P09 Drawings 06 Plumbing 100 BID - 25 pages.pdf

PDF 5 MB Posted

Attached to
Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
Solicitation number
36C25520R0040_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This solicitation is for the construction of a surgical suite addition at a Veterans Affairs medical center. The scope of work includes constructing three operating rooms, endovascular services, and an ambulatory surgical service on the second floor of two buildings. Infrastructure will also be installed to support uninterruptible power supply requirements. Upon completion, the facility will have a fully operational three operating room inpatient surgical and endovascular suite as well as an ambulatory surgical service. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MA

MV

CO

EV

VE

AI

FOV

FOR

FOS

FP

LPG

NPW

NO

O

N

G

MPG

G

MPG

CA

CD

ACD

V

AV

AW

AW

SD

OSD

GW

GW

SS

W

ID

SPD

T

T

SCW

WS

140°

SAN

W

SD

CAP

AV

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT

PUMP NO.3 IN BUILDING NO.26

EQUIPMENT ABBREVIATION (PUMP)

IS LOCATED.

ORAL EVACUATION

LABORATORY VACUUM

LABORATORY AIR

TEMPERED WATER RETURN

TEMPERED WATER SUPPLY

INDUSTRIAL AIR

LA

LV

OA

IA

TWR

TWS

FILTERED COLD WATERFCW

FUEL OIL DISCHARGEFOD

ANCHOR

CONNECTION - SIDE

ECCENTRIC REDUCER

CONNECTION - BOTTOM, 45° OR 90°

CONNECTION - TOP, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

RISE OR DROP IN PIPE

STRAINER

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES

PIPING ACCESSORIES

INVERTED BUCKET TRAP SET INCLUDING

FLOOR DRAIN (FD), SIZE & TYPE

ROOF DRAIN (RD), SIZE & TYPE

FLOOR SINK (FS), SIZE & TYPE

NATURAL GAS BELOW GRADE (G)

SUMP OR SEWAGE PUMP DISCHARGE (SPD)

CONDENSATE DRAIN (CD)

INDIRECT DRAIN (ID)

NATURAL GAS (G)

NITROUS OXIDE (NO)

LIQUIFIED PETROLEUM GAS (LPG)

FIRE PROTECTION (FP)

WATER SERVICE (WS)

COMPRESSED AIR (CA)

NITROGEN (N)

MEDICAL AIR (MA)

OXYGEN (O)

DOMESTIC HOT WATER RECIRC.

SOIL PIPING - ABOVE FLOOR (SS)

SOIL PIPING - BELOW FLOOR (SAN)

STORM DRAIN - ABOVE FLOOR (SD)

STORM DRAIN - BELOW FLOOR (SD)

ACID WASTE - ABOVE FLOOR (AW)

ACID WASTE - BELOW FLOOR (AW)

DOMESTIC COLD WATER

DOMESTIC HOT WATER

140° DOMESTIC HOT WATER (140°)

WASTE PIPING - ABOVE FLOOR (W)

WASTE PIPING - BELOW FLOOR (W)

GREASE WASTE - ABOVE FLOOR (GW)

GREASE WASTE - BELOW FLOOR (GW)

SOFTENED COLD WATER (SCW)

ACID VENT (AV)

VENT PIPING (V)

HOSE BIBB (HB)

NONFREEZE WALL HYDRANT (NW)

WALL CLEANOUT (WCO)

FLOOR CLEANOUT (FCO)

EXTERIOR CLEANOUT (ECO)

THERMOSTATIC MIXING VALVE

BACKFLOW PREVENTER

OVERFLOW STORM DRAIN - ABOVE FLOOR (OSD)

NON POTABLE WATER (NPW)

FUEL OIL SUPPLY (FOS)

FUEL OIL RETURN (FOR)

FUEL OIL VENT (FOV)

AUXILIARY CONDENSATE DRAIN (ACD)

CARBON DIOXIDE (CO)

MEDICAL VACUUM (MV)

EVACUATION (EV)

MEDICAL VACUUM EXHAUST (VE)

MEDICAL AIR INTAKE (AI)

TRAP PRIMER LINE (T)

WATER METER

MEDIUM PRESSURE NATURAL GAS (MPG)

MEDIUM PRESSURE NATURAL GAS ON ROOF (MPG)

ELBOW DOWN WITH SHUT-OFF VALVE (SOV)

TEE DOWN WITH SHUT-OFF VALVE (SOV)

TEE UP WITH SHUT-OFF VALVE (SOV)

RECIRCULATION PUMP

DIRECTION OF FLOW

EXISTING PIPING TO REMAIN

EXISTING PIPING TO BE REMOVED

FLANGE CONNECTION

CLEANOUT

ELBOW DOWN

ELBOW UP

TEE DOWN

ELBOW UP WITH SHUT-OFF VALVE (SOV)

TEE UP

UNION

THERMOMETER

PRESSURE GAUGE

PRESSURE REDUCING VALVE

REDUCER

SHOWER HEADS

JANITORS SINK

DRINKING FOUNTAIN & TYPE

SHOWER

BATHTUB

TANK TYPE WATER CLOSET

COUNTER TOP LAVATORY & TYPE

WALL MOUNTED LAVATORY & TYPE

URINAL SINK & TYPE

BALL VALVE

GATE VALVE WITH 3/4 " HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

GATE VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

GLOBE VALVE

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

AUTOMATIC AIR VENT

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL OR FIRE ALARM PLAN NOTE CALL OUT

TECHNOLOGY PLAN NOTE CALL OUT

PLUMBING EQUIPMENT DESIGNATION

MECHANICAL EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL NUMBER

SHEET NUMBER

LIMIT OF DEMOLITION

TRAP PRIMER LINE - BELOW SLAB (T)

CO

DOUBLE EXTERIOR CLEANOUT (ECO)

CLEANOUTS

DRAINS AND TRAPS

EQUIPMENT

FITTINGS AND ACCESSORIES

SHEET NUMBER

SECTION NUMBER

JANITORS SINK - CORNER

MEDICAL GAS OUTLET (TYPE)

EXISTING TO REMAIN

A

A/E ARCHITECT / ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF ECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

B

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BREAK HORSEPOWER

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CELSIUS

CA COMPRESSED AIR

CGA COMPRESSED GAS ASSOCIATION

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CO CLEANOUT

CS CLINICAL SINK

CV CONTROL VALVE

D

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

E

EL ELEVATION

EMCS ENERGY MONOSERRAT

AND CENTRAL SYSTEM

EPA ENVIROMENTAL PROTECTION AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

F

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

G

GAL GALLON

GCO GRADE CLEANOUTS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

H

H&CW HOT AND COLD WATER

HB HOSE BIBB

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

I

ID INSIDE DIAMETER

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

K

KW KILOWATT

KWH KILOWATT-HOUR

L

L/S LITER PER SECOND

LA LABORATORY AIR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT

ROOM

MH MANHOLE

MOU MEMORANDUM OF

UNDERSTADING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N

N2 NITROGEN

N20 NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW

P

PA PASCAL

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE

INSTITUTE

PG PRESSURE GAGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH

ATMOSPHERE

PSIG POUNDS PER SQUARE INCH

GAGE

PTRV PRESSURE TEMPERATURE RELIEF

VALVE

PW POTABLE WATER

R

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RO REVERSE OSMOSIS WATER

RWL RAIN WATER LEADER

S

SAN SANITARY SEWER

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS

NATIONAL ASSOCIATION

SCFM STANDARD CUBIC FOOT/MINUTE

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF SQUARE FEET

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

T

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

V

V VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

Y

YCO YARD CLEANOUT

YH YARD HYDRANT

26-P 3

PIPING SYMBOLS

ANNOTATION

XX-1

xx

X100

X100

GENERAL PLUMBING SYMBOLS

DENTAL

MEDICAL GASES

STORM

FUEL

EXISTING PIPING

WATER

WASTE

VALVE SYMBOLS

GENERAL EQUIPMENT

FLOOR MOUNTED FLUSH VALVE

WATER

CLOSET

WALL MOUNTED FLUSH VALVE

WATER

CLOSET

ETR

ABBREVIATIONS

WAGD WASTE ANESTHESIA GAS DISPOSAL

DISTILLED WATERDW

Z

ZVB ZONE VALVE BOX

ETR EXISTING TO REMAIN

FR FROM

ABV ABOVE

DOMESTIC COLD WATER RECIRC.

CONNECT TO EXISITNG

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1 /2

:5

:0

A

M

P-000

PLUMBING LEGEND

1 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

5" SD

2" DCW TO REMAIN

EXISTING. ROOF

DRAIN TO REMAIN.

V V

EXIST. 4" FD FROM

MECH ROOM ABV.

TO REMAIN.

3” VENT TO REMAIN

4” VTR TO REMAIN

3” VTR TO REMAIN

5” VTR TO REMAIN

EXIST. 4” VENT FROM BELLOW TO REMAIN. EXISTING 2” WASTE

DN/ 2” VENT UP TO

REMAIN

V

V V V

V V V

4" S S

V

E T

R

3" V

4" V

2" DCW ETR

4" V

/1 PD102C

/1 PD102C

EXIST. 4" VTR TO REMAIN2

V V

V V

3"

3"

SD

OSD

SD

OSD

CAP PIPE FLUSH WITH FLOOR

ELEVATOR 5

P3

ELEVATOR 6

P4

DIET OFFICE

208B

DIETETIC SERVICE

STORAGE

208A

CORRIDOR

C202-02

STAIR

S1-02

MEN

CART STORAGE

207C

KITCHEN

OFFSET VENT PIPE BELOW FLOOR.

2" V (ETR)

EXISTING 2" VENT TO REMAIN

X

2"

2"

2"

5" SD

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9

P D

B

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:0

A

M

PD102A

SECOND FLOOR PLUMBING

DEMOLITION PLAN AREA A

2 25Author

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

Checker

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

SECOND FLOOR PLUMBING DEMOLITION PLAN AREA A

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1. CONTRACTOR IS ONLY TO REMOVE PIPE AT

FITTING TO THIS POINT. VERIFY SIZE AND

LOCATION BEFORE REMOVING.

2. EXISTING SANITARY ABOVE CEILING TO REMAIN.

3. REMOVE EXISTING PLUMBING FIXTURE AND ALL

ASSOCIATED PIPING.

4. DEMO EXISTING DRAIN PIPE SUPPORTED TO

CEILING

5. CAP AND REMOVE EXISTING WATER LINE IN WALL

BELOW FLOOR

N

EXISTING VENT PIPE TO REMAIN

EXISTING VTR

TO REMAIN

V V

V V

2" DCW ETR

4" V

/1 PD102C/1 PD102C

P D

A

P D

A

STAIR

S2-02

CORRIDOR

C203-02

MEN

WOMEN

NUTRITION SERVICES

OUTPATIENT NUTRITION

OUTPATIENT NUTRITION

204A

STORAGE

204B

OFFICE

207A

RECREATION

STORAGE

203D

ROOM

203A

ROOM

203B

ROOM

203C

DISHWASHING

207B

2-2

2-3

2-5

2-6

2-8

2-9

2-10

F.9 C.9 A.5 AA AC

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:0

A

M

PD102B

SECOND FLOOR PLUMBING

DEMOLITION PLAN AREA B

3 25Author

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

Checker

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

SECOND FLOOR PLUMBING DEMOLITION PLAN AREA B

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1. REMOVE EXISTING PLUMBING FIXTURE AND ALL

ASSOCIATE PIPING. CAP BRANCH LINES IN WALL.

N

4" SS (ETR)

S S

E

T R

2" DCW (ETR)

3/4" DHWR (ETR)

1 1/4" DHW (ETR)

/2

D

H W

E

T R

1/2" DCW (ETR)

2" V

2" V (ETR)

2" V

3/4" DCW (ETR)

2" V

EXISTING 3/4" MEDICAL AIR/

VACUUM AN OXYGEN TO

REMAIN.

EXISTING 2" DCW, 1-14" DHW

AND 3/4" DHWR. TO REMAIN.

2"

V

E T

R

EXISTING MEDICAL AIR AND MEDICAL VACUUM FROM ABV.

2"

V V V

VV

V V

X

V

V

NOT IN SCOPE

2" DCW (ETR)

4" VENT UP ETR

4" FD ABV. ETR

3/4" DHWR (ETR)

3/4" DHW (ETR)

EXIST. VENT UP TO REMAIN.

EXIST. 2" WASTE FR. ABV.

EXIST. 4" WASTE DOWN. TO REMAIN

EXIST. 4" WASTE STACK TO REMAIN

XXX

X

X

REMOVE EXISTING DRINKING FOUNTAIN.

2" V (ETR)

S D

E

T R

2" V (ETR)

2" V

(E

TR

2" V (ETR)

V

E T

R

2" V

D C

W

E T

R

/4

D

H W

E

T R

/4

D

H W

R

E T

R

2" V

/2

D

C W

E

T R

1" DCW (ETR)

1" DCW (ETR)

V

E T

R

4" V

2" DCW (ETR)

/4

D

H W

R

E T

R

1 1/4" DCW (ETR)

1 1/4" DHW (ETR)

3/4" DCW (ETR)

3/4" DHWR

1 1/4" DHW

2" DCW

S S

S S

E

T R

EXISTING

WASTE FR.

ABV. TO

REMAIN

S S

E

T R

ETR

ETR

ETR

4" SS (ETR)

S S

E

T R

4" SS

S S

E

T R

4" SS (ETR

ETR

ETR

2" V

/4

D

H W

R

E T

R

/4

D

C W

E

T R

1" DCW (ETR)

ETR

1/2" DHW (ETR)

S D

2" V

/1 PD102A

FIBER OPTIC

236B

LOGISTICS

WOMEN

HAC

MEN

MECH.

INPATIENT DIETETIC

217A

CLINICAL DIETITION

INPATIENT DIETETIC

STORAGE

ELEC.

HAC

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

CLINIC NURSES

RESTROOM

STORAGE

214A

RECEPTIONIST

COORIDOR

C204-38

CORRIDOR

C201-38

CORRIDOR

C202-38

CORRIDOR

C203-38

WAITING

STRESS LAB

WAITING

PAMN

PAGING EQUIPMENT

ELEVATOR 2

ELEVATOR 1

OXYGEN STORAGE

WHEELCHAIR ALCOVE

C3

SOILED UTILITY

ELEC.

CORRIDOR

C2

ELEVATOR LOBBY

C1

EXISTING ROOF DRAIN FR. ABV.

2-1

O M.2 F.9 C.9 A.5 AA

/1 PD102B

P D

B

2"

C.O.

C.O.

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:0

A

M

PD102C

SECOND FLOOR PLUMBING

DEMOLITION PLAN BLDG. 38

4 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

N

1. REMOVE EXISTING PLUMBING FIXTURE AND ALL

ASSOCIATE PIPING. CAP BRANCH LINES IN WALL.

2. CONTRACTOR IS ONLY TO REMOVE PIPE TO THIS

POINT. VERIFY SIZE AND LOCATION BEFORE

REMOVING.

3. EXISTING SANITARY ABOVE CEILING TO REMAIN.

4. EXISTING VENT TO SHOWN FOR REFERENCE

ONLY.

5. EXISTING DOMESTIC WATER LINES TO REMAIN.

1/4" = 1'-0"

SECOND FLOOR PLUMBING DEMOLITION PLAN BLDG. 38

UP

W.I.F.

(461 SF.)

W.I.C.

(303 SF.)

KITCHEN

DRY

/4

D

H W

R

/4

D H

W

ROUTE NEW 1-1/4" DHW, 3/4"

DHWR, AND 1" OXYGEN

SUPPLY UP TO 2ND FLOOR.1-1/2" DCW (ETR)

1" DHW (ETR)

1/2" DHWR (ETR)

2" DCW (ETR)

1" DHWR (ETR)

2" DCW/ 1-1/2" DHW

& 3/4" DHWR (ETR)

1-1/2" DHW (ETR)

2-1/2" DCW ENTRY (ETR)

3/4" DHW (ETR)

3/4" DCW (ETR)

1/2" DHWR (ETR)

1" DHW (ETR)

1-1/2" DCW (ETR)

EXIST. 1-1/2"

DCW,1" DHW, &

1/2" DHWR (ETR)

1-1/4" DCW (ETR)

3/4" DHW (ETR)

DHW (ETR)

DCW (ETR)

3/4" OX (ETR)

1-1/4" OX (ETR)

2-1/2" DCW

(ETR)

1-1/4" DCW, 1-1/4" DHW,

& 1/2" DHWR (ETR)

DCW (ETR)

1" DHWR (ETR)

1-1/2" DHW (ETR)

2" DCW (ETR)

5" SS

4" SS

S S

EXIST. HEAT EXCHANGER

EXIST. HHW

PUMPS 1-2

4" SS-ETR

EXIST. GW

O

1 1/4" O

/4

O

1 1/4" O

4" SS (ETR)

2" SS

S S

2" WASTE FR. ABV.

S S

4" S

S

4" WASTE FR. ABV.

S

S

S S S

S S

G W

G W

GW

GW

GW

GW

G W

GW

GW

GW

G W

G W

GW

S S

V

V

4"

2"

GW EXIST. MECH ROOM

BLDG. #2

EXISTING PIPE TUNNEL

/4

G

E T

R

/4

O

E T

R

/2

D H

W

E T

R

/4

D

H W

R

E T

R

/4

L P

C

/4

G

M P

S

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9 C.9 A.5 AA AC

C.O.

EXIST. HEAT EXCHANGER

EXIST. MECH ROOM

BLDG. #1

EXIST. FIRE PUMP

EXISTING CIRC. PUMPS.

MOUNTED ON ALL

1 1/4" O (ETR)

/4

G

E T

R

/4

O

E T

R

1 1/4" O (ETR)

4" DCW (ETR)

2 1/2" DHW (ETR)

1 1/2" DHWR (ETR)

1 1/2" DHWR (ETR)

2 1/2" DHW (ETR)

4" DCW (ETR)

2" DCW (ETR)

1" DHW (ETR)

1/2" DHWR (ETR)

1 1/2" DHWR (ETR)

2" DCW (ETR)

1" DHW (ETR)

D C

W R

/2

D C

W

D H

W

/4

D

H W

R

RP-1

EXISTING OPENING FROM

PIPE CHASE TO MECH.

ROOM

NOT IN SCOPE

Q

7 O M.2 F.9 C.9 A.5 AA AC

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:0

A

M

PP100A

PARTIAL PIPE BASEMENT PLUMBING

PLAN

5 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

1, 2

JES

1/8" = 1'-0"

PARTIAL PIPE BASEMENT PLUMBING PLAN

N

1. CONNECT TO EXISTING 1-1/4" OXYGEN

SUPPLY. CONTRACTOR TO VERIFY SIZE AND

LOCATION.

2. CONNECT NEW 1-1/2" DHW TO EXISTING

ARMSTRONG HEAT EXCHANGER IN PIPE

BASEMENT.

3. 3/4" STEAM CONDENSATE FROM ABOVE.

4. 2-1/2" DCW, 1" DHW,3/4" DHWR, & 1" DCWR,

FROM ABOVE.

5. 1" STEAM UP TO 2ND FLOOR FOR

STERILIZER

6. CONNECT NEW STEAM SUPPLY AND

CONDENSATE TO EXISTING STEAM LINES.

VERIFY LOCATION, PRESSURE AND SIZE.

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1/8" = 1'-0"

PARTIAL PIPE BASEMENT PLUMBING PLAN

N

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

BLDG.#1

DN

DN DN

DNCOURTYARD

MRI ADDITION

EXISTING CORRIDOR #8

W.I.F.

(461 SF.)

W.I.C.

(303 SF.)

KITCHEN

LOADING

DOCK

MEN'S

TOILET

WOMEN'S

TOILET

J.

CLO.

KITCHEN

DRY

STORAGE(437 SF.)

OFFICE #2

OFFICE #1

OFFICE #3

EXISTING CANTEEN

(NO CHANGE)

RETAIL

SHOP

EXISTING

SECTION OF

KITCHEN

EXISTING

CORRIDOR #6

EXISTING

STAIR

EXISTING

ELEVATOR

VESTIBULE

INDUSTRIAL

CORRIDOR #2

EXTRACTOR

INDUSTRIAL

CORRIDOR #1

STAIR

#1

RETAIL

STORAGE

CASHIER

PASS-THRU

REFRIG.

LOCKER

EXISTING

OFFICE #1

EXISTING

OFFICE #2

EXIST. ELEC. RM.

EXISTING

FOOD STORAGE

EXISTING CORRIDOR #7

STAFF

TOILET

LOCKER

CORRIDOR #3

CORRIDOR #4

EXISTING

CORRIDOR #5

EXISTING

WORK ROOM

ELEC. ROOM AELEC. ROOM B

EXISTING SERVING AREA

(NO CHANGE)

EXISTING CANTEEN VESTIBULE

DUMPSTER

ENCLOSURE

GREASE

WASTE

ENCLOSURE

COVERED

LOADING DOCK

EXISTING

ELEVATOR

EXISTING

VESTIBULE

COVERED

WALKWAY

COVERED

LOADING

DOCK

EXISTING BIO-WASTE

CONTAINER

TRASH COMPACTOR

EXISTING

BIO-HAZARD WASTE

CONTAINER

LINEN

CONTAINER

STAIR #2

F.E.C.

F.E.C.

F.E.C.

F.E.C.

3"

V.T.R.

4"

4"

3"

4"

3"

4"

FD-A

FD-S

FD-S

FD-S

FD-S

FD-S

FD-S

FD-S

FD-A

FD-A

FD-A

FD-S

FD-A

C.O.1

FD-A

FD-A

C.O.2

V

V

V V

C W

H W

H W R

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

2" WASTE FR. ABV.

ROUTE 2" WASTE DOWN TO PIPE BASEMENT

2" SS

S S

4" WASTE FR. ABV.

4" WASTE DN.

TO PIPE

BASEMENT

OFFSET PIPE IN

CEILING TO FIT IN

CHASE ABV.

Q

2-1

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9 C.9 A.5 AA AC

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PP100B

PARTIAL GROUND FLOOR PLUMBING

PLAN

6 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/8" = 1'-0"

PARTIAL GROUND FLOOR PLUMBING PLAN

N

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

5" ROOF DRAIN (ETR)

3" SS

EXIST. 4” WASTE DN/ 4” VENT UP

EXIST. 2” VENT UP

EXIST. 2”

VENT UP

EXIST. 4" WASTE STACK

EXIST. 2" VENT STACK

S S

S S

2" WASTE FR. ABV.

2" WASTE FR. ABV.

4" C.O.

4" WASTE FR. ABV.

2" WASTE FR. ABV.

3" WASTE FR.

SERVICE SINK

ABV.

2" WASTE

FR. ABV.

2" S

S

S S

S S

2" SS

C.O.

4" WASTE

FR. ABV.

4" WASTE DOWN

C.O.

2" WASTE FR. SINK'S ABV.

4" WASTE DN./ 2" VENT UP

C.O.

S S

4" SS

S S

2" SS

S S

/4

L P

C

3/4" LPC

2" WASTE FR. ABV.

2" SS 2" SS 1-1/2" VENT UP/ 2" WASTE DN.

2" FD FROM ABV.

2" WASTE FR. ABV.

S S

4" WASTE DN/ 2" VENT

UP (TYP.)

2" WASTE FR. ABV.

2" FD ABV.

4" WASTE FR. ABV.

4" WASTE DN/ 2" VENT

UP (TYP.)

2" FD ABV.

2" WASTE FR. ABV.

4" SS2" SS

S S

C.O.

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9

/1 PL101C

P L B

/1 PL101C

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PL101A

FIRST FLOOR SANITARY PLAN A

7 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

FIRST FLOOR SANITARY PLAN AREA A

N

1. ROUTE NEW SANITARY PIPE ABOVE THE

CEILING.

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

3/4" STEAM

CONDENSATE DOWN.

5" ROOF DRAIN (ETR)

4" S.S. (ETR)

2" WASTE FR. ABV.

2" C.O.

2" WASTE DN.

4" C.O.

2" WASTE FR. ABV.

2" SS

C.O.

S S

S S

3" FLOOR DRAIN ABV.

3" WASTE DN./ 2" VENT UP

2" S

S

3" SS

2" WASTE FR. ABV.

2" WASTE FR. ABV.

S S

3/4" LPC

/4

L P

C

3/4" STEAM CONDENSATE DOWN. FR. ABV.

ROUTE 3/4" STEAM

CONDENSATE DOWN

TO BASEMENT

2" WASTE FR. ABV.

2" SS

2" SS

C.O.

2-2

2-3

2-5

2-6

2-8

2-9

2-10

F.9 C.9 A.5 AA AC

/1 PL101C

/1 PL101C

P L A

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PL101B

FIRST FLOOR SANITARY PLAN B

8 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

FIRST FLOOR SANITARY PLAN AREA B

NORTH

1. ROUTE NEW SANITARY PIPE ABOVE THE

CEILING.

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

4" SS (ETR)

S S

4" SS 4" SS

5" ROOF DRAIN (ETR)

2" V (ETR)

2" V (ETR)

2" V (ETR)

2" V (ETR)

2" V (ETR)

V

E T

R

6" SD (ETR)

4" SS

S S

E

T R

4" SS (ETR)

2" SS (ETR)

OFFSET EXISTING

VENT PIPE IN

CEILING

ROUTE EXISTING

VENT UP

ROUTE EXISTING VENT UP

2" WASTE FR. ABV.

EXISTING 4" WASTE STACK

EXISTING 4" WASTE STACK

2" WASTE FR. ABV.

4" WASTE FR. ABV.

4" WASTE FR. ABV.

2" WASTE FR. ABV.

S S

2" WASTE DN./ 2" VENT UP

2" WASTE FROM ABV.

2" WASTE FR. ABV.

3" MSB ABOVE.

2" VENT UP

4" WASTE FR. ABV.

2" WASTE FR. ABV.

2" WASTE

FR. ABV.

4" SS

S S

S S

C.O.

CAP EXISTING WASTE ABV.

REROUTE EXISTING 4" VENT

2" V (ETR)

2" ETR

2" ETR EXIST. 2" VENT UP

ETR

ETR

4" WASTE (ETR)

4" SS (ETR) 4" SS (ETR)

4" SS (ETR)

2" V (ETR)

4" SS (ETR)

2" V (ETR)

4" SS

2" SS FFA

4" SS FFA

4" SS FFA

4" SS (ETR)

2" SS FFA

6" SD (ETR)

V

E T

R

C.O.

C.O.

4" SS (ETR)

V

E T

R

S S

E

T R

2" SS

2-1

O M.2 F.9 C.9 A.5 AA

2" SS

S S

4" SS

4" SSEXISTING 2" VENT UP

P L B

NOT IN SCOPE

4" WASTE DN. 2" VENT UP

4"WASTE DN. 2" VENT UP

/1 PL101A /1 PL101B

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PL101C

FIRST FLOOR SANITARY PLAN BLDG. 38

9 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

FIRST FLOOR SANITARY PLAN BLDG. 38

N

1. ROUTE NEW SANITARY PIPE ABOVE THE

CEILING.

2. 2" FD-C FROM ABOVE.

3. 2" SHOWER DRAIN FROM ABOVE.

2" ETR

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

A

P-414

P-502

P-414

P-708

V

E T

R

EXISTING 3" VENT

2" WASTE DN/

1-1/2" VENT UP

EXIST. 4" VTR

2" WASTE DN./ 1-1/2" VENT UP

3" V

2" V

2" V

V

2" V

1-1/2" VENT

UP FROM

SINK.

ETR VTR

2" VENT UP

V

2" V

2" VENT UP

4" WASTE DN./

2" VENT UP

3" V

5" SD

EXISTING SD ETR

P-414

P-101 P-101

P-414

P-528

P-101

P-414

P-528

P-528

P-414

P-414

P-414 1 1/2" V

1 1/2" V2" V

2" V

/2

V

V

2" V

1-1/2" VENT UP

2" FD-B

EXIST 2" VENT FROM BELOW

P-708

CORRIDOR

C202-02

CORRIDOR

C204-02

PRE/POST

PRE/POST

PACU

CLEAN SUPPLY

SOILED HOLDING

HAC

CARE STATION

MEDS

CORRIDOR

C207-02

ALCOVE

C207-02A

CORRIDOR

C206-02

STORAGE

STAIR

S1-02

CORRIDOR

C203-02

PRE/POST

PACU

PACU

ALCOVE

C206-02A

ISOLATION

ANTE

DICTATION

TOILET

TOILET

STAFF TOILET

PRE/POST

PRE/POST

PRE/POST

PRE/POST

CORRIDOR

C208-02

1 1/2" V

2" V

1 1/2" V

2" V

V

V

2" V

2" V

1-1/2" VENT

UP FROM

SINK.

2" VENT UP/ 4"

WASTE DN.

(TYP.)

2" VENT UP/ 4"

WASTE DN.

(TYP.)

2" FD-C

2" FD-C

2" FD-C

4" S

S (E

TR

4" ETR

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9

2" V (ETR)

EXIST 2" VENT FROM BELOW

/1 PL102C

P L B

/1 PL102C

1 / PL102A

1 / PL102B

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PL102A

SECOND FLOOR SANITARY PLAN A

10 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

SECOND FLOOR SANITARY PLAN A

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

N

1. ROUTE NEW VENT PIPE ABOVE THE CEILING.

2. EXISTING SANITARY PIPE IS ABOVE THE

CEILING IS SHOW FOR REFERENCE ONLY.

CONTRACTOR TO VERIFY SIZE AND

LOCATION AND REROUTE TO

ACCOMMODATE OTHER TRADES.

3. REROUTE EXISTING 2" VENT UP TO NEW

VENT LINE.

4. 2" WASTE DOWN, 1-1/2" VENT UP FROM

EYEWASH.

4" V (ETR)

A

P-528 P-528

P-520 P-520

2" V

2" V

2" V

V

2" VTR

2" WASTE DOWN. PROVIDE

AIR ADMITTANCE VALVE

UNDER SINK

2" VENT UP

3" FD-C

3" WASTE DN/ 2" VENT UP

V

V

2" V

3/4" STEAM

CONDENSATE DOWN

FROM STERILIZER.

P-520

1 1/2" V

ELECTRICAL

ALCOVE

C207-02A

CORRIDOR

C204-2

CORRIDOR

205-02

OR

OR

251OR

2" V

V

V

1/

2" V

4" S S (E

TR

2-2

2-3

2-5

2-6

2-8

2-9

2-10

F.9 C.9 A.5 AA AC

/1 PG102C

/1 PL102C

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:1

A

M

PL102B

SECOND FLOOR SANITARY PLAN B

11 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

SECOND FLOOR SANITARY PLAN B

N

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1. 2" WASTE DOWN, 1-1/2" VENT UP FROM

SCRUB SINK

4" SS

4" SS

4" SS FFA

4" SS FFA

4" SS FFA

4" SS (ETR)

2" V (ETR)

P-505

P-502

P-528

P-524

P-708

P-414 P-414

V

2" V

V

CONNECT TO EXISTING VTR

2" VENT

FROM

BELOW

NOT IN SCOPE

4" END VENT ETR

ETR

S S

E

T R

4" SS

S S

E

T R

S S

E

T R

4" WASTE ETR

C.O.

C.O.

S S

E

T R

4" SS (ETR)

EXISTING WASTE FR. ABV. ETR

V

2" V

2" WASTE DN. 2" VENT UP

2" WASTE DN.

2" VENT UP

2" WASTE DN.

2" VENT UP

EXISTING VENT ETR

ETR

WASTE FR. ABV. ETR

C.O.

2" WASTE DN. 1-1/2" VENT UP

P-702

P-702

P-101

P-414

P-101

/2

V

4" V (ETR)

2" VENT

FROM

BELOW

P-528

4" SS (ETR)

4" SS (ETR)

EXIST. 4" WASTE DN.

P-101

P-101

ELECTRICAL

ELECTRICAL

CORRIDOR

C202-02

CORRIDOR

C204-02

CONSULTATION

CHASE

V

EQUIPMENT

ANESTHESIA

CORRIDOR

C203-38

HAC

SOILED

STAFF LOUNGE

WOMEN'S LOCKER

MEN'S LOCKER

STAFF TOILET

STAFF TOILET

CORRIDOR

C201-38

RECEPTION

CHASE

C202-56

WAITING

CORRIDOR

C204-02

OFFICE

PSA OFFICE

N. MANAGER OFFICE

BIO-MED

225TOILET

TOILET

2" V

V

ROUTE TO NEAREST VENT

2" V 1 1/2" V

FD-C

FD-C

FD-C

FD-C

4" WASTE DN/ 2" VENT UP2" V

2" V

V

2-1

O M.2 F.9 C.9 A.5 AA

P L B

2" V

2" V

1 1/2" V 2" V

V

1 / PL102A

1 / PL102B

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:2

A

M

PL102C

SECOND FLOOR SANITARY PLAN BLDG.

12 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

SECOND FLOOR WASTE AND VENT PLAN BLDG.38

N

1. ROUTE NEW VENT PIPE ABOVE THE CEILING.

2. EXISTING SANITARY PIPE IS ABOVE THE

CEILING IS SHOW FOR REFERENCE ONLY.

CONTRACTOR TO VERIFY SIZE AND

LOCATION AND REROUTE TO

ACCOMMODATE OTHER TRADES.

3. 2" WASTE DOWN, 1-1/2" VENT UP FOR

EYEWASH.

4. ROUTE 1-1/2" TRAM-ARM IN WALL TO SINK.

5. EXISTING SANITARY VENT PIPE IS ABOVE

THE CEILING IS SHOW FOR REFERENCE

ONLY. CONTRACTOR TO VERIFY SIZE AND

LOCATION AND REROUTE TO

ACCOMMODATE OTHER TRADES.

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

2" DCW

3/4" DHW

/4

D

C W

1" DHW

D C

W

D H

W

1" DHW

P-414

P-502

P-414

P-708

/4

D H

W

1" D

H W

/4

D

H W

R

/4

D

H W

R

D C

W

3/4" DHW

3/4" DCW

D H

W

/4

D

H W

R

D H

W

/4

D

H W

R

1/2" DHWR

/2

D

H W

R

/4

D

H W

/4

D

C W

P-101

P-414 P-414 P-414

P-101

P-528

P-528

P-414

P-414

M P

S

P-528

1/2" DHWR

P-401

/4

D

C W

3/4" DCW

1/2" DHW

1/2" DHWR

BALANCE VALVE

1/2" DCW3/4" DCW

3/4" DHW

3/4" DCW

P-101

1/2" DCWR

1/2" DCWR

1/2" DHW

3/4" DHWR

3/4" DCWR

/4

D

C W

R

/2

D C

W /4

D

C W

3/4" DCW

3/4" DHW

M P

S

2" DCW

1/2" DCWR

CORRIDOR

C202-02

CORRIDOR

C204-02

PRE/POST

PRE/POST

PACU

CLEAN SUPPLY

SOILED HOLDING

HAC

CARE STATION

MEDS

CORRIDOR

C207-02

ALCOVE

C207-02A

CORRIDOR

C206-02

STORAGE

STAIR

S1-02

CORRIDOR

C203-02

PRE/POST

PACU

PACU

ALCOVE

C206-02A

ISOLATION

ANTE

DICTATION

TOILET

TOILET

STAFF TOILET

CHASE

PRE/POST

PRE/POST

PRE/POST

PRE/POST

CORRIDOR

C208-02

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9

/1 PP102C

P P

B

/1 PP102C

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:2

A

M

PP102A

SECOND FLOOR DOMESTIC WATER

PLAN A

13 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

N

1/4" = 1'-0"

SECOND FLOOR DOMESTIC PLUMBING PLAN A

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1. PROVIDE 1/2" DCW/DHW DOWN TO SINK.

2. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

COLD WATER SHUT-OFF VALVE.

3. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

HOT WATER SHUT-OFF VALVE.

4. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON HOT

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

5. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON COLD

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

6. 1/2" DCW UP TO HUMIDIFIERS IN PENTHOUSE ABOVE.

7. ROUTE NEW 1-1/4" DHW AND 3/4" DHWR DOWN TO

FLOORS BELOW. PIPE WILL CONNECT IN PIPE

BASEMENT MECH. ROOM IN BUILDING #2.

8. ROUTE NEW 1" STEAM LINE DOWN TO PIPE BASEMENT

IN MECH. ROOM OF BUILDING #2.

9. ROUTE 1/2" DCW DOWN WALL FOR ICE MAKER VALVE

BOX. PROVIDE FILTER AND ISOLATION VALVES FOR ICE

MAKER.

2 3 4 5

CONTINUED ON PP102B

CONTINUED ON PP102C

CONTINUED ON PP102B

3/4" DHWR

1" DCW

P-528

P-528

P-520 P-520

1" DHW

D H

W

/4

D

H W

R

3/4" DHWR 3/4" DHWR

3/4" DHW

1-1/4" DHW AND 3/4" DHWR

DOWN TO BASEMENT

REFER TO PP102A FOR CONT.

REFER TO PP102A FOR CONT.

REFER TO PP102C FOR CONT.

1/2" DHWR

1/2" DCW1/2" DHW

ROUTE 3/4" DHW/DCW

DOWN WALL

1" MPS

1" STEAM PIPE DOWN TO STERILIZER.

3/4" STEAM CONDENSATE DOWN TO FLOOR BELOW.

BALANCE VALVE

3/4" DHW

3/4" DCW

3/4" DCW UP TO PENTHOUSE

1/2" DCWR

3/4" DCW

3/4" DHW

STAIR

S2-02

HAC

ELECTRICAL

OR

CORRIDOR

C204-2

CORRIDOR

205-02

OR

STERILE CORE

CORRIDOR

C201-02

ALCOVE

C207-02A

SCRUB STATION

247A

ALCOVE

249A

SCRUB STATION

249B

SCRUB STATION

250A

CHASE

C202-57

IMMED. STER.

OR

1" DCW

2-2

2-3

2-5

2-6

2-8

2-9

2-10

F.9 C.9 A.5 AA AC

/1 PP102C

/1 PP102C

P P

A

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:2

A

M

PP102B

SECOND FLOOR DOMESTIC WATER

PLAN B

14 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

N

1/4" = 1'-0"

SECOND FLOOR DOMESTIC PLUMBING PLAN B

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

2 3 4 5

1. PROVIDE 1/2" DCW/DHW DOWN TO SINK.

2. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

COLD WATER SHUT-OFF VALVE.

3. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

HOT WATER SHUT-OFF VALVE.

4. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON HOT

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

5. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON COLD

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

REFER TO PP102A

FOR CONT.

3/4" DHWR (ETR)

1 1/4" DHW (ETR)

2" DCW (ETR)

3/4" DCW (ETR)

D C

W

/4

D

H W

R

1/2" DHW (ETR)

1/2" DCW (ETR)

3/4" DHWR (ETR)

3/4" DHWR (ETR)

1" DHW

2" DCW

P-401

P-401

NOT IN SCOPE

P-505

P-502

P-528

P-528

P-524

P-708

3/4" DHWR

1" DHW

2 1/2" DCW

/2

D C

W

D H

W

/4

D

H W

R

1 1/2" DCW

3/4" DHW

/4

D

H W

R 3 /4

D

H W

1/2" DHWR

ETR

ETR

ETR

MIXING VALVE

FOR EYEWASH

MIXING VALVE

FOR EYEWASH

3/4" DCW (ETR)

1 1/2" DCW (ETR)

1 1/4" DHW (ETR)

REFER TO PP102C FOR CONT.

P-101

P-414 P-414

P-101

1 1/4" DCW (ETR)

1 1/2" DCW (ETR)

1 1/4" DHW (ETR)

3/4" DCW (ETR)

1 1/4" DHW (ETR)

1/2" DHWR

1/2" DHW

1/2" DCW

/2

D

H W

R

/4

D

H W

/2

D C

W

/2

D C

W

3/4" DHWR

2" DCW

3/4" DHW

1/2" DHWR

D C

W R

1/2" DCWR

3/4" DCWR

/4

D

C W

R

3/4" DCWR

ETR

ETR

3/4" DCWR

/4

D

C W

R

/4

D

C W

1/2" DHW

1/2" DCWR

1" DHW

2" DCW

1/2" DCWR

MEN'S LOCKER

STAFF TOILET

WOMEN'S LOCKER

STAFF TOILET

EQUIPMENT

STAFF LOUNGE

SOILED

HAC

ELECTRICAL

CORRIDOR

C203-38

ELECTRICAL

CORRIDOR

C201-38

WAITING

ELEVATOR SHAFT

C202-54

CHASE

CHASE

C202-56

ELEVATOR 2

C207-02B

ELEVATOR 1

C207-02C

FIBER OPTIC

LOGISTICS

PAMN

C207-02F

PAGING EQUIPMENT

C207-02G

WHEELCHAIR ALCOVE

C3

SOILED UTILITY

ELEC.

CORRIDOR

C2

STRESS LAB

ELEVATOR LOBBY

C1

ANESTHESIA

BIO-MED

TOILET

TOILET

N. MANAGER OFFICE

CONSULTATION

RECEPTION

PSA OFFICE

CHASE

P-101

P-101

P-414

P-702

P-702

/2

D C

W

D C

W R

OFFICE

2-1

O M.2 F.9 C.9 A.5 AA

REFER TO PP102A FOR CONT.

FD-C

FD-C

FD-C

FD-C

P P

B

P P

A

1/ PP102B1/ PP102A

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:3

A

M

PP102C

SECOND FLOOR DOMESTIC WATER

PLAN BLDG. 38

15 25GH

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

JES

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

N

1. THE AREA OF WORK SHOWN IS

ASSOCIATED WITH AN OPERATING

FACILITY THAT MUST REMAIN IN SERVICE

24 HOURS A DAY, 7 DAYS A WEEK.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S

REPRESENTATIVE.

3. COORDINATE PLUMBING WORK WITH ALL

OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF

WORK.

4. SCHEDULE WORK IN THE EXISTING

BUILDING TO MINIMIZE DISRUPTION OF

SERVICES.

5. CONTRACTOR TO VERIFY LOCATION AND

SIZE OF EXISTING PIPE BEFORE ANY

CONNECTION OF NEW SYSTEMS ARE

MADE.

1/4" = 1'-0"

SECOND FLOOR DOMESTIC PLUMBING PLAN BLDG. 38

1. PROVIDE 1/2" DCW/DHW DOWN TO SINK.

2. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

COLD WATER SHUT-OFF VALVE.

3. PROVIDE TEMPERATURE SENSOR DOWNSTREAM OF

HOT WATER SHUT-OFF VALVE.

4. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON HOT

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

5. PROVIDE 0.5 GPM FLOW CONTROL VALVE ON COLD

WATER RECIRCULATION LINES. ALL OTHER FLOW

CONTROL VALVES SHALL BE 0.3 GPM UNLESS

OTHERWISE NOTED.

6. 2-1/2" DCW,1" DHW, 1" DCWR AN 3/4" DHWR DOWN TO

BUILDING #1 BASEMENT FOR CONNECTION TO

EXISTING.

7. DCW RECIRCULATION PUMP WILL BE LOCATED IN

BASEMENT OF BUILDING #1 .

8. OFFEST EXISTING WATER LINES IN WALL

1 1/4" MV

1" MA

P-401

M V

M A

2" MED. VACUUM FROM ABV.

1" OXYGEN FROM BELOW

3/4" MA

3/4" MV

3/4" MV

3/4" MA

3/4" MA

3/4" MV

3/4" MV

3/4" MA

3/4" MV

3/4" MA

1" NO

C O

W A

G D

O

M A

M V

W A

G D

O

M A

2" WAGD

2" MV

3/4" O

3/4" MV

3/4" O

3/4" MA

3/4" O

3/4" O

3/4" O

3/4" O

1" MA

1" O

1 1/4" MV

1" O

1 1/4" MV

1" O

1" MA

M A

M V

O

1" M

A

1" O

1/

4" M

V

M A

/4

M V

O

ZVB

AAP

/4

M

V /4

O

/4

M

A

/4

M

V /4

O

/4

M

A

/4

M

V /4

O

/4

M

A

CORRIDOR

C202-02

CORRIDOR

C204-02

PRE/POST

PRE/POST

PACU

CLEAN SUPPLY

SOILED HOLDING

HAC

CARE STATION

MEDS

CORRIDOR

C207-02

ALCOVE

C207-02A

CORRIDOR

C206-02

STORAGE

STAIR

S1-02

CORRIDOR

C203-02

PRE/POST

PACU

PACU

ALCOVE

C206-02A

ISOLATION

ANTE

DICTATION

TOILET

TOILET

STAFF TOILET

CHASE

PRE/POST

PRE/POST

PRE/POST

PRE/POST

CORRIDOR

C208-02

3/4" MV

3/4" O

3/4" MA

Q

2-2

2-3

2-5

2-6

2-8

2-9

2-10

2-11

O M.2 K.1 F.9

/1 PG102C

P G

B

/1 PG102C

Engineers Architects

## KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

2-HR FIRE BARRIER

2-HR FIRE/SMOKE BARRIER

SMOKE PARTITION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

/1 /2

:5

:3

A

M

PG102A

SECOND FLOOR MED GAS PLAN A

16 25Author

RELOCATE AND UPGRADE

OPERATING ROOM SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/15/2019

BID DOCUMENTS

657-50119-126

Checker

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

N

1/4" = 1'-0"

SECOND FLOOR MED GAS PLAN AREA A

GAS CYLINDERS, BY OTHERS

GAS CYLINDERS, BY OTHERS

GAS CYLINDERS, BY OTHERS

MEDICAL GAS GENERAL NOTES

1. THE AREA OF WORK SHOWN IS ASSOCIATED WITH

AN OPERATING FACILITY THAT MUST REMAIN IN

SERVICE 24/7.

2. COORDINATE WORK SCHEDULE WITH THE

CONTRACTING OFFICER’S REPRESENTATIVE

BEFORE THE START OF WORK.

3. COORDINATE MEDICAL GAS PLUMBING WORK WITH

ALL OTHER TRADES. VERIFY ALL EXISTING

CONDITIONS BEFORE THE START OF WORK.

4. SEE SHEET [SHEET #] FOR ADDITIONAL INFORMATION

REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE

DISRUPTION OF SERVICES.

5. POSITIVE PRESSURE PATIENT MEDICAL GAS PIPING

SHALL NOT BE BREACHED OR PENETRATED BY ANY

MEANS OR PROCESS THAT WILL RESULT IN

RESIDUAL COPPER PARTICLES OR OTHER DEBRIS

REMAINING IN THE PIPING, OR THAT AFFECTS THE

OXYGEN-CLEAN INTERIOR OF THE PIPING. IF

BREACHING OR PENETRATING THE MEDICAL GAS

PIPING IS REQUIRED, THE PROCESS SHALL ENSURE

THAT ANY DEBRIS CREATED BY THE PROCESS

REMAINS CONTAINED WITHIN THE WORK AREA.

6. ALL VALVES IN THE MEDICAL GAS SYSTEMS SHALL

BE QUARTER TURN OFF WITH INDICATION OF

WHETHER THE VALVE IS OPEN OR CLOSED. A LABEL

SHALL BE PROVIDED ON ALL VALVES INDICATING

THE TYPE OF SERVICE, THE AREA(S) OR ROOM(S)

SERVED, AND A WARNING THAT THE VALVE SHALL

NOT BE OPENED OR CLOSED EXCEPT FOR

EMERGENCY SITUATIONS

7. HOT TAPS OR SIMILAR VALVE ASSEMBLIES ARE NOT

PERMITTED IN MEDICAL GAS PIPING SYSTEMS.

8. EACH NEW…

This is the start of the file's text. The full file is on GovTribe.