P09 Corrected OR_ARCH_A-501 - PARTITION TYPE DETAILS - 1 Page.pdf
PDF 241 KB Posted
- Attached to
- Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
- Solicitation number
- 36C25520R0040-0001
About this file
This document contains construction drawings for partition types and details to be used in a surgical suite addition project for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. Key details include specifications for 1-hour and 3-5/8 inch metal stud partitions to be installed at various locations throughout the project site, with requirements for fire caulking and sealant at penetrations. Deflection details are also provided specifying attachment methods for wall boards. Plaster work details indicate a smooth 1/8 inch finish is required where plaster is used.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARTITION TYPES
TEMPORARY PARTITION DETAIL - 1 HR/NEW CONSTRUCTION - 1 HR A1 1/2" = 1'-0" 1 1/2" = 1'-0"C1 1/2" = 1'-0"B1 1/2" = 1'-0" F1 1/2" = 1'-0"
H1 1/2" = 1'-0"
D1 1/2" = 1'-0" ETYPICAL 3-5/8" METAL STUD PARTITION FURRING @ EXISTING EXTERIOR WALL CONSTRUCTIONFURRING @ EXISTING CONSTRUCTION
FLOOR FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
5/8" TYPE 'X' GYPSUM BOARD
18 GAUGE 2 1/2" METAL STUDS @ 16"
O.C.
EXISTING WALL CONSTRUCTION
NEW CONSTRUCTIONEXG. CONSTRUCTION
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED - TYP. EACH SIDE
FIRE RATED SEALANT - TYP. EACH SIDE
5/8" TYPE 'X' GYP. BD.
NOTE:
1. FIRE CAULK AND SEAL ALL PENETRATIONS.
2. PROVIDE TEMPORARY PARTITIONS WHERE INDICATED
AND AS REQUIRED BY V.A. INFECTION CONTROL POLICY.
3 5/8" METAL STUDS @ 16" O.C.
FIRE STOP SEALANT - TYP. BOTH SIDES
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
4 7/8"
2 1/2" SPRAY FOAM INSULATION
FLOOR FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
3/4" HAT CHANNEL FURRING (18 Ga.)
@ 16" O.C. MECHANICALLY ATTACHED
EXISTING WALL CONSTRUCTION
NEW CONSTRUCTIONEXG. CONSTRUCTION
FIRE SEALANT
J1 1/2" = 1'-0"
CHASE @ ORN1 1/2" = 1'-0"
TYPICAL 6" METAL STUD PARTITION
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED - TYP. EACH SIDE
SEALANT - TYP. EACH SIDE
5/8" TYPE 'X' MOLD RESISTANT GYP. BD.
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
4 7/8"
FLOOR FINISH AS SCHEDULED
5/8" TYPE 'X' MOLD RESISTANT GYP. BD. TYP.
EACH SIDE
18 Ga. 3 5/8" METAL STUDS @ 16" O.C. PROVIDE 14 Ga. STUDS @ FIXTURE LOCATIONS. TYP.
EACH SIDE
EXG. CONCRETE DECK
SOLID POLYMER PANEL. TYP. EACH SIDE
1/16" MIN. SILICONE ADHESIVE. TYP. EACH SIDE
WALL BASE AS SCHEDULED. TYP. EACH SIDE
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED
18 GA. 6" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD. TYP. EACH SIDE 5/8" TYPE 'X' GYPSUM BOARD
Q1 1/2" = 1'-0"
3 5/8" METAL STUD PARTITION AT TOILET3-5/8" METAL STUD WALL
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED. TYP. EACH SIDE
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
EXISTING CONCRETE DECKEXISTING CONCRETE DECK
FULL WIDTH FRICTION FIT SOUND BATT
INSULATION.
FIRE STOP SEALANT. - TYP. EACH SIDE
G1 1/2" = 1'-0"FURRING @ EXISTING EXTERIOR WALL CONSTRUCTION
FLOOR FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
5/8" TYPE 'X' GYPSUM BOARD
18 GAUGE 6" METAL STUDS
@ 16" O.C.
EXG. WALL CONSTRUCTION
NEW CONSTRUCTIONEXG. CONST.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
VARIES
EXISTING CONCRETE DECK
CERAMIC WALL TILE
4'-0" A.F.F.
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED. TYP. EACH SIDE
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD.
CERAMIC WALL TILE. TYP. EACH SIDE
4'-0" A.F.F.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
K1 1/2" = 1'-0"3 5/8" METAL STUD PARTITION AT EXISTING CONSTRUCTION
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED. TYP. EACH SIDE
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD.
CERAMIC WALL TILE. TYP. EACH SIDE
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
EXISTING WALL CONSTRUCTION
4'-0" A.F.F.
TOILET SIDE TOILET SIDE TOILET SIDE NEW CONSTRUCTIONEXG. CONSTRUCTION
L1 1/2" = 1'-0"6" METAL STUD WALL
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED. TYP. EACH SIDE
18 GA. 6" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD.
CERAMIC WALL TILE
4'-0" A.F.F.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
TOILET SIDE
M1 1/2" = 1'-0"
P1 1/2" = 1'-0"3 5/8" METAL STUD PARTITION
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED.
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT
5/8" TYPE 'X' GYP. BD.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
VARIES
6" METAL STUD PARTITION R1 1/2" = 1'-0"
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED.
18 GA. 6" METAL STUDS @ 16" O.C.
SEALANT
5/8" TYPE 'X' GYP. BD.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
S1 1/2" = 1'-0" 6" METAL STUD PARTITION T1 1/2" = 1'-0"
FLOOR FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
5/8" TYPE 'X' GYPSUM BOARD
18 GAUGE 6" METAL STUDS
@ 16" O.C.
EXG. WALL CONSTRUCTION
NEW CONSTRUCTIONEXG. CONST.
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
EXISTING CONCRETE DECK
CERAMIC WALL TILE
4'-0" A.F.F.
U1 1/2" = 1'-0" V1 1/2" = 1'-0"3 5/8" METAL STUD PARTITION @ SHOWER W1 1/2" = 1'-0" DEFLECTION DETAIL - TYPICAL TO ALL PARTITIONS
/2
EXISTING CONCRETE DECK
/2
TOP OF STUDS
METAL STUDS @ 16" O.C.
ATTACH WALLBOARD TO
STUDS. DO NOT ATTACH
TO TOP TRACK.
X1 1/2" = 1'-0"
SEALANT - TYP. EACH SIDE
FLOOR FINISH AS SCHEDULED
EXISTING CONCRETE DECK
WALL BASE AS SCHEDULED. TYP. EACH SIDE
18 GA. 3 5/8" METAL STUDS @ 16" O.C.
SEALANT - TYP. BOTH SIDES
5/8" TYPE 'X' GYP. BD.
CERAMIC WALL TILE
FULL WIDTH FRICTION FIT
SOUND BATT INSULATION
SHOWER SIDE
NOTE:
1. SEE PLAN FOR SPECIFIC
WALL FIRE RATING
DEFLECTION CLIPS - TYP.
FLOOR FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
EXISTING WALL CONSTRUCTION
NEW CONSTRUCTIONEXG. CONSTRUCTION
EXISTING CONCRETE DECK
PLASTER @ EXISTING EXTERIOR WALL CONSTRUCTION
1/8" PLASTER, SKIM COATING. SMOOTH FINISH
PREPARE SURFACE FOR FINISHES
NOT USED
NOT USED
NOT USEDNOT USED
NOT USED
NOT USED NOT USED
NOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USED
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
N
T
C E
I L
TA
S SHEILA
001-016606
CD A R
S E
LYNN
T C
H I
T E
ILOF I L
E NO
I S
EXPIRES 11-30-20
HENSLEY
BAYSINGER
/1
/2
:0
:2
P
M
A-501
PARTITION TYPE DETAILS
18 28ZC
RELOCATE AND UPGRADE
OPERATING SUITES -
MARION, IL
MARION VAMC
MARION, IL 62959
11/13/2019
BID DOCUMENTS
657-501
MM
FIRE CAULK AND SEAL ALL PENETRATIONS,
INCLUDING PERIMETER OF ELECTRICAL BOXES, IN
PARTITIONS OF FIRE RATED PARTITIONS.
PROVIDE ACOUSTICAL SEALANT AT ALL
PENETRATIONS, INCLUDING PERIMETER OF
ELECTRICAL BOXES, IN PARTITIONS INDICATED TO
RECEIVE ACOUSTICAL SEALANT OR INDICATED AS
AN STC PARTITION.
USE SLIP TRACKS FOR ALL TOP TRACKS OF
PARTITIONS, UNLESS NOTED OTHERWISE. WALL
BOARD SHALL BE ATTACHED TO STUDS. DO NOT
ATTACH WALL BOARD TO TOP TRACK. RE:
DEFLECTION DETAILS THIS SHEET.
PROVIDE BULLNOSE CORNERS. TYPICAL ALL
LOCATIONS.
1/8" SKIM COAT PLASTER WORK SHALL HAVE A
SMOOTH FINISH. PLASTER SURFACE TO BE
PREPARED FOR FINISHES
ALL SOLID POLYMER PANELS USED AS A WALL
FINISH SHALL BE 1/4" THICK PANELS.
FIRE DAMPERS ARE NOT REQUIRED FOR 1-HOUR
WALLS.
ALL 2-HOUR FIRE RATED WALLS TO HAVE (2)
LAYERS OF 5/8" GYPSUM BOARD, EACH SIDE.
1.
2.
3.
4.
5.
6.
7.
8.
File details come from the government source that posted it. Updated .