P09 Drawings 03 Structural 100 BID - 15 pages.pdf
PDF 2 MB Posted
- Attached to
- Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
- Solicitation number
- 36C25520R0040_1
About this file
This solicitation is for the construction of a surgical suite addition at the Marion VA Medical Center in Marion, Illinois. The scope of work includes constructing three operating rooms and support services on the second floor of Building 2 and Building 38 to replace the current recreation hall and kitchen. Infrastructure will be installed to provide UPS power meeting all VA requirements. The completed project will deliver a fully operational three operating room inpatient surgical/endovascular and ambulatory surgical service. The solicitation number is 36C25520R0040_1 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. The response due date and award date are not specified. Pricing terms and federal agencies involved are not outlined. No incumbent contractor or set aside information is provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| P09 Drawings 05 Interiors 100 BID - 11 pages.pdf | ||
| P09 Revised official MEP Combined Spec Set VOL 2-1236 pages.pdf | ||
| P09 Drawings 06 Plumbing 100 BID - 25 pages.pdf | ||
| P09 Drawings 07 Mechanical 100 BID - 32 pages.pdf | ||
| P09 Drawings 02 HA 100 BID - 5 pages.pdf | ||
| P09 Drawings 10 FS 100 BID - 4 pages.pdf | ||
| P09 Drawings 08 Electrical 100 BID - 15 pages.pdf | ||
| P09 Drawings 04B Architecture 100 BID - 8 pages.pdf | ||
| P09 Drawings 04A Architectural 100BID - 20 pages.pdf | ||
| Solicitation 36C25520R0040_1 657-501-Construct Surgical Suite Addition 3.docx | DOCX document | |
| P09 Drawings 01 General 100 BID - 5 pages.pdf | ||
| P09 Drawings 09 LV FIREALARM 100 BID - 9 pages.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STEEL BEAM LEGEND
W18X40 C=1"
CAMBERBEAM SIZE
20K20K
BEAM REACTION,
TYP
(20)
QUANTITY OF SHEAR STUDS,
UNIFORMLY SPACED BETWEEN
SUPPORTS, UNO
"(MIN)" = STUDS @ 24" OC FOR
FULL BEAM LENGTHNOTES:
1) REACTION VALUE IS ASD (KIPS), UNO.
2) WHERE NO VALUE IS SHOWN, DESIGN CONNECTION FOR A MINIMUM REACTION OF 16
KIPS.
3) POSITIVE CAMBER UPWARDS, NEGATIVE CAMBER DOWNWARDS. CAMBER SHOWN
ON CANTILEVERS IS AT END OF CANTILEVER.
4) BEAMS ARE PRIMARY MEMBERS FOR FIREPROOFING UNLESS NOTED AS SECONDARY.
5) "M" IN PLACE OF BEAM SIZE INDICATES W10X12.
6) LATERAL FORCE TO BE TRANSFERRED THROUGH SUPPORT BY CONNECTIONS IN
ADDITION TO VERTICAL REACTION FORCES. FORCE MAY ACT IN EITHER DIRECTION.
FORCE IS GREATER OF 0.6W OR 0.7E, UNO.
MOMENT CONNECTION
CANT BM, SAME SIZE
AND END REACTION AS
BACKSPAN, UNO
C=1/2" CAMBER
##K
NOTE 6
MISCELLANEOUS SYMBOLS
NORTH ARROW
GRIDLINES
SOIL
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION
REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
C# COLUMN NOTATION
Z# PRECAST/ BRICK SUPPORT
L# LINTEL NOTATION
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PB ## POST-TENSIONED CONCRETE
BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRANULAR FILL
Name
Elevation
WALL PIER NOTATIONWP ##
W ## WALL NOTATION
N
TS ## THICKENED SLAB NOTATION
# KEYED PLAN NOTE
CONCRETE SYMBOLS
POST-TENSION TENDON
ANCHOR DEAD END
LOCATION
POST-TENSION TENDON
ANCHOR JACKING
LOCATION
REBAR
CHANGE OF SLAB
ELEVATION
SLOPING SLAB
CHANGE OF SLAB
THICKNESS
MECHANICAL COUPLER
REBAR SPLICE
LIMIT OF MEMBER OR
SPAN MARK
DIRECTION OF SPAN
OPENING
SELF-EXPANDING
WATERSTOP
CONTROL JOINT LOCATION
IN CONCRETE WALLS
REBAR TERMINATOR
INTENTIONALLY
ROUGHENED
CONSTRUCTION JOINT
TO 1/4" AMPLITUDE
WELDED WIRE
REINFORCING
PVC WATERSTOP
COLUMN CONTINUES
COLUMN TERMINATED
FORM-SAVER
SLAB ON GRADE
MARK
SOG# WALL FOOTING OR
THICKENED SLAB
WF# / TS#
F#
ISOLATED FOOTING
CONNECTORS
HEADED STUD
CONNECTOR SECTION END/ALT VIEW
CAST-IN ANCHOR
ROD
POST-INSTALLED
MECHANICAL ANCHOR
BOLT
POST INSTALLED
ADHESIVE ANCHOR
STEEL MEMBERS
W-SHAPE BEAM
SHAPE SECTION PLAN VIEWELEVATION
CHANNEL
ANGLE
DOUBLE ANGLE
HOLLOW STRUCTURAL
SECTION
-RECTANGULAR
LLV LLH
HOLLOW STRUCTURAL
SECTION
-CIRCULAR (PIPE)
OPEN WEB STEEL
JOIST
STEEL SYMBOLS
STEEL DECK
STEEL DECK MARK AND
SPAN DIRECTION
BEAM SPLICE
CONNECTION
BEAM MOMENT
CONNECTION AT COLUMN
BEAM SHEAR CONNECTION
AT COLUMN
BEAM CONTINUOUS OVER
COLUMN
SLAB ON STEEL
DECK
SLAB ON STEEL
DECK
WWR
COLUMN STARTS HERE
HANGER OR POST
HANGER OR POST
BELOW FLOOR
SLAB-ON-DECK MARK AND
SPAN DIRECTION
OR
D#
S#
C# COLUMN MARK
INT INTERIOR
J/BRG JOIST BEARING
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABORATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MF MOMENT FRAME
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
OWJ PRE-MANUFACTURED OPEN WEB JOIST
PC PRECAST CONCRETE
PEMB PRE-ENGINEERED METAL BUILDING
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
RTU ROOFTOP MECHANICAL UNIT
S SLOPE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SOMD SLAB ON METAL DECK
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TC TOP CHORD
TEMP TEMPERATURE
THRU THROUGH
TJI PREFABRICATED WOOD I-JOIST
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WH WEEP HOLE
WP WORK POINT
WT WEIGHT, STRUCTURAL T
WWF, WWR WELDED WIRE REINFORCEMENT
XS EXTRA STRONG (PIPE)
XXS DOUBLE EXTRA STRONG (PIPE)
& AND
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BC BOTTOM CHORD
BD BOARD
BF BRACED FRAME
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
BU BUILT UP
C STANDARD CHANNEL
CA COLUMN ABOVE
CANT CANTILEVER
CB COLUMN BELOW
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION
JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GL GLUED LAMINATED TIMBER (GLULAM)
GRND GROUND
GT GIRDER TRUSS
HAS HEADED ANCHOR STUD
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR
CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
STRUCTURAL DRAWINGS ABBREVIATIONS
SHEET # SHEET NAME
SS001 ABBREVIATIONS AND SYMBOLS
SS002 GENERAL NOTES
SS003 SPECIAL INSPECTION REQUIREMENTS
SS004 LOAD MAPS
SD101 SECOND FLOOR DEMOLITION PLAN
SD102 ROOF DEMOLITION PLAN
SS102 BUILDING 02 SECOND FLOOR AREA 'A' FRAMING PLAN
SS103 BUILDING 02 SECOND FLOOR AREA'B' FRAMING PLAN
SS105 BUILDING 02 SECOND FLOOR CEILING AREA 'B' FRAMING PLAN
SS106 BUILDING 02 ROOF AREA 'A' FRAMING PLAN
SS107 BUILDING 02 ROOF AREA 'B' FRAMING PLAN
SS108 BUILDING 38 ROOF FRAMING PLAN
SS301 CONCRETE SCHEDULES, SECTIONS AND DETAILS
SS501 STEEL SCHEDULES, SECTIONS, AND DETAILS
SS502 STEEL SECTIONS AND DETAILS
STRUCTURAL INDEX
9025 RIVER ROAD, SUITE 200
INDIANAPOLIS, IN 46240
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
DAVID A. CLARK
081-007588
R E E
NI
G
NE
LA
RUTCURTS
DE
S N E
CI
L
S T
A
TE
OF I LL
IN
O
IS
LICENSE EXPIRES:
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
2020-11-30
AMERICAN
INC.
/1 /2
:3
:5
P M
SS001
ABBREVIATIONS AND SYMBOLS
1 15AJD
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/15/2019
BID DOCUMENTS
657-501
02, 38
DAC
GENERAL
STRUCTURES INDICATED ON THESE DRAWINGS HAVE BEEN DESIGNED FOR THE IN-
SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF
CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURES
ARE DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER CONSTRUCTION IS
COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE
CONSTRUCTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
STRUCTURES AND RELATED COMPONENTS DURING CONSTRUCTION. THIS INCLUDES
THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS,
TIEDOWNS, ETC.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT CONSTRUCTION LOADS
DO NOT EXCEED THE CAPACITY OF ANY STRUCTURAL ELEMENT AT THE TIME THE
LOADS ARE APPLIED, INCLUDING BUT NOT LIMITED TO: WEIGHTS OF MATERIALS,
WEIGHTS OF EQUIPMENT AND WORKERS, AND ALL LOADS APPLIED FROM
TEMPORARY LIFTS, HOISTS AND CRANES, ETC.
THE STRUCTURAL DRAWINGS AND SPECIFICATIONS SHALL BE USED IN CONJUNCTION
WITH THE DRAWINGS AND SPECIFICATIONS OF ALL OTHER DISCIPLINES, TRADES, AND
DELEGATED DESIGN ELEMENTS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATION OF THE STRUCTURAL WORK WITH ALL OTHER APPLICABLE TRADES.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH
THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT.
DO NOT SCALE THE DRAWINGS. REFER TO THE WRITTEN DIMENSIONS AND
INFORMATION.
IF A DISCREPANCY IS NOTED ON THE DRAWINGS, GENERAL NOTES, OR
SPECIFICATIONS, THE CONTRACTOR SHALL SUBMIT TO THE STRUCTURAL ENGINEER
A WRITTEN REQUEST FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE
AFFECTED WORK WITHOUT DOCUMENTED RESOLUTION OF THE DISCREPANCY. ALL
COSTS RESULTING FROM THE CONTRACTOR IMPROPERLY PROCEEDING WITH THE
AFFECTED WORK PRIOR TO DOCUMENTED RESOLUTION OF THE DISCREPANCY,
INCLUDING COST OF REMOVAL AND REPLACEMENT OF NON-CONFORMING WORK,
SHALL BE BORNE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC
ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN
THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN
ADOBE PDF FORMAT.
1. ADHESIVE ANCHORS
2. NON-SHRINK GROUT
3. CEMENT
4. FLY ASH
5. AGGREGATE AND GRADATION REPORT
6. CONCRETE CURING COMPOUND
7. STEEL MILL REPORTS
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS
TAKEN FROM DRAWINGS THAT WERE PREPARED FOR (VETERANS ADMINISTRATION
FACILITY MARION, ILL), PREPARED BY (VA MARION, ILL), ENTITLED (HOSPITAL DINING
HALL BLDG. NO 2), DATED (SEPT. 1940). AS WELL AS DRAWINGS PREPARED FOR (VAMC
MARION ILLINOIS), PREPARED BY (SIEBOLD, SYDROW, & ELFANBAUM), ENTITLED
(EXPAND DIETETICS SPD ADDITION), DATED (2 FEB 87).
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS
PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS
INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES,
MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE
STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS AND METHODS OF
DEMOLITION REQUIRED TO COMPLETE THE WORK, INCLUDING MAINTAINING THE
SAFETY AND INTEGRITY OF THE EXISTING STRUCTURE. DEMOLISHED MATERIALS
SHALL BE DISPOSED OF SAFELY AND IN CONFORMANCE WITH THE CONTRACT
DOCUMENTS AND ALL APPLICABLE LAWS, CODES AND REGULATIONS.
WHERE ELEMENTS ARE INDICATED TO BE CUT AND REMOVED, DO NOT CUT BEYOND
THE EXTENTS OF THE ELEMENTS INDICATED TO BE REMOVED AND DO NOT EXTEND
CUTS INTO ELEMENTS THAT ARE TO REMAIN.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK
ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR
DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO THE FABRICATION AND
ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THIS PROJECT,
THAT BECOME DAMAGED, SHALL BE REPLACED WITH NEW MATERIAL OF EQUAL
QUALITY AND APPEARANCE, AT THE CONTRACTOR'S EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE OR DISRUPTION TO ADJACENT
RETAINED WORK. ADJACENT EXISTING CONSTRUCTION SHALL BE PROTECTED FROM
DUST, DIRT AND DEBRIS ACCUMULATION AT ALL TIMES.
DESIGN DATA
NEW STRUCTURES ON THESE DRAWINGS HAVE BEEN DESIGNED IN ACCORDANCE
WITH THE 2015 INTERNATIONAL BUILDING CODE.
O.R. CEILING LOADS
DEAD LOAD 30 PSF
FLOOR LOADS
SEE LOAD MAPS
ROOF LOADS
SEE LOAD MAPS
SNOW LOAD DESIGN DATA (2015 IBC)
GROUND SNOW LOAD (PG) = 15 PSF
SNOW EXPOSURE FACTOR (CE) = 1.0
THERMAL FACTOR (CT) = 1.0
SNOW LOAD IMPORTANCE FACTOR (IS) = 1.2
LOW-SLOPE ROOF SNOW LOAD (PF) = 18.0 PSF
WIND LOAD DESIGN DATA
BASIC WIND SPEED (3-SECOND GUST) = 125 MPH
WIND EXPOSURE = C
WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
EARTHQUAKE DESIGN DATA
SHORT PERIOD SPECTRAL RESPONSE (SS) = 0.909
1-SECOND SPECTRAL RESPONSE (S1) = 0.310
SEISMIC IMPORTANCE FACTOR (IE) = 1.5
RISK CATEGORY = IV
SITE CLASSIFICATION = D
SEISMIC DESIGN CATEGORY = D
SHORT PERIOD SPECTRAL RESPONSE (SDS) = 0.688
1-SECOND SPECTRAL RESPONSE (SD1) = 0.366
ADHESIVE ANCHORS FOR SOLID SUBSTRATES (THREADED ROD AND REBAR)
ADHESIVE ANCHORS FOR SOLID SUBSTRATES SHALL BE HILTI "HIT-HY 200" OR AN
EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
THREADED ANCHORS SHALL BE ASTM A36 RODS FOR INTERIOR EXPOSURES AND
AISI 316 STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL
IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
ADDITIONALLY, ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR
MASONRY WITH AN AGE OF LESS THAN 21 DAYS.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN
ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED,
NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA
SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING
COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
PENETRATIONS AND EMBEDDED ITEMS
CONTRACTOR SHALL COORDINATE WITH ALL AFFECTED TRADES THE REQUIRED
SIZES, TYPES, AND LOCATIONS OF ALL EMBEDDED ITEMS IN, AND ALL PENETRATIONS
THROUGH, STRUCTURAL ELEMENTS PRIOR TO CONSTRUCTION.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN
ON THE STRUCTURAL DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER.
NO ITEMS (INCLUDING, BUT NOT LIMITED TO, CONDUIT, PIPING, ETC.), OTHER THAN
THOSE SHOWN ON THE STRUCTURAL DRAWINGS, SHALL BE EMBEDDED IN
STRUCTURAL ELEMENTS WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
ALL EMBEDDED ITEMS IN EXPOSED EXTERIOR CONCRETE SHALL BE GALVANIZED,
PLASTIC, OR EPOXY-COATED.
DELEGATED DESIGN
FOR ALL SUBMITTALS INDICATED AS "DELEGATED DESIGN," THE CONTRACTOR SHALL
ENGAGE A SPECIALTY STRUCTURAL ENGINEER LICENSED IN THE STATE WHERE THE
PROJECT IS LOCATED TO DESIGN AND DETAIL THE ITEMS NOTED IN THE STRUCTURAL
SUBMITTALS AND SPECIFICATIONS AS A DELEGATED DESIGN.
DELEGATED DESIGN CALCULATIONS AND RELATED DRAWINGS SHALL CONTAIN THE
FOLLOWING, AS A MINIMUM:
1. COVER PAGE SIGNED AND SEALED BY THE SPECIALTY STRUCTURAL ENGINEER
INCLUDING A STATEMENT OF CERTIFICATION THAT THE SUBMITTED
CALCULATIONS ARE IN CONFORMANCE WITH THE DESIGN CRITERIA PROVIDED
IN THE CONTRACT DOCUMENTS AND THAT THE RELATED SHOP DRAWINGS
ARE IN CONFORMANCE WITH THE SUBMITTED CALCULATIONS.
2. TABLE OF CONTENTS, PLACED ON, OR IMMEDIATELY FOLLOWING THE COVER
SHEET.
3. SUMMARY OF APPLICABLE CODE CRITERIA, LOAD DATA AND PERFORMANCE
CRITERIA AS OUTLINED IN THE CONTRACT DOCUMENTS.
4. CLEAR DEFINITION OF THE LOCATION(S) IN THE STRUCTURE WHERE EACH
CALCULATION APPLIES.
5. LOCATION, TYPE, MAGNITUDE AND DIRECTION OF ALL LOADS IMPOSED ON THE
STRUCTURE BY THE DELEGATED DESIGN SYSTEM/COMPONENTS.
SUBMITTALS THAT DO NOT CONTAIN THE INFORMATION NOTED ABOVE WILL BE
REJECTED WITHOUT COMMENT.
THE STRUCTURAL ENGINEER’S REVIEW OF DELEGATED DESIGN SUBMITTALS WILL BE
FOR GENERAL CONFORMANCE WITH THE DESIGN LOADING, DESIGN INTENT AND
LOADS IMPOSED.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE ALL PARTS
OF THE WORK TO BE FABRICATED AND CONSTRUCTED IN ACCORDANCE WITH THE
DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR
GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS
RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL
TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S
REVIEW WILL BE RETURNED UNCHECKED.
PROVIDE ALL SUBMITTALS IN ELECTRONIC PDF FORMAT.
WORK REQUIRING SUBMITTALS FOR STRUCTURAL ENGINEER REVIEW SHALL NOT BE
STARTED BY THE CONTRACTOR WITHOUT APPROPRIATE REVIEWED SUBMITTALS.
WORK PERFORMED BY THE CONTRACTOR PRIOR TO RECEIVING APPROPRIATE
REVIEWED SUBMITTALS SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AS
DEEMED NECESSARY BY THE STRUCTURAL ENGINEER, AT THE CONTRACTOR'S
EXPENSE, AND WITH NO COST TO THE OWNER.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. STRUCTURAL STEEL
2. STEEL DECK
SUBMIT DELEGATED DESIGN SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. STRUCTURAL STEEL CONNECTIONS (INCLUDING DESIGN CALCULATIONS AND
SUMMARY PAGE FOR CONNECTIONS NOT SPECIFICALLY DETAILED IN THE
CONTRACT DRAWINGS)
OMISSION OF ANY MATERIALS REQUIRED BY THE CONTRACT DOCUMENTS FROM SHOP
DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FOR
FURNISHING THESE MATERIALS REGARDLESS OF WHETHER THE SUBMITTALS HAVE
BEEN REVIEWED.
THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THE CONTRACT DOCUMENTS
BY THE CONTRACTOR SIGNIFIES CONTRACTOR’S ACCEPTANCE OF ALL THE
INFORMATION SHOWN “AS IS”. CONTRACTOR WILL BE RESPONSIBLE FOR VERIFYING
THE ACCURACY AND COMPLETENESS OF THE INFORMATION PROVIDED. ISSUED
DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE OVER ANY ELECTRONIC
INFORMATION PROVIDED. ADDENDA, CHANGE ORDERS, SUPPLEMENTAL
INSTRUCTIONS ARE NOT NECESSARILY INCLUDED IN THE ELECTRONIC FILES.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN ALL CONTRACT
DOCUMENTS, INCLUDING LATEST ADDENDA, AND TO DISTRIBUTE TO ALL
SUBCONTRACTORS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS.
STRUCTURAL STEEL
STRUCTURAL STEEL MEMBERS, BRACING, COMPONENTS AND CONNECTIONS SHALL
BE IN ACCORDANCE WITH AISC ALLOWABLE STRESS DESIGN (ASD) UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO
THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST
EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE
SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED OTHERWISE.
HOLLOW STRUCTURAL STEEL SECTIONS (SQUARE, RECTANGULAR, AND ROUND
TUBES) SHALL CONFORM TO ASTM A500 GRADE C, UNLESS NOTED OTHERWISE.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
STRUCTURAL STEEL ROD HANGERS AND BRACING SHALL CONFORM TO ASTM A36,
UNLESS NOTED OTHERWISE.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED
OTHERWISE.
FABRICATE AND ERECT STEEL FRAMING SO THAT CAMBER IS UPWARD AFTER
INSTALLATION.
SPLICE MEMBERS ONLY AT LOCATIONS SPECIFICALLY INDICATED ON
THE DRAWINGS.
DO NOT FIELD MODIFY STRUCTURAL STEEL WITHOUT PRIOR WRITTEN APPROVAL OF
THE STRUCTURAL ENGINEER.
AT STRUCTURAL STEEL AND STEEL JOIST FRAMED ROOFS PROVIDE L4X4X1/4 FRAMED
OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER ALONG ANY SIDE,
UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING
DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING SIZES AND
LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
STRUCTURAL STEEL CONNECTIONS
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION
AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE
DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM
SHEAR REACTION OF 16 KIPS ASD. PROVIDE NO LESS THAN 2 BOLTS IN ANY VERTICAL
ROW OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
BOLTS IN STRUCTURAL STEEL JOINTS SHALL CONFORM TO ASTM F3125 AND SHALL BE
3/4" DIAMETER GRADE A325, UNLESS NOTED OTHERWISE. (TWIST-OFF TENSION
CONTROL BOLTS, IF USED, SHALL CONFORM TO ASTM F3125 AND SHALL BE 3/4"
DIAMETER GRADE F1852, UNLESS NOTED OTHERWISE.)
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL
JOINTS USING HIGH STRENGTH BOLTS, APPROVED BY THE RESEARCH COUNCIL ON
STRUCTURAL CONNECTIONS. UNLESS NOTED OTHERWISE, BOLTED CONNECTIONS
SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED
CONNECTIONS IN BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A
FAYING SURFACES.
BURNING OF HOLES IN STRUCTURAL STEEL IS EXPLICITLY PROHIBITED UNLESS
WRITTEN PERMISSION IS GRANTED BY THE STRUCTURAL ENGINEER. DO NOT FLAME-
CUT HOLES OR ENLARGE HOLES BY BURNING. DRILL HOLES IN STRUCTURAL STEEL.
DO NOT ENLARGE UNFAIR HOLES IN MEMBERS BY BURNING OR BY USING DRIFT PINS.
REAM HOLES THAT MUST BE ENLARGED TO ADMIT BOLTS. FIELD MODIFICATIONS TO
HOLES IN STRUCTURAL STEEL ARE EXPLICITLY PROHIBITED UNLESS WRITTEN
PERMISSION IS GRANTED BY THE STRUCTURAL ENGINEER.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN
WELDING SOCIETY'S STRUCTURAL WELDING CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE
WITH E70XX LOW HYDROGEN ELECTRODES. UNLESS OTHERWISE SHOWN OR NOTED
ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD
E70XX ELECTRODES.
WELD SIZES SHOWN ON THE DRAWINGS ARE THE REQUIRED EFFECTIVE WELD SIZE.
INCREASE WELD SIZES PER AWS FOR SKEWED CONNECTIONS AND CONNECTIONS
WITH GAPS BETWEEN MEMBERS TO MEET THE EFFECTIVE WELD SIZE REQUIREMENT.
PROVIDE RUN-OFF TABS TO ENSURE COMPLETION OF COMPLETE JOINT
PENETRATION (CJP) WELDS AND BEVEL WELDS. REMOVE TABS AND GRIND
SMOOTH AFTER COMPLETION.
REMOVE WELD BACKING BARS AFTER COMPLETION OF WELDING AND GRIND SMOOTH
FOR ALL CONDITIONS EXPOSED TO VIEW IN THE COMPLETED CONSTRUCTION.
CONNECTION DETAILS SHOWN ON THE DRAWINGS ARE INTENDED TO CONVEY THE
DESIGN INTENT. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS,
BOLTS, WELDS, PLATES, ETC., AS NECESSARY FOR A COMPLETE ASSEMBLY FOR
EACH CONNECTION.
IF TEMPORARY ERECTION SUPPORTS ARE UTILIZED BY THE CONTRACTOR, SUCH
SUPPORTS SHALL BE REMOVED AFTER COMPLETION OF THE WORK.
STRUCTURAL STEEL FINISHES
STRUCTURAL STEEL SHALL BE PROVIDED WITH THE FOLLOWING SHOP FINISH UNLESS
SPECIFICALLY NOTED OTHERWISE:
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH
RUST-INHIBITING PRIMER. VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT
SYSTEM SPECIFIED BY THE ARCHITECT. COORDINATE FINISH PAINTING
REQUIREMENTS WITH THE ARCHITECT. STRUCTURAL STEEL THAT IS NOT EXPOSED
IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT
BE SHOP-PRIMED.
ALL EXTERIOR STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE HOT DIP
GALVANIZED, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN
ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE.
FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR
GALVANIZED STEEL, USE A ZINC-RICH COLD-GALVANIZING PAINT.
SERVICEABILITY LIMITS
LIVE LOAD DEFLECTION: SPAN/360 UNO
TOTAL LOAD DEFLECTION: SPAN/360 UNO
9025 RIVER ROAD, SUITE 200
INDIANAPOLIS, IN 46240
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
DAVID A. CLARK
081-007588
R E E
NI
G
NE
LA
RUTCURTS
DE
S N E
CI
L
S T
A
TE
OF I LL
IN
O
IS
LICENSE EXPIRES:
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
2020-11-30
AMERICAN
INC.
/1 /2
:3
:5
P M
SS002
GENERAL NOTES
2 15AJD
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/15/2019
BID DOCUMENTS
657-501
02, 38
DAC
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE
STEEL DECK INSTITUTE'S SPECIFICATIONS AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS
EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION,
WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS.
PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION
UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS
AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE
WET WEIGHT OF CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT
THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION
WHEREVER POSSIBLE. WHERE THREE SPAN CONDITION IS NOT POSSIBLE, NOTIFY
STRUCTURAL ENGINEER PRIOR TO FABRICATION OF DECK SO THAT EVALUATION OF
THE LESSER SPAN CONDITION(S) CAN BE PERFORMED.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK SUPPORTING EXTERIOR SLABS WITH A GALVANIZED FINISH IN
ACCORDANCE WITH ASTM A924 G90.
VIBRATION CRITERIA
ELEVATED STRUCTURAL FLOOR FRAMING HAS NOT BEEN DESIGNED NOR
REINFORCED TO MITIGATE VIBRATION FROM WALKING EXCITATION.
THE STRUCTURE HAS NOT BEEN DESIGNED TO MITIGATE VIBRATIONS FROM
VIBRATING EQUIPMENT. EQUIPMENT CONTRACTOR SHALL PROVIDE AND INSTALL
VIBRATION ISOLATORS AS REQUIRED TO MITIGATE EQUIPMENT VIBRATION.CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER
A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL
BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE
CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE
OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING
INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION
OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION,
AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND
LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION
OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND
MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN
ACCORDANCE WITH "STANDARD DEVIATION" DETERMINATION OUTLINED IN
ACI 318.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY
(ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301).
READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN
CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE
CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1
PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON
THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL HAVE THE PROPERTIES AS INDICATED IN THE
CONCRETE MIX SCHEDULE AND SPECIFICATIONS.
DO NOT INSTALL OR EMBED ALUMINUM ITEMS, INCLUDING BUT NOT LIMITED TO
ALUMINUM CONDUIT, INTO OR IN CONTACT WITH CONCRETE.
WHERE NEW CONCRETE IS PLACED AGAINST HARDENED/EXISTING CONCRETE,
VERIFY SOUNDNESS OF EXISTING CONCRETE AND REMOVE ALL LOOSE MATERIAL,
SNOW, ICE, FROST, WATER, SOIL, DEBRIS AND OTHER DETRIMENTAL MATERIALS
PRIOR TO PLACEMENT OF NEW CONCRETE.
WELDED WIRE REINFORCEMENT
WELDED WIRE REINFORCEMENT SHALL BE SMOOTH WIRE FABRIC CONFORMING TO
ASTM A1064. REINFORCEMENT SHALL BE SUPPLIED IN FLAT SHEETS AND LAPPED A
MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE REINFORCEMENT SHALL BE PLACED AS FOLLOWS, UNLESS NOTED
OTHERWISE:
SLABS ON COMPOSITE DECK: 3/4" DOWN FROM TOP OF SLAB
SUPPORT REINFORCEMENT ON NON-METALLIC CHAIRS TO MAINTAIN PROPER
POSITION THROUGHOUT CONCRETE PLACEMENT.
(NOTE: THE TERM "WELDED WIRE FABRIC," IF USED, IS THE SAME AS "WELDED WIRE
REINFORCEMENT.")
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL
DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN A CONSTANT SLAB THICKNESS.
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO
THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES
AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE
BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR
SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL FRAMING,
INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY
DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER FRAMING ELEVATIONS,
ETC.) IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR
REVIEW BY THE STRUCTURAL ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED
NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT
WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS;
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL
NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE
STRUCTURAL ENGINEER.
PROVIDE SLABS ON METAL DECK WITH A SMOOTH TROWEL FINISH UNLESS NOTED
OTHERWISE.
CONTRACTOR SHALL REVIEW ALL REQUIRED FLOOR FINISH MATERIAL REQUIREMENTS
PRIOR TO PLACEMENT OF CONCRETE AND SHALL PROVIDE FLOOR SLAB FLATNESS
MEETING THE FINISH MATERIAL SUPPLIER’S WRITTEN REQUIREMENTS. FLATNESS
SHALL BE THE MORE STRINGENT OF THE FINISH MATERIAL REQUIREMENTS AND THE
FOLLOWING:
ALL SLABS, UNO:
OVERALL VALUES: FF=25
LOCAL VALUES: FF=20
CONTRACTOR SHALL PROVIDE ALL NECESSARY REPAIR, GRINDING AND/OR LEVELING
OF THE CONCRETE SLAB TO ACCOMMODATE ALL FLOOR FINISHES PRIOR TO
INSTALLATION OF THE FINISH MATERIALS WITH NO ADDITIONAL COST TO THE
PROJECT.
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON
THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS ON METAL DECK AS REQUIRED TO
ACCOMMODATE FLOOR FINISHES AND FINISH MATERIALS PER THE ARCHITECTURAL
DRAWINGS AND SPECIFICATIONS. REVIEW ALL FLOOR FINISH REQUIREMENTS PRIOR
TO PLACEMENT OF CONCRETE SLABS AND COORDINATE SLAB MIX, PLACEMENT AND
CURING TO COMPLY WITH FINISH FLOORING MATERIAL MANUFACTURER’S
REQUIREMENTS.
CURING PROCEDURES SHALL COMPLY WITH ACI 302.1R AND USE OF CURING
MATERIALS SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER’S
REQUIREMENTS. MOISTURE RETENTION COVERS, IF USED, SHALL BE APPLIED FLAT
AND SMOOTH TO RESULT IN A UNIFORM APPEARANCE AND MINIMIZE SURFACE
MARKINGS AND BLEMISHES.
UNLESS NOTED OTHERWISE, OR UNLESS MORE STRINGENT REQUIREMENTS APPLY,
CURE SLABS ON METAL DECK AS FOLLOWS:
SLABS RECEIVING FLOOR COVERING MATERIALS: MOIST CURE A MINIMUM OF 7
DAYS (OR, IF APPROVED BY FLOOR FINISH MATERIAL MANUFACTURER, USE ASTM
C309, TYPE 1, CLASS B, WATERBORNE, MEMBRANE-FORMING CURING COMPOUND,
DISSIPATING). REMOVAL OF CURING COMPOUND MATERIAL, IF REQUIRED FOR
PROPER INSTALLATION OF FLOOR FINISH MATERIALS, SHALL BE PERFORMED BY
THE CONCRETE CONTRACTOR.
EXPOSED SLABS: USE ASTM C1315, TYPE 1, CLASS A, WATERBORNE, MEMBRANE-
FORMING CURING AND SEALING COMPOUND.
FINISH SLABS WITH FIBER REINFORCEMENT IN ACCORDANCE WITH THE FIBER
MANUFACTURER'S RECOMMENDATIONS AND AS REQUIRED TO MINIMIZE FIBER
EXPOSURE AT THE SLAB SURFACE. FOR SLABS WITH APPLIED FINISHES AND/OR
MATERIALS, INCLUDING POLISHED CONCRETE FINISHES WHEN USED, REMOVE ALL
PROTRUDING FIBERS PER THE FIBER MANUFACTURER’S RECOMMENDATIONS AND AS
REQUIRED TO PROPERLY INSTALL THE FINISHES AND/OR MATERIALS. FOR SLABS
EXPOSED TO VIEW IN THE COMPLETED CONSTRUCTION, REMOVE ALL PROTRUDING
FIBERS PRIOR TO COMPLETION OF CONSTRUCTION PER THE FIBER MANUFACTURER’S
RECOMMENDATIONS.
LIGHTWEIGHT CONCRETE
ALL REQUIREMENTS SHALL BE THE SAME AS FOR "CONCRETE" EXCEPT AS FOLLOWS:
LIGHTWEIGHT AGGREGATES SHALL CONFORM TO ASTM C330.
LIGHTWEIGHT CONCRETE SHALL HAVE A MAXIMUM DRY DENSITY OF 110 POUNDS PER
CUBIC FOOT AND A MAXIMUM DENSITY AT PLACEMENT OF 116 PCF.
LIGHTWEIGHT CONCRETE SHALL HAVE THE PROPERTIES AS INDICATED IN THE
CONCRETE MIX SCHEDULE AND SPECIFICATIONS.
WELDED WIRE REINFORCEMENT
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI, UNO.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318, ACI
DETAILING MANUAL (SP66), AND CRSI MANUAL OF STANDARD PRACTICE.
THE CONTRACTOR SHALL PROVIDE BAR SUPPORTS AND SPACERS AS REQUIRED TO
MAINTAIN PROPER SUPPORT AND POSITIONING OF THE REINFORCING STEEL
THROUGHOUT CONCRETE PLACEMENT OPERATIONS. DESIGN OF THE SUPPORT
SYSTEM SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
ELEVATED SLAB TOP REINFORCEMENT: 2 INCHES
ELEVATED SLAB BOTTOM REINFORCEMENT: 1 INCH
SLAB ON METAL DECK REINFORCEMENT: SEE DETAILS
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
LAP SPLICES SHALL BE TENSION LAPS IN ACCORDANCE WITH SPLICE/EMBEDMENT
TABLES, UNO.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
SPECIAL INSPECTION SERVICES SCHEDULE - STEEL CONSTRUCTION
REFER TO IBC 2015 CHAPTER 17 AND AISC 360-10
ITEM TASK APPLICABLE TO
PROJECT (Y/N)
PERFORM OR
OBSERVE
PRIOR TO WELDING:
VERIFY CONTRACTOR MAINTAINS WELDING PROCEDURE SPECIFICATIONS
READILY AVAILABLE FOR ALL WELDERS FOR ALL TYPES OF WELDS
PERFORMED ON THE PROJECT
PERFORM
PERFORM
PERFORM
VERIFY MATERIAL CERTIFICATIONS ARE AVAILABLE FOR ALL CONSUMABLE
WELDING MATERIALS
VISUALLY INSPECT TO CONFIRM NO ARC STRIKES
Y
Y
Y
REFERENCE
AISC 360 TABLE N5.4-1WELDING PROCEDURE
SPECIFICATIONS
WELD MATERIAL
CERTIFICATIONS
ARC STRIKES AISC 360 TABLE N5.4-3
OBSERVEVERIFY FABRICATOR/ERECTOR AS APPLICABLE MAINTAINS RECORDS OF
WHO WELDED EVERY JOINT
YWELDER IDENTIFICATION
SYSTEM
OBSERVEINSPECT FOR PROPER FIT-UP INCLUDING JOINT PREPARATION,
DIMENSIONS, CLEANLINESS, TACKING, AND BACKING (WHERE BACKING IS
APPLICABLE)
NFIT-UP OF GROOVE WELDS
OBSERVEINSPECT FOR CONFIGURATION AND FINISH OF ACCESS HOLES YACCESS HOLES AISC 360 TABLE N5.4-1
OBSERVEINSPECT FOR PROPER FIT-UP INCLUDING DIMENSIONS, CLEANLINESS, AND
TACKING
YFIT-UP OF FILLET WELDS AISC 360 TABLE N5.4-1
DURING WELDING:
OBSERVEVERIFY USE OF QUALIFIED WELDERS YQUALIFIED WELDERS AISC 360 TABLE N5.4-2
OBSERVEINSPECT FOR PROPER PACKAGING, STORAGE AND PROTECTION YWELDING CONSUMABLES AISC 360 TABLE N5.4-2
OBSERVEVERIFY NO WELDING OCCURS OVER CRACKED TACK WELDS YTACK WELDS AISC 360 TABLE N5.4-2
OBSERVEVERIFY WIND SPEED WITHIN LIMITS AND PROPER
PROTECTION/PREPARATION FOR PRECIPITATION AND TEMPERATURE
YFIELD CONDITIONS AISC 360 TABLE N5.4-2
AFTER WELDING:
OBSERVEVERIFY PROPER CLEANING OF COMPLETED WELDS YWELDS CLEANED AISC 360 TABLE N5.4-3
INSPECT WELDS TO CONFIRM PROPER SIZE, LENGTH, LOCATION AND
VISUAL ACCEPTANCE CRITERIA (CRACK PROHIBITION, WELD/BASE METAL
FUSION, CRATER CROSS SECTION, WELD PROFILES, WELD SIZE, UNDERCUT,
POROSITY) AS FOLLOWS:
SIZE, LENGTH, LOCATION, AND
VISUAL ACCEPTANCE CRITERIA
(NOTE 3 - SEE AISC 360)
AISC 360 TABLE N5.4-3
PERFORMVISUALLY INSPECT AND VERIFY ULTRASONIC TESTING IS PERFORMED FOR
100% OF ALL CJP WELDS
Y
PERFORMVISUALLY INSPECT 100% OF ALL CJP WELDS Y
PERFORMVISUALLY INSPECT ALL DOUBLER PLATES, CONTINUITY PLATES AND
STIFFENER PLATES WHERE WELDING OCCURS WITHIN THE k-AREA OF THE
STEEL SECTION TO CONFIRM NO CRACKS IN THE MEMBER WEB
N"k"-AREA WELDING AISC 360 TABLE N5.4-3
PERFORMVISUALLY INSPECT TO CONFIRM PROPER REMOVAL OF ALL BACKING
REMOVED. VERIFY ALL WELD TABS REMOVED (IF REQUIRED)
NBACKING AND WELD TABS
REMOVED
AISC 360 TABLE N5.4-3
PERFORMDOCUMENT ACCEPTANCE OR REJECTION OF WELDED CONNECTIONS YDOCUMENTATION AISC 360 TABLE N5.4-3
PERFORMVERIFY MANUFACTURER'S CERTIFICATIONS ARE AVAILABLE FOR FASTENER
MATERIALS
Y
PRIOR TO BOLTING:
MATERIAL CERTIFICATIONS AISC 360 TABLE N5.6-1
OBSERVEVERIFY FASTENERS ARE MARKED PER ASTM STANDARDS YFASTENER MARKINGS AISC 360 TABLE N5.6-1
OBSERVEVERIFY CORRECT GRADE, TYPE, AND SUFFICIENT LENGTH FOR THREADS
EXCLUDED FROM THE SHEAR PLANE (ONLY WHERE SPECIFICALLY
INDICATED)
YFASTENER SELECTIONS AISC 360 TABLE N5.6-1
OBSERVEVERIFY PROPER BOLTING PROCEDURE FOR THE JOINT YBOLTING PROCEDURE AISC 360 TABLE N5.6-1
OBSERVEVERIFY CONNECTING ELEMENTS, INCLUDING FAYING SURFACES AND HOLE
PREPARATION (IF SPECIFIED) MEET APPLICABLE REQUIREMENTS
YCONNECTING ELEMENTS AISC 360 TABLE N5.6-1
NOTES:
1. SEE CONTRACT DOCUMENTS FOR WELDING REQUIREMENTS. SEE AISC 360 FOR ADDITIONAL INFORMATION.
2. SEE AISC 360 FOR SPECIFIC REQUIRED ELEMENTS OF WELD PROCEDURE SPECIFICATION.
3. SEE AISC 360 FOR SPECIFIC REQUIRED VISUAL ACCEPTANCE CRITERIA.
4. "OBSERVE" REQUIRES OBSERVATION ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
5. "PERFORM" REQUIRES TASKS TO BE PERFORMED FOR EACH OPERATION, JOINT OR MEMBER AS APPLICABLE.
VERIFY ALL WELD MATERIALS ARE PROPERLY MARKED WITH VALID
TYPE/GRADE IDENTIFICATION
OBSERVEY AISC 360 TABLE N5.4-1WELD MATERIAL
IDENTIFICATION
WELDED MEMBERS
AISC 360 TABLE N5.4-1
AISC 360 TABLE N5.4-1
AISC 360 TABLE N5.4-1
OBSERVEVERIFY WELDING PROCEDURE SPECIFICATIONS ARE FOLLOWED YWELDING PROCEDURE
SPECIFICATION (NOTE 2 - SEE
AISC 360)
AISC 360 TABLE N5.4-2
OBSERVEVERIFY EACH PASS MEETS PROFILE LIMITATIONS AND QUALITY
REQUIREMENTS, INTERPASS AND FINAL CLEANING
YWELDING TECHNIQUES AISC 360 TABLE N5.4-2
OBSERVEINSPECT FOR PROPER PLACEMENT AND INSTALLATION OF STEEL HEADED
STUD ANCHORS
NCOMPOSITE BEAM HEADED
STUD ANCHORS
PERFORMVISUALLY INSPECT 100% OF WELDS IN LATERAL LOAD RESISTING MOMENT
FRAMES AND BRACED FRAMES
Y
PERFORMVISUALLY INSPECT 20% OF ALL FILLET WELDS NOT IN LATERAL LOAD
RESISTING MOMENT FRAMES AND BRACED FRAMES
Y
PERFORMVERIFY APPROVED REPAIRS OF NON-CONFORMING ITEMS (WHEN
REQUIRED) ARE PROPERLY COMPLETED
YREPAIRS AISC 360 TABLE N5.4-3
BOLTED MEMBERS
OBSERVEVERIFY PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION
PERSONNEL IS OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES
AND METHODS USED
YPRE-INSTALLATION
VERIFICATION
AISC 360 TABLE N5.6-1
OBSERVEVERIFY PROPER STORAGE OF BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS
YPROPER STORAGE AISC 360 TABLE N5.6-1
OBSERVEVERIFY ALL FASTENING ELEMENTS ARE PROPERLY POSITIONED IN THE
JOINT PRIOR TO TIGHTENING
Y
DURING BOLTING:
PROPER POSITIONING AISC 360 TABLE N5.6-2
OBSERVEVERIFY COMPONENT NOT TURNED BY THE WRENCH IS PREVENTED FROM
ROTATING DURING TIGHTENING
YBOLT TIGHTENING AISC 360 TABLE N5.6-2
OBSERVEVERIFY ALL BOLTS AT A CONNECTION TO BE PRETENSIONED ARE FIRST
BROUGHT INTO SNUG-TIGHT CONDITION PRIOR TO START OF PRE-
TENSIONING
YPRETENSIONED BOLTS SNUG
TIGHTENED
AISC 360 TABLE N5.6-2
OBSERVEVERIFY FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH RCSC
SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS
YPRETENSIONED BOLTS
TIGHTENING
AISC 360 TABLE N5.6-2
PERFORMDOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS YDOCUMENTATION AISC 360 TABLE N5.6-3
AFTER BOLTING:
PERFORMINSPECT INSTALLATION OF ALL BASE PLATES FOR PROPER ANCHORAGE
(INCLUDING WELDED PLATE WASHERS WHERE INDICATED) AND GROUTING
BENEATH BASE PLATE
Y
STEEL FRAMING (GENERAL)
COLUMN BASES
PERFORMINSPECT ALL COLUMN SPLICES TO CONFIRM THAT GAPS BETWEEN
BEARING ELEMENTS DO NOT EXCEED 1/16-INCH
NCOLUMN SPLICES
PERFORMINSPECT FOR CONFORMANCE WITH REQUIRED SIZE, SPACING AND
CONNECTION REQUIREMENTS
YBEAM, GIRDER AND COLUMN
MEMBERS
PERFORMINSPECT SUPPORT MATERIALS FOR PROPER SIZE, POSITIONING AND
CONNECTIONS
YROOF AND FLOOR DECK/SLAB
EDGE SUPPORTS
PERFORMINSPECT INSTALLATION OF ALL MEMBERS AND CONNECTIONS IN BRACED
FRAMES AND MOMENT FRAMES FOR PROPER SIZE, POSITIONING AND
CONNECTIONS
NBRACED FRAMES AND
MOMENT FRAMES
PERFORMVERIFY PROPER PLACEMENT AND INSTALLATION OF STEEL DECK N
COMPOSITE STEEL FRAMING
PERFORMINSPECT DIAMETER, LENGTH, QUANTITY AND POSITIONING OF STEEL
HEADED STUD ANCHORS
N
PERFORMRING TEST 100% OF HEADED STUD ANCHORS WITH A 3 LB HAMMER N
PERFORMBEND TEST QUESTIONABLE HEADED STUD ANCHORS TO 15 DEGREES N
PERFORMDOCUMENT ACCEPTANCE OR REJECTION OF COMPOSITE STEEL FRAMING
ELEMENTS
N
INSPECT COMPOSITE STEEL FRAMING PRIOR TO PLACEMENT OF
CONCRETE AS FOLLOWS:
AISC 360 TABLE N6.1
AISC 360 TABLE N6.1
STEEL GRATING INSPECT STEEL GRATING AS FOLLOWS:
PERFORMVERIFY PROPER SIZE, TYPE AND FINISH N
PERFORMVERIFY PROPER ATTACHMENTS TO SUPPORTING STRUCTURE(S) N
SPECIAL INSPECTION
THE GENERAL CONTRACTOR SHALL EMPLOY INDEPENDENT AGENCY(IES) OR
INDIVIDUAL(S) TO PROVIDE SPECIAL INSPECTION FOR ITEMS AS INDICATED ON THE
DRAWINGS.
SPECIAL INSPECTION IS A MANDATORY REQUIREMENT FOR VERIFYING CONFORMANCE
OF THE INDICATED CONSTRUCTION. SPECIAL INSPECTION IS REQUIRED IN ADDITION TO
ALL MATERIAL TESTS AND INSPECTIONS IDENTIFIED ELSEWHERE IN THE CONSTRUCTION
DOCUMENTS.
THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON, WHO SHALL DEMONSTRATE
COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL AND THE STRUCTURAL
ENGINEER, FOR INSPECTION OF EACH PARTICULAR TYPE OF CONSTRUCTION OR
OPERATION REQUIRING SPECIAL INSPECTION.
“PERIODIC” SPECIAL INSPECTION IS DEFINED AS “THE PART-TIME OR INTERMITTENT
OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL
INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING
PERFORMED AND AT THE COMPLETION OF THE WORK.”
“CONTINUOUS” SPECIAL INSPECTION IS DEFINED AS “THE FULL-TIME OBSERVATION OF
WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS
PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.”
SUBMIT TO THE STRUCTURAL ENGINEER FOR REVIEW A MINIMUM OF 14 DAYS PRIOR TO
COMMENCEMENT OF CONSTRUCTION OF ELEMENTS REQUIRING SPECIAL INSPECTION
THE FOLLOWING:
1. NAME(S), ADDRESS(ES), TELEPHONE NUMBER(S), EMAIL ADDRESS(ES), AND
STATEMENT(S) OF QUALIFICATIONS OF ALL SPECIAL INSPECTOR(S) TO BE
ENGAGED ON THE PROJECT.
2. A LISTING OF ALL ITEMS TO RECEIVE SPECIAL INSPECTION, DESIGNATION
WHETHER INSPECTIONS WILL BE CONTINUOUS OR PERIODIC AND THE NAME OF
THE INDIVIDUAL THAT WILL BE PERFORMING INSPECTION FOR EACH ITEM.
THE CONTRACTOR SHALL COORDINATE WITH THE SPECIAL INSPECTOR SUFFICIENTLY IN
ADVANCE OF WORK REQUIRING SPECIAL INSPECTION AND SHALL PROVIDE ACCESS TO
THE SITE AND TO THE CONSTRUCTION DOCUMENTS (CURRENT DRAWINGS AND
SPECIFICATIONS) FOR THE SPECIAL INSPECTOR CARRY OUT THE REQUIRED
OPERATIONS.
THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK REQUIRING SPECIAL INSPECTION
FOR CONFORMANCE TO THE CONSTRUCTION DOCUMENTS. ALL NON-CONFORMING
WORK SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR
CORRECTION, THEN, IF UNCORRECTED, TO THE IMMEDIATE ATTENTION OF THE OWNER
OR OWNER’S AGENT AND STRUCTURAL ENGINEER.
THE SPECIAL INSPECTOR SHALL SUBMIT PERIODIC PROGRESS REPORTS TO THE OWNER
OR OWNER’S AGENT, CONTRACTOR AND STRUCTURAL ENGINEER IDENTIFYING ALL
SPECIAL INSPECTION OPERATIONS PERFORMED. REPORTS SHALL BE SUBMITTED NO
MORE THAN 7 DAYS FOLLOWING EACH SPECIAL INSPECTION OPERATION. REPORTS
SHALL IDENTIFY THE ITEM(S) INSPECTED AND AN INDICATION OF WHETHER THE
INSPECTED ITEMS WERE IN CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
AT THE COMPLETION OF ALL WORK REQUIRING SPECIAL INSPECTION, THE SPECIAL
INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT TO THE OWNER OR OWNER’S AGENT,
CONTRACTOR AND STRUCTURAL ENGINEER STATING WHETHER THE WORK REQUIRING
SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTOR'S KNOWLEDGE, IN
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
FAILURE TO PERFORM SPECIAL INSPECTION FOR THE INDICATED CONSTRUCTION OR
FAILURE TO CORRECT NON-CONFORMING WORK SHALL CONSTITUTE A BASIS FOR
REJECTION OF THE WORK AND REMOVAL AND REPLACEMENT BY THE GENERAL
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER, INCLUDING, BUT NOT LIMITED
TO:
1. THE COST OF REMOVAL AND REPLACEMENT OF ALL WORK FOR WHICH SPECIAL
INSPECTION WAS REQUIRED BUT NOT PERFORMED, INCLUDING THE COST OF
TESTING AND SPECIAL INSPECTION FOR THE REPLACEMENT WORK.
2. THE COST OF ALL RELATED WORK MADE NECESSARY BY THE REMOVAL AND
REPLACEMENT OF THE UNINSPECTED WORK PER ITEM 1 ABOVE.
3. THE COST FOR DESIGN PROFESSIONAL’S SERVICES RELATED TO ALL WORK FOR
WHICH SPECIAL INSPECTION WAS REQUIRED BUT NOT PERFORMED AND
SERVICES RELATED TO THE REPLACEMENT WORK.
PROVIDE SPECIAL INSPECTION FOR THE FOLLOWING CONSTRUCTION:
STEEL CONSTRUCTION
SEE TABLES ON THE DRAWINGS FOR SPECIAL INSPECTION PROGRAM REQUIREMENTS.
9025 RIVER ROAD, SUITE 200
INDIANAPOLIS, IN 46240
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
DAVID A. CLARK
081-007588
R E E
NI
G
NE
LA
RUTCURTS
DE
S N E
CI
L
S T
A
TE
OF I LL
IN
O
IS
LICENSE EXPIRES:
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
2020-11-30
AMERICAN
INC.
/1 /2
:3
:5
P M
SS003
SPECIAL INSPECTION REQUIREMENTS
3 15AJD
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/15/2019
BID DOCUMENTS
657-501
02, 38
DAC
A
H
C
C
C CE
E
H
D
C
H
NOT IN SCOPE
G
H
F
H
H
E X
S E
IS
M
IC
T
O W
E R
E X
S E
IS
M
IC
T
O W
E R
C
H
G
A
H
D
K
UNIFORM LOAD SCHEDULE
MARK DESCRIPTION
DESIGN LOADS (PSF)
DEAD LIVE
A
NOTES:
1. DEAD LOAD (WHEN DEFINED) REPRESENTS SELF-WEIGHT ALLOWANCE OF THE PRIMARY
STRUCTURAL SYSTEM. WHEN NOT DEFINED, SEE DRAWINGS FOR MEMBER MATERIALS AND SIZES.
2. SUPERIMPOSED DEAD LOAD IS PERMANENT UNIFORM DEAD LOAD ALLOWANCE SUPPORTED BY THE
STRUCTURE.
3. FOR SNOW LOADS DESIGN FOR WORST CASE OF UNIFORM SNOW OR SNOW DRIFT CONDITION.
4. "NR" = NON-REDUCIBLE LIVE LOAD.
5. INCLUDES 15 PSF LIVE LOAD ALLOWANCE FOR PARTITIONS.
B
D
20TYPICAL ROOF
SNOW
18 PSF MIN -OR-
DRIFT PER LOAD
MAPS / DIAGRAMS
100STAIRS SEE NOTE 1 NA
C
SUPERIMPOSED
DEAD
NA
E
100CORRIDOR 15 NA
F
60OPERATING ROOMS 15 NA
G
40PATIENT ROOMS 15 NA
H
65 NOTE 5OFFICE 15 NA
60PASSAGE/LOUNGE
/WAITING
15 NA
75 NOTE 5SUPPORT SPACES 15 NA
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
SEE NOTE 1
J 150MECHANICAL ROOMS 15 NASEE NOTE 1
K 125STORAGE 15 NRSEE NOTE 1
NOT IN SCOPE
J
J
B
B
B
BUILDING 2 ROOF
BELOW
J
B
B
9025 RIVER ROAD, SUITE 200
INDIANAPOLIS, IN 46240
TEL 317.547.5580 FAX 317.543.0270
www.structurepoint.com
DAVID A. CLARK
081-007588
R E E
NI
G
NE
LA
RUTCURTS
DE
S N E
CI
L
S T
A
TE
OF I LL
IN
O
IS
LICENSE EXPIRES:
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
2020-11-30
AMERICAN
INC.
/1 /2
:3
:0
P M
SS004
LOAD MAPS
4 15AJD
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/15/2019
BID DOCUMENTS
657-501
02, 38
DAC
1/16" = 1'-0"SS004
1 LOAD MAP - 2ND FLOOR
1/16" = 1'-0"SS004
3 LOAD MAP -…