Ocean County Administration Building HVAC and Roofing Upgrades - Construction Drawings
This is a comprehensive set of construction drawings and specifications for the Ocean County Administration Building HVAC and Roofing Upgrades project located at 101 Hooper Avenue, Toms River, New Jersey. The project encompasses significant mechanical and roofing work including the installation of a new 250-ton air-cooled screw chiller (CHLR-1), two variable frequency drive (VFD) chilled water pumps rated at 15 horsepower each with a capacity of 540 gallons per minute at 75 feet of total dynamic head, dry coolers, multiple fan coil units distributed across basement through third floor levels, and comprehensive chilled water piping systems with associated controls and instrumentation. The roofing component includes a TPO overlay (recover application) covering approximately 10,700 square feet of base scope roof restoration, 350 square feet of wet insulation repair and replacement, and 13 roof drain bowl replacements on a unit price basis. The drawings indicate the project was issued for bid on May 27, 2026, at 60% review level (December 20, 2024), progressing through 80% review (March 10, 2025) and 90% review (March 28, 2025) stages. Contractor responsibility includes obtaining all local and state permits, providing temporary protection and weatherproofing, coordinating with existing building operations, maintaining clean conditions throughout construction, and submitting final as-built drawings and operations manuals upon completion.
The contract documents establish that the single prime contractor is responsible for furnishing and installing all equipment, materials, and products shown on the drawings and detailed in specifications unless explicitly identified as work furnished by others. All demolition work, including removal of existing water-cooled chillers, chilled water and cooling water pumps and piping, and existing cooling towers, becomes the contractor's property and must be removed and disposed of off-site. The contractor must verify all existing conditions, dimensions, roof areas, and equipment locations prior to bidding and submit shop drawings for engineer approval before fabrication. All work must comply with applicable codes including the 2021 International Building Code (New Jersey Edition), 2021 National Standard Plumbing Code, 2020 National Electrical Code, ASHRAE 90.1 (2019), applicable mechanical and fuel gas codes, and the New Jersey Rehabilitation Subcode. The project requires coordination with the owner's construction manager regarding building access, staging areas, and dumpster management, with particular attention to maintaining means of egress for building occupants and protecting existing paved and planted areas from damage during construction.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T-00
TITLE SHEET
AS NOTED
12/20/24
AIL
MA
WC
Revision History
William T. Conley (NJ)
24GE04587200
Seal
OCEAN COUNTY ADMINISTRATION BUILDING
HVAC AND ROOFING UPGRADES
101 Hooper Avenue Toms River, NJ 08753
2 LOCATION MAP
N.T.S.1 VICINITY MAP
N.T.S.
PROJECT
LOCATION
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
INDEX OF DRAWINGS
TITLE
GENERAL
IS
SU
ED
F
O R
RE
VI
EW
/2 0/
ISSUE HISTORY:
T-00 TITLE SHEET
DG-200 DEMOLITION PLAN - BASEMENT
ELECTRICAL
E-00 GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
E-100 ELECTRICAL ONELINE - DEMO & NEW WORK
E-200 PARTIAL BASEMENT PLAN - NEW WORK
E-201 PARTIAL ROOF PLAN - NEW WORK
G-200 BASEMENT FLOOR PLAN
G-201 PROPOSED FAN COIL LAYOUT - FIRST FLOOR
G-202
G-203
PROPOSED FAN COIL LAYOUT - SECOND FLOOR
PROPOSED FAN COIL LAYOUT - THIRD FLOOR
G-204 ROOF PLAN
MECHANICAL
DM-300 MECHANICAL DEMOLITION DETAILS
DM-301 MECHANICAL DEMOLITION DETAILS
DM-302 MECHANICAL DEMOLITION DETAILS
DM-303 MECHANICAL DEMOLITION DETAILS
M-00 LEGEND
M-100 NOTES
M-110 DEMO P&ID
M-165 CHW SYSTEM P&ID
M-195 EQUIPMENT SCHEDULES
M-800 MECHANICAL DETAILS
M-900 PIPE SUPPORT DETAILS
STRUCTURAL
S-200 ROOF FRAMING PLAN
E-700 ELECTRICAL PANEL SCHEDULES
DE-200 ELECTRICAL DEMOLITION PARTIAL FLOOR PLANS
IS
SU
ED
F
O R
RE
VI
EW
/1 0/
IS
SU
ED
F
O R
RE
VI
EW
/2 8/
M-200 PROPOSED PIPING PLANS & SECTIONS
M-197 SEQUENCE OF OPERATIONS
ISSUED FOR BID5/27/260
IS
SU
ED
F
O R
BI
D
/0
7/
OCEAN COUNTY COMMISSIONERS
FRANK SADEGHI, DIRECTOR
JENNIFIER BACCHIONE, DEPUTY DIRECTOR
ROBERT S. ARACE, COMMISSIONER
SAM ELLENBOGEN, COMMISSIONER
RAY GORMLEY, COMMISSIONER
G-102 ROOF DETAILS
G-101 ROOF DETAILS
G-100 ROOF RESTORATION PLAN
G-100 GENERAL NOTES
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text Name:
AutoCAD SHX Text Date:
AutoCAD SHX Text Signed:
AutoCAD SHX Text License#:
AutoCAD SHX Text I hereby certify that this document was prepared by me or under my direct supervision and that I am a duly registered Professional Engineer under the laws of the State of New Jersey.
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
AutoCAD SHX Text Drawn by:
G-001
GENERAL NOTES
AS NOTED
04/11/26
MA
WC
WC
Revision History
GENERAL PROJECT NOTES:
1. THE CONTRACTORS ARE RESPONSIBLE FOR ALL REQUIREMENTS OUTLINED IN THE I.B.C. CODE, STATE UNIFORM CONSTRUCTION CODE, MUNICIPAL CODES AND ORDINANCES, AND SHALL COMPLY WITH GOVERNING CODE AS ADMINISTERED BY MUNICIPAL BUILDING OFFICIALS AND SHALL BE CONSIDERED AS PART OF THESE CONSTRUCTION DOCUMENTS. WHERE DRAWINGS CONFLICT WITH CODES, CODE
REQUIREMENTS SHALL TAKE PRECEDENCE.
2. THE CONTRACTOR SHALL INVESTIGATE AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS BEFORE ORDERING MATERIALS AND PREFABRICATED ITEMS. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, LABOR AND MATERIALS NECESSARY FOR THE PROPER
EXECUTION AND COMPLETION OF THE WORK IN ACCORDANCE WITH THESE PLANS.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL LOCAL AND STATE PERMITS NEEDED FOR CONSTRUCTION AND COMPLETION
OF PROJECT.
4. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO KEEP ALL WORK AREAS AND MATERIALS SECURE AND LOCKED DURING ALL PHASES OF
CONSTRUCTION.
5. THE BUILDING AND SITE SHALL BE KEPT CLEAN AT ALL TIMES. AFTER COMPLETION OF THE WORK THE CONTRACTOR SHALL REMOVE ALL
EXCESS MATERIALS, ALL TRASH AND DEBRIS BY HIS WORK.
6. THESE DRAWINGS ARE NOT INTENDED TO PROVIDE COMPLETE FABRICATION AND INSTALLATION OF ALL WORK DESCRIBED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE OWNER'S ENGINEER DURING THE BID PERIOD IF, IN THEIR OPINION, ANY WORK IDENTIFIED ON THE DRAWINGS AND SPECIFCATIONS IS INCOMPLETE WITH THE INFORMATION GIVEN HEREIN. FAILURE TO NOTIFY THE ENGINEER SHALL MEAN THE CONTRACTOR UNDERSTANDS THE DOCUMENTS AND THEIR INTENT, AND ALL ITEMS WILL BE COMPLETE IN
EVERY DETAIL.
7. THE ENGINEER IS NOT RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, PROCEDURES, SAFETY PRECAUTIONS, NOR FOR THE CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
8. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS SHOWN HEREIN UNLESS SPECIFICALLY NOTED AS BEING FURNISHED BY OTHERS.
SHOULD THERE BE ANY QUESTIONS CONCERNING RESPONSIBILITY, THEY SHALL BE SETTLED BEFORE BID SUBMISSION AND CONTRACT SIGNING. NO EXTRA CHARGES WILL BE ALLOWED. THE ENGINEER WILL NOT BE RESPONSIBLE WHERE CONSTRUCTION DEVIATES FROM
THESE DRAWINGS.
9. THE CONTRACTOR SHALL FULLY ACCOUNT HIMSELF WITH THE EXISTING CONDITIONS AND SHALL HAVE VISITED AND INSPECTED THE JOB SITE AND BE FULLY INFORMED AS TO THE NATURE OF EQUIPMENT AND FACILITIES NEEDED FOR THE PROPER EXECUTION OF THE WORK.
STARTING OF DEMOLITION AND REMOVAL OPERATIONS WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS COMPLIED WITH THESE REQUIREMENTS: ANY LATER CLAIMS FOR DIFFICULTIES ENCOUNTERED, WHICH COULD HAVE BEEN FORESEEN, WILL NOT BE
RECOGNIZED.
10. VERIFY ALL EXISTING ELEVATIONS, CONDITIONS AND DIMENSIONS AT THE SITE, AGAINST THE DRAWINGS, AND INFORM THE ENGINEER OF ANY DISCREPANCIES PRIOR TO COMMENCING WITH WORK AND SUBMISSION OF ANY SHOP DRAWINGS.
11. ALL WORK, WHETHER SHOWN OR IMPLIED, UNLESS SPECIFICALLY QUESTIONED, SHALL BE CONSIDERED FULLY UNDERSTOOD IN ALL RESPECTS BY THE CONTRACTOR. THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY MISINTERPRETATIONS AND/OR CONSEQUENCES
THEREOF, FOR ALL WORK ON ALL DRAWINGS.
12. CONTRACTOR SHALL FOLLOW ACCEPTED TRADE PROCEDURES AND MANUFACTURER'S STANDARDS AND SHALL PRODUCE THE PROJECT IN A GOOD AND WORKMANLIKE MANNER. ALL MATERIALS ARE TO BE NEW, UNLESS OTHERWISE NOTED IN THE DRAWINGS: AND CONTRACTOR SHALL NOT SUBSTITUTE ANY STRUCTURAL GRADE MATERIALS WITHOUT PRIOR WRITTEN APPROVAL FROM THE ENGINEER.
13. CONTRACTOR SHALL SCHEDULE ALL WORK TO CONFORM TO THE GENERAL CONSTRUCTION SCHEDULE AND SHALL COOPERATE WITH OTHER CONTRACTORS IN THE REQUIRED SEQUENTIAL INSTALLATION SCHEDULE AS APPROVED BY THE ENGINEER ALL WORK SHALL
COMMENCE AND CONTINUE UNTIL COMPLETION WITHOUT UNDUE DELAY.
14. THE CONTRACTORS SHALL LEAVE THE PREMISES IN A NEAT, CLEAN AND SAFE CONDITION AT THE COMPLETION OF WORK EACH DAY.
15. ALL CONDITIONS WHICH OCCUR AND WHICH ARE NOT IN CONFORMANCE WITH THESE SPECIFICATIONS AND ADJACENT DRAWINGS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ENGINEER FOR PROMPT RESOLUTION. FAILURE TO DO SUCH SHALL BE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
16. NO MATERIAL SUBSTITUTIONS SHALL BE MADE. THE ENGINEER WILL CONSIDER MATERIAL CHANGE REQUESTS ON AN INDIVIDUAL BASIS.
CONTRACTOR SHALL SUBMIT SAMPLES AND CUTS FOR WRITTEN APPROVAL BY THE ENGINEER PRIOR TO THE START OF ANY WORK.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF WORK AND ESTABLISHING SCHEDULES FOR ALL TRADES. HE SHALL AFFORD OTHER SUB-CONTRACTORS REASONABLE OPPORTUNITY FOR THE INTRODUCTION AND STORAGE OF THEIR MATERIALS AND
EQUIPMENT AND THE EXECUTION OF THEIR WORK.
18. ALL MANUFACTURED ARTICLES, MATERIALS AND EQUIPMENT SHALL BE INSTALLED, CONNECTED, ERECTED, USED, CLEANED AND CONDITIONED AS DIRECTED BY THE MANUFACTURER, UNLESS OTHERWISE SPECIFIED ON THE DRAWINGS.
19. EACH SUBTRADE WILL BE RESPONSIBLE FOR REVIEWING THE ENTIRE SET OF DRAWINGS AND NOTING HIS WORK AS APPLICABLE. WORK INDICATED OR INFERRED ON THE DRAWINGS WILL BE DEEMED AND INCLUDED IN SUB-CONTRACTOR'S COSTS.
20. THE CONTRACTOR SHALL SUBMIT, IN WRITING, ALL PROPOSALS FOR ADDITIONAL WORK TO THE A/E'S OFFICE FOR REVIEW AND APPROVAL.
NO WORK IS TO PROCEED UNTIL A SIGNED PROPOSAL IS RETURNED TO THE GENERAL CONTRACTOR.
21. PERMITS: THE CONTRACTOR WILL SECURE REQUIRED BUILDING PERMITS PRIOR TO START OF WORK. INDIVIDUAL SUBCONTRACTORS ARE
TO SECURE NECESSARY PERMITS PRIOR TO START OF THEIR RESPECTIVE WORK.
22. TEMPORARY PROTECTION: PARTICULAR ATTENTION SHALL BE GIVEN TO THE PROTECTION OF EXISTING STRUCTURE AND FINISHES SO AS TO PREVENT ANY DAMAGE OF EXISTING FINISHES NOT DESIGNATED FOR DEMOLITION. PROVIDE ALL NECESSARY, TEMPORARY CONSTRUCTION AND DUSTPROOF PROTECTION. PROTECTIONS SHALL BE IN COMPLIANCE WITH BUILDING STANDARDS. TYPE AND LOCATION OF PROTECTION SHALL BE REVIEWED WITH OWNER'S CONSTRUCTION REPRESENTATIVE PRIOR TO COMMENCING WORK. CONTRACTOR SHALL FULLY BRACE AND OTHERWISE PROTECT ALL WORK IN PROGRESS UNTIL THE BUILDING IS COMPLETED.
23. PROVIDE FULL AND COMPLETE PROTECTION REQUIRED FOR ALL AREAS REMAINING OPERATIONAL DURING ALL PHASES OF THIS PROJECT.
CONTRACTOR TO TAKE ALL NECESSARY MEASURES TO PREVENT DAMAGE TO ANY ADJACENT PROPERTY AND/OR PERSONS.; THE CONTRACTOR SHALL REPAIR AND PATCH ANY AREAS THAT ARE ALTERED OR DAMAGED DURING PROCESS OF ALTERATION.
24. ANY EXISTING WORK DAMAGED BY THE CONTRACTOR OR SUB-CONTRACTORS SHALL BE RETURNED TO ITS ORIGINAL CONDITION AT THE
CONCLUSION OF THE PROJECT, AT NO ADDITIONAL COST TO THE OWNER.
25. IT IS THE RESPONSIBILITY OF THE CONTRACTOR & IT'S SUB-CONTRACTORS TO KEEP THE BUILDING WEATHERTIGHT AND MAINTAIN ALL BARRICADES, SHORING, BRACING AND OTHER SAFETY MEASURES REQUIRED TO PROTECT THE BUILDING, WORKMEN AND THE PUBLIC.
26. CLEAN-UP: ALL MATERIALS DEMOLISHED, EXCEPT AS INDICATED ON THE DRAWINGS TO BE SALVAGED, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED AND DISPOSED OF, OFF THE SITE WITH SUCH DILIGENCE AS TO CAUSE NO INTERFERENCE WITH SUBSEQUENT BUILDING OPERATIONS, USE OF BUILDING BY OCCUPANTS OR ANY UNSIGHTLY ACCUMULATION OF DEBRIS CONSTRUCTION
DEBRIS SHALL BE REMOVED DAILY.
27. UPON COMPLETION OF ALL DEMOLITION AND REMOVAL WORK, REMOVE ALL TOOLS AND APPARATUS FROM THE PREMISES. REMOVE FROM THE AREA OF WORK ALL DEMOLISHED MATERIAL NOT DESIGNATED FOR RE-USE. REMOVE ALL TEMPORARY SHORING, BRACING, LINTELS PROTECTION, ETC., AS DIRECTED. LEAVE THE AREA OF WORK, BROOM-CLEAN, NEAT AND ORDERLY, TO THE SATISFACTION OF THE OWNER. STORAGE OF MATERIALS SHALL NOT INTERFERE WITH THE MEANS OF EGRESS OF THE EXISTING CORRIDOR SPACES.
28. SHOPS DRAWINGS: THE CONTRACTOR SHALL CHECK AND VERIFY ALL FIELD MEASUREMENTS AND SUBMIT, WITH PROMPTNESS, SHOP DRAWINGS, SAMPLES, MANUALS AND SCHEDULES REQUIRED FOR APPROVAL. THE /ENGINEER'S APPROVAL SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR DEVIATIONS AT THE TIME OF SUBMISSION, NOR SHALL IT RELIEVE HIM FROM RESPONSIBILITY FOR ERRORS IN SHOP DRAWINGS. THIS SHALL BE DONE PRIOR TO FABRICATION AND REVIEWED BY THE ENGINEER.
29. WHEN REQUIRED BY THE ENGINEER, SHOP DRAWINGS OF FABRICATED WORK SHALL BE SUBMITTED. IF CORRECTIONS ARE REQUIRED, THIS
PROCEDURE SHALL BE FOLLOWED FOR SUBSEQUENT SUBMISSIONS UNTIL FINAL APPROVAL.
30. ALL SUBCONTRACTOR'S SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL, THROUGH THE CONTRACTOR, PRIOR TO WORK BEING PERFORMED, UNLESS OTHERWISE NOTED. THE SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR AND VISIBLY INDICATED AS SUCH ON THE DRAWINGS, PRIOR TO SUBMISSION FOR THE ENGINEER'S REVIEW.
31. APPROVALS: THE ENGINEER WILL REVIEW SUBMITTAL WITH REASONABLE PROMPTNESS, SO AS TO CAUSE NO DELAY, BUT ONLY FOR CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS.
32. NO PORTION OF THE WORK REQUIRING A SUBMISSION SHALL BE COMMENCED BY THE CONTRACTOR, UNTIL THE SUBMISSION HAS BEEN
REVIEWED AND NOTED BY THE ENGINEER.
33. ALL COLOR SELECTIONS SHALL BE MADE AND COORDINATED THROUGH THE OFFICE OF THE ENGINEER, EXCEPT AS OTHERWISE DIRECTED BY THE OWNER. COLORS: UNLESS THE PRECISE COLOR AND PATTERN IS SPECIFICALLY DESCRIBED IN THE CONTRACT DOCUMENTS, WHENEVER A CHOICE OF COLOR OR PATTERN IS AVAILABLE IN A SPECIFIED PRODUCT, SUBMIT ACCURATE COLOR CHARTS AND PATTERN
CHARTS TO THE ENGINEER FOR HIS REVIEW AND SELECTION.
34. THE CONTRACTOR SHALL SUBMIT FINAL "AS BUILT" DRAWINGS - SIX (6) PRINTS OF EACH TRADE AS PART OF THE CONTRACT.
35. THE CONTRACTOR SHALL SUBMIT THE SAMPLES IN SUFFICIENT TIME TO PERMIT CHECKING, RESUBMISSION, RECHECKING, APPROVAL FABRICATION AND DELIVERY. FAILURE TO DO SO WILL NOT JUSTIFY A DELAY IN THE TIME OF COMPLETION OF WORK.
36. DETAILS SHOWN IN ANY SECTION APPLY TO ALL SIMILAR SECTIONS UNLESS OTHERWISE NOTED.
GENERAL PROJECT NOTES (CONT'D):
37. WHEN CERTAIN ITEMS OF EQUIPMENT AND OTHER WORK ARE INDICATED AS "NIC" (NOT IN CONTRACT) OR TO BE FURNISHED AND INSTALLED UNDER OTHER CONTRACTS, ANY REQUIREMENTS FOR PREPARATION OF OPENINGS, PROVISION OF BACKING, ETC. FOR RECEIPT OF SUCH "NIC" WORK, SHALL BE PROVIDED TO THE CONTRACTOR, WHO SHALL PROPERLY FORM AND OTHERWISE PREPARE
HIS WORK IN A SATISFACTORY MANNER TO RECEIVE SUCH "NIC" WORK.
38. UPON WRITTEN REQUEST OF CONTRACTOR, THE OWNER WILL FURNISH TO THE CONTRACTOR A SCHEDULE INDICATING DELIVERY DATES AND INSTALLATION REQUIREMENTS OF EQUIPMENT TO BE FURNISHED AND INSTALLED UNDER SEPARATE CONTRACTS.
39. IT WILL BE THE CONTRACTOR'S RESPONSIBILITY TO SEE THAT THE BUILDING AREAS ARE MADE READY TO RECEIVE AND INSTALL THE OWNER'S EQUIPMENT, IN ACCORDANCE WITH THE DELIVERY SCHEDULE AND SPECIFIC REQUIREMENTS FURNISHED. FAILURE TO MEET THE SCHEDULE ON ITEMS OF THE OWNER-FURNISHED EQUIPMENT WILL BE CONSIDERED AS IMPORTANT TO THE COMPLETION
SCHEDULE AS ANY OTHER PART OF THE WORK.
40. ALL OPENINGS IN PARTITIONS OR BLOCK WALLS INCLUDING, BUT NOT LIMITED TO, DUCTWORK, PENETRATIONS, DOOR OPENINGS, ETC. SHALL BE SUPPORTED BY STEEL LINTEL UNLESS OTHERWISE INDICATED. CONTRACTOR IS TO FURNISH AND INSTALL ALL ANGLES, STRUTS, BRACKETS, TOGGLES, EYE BOLTS, ETC. WHEREVER NECESSARY TO PROPERLY SUPPORT, BRACE OR REINFORCE ALL FINISHES, FRAMES, EQUIPMENT, ETC.
41. ALL BLOCK AND ADJACENT RATED WALL CONSTRUCTION SHALL MEET THE FIRE RESISTIVE RATINGS AND OTHER REQUIREMENTS OF BUILDING CODE AND REGULATIONS, LOCAL LAWS, ORDINANCES, REGULATIONS AND AUTHORITIES HAVING JURISDICTION.
42. ALL CUTTING AND PATCHING OF OPENINGS SHALL BE POINTED UP, AND SURFACE REPAIRED FOR AN AIRTIGHT SEAL.
43. ALL EXISTING WALL FINISHES OR EQUIPMENT, ETC. WHICH ARE DISTURBED DURING CONSTRUCTION AND PROVE NOT TO BE NECESSARY AND NOT BE SPECIFICALLY INDICATED "TO REMAIN", SHALL BE REMOVED, PATCHED, REPAIRED OR COVERED. EITHER AS INDICATED ON THE PLANS OR TO CREATE A FLUSH, UNIFORM SURFACE HAVING THE INTEGRITY OF SUCH.
44. ALIGNMENT OF NEW CONSTRUCTION TO EXISTING WALLS AND COLUMNS SHALL HAVE BE DONE IN A MANNER AS TO VISIBLY ELIMINATE THE POINT OF CONTACT OR JOINT OF NEW AND EXISTING MATERIALS. NEW CONSTRUCTION SHALL BE FLUSHED WITH EXISTING.
45. ALL WOOD PRODUCTS, FURRING STRIPS, BLOCKING ETC., SHALL BE FIRE RATED, IN ACCORDANCE WITH APPLICABLE STATE, CITY AND
LOCAL BUILDING CODES.
46. THE CONTRACTOR SHALL PATCH ALL CUTTING BY MECHANICAL AND ELECTRICAL TRADES AND ALL ADDITIONAL CUTTING BY OTHERS.
COORDINATE THE WORK PRIOR TO THESE TRADES PROCEEDING. NO EXTRAS WILL BE ALLOWED. DUE TO FAILURE TO COORDINATE SUCH, OR PROCEEDING WITH WORK THAT COULD HAVE BEEN AVOID WITH SUCH/PROPER PLANNING. REQUIRED.
47. NEW WORK IS TO MEET OR EXCEED THE APPLICABLE ENERGY CODE, NATIONAL ELECTRIC CODE NEC, NATIONAL STANDARD PLUMBING CODE (NSP), APPLICABLE MECHANICAL CODES, OSHA (WHERE APPLICABLE), AND ALL UL REQUIREMENTS. THE MOST RECENT
PUBLICATION DATE OF ALL AFOREMENTIONED CODES SHALL APPLY.
48. GUARANTEES: ALL MATERIALS AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE, UNLESS SPECIFIED OTHERWISE FOR A LONGER PERIOD OF TIME FOR SPECIFIC ITEMS. EACH SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS INCIDENTAL THERETO. INCLUDING DAMAGE TO OTHER WORK, FURNISHINGS OR EQUIPMENT IF THE SUB-CONTRACTOR, AFTER NOTICE IN WRITING FROM THE CM AND ENGINEER, FAILS TO PROCEED PROMPTLY TO COMPLY WITH THE TERMS OF THE GUARANTEE. THE CM MAY HAVE THE DEFECTS CORRECTED AND THE SUB-CONTRACTOR WILL BE RESPONSIBLE FOR ALL
EXPENSES INCURRED.
49. A CONTRACTOR MAKING A BID FOR WORK ON THIS PROJECT IS MADE AWARE BY THIS NOTE THAT IT IS THE INTENT OF THE OWNER TO HAVE A COMPLETELY INSTALLED JOB BY A SINGLE PRIME CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING ALL EQUIPMENT AND MATERIALS / PRODUCTS SHOWN AND / OR DETAILED ON ANY PROJECT DRAWINGS OR SPECIFICATIONS UNLESS SPECIFICALLY IDENTIFIED ELSEWHERE AS WORK BEING FURNISHED BY OTHERS. WHERE EQUIPMENT REQUIRING WIRING IS SPECIFIED OR SHOWN ON SHOP DRAWINGS SUBMITTED LATER, THE CONTRACTOR CAN AND SHALL REQUEST DIRECTION REGARDING CIRCUIT SIZING PROTECTION AND ROUTING WHERE NECESSARY BUT SHALL UNDERSTAND ALL NECESSARY WORK TO COMPLETE THE INSTALLATION SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER OF THE PROJECT.
ACCEPTANCE OF BID WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS COMPLIED WITH ALL REQUIREMENTS STATED
ABOVE.
50. ALL EXISTING ROOF DRAINS TO BE SNAKED OUT AND TO BE FREE FLOWING. GC TO INSPECT AND PERFORM A WATER TEST AS PER
SPECIFICATIONS.
GENERAL ROOF RESTORATION NOTES (REFER TO PLANS FOR SPECIFIC SCOPE OF WORK):
1. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL ACCESS TO WORK AREAS AS REQUIRED, IN COMPLIANCE WITH ALL CODE, AND OSHA SAFETY REQUIREMENTS. THIS SHALL INCLUDE, BUT IS NOT LIMITED TO, SUPPORTED SCAFFOLDS, SUSPENDED PLATFORMS, LIFTS, PLATFORMS, LADDERS, STAIRS, RAILINGS, ETC.
2. ROOF AREAS PROVIDED ON THE DRAWINGS ARE APPROXIMATE AND ARE PROVIDED FOR CONTRACTORS REFERENCE ONLY. THE BIDDER/CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL ROOF AREAS INDICATED PRIOR TO SUBMITTING THEIR BID. ROOF PLANS
PROVIDED SHALL NOT BE SCALED, REGARDLESS OF ANY SCALE PROVIDED.
3. ALL WORKERS ARE TO WEAR SAFETY EQUIPMENT AND FALL PROTECTION AS REQUIRED BY OSHA AND ALL APPLICABLE CODES
4. CONTRACTOR TO PROVIDE ACCESS TO WORK AREAS FROM EXTERIOR OF BUILDING WHENEVER POSSIBLE.
5. CONTRACTOR TO COORDINATE WITH OWNER'S CONSTRUCTION MANAGER FOR ACCESS TO BUILDING.
6. CONTRACTOR TO COORDINATE STORAGE AND STAGING AREAS WITH OWNER'S CONSTRUCTION MANAGER.
7. THE CONTRACTOR SHALL MAINTAIN ALL BARRICADES, SHORING, BRACING AND OTHER SAFETY MEASURES TO PROTECT THE BUILDING, WORKMEN AND THE PUBLIC.
8. THE CONTRACTOR SHALL FULLY FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS AND SHALL HAVE VISITED AND INSPECTED THE JOB SITE AND BE FULLY INFORMED AS TO THE NATURE OF EQUIPMENT AND FACILITIES NEEDED FOR THE PROPER EXECUTION OF THE WORK. STARTING OF DEMOLITION AND REMOVAL OPERATIONS WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS COMPLIED WITH THESE REQUIREMENTS ANY LATER CLAIMS FOR DIFFICULTIES ENCOUNTERED. WHICH COULD HAVE BEEN FORESEEN, WILL NOT BE CONSIDERED.
9. CONSTRUCTION OPERATIONS WILL NOT BLOCK MEANS OF EGRESS FOR BUILDING OCCUPANTS FROM VARIOUS AREAS OF THE BUILDING.
10. CONSTRUCTION OPERATIONS WILL NOT INVOLVE THE INTERRUPTION OF LIFE SAFETY OR FIRE SAFETY SERVICES TO THE BUILDING UNLESS PROPER NOTIFICATION IS MADE TO THE OWNER AND ALL LOCAL GOVERNING AUTHORITIES.
11. THE CONTRACTOR SHALL COORDINATE ALL DUMPSTER STAGING AND TRUCK ROUTES WITH THE OWNER'S CONSTRUCTION MANAGER.
12. THE CONTRACTOR SHALL PROTECT ALL EXISTING PAVED AND PLANTED AREAS. THE CONTRACTOR SHALL REPAIR ANY PAVED OR PLANTED AREAS DAMAGED DURING CONSTRUCTION. REPAIRS SHALL BE MADE TO THE SATISFACTION OF THE OWNER. THE REPAIRS ARE TO INCLUDE, BUT ARE NOT LIMITED TO, REPAVING OF ASHPHALT DRIVEWAYS AND PARKING LOTS, REGRADING AND SEEDING OF
LAWN AND REPLACING DAMAGED PLANTS, SHRUBS, ETC.
13. THE TERM 'SALVAGE' SHALL BE DEFINED AS: THE PROCESS OF THE CONTRACTOR CAREFULLY REMOVING THE MENTIONED ITEM AND STORING IT (IN LOCATION DETERMINED BY OWNER) UNTIL NEEDED FOR THE CONSTRUCTION PHASE. IF THE CLIENT DOES NOT NEED
SAID ITEM CONTRACTOR SHALL DISPOSE OF PROPERLY AT NO ADDITIONAL COST.
14. THE TERM 'PATCH AND REPAIR' SHALL BE DEFINED AS: THE PROCESS OF REPAIRING FLOOR, WALL, OR CEILING SURFACES THAT HAVE BEEN DAMAGED OR ARE ADJACENT TO DEMOLISHED CONSTRUCTION. THE REPAIR SHALL INCLUDE, BUT NOT BE LIMITED TO: FILLING VOIDS SOLID WITH CONCRETE, PREPARING SURFACES FOR NEW FINISH MATERIAL PER MANUFACTURER'S RECOMMENDATIONS, MATCH EXISTING FINISHES AND MATERIALS WHERE NO NEW FINISHES ARE CALLED FOR, CLOSING WALL, FLOOR OR ROOF PENETRATIONS AS
DIRECTED BY THE ENGINEER.
15. ALL TAGGED DETAILS ARE TYPICAL FOR THE ITEM OR SYSTEM INDICATED. THE SCOPE OF WORK INDICATED AS PART OF THE TAG OR
DETAIL MARK SHALL APPLY TO ALL OTHER SIMILAR SYMBOLS OR ITEMS.
16. THE TERM "TYP." OR “TYPICAL” FOLLOWING A NOTE, TAG, OR DETAIL FLAG INDICATES THAT ALL LIKE, SIMILAR, OR INDICATED ITEMS
SHALL BE PROVIDED WITH THE SPECIFIED DETAIL, NOTE, OR SPECIFICATION.
17. ALL ITEMS ARE CONSIDERED TO BE NEW UNLESS SPECIFICALLY IDENTIFIED AS EXISTING.
18. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS INCLUDING BUT NOT LIMITED TO SQUARE FOOTAGES, LOCATIONS, QUANTITIES AND SIZES OF ALL ROOF TOP EQUIPMENT, VENT STACKS, SKYLIGHTS, GUTTERS, CONDUCTORS, DOWNSPOUTS, ETC.
PRIOR TO BIDDING. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, DO NOT SCALE DRAWINGS.
19. COMPLY WITH ALL APPLICABLE SMACNA DETAILS AND RECOMMENDATIONS.
20. ALL EXISTING ROOFING MATERIAL, FLASHING & COUNTER-FLASHING, ROOF RELIEF VENTS, MISC. WOOD BLOCKING, TERMINATION BARS, ETC., SHALL BE REMOVED IN THEIR ENTIRETY TO THE STRUCTURAL ROOF DECK TYPICAL FOR ALL NOTE NEW ROOF AREAS.
21. ALL ROOFS TO BE PITCHED 1/4" PER FOOT UNLESS NOTED OTHERWISE.
22. ALL BLOCKING TO BE FIRE RETARDANT WOOD BLOCKING, TYP. BLOCKING SHOWN ON DETAILS IS DIAGRAMMATIC. CONTRACTOR TO PROVIDE ALL BLOCKING AS NEEDED TO ACHIEVE REQUIRED MINIMUM HEIGHTS AND AS REQUIRED BY MANUFACTURER'S DETAILS.
23. ALL EXISTING WALL PENETRATIONS ARE TO BE PROPERLY FLASHED AND COUNTER FLASHED AS PER THE MANUFACTURER'S
RECOMMENDATIONS.
24. ALL JOINTS BETWEEN DISSIMILAR MATERIALS SHALL BE CAULKED. WHERE REQUIRED PROVIDE CLOSED CELL BACKER ROD AND CAULK.
WHERE DISSIMILAR MATERIALS COME INTO DIRECT CONTACT WITH EACH OTHER, PROVIDE A BOND BREAK.
25. ONCE ROOFING IS REMOVED CONTRACTOR SHALL INSPECT ROOF DECK AND NOTE ALL AREAS THAT REQUIRE REPAIR OR REPLACEMENT, UNLESS NOTED ON DRAWINGS AND/OR INFRARED SCANS AS BEING REQUIRED TO BE REPLACED. VERIFY WITH
ENGINEER PRIOR TO ANY WORK FOR SCOPE AND QUANTITY.
26. ALL UTILITY DISCONNECTS SHALL BE COORDINATED WITH THE OWNER AND UTILITY PROVIDER. THE CONTRACTOR SHALL NOTIFY THE
OWNER OF ANY REQUIRED DISCONNECT NO LESS THAN 72 HOURS IN ADVANCE.
27. THE REINSTALLATION OF EXISTING EQUIPMENT AND MISC. ACCESSORIES SHALL BE COORDINATED AS TO MINIMIZE THE POSSIBILITY OF DAMAGE CAUSED BY CONSTRUCTION ACTIVITIES. ALL REINSTALLED EQUIPMENT SHALL BE TESTED AFTER REINSTALLATION TO ENSURE
PROPER OPERATION.
28. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING ALL NECESSARY REPAIRS, MODIFICATIONS, ETC., IN ORDER TO REINSTALL ALL EQUIPMENT, VENTS, AIR-HANDLING UNITS, EXHAUST FANS, ETC. IN A WATERTIGHT CONDITION. TEST ALL EQUIPMENT PRIOR TO
SUBSTANTIAL COMPLETION TO VERIFY WATERTIGHT CONDITIONS EXIST.
29. ALL EQUIPMENT DISCONNECTS AND RECONNECTS OF MECHANICAL, PLUMBING, GAS, ELECTRICAL, AND REFRIGERANT SYSTEMS SHALL BE COMPLETED BY A TRADE CRAFTSMAN LICENSED IN THE RESPECTIVE TRADE AND IN ACCORDANCE WITH ALL APPLICABLE CODE AND
REGULATORY REQUIREMENTS.
30. ALL LOOSE LAID CABLES ARE TO BE BUNDLED AND TIED TO EXISTING ELECTRICAL CONDUIT RACEWAY. CONTRACTOR TO COORDINATE W/ OWNER AS TO WHETHER CABLES/WIRING ARE ACTIVE OR INACTIVE. IF CABLES/WIRING ARE INACTIVE CONTRACTOR SHALL
REMOVE CABLES/WIRING BACK TO NEAREST SOURCE PANEL. TYP.
31. CONTRACTOR TO PROVIDE NEW NAILERS AND BLOCKING. VERIFY HEIGHT REQUIRED.
32. ALL EXISTING ROOF DRAINS TO BE SNAKED OUT AND FREE FLOWING. CONTRACTOR SHALL INSPECT AND PERFORM A WATER TEST AS
PER SPECS. CONTRACTOR TO PROVIDE AND INSTALL NEW STRAINERS
33. AT COMPLETION OF JOB, CONTRACTOR SHALL LEAVE THE AREA DUST FREE AND CLEAN.
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text 05/27/26
AutoCAD SHX Text
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
A
2 3 4 5 6 7 8
B
C
D
D3
E
(E)DRY COOLERS
(N)CHILLER ON STEEL DUNNAGE
REFER TO MECHANICAL/STRUCTURAL DRAWINGS
UPPER ROOF
(E)ROOF DRAIN (TYP)
UPPER ROOF
UPPER ROOF
SEE NOTE 3
G-100
PROPOSED
OVERALL ROOF RESTORATION PLAN
AS NOTED
12/20/24
AIL
MA
WC
Revision History
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
0' 2' 4' 8'
SCALE BAR: 3/16" = 1'-0"
1 ROOF PLAN
SCALE: 3/16" = 1'-0"
N
BUILDING
NORTH
TRUE
NORTH
NOTES:
1. ALL ROOF AREAS SHOWN ARE TO RECEIVE NEW TPO OVERLAY
(RECOVER APPLICATION.
2. REFER TO SPECIFICATION SECTION 075423 AND SHEETS G-101 AND
G-102 FOR ADDITIONAL INFORMATION.
3. PREVIOUSLY IDENTIFIED AREAS OF WET INSULATION. ROOFING
CONTRACTOR SHALL PERFORM INFRARED SCAN/SURVEY TO IDENTIFY
ALL AREAS OF WET INSULATION TO BE REMOVED AND REPLACED, IN
ACCORDANCE WITH THE SPECIFICATIONS. REPLACE ONE FOOT
ADDITIONAL AREA BEYOND IDENTIFIED AREAS TO ENSURE NO
FURTHER MOISTURE HAS EXTENDED BEYOND THE AREAS IDENTIFIED.
PROVIDE UNIT PRICE FOR AND ADD OR DEDUCT OF 1SF OF WET
INSULATION REPAIR/REPLACEMENT.
4. BASE BID PRICE ASSUMES ALL DRAIN BOWL REPLACEMENT. THIS
WORK SHALL BE PERFORMED ON A UNIT PRICE BASIS ONLY AFTER
DETERMINATION BY ENGINEER THAT THE DRAIN BOWL IS DAMAGED.
CONTRACTOR SHALL INSPECT EACH DRAIN BOWL AND ADVISE
ENGINEER OF CONDITION.
ISSUED FOR BID05/27/260
EXISITING ROOF DRAIN
DAMAGED ROOF AREA TO BE REPLACED
APPROXIMATE ROOF AREAS:
1. BASE SCOPE (ROOF RESTORATION/OVERLAY): 10,700 SF
2. BASE SCOPE (WET INSULATION REPAIR): 350 SF
3. BASE SCOPE - ROOF DRAIN BOWL REPALCEMENT QTY: 13
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
TPO COATED METAL BASE FLASHING BUTT JOINT12
EXPANSION JOINT CURB13 PITCH POCKET DETAIL14 CURB FLASHING DETAIL15
HIGH TEMPERATURE PIPE FLASHING19
TWO - PIECE PIPE FLASHING18PREFABRICATED VENT PIPE FLASHING17CURB FLASHING DETAIL16
END LAP DETAIL20 CURB FLASHING USING TPO METAL21 EXPOSED SLEEPER22
1. ALL DETAILS ARE TO SHOW INTENT.
GENERAL NOTES:
COATED METAL ROOF EDGE DETAIL01
2. PRIME ALL METAL SURFACES BEFORE INSTALLATION
FOLLOW ALL MANUFACTURES REQUIREMENTS FOR
PROPER INSTALLATION.
SHOP FABRICATED EDGE w/EXTENDER02 SHOP-FABRICATED ROOF EDGE03 ROOF TO ROOF TRANSTION04
WALL EXPANSION JOINT FLASHING08WALL FLASHING07
REGLET METAL COUNTERFLASHING06PARAPET WALL FLASHING05
HIGH PARAPET WALL FLASHING09 PARAPET WALL FLASHING10 DRAIN DETAIL11
FIELD CONDITIONS SHALL DETERMINE IF DETAIL NEEDS TO BE
MODIFY FOR INSTALLATION.
FIXED EQUIPMENT SUPPORT24
3. AT THE DISCRETION OF THE OWNER, ALL UNUSED ROOF
PENETRATIONS SHALL BE
FIELD PATCHED IN-KIND WITH NEW INSULATION AND ROOF
MEMBRANE.
G-101
ROOF TPO DETAILS
AS NOTED
05/20/26
AIL
WC
WC
Revision History
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
AutoCAD SHX Text
MIN 1 1/2"
AutoCAD SHX Text
2" MAX
AutoCAD SHX Text
WELD
AutoCAD SHX Text
TPO MEMBRANE 6" STRIP
AutoCAD SHX Text
2" MAX. FOIL TAPE COVERING
AutoCAD SHX Text
ENTIRE LENGTH OF METAL JOINT
AutoCAD SHX Text
TPO COATED METAL
AutoCAD SHX Text
EXTEND 6" STRIP
AutoCAD SHX Text
OF TPA METAL
AutoCAD SHX Text
1/8" MIN.
AutoCAD SHX Text
1/4" MAX.
AutoCAD SHX Text 4"
AutoCAD SHX Text
BEYOND EDGE
AutoCAD SHX Text A
AutoCAD SHX Text
TURN ENDS DOWN 45 ANGLE
AutoCAD SHX Text
%%U SECTION A-A
AutoCAD SHX Text
OVER EXPANSION JOINT
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
TPO FB MEMBRANE
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
8" MIN.
AutoCAD SHX Text
ROOF INSULATION
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
FULLY ADHERED
AutoCAD SHX Text
TPO PLATES & SCREWS
AutoCAD SHX Text
COMPRESSIBLE INSULATION
AutoCAD SHX Text
FLEXIBLE MEMBRANE DRAPED
AutoCAD SHX Text
FASTEN AT 18" O.C. WITH
AutoCAD SHX Text
NEOPRENE GASKETED FASTENERS
AutoCAD SHX Text
TREATED WOOD BLOCKING
AutoCAD SHX Text
INSULATION RETAINER
AutoCAD SHX Text
TO HOLD INORGANIC
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text 1"
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
2. ALLOW 2" MINIMUM CLEARANCE AROUND THE PROJECTION.
AutoCAD SHX Text
1. USE TPO COATED METAL TO FORM PITCH PAN.
AutoCAD SHX Text
3. TPO PREFABRICATED CORNERS MUST BE USED AT ALL 4 CORNERS
AutoCAD SHX Text
4" FLANGE WITH
AutoCAD SHX Text
TPO MEMBR.
AutoCAD SHX Text
HEMMED EDGE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
TPO PREFAB CORNER
AutoCAD SHX Text
TPO COATED METAL
AutoCAD SHX Text
NON-SHRINK GROUT
AutoCAD SHX Text
SPECIFIED SEALANT
AutoCAD SHX Text
AND DRAWBAND
AutoCAD SHX Text
PITCH PAN SEALANT
AutoCAD SHX Text
METAL HOOD
AutoCAD SHX Text %%uNOTES:
AutoCAD SHX Text
HEAT WELDED
AutoCAD SHX Text
FASTENED 4" O.C.
AutoCAD SHX Text
SPECIFIED SEALANT TOOLED NEATLY
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
TF TAPE
AutoCAD SHX Text
TERMINATION BAR FASTENED 8" O.C.
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
FULLY ADHERED TO SUBSTRATE
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
METAL CURB COUNTERFLASHING
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
1. ALL FLASHING SHALL BE A MINIMUM OF 8" HIGH.
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
FASTENERS
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
FOLD FLASHING OVER CURB AND
AutoCAD SHX Text
FASTEN 8" O.C. WITH SPECIFIED
AutoCAD SHX Text
TPO UNIVERSAL CORNER
AutoCAD SHX Text NOTES: 1. USE THIS DETAIL WHEN COUNTERFLASHING IS PART OF THE CURB MOUNTED EQUIPMENT. 2. USE THE SPECIFIED FASTENERS AND PLATE AROUND THE CURB PER WRITTEN SPECIFICATIONS
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
VENT STACK
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
TPO APPROVED SEALANT
AutoCAD SHX Text
STAINLESS STEEL CLAMP
AutoCAD SHX Text
TPO ONE PIECE BOOT
AutoCAD SHX Text NOTES: 1. DO NOT CUT PREFABRICATED BOOT. IT MUST BE PULLED OVER VENT PIPE. 2. PREFABRICATED BOOTS ARE AVAILABLE IN SMALL & LARGE SIZES, AND MUST BE USED WHENEVER POSSIBLE TO FLASH PIPES 1" TO 8" IN DIAMETER.
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text
NOTES: 1. THIS DETAIL TO BE USED WHEN TEMPERATURE OF STACK EXCEEDS 140°F.
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
TPO BONDING ADHESIVE
AutoCAD SHX Text
TPO UNREINFORCED
AutoCAD SHX Text
STAINLESS STEEL CLAMP
AutoCAD SHX Text
TREMSEAL SEALANT
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
PIPE SUPPORT
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
TPO BONDING ADHESIVE
AutoCAD SHX Text
MEMBRANE
AutoCAD SHX Text
SPECIFIED TPO
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
22 GA. GALV. PAN
AutoCAD SHX Text
STAINLESS STEEL CLAMP
AutoCAD SHX Text
HIGH TEMP SEALANT
AutoCAD SHX Text
RAIN HOOD
AutoCAD SHX Text
PIPE STACK
AutoCAD SHX Text
HIGH TEMPERATURE
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
STAGGERED 1"
AutoCAD SHX Text
TPO MEMBRANE STRIP
AutoCAD SHX Text
TREATED WOOD NAILER
AutoCAD SHX Text
HEAT WELDED LAPS
AutoCAD SHX Text
MECHANICALLY ATTACH 4" O.C.
AutoCAD SHX Text
1" CANT OPTIONAL
AutoCAD SHX Text
TPO COATED METAL
AutoCAD SHX Text
CURB COUNTERFLASHING
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
TPO MEMBRANE STRIP 6" WIDE
AutoCAD SHX Text
6" MIN.
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SECTION A-A
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
ROUND ALL CORNERS
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
HEAT WELDED LAPS
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
8" MIN.
AutoCAD SHX Text
TREATED WOOD BLOCKING
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
TREATED WOOD NAILER
AutoCAD SHX Text
UNDER BLOCKING
AutoCAD SHX Text
TPO MEMBRANE CONTINUOUS
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text 2)
AutoCAD SHX Text 1)
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
TPO FLEECE BACKED MEMBRANE
AutoCAD SHX Text
CONTINUOUS CLEAT FASTENED 16" O.C.
AutoCAD SHX Text
TPO COATED METAL DRIP EDGE
AutoCAD SHX Text
WITH HEMMED EGDE
AutoCAD SHX Text
TPO MEMBRANE STRIP
AutoCAD SHX Text
HEAT WELDED LAPS
AutoCAD SHX Text
MECHANICALLY ATTACH 4" O.C.
AutoCAD SHX Text
MECHANICALLY ATTACH WOOD BLOCKING
AutoCAD SHX Text
MAX. FACE DIMENSION SHOULD BE 5" TO PREVENT DISTORTION FROM
AutoCAD SHX Text
"OIL CANNING." IF SURFACE DISTORTION IS ACCEPTABLE, FACE
AutoCAD SHX Text
DIMENSION MAY BE INCREASED TO 8".
AutoCAD SHX Text
FOR FASCIAS GREATER THAN 8" INSTALL IN TWO SECTIONS.
AutoCAD SHX Text
HEAT WELDED LAPS
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
COPING CAP
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
CONTINUOUS CLEAT FASTENED 16 " O.C.
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
FULLY ADHERED TO SUBSTRATE
AutoCAD SHX Text
WITH TPO BONDING ADHESIVE
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
NEOPRENE GASKETED FASTENER @ 24 O.C.
AutoCAD SHX Text %%uNOTES:
AutoCAD SHX Text
1. THIS DETAIL TO BE USED WHEN TEMPERATURE OF STACK EXCEEDS 140%%DF.
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
TF TAPE
AutoCAD SHX Text 1)
AutoCAD SHX Text
%%UNOTE:
AutoCAD SHX Text
FLASHING MUST BE A MINIMUM OF 8" HIGH.
AutoCAD SHX Text
PRESSURE BAR FASTENED @ 8"O.C.
AutoCAD SHX Text
DO NOT COVER OR BLOCK WEEP HOLES WITH FLASHING OR SEALANT.
AutoCAD SHX Text
APPROVED SEALANT TOOLED NEATLY
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
WITH TPO BONDING ADHESIVE
AutoCAD SHX Text
FULLY ADHERED TO SUBSTRATE
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
WITH TPO BONDING ADHESIVE
AutoCAD SHX Text
FULLY ADHERED TO SUBSTRATE
AutoCAD SHX Text
PRESSURE BAR FASTENED @ 8"O.C.
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
SURFACE MOUNTED COUNTERFLASHIING
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
FASTENED 8'' O.C. MINIMUM
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
SPECIFIED SEALANT
AutoCAD SHX Text
SPECIFIED SEALANT
AutoCAD SHX Text
TF TAPE
AutoCAD SHX Text
TF TAPE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
TPO WALL FLASHING
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
CLOSED CELL FOAM BACKER ROD
AutoCAD SHX Text
TREATED WOOD NAILER
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
TPO MEMBRANE ADHERED IN
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
ROOF INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
AS A RETAINER
AutoCAD SHX Text
WITHIN A FLEXIBLE SHEET
AutoCAD SHX Text
COMPRESSIBLE INSULATION
AutoCAD SHX Text NOTES: 1) WOOD NAILER SECURED TO THE DECK PER FACTORY MUTUAL LOSS PREVENTION DATA I-49.
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (AS SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
SEE SPECIFIC WALL TERMINATION
AutoCAD SHX Text
36" MAX.
AutoCAD SHX Text
TPO FASTENERS 12" O.C.
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
18" MAX.
AutoCAD SHX Text
18" MAX.
AutoCAD SHX Text
SEE SPECIFIC WALL TERMINATION
AutoCAD SHX Text
TPO ALUM. BAR OR PLATES &
AutoCAD SHX Text
SCREWS FASTENED 8" O.C.
AutoCAD SHX Text
HEAT WELDED LAPS
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
TPO FASTENERS 12" O.C.
AutoCAD SHX Text
TPO FLASHING MEMBRANE
AutoCAD SHX Text
SPECIFIED BONDING ADHESIVE
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
INSULATION (AS SPECIFIED)
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
36" MAX.
AutoCAD SHX Text
INSULATION (AS SPECIFIED)
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
4. ALL METAL SURFACES SHALL BE PRIMED BEFORE CONTACT
AutoCAD SHX Text
TPO BONDING ADHESIVE
AutoCAD SHX Text
TPO FLEECE BACKED MEMBRANE
AutoCAD SHX Text
3. FIELD WELD MUST NOT PASS UNDER THE CLAMPING RING.
AutoCAD SHX Text
2. MEMBRANE MUST EXTEND MINIMUM 1" BEYOND THE BOLT HOLES.
AutoCAD SHX Text
1. THIS TWO PIECE DESIGN MUST BE USED WHEN INSTALLING THE
AutoCAD SHX Text
TPO UNREINFORCED MEMBRANE
AutoCAD SHX Text
TREMFAST WATERBLOCK SEALANT
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
WITH ANY ADHESIVE OR MASTIC.
AutoCAD SHX Text
3. THE CLAMPING RING MUST PENETRATE THE MEMBRANE.
AutoCAD SHX Text
TPA FLEECE BACKED MEMBRANE.
AutoCAD SHX Text %%uNOTES:
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
DRAIN CLAMP RING
AutoCAD SHX Text
DRAIN
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text
SPECIFED ROOF DECK
AutoCAD SHX Text
INSTALL TF TAPE UNDER CLEAT FLANGE
AutoCAD SHX Text
NEW WOOD BLOCKING PER SPECIFICATIONS
AutoCAD SHX Text
TPO SPECIFIED MEMBRANE MECHANICALLY
AutoCAD SHX Text
SPECIFIED TPO METAL CONTINUOUS CLEAT FASTENED
AutoCAD SHX Text
12" O.C. WITH APPROVED FASTENERS
AutoCAD SHX Text
NEW SHOP FABERICATED GRAVEL STOP
AutoCAD SHX Text
SPECIFED INSULATION
AutoCAD SHX Text
FASTENED TO SUBSTRATE
AutoCAD SHX Text
SHOP FABERICATED ROOF EDGE MAY BE SUBMITTED AS AN ALTERNATE FOR APPROVAL
AutoCAD SHX Text
MUST BE A 2 PIECE SYSTEM MADE OUT OF TREMCO METAL.
AutoCAD SHX Text 1 3/4"
AutoCAD SHX Text 8 3/8"
AutoCAD SHX Text 11 1/2"
AutoCAD SHX Text
HAND CRIMP
AutoCAD SHX Text STIFFNERS REQUIRED TO PERVENT OIL CANNING UNLESS 22 GAGE OR 20 GAGE METAL IS USED
AutoCAD SHX Text
HAND CRIMP
AutoCAD SHX Text
TPO FLASHING
AutoCAD SHX Text
24 GAGE METAL
AutoCAD SHX Text
TPO METAL USED AS NEW CLEAT
AutoCAD SHX Text
HOT AIR WELD
AutoCAD SHX Text
HOT AIR WELD PER SPECIFICATIONS
AutoCAD SHX Text
SPECIFIED FASTENER AND PLATE
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
SPECIFIED ADHESIVE
AutoCAD SHX Text 1)
AutoCAD SHX Text
HEAT WELDED LAP
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
EQUIPMENT SUPPORT BRACKET
AutoCAD SHX Text
TPO APPROVED SEALANT
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
SLEEPER HEIGHT SHOULD BE SUFFICIENT TO ELEVATE THE
AutoCAD SHX Text
EQUIPMENT SUPPORT BRACKET ABOVE THE WATER LEVEL.
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text 05/27/26
AutoCAD SHX Text
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
MULTIPLE PIPE PENETRATION DETAIL25 T-JOINT DETAIL26 WALK-PAD INSTALLATION27 METAL WALL PANEL SYSTEM30GAGE OR THICKNESS GUIDE (MINIMUM)29DAILY WATERSTOP/TIE-IN28
NEW THROUGH-WALL COUNTERFLASHING DETAIL32
4" MIN
CONTRACTOR FABRICATED
UNLESS OTHERWISE SPECIFIED.
ALL TRIMS TO BE
NOTE:
1.
BASE FLASHING AS SPECIFIED
TWO PIECE COUNTERFLASHING
EXISTING METAL PARAPET COVER
BASE TRIM
WALL PANEL
STEEL (MAX. SPACING 3' O.C.)
SUBGIRT MIN. 22 GA. GALVANIZED
24 GA. FLASHING WITH HEM
DETAIL - NOT USED31 DETAIL - NOT USED33
1. ALL DETAILS ARE TO SHOW INTENT.
GENERAL NOTES:
2. PRIME ALL METAL SURFACES BEFORE INSTALLATION
FOLLOW ALL MANUFACTURES REQUIREMENTS FOR
PROPER INSTALLATION.
FIELD CONDITIONS SHALL DETERMINE IF DETAIL NEEDS TO BE
MODIFY FOR INSTALLATION.
G-102
ROOF TPO DETAILS
AS NOTED
05/20/26
AIL
WC
WC
Revision History
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
AutoCAD SHX Text
SLOPE PIPES DOWN
AutoCAD SHX Text
AND AWAY FROM HOOD
AutoCAD SHX Text
FASTENERS 8'' O.C.
AutoCAD SHX Text
SHEET METAL COLLAR
AutoCAD SHX Text
INSULATE INSIDE OF
AutoCAD SHX Text
METAL WORK IN COLD
AutoCAD SHX Text
CLIMATES
AutoCAD SHX Text
SHEET METAL HOOD CROSS
AutoCAD SHX Text
BREAK OR SLOPE FOR
AutoCAD SHX Text
DRAINAGE
AutoCAD SHX Text
TPO UNIVERSAL CORNER
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
METAL SCREW
AutoCAD SHX Text
CLOSURE DETAIL
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
MECHANICALLY ATTACH TPO
AutoCAD SHX Text
COATED METAL FLANGE TO
AutoCAD SHX Text
NAILER WITH SPECIFIED
AutoCAD SHX Text
FASTENERS 4" O.C.
AutoCAD SHX Text
HEAT WELD TPO MEMBRANE
AutoCAD SHX Text
FLASHING TO TPO COATED
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
WITH SPECIFIED
AutoCAD SHX Text
SECURED TO DECK
AutoCAD SHX Text
WOOD NAILER
AutoCAD SHX Text
FASTENERS PER
AutoCAD SHX Text
FM I-49
AutoCAD SHX Text
METAL FLANGE
AutoCAD SHX Text
SPECIFIED TPO MEMBRANE
AutoCAD SHX Text
SPECIFIED ROOF DECK
AutoCAD SHX Text NOTE: HEAT-WELD A 4" ROUND FIELD CUT TPO FLASHING MEMBRANE(UNREINFORCED). CENTER THE FLASHING OVER EACH T-JOINT ON A 60-MIL THICK OR GREATER MEMBRANE (AS SHOWN).
AutoCAD SHX Text
MINIMUM 18''
AutoCAD SHX Text
INSULATION (WHERE SPECIFIED)
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
FEILD CUT TPO FLASHING
AutoCAD SHX Text
SEE NOTE THIS SHEET
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
TPO WALK PAD HEAT WELDED IN PLACE
AutoCAD SHX Text
ALL 4 SIDES. DO NOT CROSS FIELD SEAMS.
AutoCAD SHX Text
START AND STOP WALK PAD INSTALLATION
AutoCAD SHX Text
2" FROM FIELD SEAM.
AutoCAD SHX Text
ROOF DECK
AutoCAD SHX Text
HEAT WELDED OUTSIDE EDGE
AutoCAD SHX Text
FEILD SEAM
AutoCAD SHX Text
TPO MEMBRANE
AutoCAD SHX Text
TPO WALK PAD
AutoCAD SHX Text
ROOFING 12'' ONTO
AutoCAD SHX Text
GALVANIZED IRON
AutoCAD SHX Text
12'' AND 18'' PLY
AutoCAD SHX Text
REMOVE EMBEDDED
AutoCAD SHX Text
GRAVEL / DEBRIS
AutoCAD SHX Text
SHEETS ADHERED
AutoCAD SHX Text
NEW ROOFING
AutoCAD SHX Text
IN SPECIFIED
AutoCAD SHX Text
ADHESIVE
AutoCAD SHX Text
10'' TO 15'' FACE
AutoCAD SHX Text
8'' TO 10'' FACE
AutoCAD SHX Text
UP TO 6'' FACE
AutoCAD SHX Text
6'' TO 8'' FACE
AutoCAD SHX Text
WITHOUT BRAKES
AutoCAD SHX Text
EXPOSED FACE
AutoCAD SHX Text
''A'' DIMENSIONS
AutoCAD SHX Text
REINFORCING MESH
AutoCAD SHX Text
AND SPECIFIED
AutoCAD SHX Text
SEAL EDGE WITH
AutoCAD SHX Text
PREPARED AREA
AutoCAD SHX Text
MASTIC
AutoCAD SHX Text
COPING
AutoCAD SHX Text A
AutoCAD SHX Text
22 GA.
AutoCAD SHX Text
20 GA.
AutoCAD SHX Text
24 GA.
AutoCAD SHX Text
24 GA.
AutoCAD SHX Text
20 OZ.
AutoCAD SHX Text
ADD BRAKES
AutoCAD SHX Text
TO STIFFEN
AutoCAD SHX Text
16 OZ.
AutoCAD SHX Text
16 OZ.
AutoCAD SHX Text
COLD ROLLED
AutoCAD SHX Text
COPPER
AutoCAD SHX Text
.064'' (14 GA.)
AutoCAD SHX Text
.080'' (12 GA.)
AutoCAD SHX Text
.050'' (16 GA.)
AutoCAD SHX Text
.040'' (18 GA.)
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text 3003-H14
AutoCAD SHX Text
CAP FLASHING
AutoCAD SHX Text
AND FASCIA
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
VARIATIONS
AutoCAD SHX Text
EXISTING ROOFING
AutoCAD SHX Text
EXTEND NEW
AutoCAD SHX Text
%%UAT BOTTOM OF BASE TRIM
AutoCAD SHX Text
%%U SUBGIRT PLACEMENT
AutoCAD SHX Text WORK INCLUDES REMOVAL OF APPROXIMATELY FOUR COURSES OF BRICK AT HIGH MASONRY WALLS; INSTALLING NEW LEAD COATED COPPER FLASHINGS AND NEW BRICK MASONRY UNITS WITH WEEP SLOTS AND INSECT SCREENS. FLASHING WORK SHALL INCLUDE END DAMS, CORNER DETAILS, BITUTHENE WTAERPROOFING MEMBRANE AND PROPER TREATMENT OF PENETRATIONS AND INTRUSIONS TO PROVIDE A WATERTIGHT FLASHING SYSTEM.
AutoCAD SHX Text %%uNOTE:
AutoCAD SHX Text 1.
AutoCAD SHX Text WHEN REGLET JOINT INSTALLATION IS NOT APPLICABLE, SECURE TOP EDGE OF FLASHING TO INSIDE WALL WITH MASONRY FASTENERS AND STRIP-IN TOP EDGE OF METAL WITH MINIMUM 3" WIDE BITUTHANE MEMBRANE.
AutoCAD SHX Text 2.
AutoCAD SHX Text
SPECIFED INSULATION
AutoCAD SHX Text
TPO MEMBRANE IN SPECIFIED ADHESIVE
AutoCAD SHX Text
SPECIFIED TERMINATION
AutoCAD SHX Text SET TOP EDGE OF METAL IN REGLET AND SECURE WITH LEAD WEDGES. INSTALL BACKING ROD AND CAULK JOINT (SEE NOTE #2 BELOW).
AutoCAD SHX Text
INSTALL SELF-ADHERING BITUTHENE MEMBRANE BETWEEN WALL AND METAL SHEET.
AutoCAD SHX Text
SPECIFIED BASE FLASHING
AutoCAD SHX Text
TWO PIECE COUNTERFLASHING INSTALLED INTO RECEIVER 3'' OVERLAP AT JOINTS
AutoCAD SHX Text INSTALL NEW LEAD COATED SPECIFIED METAL FLASHINGS WITH SOLDERED JOINTS & END DAMS.
AutoCAD SHX Text
INSTALL NEW BRICK MASONRY WITH WEEP SLOTS & INSECT SCREENS INSTALLED 24" O.C.
AutoCAD SHX Text
OPTIONAL 2'' WIDE CLIP
AutoCAD SHX Text
ROOF DECK AS SPECIFIED
AutoCAD SHX Text
SPECIFIED SEALANT
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text 05/27/26
AutoCAD SHX Text
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
3 4 5
MECHANICAL
AIR HANDLING
20'-0" 20'-0" 20'-0"
DUCT SPACE
DARK RM.
PASSAGE
UNFINISHED AREA
P-3 P-4
AH-1
B-1
B-2
B-3
WC-1(R)
P-1(R) P-2(R)
P-3 P-4
P-5(R) P-6(R)
AS(R)
AH-1
B-1
B-2
B-3
ET(R)
DM-300
DM-300
2DM-300
DM-300
DM-301
DM-301
DM-301
DM-301
DM-302
DM-302
DM-302
ELECTRICAL
PANEL(R)
CHEM
FEED(R)
A
B
C
5 6
20'-0" 20'-0"
CT-1(R)
DM-302
DM-303
DM-303
DM-303
A
B
C
DG-200
DEMOLITION
PARTIAL PLANS
AS NOTED
12/20/24
AIL
MA
WC
Revision History
William T. Conley (NJ)
24GE04587200
Seal
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
0'
SCALE BAR: 1/4" = 1'-0"
4'2' 8'
DEMOLITION
PARTIAL BASEMENT PLAN
SCALE: 1/4" = 1'-0"
N
BUILDING
NORTH
TRUE
NORTH
TO BE DEMOLISHED OR RELOCATED
LEGEND:
BASEMENT KEY PLAN ROOF KEY PLAN
0'
SCALE BAR: 1/4" = 1'-0"
4'2' 8'
DEMOLITION
PARTIAL ROOF PLAN
SCALE: 1/4" = 1'-0"
ISSUED FOR BID05/27/260
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text Name:
AutoCAD SHX Text Date:
AutoCAD SHX Text Signed:
AutoCAD SHX Text License#:
AutoCAD SHX Text I hereby certify that this document was prepared by me or under my direct supervision and that I am a duly registered Professional Engineer under the laws of the State of New Jersey.
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Appv'd by:
2 3 4 5 6 7 8
MECHANICAL
AIR HANDLING
19'-11 1/2" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 19'-11 1/2"
'-3
/2
'-4
'-4
9'
-0
'-1
1/
2"
STORAGE
PASSAGE
PAPER STORAGE
PRINT SHOP
PRINT SHOP
A
B
C
D
D3
E
OFFICE
GENERAL OFFICE
06PUBLIC ELEV'R LOBBY
01WOMEN
MEN
CUST'N,
DUCT SPACE
CORRIDOR
DARK RM.
PHOTO LAB
PASSAGE
UNFINISHED AREA
TELE. EQUIP.
UNFINISHED AREA
LUNCH ROOM
P-3 P-4
AH-1
B-1
B-2
B-3
P-1
P-2
P-3 P-4
ET-1
AH-1
B-1
B-2
B-3
GMU-1
CF-1
AS-1
FCU-6
FCU-7
FCU-7
FCU-3
FCU-3
FCU-3
FCU-3
FCU-3
FCU-3FCU-3
FCU-6
FCU-6
FCU-6
FCU-6
NEW CONCRETE PAD
(E)AHU, REFER TO SPECIFICATION 237313
FOR AHU REFURBISHMENT
SCOPE OF WORK
G-200
PROPOSED BASEMENT PLAN
AS NOTED
12/20/24
AIL
MA
WC
Revision History
William T. Conley (NJ)
24GE04587200
Seal
24" x 36"
Project
RevDrawing Number
THESE DRAWINGS ARE THE PROPERTY OF DCO ENERGY AND
ITS AFFILIATES AND MAY NOT BE DUPLICATED, USED OR
DISCLOSED WITHOUT WRITTEN CONSENT OF DCO ENERGY.
ALL RIGHTS RESERVED.
Drawing Title
35-468
OCEAN COUNTY ADMINISTRATION
BUILDING HVAC AND ROOFING UPGRADES
CLIENT
101 Hooper Avenue Toms River, NJ 08753
RE
SE
RV
ED
A
RE
A
FO
R N
JD
CA
AP
PR
O
VA
L
ST
AM
P
AR
EA
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
CONTRACTOR
DCO
ENERGY
5429 Harding Highway Bldg. 500
Mays Landing, NJ 08330
EOR
DCO
ENGINEERING SERVICES
8'
SCALE BAR: 1/8" = 1'-0"
4'0' 16'
1 PROPOSED BASEMENT PLAN
SCALE: 1/8" = 1'-0"
N
BUILDING
NORTH
TRUE
NORTH
FAN COIL UNIT
LEGEND:
ISSUED FOR BID05/27/260
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Description
AutoCAD SHX Text Name:
AutoCAD SHX Text Date:
AutoCAD SHX Text Signed:
AutoCAD SHX Text License#:
AutoCAD SHX Text I hereby certify that this document was prepared by me or under my direct supervision and that I am a duly registered Professional Engineer under the laws of the State of New Jersey.
AutoCAD SHX Text Size:
AutoCAD SHX Text Check by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Proj.#:
AutoCAD SHX Text Scale:
AutoCAD SHX Text…