P09 Corrected OR_ARCH_AD101 - SECOND FLOOR DEMOLITION PLAN - 1 Page.pdf

PDF 369 KB Posted

Attached to
Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
Solicitation number
36C25520R0040-0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document package includes a demolition plan and federal contract opportunity details. The demolition plan outlines selective demolition work at the Marion VA Medical Center in Marion, Illinois. Demolition includes interior walls, ceilings, flooring, doors, plumbing fixtures, and stairs to expose structural substrates. The federal contract opportunity is solicitation number 36C25520R0040-0001 for construction of a surgical suite addition at the Marion VAMC as project number 657-501. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration VISN 15. The response deadline and award date are not provided.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Construct Surgical Suite Addition P/N: 657-501, newest first.
File Type Posted
P09 Corrected OR_ARCH_A-501 - PARTITION TYPE DETAILS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-601 - DOOR SCHEDULE DOOR ELEVATIONS AND DETAILS - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-003 - PHASING AND INFECTION CONTROL PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-101 - SECOND FLOOR OVERALL RENOVATION PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-001 - ARCHITECTURAL NOTES ABBREVIATIONS AND SYMBOLS - 1 Page.pdf PDF
S06 36C25520R0040 0001.docx DOCX document
P09 Corrected OR_ARCH_A-104 - BLDG 38 SECOND FLOOR RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS101 - LIFE SAFETY FLOOR PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC102 - BLDG 2 2nd FLOOR AREA A REFLECTED CEILING PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC101 - SECOND FLOOR REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-105 - ROOF PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS112 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 Page.pdf PDF
P09 Corrected OR_ARCH_G-001 - COVER - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-102 - BLDG 02 2ND FLOOR AREA A RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-301 - BUILDING SECTIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC103 - Bldg 2 2nd FLOOR AREA B REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-502 - GENERAL DETAILS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-202 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-103 - BLDG 02 2ND FLOOR AREA B RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS111 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-201 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-002 - SECOND FLOOR EXISTING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_G-002 - DRAWING INDEX AND PROJECT INFORMATION - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-401 - ENLARGED PLANS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC104 - BLDG 38 2ND FLOOR REFLECTED CEILING PLAN - 1 Page.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

UP

B U

IL

D

IN

G

B U

IL

D

IN

G

B U

IL

D

IN

G

B U

IL

D

IN

G

1 1

7 2

A

WOMEN

HAC

MEN

MECH.

INPATIENT

DIETETIC

217A

CLINICAL

DIETITION

INPATIENT

DIETETIC

STORAGE

ELEC.

HAC

EXAM

EXAM

EXAM

CLINIC NURSES

RESTROOM

STORAGE

214A

RECEPTIONIST

COORIDOR

C204-38

CORRIDOR

C201-38

CORRIDOR

C202-38

CORRIDOR

C203-38

WAITING

STAIR

S2-02

ELEVATOR 5

P3

ELEVATOR 6

P4

DIET OFFICE

208B

DIETETIC

SERVICE

STORAGE

208A

CORRIDOR

C202-02

CORRIDOR

C203-02

STAIR

S1-02

MEN

WOMEN

NUTRITION

SERVICES

OUTPATIENT

NUTRITION

OUTPATIENT

NUTRITION

204A

STORAGE

204B

OFFICE

207A

RECREATION

STORAGE

203D

ROOM

203A

ROOM

203B

ROOM

203C

DISHWASHING

207B

CART STORAGE

207C

KITCHEN

A

D N

5 EXISTING MOP SINK

AREAS OF WALL DEMOLITION

LEGEND: DEMOLITION

FLOOR PLAN

INDICATES AREA OF EXISTING

CONSTRUCTION TO BE REMOVED.

PER KEYNOTES 1, 2, & 7.

TEMPORARY PARTITION/BARRIER.

RE: PHASING AND INFECTION

CONTROL PLAN.

TEMPORARY PARTITION/BARRIER

AND DOOR. RE: PHASING AND

INFECTION CONTROL PLAN.

EXISTING POURED TERRAZZO BASE

EXISTING QUARRY TILE, AS OF

LAST F.V.

CONCRETE PATCH FOR FULL

DEPTH OF EXIST. FLOOR.

CONT. 3x2X1/4" STL. ANGLES

ALL SIDES, ANCHOR TO SLAB

8" O.C. MAX

#3 BARS TACK WELDED TO ANGLE

8" O.C. EA. WAY

EXIST.

CONCRETE SLAB

EXIST. PIPE

FIRE RATED SEALANT

FIRE SAFING

EXIST. CONCRETE SLAB

CONCRETE PATCH FOR FULL DEPTH

OF EXIST. FLOOR. PIN TO EXIST. SLAB

ON ALL SIDES W/ MIN. 1/4" PINS ON

OPENINGS 8" AND SMALLER.

ABANDONED FORMING - FIRE TREATED

PLYWD. REINFORCED GYP BD.

#2 PINS @ 8" O.C. ALL SIDES

CONCRETE PATCH FOR FULL

DEPTH OF EXIST. FLOOR.

FORMING - FIRE TREATED

PLYWD. REINFORCED GYP BD.

#2 PINS @ 8" O.C. ALL SIDES

LOOSE-FITTED #3 BAR

DRILLED INTO EXIST. SLAB,

MAX. 8" O.C. EA. WAY.

TIE WIRES FOR FORM

SUPPORT

EXIST. PIPE PENETRATIONS.

CONTRACTOR TO FIELD VERIFY

QUANTITY AND LOCATIONS. PROVIDE

FIRE SAFING AT ALL PIPE

PENETRATIONS.

FIRE RATED SEALANT

FIRE SAFING

METAL FRAMING ANGLE CLIPS

ALL SIDES.

EXIST. PIPE PENETRATIONS. CONTRACTOR TO

FIELD VERIFY QUANTITY AND LOCATIONS.

PROVIDE FIRE SAFING AT ALL PIPE

PENETRATIONS.

TEMPORARY FORMING

#2 PINS @ 8" O.C. EA. WAY

NON-SHRINK GROUT

PUMP HOLE FOR GROUT

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

N

T

C E

I L

TA

S SHEILA

001-016606

CD A R

S E

LYNN

T C

H I

T E

ILOF I L

E NO

I S

EXPIRES 11-30-20

HENSLEY

BAYSINGER

/1

/2

:1

:1

P

M

AD101

SECOND FLOOR DEMOLITION PLAN

4 28ZC

RELOCATE AND UPGRADE

OPERATING SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/13/2019

BID DOCUMENTS

657-501

2, 38

MM

1/8" = 1'-0"

SECOND FLOOR DEMOLITION PLAN

N

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

EXCEPT WHERE SPECIFICALLY INDICATED TO

REMAIN, DEMOLISH AND REMOVE ALL EXISTING

INTERIOR WALL CONSTRUCTION AND FINISHES TO

EXISTING STRUCTURAL SUBSTRATES. REMOVAL

INCLUDES WALL FURRING, SHEATHING, PLASTER,

FRAMING, FINISH MATERIAL, WALL MOUNTED ITEMS,

ETC. PLASTER AT EXTERIOR WALLS SHALL REMAIN

INTACT. MAINTAIN AND PROTECT EXISTING BUILDING

SERVICES WHICH TRANSMIT THE AREA AFFECTED BY

SELECTIVE DEMOLITION. REFER TO PLUMBING,

MECHANICAL, ELECTRICAL, AND FIRE PROTECTION

DRAWINGS FOR ADDITIONAL INFORMATION.

DEMOLISH AND REMOVE EXISTING FLOORING

MATERIAL TO EXPOSE EXISTING SLAB. THIS

INCLUDES THE REMOVAL OF POURED TERRAZZO

BASE AND QUARRY FLOOR TILE. ASSUME 1” DEPTH.

AT AREAS WHERE POURED TERRAZZO BASE AND

QUARRY TILE ARE REMOVED, INFILL ENTIRE 2ND

FLOOR CONCRETE FLOOR SLAB WITH SELF-

LEVELING UNDERLAYMENT. CLEAN AND PREPARE

EXISTING SLAB TO RECEIVE NEW FLOORING

MATERIALS AS SCHEDULED.

REMOVE EXISTING DOOR, FRAME, AND HARDWARE

IN ITS ENTIRETY. TURN EXISTING DOOR HARDWARE

OVER TO THE VA COR.

REMOVAL ALL INTERIOR FINISHES TO EXPOSE

EXISTING STRUCTURAL STUBSTRATE FROM

INDICATED SIDE OF WALL ONLY. MAINTAIN AND

PROTECT EXISTING BUILDING SERVICES WHICH

TRANSMIT THE AREA AFFECTED BY SELECTIVE

DEMOLITION. REFER TO PLUMBING, MECHANICAL,

ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR

ADDITIONAL INFORMATION.

REMOVE EXISITNG PLUMBING FIXTURES AND

PLUMBING ACCESSORIES IN THEIR ENTIRETY. REFER

TO PLUMBING AND ELECTRICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

REMOVE EXISTING ROOM AND INTERIOR SIGNAGE

AND TURN OVER TO THE VA COR.

EXCEPT WHERE SPECIFICALLY INDICATED TO

REMAIN, DEMOLISH AND REMOVE ALL EXISTING

CEILINGS TO EXPOSE EXISTING STRUCTURAL

SUBSTRATES. REMOVAL INCLUDES CEILING PANELS,

GRIDS, PLASTER, GYPSUM BOARD, FRAMING, FINISH

MATERIAL, ABANDONED IN PLACE CONCEALED

EQUIPMENT MOUNTS, ETC. MAINTAIN AND PROTECT

EXISTING BUILDING SERVICES WHICH TRANSMIT THE

AREA AFFECTED BY SELECTIVE DEMOLITION. REFER

TO PLUMBING, MECHANICAL, ELECTRICAL, AND FIRE

PROTECTION DRAWINGS FOR ADDITIONAL

INFORMATION.

EXISTING BUILT-UP CONCRETE RAMP TO COOLER

(COOLER REMOVED UNDER SEPARATE CONTRACT).

REMOVE EXISTING RAMP IN ITS ENTIRETY. GRIND

SMOOTH TO LEVEL OF ADJACENT FLOOR AND

PREPARE REMAINING SLAB TO RECEIVE NEW

FLOORING MATERIALS AS SCHEDULED.

EXISTING ELEVATOR TO BE REMOVED IN ITS

ENTIRETY. REFER TO STRUCTURAL DRAWINGS FOR

STRUCTURAL AND FLOOR INFILL REQUIREMENTS.

RECONFIGURE AND REPLACE PORTIONS OF

EXISTING CEILING SYSTEM AS REQUIRED FOR

RENOVATION WORK.

REPAIR ALL EXISTING AND NEW PENETRATIONS IN

FIRE BARRIERS (FLOORS, WALLS, CEILINGS). FIELD

VERIFY LOCATIONS. THIS INCLUDES FIRE

SEPARATIONS AT CHASES AND EXPANSION JOINTS.

STAIRWELL TO REMAIN UNDISTURBED. STAIRWELL

ACCESS SHALL BE CLOSED OFF AT THIS FLOOR

LEVEL DURING CONSTRUCTION. PROVIDE SIGNAGE

AS DIRECTED BY VA.

REMOVE EXISTING METAL STAIRS AND EXISTING

CONCRETE LANDING COMPLETELY. PATCH

REMAINING FLOOR SLAB AND WALL SURFACES,

PREPARE FOR NEW FINISHES. SEE DETAIL 09/AD101

DEMOLITION

KEYED NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

1 1/2" = 1'-0"

FIRE RATING REPAIR - EXISTING AND NEW 2' OPENING OR LARGER

1 1/2" = 1'-0"

FIRE RATING REPAIR - EXISTING AND NEW PIPE PENETRATION ABOVE

1 1/2" = 1'-0"

FIRE RATING REPAIR - 8" OR SMALLER

1 1/2" = 1'-0"

FIRE RATING REPAIR - LARGER THAN 8"

1 1/2" = 1'-0"

FIRE RATING REPAIR OVERHEAD - NOT ACCESSIBLE FROM ABOVE

1 1/2" = 1'-0"

FIRE RATING REPAIR OVERHEAD - NOT ACCESSIBLE FROM ABOVE - ALT. METHOD

PROJECTION ROOM LOCATED ABOVE NUTRITION

SERVICES TO REMAIN. INFILL OPENINGS IN WALL TO

MATCH ADJACENT SUBSTRATES. SEE 09/AD101

INFILL CONCRETE SLAB AFTER DUCT REMOVAL.

SEE STRUCTURAL.

14.

15.

DEMOLITION

KEYED NOTES

1 : 30

PHOTO @ EXISTING STAIR

File details come from the government source that posted it. Updated .