P09 Corrected OR_ARCH_AD101 - SECOND FLOOR DEMOLITION PLAN - 1 Page.pdf
PDF 369 KB Posted
- Attached to
- Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
- Solicitation number
- 36C25520R0040-0001
About this file
This document package includes a demolition plan and federal contract opportunity details. The demolition plan outlines selective demolition work at the Marion VA Medical Center in Marion, Illinois. Demolition includes interior walls, ceilings, flooring, doors, plumbing fixtures, and stairs to expose structural substrates. The federal contract opportunity is solicitation number 36C25520R0040-0001 for construction of a surgical suite addition at the Marion VAMC as project number 657-501. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration VISN 15. The response deadline and award date are not provided.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
B U
IL
D
IN
G
B U
IL
D
IN
G
B U
IL
D
IN
G
B U
IL
D
IN
G
1 1
7 2
A
WOMEN
HAC
MEN
MECH.
INPATIENT
DIETETIC
217A
CLINICAL
DIETITION
INPATIENT
DIETETIC
STORAGE
ELEC.
HAC
EXAM
EXAM
EXAM
CLINIC NURSES
RESTROOM
STORAGE
214A
RECEPTIONIST
COORIDOR
C204-38
CORRIDOR
C201-38
CORRIDOR
C202-38
CORRIDOR
C203-38
WAITING
STAIR
S2-02
ELEVATOR 5
P3
ELEVATOR 6
P4
DIET OFFICE
208B
DIETETIC
SERVICE
STORAGE
208A
CORRIDOR
C202-02
CORRIDOR
C203-02
STAIR
S1-02
MEN
WOMEN
NUTRITION
SERVICES
OUTPATIENT
NUTRITION
OUTPATIENT
NUTRITION
204A
STORAGE
204B
OFFICE
207A
RECREATION
STORAGE
203D
ROOM
203A
ROOM
203B
ROOM
203C
DISHWASHING
207B
CART STORAGE
207C
KITCHEN
A
D N
5 EXISTING MOP SINK
AREAS OF WALL DEMOLITION
LEGEND: DEMOLITION
FLOOR PLAN
INDICATES AREA OF EXISTING
CONSTRUCTION TO BE REMOVED.
PER KEYNOTES 1, 2, & 7.
TEMPORARY PARTITION/BARRIER.
RE: PHASING AND INFECTION
CONTROL PLAN.
TEMPORARY PARTITION/BARRIER
AND DOOR. RE: PHASING AND
INFECTION CONTROL PLAN.
EXISTING POURED TERRAZZO BASE
EXISTING QUARRY TILE, AS OF
LAST F.V.
CONCRETE PATCH FOR FULL
DEPTH OF EXIST. FLOOR.
CONT. 3x2X1/4" STL. ANGLES
ALL SIDES, ANCHOR TO SLAB
8" O.C. MAX
#3 BARS TACK WELDED TO ANGLE
8" O.C. EA. WAY
EXIST.
CONCRETE SLAB
EXIST. PIPE
FIRE RATED SEALANT
FIRE SAFING
EXIST. CONCRETE SLAB
CONCRETE PATCH FOR FULL DEPTH
OF EXIST. FLOOR. PIN TO EXIST. SLAB
ON ALL SIDES W/ MIN. 1/4" PINS ON
OPENINGS 8" AND SMALLER.
ABANDONED FORMING - FIRE TREATED
PLYWD. REINFORCED GYP BD.
#2 PINS @ 8" O.C. ALL SIDES
CONCRETE PATCH FOR FULL
DEPTH OF EXIST. FLOOR.
FORMING - FIRE TREATED
PLYWD. REINFORCED GYP BD.
#2 PINS @ 8" O.C. ALL SIDES
LOOSE-FITTED #3 BAR
DRILLED INTO EXIST. SLAB,
MAX. 8" O.C. EA. WAY.
TIE WIRES FOR FORM
SUPPORT
EXIST. PIPE PENETRATIONS.
CONTRACTOR TO FIELD VERIFY
QUANTITY AND LOCATIONS. PROVIDE
FIRE SAFING AT ALL PIPE
PENETRATIONS.
FIRE RATED SEALANT
FIRE SAFING
METAL FRAMING ANGLE CLIPS
ALL SIDES.
EXIST. PIPE PENETRATIONS. CONTRACTOR TO
FIELD VERIFY QUANTITY AND LOCATIONS.
PROVIDE FIRE SAFING AT ALL PIPE
PENETRATIONS.
TEMPORARY FORMING
#2 PINS @ 8" O.C. EA. WAY
NON-SHRINK GROUT
PUMP HOLE FOR GROUT
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
N
T
C E
I L
TA
S SHEILA
001-016606
CD A R
S E
LYNN
T C
H I
T E
ILOF I L
E NO
I S
EXPIRES 11-30-20
HENSLEY
BAYSINGER
/1
/2
:1
:1
P
M
AD101
SECOND FLOOR DEMOLITION PLAN
4 28ZC
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/13/2019
BID DOCUMENTS
657-501
2, 38
MM
1/8" = 1'-0"
SECOND FLOOR DEMOLITION PLAN
N
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
2A 2B
EXCEPT WHERE SPECIFICALLY INDICATED TO
REMAIN, DEMOLISH AND REMOVE ALL EXISTING
INTERIOR WALL CONSTRUCTION AND FINISHES TO
EXISTING STRUCTURAL SUBSTRATES. REMOVAL
INCLUDES WALL FURRING, SHEATHING, PLASTER,
FRAMING, FINISH MATERIAL, WALL MOUNTED ITEMS,
ETC. PLASTER AT EXTERIOR WALLS SHALL REMAIN
INTACT. MAINTAIN AND PROTECT EXISTING BUILDING
SERVICES WHICH TRANSMIT THE AREA AFFECTED BY
SELECTIVE DEMOLITION. REFER TO PLUMBING,
MECHANICAL, ELECTRICAL, AND FIRE PROTECTION
DRAWINGS FOR ADDITIONAL INFORMATION.
DEMOLISH AND REMOVE EXISTING FLOORING
MATERIAL TO EXPOSE EXISTING SLAB. THIS
INCLUDES THE REMOVAL OF POURED TERRAZZO
BASE AND QUARRY FLOOR TILE. ASSUME 1” DEPTH.
AT AREAS WHERE POURED TERRAZZO BASE AND
QUARRY TILE ARE REMOVED, INFILL ENTIRE 2ND
FLOOR CONCRETE FLOOR SLAB WITH SELF-
LEVELING UNDERLAYMENT. CLEAN AND PREPARE
EXISTING SLAB TO RECEIVE NEW FLOORING
MATERIALS AS SCHEDULED.
REMOVE EXISTING DOOR, FRAME, AND HARDWARE
IN ITS ENTIRETY. TURN EXISTING DOOR HARDWARE
OVER TO THE VA COR.
REMOVAL ALL INTERIOR FINISHES TO EXPOSE
EXISTING STRUCTURAL STUBSTRATE FROM
INDICATED SIDE OF WALL ONLY. MAINTAIN AND
PROTECT EXISTING BUILDING SERVICES WHICH
TRANSMIT THE AREA AFFECTED BY SELECTIVE
DEMOLITION. REFER TO PLUMBING, MECHANICAL,
ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR
ADDITIONAL INFORMATION.
REMOVE EXISITNG PLUMBING FIXTURES AND
PLUMBING ACCESSORIES IN THEIR ENTIRETY. REFER
TO PLUMBING AND ELECTRICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
REMOVE EXISTING ROOM AND INTERIOR SIGNAGE
AND TURN OVER TO THE VA COR.
EXCEPT WHERE SPECIFICALLY INDICATED TO
REMAIN, DEMOLISH AND REMOVE ALL EXISTING
CEILINGS TO EXPOSE EXISTING STRUCTURAL
SUBSTRATES. REMOVAL INCLUDES CEILING PANELS,
GRIDS, PLASTER, GYPSUM BOARD, FRAMING, FINISH
MATERIAL, ABANDONED IN PLACE CONCEALED
EQUIPMENT MOUNTS, ETC. MAINTAIN AND PROTECT
EXISTING BUILDING SERVICES WHICH TRANSMIT THE
AREA AFFECTED BY SELECTIVE DEMOLITION. REFER
TO PLUMBING, MECHANICAL, ELECTRICAL, AND FIRE
PROTECTION DRAWINGS FOR ADDITIONAL
INFORMATION.
EXISTING BUILT-UP CONCRETE RAMP TO COOLER
(COOLER REMOVED UNDER SEPARATE CONTRACT).
REMOVE EXISTING RAMP IN ITS ENTIRETY. GRIND
SMOOTH TO LEVEL OF ADJACENT FLOOR AND
PREPARE REMAINING SLAB TO RECEIVE NEW
FLOORING MATERIALS AS SCHEDULED.
EXISTING ELEVATOR TO BE REMOVED IN ITS
ENTIRETY. REFER TO STRUCTURAL DRAWINGS FOR
STRUCTURAL AND FLOOR INFILL REQUIREMENTS.
RECONFIGURE AND REPLACE PORTIONS OF
EXISTING CEILING SYSTEM AS REQUIRED FOR
RENOVATION WORK.
REPAIR ALL EXISTING AND NEW PENETRATIONS IN
FIRE BARRIERS (FLOORS, WALLS, CEILINGS). FIELD
VERIFY LOCATIONS. THIS INCLUDES FIRE
SEPARATIONS AT CHASES AND EXPANSION JOINTS.
STAIRWELL TO REMAIN UNDISTURBED. STAIRWELL
ACCESS SHALL BE CLOSED OFF AT THIS FLOOR
LEVEL DURING CONSTRUCTION. PROVIDE SIGNAGE
AS DIRECTED BY VA.
REMOVE EXISTING METAL STAIRS AND EXISTING
CONCRETE LANDING COMPLETELY. PATCH
REMAINING FLOOR SLAB AND WALL SURFACES,
PREPARE FOR NEW FINISHES. SEE DETAIL 09/AD101
DEMOLITION
KEYED NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
1 1/2" = 1'-0"
FIRE RATING REPAIR - EXISTING AND NEW 2' OPENING OR LARGER
1 1/2" = 1'-0"
FIRE RATING REPAIR - EXISTING AND NEW PIPE PENETRATION ABOVE
1 1/2" = 1'-0"
FIRE RATING REPAIR - 8" OR SMALLER
1 1/2" = 1'-0"
FIRE RATING REPAIR - LARGER THAN 8"
1 1/2" = 1'-0"
FIRE RATING REPAIR OVERHEAD - NOT ACCESSIBLE FROM ABOVE
1 1/2" = 1'-0"
FIRE RATING REPAIR OVERHEAD - NOT ACCESSIBLE FROM ABOVE - ALT. METHOD
PROJECTION ROOM LOCATED ABOVE NUTRITION
SERVICES TO REMAIN. INFILL OPENINGS IN WALL TO
MATCH ADJACENT SUBSTRATES. SEE 09/AD101
INFILL CONCRETE SLAB AFTER DUCT REMOVAL.
SEE STRUCTURAL.
14.
15.
DEMOLITION
KEYED NOTES
1 : 30
PHOTO @ EXISTING STAIR
File details come from the government source that posted it. Updated .