P683 Amendment 0003 Specs.pdf
PDF 500 KB Posted
- Solicitation number
- N6945026R0005
About this file
This is Amendment 0003 to the P-683 Engine Repair Facility specification document, which establishes technical requirements for a Design-Bid-Build firm-fixed-price construction project at Naval Air Station Jacksonville, Florida.
The amendment revises specifications across multiple construction sections, including door hardware (Section 08 71 00), folding panel partitions (Section 10 22 39), bird control devices (Section 10 81 13), and relocatable building units with sitework (Section 13 34 23.12 10). Key specification changes include updated standards references for hardware components such as hinges, locks, exit devices, and closers complying with ANSI/BHMA standards; deletion of original folding panel partition specifications with new requirements for manual operation acoustical folding partitions achieving STC ratings of 50 or greater; addition of bird control specifications requiring Type 316 stainless steel wire mesh barriers and bird spikes with 10 to 20-year warranties; and comprehensive specifications for relocatable building units (RLB Type A) including structural, electrical, mechanical, plumbing, and fire protection requirements. The RLB specifications require non-combustible construction with 84-inch minimum clear ceiling height, R-11+ floor insulation, R-20+ wall insulation, and R-40 roof insulation; HVAC units with SEER 16 or greater; compliance with UFC 1-201-01 and NFPA codes; and a minimum 15-year service life with capability for three additional deployments. Submittals require government approval for structural, electrical, mechanical, and fire protection designer qualifications; manufacturers' certifications; shop drawings; product data; test reports; and operation and maintenance manuals. Warranties must include manufacturer coverage for five years minimum on all systems and installer coverage for installation workmanship and structural leveling.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-683 Engine Repair Facility 1817922
SECTION 01 11 00
SUMMARY OF WORK
02/24
Revised by Amendment 0003
PART 1 GENERAL
1.1 SUBMITTALS
Government approval is required for submittals with a "G" classification.
Submittals not having a "G" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Salvage Plan ; G
1.2 WORK COVERED BY CONTRACT DOCUMENTS
1.2.1 Project Description
The work includes demolition of two existing administration buildings (6F & 6G), construction of an approximately 300,000 GSF one-story engine repair facility with associated 20,000 GSF two-story support/office and administration area, a 5-story Parking Garage, two surface parking lots,a 1.34-acre temporary gravel parking lot (150 parking spaces), a 3.24-acre asphalt paved parking lot (288 spaces), swing space ( SECTION 13 34 23) and incidental related work.
The project area has a history of development. Undercutting of insitu soils is anticipated to remove unsatisfactory soil and other materials (i.e., rubble, buried building strip footings). Satisfactory and unsatisfactory materials are as defined in 31 00 00 EARTHWORK. Lump sum base bid shall include the undercutting and disposal of unsatisfactory material and replacement of 150 square yards to an average depth of 4-feet. Replacement material is required to meet the definition of structural fill and compacted in accordance with the requirements of 31 00 00 EARTHWORK. Undercutting and replacement more than this quantity requires the approval of the Contracting Officer, considered a change order, and paid at a unit rate commensurate to the lump sum base bid.
1.2.2 Location
The work is located at the SW quadrant of Enterprise Ave and Ranger St. at NAS Jacksonville, FL , approximately as indicated. The exact location will be shown by the Contracting Officer.
1.3 EXISTING WORK
Remove or alter existing work in such a manner as to prevent injury or damage to any portions of the existing work which remain.
Repair or replace portions of existing work which have been altered during construction operations to match existing or adjoining work, as approved by the Contracting Officer. At the completion of operations, existing work must be in a condition equal to or better than that which existed
SECTION 01 11 00 Page 1
AMENDMENT 0003
before new work started.
1.4 LOCATION OF UNDERGROUND UTILITIES
Obtain digging permits prior to start of excavation, and comply with Installation requirements for locating and marking underground utilities.
Contact Requirements Branch at 904-542-5542 a minimum of two weeks prior to excavating, to mark utilities, and within sufficient time required if work occurs on a Monday or after a Holiday. Verify existing utility locations indicated on contract drawings, within area of work.
Identify and mark all other utilities not managed and located by the local utility companies. Scan the construction site with Ground Penetrating Radar (GPR), electromagnetic, or sonic equipment, and mark the surface of the ground or paved surface where existing underground utilities are discovered. Verify the elevations of existing piping, utilities,and any type of underground or encased obstruction not indicated, or specified to be removed, that is indicated or discovered during scanning, in locations to be traversed by piping, ducts, and other work to be conducted or installed. Verify elevations before installing new work closer than nearest manhole or other structure at which an adjustment in grade can be made.
1.4.1 Notification Prior to Excavation
Notify the Contracting Officer at least 1 4 days prior to starting excavation work.
1.5 GOVERNMENT-INSTALLED WORK
Specialty Equipment that is GFGI will be installed after final acceptance of the facility.
1.6 NAVY AND MARINE CORPS INTRANET (NMCI) COORDINATION REQUIREMENTS
1.6.1 NMCI Contractor Access
Allow the NMCI Contractor access to the facility towards the end of construction (finishes 90 percent complete, rough-in 100 percent complete, Inside Plant (ISP)/Outside Plant (OSP) infrastructure in place) to provide equipment in the telecommunications rooms and make final connections.
Coordinate efforts with the NMCI Contractor to facilitate joint use of building spaces during the final phases of construction. After the Contracting Officer has facilitated coordination meetings between the two contractors, within one week, incorporate the effort of additional coordination with the NMCI Contractor into the construction schedule to demonstrate a plan for maintaining the contract duration.
1.7 SALVAGE MATERIAL AND EQUIPMENT
Items designated by the Contracting Officer to be salvaged remain the property of the Government. Segregate, itemize, deliver and off-load the salvaged property at the Government designated storage area located within 3 miles of the construction site.
Provide a salvage plan , listing material and equipment to be salvaged, and their storage location. Maintain property control records for material or equipment designated as salvage. Provide a system for property control in the salvage plan. Store and protect salvaged materials and equipment
SECTION 01 11 00 Page 2 until disposition by the Contracting Officer.
PART 2 PRODUCTS
Not used.
PART 3 EXECUTION
Not used.
-- End of Section --
SECTION 01 11 00 Page 3
SECTION 08 71 00
DOOR HARDWARE
02/16, CHG 4: 02/22
Revised by Amendment 0003
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E283 (2019) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM F883 (2013; R 2022) Standard Performance Specification for Padlocks
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.1 (2021) Butts and Hinges
ANSI/BHMA A156.2 (2022) Bored and Preassembled Locks and Latches
ANSI/BHMA A156.3 (2020) Exit Devices
ANSI/BHMA A156.4 (2024) Door Controls - Closers
ANSI/BHMA A156.5 (2020) Cylinder and Input Devices for Locks
ANSI/BHMA A156.6 (2021) Architectural Door Trim
ANSI/BHMA A156.7 (2016) Template Hinge Dimensions
ANSI/BHMA A156.8 (2021) Door Controls - Overhead Stops and Holders
ANSI/BHMA A156.10 (2024) Power Operated Pedestrian Doors
ANSI/BHMA A156.13 (2022) Mortise Locks & Latches Series 1000
ANSI/BHMA A156.15 (2021) Release Devices Closer Holder, Electromagnetic and Electromechanical
ANSI/BHMA A156.16 (2023) Auxiliary Hardware
ANSI/BHMA A156.18 (2020) Materials and Finishes
ANSI/BHMA A156.19 (2013) Power Assist & Low Energy Power Operated Doors
SECTION 08 71 00 Page 1
ANSI/BHMA A156.21 (2019) Thresholds
ANSI/BHMA A156.22 (2021) Gasketing
ANSI/BHMA A156.23 (2010) Electromagnetic Locks
ANSI/BHMA A156.24 (2012) Delayed Egress Locking Systems
ANSI/BHMA A156.25 (2013) Electrified Locking Devices
ANSI/BHMA A156.26 (2012) Continuous Hinges
ANSI/BHMA A156.29 (2012) Exit Locks, Exit Alarms, Alarms for Exit Devices
ANSI/BHMA A156.30 (2014) High Security Cylinders
ANSI/BHMA A156.31 (2013) Electric Strikes and Frame Mounted Actuators
ANSI/BHMA A156.36 (2010) Auxiliary Locks
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 1 2024; TIA 24-1; TIA 25-2)
National Electrical Code
NFPA 72 (2022; ERTA 22-1) National Fire Alarm and Signaling Code
NFPA 80 (2025) Standard for Fire Doors and Other Opening Protectives
NFPA 101 (2024) Life Safety Code
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR A250.8 (2023) Specifications for Standard Steel Doors and Frames
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL Bld Mat Dir (updated continuously online) Building Materials Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" classification.
SECTION 08 71 00 Page 2
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in accordance with section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Manufacturer's Detail Drawings ; G
Verification of Existing Conditions ; G
Hardware Schedule ; G
Keying System ; G
SD-03 Product Data
Hardware Items ; G
SD-08 Manufacturer's Instructions
Installation
SD-10 Operation and Maintenance Data
Hardware Schedule Items, Data Package 1; G
SD-11 Closeout Submittals
Key Bitting
1.3 SHOP DRAWINGS
Submit manufacturer's detail drawings indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware. Base shop drawings on verified field measurements and include verification of existing conditions .
1.4 PRODUCT DATA
Indicate fire-ratings at applicable components. Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.
1.5 HARDWARE SCHEDULE
Provide Hardware Item List and Hardware Schedule containing the following information, and additional information as needed to identify the complete make up of each hardware set and its application to each opening:
1.5.1 Hardware Item List:
a. Hardware Type
b. Item Number
SECTION 08 71 00 Page 3
c. Quantity
d. Size(s)
e. Reference Publication / Type Number
f. Manufacturer's Name / Catalog Number
g. Key Control Symbols
h. UL Mark (If fire rated and listed)
i. BHMA Finish(es)
j. Remarks
1.5.2 Hardware Schedule
a. Hardware Set Number
b. Opening Number(s)
c. Opening Description (single/double leaf, hand, size, door/frame material)
d. Fire Rating
e. Sound Rating
f. Hardware Items
g. Quantity
h. Size
i. BHMA Finish
j. Remarks
In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
1.6 KEY BITTING CHART REQUIREMENTS
1.6.1 Requirements
Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:
a. Complete listing of all keys (e.g. AA1 and AA2).
b. Complete listing of all key cuts (AA1-123456, AA2-123458).
c. Tabulation showing which key fits which door.
d. Copy of floor plan showing doors and door numbers.
e. Listing of 20 percent more key cuts than are presently required in each master system.
SECTION 08 71 00 Page 4
1.7 QUALITY ASSURANCE
1.7.1 Hardware Manufacturers and Modifications
Provide, as far as feasible, locks, hinges, and closers of one lock, hinge, or closer manufacturer's make. Modify hardware as necessary to provide features indicated or specified.
1.7.2 Key Shop Drawings Coordination Meeting
Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith must meet to discuss and coordinate key requirements for the facility.
1.8 DELIVERY, STORAGE, AND HANDLING
Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule.
Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail. Deliver construction master keys with the locks.
PART 2 PRODUCTS
2.1 TEMPLATE HARDWARE
Hardware applied to metal or to prefinished doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.
2.2 HARDWARE FOR FIRE DOORS AND EXIT DOORS
Provide all hardware necessary to meet the requirements of NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, NFPA 252 for fire tests of door assemblies, ABA/ADA accessibility requirements, and all other requirements indicated, even if such hardware is not specifically mentioned in paragraph HARDWARE SCHEDULE. Provide Underwriters Laboratories, Inc. labels for such hardware in accordance with UL Bld Mat Dir or equivalent labels in accordance with another testing laboratory approved in writing by the Contracting Officer.
2.3 HARDWARE ITEMS
*****Amendment 0003 Clearly and permanently mark with the manufacturer's name or trademark, hinges, pivots, locks, latches, exit devices, bolts and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover. Coordinate electrified door hardware components with corresponding components. ***Amendment 0003*****
2.3.1 Hinges
Provide in accordance with ANSI/BHMA A156.1 . Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel exterior doors so that pins are non-removable when door is closed. Other anti-friction bearing hinges
SECTION 08 71 00 Page 5 may be provided in lieu of ball bearing hinges.
2.3.2 Continuous Hinges
Where continuous hinges are required, provide in accordance with
ANSI/BHMA A156.26 .
2.3.3 Locks and Latches
2.3.3.1 Mortise Locks and Latches
Provide in accordance with ANSI/BHMA A156.13 , Series 1000, Operational Grade 1, Security Grade 2. Provide knobs and roses of mortise locks with screwless shanks and no exposed screws.
2.3.3.2 Bored Locks and Latches
Provide in accordance with ANSI/BHMA A156.2 , Series 4000, Grade 1.
2.3.3.3 Auxiliary Locks
Provide in accordance with ANSI/BHMA A156.36 , Grade 1.
2.3.3.4 Combination Locks
Heavy-duty, mechanical combination lockset with five push buttons, standard sized knobs, 3/4 inch deadlocking latch, 2-3/4 inch backset.
Locks to operate by pressing two or more of the buttons in unison or individually in the proper sequence. Inside knob operates the latch.
Provide a keyed cylinder on the interior to permit setting the combination.
Provide a keyed removable core cylinder on the exterior to permit bypassing the combination.
2.3.4 Exit Devices
Provide in accordance with ANSI/BHMA A156.3 , Grade 1. Provide adjustable strikes for rim type and vertical rod devices. Provide open back strikes for pairs of doors with mortise and vertical rod devices. Provide touch bars in lieu of conventional crossbars and arms.
2.3.5 Exit Locks With Alarm
Provide in accordance with ANSI/BHMA A156.3 and ANSI/BHMA A156.29 , Type E0431 (with full width horizontal actuating bar) for single doors; Type E0431 (with actuating bar) or E0471 (with actuating bar and top and bottom bolts, both leaves active) for pairs of doors, unless otherwise specified.
Provide terminals for connection to remote indicating panel. Provide door alarms integrated with the fire alarm system in accordance with
NFPA 72 .
2.3.6 Cylinders and Cores
Provide cylinders and cores for new locks, including locks provided under other sections of this specification. Provide cylinders and cores with six pin tumblers. Provide cylinders from the products of one manufacturer, and provide cores from the products of one manufacturer. Rim cylinders, mortise cylinders, and knobs of bored locksets have interchangeable cores which are removable by special control keys. Stamp each interchangeable core with a key control symbol in a concealed place on the core.
SECTION 08 71 00 Page 6
2.3.6.1 High Security Cylinders
Provide in accordance with ANSI/BHMA A156.30 , security level A for all high security cylinder components.
2.3.7 Push Button Mechanisms
Provide in accordance with ANSI/BHMA A156.5 , Grade 1.
2.3.8 Electrified Hardware
Comply with the requirements of NFPA 70 for wiring of electrified hardware.
2.3.8.1 Electric Strikes and Frame Mounted Actuators
Provide in accordance with ANSI/BHMA A156.31 , Grade 1. Provide electric strikes and actuators as required to meet operational requirements.
Provide electric strikes that remain secure during power failure. Provide a separate power supply for electric strikes, other locking devices and ancillary parts. Provide strikes and actuators with a minimum opening force of 2300 pounds .
Provide facility interface devices that use direct current (dc) power to energize the solenoids. Provide electric strikes and actuators that incorporate end-of-line resistors to facilitate line supervision by the system. If not incorporated into the electric strike or local controller, provide metal oxide resistors (MOVs) to protect the controller from reverse current surges.
2.3.8.1.1 Solenoid
Provide actuating solenoid for strikes and actuators that are rated for continuous duty, cannot dissipate more than 12 Watts and must operate on 12 or 24 Volts dc. Inrush current cannot exceed 1 ampere and the holding current cannot be greater than 500 milliamperes. Actuating solenoid must move from fully secure to fully open positions in less than 500 milliseconds.
2.3.8.1.2 Signal Switches
Provide strikes and actuators with signal switches to indicate to the system when the bolt is not engaged or the strike mechanism is unlocked.
Signal switches must report a forced entry to the system.
2.3.8.1.3 Tamper Resistance
Provide strike guards that prevent tampering with the latch bolt of the locking hardware or the latch bolt keeper of the electric strike. Strike guards to bolt through the door using tamper resistant screws. Provide strike guards made of 1/8 inch thick brass and that are 11-1/14 inch high by 1-5/8 inch wide , with a minimum 5/32 inch wide offset.
2.3.8.1.4 Coordination
Provide electric strikes and actuators of a size, weight and profile compatible with each specified door frame. Field verify installation clearances prior to procurement.
SECTION 08 71 00 Page 7
2.3.8.1.5 Mounting Method
Provide electric strikes and actuators suitable for use with single and double doors, with mortise or rim type hardware specified, and for right or left hand mounting as specified. In double door installations, locate the lock in the active leaf and monitor the fixed leaf.
2.3.8.2 Electrified Mortise Locks
Provide in accordance with ANSI/BHMA A156.25 , Grade 1. Provide electrified mortise locks that remain secure during power failure.
Provide facility interface devices that use dc power to energize solenoids. Provide solenoids, resisters, and signal switches in accordance with paragraph ELECTRIC STRIKES AND FRAME MOUNTED ACTUATORS.
2.3.8.2.1 Power Transfer Hinges
Provide power transfer hinges with each electrified lock that route power and monitoring signals from the lockset to the door frame. Coordinate power transfer hinges with door frames.
2.3.8.3 Card Readers and Keypad Access Control Hardware
***Amendment 0003 Provide in accordance with ANSI/BHMA A156.5 and ANSI/BHMA A156.25 , Grade 1 components. Provide devices that are tamper alarmed, tamper and vandal resistant, solid state, and do not contain electronics which could compromise the access control subsystem should the subsystem be attacked. Provide surface, semi-flush, pedestal, or weatherproof mountable devices as specified for each individual location.
Each device to contain a visual display, either mounted on the face, or on an integral part of the device, to indicate access or exit request processing, request approval, and request denial. Provide in accordance with Base Security Requirements type card readers capable of reading magnetic stripe or high coercivity magnetic stripe or Wiegand or Hollerith or proximity or Transmissive Infrared or Keypad or Smart Card or Biometric type access control cards. Provide keypads that contain an integral 12-digit tactile keyboard with digits arranged in numerical order.
Provide keypads that are a standalone device or integrated into the card reader. Coordinate access control hardware with corresponding devices and systems. Amendment 0003*****
2.3.8.4 Power Operated Pedestrian Door Hardware
Provide in accordance with ANSI/BHMA A156.10 , Grade 1.
2.3.8.5 Release Devices
In accordance with ANSI/BHMA A156.15 , Grade 1.
2.3.8.5.1 Closer Holders
Provide floor or door or header mounted closer holder devices connected by integral releasing to fire and smoke detecting devices.
2.3.8.6 Power Assist and Low Energy Power Operated Doors
Provide in accordance with ANSI/BHMA A156.19 , Grade 1.
SECTION 08 71 00 Page 8
2.3.8.7 Electromagnetic Locks
Provide in accordance with ANSI/BHMA A156.23 , Grade 1. Provide electromagnetic locks that do not contain any moving parts and depend solely upon electromagnetism to secure a portal by generating at least 1200 pounds of holding force. The lock must interface with the local processors without external, internal or functional alteration of the local processor. The electromagnetic lock must incorporate an end of line resistor to facilitate line supervision by the system. Provide metal-oxide resistors (MOVs) to protect controllers from reverse current surges, if not incorporated into the electromagnetic lock or local controller.
2.3.8.7.1 Armature
Provide electromagnetic locks with internal circuitry to eliminate residual magnetism and inductive kickback. Provide atuating armature that operates on 12 or 24 Volts dc and cannot dissipate more than 12 Watts.
Holding current must be less than 500 milliamperes. Actuating armature must take less than 300 milliseconds to change the status of the lock from fully secure to fully open or fully open to fully secure.
2.3.8.7.2 Tamper Resistance
Provide lock mechanism encased in hardened guard barriers to deter forced entry.
2.3.8.7.3 Mounting Method
Provide electromagnetic lock suitable for use with single and double door with mortise or rim type hardware and compatible with right or left hand mounting.
2.3.8.8 Delayed Egress Locking System
Provide in accordance with ANSI/BHMA A156.24 , Grade 1.
2.3.9 Keying System
Provide a grand master keying system as an extension of the existing base keying system. Existing Base locks were manufactured by Schlage and have interchangeable cores.Provide key cabinet as specified.
2.3.10 Lock Trim
Provide cast, forged, or heavy wrought construction and commercial plain design for lock trim.
2.3.10.1 Lever Handles
Provide lever handles where indicated in the Hardware Schedule. Provide in accordance with ANSI/BHMA A156.3 for mortise locks of lever handles for exit devices. Provide lever handle locks with a breakaway feature (such as a weakened spindle or a shear key) to prevent irreparable damage to the lock when force in excess of that specified in ANSI/BHMA A156.13 is applied to the lever handle. Provide lever handles return to within 1/2 inch of the door face.
SECTION 08 71 00 Page 9
2.3.11 Keys
Furnish one file key, one duplicate key, and one working key for each key change and for each master keying system. Furnish one additional working key for each lock of each keyed-alike group. Furnish a quantity of key blanks equal to 20 percent of the total number of file keys. Stamp each key with appropriate key control symbol and "U.S. property - do not duplicate." Do not place room number on keys.
2.3.12 Door Bolts
Provide in accordance with ANSI/BHMA A156.16 . Provide dustproof strikes for bottom bolts, except at doors having metal thresholds. Provide automatic latching flush bolts in accordance with ANSI/BHMA A156.3 , Type 25.
2.3.13 Closers
Provide in accordance with ANSI/BHMA A156.4 , Series C02000, Grade 1, with PT 4C. Provide with brackets, arms, mounting devices, fasteners, full size covers, except at storefront mounting, and other features necessary for the particular application. Size closers in accordance with manufacturer's printed recommendations, or provide multi-size closers, Sizes 1 through 6, and list sizes in the Hardware Schedule. Provide manufacturer's 10 year warranty.
Use stainless steel inside bracketed or door mounted closers on exterior doors. Non-ferrous closers, such as aluminum or cast bronze, are permissible where door utilization is minimal. On interior doors use closers of 302 or 304 stainless steel or non-ferrous materials. On surface-mounted closers use or apply rust inhibiting finish on all ferrous parts. Also apply this finish on concealed closers.
2.3.13.1 Identification Marking
Engrave each closer with manufacturer's name or trademark, date of manufacture, and manufacturer's size designation in locations that will be visible after installation.
2.3.14 Overhead Holders
Provide in accordance with ANSI/BHMA A156.8 .
2.3.15 Door Protection Plates
Provide in accordance with ANSI/BHMA A156.6 .
2.3.15.1 Sizes of Mop and Kick Plates
2 inch less than door width for single doors; 1 inch less than door width for pairs of doors. Provide 10 inch kick plates for flush doors .
Provide a minimum 36 inch armor plates for flush doors and completely cover lower panels of panel doors, except 16 inch high armor plates on fire doors. Provide 4 inch mop plates.
2.3.15.2 Edge Guards
Stainless steel, of same height as armor plates. Apply to hinge stile , lock stile or meeting stiles.
SECTION 08 71 00 Page 10
2.3.16 Door Stops and Silencers
Provide in accordance with ANSI/BHMA A156.16 . Silencers Type L03011.
Provide three silencers for each single door, two for each pair.
2.3.17 Padlocks
Provide in accordance with ASTM F883.
2.3.18 Thresholds
Provide in accordance with ANSI/BHMA A156.21 . Use J35100, with vinyl or silicone rubber insert in face of stop, for exterior doors opening out, unless specified otherwise. Thresholds at exterior doors must be Florida Building Code compliant.
2.3.19 Weatherstripping Gasketing
Provide in accordance with ANSI/BHMA A156.22 . Provide the type and function designation where specified in paragraph HARDWARE SCHEDULE.
Provide a set to include head and jamb seals, sweep strips, and, for pairs of doors, astragals. Air leakage of weatherstripped doors not to exceed
0.5 cubic feet per minute of air per square foot of door area when tested in accordance with ASTM E283. Provide weatherstripping with one of the following:
2.3.19.1 Extruded Aluminum Retainers
Extruded aluminum retainers not less than 0.050 inch wall thickness with vinyl, neoprene, silicone rubber, or polyurethane inserts. Provide bronze anodized aluminum.
2.3.19.2 Interlocking Type
Zinc or bronze not less than 0.018 inch thick.
2.3.19.3 Spring Tension Type
Spring bronze or stainless steel not less than 0.008 inch thick.
2.3.20 Soundproofing Gasketing
Provide in accordance with ANSI/BHMA A156.22 . Provide adjustable doorstops at heads,jambs and automatic door bottoms in accordance with the hardware set, of extruded aluminum, clear (natural) anodized, surface applied, with vinyl fin seals between plunger and housing. Provide doorstops with solid neoprene tube, silicone rubber, or closed cell sponge gasket. Provide door bottoms with adjustable operating rod and silicone rubber or closed cell sponge neoprene gasket. Provide doorstops that are mitered at corners. Provide type and function designation where specified in paragraph HARDWARE SETS.
2.3.21 Rain Drips
Provide in accordance with ANSI/BHMA A156.22 . Provide extruded aluminum rain drips, not less than 0.08 inch thick, bronze anodized finish.
Provide the manufacturer's full range of color choices to the Contracting Officer for color selection. Provide rain drips with a 4 inch overlap on
SECTION 08 71 00 Page 11 each side of each exterior door that is not protected by an awning, roof, eave or other horizontal projection. Set drips in sealant and fasten with stainless steel screws.
2.3.21.1 Door Rain Drips
Approximately 1-1/2 inch high by 5/8 inch projection. Align bottom with bottom edge of door.
2.3.21.2 Overhead Rain Drips
Approximately 1-1/2 inch high by 2-1/2 inch projection. Align bottom with door frame rabbet.
2.3.22 Auxiliary Hardware (Other than locks)
Provide in accordance with ANSI/BHMA A156.16 , Grade 1.
2.3.23 Special Tools
Provide special tools, such as spanner and socket wrenches and dogging keys, as required to service and adjust hardware items.
2.4 FASTENERS
Provide fasteners of type, quality, size, and quantity appropriate to the specific application. Fastener finish to match hardware. Provide stainless steel or nonferrous metal fasteners in locations exposed to weather. Verify metals in contact with one another are compatible and will avoid galvanic corrosion when exposed to weather.
2.5 FINISHES
Provide in accordance with ANSI/BHMA A156.18 . Provide hardware in BHMA 630 finish (satin stainless steel), unless specified otherwise. Provide items not manufactured in stainless steel in BHMA 626 finish (satin chromium plated) over brass or bronze, except aluminum paint finish for surface door closers, and except BHMA 652 finish (satin chromium plated) for steel hinges. Provide hinges for exterior doors in stainless steel with BHMA 630 finish or chromium plated brass or bronze with BHMA 626 finish. Furnish exit devices in BHMA 626 finish in lieu of BHMA 630 finish except where BHMA 630 is specified under paragraph HARDWARE SETS.
Match exposed parts of concealed closers to lock and door trim. Match hardware finish for aluminum doors to the doors.
2.6 KEY CABINET AND CONTROL SYSTEM
Provide in accordance with ANSI/BHMA A156.5 . Type required to yield a capacity (number of hooks) 50 percent greater than the number of key changes used for door locks.
PART 3 EXECUTION
3.1 INSTALLATION
Provide hardware in accordance with manufacturers' printed installation instructions. Fasten hardware to wood surfaces with full-threaded wood screws or sheet metal screws. Provide machine screws set in expansion shields for fastening hardware to solid concrete and masonry surfaces.
SECTION 08 71 00 Page 12
Provide toggle bolts where required for fastening to hollow core construction. Provide through bolts where necessary for satisfactory installation.
3.1.1 Weatherstripping Installation
Provide full contact, weathertight seals that allow operation of doors without binding the weatherstripping.
3.1.1.1 Stop Applied Weatherstripping
Fasten in place with color matched sheet metal screws not more than 9 inch on center after doors and frames have been finish painted.
3.1.1.2 Interlocking Type Weatherstripping
Provide interlocking, self adjusting type on heads and jambs and flexible hook type at sills. Nail weatherstripping to door 1 inch on center and to heads and jambs at 4 inch on center.
3.1.1.3 Spring Tension Type Weatherstripping
Provide spring tension type on heads and jambs. Provide bronze nails with bronze. Provide stainless steel nails with stainless steel. Space nails not more than 1-1/2 inch on center.
3.1.2 Lightproofing and Soundproofing Installation
Provide as specified for stop applied weatherstripping.
3.1.3 Threshold Installation
Extend thresholds the full width of the opening and notch end for jamb stops. Set thresholds in a full bed of sealant and anchor to floor with cadmium-plated, countersunk, steel screws in expansion sleeves. For aluminum thresholds placed on top of concrete surfaces, coat the underside surfaces that are in contact with the concrete with fluid applied waterproofing as a separation measure prior to placement.
3.2 FIRE DOORS AND EXIT DOORS
Provide hardware in accordance with NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, and NFPA 252 for fire tests of door assemblies.
3.3 HARDWARE LOCATIONS
Provide in accordance with SDI/DOOR A250.8 , unless indicated or specified otherwise.
a. Kick and Armor Plates: Push side of single-acting doors. Both sides of double-acting doors.
b. Mop Plates: Bottom flush with bottom of door.
3.4 KEY CABINET AND CONTROL SYSTEM
Locate where directed. Tag one set of file keys and one set of duplicate keys. Place other keys in appropriately marked envelopes, or tag each
SECTION 08 71 00 Page 13 key. Provide complete instructions for setup and use of key control system. On tags and envelopes, indicate door and room numbers or master or grand master key.
3.5 FIELD QUALITY CONTROL
After installation, protect hardware from paint, stains, blemishes, and other damage until acceptance of work. Submit notice of testing 15 days before scheduled, so that testing can be witnessed by the Contracting Officer. Adjust hinges, locks, latches, bolts, holders, closers, and other items to operate properly. Demonstrate that permanent keys operate respective locks, and give keys to the Contracting Officer. Correct, repair, and finish, errors in cutting and fitting and damage to adjoining work.
3.6 HARDWARE SETS
The hardware sets represent the design intent. They are a guideline only and should not be considered a detailed hardware schedule. Discrepancies, conflicting hardware and missing items should be brought to the attention of the Contracting Officer with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.
a. Quantities listed are for each pair of doors, or for each single door.
b. The supplier is responsible for handing and sizing all products.
c. Where multiple options for a piece of hardware are given in a single line item, the supplier shall provide the appropriate application for the opening.
d. Basis of design hardware manufacturers are provided to establish level of quality. Products from other manufacturers having equal or greater quality, and meeting the specified performance requirements, may be provided.
Manufacturer's Abbreviations:
1. MK - McKinney
2. MR - Markar
3. PE - Pemko
4. RF - Rixson
5. SU - Securitron
6. RO - Rockwood
7. YA - ASSA ABLOY ACCENTRA
8. SA - SARGENT
9. AD - Adams Rite
10. MC - Medeco
11. HS - HES
12. NO - Norton
SECTION 08 71 00 Page 14
SECTION 10 22 39
FOLDING PANEL PARTITIONS
08/20
Deleted by Amendment 0003
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C423 (2023; E 2024) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM E90 (2023) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
ASTM E413 (2022) Classification for Rating Sound Insulation
ASTM E557 (2012; R 2020) Standard Guide for Architectural Design and Installation Practices for Sound Isolation between Spaces Separated by Operable Partitions
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" classification.
Submittals with an "S" are for inclusion in the Sustainability eNotebook, SECTION 10 22 39 Page 1 in accordance with Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Coordination Drawings ; G, Layouts ; G
Installation Drawings ; G
SD-03 Product Data
Folding Panel Partitions ; G
Recycled Content for Steel Components
SD-04 Samples
Partition System Samples ; G
SD-06 Test Reports
Acoustical Test Reports ; G
SD-07 Certificates
Indoor Air Quality for Finish Covering ; S
Installer Qualifications
Manufacturer's Qualifications
SD-08 Manufacturer's Instructions
Installation Instructions
SD-10 Operation and Maintenance Data
Folding Panel Partitions , Data Package 1 and 2; G
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certification
1.3.1.1 Finish Covering
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
SECTION 10 22 39 Page 2
1.4 QUALITY ASSURANCE
1.4.1 Coordination Drawings
Provide reflected ceiling plans, applicable details and other drawings as required to suit conditions, drawn to scale, for the following coordinated items, using input from adjacent materials/systems installers, field measurements and verification of conditions:
a. Partition track, track supports and bracing, switches, turning space, and storage layout.
b. Suspended ceiling system components and structural members used for attachment.
c. Items penetrating finished ceiling in vicinity of folding panel partition location.
d. Accessories located within the folding panel partitions.
1.4.2 Installer Qualifications
Installer must have a minimum of 5 years of documented successful experience in the installation of folding panel partitions. When required by manufacturer, folding panel partitions must be installed by an authorized dealer with a certified crew.
1.4.3 Manufacturer's Qualifications
Manufacturer must have a minimum of 10 years of documented successful experience in designing and manufacturing folding panel partitions conforming to the requirements specified in this Section.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the jobsite in the manufacturer's original, unopened, and undamaged packages with labels legible and intact. Provide labels to indicate the manufacturer, brand name, size, finish, and placement location. Store partitions and accessories in unopened packages in a manner to prevent damage. Handle partition materials in accordance with manufacturer's instructions. Protect materials from the weather, humidity and temperature variations, dirt and dust, or other contaminants.
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for specified warranty periods from date of final acceptance of the work as follows:
1.6.1 Warranty Periods
a. Structural: 10 years
b. Plastic and Wood Materials: 3 years
c. Fabric Materials: 3 years
d. Electrical Components: 5 years
SECTION 10 22 39 Page 3
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide manual operation, acoustical folding panel partitions, factory finished, supported from overhead track with operable floor seals , as shown on the drawings including all hardware, seals, track and rollers as needed to close the specified opening.
Submit detail coordination drawings and installation drawings of each folding panel partition indicated. Include elevations, dimensions, clearances, details of construction and anchorage, and details of joints and connections.
Submit manufacturers' descriptive product data for folding panel partition indicated. Include manufacturers' literature, finishes, profiles and thicknesses of materials.
Submit manufacturers' operations and maintenance data for folding panel partition in accordance with Section 01 78 23 OPERATIONS AND MAINTENANCE
DATA.
2.1.1 Manual Operation
Manual operation must be a force no greater than 20lbf to start movement at the rate of 3.33 ft/s (200 ft/min) . Use a removable handle to extend and retract the bottom operable seals; vertical movement of seals must be nominal 2 inches . Provide closure to the lead wall with the use of a flexible bulb; accomplish final closing by means of a lever exerting pressure against the wall.
2.1.2 Performance Requirements
2.1.2.1 Laboratory Acoustical Requirements
Provide partitions tested in accordance with ASTM E90, by a laboratory accredited by the U.S. Bureau of Standards, that have attained a sound transmission class (STC) of not less than 50 in a fully extended position, with a Noise Reduction Coefficient (NRC) of 0.25-0.30 for napped, tufted or looped fabric. Provide documentation that the partition tested is the same construction, materials, and model number as the partition to be provided and be fully operable. Test specimen is not less than 126 square feet in area . Provide a minimum panel weight of 8.0 pounds per square foot for STC up to 50. Design panel thickness 3 inch nominal and composition to provide the required STC rating in accordance with ASTM E90 and ASTM E413. Submit acoustical test reports in accordance with ASTM E90, ASTM C423 and ASTM E413.
2.2 MATERIALS
Provide heavy-duty type hardware standard with the manufacturer. Provide pulls and latches for all partitions. Provide partitions with interlocking seals between panels . Provide finish hardware , and horizontal and vertical trim , of color(s) selected from manufacturer's standard range .
2.3 FOLDING PANEL PARTITIONS
Provide folding panel partitions using top hung ball bearing carriers which support modular panels.
SECTION 10 22 39 Page 4
a. Provide partitions made up of a series of rigid panels, each panel being a one-piece assembly. Unless otherwise specified, use the least number of panels. The mechanical seal of the panel must actuate with a single operating action.
b. Provide paired(centerfold) type panels as indicated.
2.3.1 Panels
Provide panels of gypsum board, laminated to appropriate structural acoustical backing, mounted in full perimeter protective frame. Steel for the panel frames must be minimum 18-gage formed steel with overlapped and welded corners for rigidity . . Frame must enclose and protect all edges of the surface material. Provide panels not more than 4 feet wide, except for end closure panels, and full height to track. Panels must lock in place to form a stable, rigid partition; low profile hinges may not project more than 1/4 inch maximum from panel edge. Panel surfacing must wrap around the vertical panel edges without vertical trim.
Provide steel components that contain a minimum of 10 percent recycled content. Provide data identifying percentage of recycled content for steel components .
2.3.2 Partition System
Provide panel face finish acrylic backed fabric of of full height steel markerboard work surface . Provide finish covering that meets emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification of indoor air quality for finish covering .
2.3.3 Track
Provide recess enamel finish steeltrack as shown.Provide steel that conforms to ASTM A653/A653M . Provide track that is the manufacturer's standard product designed for the weight of the finished partition, including door. Provide track sections in the maximum lengths practicable, and not less than 6 feet long except for narrow doors and at ends of runs where short length and "drop-out service" sections of track are required. Provide suitable joint devices such as interlocking keys at each joint to provide permanent alignment of track.
2.3.4 Suspension System
Provide a suspension system consisting of steel track connected to the structural support by threaded rods, and trolleys designed to support the weight of the partition. Provide steel track of 7 gauge minimum, phosphate treated or painted.Provide center hung panel with 1 trolley with four ball bearing nylon or steel tired wheels per panel.
2.4 ACCESSORIES
2.4.1 Pocket Doors
Provide manually operated acoustic pocket doors to conceal panel storage area. Provide double doors hinged to a jamb on each side and closing in the center. One of the door panels is equipped with a smaller hinged panel that folds back when the operable partition is extended into pocket.
SECTION 10 22 39 Page 5
Panels shall be nominal 3-inch thick in manufacturer’s standard width, of specified panel construction and finish, providing an acoustical rating of minimum 47 STC.
Provide full leaf butt hinges attached directly to panel frame with welded hinge anchor plates within panel to further support hinge mounting to frame. Hinges mounted into panel edge or vertical astragal are not acceptable.
No vertical trim required or allowed on edges of panels; minimal groove appearance at panel joints.
Provide pocket door jambs of continuous channels anchored to a fixed wall. Welded hinge anchor plates support pocket door hinges and permit a full 180-degree swing.
Pocket Door hanging weight shall not exceed 9 lbs./square foot.
Prefabricate pocket doors with jambs and hardware installed. Pre-finish to match paired panels.
2.4.2 Markerboards
Provide markerboards of white enamel on steel , bonded to the face of the panel with horizontal trim without exposed fasteners . Trim is not acceptable on vertical edges to provide uninterrupted work surface.
2.5 SEALS AND SWEEPSTRIPS
Provide perimeter seals or sound insulation, of manufacturer's standard product, to achieve the sound transmission class specified , without crack or craze when subjected to severe usage. Provide manufacturer's vertical seals between panels to ensure acoustical rating. Bottom seals consist of a vinyl sweep mechanical seal which expands in place, or provide panels which can be lowered by a removable operating device. Provide vertical seal between panels which is anodized, architectural grade, aluminum extrusion with sound seal. Sweep strips must be vinyl or other material that will not crack or craze with severe usage. Provide sweep strip STC to the specified rating.
2.6 COLOR
Provide partition system samples in sizes indicated below and colors as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
2.6.1 Sample Size
a. Textile Facing Material: Full width by not less than 36 inches long.
b. Panel Facing Material: Manufacturer's standard size, not less than 6 inches square.
c. Panel Edge Material: Manufacturer's standard size, not less than 6 inches long.
SECTION 10 22 39 Page 6
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth. Install in accordance with the approved installation drawings and the manufacturer's written installation instructions .
3.1.1 Preparation Work
Verify dimensions and condition of openings scheduled to receive folding panel partitions. Install partitions in accordance with the approved partition layouts , manufacturer's directions, and ASTM E557. Provide structural support for the track support elements as indicated.
3.1.2 Adjustment
Adjust manually operated partitions to open and close from any position with a maximum horizontal force as specified in paragraph MANUAL OPERATION applied to pendant pull, box or handle. Adjust partitions to operate smoothly, easily, and quietly, free from binding, warp, excessive deflection, distortion, nonalignment, misplacement, disruption, or malfunction, throughout entire operational range. Lubricate hardware and other moving parts.
3.2 FIELD TESTS
3.2.1 Operational Test
In the presence of the Contracting Officer, operate partition at least three times to demonstrate that partition is capable of being moved from the stored position to the fully extended position smoothly and quietly .
Activate mechanical seals top and bottom. Adjust partitions which do not operate properly and retest.
3.2.2 Visual Test
Conduct visual field tests for light leakage with all room lights turned on in the space on one side of the partition. Darken space on the other side of the partition. Light leakage from the lighted space to the darkened space is not acceptable. If light leakage does occur, adjust the partition to correct the problem and retest.
3.3 CLEANING
Clean any soiled parts of the partition in accordance with manufacturer's written instructions.
-- End of Section --
SECTION 10 22 39 Page 7
SECTION 10 81 13
BIRD CONTROL DEVICES
01/18
Added by Amendment 0003
PART 1 GENERAL
1.1 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL DESCRIPTIONS:
SD-02 Shop Drawings
Bird Screen Wire Mesh Barrier ; G
Bird Screen Wire Mesh Barrier Hardware ; G
SD-03 Product Data
Bird Screen Wire Mesh Barrier ; G
Bird Screen Wire Mesh Barrier Hardware ; G
Bird Spikes ; G
Bird Spike Mounting Hardware ; G
Warranties ; G
SD-05 Design Data
Bird Screen Wire Mesh Barrier System ; G
Bird Spike System ; G
SD-08 Manufacturer's Instructions
Bird Spike System Installation; G
Provide documentation confirming that the international standards used by the manufacturer meet the specified standards indicated in the contract documents.
1.2 DELIVERY, STORAGE, AND HANDLING
Deliver materials in manufacturer's original, unopened containers or packaging with labels intact and legible. Deliver, store, and handle materials so as to prevent damage. Replace damaged or defective materials with new.
SECTION 10 81 13 Page 1
1.3 QUALITY CONTROL
1.3.1 Installer Qualifications
An authorized representative of the bird control device manufacturer for installation of units required for this Project.
1.3.2 Manufacturer Qualifications
Manufacturer shall design, engineer, and fabricate bird screen wire mesh barrier system to withstand the tensions required using the materials specified to provide a nonsagging installation.
Furnish products from one manufacturer for entire project.
1.3.3 Fabricator Qualifications
Shop that employs skilled workers who custom-fabricate products similar to those required for this Project and whose products have a record of successful in-service performance.
1.4 PROJECT CONDITIONS
Field Measurements: Verify existing conditions, ceiling areas, fixtures piping, ductwork and sills to recieve bird control devices and take field measurements prior to fabrication and indicate measurements on Shop Drawings.