P09 Corrected OR_ARCH_AC102 - BLDG 2 2nd FLOOR AREA A REFLECTED CEILING PLAN - 1 Page.pdf

PDF 541 KB Posted

Attached to
Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
Solicitation number
36C25520R0040-0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document includes a reflected ceiling plan drawing for the second floor area A of Building 2 of a VA medical center, along with details of proposed ceiling, corridor, and care station soffit construction. The related federal contract opportunity is a solicitation to construct a surgical suite addition at the Marion VA Medical Center in Marion, Illinois. Key details include a solicitation number of 36C25520R0040-0001 to upgrade operating suites under project number 657-501. The scope of work involves relocating and upgrading operating rooms at the Marion VAMC with the contracting agency listed as the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Construct Surgical Suite Addition P/N: 657-501, newest first.
File Type Posted
P09 Corrected OR_ARCH_A-301 - BUILDING SECTIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC103 - Bldg 2 2nd FLOOR AREA B REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-502 - GENERAL DETAILS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-202 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-501 - PARTITION TYPE DETAILS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-601 - DOOR SCHEDULE DOOR ELEVATIONS AND DETAILS - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-003 - PHASING AND INFECTION CONTROL PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-101 - SECOND FLOOR OVERALL RENOVATION PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-001 - ARCHITECTURAL NOTES ABBREVIATIONS AND SYMBOLS - 1 Page.pdf PDF
S06 36C25520R0040 0001.docx DOCX document
P09 Corrected OR_ARCH_A-104 - BLDG 38 SECOND FLOOR RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS101 - LIFE SAFETY FLOOR PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC101 - SECOND FLOOR REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-105 - ROOF PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS112 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 Page.pdf PDF
P09 Corrected OR_ARCH_G-001 - COVER - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-102 - BLDG 02 2ND FLOOR AREA A RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-103 - BLDG 02 2ND FLOOR AREA B RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS111 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-201 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AD101 - SECOND FLOOR DEMOLITION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-002 - SECOND FLOOR EXISTING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_G-002 - DRAWING INDEX AND PROJECT INFORMATION - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-401 - ENLARGED PLANS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC104 - BLDG 38 2ND FLOOR REFLECTED CEILING PLAN - 1 Page.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL

ELECTRICAL

CORRIDOR

C202-02

CORRIDOR

C204-02

PRE/POST

PRE/POST

PACU

CLEAN SUPPLY

SOILED HOLDING

HAC

CARE STATION

MEDS

CORRIDOR

C207-02

ALCOVE

C207-02A

CORRIDOR

C206-02

STORAGE

STAIR

S1-02

CORRIDOR

C203-02

9' - 0"

10' - 0"

9' - 0"

9' - 0"

8' - 0"

8' - 6"

9' - 0"

8' - 0"

9' - 0"

9' - 0"

9' - 0"

AC102

AC102

AC102

Sim

AC102

AC102

Sim

AC102

8' - 6"

9' - 0"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

AC102

Sim

8' - 0"

8' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0" 8' - 0"

AC102

8' - 9"

8' - 9"

8' - 9" 8' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"9' - 0"9' - 0"

9' - 0"

8' - 6"

4"

3' - 4"

3'

4"

"5

/8

8' - 0 5/8" 5' - 0"

1' - 0"

1' - 0"

PRE/POST

PACU

PACU

ALCOVE

C206-02A

ISOLATION

ANTE

DICTATION

TOILET

TOILET

STAFF TOILET

CHASE

PRE/POST

PRE/POST

PRE/POST

PRE/POST

CORRIDOR

C208-02

AFTER REMOVAL OF TEMPORARY

PARTITION/CONSTRUCTION BARRIER, MODIFY

EXISTING CORRIDOR CEILING SYSTEM (TILE AND

GRID) AS REQUIRED TO INSTALL NEW CEILING AS

INDICATED. REPLACE ANY PORTION OF CEILING

DAMAGED DURING RENOVATION TO MATCH

EXISTING.

PROVIDE NEW CEILING SYSTEM (TILE AND GRID) AS

INDICATED. TIE-IN TO EXISTING CEILING SYSTEM

WHERE REMOVAL IS NOT REQUIRED. MATCH

EXISTING CEILING GRID AND TILE (MATERIALS AND

LAYOUT). PROVIDE SEAMLESS TRANSITION BETWEEN

NEW AND EXISTING.

REFLECTED CEILING

PLAN KEYED NOTES

1.

2.

LEGEND: REFLECTED

CEILING PLAN

2x2 ACOUSTICAL CEILING TILE

GYPSUM BOARD CEILING

2x4 LIGHT FIXTURE

PENDANT LIGHT FIXTURE

AIR TERMINAL

RETURN AIR GRILLE

SUPPLY AIR

EXHAUST AIR

CUBICLE CURTAIN TRACKS

CEILING HEIGHT

CIRCULAR DOWNLIGHT

SURGICAL LIGHTS

CEILING MOUNTED DUAL MONITOR

24"X24" ACCESS PANEL

PATIENT LIFT

EXIT SIGN

X' - X"

M

IN

9'-0" A.F.F.

8'-6" A.F.F.

1' - 0"

ACOUSTICAL

CEILING TILE

3 5/8" METAL STUD

FRAMING, TYP.

5/8" TYPE 'X' GYPSUM

BOARD, TYP.

O

10'-0" A.F.F.

8'-6" A.F.F.

3 5/8" METAL

STUD

FRAMING, TYP.

ACOUSTICAL

CEILING TILE

9'-0" A.F.F.

5/8" TYPE 'X'

GYPSUM BOARD

M

IN

8'-9" A.F.F.

5/8" TYPE 'X'

GYPSUM BOARD

RECESSED LIGHT

RE: ELECTRICAL

1' - 0"5' - 0"

5/8" TYPE 'X'

GYPSUM BOARD

3 5/8" METAL

STUD

FRAMING, TYP.

3 5/8" METAL STUD

FRAMING, TYP.

EXISTING CONCRETE DECK

FRAMING EXTENDS

TO DECKING

DEFLECTION CLIPS

TOP OF STUD, CHANNEL

ACOUSTICAL

CEILING TILE

9'-0" A.F.F.

ACOUSTICAL

CEILING TILE

9'-0" A.F.F. 6

M

IN

8'-0" A.F.F.

VARIES

5/8" TYPE 'X'

GYPSUM BOARD,

TYP.

3 5/8" METAL STUD

FRAMING, TYP.

RECESSED

LIGHT. RE:

ELECTRICAL.

4"

WALL BEYOND

2-6 2-7F

3' - 0"

M

IN

RECESSED LIGHT. RE:

ELECTRICAL.

8'-0" A.F.F.

5/8" TYPE 'X'

GYPSUM BOARD, TYP.

3 5/8" METAL STUD

FRAMING, TYP.

ACOUSTICAL

CEILING TILE

9'-0" A.F.F.9'-0" A.F.F.

WALL BEYOND

4"

9'-0" A.F.F.

8'-0" A.F.F.

3' - 4"

9'-0" A.F.F.

5/8" TYPE 'X'

GYPSUM BOARD, TYP.

3 5/8" METAL STUD

FRAMING, TYP.

ACOUSTICAL

CEILING TILE

M

IN

RECESSED LIGHT

RE: ELECTRICAL

LIFE SAFETY LEGEND:

NEW 2-HR FIRE BARRIER

EXISTING 2-HR FIRE/SMOKE BARRIER

NEW SMOKE PARTITION

EXIT SIGN

TRAVEL DISTANCE

FIRE EXTINGUISHER CABINET

E

F.E.C.

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

THE ROOM NUMBERING SEQUENCE IS FOR

CONSTRUCTION IDENTIFICATION ONLY. FINAL ROOM

NUMBERING SHALL BE CORRELATED WITH CURRENT

BAS IDENTIFICATION POINTS THAT ARE NOT BEING USED

DUE TO DEMOLITION. FINAL ROOM NUMBERING AND

SIGNAGE SHALL EB APPROVED BY VA STAFF ON

SITE

N

T

C E

I L

TA

S SHEILA

001-016606

CD A R

S E

LYNN

T C

H I

T E

ILOF I L

E NO

I S

EXPIRES 11-30-20

HENSLEY

BAYSINGER

/1

/2

:1

:0

P

M

AC102

BUILDING 02 SECOND FLOOR AREA 'A'

REFLECTED CEILING PLAN

11 28ZC

RELOCATE AND UPGRADE

OPERATING SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/13/2019

BID DOCUMENTS

657-501

MM

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

2A 2B

1/4" = 1'-0"

BUILDING 02 SECOND FLOOR AREA 'A' REFLECTED CEILING PLAN

N

1" = 1'-0"

CORRIDOR SOFFIT DETAIL - TYP.

1" = 1'-0"

CORRIDOR SOFFIT DETAIL - C205-02 SOUTH

1" = 1'-0"

CARE/SCRUB STATION SOFFIT DETAIL - TYP.

1" = 1'-0"

ALCOVE C206-02A SOFFIT DETAIL

1" = 1'-0"

NURSE STATION SOFFIT DETAIL - TYP.1