S S

S

F

F

F

F

F

F S

1/

W

C d

FS

1/

W

C d

S

S

E

E

W

N 1

N 1

A

Q

2-11

O M.2 K.1 F.9 C.9 A.5

2-10

2-8

2-6

2-5

2-3

2-2

2-1

2-9

AA AC

2-4

2-7

L.5

N

D

K.2

F.8

A

TYP.

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:5

P M

TD101

SECOND FLOOR

TECHNOLOGY/SYSTEMS DEMOLITION

PLAN

2 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

Scale: 1/8" = 1'-0"

SECOND FLOOR TECHNOLOGY/SYSTEMS DEMOLITION PLAN 0 4 8 16

NORTH

PLAN

A. REMOVE ALL EXISTING DATA/TELEPHONE

CABLE, CONDUITS, JUNCTION BOXES,

PATCH PANELS, AND RELATED MATERIALS

ALL THE WAY TO SOURCE.

B. DEMOLISH ALL EXISTING FIRE ALARM IN

THE REMODELED AREA.

C. KEEP EXISTING FIRE ALARM SYSTEM

OPERATIONAL AT ALL TIMES.

D. THESE DRAWINGS BASED ON THE BEST

AVAILABLE INFORMATION AT THE TIME OF

SURVEY & VISUAL INSPECTION. VERIFY ALL

FIELD CONDITIONS.

E. PROTECT ALL EXISTING CCTV CAMERA

EQUIPMENT DURING DEMOLITION &

MAINTAIN SYSTEM OPERATION.

F. PROTECT ALL EXISTING PACS EQUIPMENT

DURING DEMOLITION & MAINTAIN SYSTEM

OPERATION.

1 EXISTING IT ROOM TO REMAIN.

2 EXISTING FIRE ALARM NAC PANEL TO REMAIN.

3 EXISTING ANTENNA DEVICES SHALL BE

PROTECTED DURING CONSTRUCTION. BAG

AND SUPPORT ABOVE THE CEILING,

REINSTALL IN CEILING GRID AFTER NEW

CEILING IS INSTALLED. VERIFY

REQUIREMENTS IN THE FIELD AND WITH COR.

3 3

3 3

3 3

3 3 3

3 3

60"60" 60"

W W W

W

W

W

W

W

W

W

W

W

W

W

W

W

R

60"

60" 60"

3 3 3

3 3

WWW

S

S

S S

S

S

S

S S

SS

S

S

S S

S

S

S

S

Q

2-11

O M.2 K.1 F.9 C.9 A.5

2-10

2-8

2-6

2-5

2-3

2-2

2-1

2-9

AA AC

2-4

2-7

L.5

N

D

K.2

F.8

TK401

TK401

12"12" 12"

12"12"

18"

2 2

3 3

1 1 1 1

CARE STATION

ISOLATION

ANTE

STAFF TOILET

TOILET

TOILET

STORAGE

MEDS

SOILED HOLDING

HAC

DICTATION

CORRIDOR

C206-02

PACU

PACU

PACU

PRE/POST

241PRE/POST

PRE/POST

PRE/POST

PRE/POST

PRE/POST

PRE/POST

CORRIDOR

C208-02

CORRIDOR

C204-02

CONSULTATION

WAITING

ELECTRICAL

CHASE

RECEPTION

CHASE

C202-56

CORRIDOR

C201-38

PSA OFFICE

TOILET

TOILET

N. MANAGER OFFICE

STAFF LOUNGE

WOMEN'S LOCKER

MEN'S LOCKER

STAFF TOILET

STAFF TOILET

EQUIPMENT

ANESTHESIA

CORRIDOR

C203-38

SOILED

HAC

OR

OR

OR

CORRIDOR

C201-02

CORRIDOR

C204-2

CORRIDOR

205-02

STERILE CORE

IMMED. STER.

CLEAN SUPPLY

CORRIDOR

C207-02

CORRIDOR

C202-02STAIR

S1-02

ELECTRICAL

STRESS LAB

ELEVATOR SHAFT

C202-54

LOGISTICS

BIO-MED

WHEELCHAIR ALCOVE

C3

FIBER OPTIC

PAMN

C207-02F

ELEVATOR LOBBY

C1

ELEVATOR 2

C207-02B

ELEVATOR 1

C207-02C

ELEC.

SOILED UTILITY

CORRIDOR

C2

PAGING EQUIPMENT

C207-02G

12"

STAIR

S2-02

18"

OFFICE

TYP.

CHASE

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:0

P M

TK101

SECOND FLOOR TECHNOLOGY PLAN

3 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

Scale: 1/8" = 1'-0"

SECOND FLOOR TECHNOLOGY PLAN 0 4 8 16

NORTH

PLAN

1 TELEMETRY DATA OUTLET. SEE TK401 FOR

MORE INFORMATION. SEE INTERIORS

DRAWINGS FOR PLACEMENT.

2 TELEMETRY ANTENNA. PROVIDE 2-4PR UTP

AT EACH LOCATION. RUN TO BIO MED RM.

3 SEE TK401 FOR MORE INFORMATION.

4 CEILING MOUNTED BOOMS WITH CABLING.

PROVIDE 3-4PR UTP FOR EACH BOOM.

5 PROVIDE (2) 4" FIRE/SMOKE RATED UL LISTED

ASSEMBLY SLEEVES FOR FIBER AND

COPPER. SEE SHEET TK502 FOR MORE

INFORMATION.

6 EXISTING PAGING EQUIPMENT BLDG #1, RM

232.

7 EXISTING ANTENNAE TO BE REINSTALLED IN

POSITIONS INDICATED.

1. PROVIDE AND INSTALL ALL DEVICES SHOWN AS

NEW UNO.

N 1

N 1

N 1

N 1

P S

T

M

C R

R X

ES

D

C

C R

CR

CR

CR

ES

RX

DC

CR

ES RX DC

CR

CR

D

D

P SP S

N 1 N 1

N Z

N 1

N 1

N 1

N 1

N 1

N Z

P S

N 1 N 1

N 1 N 1

TT

D

PS

P S

S S

S S

S P

P P

P P

N 1

N 1

D

D

S P

E

E

N 1

N 1

D C

R X

ES

N

E

PB

D

E

E

N 1 N 1

ES

D

C R

X

C R

D

D C

R X

ES

CR

ES

R

X D

C

C R

ES

R

X D

C

C R

D

ES RX

DC

ES

RX

DC

CR

CR

C R

ES

DC

ES

RX

DC CR

ES

R

X

D C

ESD

C

ES

R

X

D C

ESD

C

ES

R

X

D C

ESD

C

R X

ES

D

C R

X

ES

D C

C R

C R

IC IC

IC

IC

IC

S

S

S S

S

S

S

S S

SS

S

S

S S

S

S

S

S

A

Q

2-11

O M.2 K.1 F.9 C.9 A.5

2-10

2-8

2-6

2-5

2-3

2-2

2-1

2-9

AA AC

2-4

2-7

L.5

N

D

K.2

F.8

TK401

TK401

12"12" 12"

12"12"

18"

CARE STATION

ISOLATION

ANTE

STAFF TOILET

TOILET

TOILET

PRE/POST

PRE/POST

PRE/POST

PRE/POST

PRE/POST

PRE/POST

PACU

PACU

PACU

CLEAN SUPPLY

CORRIDOR

C206-02

ALCOVE

C206-02A

DICTATION

HAC

SOILED HOLDING

CORRIDOR

C207-02

IMMED. STER.

OR

CORRIDOR

205-02

CORRIDOR

C204-2

OR

OR

STERILE CORE

CORRIDOR

C201-02

CORRIDOR

C203-02

CORRIDOR

C204-02

CORRIDOR

C208-02

CONSULTATION

CHASE

C202-56

ELECTRICAL

210CHASE

WAITING

STAFF LOUNGE

SOILED

HAC

ELECTRICAL

ANESTHESIA

EQUIPMENT

WOMEN'S LOCKER

207 STAFF TOILET

STAFF TOILET

MEN'S LOCKER

STRESS LAB

PSA OFFICE

N. MANAGER OFFICE

TOILET

TOILET

CORRIDOR

C201-38

BIO-MED

ELEVATOR SHAFT

C202-54

LOGISTICS

PRE/POST

MEDS

STORAGE

CORRIDOR

C202-02

K

K

1 1 1 1

RECEPTION

FIBER OPTIC

203WHEELCHAIR ALCOVE

C3

ELEC.

PAMN

C207-02F

M

OFFICE

CHASE

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:0

P M

TK102

SECOND FLOOR SYSTEMS PLAN

4 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

Scale: 1/8" = 1'-0"

SECOND FLOOR SYSTEMS PLAN 0 4 8 16

NORTH

PLAN

1 PROVIDE DOME CEILING MOUNTED PATIENT

CAMERAS. SEE DETAIL 7 ON SHEET TK401.

2 PROVIDE 42" LED TV MONITOR.

3 PROVIDE (2) 4" FIRE/SMOKE RATED UL LISTED

ASSEMBLY SLEEVES FOR FIBER AND

COPPER. SEE SHEET TK502 FOR MORE

INFORMATION.

4 APPROXIMATE LOCATION OF THE EXISTING

RAULAND RESONDER 5 IN NEW 2A. VERIFY

LOCATION.

1. PROVIDE AND INSTALL ALL DEVICES SHOWN AS

NEW UNO.

N A

C

M

FIBER OPTIC

ELEC.

PACS

PACS

EXISTING

POE IN RM IT203

4PR UTP

TO IT RM

4PR UTP

TO IT RM

C-1

C-2

C-3

C-4

C-8

C-7

C-6

C-5

NOTE

1. CAMERAS ARE TO BE AXIS

MODEL F4005

2. DUAL AUDIO UNITS ARE AXIS

MODEL F44

DUAL AUDIO UNITS

PHYSICAL

ACCESS CONTROL

PANEL(S) SEE PACS

WALL ELEVATION

FOR MORE INFO

PULL

BOX

TO PACS DOORS

SEE DOOR CARD

ACCESS DETAILS FOR

MORE INFORMATION

PULL

BOX

TO PACS DOORS

SEE DOOR CARD

ACCESS DETAILS FOR

MORE INFORMATION

S S SS S

PAGING

EQUIPMENT

BLDG #1, RM 232

FLOOR

NEW SPEAKERS

NORMAL POWER

CRITICAL BRANCH

GASES

LOW VOLTAGE

1-1/4"C TO CABLE TRAY

1. 3 TELECOM PORT PROVISION, 1 GANG W/ FACEPLATE

2. NOT USED

3. ENHANCED NURSE CALL (PATIENT STATION W/ PILLOW

SPEAKERS)

4. CRITICAL BRANCH PROVISION, 1 GANG W/ FACEPLATE

5. NORMAL POWER PROVISION, 1 GANG W/ FACEPLATE

6. RECEPTACLE, DUPLEX IVORY (20A)

7. DUPLEX 20A RED ILLUMINATED

8. 120V FOR OVERHEAD/EXAM LIGHT

9. VACUUM

10. AIR

11. OXYGEN (O2)

12. TELEMETRY MONTIOR PROVISION, 2 TELECOM PORTS,

1 GANG W/ FACEPLATE

13. PATIENT BED RECEPTACLE.

3 3

S

P

TO OIT ROOM, SEE NOTE 1

NOTE:

1. PROVIDE 1-4PR UTP TO EACH

CAMERA.

2. PROVIDE 42" LED TV MONITOR.

TO PHYSICAL ACCESS CONTROL SYSTEM

(PACS) EQUIPMENT, SEE NOTE 1

24 PORT P.O.E. SWITCH

WIRE MANAGEMENT

WIRE MANAGEMENT

24-PORT FIBER OPTIC

PATCH PANEL

SPACE

DOME

CAMERA

4 PR UTP

24 PORT COPPER

PATCH PANEL

WIRE MANAGEMENT

TO SECURITY

OFFICE (VERIFY

LOCATION)

20A, 120V

STANDARD FIXED WALL OR

DOME CAMERA (TYPICAL)

4 PR UTP

42" LED TV

MONITOR

CCTV SERVER

WITH PC

WORK

STATION AT

NURSE

STATION.

TO GROUNDING BUS

SPACE

DVR/NVR

SPACE

UPS

POE

4 PR UTP

DETAIL NOTES:

A. ALL CABLING SHALL BE 4PR UTP CAT6.

B. POE SHALL BE MOUNTED IN THE IT ROOM.

B.O.D. CISCO 3850-24 POE OR EQUAL.

C. INTERCOM STATION SHALL BE RECESSED IN

2 GANG BOX. B.O.D. AIPHONE IX-SS-2G OR

EQUAL.

D. MASTER STATION SHALL BE EITHER DESK OR

WALL MOUNT. B.O.D. AIPHONE IX-MV(DESK)

OR IX-MV7-W(WALL) OR EQUAL.

E. PROVIDE ADAPTERS, POWER SUPPLIES,

BACK BOXES & RELATED MATERIALS FOR A

COMPLETE AND OPERATIONAL SYSTEM.

ICIC

M

IC IC

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:0

P M

TK401

TECHNOLOGY ENLARGEMENTS

5 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

Scale: 1/4" = 1'-0"

ENLARGED PLAN - BIO MED RM

Scale: 1/4" = 1'-0"

ENLARGED PLAN - IT ROOM - EXISTING

1 EXISTING IT ROOM TO REMAIN.

2 PROVIDE NEW PACS CONTROLLER FOR ALL

NEW DOORS & CONNECT TO EXISTING PACS

CONTROLLER IN ELECTRICAL ROOM.

3 EXISTING PACS CONTROLLER IN EXISTING

ELECTRICAL ROOM.

4 EXISTING IT RACK WITH SPARE CAPACITY

FOR THE WAP & CCTV CABLING. PROVIDE

NEW PATCH PANELS & WIRE MANAGEMENT.

5 EXISTING IT RACK WITH SPARE CAPACITY

FOR NEW DATA CABLING, PROVIDE NEW

PATCH PANELS AND WIRE MANAGEMENT.

6 NEW NURSE CALL EQUIPMENT CABINET.

7 NEW BIOMED EQUIPMENT IN HINGED WALL

CABINET.

8 NEW TELECOM GROUND BAR. CONNECT TO

TGB IN IT ROOM WITH 1 AWG EG

CONDUCTOR.

9 NEW FA NAC PANEL.

10 PATIENT CAMERA SYSTEM.

11 PROVIDE TGB & CONNECT TO EXISTING IT

ROOM WITH #1/0 GRD COPPER CABLE.

Scale: N.T.S.

CCTV SYSTEM RISER DIAGRAM - (IN EXISTING IT RM 203)

Scale: N.T.S.

PHYSICAL ACCESS CONTROL SYSTEM (PACS) RISER

DIAGRAM

Scale: N.T.S.

PAMS RISER DIAGRAM

Scale: N.T.S.

HEADWALL UNIT ELEVATION DIAGRAM

Scale: N.T.S.

PACU & PRE-POST ROOM MONITORING SYSTEM

Scale: N.T.S.

DOOR INTERCOM SYSTEM RISER DIAGRAM

1' - 0"1' - 0"

LAY-IN CEILING

NOTES:

1. BUILDING STRUCTURE.

2. UNISTRUT.

3. 3/8" THREADED ROD WITH BUSHING AND NUTS.

4. CABLE TRAY.

5. GROUND LUG.

6. GROUND CABLE TO TGB.

7. PROVIDE MINIMUM CLEARANCE PER TIA/EIA 569-B.

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

2625 27 28 29 30 31 32 3433 35 36 37 38 39 40 4241 43 44 45 46 47 48

1817 19 20 21 22 23 24109 11 12 13 14 15 1621 3 4 5 6 7 8

FINISHED FLOOR

TYPICAL DATA RACK DETAIL NOTES:

1. 24 PORT FIBER OPTIC PATCH PANEL

WITH COUPLERS.

2. HORIZONTAL WIRE MANAGEMENT.

3. 48 PORT COPPER PATCH PANEL, VOICE.

4. UNINTERRUPTIBLE POWER SUPPLY,

GOVERNMENT FINISH, GOVERNMENT

INSTALLED.

5. DUPLEX RECEPTACLE, SEE ELECTRICAL

DRAWINGS.

6. 48 PORT COPPER PATCH PANEL, DATA.

7. 2-POST EQUIPMENT RACK WITH POWER

STRIP, GROUND BUS, AND VERTICAL &

HORIZONTAL WIRE MANAGEMENT.

8. VERTICAL POWER STRIP.

9. VERTICAL GROUND BUS.

5 5

30"

FINISHED FLOOR

EPCR

ES DC

RX

NOTE:

1. ELECTRICAL CONTRACTOR

SHALL PROVIDE CONDUIT,

BOXES, AND SUPPORTS.

COORDINATE AND VERIFY

LOCATIONS WITH OWNER.

2. PROVIDE CABLING PER

MANUFACTURER'S

RECOMMENDATION.

ELECTRONIC

LOCKING

MECHANISM

3/4" C 1/2" C

1/2" C

FINISHED CEILING

8"x8"x4" HINGED

CONTROLLER BOX

MOUNTED ABOVE

CEILING

1" C / CABLING

TO ACCESS CONTROL

SYSTEM PANEL (PACS),

VERIFY LOCATION

EP

ESDC

1/2" C

1/2" C

1/2" C

1/2" C 1/2" C

ELECTRONIC PANIC

HARDWARE

CARD READER IN SINGLE

GANG BACK BOX, FACING

TOWARDS UNSECURED SIDE

OF DOOR

H E

IG

H

T P

E R

L E

G E

N D

DOOR CONTACT

REQUEST FOR EXIT

SENSOR(S), FACING

TOWARDS SECURED SIDE OF

DOOR

EEB

EMERGENCY EXIT

BUTTON IN SINGLE

GANG BACK BOX

3/4" C

FINISHED FLOOR

CR

ES DC

RX

NOTE:

1. ELECTRICAL CONTRACTOR SHALL

PROVIDE CONDUIT, BOXES, AND

SUPPORTS. COORDINATE AND VERIFY

LOCATIONS WITH OWNER.

2. PROVIDE CABLING PER

MANUFACTURER'S RECOMMENDATION.

ELECTRONIC LOCKING

MECHANISM

3/4" C 1/2" C

1/2" C

FINISHED CEILING

8"x8"x4" HINGED

CONTROLLER BOX

MOUNTED ABOVE CEILING

1" C / CABLING

TO ACCESS CONTROL

SYSTEM PANEL (PACS),

VERIFY LOCATION

CARD READER IN SINGLE

GANG BOX, OR AS REQUIRED

BY MANUFACTURER, FACING

TOWARDS UNSECURED SIDE

OF DOOR

REQUEST FOR EXIT

SENSOR(S), FACING

TOWARDS SECURED SIDE OF

DOOR

EL

1/2" C3/4" C

ELECTRONICALLY

OPERATED LATCH

STRIKE

DOOR CONTACT

EEB

(1) 4 PR UTP

DATA CABLE, BLUE

(1) 4 PR UTP

TELEPHONE

CABLE, BLUE

1/2" HIGH BLACK LETTERS

ON CLEAR BACKGROUND,

PANDUIT OR EQUAL ON

PERMANENT LABEL,

TYPICAL.

XXX

XXX

B B

T

BLANK

SINGLE GANG

COVER PLATE WITH

6 OUTLETS

(TYPICAL).

LOCATIONS AS

SHOWN ON PLANS

TELE/DATA (TYP.) ( 3)

C C

(1) 4 PR UTP

DATA CABLE, BLUE

NOTE: ALL EQUIPMENT AND INSTALLATION SHALL

BE APPROVED BY VAMC IT DEPARTMENT.

BLANK

B

BLANK

FINISHED FLOOR

MOUNTING HEIGHT AS

SHOWN IN DRAWINGS

4-11/16" SQ. BY 2-1/2"

DEEP BOX WITH SINGLE

GANG 5/8" TILE RING.

1-1/4" CONDUIT WITH

COMMUNICATIONS WIRING

WALL

CORRIDORROOM

6"

NYLON BUSHING

COORDINATE WITH DUCTWORK

EXTEND CONDUIT TO ABOVE

FINISHED ACCESSABLE

CEILING IN CORRIDOR TO

CABLE TRAY UNLESS NOTED

OTHERWISE.

SUSPENDED LAY-IN

CEILING

CABLE TRAY

TYPICAL NURSE CALL SYSTEM RISER NOTES:

1. NURSE CALL EQUIPMENT CABINET (RAULAND BORG

RESPONDER 5)

2. NURSE CALL CABLE, 4 PR CAT 6 (BLUE) OR PER MANUFACTURER'S

RECOMMENDATIONS.

3. NURSE CALL POWER CABLE, 2-12 AWG, 1-12 AWG EG IN 3/4"

CONDUIT OR PER MANUFACTURER'S RECOMMENDATIONS.

REQUIRED ON FIRST DOME LIGHT OR DOMELESS CONTROLLER OF

EVERY SIX CONSECUTIVE DOME LIGHTS OR DOMELESS

CONTROLLERS ON CHAIN.

4. LIGHTING CONTROL CABLE, 3-20 AWG IN 1/2" CONDUIT OR PER

MANUFACTURER'S RECOMMENDATIONS.

5. NURSE CALL MULTI-COLOR DOME LIGHT.

6. NURSE CALL PATIENT BED STATION, SINGLE. IF CODE BLUE/CODE

WHITE ARE INTEGRATED INTO BED STATION, EXTERNAL DEVICES

FOR CODE BLUE/CODE WHITE ARE NOT REQUIRED AT THAT

STATION.

7. NURSE CALL PATIENT BED INTERFACE RECEPTACLE (VERIFY BED

TYPE).

8. NURSE CALL EMERGENCY STATION PULL CORD STATION. (+40")

9. NOT USED

10. NURSE CALL MASTER CONSOLE STATION (TOUCH SCREEN).

11. NURSE CALL DUTY/STAFF STATION (SEE DRAWINGS FOR MORE

INFORMATION).

12. NURSE CALL DOMELESS CONTROLLER (SEE DRAWINGS FOR MORE

INFORMATION).

13. TO OTHER NURSE CALL EQUIPMENT CABINET(S) (IN 2A).

14. NURSE CALL CODE STATION (SEE DRAWINGS FOR MORE INFO). IF

CODE STATIONS ARE INTEGRATED INTO BED STATION, EXTERNAL

CODE STATION DEVICES ARE NOT REQUIRED AT THAT BED

STATION.

15. NURSE CALL PILLOW SPEAKER AND CONTROLS (ENTERTAINMENT

TV, LIGHTING, AND OTHER SYSTEMS PER VA).

16. PATIENT ROOM TV (GOVERNMENT FURNISHED AND INSTALLED).

17. PATIENT ROOM LIGHTING.

18. NURSE CALL PATIENT STATION WITH CALL CORD.

19. NURSE CALL STAFF TERMINAL.

20. PROVIDE INTERGATION WITH THE FOLLOWING:

A. HOSPITAL SIP PHONE SYSTEM.

B. TV ENTERTAINMENT SYSTEM.

C. HL7/ADT.

D. OTHER SYSTEMS AS IDENTIFIED IN SPECS.

TO TELECOM

ROOM

NURSE CALL

EQUIPMENT

CABINET

TYPICAL PATIENT BATHROOMTYPICAL PATIENT BED

2 16

5 N12 N D

TO GROUNDING

BUS

GENERAL NURSE CALL SYSTEM RISER NOTES:

A. PROVIDE 1" CONDUIT FROM EACH DEVICE TO

THE CABLE TRAY.

B. PROVIDE A COMPLETE RACEWAY SYSTEM

FOR THE NURSE CALL SYSTEM IF CABLE

TRAY IS NOT AVAILABLE.

C. CONTRACTOR SHALL VERIFY RACEWAY

REQUIREMENT WITH THE NURSE CALL

SYSTEM MANUFACTURERS.

B

S

P

T

E

M

NW

D

TO NEXT

DOME LIGHT

5 N

B

Example: 2 C A101 04

JACK #

ROOM #

UNIT # (IF APPLICABLE)

FLOOR #

Example: B01 F2 IT102 B A 02

BLDG # (IF APPLICABLE)

FLOOR # (IF APPLICABLE)

IT CLOSET #

IT CLOSET LOCATION (UNIT B)

PATCH PANEL #

PORT #

NOTES:

1. ALL CONNECTIONS TO THE TMGB AND TGB SHALL BE MADE

WITH COMPRESSION STYLE LONG BARREL CONNECTORS ON THE

CONDUCTOR AND 2-LUG BOLTED CONNECTIONS TO THE

GROUNDING BARS. CONNECTIONS TO STEEL SHALL BE

WITH SILICON BRONZE HARDWARE. CONNECTION TO SLEEVES

OR CONDUITS SHALL BE BY AN APPROVED GROUNDING

BUSHING.

2. LOCATE TMGB AND TGB ON THE LEFT OF THE TTB AND 16"

AFF.

3. ALL CONDUCTORS USED FOR GROUNDING SHALL BE

MARKED AT CONNECTION POINT AND EVERY TEN FEET (10')

THEREAFTER

WITH A LABEL IDENTIFYING IT AS THE

TELECOMMUNICATIONS GROUNDING BACKBONE (TBB). USE

PANDUIT #LTYK OR

APPROVED EQUIVALENT.

4. PROVIDE 4"H x 20"L x 1/4"W TMGB.

5. PROVIDE 2"H x 24"L x 1/4"W TGB.

6. CONTRACTOR SHALL CLEAN THE BUS BAR AND APPLY ANTI-

OXIDANT PRIOR TO FASTENING THE CONNECTORS TO THE

BUS BAR.

7. ALL COPPER BACKBONE CABLING SHALL MEET THE

REQUIREMENTS OF TIA/EIA 568-C FOR RISER CABLE.

C O

M M

E

Q U

IP

M

E N

T /R

A C

K S

M E

T A

L S

L E

E V

E S

(W

IT

H

IN

C O

M M

R

M

S T

R U

C T

U R

A L S

T E

E L

B A

S K

E T

T R

A Y

G R

O U

N D

L O

O P

MAIN

TMGB

TR-#1

TGB

COMM. EQUIPMENT/RACKS

ELECTRICAL PANEL

STRUCTURAL STEEL

CABLE TRAY

TR-#2

TGB

COMM. EQUIPMENT/RACKS

ELECTRICAL PANEL

STRUCTURAL STEEL

CABLE TRAY

PROVIDE 6 AWG

CONDUCTOR, EACH

RUN

PROVIDE 1/0 AWG CONDUCTOR

TO TGB FOR EACH TR

PROVIDE 2/0 AWG

CONDUCTOR TO GROUND

RING FOR ELECTRICAL

SYSTEM

PROVIDE 1/0 AWG

CONDUCTOR TO

TGB FOR EACH TR

E L E

C T

R

IC

A L P

A N

E L

10"

4"

1/4"

3/16" DIAMETER, TYP. FOR 6

1/4" DIAMETER, TYP. FOR 12

TMGB & TGB

1 TELECOM ROOM OPPER GOUND BAR, 1/4" x 4" x 10", CHATSWORTH PRODUCTS

INC. NO. 10622-010 OR APPROVED EQUAL BY ERICO OR HARGER GOUNDING

PRODUCTS. HOLE CENTERS TO MATCH NEMA DOUBLE LUG CONFIGURATION.

STANDOFF BRACKET ASSEMBLY WITH INSULATORS, TYP. FOR 2.

LOCK WASHER, TYPICAL FOR 2.

ANCHOR BOLTS, TYPICAL FOR 2.

A CONTINUOUS #3/0 GREEN INSULATED CONDUCTOR SHALL BE RUN

FROM SERVICE GROUND AT MAIN SWITCHBOARD (MSB) TO MAIN TELECOM

ROOM GROUND BAR (TMGB).

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:1

P M

TK501

TECHNOLOGY DETAILS

6 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

Scale: N.T.S.

CABLE TRAY ELEVATION - CORRIDOR

Scale: N.T.S.

DATA RACK ELEVATION

Scale: N.T.S.

DOUBLE DOOR CARD ACCESS

Scale: N.T.S.

SINGLE DOOR CARD ACCESS

Scale: N.T.S.

TELECOMMUNICATIONS FACEPLATE

Scale: N.T.S.

TELECOMMUNICATIONS OUTLET INSTALLATION

Scale: N.T.S.

NURSE CALL RISER DIAGRAM

Scale: N.T.S.

IT CLOSET LABELING SCHEME

Scale: N.T.S.

JACK LABELING SCHEME

Scale: N.T.S.

TELECOMMUNICATIONS GROUNDING

Scale: 3/16" = 1'-0"

TELECOM & MAIN ELECTRICAL GROUND BAR

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE

CONSTRUCTED

OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION

DESIGNS

IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC

WITH

NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES.

THE

GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE

AS

SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND

PERIPHERY

OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12

IN.

(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL

ELECTRICAL METALLIC TUBING

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING

E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL

GAS

PIPING MAY BE USED:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

OMEGA FLEX INC

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

TITEFLEX CORP

A BUNDY CO

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

WARD MFG INC

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM)

THICKNESS

OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH

SURFACES

OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT

CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL

ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT

AND

THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

SYSTEM NO.W-L-1001

JUNE 15, 2005

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

MAX PIPE OR

CONDUIT DIAM

IN. (mm)

1 (25)

1 (25)

4 (102)

6 (152)

12 (305)

F RATING

HR

1 OR 2

3 OR 4

1 OR 2

3 OR 4

1 OR 2

T RATING

HR

0+, 1 OR 2

3 OR 4

SECTION A-A

1B

1A

3A

A

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:1

P M

TK502

TECHNOLOGY DETAILS

7 7KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

Scale: N.T.S.

UL PENETRATION DETAIL W-L-1001

FIRE ALARM SYMBOL LEGEND

FIRE ALARM PULL STATION

SYMBOL HEIGHT DESCRIPTION

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

F

F

S

FIRE ALARM SPEAKER

FIRE ALARM STROBE

FIRE ALARM PULL SPEAKER AND STROBE

FIRE ALARM ELECTROMAGNETIC DOOR HOLDER WITH

SMOKE DETECTOR ON EACH SIDE

FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR

FIRE ALARM CEILING MOUNTED SPEAKER

P

FIRE ALARM DUCT SMOKE DETECTOR

FIRE ALARM HEAT DETECTOR

48"

90"

90"

90"

FIRE ALARM CONTROL PANEL

FIRE ALARM NAC PANEL

FIRE ALARM ANNUNCIATOR PANEL

FLOW SWITCH

FACP

NAC

FAAP

TAMPER SWITCH

POST INDICATOR VALVEPIV

REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS

F FIRE ALARM BELL90"

XX - CANDELA

XX - CANDELA

XX - WATTAGEF

S

F

S

H

GENERAL FIRE ALARM NOTES

1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:

A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.

B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.

C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.

D. NFPA 70 NATIONAL ELECTRICAL CODE.

E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.

F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.

G. NFPA 101 LIFE SAFETY CODE.

H. VA FIRE PROTECTION DESIGN MANUAL.

I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.

J. NFPA 88A STANDARD FOR PARKING STRUCTURES.

1. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).

2. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.

3. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

4. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.

5. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

6. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.

7. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE

ALARM DEVICES. COORDINATE WITH COR.

8. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE

LOCATION WITH THE SPRINKLER CONTRACTOR.

9. CONNECT ALL ELECTROMAGNETIC DOOR HOLD OPEN DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE

WITH THE DOOR HARDWARE CONTRACTOR.

10. PROVIDE RELAY CONTROL MODULES FOR PACS, COORDINATE WITH PHYSICAL ACCESS CONTROL SYSTEM

(PACS), CONTRACTOR AND COR.

11. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42"

(1.07M) AND NOT MORE THEN 48" (1.22M) FROM FINISH FLOOR.

12. REFERENCE SHEET TD101 FOR FIRE ALARM DEMOLITION INFORMATION.

NOTES:

1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH

ACCESS CONTROL SYSTEM TO ALLOW EGRESS DURING

ALARM CONDITIONS. COORDINATE BETWEEN ACCESS

CONTROL SYSTEM AND FIRE ALARM SYSTEM

MANUFACTURERS.

2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED

"RED" EMT CONDUIT.

3. ALL WIRING SHALL BE AS RECOMMENDED BY

MANUFACTURER.

4. PROVIDE SEPERATE OUTPUT SIGNALS TO AIR HANDLER

UNIT VFD FOR INDIVIDUAL UNIT SHUT-DOWN.

5. PROVIDE ZONE ADAPTER MODULES TO CONNECT NON

ADDRESSABLE DEVICES SUCH AS FLOW AND TAMPER

SWITCHES, DOOR HOLD-OPEN DEVICES, AND CONTROL

SIGNALS.

6. PROVIDE POWER SUPPLY AND/OR NAC (NOTIFICATION

APPLIANCE CIRCUIT) PANEL AS REQUIRED FOR

ADDITIONAL DEVICES.

7. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.

8. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE

EXISTING SIEMENS FIRE ALARM SYSTEM

FS TS

TO ADDITIONAL

INDICATING

APPLIANCES

TO ADDITIONAL FLOW

AND TAMPER SWITCHES

TO

ADDITIONAL

INITIATING

DEVICES

TO SMOKE DAMPERS

(EX.)

FIRE ALARM

CONTROL

PANEL (FACP)

SPRINKLER SYSTEM DEVICES

S S S TO ADDITIONAL FIRE

ALARM SPEAKERS

R R

CONTROL RELAY

FOR AUTO DOORS

(TYPICAL)

F

F P

RFOR PACS

(EX.)

SECURITY

SYSTEM

INTERCONNECT

(EX.)FIRE ALARM

SYSTEM

REMOTE

ANNUNCIATOR EXISTING

FIRE

ALARM

PANEL

NAC

PANEL

TO ADDITIONAL

FIRE ALARM

DEVICES

F

S

F

S

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:5

P M

FA001

FIRE ALARM GENERAL NOTES,

SYMBOL LEGEND, AND RISER

1 2KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

Scale: N.T.S.

FIRE ALARM RISER

F

F

S

1/2 W 75 Cd

F

C d

F S

1/

W

C d

F

S

1/2 W 75 Cd

F

S

1/2 W 75 Cd

F

S

1/2 W 75 Cd

F

F

S

1/2 W 75 Cd

F

S

1/2 W 75 Cd

F

F

S

1/2 W 75 Cd

F S

1/

W

C d

N A

C

FS

1/

W

C d

F S

1/

W

C d

F

S

1/2 W 30 Cd

FS

1/

W

C d

F

S

1/2 W 30 Cd

F

C d

F S

1/

W

C d

F S

1/

W

C d

F

F

30 Cd

F 15 Cd

F

15 Cd

F

15 Cd

F 30 Cd

F30 Cd

F

30 Cd

F

30 Cd

F

15 Cd

F

15 Cd

A

Q

2-11

O M.2 K.1 F.9 C.9 A.5

2-10

2-8

2-6

2-5

2-3

2-2

2-1

2-9

AA AC

2-4

2-7

L.5

N

D

K.2

F.8

STAIR

S2-02

MEN'S LOCKER

STAFF TOILET

WOMEN'S LOCKER

STAFF TOILET

EQUIPMENT

STAFF LOUNGE

SOILED

HAC

ELECTRICAL

CORRIDOR

C203-38

ELECTRICAL

CORRIDOR

C201-38

WAITING

CORRIDOR

C202-02

CORRIDOR

C204-02

PRE/POST

PRE/POST

PRE/POST

PACU

CLEAN SUPPLY

SOILED HOLDING

HAC

CARE STATION

MEDS

CORRIDOR

C207-02

OR

CORRIDOR

C204-2

CORRIDOR

205-02

OR

STERILE CORE

CORRIDOR

C201-02

CORRIDOR

C206-02

STORAGE

STAIR

S1-02

CORRIDOR

C203-02

SCRUB STATION

247A

ALCOVE

249A

SCRUB STATION

249B

SCRUB STATION

250A

ELEVATOR SHAFT

C202-54

CHASE

C202-56

ELEVATOR 2

C207-02B

ELEVATOR 1

C207-02C

FIBER OPTIC

LOGISTICS

PAMN

C207-02F

PAGING EQUIPMENT

C207-02G

WHEELCHAIR ALCOVE

C3

SOILED UTILITY

ELEC.

CORRIDOR

C2

STRESS LAB

ELEVATOR LOBBY

C1

PRE/POST

PACU

PACU

ALCOVE

C206-02A

ISOLATION

237 ANTE

DICTATION

TOILET

TOILET

STAFF TOILET

ANESTHESIA

IMMED. STER.

BIO-MED

TOILET

TOILET

227 N. MANAGER OFFICE

CONSULTATION

RECEPTION

PSA OFFICE

CHASE

PRE/POST

PRE/POST

PRE/POST

OR

OFFICE

CHASE

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:3

:5

P M

FA101

SECOND FLOOR FIRE ALARM PLAN

2 2KG

RELOCATE AND UPGRADE

OPERATING SUITES-

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

2, 38

RSB

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

0 4 8 16

NORTH

PLAN

1 EXISTING FIRE ALARM PULL STATION TO

REMAIN.

2 EXISTING IT TO REMAIN.

3 NEW NAC PANEL

Scale: 1/8" = 1'-0"

SECOND FLOOR FIRE ALARM PLAN

1. PROVIDE AND INSTALL ALL DEVICES SHOWN AS

NEW UNO.

Sheets
TK001 - TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS
TD101 - SECOND FLOOR TECHNOLOGY/SYSTEMS DEMOLITION PLAN
TK101 - SECOND FLOOR TECHNOLOGY PLAN
TK102 - SECOND FLOOR SYSTEMS PLAN
TK401 - TECHNOLOGY ENLARGEMENTS
TK501 - TECHNOLOGY DETAILS
TK502 - TECHNOLOGY DETAILS
FA001 - FIRE ALARM GENERAL NOTES, SYMBOL LEGEND, AND RISER
FA101 - SECOND FLOOR FIRE ALARM PLAN
2019-11-14T08:23:53-0800
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .