P09 Corrected OR_ARCH_AC101 - SECOND FLOOR REFLECTED CEILING PLAN - 1 page.pdf
PDF 451 KB Posted
- Attached to
- Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
- Solicitation number
- 36C25520R0040-0001
About this file
This document contains a reflected ceiling plan and construction details for renovations to the second floor of a VA medical center to relocate and upgrade operating suites, as well as the related federal contract solicitation.
The ceiling plan depicts the layout and finishes for the second floor, including new 2-hour fire barriers and smoke partitions. Construction details show specifications for installing a new soffit and suspended ceiling system using 3/8" cross tee stabilizer bars, 3/4" minimum supports at unattached walls, and #12 hanger wires. The solicitation is for contract 36C25520R0040 issued by the Department of Veterans Affairs to construct a surgical suite addition at the Marion VA Medical Center in Marion, Illinois. The solicitation number is Z2DA--Construct Surgical Suite Addition and the project number is 657-501. The response due date and award date are not provided.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STAIR
S2-02
MEN'S LOCKER
STAFF TOILET
WOMEN'S
LOCKER
STAFF TOILET
EQUIPMENT
STAFF LOUNGE
SOILED
HAC
ELECTRICAL
CORRIDOR
C203-38
ELECTRICAL
CORRIDOR
C201-38
WAITING
CORRIDOR
C202-02
CORRIDOR
C204-02
PRE/POST
PRE/POST
PACU
CLEAN SUPPLY
SOILED HOLDING
HAC
CARE STATION
MEDS
CORRIDOR
C207-02
OR
CORRIDOR
C204-2
CORRIDOR
205-02
OR
STERILE CORE
CORRIDOR
C201-02
ALCOVE
C207-02A
CORRIDOR
C206-02
STORAGE
STAIR
S1-02
CORRIDOR
C203-02
SCRUB STATION
247A
ALCOVE
249A
SCRUB STATION
249B
SCRUB STATION
250A
ELEVATOR
SHAFT
C202-54
CHASE
CHASE
CHASE
C202-57
AC104
AC102
AC103
B U
IL
D
IN
G
B U
IL
D
IN
G
B U
IL
D
IN
G
B U
IL
D
IN
G
B U
IL
D
IN
G
B
U
IL
D
IN
G
B U
IL
D
IN
G
B
U
IL
D
IN
G
D N
ELEVATOR 2
C207-02B
ELEVATOR 1
C207-02C
FIBER OPTIC
LOGISTICS
PAMN
C207-02F
PAGING
EQUIPMENT
C207-02G
WHEELCHAIR
ALCOVE
C3
SOILED UTILITY
ELEC.
CORRIDOR
C2
STRESS LAB
ELEVATOR
LOBBY
C1
PRE/POST
PACU
PACU
ALCOVE
C206-02A
ISOLATION
ANTE
DICTATION
TOILET
TOILET
STAFF TOILET
ANESTHESIA
IMMED. STER.
BIO-MED
TOILET
TOILET
N. MANAGER
OFFICE
CONSULTATION
RECEPTION
PSA OFFICE
CHASE
PRE/POST
PRE/POST
PRE/POST
PRE/POST
OR
CORRIDOR
C208-02
ELEVATOR
LOBBY
C202-38
OFFICE
RECONFIGURE EXISTING SUSPENDED CEILING
SYSTEM AS REQUIRED TO INSTALL NEW
SOFFIT AND ADJACENT CEILING SYSTEM
3/8" MIN.
CROSS TEE
STABILIZER BAR TO PREVENT PERIMETER
COMPONENTS FROM SPREADING APART
3/4" MIN. @ UNATTACHED WALLS
2" MIN.
MAIN TEE
(STABILIZER END VIEW)
STABILIZER BAR TO PREVENT
PERIMETER COMPONENTS
FROM SPREADING APART
ANGLE MOLDING
#12 HANGER WIRE
ANCHORED TO
STRUCTURE ABOVE
MAIN TEEMAIN TEE
MAIN TEE
STEEL STUD COMPRESSION POST
ON MAIN TEE - LOCATED 6'-0" MAX.
FROM END WALL AND 12"-0" MAX.
EACH WAY IN FIELD.
#12 HANGER
WIRE
45° O R
LESS45
° O R L
ESS
IN ADDITION: PROVIDE #12
HANGER WIRE AT EACH CORNER
(4 TYP.) OF ALL LIGHT FIXTURES
AND MECHANICAL GRILLES.
NOTE: DETAILS TO BE USED
AT ALL SUSPENDED
LOCATIONS THROUGHOUT.
O R
L E
S S
° O
R L
E S
S
CROSS TEE
MAIN TEE
(STABILIZER SIDE VIEW)
LEGEND: REFLECTED
CEILING PLAN
2x2 ACOUSTICAL CEILING TILE
GYPSUM BOARD CEILING
2x4 LIGHT FIXTURE
PENDANT LIGHT FIXTURE
AIR TERMINAL
RETURN AIR GRILLE
SUPPLY AIR
EXHAUST AIR
CUBICLE CURTAIN TRACKS
CEILING HEIGHT
CIRCULAR DOWNLIGHT
SURGICAL LIGHTS
CEILING MOUNTED DUAL MONITOR
24"X24" ACCESS PANEL
PATIENT LIFT
EXIT SIGN
X' - X"
LIFE SAFETY LEGEND:
NEW 2-HR FIRE BARRIER
EXISTING 2-HR FIRE/SMOKE BARRIER
NEW SMOKE PARTITION
EXIT SIGN
TRAVEL DISTANCE
FIRE EXTINGUISHER CABINET
E
F.E.C.
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
THE ROOM NUMBERING SEQUENCE IS FOR
CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM
NUMBERING SHALL BE CORRELATED WITH CURRENT
BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED
DUE TO DEMOLITION. FINAL ROOM NUMBERING AND
SIGNAGE SHALL EB APPROVED BY VA STAFF ON
SITE
N
T
C E
I L
TA
S SHEILA
001-016606
CD A R
S E
LYNN
T C
H I
T E
ILOF I L
E NO
I S
EXPIRES 11-30-20
HENSLEY
BAYSINGER
/1
/2
:0
:5
P
M
AC101
SECOND FLOOR REFLECTED CEILING
PLAN
10 28ZC
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/13/2019
BID DOCUMENTS
657-501
2, 38
MM
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
2A 2B 1/8" = 1'-0"
SECOND FLOOR OVERALL RENOVATION CEILING PLAN
N
1" = 1'-0"
SEISMIC CEILING DETAILS