P09 Corrected OR_ARCH_A-502 - GENERAL DETAILS - 1 Page.pdf

PDF 167 KB Posted

Attached to
Z2DA--Construct Surgical Suite Addition P/N: 657-501 Federal contract opportunity
Solicitation number
36C25520R0040-0001
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document contains construction drawings and details for a surgical suite addition project. The drawings show plans for expanding operating room capacity, including layouts for a reception counter, transaction window, ceiling systems, wall construction, window renovations, and notes specifying materials like gypsum board and metal studs. Related procurement information indicates this project is in response to solicitation number 36C25520R0040-0001 issued by the Department of Veterans Affairs for constructing the surgical suite addition at the Marion VA Medical Center in Marion, Illinois. The bid documents were released in November 2019 as part of a planned renovation and upgrade of operating rooms.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Construct Surgical Suite Addition P/N: 657-501, newest first.
File Type Posted
P09 Corrected OR_ARCH_A-501 - PARTITION TYPE DETAILS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-601 - DOOR SCHEDULE DOOR ELEVATIONS AND DETAILS - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-003 - PHASING AND INFECTION CONTROL PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-101 - SECOND FLOOR OVERALL RENOVATION PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-001 - ARCHITECTURAL NOTES ABBREVIATIONS AND SYMBOLS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-301 - BUILDING SECTIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC103 - Bldg 2 2nd FLOOR AREA B REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-202 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-103 - BLDG 02 2ND FLOOR AREA B RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS111 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-201 - EXTERIOR BUILDING ELEVATIONS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AD101 - SECOND FLOOR DEMOLITION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-002 - SECOND FLOOR EXISTING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_G-002 - DRAWING INDEX AND PROJECT INFORMATION - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-401 - ENLARGED PLANS - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC104 - BLDG 38 2ND FLOOR REFLECTED CEILING PLAN - 1 Page.pdf PDF
S06 36C25520R0040 0001.docx DOCX document
P09 Corrected OR_ARCH_A-104 - BLDG 38 SECOND FLOOR RENOVATION PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS101 - LIFE SAFETY FLOOR PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC102 - BLDG 2 2nd FLOOR AREA A REFLECTED CEILING PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_AC101 - SECOND FLOOR REFLECTED CEILING PLAN - 1 page.pdf PDF
P09 Corrected OR_ARCH_A-105 - ROOF PLAN - 1 Page.pdf PDF
P09 Corrected OR_ARCH_LS112 - LIFE SAFETY - ACCESSIBILITY GUIDELINES - 1 Page.pdf PDF
P09 Corrected OR_ARCH_G-001 - COVER - 1 Page.pdf PDF
P09 Corrected OR_ARCH_A-102 - BLDG 02 2ND FLOOR AREA A RENOVATION PLAN - 1 Page.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLAN

ISOMETRIC

GENERAL NOTES

1. CONTRACTOR SHALL

COORDINATE LOCATIONS

OF HORIZONTAL

FASTENERS

WALL FINISH

VERTICAL WALL

STUDS @ 16"

(406MM) O.C.

CUT HORIZ.

FASTENER FROM

STUD

FASTEN AT BOTH

ENDS WITH MIN.

4 TAPPING SCREWS

CONT. SANTOPRENE

SEAL

CONT. ALUMINUM

FRAME

POP RIVET

SUSPENDED ACT

CEILING SYSTEM

2"

CONT. SANTOPRENE

SEAL

CONT. ALUM. FRAME

SELF-TAPPING SHEET

METAL SCREWS - 7 PER

FRAME @ 18" O.C.

FEATHERED JOINT

COMPOUND

MOLD-RESISTANT

GYP. BD.

LT. GAUGE METAL

FRAMING

FIRE CAULK 2 HR. BARRIER

20 GA. GALVANIZED

RETAINER

FIRE CAULK

HEX HEAD CONCRETE

SCREW - 7 PER FRAME

@ 18" O.C.

FLOOR FINISH AND

BACKFILL

CONT. ALUM. RECESSED FRAME

CONT. ALUM. GLIDE PLATE W/

CRENELLATED SURFACE

CONT. FLEXIBLE

VINYL GASKET

CONT. ALUM. SLIDE-

IN UPSTAND

1/

8"

1/ 2"

3 1/4" 2" 2 3/4"

NOTE:

TO DETERMINE BLOCKOUT DEPTH, DEDUCT THICKNESS OF

FLOOR FINISH FROM FRAME HEIGHT.

SECOND FLOOR

494' - 4"

RECEPTION COUNTER.

RE: INTERIORS.

SOLID SURFACE

TRANSACTION COUNTER

OVER 1/2" PARTICLE

BOARD. ALL EXPOSED

EDGES SHALL BE

BULLNOSED.

1' - 0"

1"

SLIDING RECEPTION

WINDOW

SECOND FLOOR

494' - 4"

A .F

.F

1' - 2"

7"

11/2" DIA. STEEL

HANGER ROD

STEEL BRACKET,

@ 16" O.C.

EXISTING WALL

MELAMINE SHELF

BULLNOSE EDGE

EXTERIOR

WINDOW OPENING

C O

N S

T R

U C

T

IO

N

E X

IS

T

IN

G

W A

L L

5/8" GYP. TYPE X

18G METAL STUDS

@ 16" O.C.

REMOVE WINDOW SILL

TO PROVIDE SMOOTH

TRANSITION

BITUMONOUS

COATING

18 GA. 21/2" METAL STUD

FRAMING @ 6" O.C.

11/2" RIGID INSULATION

5/8" PLY. BOARD

SEAL ALL GAPS AT

WINDOW JAMBS

INTERIOR

A-502

1x BLOCKING

FASTEN TO EXISTING

JAMB

1/8" DIA WEEP HOLES.

3 THUS

E X

T E

R I O

R

W

IN

D O

W O

P E

N

IN

G

CONSTRUCTION

EXISTING WALL

5/8" GYP. TYPE X

18G METAL STUDS @ 16"

O.C.

REMOVE WINDOW SILL

TO PROVIDE SMOOTH

TRANSITION

BITUMONOUS

COATING

IN

TE

R

IO

R

1X BLOCKING FASTEN

TO EXISTING JAMB

BATT INSULATION

18 GA. 21/2" METAL STUD

FRAMING @ 6" O.C.

SEAL ALL GAPS AT

WINDOW SILL

11/2" RIGID INSULATION

5/8" PLY. BOARD

1/8" DIA. WEEP

HOLES.

3 THUS

SEAL ALL GAPS AT

WINDOW SILL

A-502

1X BLOCKING FASTEN

TO SILL

E X

T E

R I O

R

W

IN

D O

W O

P E

N

IN

G

EXISTING WALL

EXISTING WALL

3/4" SOLID SURFACE;

SEE INTERIORS 1/2" SHIM

FIELD VERIFY 3/4"

EXISTING WINDOW SILL

WALL BEYOND

5/8" GYP. TYPE X

18G METAL STUDS @ 16" O.C.

BATT INSULATION

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg. of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

N

T

C E

I L

TA

S SHEILA

001-016606

CD A R

S E

LYNN

T C

H I

T E

ILOF I L

E NO

I S

EXPIRES 11-30-20

HENSLEY

BAYSINGER

/1

/2

:0

:3

P

M

A-502

GENERAL DETAILS

19 28ZC

RELOCATE AND UPGRADE

OPERATING SUITES -

MARION, IL

MARION VAMC

MARION, IL 62959

11/13/2019

BID DOCUMENTS

657-501

2, 38

MM

1 1/2" = 1'-0"

ANCHORAGE - GRAB BARS AND CABINETS & WALL MOUNTED ITEMS

6" = 1'-0"

EXPANSION JOINT - ACT CEILING

6" = 1'-0"

EXPANSION JOINT - GYP BOARD

6" = 1'-0"

FIRE RATED EXPANSION JOINT - FLOOR

1 1/2" = 1'-0"

RECEPTION 224 TRANSACTION COUNTER DETAIL

1 1/2" = 1'-0"

HANGING ROD & SHELF

1 1/2" = 1'-0"

WINDOW RENOVATION @ JAMB

1 1/2" = 1'-0"

WINDOW RENOVATION @ HEAD & SILL

1 1/2" = 1'-0"

EXISTING WINDOW SILL RENOVATION

File details come from the government source that posted it. Updated .