This federal solicitation seeks design-build construction services for a Flight Simulator Facility and Squadron Operations/Aircraft Maintenance Unit Facility at NAS Fort Worth JRB, Texas. The projects include demolishing existing buildings totaling 8,009 square feet and constructing a new 20,000 square-foot Flight Simulator Facility and 33,729 square-foot Squadron Operations/Aircraft Maintenance Unit building. The Simulator Facility will house four Full Mission Simulators and include secured spaces for simulators, computer equipment, debriefing rooms, and storage, as well as unsecured offices and support spaces. The Squadron Operations/Aircraft Maintenance Unit will provide maintenance equipment and ready rooms on the first floor and secure administrative offices, flight operations, and conference rooms on the second floor. Both buildings will have reinforced concrete foundations, structural steel frames, standing seam metal roofs, and 4-inch split face masonry exteriors. The solicitation was issued by NAVFAC Southeast on behalf of the Department of the Navy for design-build services with responses due by a specified date.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN CRITERIA
CODES AND STANDARDS
A. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE
(ACI), ACI 318-16.
B. MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES, ASCE 7-16.
C. INTERNATIONAL BUILDING CODE (IBC), 2018
D. BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURE, ACI 530 (2011)
E. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) STEEL CONSTRUCTION MANUAL, 14th EDITION
F. STRUCTURAL COMPONENTS IN THIS PROJECT DESIGNED USING LFRD METHODOLOGY
G. AISI AMERICAN IRON AND STEEL INSTITUTE.
1.0 MINIMUM DESIGN LOADS AND REQUIREMENTS IN ACCORDANCE WITH IBC, 2016_____________________
SIMULATOR ROOMS
RAISED ACCESS FLOOR AREAS
MECH.
ALL OTHERS
WIND DESIGN DATA:
ULTIMATE WIND SPEED
NOMINAL WIND SPEED
RISK CATEGORY
WIND IMPORTANCE FACTOR
WIND EXPOSURE
COMPONENTS AND CLADDING DESIGN PRESSURE
EARTHQUAKE DESIGN DATA:
SEISMIC IMPORTANCE FACTOR
OCCUPANCY CATEGORY
SS
S1
SITE CLASS
SDS
SD1
SEISMIC DESIGN CATEGORY
SEISMIC RESISTING SYSTEM
DESIGN BASE SHEAR
CS
R
DESIGN METHOD
SNOWLOADS:
ULTIMATE ROOF DESIGN SNOWLOADS
GENERAL STRUCTURAL NOTES
250 PSF
6000 # FORKLIFT (14,400 AXLE LOAD)
250 PSF
250 PSF
100 PSF
106 MPH
82 MPH
II
1.0
C
SEE TABLE 1/S-001
1.0 C
0.092g 0.05g
C 0.08g 0.05g
A
MASONRY SHEAR WALLS
0.04 W
0.04 2.0
EQUIVALENT LATERAL FORCE
5 PSF
2.0 MATERIALS __________________
CONCRETE (28-DAY STRENGTH):
DRILLED PIERS 5000 PSI (COMP. STRENGTH)
GRADE BEAMS, FOUNDATION WALLS AND PILE CAPS 4000 PSI (COMP. STRENGTH)
CONCRETE BOND BEAMS AT MASONRY WALLS 4000 PSI (COMP. STRENGTH)
CONCRETE WALLS, CURBS & GUTTERS 4000 PSI (COMP. STRENGTH)
INTERIOR SLABS ON GRADE 4000 PSI (COMP. STRENGTH)
COMPOSITE DECK TOPPING 4000 PSI (COMP. STRENGTH)
ALL OTHERS 4000 PSI (COMP. STRENGTH)
REINFORCING:
BARS ASTM A615/A615M
WELDED WIRE FABRIC ASTM A185
APPLICABLE SHAPE SERIES
W M S C
MC
L
HSS (RECTANGLE)
HSS (ROUND)
PIPE
PLATES
PLATES
BARS
ASTM DESIGNATION
A992 A36 A36 A36 A36 A36 A500 A500 A53 A36 A572 A572
MIN. YIELD STRESS (FY) (KSI)
BOLTS:
BOLTS
CONCRETE MASONRY UNITS:
HOLLOW LOAD BEARING UNITS
MORTAR:
MORTAR SHALL BE TYPE S CONFORMING TO ASTM C270. ALL GROUT SHALL BE PUDDLED OR VIBRATED
IN PLACE.
ANCHOR RODS:
ANCHOR RODS
GROUT:
GROUT
HEADED STEEL STUDS:
YIELD STRENGTH
SHANK DIAMETER
HEAD DIAMETER
HEAD THICKNESS
LENGTH
ASTM A325, BEARING TYPE N
ASTM C90
ASTM F1554. GRADE 36
2 KSI
36 KSI
1/2"
1" 5/8"
6"
STRUCTURAL STEEL SHAPES, PLATES AND MISCELLANEOUS SHAPES:
3.0 CAST-IN-PLACE CONCRETE NOTES _(CONTINUED)_
3.2 UNLESS SPECIFICALLY NOTED, SCHEDULED OR DETAILED OTHERWISE PROVIDE
DEVELOPMENT LENGTH FOR REINFORCING IN CONCRETE COMPONENTS IN ACCORDANCE
WITH THE SCHEDULE IN NOTE 3.3 BELOW. THIS SCHEDULE SHALL APPLY TO ALL
DEVELOPMENT LENGTHS NOT OTHERWISE NOTED, DETAILED OR SCHEDULED IN THE
DRAWINGS OR SPECIFICATIONS.
3.3 REINFORCING BAR DEVELOPMENT LENGTHS Ld (f'c = 4000 PSI)
NOTE: THIS TABLE IS BASED ON BAR CLEAR SPACING OF 2 BAR DIAMETER MIN. FOR BAR CLEAR
SPACING LESS THAN 2 BAR DIAMETER, MULTIPLY THE ABOVE VALUES BY 2.0.
3.4 LAP SPLICE LENGTHS FOR REINFORCING BARS SHALL BE THE SAME AS TABLE IN NOTE
3.3 ABOVE WHEN TWO BARS OF DIFFERENT SIZES ARE LAPPED, THE SMALLER SIZE GOVERNS THE
LAP LENGTH UNLESS SPECIFICALLY NOTE OTHERWISE.
3.5 WHEN REINFORCING STEEL IS NOTED AS CONTINUOUS REINFORCING IN GRADE BEAMS,
WALLS, SLABS AND/OR BEAMS, SPLICE CONTINUOUS REINFORCING STEEL ONLY WHEN
UNAVOIDABLE DUE TO STOCK LENGTHS. STAGGER ALL SPLICES A MINIMUM OF 4'-0".
ADJACENT BAR SPLICES ARE NOT ACCEPTABLE. LOCATE THE TOP BAR SPLICES WITHIN THE
MIDDLE HALF OF THE SPAN AND LOCATE THE BOTTOM BAR SPLICES AT SUPPORTS, OR
BETWEEN SUPPORTS AND 1/3 SPAN POINT, UNLESS NOTED OTHERWISE ON PLANS, DETAILS
OR SCHEDULES.
3.6 HORIZONTAL WALL REINFORCEMENT SHALL BE CONTINUOUS AND SHALL HAVE 90-DEGREE
BENDS AND EXTENSIONS, OR CORNER BARS OF EQUIVALENT SIZE LAPPED 42 BAR
DIAMETERS AT CORNERS AND INTERSECTIONS.
3.7 HORIZONTAL JOINTS WILL NOT BE PERMITTED IN CONCRETE CONSTRUCTION EXCEPT AS
SHOWN ON THE DRAWINGS. VERTICAL JOINTS SHALL OCCUR AT LOCATIONS INDICATED.
3.8 AT CONSTRUCTION JOINTS, CONTACT SURFACES SHALL BE CLEAN AND FREE OF LATENCIES
AND INTENTIONALLY ROUGHENED TO A FULL AMPLITUDE OF APPROXIMATELY 1/4 INCH
3.9 PROVIDE FULL EMBEDMENT WITH 90-DEGREE HOOKS FOR ALL DOWELS IF NOT OTHERWISE
NOTED.
3.10 CHAMFER ALL EXPOSED TO VIEW CORNERS 3/4", U.N.O.
3"
1 1/2" 2"
1" 1 1/2"
BAR SIZE
GRADE 60
#3 #4 #5 #6
DEVELOPMENT
LENGTH
BAR SIZE
GRADE 60
#7 #8 #9 #10
DEVELOPMENT
LENGTH
4.0 MASONRY:
4.1 MASONRY UNITS SHALL BE GRADE N-1, TWO CELL UNITS CONFORMING TO THE ASTM C 90.
MORTAR SHALL BE TYPE S CONFORMING TO ASTM C 270. ALL GROUT SHALL BE PUDDLED OR
VIBRATED IN PLACE. WHERE REQUIRED, CELLS SHALL BE SOLIDLY FILLED WITH 2000 PSI
GROUT. POURS SHALL BE STOPPED 1-1/2" BELOW THE TOP OF A COURSE TO FORM A KEY AT
POUR JOINTS. ALL CMU BLOCK TO BE 8"x8"x16" U.N.O.
4.2 UNLESS OTHERWISE NOTED, ALL MASONRY SHALL HAVE A MINIMUM COMPRESSIVE
STRENGTH (f'm) OF 2000 PSI AT 28 DAYS.
4.3 REINFORCED CONCRETE MASONRY, STRUCTURAL STEEL OR CAST-IN-PLACE LINTELS SHALL
BE PROVIDED AT EACH DOOR OR WINDOW OPENING AS INDICATED IN THE TYPICAL DETAILS.
4.4 MASONRY GROUTING SHALL BE DONE IN ACCORDANCE WITH ACI 530.1
4.5 8-INCH CMU MASONRY REINFORCING:
a. MINIMUM BAR SIZE FOR REINFORCING SHALL BE #5.
b. EACH SIDE OF EACH OPENING
3.0 CAST-IN-PLACE CONCRETE NOTES __________________
3.1 CONCRETE COVER FOR REINFORCEMENT:
A. CONCRETE DEPOSITED AGAINST AND PERMANENTLY
EXPOSED TO EARTH
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BARS OR SMALLER
#5 BARS OR LARGER
C. CONCRETE NOT EXPOSED TO WEATHER OR NOT IN CONTACT WITH
GROUND:
SLABS, WALLS, AND JOISTS
BEAMS
5.0 FOUNDATION AND STRUCTURAL SLAB:
5.1 FOUNDATION SHALL CONSIST OF DRILLED PIERS AND GRADE BEAMS SUPPORTING A
STRUCTURAL SLAB. DESIGN BEARING PRESSURE FOR PIERS IS 40 KSF BASED UPON
GEOTECHNICAL INVESTIGATION PERFORMED BY TERRACONN DATED MARCH 2020.
5.2 ALL GRADE BEAMS AND STRUCTURAL SLABS SHALL BE CONSTRUCTED ON A 6 INCH DEEP
CONCRETE VOID FORM WITH A 15 MIL VAPOR BARRIER.
5.3 PROTECT PIPES AND CONDUITS RUNNING THRU WALLS AND SLABS WITH 1/2 INCH EXPANSION
MATERIAL.
5.4 MAINTAIN SUBGRADE AND FILL MOISTURE CONTENT UNTIL FOUNDATIONS ARE PLACED.
ARRANGE FOR OWNER'S INDEPENDENT TESTING AGENCY TO MONITOR CUT AND FILL
OPERATIONS, AND PERFORM FIELD DENSITY AND MOISTURE CONTENT TESTS TO VERIFY
COMPACTION AND APPROVE FOOTING SUBGRADE PRIOR TO PLACING CONCRETE.DO NOT
PLACE SLAB AGAINST SUBGRADE CONTAINING FREE WATER, FROST, OR ICE.
5.5 MAINTAIN PROPER SITE DRAINAGE DURING CONSTRUCTION TO ENSURE SURFACE RUNOFF
AWAY FROM STRUCTURES AND TO PREVENT PONDING OF SURFACE RUNOFF NEAR THE
STRUCTURES.
KEEP OPEN EXCAVATIONS AROUND BUILDING DRY. BACKFILL AGAINST GRADE BEAMS AS SOON
AS PRACTICAL. PUMP WATER OUT OF OPEN EXCAVATIONS IF FLOODING OCCURS PRIOR TO
BACKFILLING.
FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE END BEARING OF 40 KSF (FOR DRILLED
PIERS BEARING IN GRAY LIMESTONE) AND AN ALLOWABLE SKIN FRICTION OF 6 KSF FOR
COMPRESSIVE LOADS AND 4 KSF FOR TENSILE LOADS (NEGLECTING THE FIRST TWO FEET OF
PENETRATION INTO GRAY LIMESTONE)
5.6 DEPTH OF BEARING STRATUM VARIES FROM 19 FEET TO 22 FEET FOR ESTIMATING PURPOSES.
PROVIDE PIER DIAMETER AND REINFORCING AS SCHEDULED.
5.7 PLACE CONCRETE FOR PIER HOLES WITHIN 8 HOURS AFTER DRILLING. DO NOT LEAVE HOLE
OPEN OVERNIGHT.
6.0 GENERAL: __
6.1 WHERE A SECTION OR DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL ONLY APPLY TO LIKE
OR SIMILAR CONDITIONS.
7.0 STRUCTURAL STEEL NOTES:
7.1 DIMENSIONS: TO CENTERLINES OF COLUMNS AND BEAMS AND TO TOP SURFACES OF TOP
FLANGES OF BEAMS, AND BACKS OF CHANNELS AND ANGLES, UNLESS SHOWN OTHERWISE.
7.2 ELEVATIONS: REFER TO TOP SURFACE OF FLANGE OR MEMBER, UNLESS SHOWN OTHERWISE.
7.3 WELD SIZES NOT INDICATED ON DRAWINGS: PROVIDE MINIMUM WELD CONNECTIONS IN
ACCORDANCE WITH AISC. WELD IN ACCORDANCE WITH AWS REQUIREMENTS
7.4 STRUCTURAL OR MISCELLANEOUS STEEL: STRUCTURAL OR MISCELLANEOUS STEEL SHALL BE
DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC SPECIFICATIONS FOR
BUILDINGS. SHOP CONNECTIONS SHALL BE WELDED. FIELD CONNECTIONS SHALL BE MADE
WITH MINIMUM 3/4" DIAMETER ASTM A325 TYPE N BOLTS, UNLESS OTHERWISE NOTED. PROVIDE
4X4X1/4 ANGLE FRAMES FOR OPENINGS IN ROOF, UNLESS OTHERWISE NOTED. FRAMES TO BE
WELDED TO SUPPORTING MEMBERS.
8.0 ADHESIVE ANCHORS:
8.1 ADHESIVE ANCHORS SHALL BE STAINLESS STEEL AND HAVE AN ALLOWABLE LOAD AS SHOWN
IN THE FOLLOWING TABLE.
DIAMETER
(INCHES)
3/4"
EMBEDMENT DEPTH
(INCHES)
3"
SHEAR STRENGTH
(POUNDS)
TENSION
(POUNDS)
9.0 FIELD INSTALLED ADHESIVE BOLT NOTES:
A. INSTALL BOLTS PERPENDICULAR TO THE FACE OF CONCRETE. DEVIATION FROM
PERPENDICULAR GREATER THAN 10 DEGREES WILL NOT BE ACCEPTABLE.
B. CREATE A TEMPLATE AT EACH BOLT CONNECTION LOCATION PRIOR TO FABRICATING HOLES IN
CONNECTION PLATES. MAKE TEMPLATE BY LOCATING EXISTING REBAR WITH A PACHOMETER.
REPOSITION BOLTS A MAXIMUM OF 1-1/2 INCHES TO AVOID CONFLICTS WITH EXISTING
REINFORCING.
C. DRILL HOLES TO DEPTH AND DIAMETER RECOMMENDED BY MANUFACTURER. DO NO ENLARGE
OR REDIRECT HOLES ALONG LENGTH OF BOLT.
D. DRILL HOLES IN CONTINUOUS OPERATION. BLOW DUST FROM THE HOLE USING COMPRESSED
AIR.
E. FILL ABANDONED HOLES WITH EPOXY GROUT.
10.0 PRE-ENGINEERED MEAL BUILDING (PEMB) NOTES:
10.1 DESIGN OF THE SUPERSTRUCTURE SHALL BE PROVIDED BY THE PRE-ENGINEERED METAL
BUILDING SUPPLIER, FURTHER REFERENCED IN THESE DRAWING AS THE "BUILDING SUPPLIER".
THE SUPERSTRUCTURE SHALL COMPLY WITH THE METAL BUILDING MANUFACTURERS
ASSOCIATION 2018 METAL BUILDING SYSTEMS MANUAL. THE BUILDING SUPPLIER'S ENGINEER IS
THE DELEGATED ENGINEER RESPONSIBLE FOR THE SUPERSTRUCTURE DESIGN AND FOR THE
ACCURACY OF THE BUILDING FRAME REACTIONS SUPPLIED TO NAVFAC.
10.2 THE SUPERSTRUCTURE SHALL BE DESIGNED PER THE DESIGN CRITERIA LISTED ON THIS SHEET
AND ALL APPLICABLE CODES.
10.3 NO FABRICATION OF THE PRE-ENGINEERED METAL BUILDING SHALL BEGIN UNTIL SHOP
DRAWINGS ARE REVIEWED BY THE NAVFAC STRUCTURAL ENGINEER AND ARCHITECT OF
RECORD. FINAL METAL BUILDING DRAWINGS SHALL BE SIGNED AND SEALED BY A LICENSED
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF TEXAS FOR THEIR PREPARATION.
10.4 BUILDING SUPPLIER'S FINAL DRAWINGS SHALL INCLUDE COLUMN REACTIONS BY LOAD CASE
INCLUDING WIND UPLIFT PER ASCE 7-16.
10.5 FRAME COLUMNS SHALL BE DESIGNED AND DETAILED TO HAVE A PIN BASE AND THEREFORE
SHALL NOT BE DESIGNED TO TRANSFER MOMENT TO THE FOUNDATIONS.
10.6 PRE-ENGINEERED METAL BUILDING SHALL BE COORDINATED TO SUPPORT ALL MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION COMPONENTS HUNG FROM THE ROOF
STRUCTURE. SEE MECHANICAL DRAWINGS FOR LAYOUT AND SUPPORT DETAILS OF AHU AND
DUCTWORK. SEE ELECTRICAL DRAWINGS FOR LAYOUT AND SUPPORT OF ELECTRICAL
EQUIPMENT. SEE FIRE PROTECTION DRAWINGS FOR PIPING COMPONENTS.
10.7 FRAMING MEMBERS, WALL PANELS, ROOF PANELS, HARDWARE, AND ALL OTHER BUILDING
COMPONENTS SHALL BE PROVIDED WITH A PROTECTIVE FINISH PER SPECIFICATION 13 34 19, METAL BUILDING SYSTEMS.
5.0 FOUNDATION AND STRUCTURAL SLAB: (CONTINUED)
5.8 USE TEMPORARY CASING IF REQUIRED TO PREVENT CAVING OR SLOUGHING OF THE HOLE, OR
TO PREVENT INFLUX OF WATER.
5.9 CLEAN BOTTOM OF EACH PIER HOLE OF LOOSE MATERIAL.
5.10 PLACE CONCRETE USING A HOPPER AND CHUTE PIPE. PROVIDE CONCRETE FREE FALL OF LESS THAN 10 FEET. REMOVE LAITANCE MATERIAL FROM THE TOP OF EACH PIER PRIOR TO PLACING
CONCRETE.
5.11 FORM SIDES OF BEAMS STRAIGHT AND TO SPECIFIED DIMENSIONS. EARTH FORMS WILL NOT BE
PERMITTED.
5.12 WHERE SHOWN ON DRAWINGS, CONSTRUCT BEAMS OVER MINIMUM VOID SPACE OF 6 INCHES.
USE SOIL RETAINERS TO MINIMIZE THE POTENTIAL FOR INFILLING OF THE VOID SPACE OVER
TIME.
5.13 ALL SLABS AND GRADE BEAMS TO BE PLACED ON VOID FORMS AS INDICATED.
5.14 SLAB S3 IS TO BE PLACED IN A SINGLE, MONOLITHIC POUR WITH NO CONSTRUCTION OR
EXPANSION JOINT.
10.0 PRE-ENGINEERED MEAL BUILDING (PEMB) NOTES: (CONTINUED)
10.8 COORDINATE WITH ARCHITECTURAL DRAWINGS FOR OTHER PRE-ENGINEERED METAL
BUILDING REQUIREMENTS.
10.9 LATERAL DRIFT LIMITS SHALL NOT EXCEED H/480 IN ANY DIRECTION FOR A 10 YR WIND MRI PER
THE REQUIREMENTS OF UFC 3-301-01.
10.10 RIGID FRAME ANCHOR BOLTS SHALL BE DESIGNED AND FURNISHED BY THE CONTRACTOR.
ANCHOR BOLTS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER, LICENSED IN THE
PROJECT STATE, FOR THE FRAME REACTIONS PROVIDED BY THE BUILDING SUPPLIER. THE
ANCHOR BOLT DESIGN ANALYSIS SHALL BE SUBMITTED FOR APPROVAL.
11.0 SPECIAL INSTRUCTION NOTES:
PERFORM ALL TESTS AND SPECIAL INSPECTIONS PER IBC 2018, CHAPTER 17.
11.1 SPECIAL INSPECTIONS MUST BE PERFORMED IN ACCORDANCE WITH SPECIFICATION 01 45 35, THE STATEMENT OF SPECIAL INSPECTIONS, AND THE SCHEDULE OF SPECIAL INSPECTIONS.
ANY ITEM WHICH FAIL TO COMPLY WITH THE APPROVED CONSTRUCTION DOCUMENTS SHALL
IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF
DISCREPANCIES ARE NOT CORRECTED THEY SHALL BE BROUGHT TO THE ATTENTION OF THE
CONTRACTING OFFICER PRIOR TO COMPLETION OF THAT PHASE OF WORK. SPECIAL
INSPECTION AND TESTING REQUIREMENTS APPLY EQUALLY TO ALL CONTRACTOR DESIGNED
COMPONENTS.
11.2 ANY CONSTRUCTION OR MATERIAL THAT HAS FAILED INSPECTION SHALL BE SUBJECT TO
REMOVAL AND REPLACEMENT.
11.3 EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND OR SEISMIC
FORCE RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM, OR A WIND OR SEISMIC RESISTING
COMPONENT LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS, SHALL SUBMIT A WRITTEN
STATEMENT OF RESPONSIBILITY TO THE CONTRACTING OFFICER PRIOR TO THE
COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE CONTRACTOR'S STATEMENT
OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL
REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION.
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
S-002
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
G E
N E
R A
L S
TR
U
C T
U R
A L
N O
TE
S
D.R.L.
15154704
T.H.T. R.P.B.
1651220
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
M D
T
R E
V
IS
E D
A W
/1
3/
FD
FD
FD
FD
FD
FD
FD
FD
FD FD
FD
FD FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
S2
B1
S-502
SIM
2 2 2
A
B
C
D
1 2 3 4 5 6 7
T.O.S. : + 0' - 0"
T.O.S. : -1' - 6" T.O.S. : -1' - 6"
T.O.S. : + 0' - 0" T.O.S. : + 0' - 0"
T.O.S. : + 0' - 0"
E.O.S.
E.O.S.
E.O.S.
E.O.S. E.O.S.
E.O.S.
E.O.S.
S2
E.O.S.
E.O.S.
S3
S2
S2 S2
S2
3 3 3 3
B1
S-502
SIM
B1
S-502
SIM
B1
S-502
SIM
E.O.S.
E.O.S.E.O.S.
E.O.S.
S3
S3
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø
8" Ø 8" Ø
8" Ø
8" Ø 8" Ø
" 30"
30"
C4
S-502
TYP
S-502 C3
C4
S-502
TYP
S1
S1S1
S1
S1
S-502 C1
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
CJ CJ
16' - 4" 15' - 4"
T Y
P
/8
15' - 4" 16' - 4"15' - 4" 16' - 4" 16' - 4" 15' - 4"
T Y
P
/8
T Y
P
TYP
9' - 9 1/8" 9' - 9 1/8" 9' - 9 1/8" 9' - 9 1/8"
E.O.S.E.O.S.
8" Ø
A3
S-503
TYP
A3
S-503
TYP
8" Ø 8" Ø
8" Ø 8" Ø
8" Ø
32' - 3 1/2"
190' - 2"
/4
1 KEYED NOTE
SLAB PENETRATIONS,
SEE PLUMBING / MECHANICAL DRAWINGS
FLOOR DRAIN OR CLEAN OUT,
SEE PLUMBING DRAWINGS
SLAB STEP DOWN
SLOPE
2-WAY SLAB
CONSTRUCTION JOINT
SLOPE
FD
S2
CJ
PLAN
NORTH
GENERAL NOTES
WORK NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
KEY PLAN
A B
CD
The Johnson-McAdams Firm P.A.
S-103
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
S
LA
B P
LA
N
D.R.L.
15154707
T.H.T. R.P.B.
1651220
SCALE: 3/32" = 1'-0"
A1
SLAB PLAN
0' 8' 16' 32'4'
1. ELECTRICAL POWER UTILITY TRENCH
2. COMMUNICATION FACILITY TRENCH
3. PRE-ENGINEERED METAL BUILDING (PEMB) COLUMN, SEE C2/S-501
4. CENTER POINT OF SIMULATOR
5. SLAB IS TO BE SINGLE MONOLITHIC POUR WITH NO CONSTRUCTION OR
EXPANSION JOINTS.
6. COLUMN PEDESTAL REQUIRED AT INTERIOR COLUMN GRATED BEAMS,
SEE B3/S-501
1. SEE S-001 AND S-002 FOR GENERAL NOTES.
2. SEE SHEETS S-501 & S-502 FOR FOUNDATION & SLAB DETAILS AND NOTES.
3. SEE DETAIL A1/S-502 FOR SLAB SCHEDULE, FOR S1 & S2.
4. SEE MECHANICAL, ELECTRICAL, PLUMBING AND ARCHITECTURAL DRAWINGS
FOR FLOOR DRAIN AND SLAB-ON-GRADE DEPRESSION LOCATIONS AND
REQUIREMENTS.
TRUE
NORTH
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
A
M D
T
R E
V
IS
E D
A W
/1
3/
PROVIDE 90 DEGREE
STANDARD HOOK @ TOP
TOP OF PIER ELEV.
.2
C L R
M
IN
P
E N
E T
R A
T
IO
N
3" CLR TYP.
BEARING STRATUM,
SEE BORING LOG
VERT. REINF.
SEE PIER SCHEDULE
TIES
SEE PIER SCHEDULE
DOWELS (SAME
SIZE & NO OF
PIER VERTICAL
BARS UNO)
S C
H
D
S E
E G
R A
D E
B E
A M
GRADE BEAM,
SEE GRADE
BEAM SCHEDULE
S E
E S
C H
E D
U L E
S H
A F
T D
IA
M
E T
E R
CLASS "B" SPLICE
T
IE
S P
A C
IN
G
S E
E P
IE
R
S C
H E
D U
LE
6" MIN
SPLICE
LAP
SUPPORT SUPPORT
S E
E S
C H
E D
U L E
D E
P T
H
0.33 L
L2
L IS LARGER
OF L1 OR L2
33% (MIN) OF BOTTOM
BARS-2 BARS MIN
0.25 L1
L1
L IS LARGER OF L1 OR L2
0.33 L
TOP RIGHT ADDL BARS
0.33 L1
TOP CONT. BARS
AS SCHEDULED
TOP LEFT ADDL BARS
T Y
P
T Y
P
BOTTOM
BARS
TYP.
3" CLR
STIRRUPS-SEE
SCHEDULE FOR
SIZE & SPACING
0.25 L1
S T
IR
R
U P
Ø T
Y P
C
L R
M
IN
NOTES:
1. WHERE TOP BARS AT ADJACENT BEAMS DIFFER, USE GREATER BAR AREA.
2. SPLICE TOP CONTINUOUS BARS AT MID-SPAN WHERE REQUIRED, CLASS "B" TENSION SPLICE.
MID BARS
VERT. REINF. IN PIERS TO
TERMINATE IN GRADE BEAM
WITH ACI HOOK OR BEND
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
SEE SLAB SCHEDULE
FOR REINF.
SEE BEAM SCHEDULE
FOR REINF.
STIRRUP, SAME SIZE
AND SPACING AS
GRADE BEAM
6" VOID FORM
SEE PIER SCHEDULE
FOR REINF.
F.F. EL: ± 0'-0"
24"
7" 5" 12" 7" 5" 12"
24"
VERT. REINF. IN PIERS TO
TERMINATE IN GRADE BEAM
WITH ACI HOOK OR BEND
6" VOID FORM
SEE SLAB SCHEDULE
FOR REINF.
SEE BEAM SCHEDULE
FOR REINF.
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
SEE PIER SCHEDULE
FOR REINF.
F.F. EL: ± 0'-0" F.F.E.
0' - 0"
17"7"
/2
24"
VERT. REINF. IN PIERS TO
TERMINATE IN GRADE BEAM
WITH ACI HOOK OR BEND
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
SEE SLAB SCHEDULE
FOR REINF.
SEE BEAM SCHEDULE
FOR REINF., C3/S-501
STIRRUP, SAME SIZE
AND SPACING AS G.B.
6" VOID FORM
SEE PIER SCHEDULE
FOR REINF.
12" 4"
/2
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
VERT. REINF. IN PIERS TO
TERMINATE WITH ACI
HOOK OR BEND
SEE SLAB SCHEDULE
FOR REINF.
SEE BEAM SCHEDULE
FOR REINF.
STIRRUP, SAME SIZE
AND SPACING AS
GRADE BEAM
SEE SLAB SCHEDULE
FOR REINF.
6" VOID FORM
6" VOID FORM
SEE BEAM SCHEDULE
FOR REINF.
F.F. EL: ± 0'-0"
BOTTOM OF
UTILITY TRENCH,
TYP.
RECESSED FLOOR
-1' - 6"
F.F.E.
0' - 0"
1 1/4"
VERT. REINF. IN PIERS TO
TERMINATE IN GRADE BEAM
WITH ACI HOOK OR BEND
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
SEE SLAB SCHEDULE
FOR REINF.SEE BEAM SCHEDULE
FOR REINF.
STIRRUP, SAME SIZE
AND SPACING AS
GRADE BEAM
SEE SLAB SCHEDULE
FOR REINF.
6" VOID FORM
6" VOID FORM
14 3/4"
SEE PIER SCHEDULE
FOR REINF.
V A
R
IE
S
S E
E S
L A
B P
L A
N
12"
24"
VERT. REINF. IN PIERS TO
TERMINATE IN GRADE BEAM
WITH ACI HOOK OR BEND
6" VOID FORM TO
EXTEND 6" PAST G.B,
TYP.
SEE SLAB SCHEDULE
FOR REINF.
SEE BEAM SCHEDULE
FOR REINF.
STIRRUP, SAME SIZE
AND SPACING AS
GRADE BEAM
6" VOID FORM
SEE PIER SCHEDULE
FOR REINF.
F.F.
EL: ± 0'-0"
PEMB COLUMN, BASE
PLATE AND ANCHOR BOLTS
OUTLINE OF PIER BELOW
PEMB COLUMN, BASE
PLATE AND ANCHOR
BOLTS
1-1/2" GROUT
AT BASE PLATE
(4) #3 TIES AROUND
ANCHOR BOLTS
S3
S2
(4) #6 EXTEND FROM PIER
PIER
PLAN ELEVATION
NOTE:
GRADE BEAMS, PIER REINFORCING AND
VOID FORMS NOT SHOWN FOR CLARITY
GB-4
F.F.
±0'-0"
B.F.F.
-1'-6"
C
2 2
4"
1' - 4"
1' - 4"
1/2" EXP. JT. MATERIAL
AROUND COLUMN,
TYP.
1' - 1 7/8"
F.F.E.
0' - 0"
PIER, SEE SCHEDULE
GRADE BEAM,
SEE SCHEDULE
ANCHOR BOLTS TO
EXTEND A MINIMUM OF
12" INTO GRADE BEAM
STRUCT. SLAB,
SEE SCHEDULE
1/2" GROUT
7" 1"
(4) - #3 TIES AROUND
ANCHOR BOLTS
NOTE:
GRADE BEAMS, SLAB AND PIER REINFORCING NOT SHOWN FOR CLARITY.
GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
S-501
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
F O
U N
D A
T
IO
N D
E
TA
IL
S
D.R.L.
15154708
T.H.T. R.P.B.
1651220
NTSC1 DRILLED PIER DETAIL WITH GRADE BEAM
NTSC3 CONCRETE GRADE BEAM REINFORCING
1. SEE S-001 AND S-002 FOR GENERAL NOTES.
2. SEE MECHANICAL, ELECTRICAL, PLUMBING AND ARCHITECTURAL DRAWINGS
FOR FLOOR DRAIN AND SLAB-ON-GRADE DEPRESSION LOCATIONS AND
REQUIREMENTS.
NTSA1 GRADE BEAM - 1
NTSA2 GRADE BEAM - 2
NTSA3 GRADE BEAM - 3
NTSA4 GRADE BEAM - 4
NTSB1 GRADE BEAM - 5
NTSB2 GRADE BEAM - GB7 @ DOOR
PIER SCHEDULE
DIAMETER
PENETRATION
INTO BEARING
STRATUM
VERTICAL
REINF.
TIES
18" 3'-0" 8 #5 #4 @ 12"
24" 3'-0" 10 #5 #4 @ 12"
30" 3'-0" 12 #5 #4 @ 12"
36" 3'-0" 14 #5 #4 @ 12"
SCALE: 1/2" = 1'-0"
B3
INTERIOR COLUMN PEDESTAL DETAIL 1' 2' 4'0'
SCALE: 1/2" =1'-0"
NTSC2 COLUMN PEDESTAL DETAIL
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
A
M D
T
R E
V
IS
E D
A W
/1
3/
GB-7 22 18 (3) #6 N/A (3) #6 #3 @ 17
GB-6 22 18 (3) #6 N/A (3) #6 #3 @ 17
GB-5 28 16 (3) #6 N/A (3) #6 #3 @ 14
GB-4 28 16 (3) #6 N/A (3) #6 #3 @ 14
GB-3 20 24 (5) #6 N/A (5) #6 #3 @ 10
GB-2 28 24 (5) #6 N/A (5) #6 #3 @ 14
GB-1 22 24 (5) #6 N/A (5) #6 #3 @ 10
Mark DEPTH (D) (inches) WIDTH (W) (inches) TOP MID BOTTOM STIRRUPS
GRADE BEAM & REINFORCING SCHEDULE
SLAB REINFORCING SCHEDULE
MARK
THICKNESS
(T)
TOP REINF. BOTTOM REINF.
S1 6"
S2 10"
#6 @ 12" O.C., E.W.
#7 @ 7 1/2" E.W. #7 @ 7 1/2" O.C., E.W.
#6 @ 12" O.C., E.W.
S3 12 1/2" #7 @ 7 1/2" E.W. #7 @ 7 1/2" O.C., E.W.
MIN. TOP REINF.
CLEARANCE
1"
1"
4"
NOTES:
1. SLAB MARKED S3 SHALL BE PLACED IN A SINGLE MONOLITHIC POUR
WITH NO CONSTRUCTION OR EXPANSION JOINTS.
NOTES
MIN. BOTTOM
REINF. CLEARANCE
1"
1 1/2"
1 1/2"6" VOID FORM
10 MIL VAPOR BARRIER
OVER VOID FORM
T
C O
V E
R
S
C O
V E
R
S
S
/2
C O
V E
R
S
S
C O
V E
R
S
TOP REINFORCING
BOTTOM
REINFORCING
UTILITY HANGER SPACING
UTILITY PIPE MATERIAL DIAMETER SPACING
DOMESTIC WATER
FIRE PROTECTION
SANITARY
POWER
SLAB VOID FORM
EMBED PLATE/WASHER
1/2" GALV. THREADED ROD
SLAB REINF. SEE SLAB
SCHEDULE, A1/S-502
SYSTEM WASHER
VAPOR BARRIER
1/4" HARDBOARD, MIN.
SPLIT-SCORED TOP CAP
INT. SPACERS 2" O.C.,
ABOVE OR BELOW PIPE
PIPE HANGER
1/2" PLASTIC SIDE PANEL
PLUMBING VOID
#3 BENT BAR (12" O.C.)
8" VOID SPACE
6" GRAVEL BASE
BACKFILL
CLEVIS HANGER
1/2" PLASTIC SIDE PANEL
EL: VARIES
SLOPE AS REQ'D FOR UTILITY
NOTE: ALL BELOW SLAB PIPING AND CONDUITS WILL BE INSTALLED AS INDICATED ABOVE
COPPER
D.I.
PVC
NA
2"
8"
2",3",4"
NA
4'
AT STUB UP
4'
NA
/2
1' - 4" 0' - 8"
POWER TRENCH
F.F. EL: ± 0'-0"
CLR.
12"
S3
1 1
1 1
CONT. L1-1/2" x 1-1/2" x 3/16", E.S.
CUT VERT. LEG AND GRIND SMOOTH
PRIOR TO INSTALLATION W/ 1/2" Ø x
6" HEADED STUD @ 24" O.C..
PL 3/8 x 10 3/8 RAISED PATTERN FLOOR PLATE.
PROVIDE PLATES IN SEGMENTS NOT TO EXCEED
50 LBS. (2) 1" Ø LIFTING HOLES AT EACH END OF
SEGMENT, CENTERED IN PLATE DEPTH
T Y
P
C L R
" C
L R
#6 BARS - EXTEND 2'-0" BEYOND
TRENCH RECESSION 3 SIDES, TYP
PL 3/8x14 3/8 RAISED PATTERN FLOOR PLATE.
PROVIDE PLATES IN SEGMENTS NOT TO
EXCEED 50 LBS. (2) 1" Ø LIFTING HOLES AT E.E.
OF SEGMENT, CENTERED IN PLATE DEPTH
FMS OTW S.O.G.,
SEE SLAB PLAN
C L R
TYP
LAP
12" VOID FORM,
TYP.
BENT BARS
CLR
8"
COMM. TRENCH
6' - 7"
NOTE:
CONSTRUCTION JOINTS MAY ONLY BE USED IN INDICATED AREAS.
NO CONSTRUCTION JOINTS WILL BE ALLOWED IN OTW / SIMULATOR AREAS.
GALV.
KEYWAY PROVIDE (1) ADDN'L BEAM
STIRRUP SIDE OF CONSTRUCTION
JOINT AND EACH END OF ADDN'L
DOWEL
CONSTRUCTION JOINT
CONSTRUCTION JOINT NOTES:
1. GENERAL CONTRACTOR SHALL SUBMIT DESIRED CONSTRUCTION JOINT LAYOUT
AS A SHOP DRAWING FOR APPROVAL, A MINIMUM OF TWO WEEKS PRIOR TO POUR.
2. CONSTRUCTION JOINT LOCATIONS SHALL BE CO-ORDINATED WITH REINFORCING
STEEL SUPPLIER AND ERECTOR.
3. JOINT LOCATIONS SHALL BE WITHIN TWO FEET EITHER SIDE OF BEAM MID-SPAN.
4. FOR JOINT LOCATIONS OTHER THAN WITHIN TWO FEET EITHER SIDE OF THE BEAM
MID-SPAN, CONTRACTOR SHALL CO-ORDINATE REQUIRED ADDITIONAL
REINFORCEMENT WITH THE ENGINEER ON THE SHOP DRAWINGS.
B M
D
E P
T H
D
D /3
D /3
D /3
3"3" 3"3"
3"
EQ EQ
1" T
A P
E R C.J.
CONT. T & B REINF. @
C.J.ADDN'L. DWL. USE
(2) #5 x 4'-0" T & B
F.F. EL: ± 0'-0"
O" O"
O
O
O" O"
O
O
CORNER BARS TO
MATCH TOP, BOTTOM
AND FACE BARS
3'-0"
3' -0
PLAN VIEW
GRADE BEAM "T"
INTERSECTION
PLAN VIEW
GRADE BEAM
CORNER
BOTTOM REINFORCING TO
BE CONTINUOUS ACROSS
JOINT - NO SPLICE
PERMITTEDNOTE:
CONSTRUCTION JOINTS MAY ONLY BE USED IN INDICATED AREAS.
NO CONSTRUCTION JOINTS WILL BE ALLOWED IN OTW / SIMULATOR
AREAS.
.SEE SCHEDULE FOR
SLAB THICKNESS, TYP
CONSTRUCTION JOINT, LOCATE
AT MIDSPAN OF SLAB
F.F.
EL: ± 0'-0"
SEE SCHEDULE FOR
MIN CLEARANCE, TYP
ADJUST SPACING AS REQ'D TO
MAINTAIN MIN. OF 2" HORIZ.
CLEARANCE
TOP REINFORCING MAY BE
SPLICED AT JOINT
2" TYP
GENERAL NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
S-502
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
S
LA
B D
E T
A
IL
S
D.R.L.
15154709
T.H.T. R.P.B.
1651220
NTSA1 TYPICAL SLAB DETAIL
NTSA4 TYPICAL UTILITY VOID FORM
1. SEE S-001 AND S-002 FOR GENERAL NOTES.
2. SEE MECHANICAL, ELECTRICAL, PLUMBING AND ARCHITECTURAL DRAWINGS
FOR FLOOR DRAIN AND SLAB-ON-GRADE DEPRESSION LOCATIONS AND
REQUIREMENTS.
NTSB1 FMS OTW TRENCH DETAIL
NTSC1
GRADE BEAM CONSTRUCTION JOINTS,
TYPICAL
NTSC3
GRADE BEAM REINF. STEEL CORNER
BARS, TYPICAL
NTSC4 SLAB CONSTRUCTION JOINT, TYPICAL
S Y
M D
E S
C R
IP
TI
O N
D A
TE
A
P P
R
A
M D
T
R E
V
IS
E D
A W
/1
3/
A-201
B1
A-202
C1
A-202
A1
A-201
C1
1 2 3 4 5 6 7
B
C
D
A
8" OGEE GUTTER WITH
4"x4" DOWNSPOUTS
8" OGEE GUTTER WITH
4"x4" DOWNSPOUTS
STANDING SEAM METAL
ROOF SYSTEM
GABLE TRIM
RIDGE CAP
36' - 6 7/8" 21' - 6 1/2" 36' - 6 3/4" 36' - 4 3/4" 21' - 10 5/8"
20' - 1 7/8" 23' - 0" 24' - 2" 25' - 0" 25' - 0" 22' - 0" 25' - 0" 25' - 0"
195' - 5 1/4"
/4
/2
/ 1 '-0
/ 1
'-0
A1
A-301
C1
A-301
C1
A-302
A1
A-302
C1
A-303
A1
A-303
DOWNSPOUT LOCATIONS
DOWNSPOUT LOCATIONS
3" PLUMBING VENT SEE
DETAIL C1/A-606 AND
PLUMBING DRAWINGS.
8" BOILER FLUE SEE
DETAIL A1/A-606 AND
MECHANICAL DRAWINGS
8" BOILER INTAKE AIR SEE
DETAIL A3/A-606 AND
MECHANICAL DRAWINGS.
2.1 2.9 5.1 5.9
GPS ANTENNA TYP. SEE DETAIL A1/A-607
2' - 0"
OUTLINE OF BUILDING BELOW
TYP. ROOF OVERHANG
36' - 4 5/8"
PLAN
NORTH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
KEY PLAN
A B
CD
The Johnson-McAdams Firm P.A.
A-103
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
R O
O F
P
LA
N
D.R.L.
15154717
R.E.H J.L.F.
1651221
SCALE: 3/32" = 1'-0"
A1
ROOF PLAN
0' 8' 16' 32'4'
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
M D
T
R
E V
IS
E
D N
O T
E J
F
4/
/2
COCKPIT
OTW/
DISPLAY
ROOM
HVAC SUPPLY TYPICAL SEE
MECHANICAL DRAWINGS
HVAC SUPPLY AT FLOOR
TYPICAL SEE MECHANICAL
DRAWINGS
HVAC RETURN DUCT/DIFFUSER
LOCATED AT CENTER OF DOME
WALL LIGHT FIXTURE TYPICAL
SEE ELECTRICAL DRAWINGS
CENTER OF TRAINER DOME.
(TRAINER NOT SHOWN FOR CLARITY.)
15' - 0" DIMENSIONS FOR TRAINER ARE FROM FACE
OF GYPSUM BOARD TO CENTER OF TRAINER DOME.
D
IM
E N
S
IO
N S
F O
R T
R A
IN
E
R A
R E
F R
O M
F A
C E
O F
G Y
P S
U M
B O
A R
D T
O C
E N
T E
R O
F T
R A
IN
E
R D
O M
E
CEILING SLOPE
3 4
B
C
FIRE SPRINKLER HEAD, TYP.
45.06°
52.24°
.9
50.47° 52.93°
.2
.1
2°
' - 1
/2 " 9
/8
9' - 8 3/8"
9' - 2" ' - 0
8' -
/4
10' - 3"
FURRING ABOVE FURRING ABOVE
UNISTRUT FRAMING FOR
EQUIPMENT SUPPORT AT 4"
BELOW SLOPED CEILING.
ASSUME MEP LOAD OF 10
PSF.
2"
CENTER LINE
OF TRAINER
.4
COCKPIT
OTW/
DISPLAY
ROOM
WALL LIGHT FIXTURE
TYPICAL SEE ELECTRICAL
DRAWINGS
HVAC SUPPLY AT FLOOR
TYPICAL SEE MECHANICAL
DRAWINGS
HVAC SUPPLY TYPICAL SEE
MECHANICAL DRAWINGS
HVAC RETURN DUCT/DIFFUSER
LOCATED AT CENTER OF DOME.
CENTER OF TRAINER DOME.
(TRAINER NOT SHOWN FOR CLARITY.)
D
IM
E N
S
IO
N S
F O
R T
R A
IN
E
R A
R E
F R
O M
F A
C E
O F
G Y
P S
U M
B O
A R
D T
O C
E N
T E
R O
F T
R A
IN
E
R D
O M
E
15' - 0" DIMENSIONS FOR TRAINER ARE FROM FACE
OF GYPSUM BOARD TO CENTER OF TRAINER DOME.
CEILING SLOPE
48.52°
45.05°
.8
7°
.8
° 5
.2
' - 9
/8
50.89° 52.57°
9' -
/8
9' - 6 1/2" 10' - 4
7/8"
/4
8' - 8 1/4"
/8
1 2
B
C
FIRE SPRINKLER HEAD, TYP.
FURRING ABOVE FURRING ABOVE
UNISTRUT FRAMING FOR
EQUIPMENT SUPPORT AT 4"
BELOW SLOPED CEILING.
ASSUME MEP LOAD OF 10
PSF.
2"
.1
CENTER LINE OF TRAINER
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-106
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
E N
LA
R
G E
D C
O M
P O
S
IT
E C
O O
R D
IN
A
T
IO
N P
LA
N
D.R.L.
15154720
R.E.H J.L.F.
1651221
SCALE: 3/8" = 1'-0" (A-104)
A4
SIMULATOR BAY 136 ENLARGED COMPOSITE COORDINATION
PLAN
PLAN
NORTH
0' 2' 4' 6'
PLAN
NORTH
0' 2' 4' 6'SCALE: 3/8" = 1'-0" (A-104)
A1
SIMULATOR BAY 138 ENLARGED COMPOSITE COORDINATION
PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
/2
2/
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
1 1
COCKPIT
OTW/
DISPLAY
ROOM
WALL LIGHT FIXTURE
TYPICAL SEE ELECTRICAL
DRAWINGS
HVAC SUPPLY AT FLOOR
TYPICAL SEE MECHANICAL
DRAWINGS
HVAC SUPPLY TYPICAL SEE
MECHANICAL DRAWINGS
HVAC RETURN DUCT/DIFFUSER
LOCATED AT CENTER OF DOME.
CEILING SLOPE
B
C
4 5
.2
4°
45.06°
49.15°
.2
52.93° 50.47°
.9
9' -
9' - 8 3/8"
' - 1
/8 " 9
/2
10' - 3
8' - 6 3/4"
FIRE SPRINKLER HEAD, TYP.
15' - 0" DIMENSIONS FOR TRAINER ARE FROM FACE
OF GYPSUM BOARD TO CENTER OF TRAINER DOME.
D
IM
E N
S
IO
N S
F O
R T
R A
IN
E
R A
R E
F R
O M
F A
C E
O F
G Y
P S
U M
B O
A R
D T
O C
E N
T E
R O
F T
R A
IN
E
R D
O M
E
CENTER OF TRAINER DOME
(TRAINER NOT SHOWN FOR CLARITY.)
FURRING ABOVE FURRING ABOVE
UNISTRUT FRAMING FOR
EQUIPMENT SUPPORT AT 4"
BELOW SLOPED CEILING.
ASSUME MEP LOAD OF 10
PSF.
2"
CENTER LINE OF TRAINER
.4
COCKPIT
OTW/
DISPLAY
ROOM
HVAC SUPPLY TYPICAL SEE
MECHANICAL DRAWINGS
HVAC SUPPLY AT FLOOR
TYPICAL SEE MECHANICAL
DRAWINGS
HVAC RETURN DUCT/DIFFUSER
LOCATED AT CENTER OF DOME.
WALL LIGHT FIXTURE TYPICAL
SEE ELECTRICAL DRAWINGS
CEILING SLOPE
B
C
6 7
FIRE SPRINKLER HEAD, TYP.
D
IM
E N
S
IO
N S
F O
R T
R A
IN
E
R A
R E
F R
O M
F A
C E
O F
G Y
P S
U M
B O
A R
D T
O C
E N
T E
R O
F T
R A
IN
E
R D
O M
E
15' - 0" DIMENSIONS FOR TRAINER ARE FROM FACE
OF GYPSUM BOARD TO CENTER OF TRAINER DOME
.7
4°
45.06°
52.63°
.4
50.74°52.71°
.6
' - 1
/8 " 9
/8
9' - 7 1/4"
9' - 1"
' - 1
/ 8
8' -
/4
10' - 4 1/8"
CENTER OF TRAINER DOME,
(TRAINER NOT SHOWN FOR CLARITY.)
FURRING ABOVE FURRING ABOVE
UNISTRUT FRAMING FOR
EQUIPMENT SUPPORT AT 4"
BELOW SLOPED CEILING.
ASSUME MEP LOAD OF 10
PSF.
2"
CENTER LINE
OF TRAINER
.2
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-107
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
E N
LA
R
G E
D C
O M
P O
S
IT
E C
O O
R D
IN
A
T
IO
N P
LA
N
D.R.L.
15154721
R.E.H J.L.F.
1651221
SCALE: 3/8" = 1'-0" (A-104)
A1
SIMULATOR BAY 125 ENLARGED COMPOSITE COORDINATION
PLAN
SCALE: 3/8" = 1'-0" (A-104)
A4
SIMULATOR BAY 123 ENLARGED COMPOSITE COORDINATION
PLAN
PLAN
NORTH
0' 2' 4' 6'
PLAN
NORTH
0' 2' 4' 6'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
D
UNSECURE
OPEN OFFICE
ELCT. ROOM
VESTIBULE
OFFICE
OFFICE
JAN.
WOMEN'S
RESTROOM
BREAK ROOM
MEN'S
RESTROOM
MAN TRAP
COMM.
MOTHER'S
ROOM
CORRIDOR
5' - 6 7/8" 4' - 11 7/8" 12' - 8" 8' - 5 5/8" 5' - 5 5/8" 7' - 3 1/4" 11' - 9 1/8" 0' - 5 7/8"
/4
/4
/4
/8
/8
/4
18' - 6 1/4"
/2
/4
A-401
A1
A-401
B4
6' - 4 7/8"
2' - 2"
2' - 6"
2' - 2" 2' - 2"
2' - 9"
FE FE
2' - 7 1/4"
FD
FD
4' - 4 1/8"
4' - 4 3/8"
2' - 2 1/2" 2' - 2 1/2"
/4
33' - 0 7/8" 9' - 3 1/8" 9' - 3 1/8" 8' - 8 3/8" 9' - 8 1/8" 12' - 9 3/4" 4' - 11 1/2"1' - 11 3/8" 12' - 9 1/2"
/8
/8
CELL PHONE
LOCKERS, INSTALL
PER MANUFACTURERS
INSTRUCTIONS
FIRE EXTINGUISHER CABINET
FE
PARTITION
AS SCHEDULED
FD 3" FLOOR DRAIN
PLAN
NORTH
WORK NOTES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
KEY PLAN
A B
CD
The Johnson-McAdams Firm P.A.
A-114
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
A R
E A
P
LA
N D
D.R.L.
15154728
R.E.H J.L.F.
1651221
SCALE: 3/16" = 1'-0"
A1
AREA PLAN D
PLAN
NORTH
0' 4' 8' 12'
1. CORNER GUARD AS DETAILED AND SPECIFIED.
LEGEND
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
1/
/2
A
M D
T
R
E V
IS
E
D N
O T
E J
F
4/
/2
OVERALL FLOOR
PLAN
0' - 0" F.F.E.
0' - 0"
CEILING HT.
10' - 0"
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
POWER AND DATA, SEE ELECTRICAL
OVERALL FLOOR
PLAN
0' - 0" F.F.E.
0' - 0"
CEILING HT.
10' - 0"
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
POWER AND DATA, SEE ELECTRICAL
OVERALL FLOOR
PLAN
0' - 0" F.F.E.
0' - 0"
CEILING HT.
10' - 0"
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
OVERALL FLOOR
PLAN
0' - 0" F.F.E.
0' - 0"
CEILING HT.
10' - 0"
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
WORKSTATION, SEE INTERIORS.
TASK CHAIR, SEE INTERIORS.
WHITEBOARD, SEE INTERIORS
SEE ELECTRICAL
POWER AND DATA, SEE ELECTRICAL
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-204
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
IN
T
E R
IO
R
E
LE
V A
T
IO
N S
D.R.L.
15154732
R.E.H J.L.F.
1651221
SCALE: 3/8" = 1'-0" (A-111)
C1
INTERIOR ELEVATION ROOM 128 SOUTH
SCALE: 3/8" = 1'-0" (A-107)
C3
INTERIOR ELEVATION ROOM 128 WEST
0' 2' 4' 6' 0' 2' 4' 6'
SCALE: 3/8" = 1'-0" (A-111)
A1
INTERIOR ELEVATION ROOM 128 NORTH
SCALE: 3/8" = 1'-0" (A-106)
A3
INTERIOR ELEVATION ROOM 128 EAST
0' 2' 4' 6' 0' 2' 4' 6'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
21NOTE:
FURNITURE IS SHOWN FOR CLARIFICATION ONLY.
FURNITURE INCLUDING WHITEBOARD WILL BE
ACQUIRED VIA A PLANNED CONSTRUCTION
CONTRACT MODIFICATION AT A LATER DATE.
FINISHED FLOOR
0' - 0"
EAVE HEIGHT
20' - 0" A.F.F.
8" OGEE GUTTER
0' - 0 3/4"
" ALUMINUM SKIRT
W/ CONT. CLEAT
ALUMINUM SOFFIT PANEL
0' - 1 1/4"
ALUMINUM FASCIA
W/ "J" TRIM
2' - 0"
12" EAVE STRUT
8" CHANNEL. ATTACH TO
OUTRIGGERS AT COLUMN LINE
OUTRIGGER
B
SPRAY FOAM AIR BARRIER
ROOF SYSTEM CLIP ANCHOR
W/ R-2.5 THERMAL SPACER
ROOF EDGE CLIP W/ R-2.5
THERMAL SPACER
24 GA. STANDING SEAM METAL ROOF
PANEL
R-11 FIBERGLASS SOUND
ATTENUATION INSULATION
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION W/ 1" STEEL
BANDING PERPENDICULAR TO PURLINS
@30" O.C.
12" ROOF PURLIN
3/8" DIA. THREADED SUSPENSION
RODS @ MAX. SPACING 48"O.C.
PROVIDE (2) BEVELED WASHERS
AND (2) SOUND DEADENING 60
SHORE HARDNESS NEOPRENE
WASHERS AT EACH CONNECTION
1-5/8" x 2-7/16" x 12GA.
CHANNEL @ 48" O.C. RUNNING
PARALLEL W/ PEMB FRAME
7/8" x 20GA. HAT CHANNEL @ 16" O.C.
3/8" DIA. THREADED SUSPENSION
RODS @ MAX. SPACING 48"O.C.
PROVIDE (2) BEVELED WASHERS
AND (2) SOUND DEADENING 60
SHORE HARDNESS NEOPRENE
WASHERS AT CONNECTION TO
UPPER CHANNEL. PROVIDE 1-5/8" x 2-7/16" x 12GA. CHANNEL @ 48"MAX.
PERPENDICULAR TO UPPER
CHANNEL W/ (2) SELF LOCKING
NUTS. CHANNEL FOR EQUIPMENT
SUSPENSION SUPPORT.
5/8" GYPSUM BOARD
A-611
C1
DOOR AS SCHEDULED
MASONRY VENEER
WALL TIES @ 16"O.C. EA. WAY
2" SPRAY FOAM AIR BARRIER
5/8" GYPSUM SHEATHING
(2) LAYERS 5/8" GYP.BD. ON 1"
"Z" @ 16"O.C. VERT.
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION
6" x 16GA. STEEL STUDS @ 16"O.C.
2' - 7 7/8"
FINISHED FLOOR
0' - 0"
CEILING HEIGHT
AS SCHEDULED
EAVE HEIGHT
13' - 11-3/4" A.F.F.
D
8" OGEE GUTTER
0' - 0 3/4"
"ALUMINUM SKIRT
W/ CONT. CLEAT
ALUMINUM
SOFFIT PANEL
0' - 1 1/4"
ALUMINUM FASCIA
W/ "J" TRIM
12" EAVE STRUT
8" CHANNEL. ATTACH TO
OUTRIGGERS AT
COLUMN LINE
OUTRIGGER
SPRAY APPLIED AIR BARRIER
ROOF EDGE CLIP W/R-2.5
THERMAL SPACER
ROOF SYSTEM CLIP ANCHOR
W/R-2.5 THERMAL SPACER
MASONRY VENEER
WALL TIES @ 16" O.C.
EA. WAY
2" SPRAY FOAM
AIR BARRIER
5/8" GYPSUM SHEATHING
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION
6" x 16GA. STEEL
STUDS @ 16"O.C.
5/8" GYP.BD.
R-11 FIBERGLASS SOUND
ATTENUATION INSULATION
24 GA. STANDING SEAM METAL ROOF
PANEL
2' - 0"
THROUGH WALL FLASHING CONT.
MESH WEEPS @ 32" O.C.
2' - 7 7/8"
FINISHED FLOOR
0' - 0"
EAVE HEIGHT
16' - 1 5/8" A.F.F.
8" OGEE GUTTER
0' - 0 3/4"
" ALUMINUM SKIRT
W/ CONT. CLEAT
ALUMINUM
SOFFIT PANEL
12" EAVE STRUT
8" CHANNEL. ATTACH TO
OUTRIGGERS AT
COLUMN LINE
OUTRIGGER
SPRAY FOAM
AIR BARRIER
ROOF EDGE CLIP W/R-2.5
THERMAL SPACER
ROOF SYSTEM CLIP ANCHOR
W/R-2.5 THERMAL SPACER
24 GA. STANDING SEAM
METAL ROOF PANEL
R-11 FIBERGLASS SOUND
ATTENUATION INSULATION
MASONRY VENEER
WALL TIES @ 16" O.C.
EA. WAY
1" SPRAY APPLIED
AIR BARRIER
5/8" GYPSUM SHEATHING
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION
6" x 16GA. STEEL
STUDS @ 16"O.C.
0' - 1 1/4"
ALUMINUM FASCIA
W/ "J" TRIM
THROUGH WALL FLASHING CONT.
MESH WEEPS @ 32" O.C.
2' - 0"
5/8" GYPSUM BOARD
A
2' - 7 7/8"
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-311
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
W A
LL
S
E C
T
IO
N S
D.R.L.
15154737
R.E.H J.L.F.
1651221
0' 1' 2' 3' 0' 1' 2' 3' 0' 1' 2' 3'
SCALE: 3/4" = 1'-0" (A-301)
A1
WALL SECTION (TYPE E1 WALL)
SCALE: 3/4" = 1'-0" (A-301)
A3
WALL SECTION (TYPE E2 WALL)
SCALE: 3/4" = 1'-0" (A-301)
A4
WALL SECTION (TYPE E2 WALL)
PEMB FRAMING CONCEALED BY FURRING.
FOUNDATION, SEE STRUCTURAL
FOUNDATION, SEE STRUCTURAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
/2
2/
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
FINISHED FLOOR
0' - 0"
CEILING HEIGHT
AS SCHEDULED
RECESSED FLOOR
-1' - 6"
B
5/8" GYP.BD. ON 1" "Z" @
16"O.C. VERT.
3 1/2" SOUND
ATTENUATION INSULATION
3-5/8" x 16GA. STEEL
STUDS @ 16"O.C.
RAISED FLOORING SYSTEM
AS SPECIFIED
SEE A1/A-604 FOR
STC RATED ROOF SYSTEM
SEE A3/A-604 FOR NON
STC RATED ROOF SYSTEM
3-5/8" x 16GA. STEEL
STUDS @ 16"O.C.
PEMB FRAME CROSS
BRACING CHASE.
5/8" GYPSUM BOARD
7/8" HATT CHANNEL @ 16"O.C.
CONT. DEFLECTION TRACK
BEAMS SEE S-503
FOUNDATION, SEE
STRUCTURAL
FURRING AROUND PEMB
FRAMING BEYOND
FINISHED FLOOR
0' - 0"
CEILING HEIGHT
AS SCHEDULED
EAVE HEIGHT
13' - 11-3/4" A.F.F.
D
8" OGEE GUTTER
0' - 0 3/4"
"ALUMINUM SKIRT
W/ CONT. CLEAT
ALUMINUM
SOFFIT PANEL
0' - 1 1/4"
ALUMINUM FASCIA
W/ "J" TRIM
12" EAVE STRUT
8" CHANNEL. ATTACH TO
OUTRIGGERS AT
COLUMN LINE
OUTRIGGER
SPRAY APPLIED AIR BARRIER
ROOF EDGE CLIP W/R-2.5
THERMAL SPACER
ROOF SYSTEM CLIP ANCHOR
W/R-2.5 THERMAL SPACER
MASONRY VENEER
WALL TIES @ 16" O.C.
EA. WAY
2" SPRAY FOAM
AIR BARRIER
5/8" GYPSUM SHEATHING
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION
6" x 16GA. STEEL
STUDS @ 16"O.C.
5/8" GYP.BD.
R-11 FIBERGLASS SOUND
ATTENUATION INSULATION
24 GA. STANDING SEAM METAL ROOF
PANEL
2' - 0"
ALUMINUM DOOR
AND FRAME
AS SCHEDULED
STEEL LINTEL
THROUGH WALL FLASHING CONT.
MESH WEEPS @ 32" O.C.
2' - 7 7/8"
FOUNDATION, SEE STRUCTURAL
CANOPY, SEE DETAIL A3/A-605
THRESHOLD AS SPECIFIED.
PROVIDE (3) ANCHORS MIN.
FINISHED FLOOR
0' - 0"
CEILING HEIGHT
AS SCHEDULED
TOP OF STEEL
VARIES
RECESSED FLOOR
-1' - 6"
THROUGH WALL FLASHING CONT.
MESH WEEPS @ 32" O.C.
8" CHANNEL. ATTACH TO
OUTRIGGERS AT
COLUMN LINE
R-11 FIBERGLASS SOUND
ATTENUATION INSULATION
24 GA. STANDING SEAM METAL ROOF
PANEL
MASONRY VENEER
WALL TIES @ 16" O.C.
EA. WAY
2" SPRAY FOAM
AIR BARRIER
5/8" GYPSUM SHEATHING
6" x 16GA. STEEL
STUDS @ 16"O.C.
PEMB FRAME SEE
STRUCTURAL
SEE A1/A-604 FOR
STC RATED ROOF
SYSTEM
ALUMINUM
SOFFIT PANEL
0' - 1 1/4"
ALUMINUM FASCIA
W/ "J" TRIM
3' - 0"
2' - 0"
(2) LAYERS 5/8" GYP.BD. ON 1"
"Z" @ 16"O.C. VERT.
FOUNDATION, SEE STRUCTURAL
ALUMINUM SKIRT
W/ CONT. CLEAT
0' - 0 3/4"
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-312
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
W A
LL
S
E C
T
IO
N S
D.R.L.
15154738
R.E.H J.L.F.
1651221
0' 1' 2' 3' 0' 1' 2' 3'SCALE: 3/4" = 1'-0" (A-301)
A1
WALL SECTION
SCALE: 3/4" = 1'-0" (A-301)
A3
WALL SECTION (TYPE E2 WALL)
SCALE: 3/4" = 1'-0" (A-303)
A4
WALL SECTION (TYPE E1 WALL)
0' 1' 2' 3'
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
/2
2/
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
RECESSED FLOOR
-1' - 6"
FINISHED FLOOR
0' - 0"
FOUNDATION. SEE STRUCTURAL
RAISED FLOORING SYSTEM AS SPECIFIED
CASING BEAD WITH SEALANT
1" "Z" FURRING @ 16"O.C. VERT.
SEE PARTITION TYPES SHEETS A-501, A-502
CASING BEAD WITH SEALANT
WALL BASE AS SCHEDULED
2-1/2" x 14GA. STEEL
STUD @ PURLIN
V A
R
IE
S C
O O
R D
IN
A
T E
W
IT
H R
IG
ID
F R
A M
E D
E P
T H
P E
R M
A N
U F
A C
T U
R E
RS
E
E A
-A
PEMB FRAME
SEE PARTITION TYPES, SHEET A-501, A-502
5/8" GYP.BD.
4" x 20GA STUD HORIZONTAL
@ BOTTOM OF CEILING
7/8" HAT CHANNEL @ 16" O.C.
PROVIDE 1/8" THICK x 4" WIDE CLOSED CELL FOAM SEAL SOUND
PROOFING TAPE BETWEEN STUD AND PURLIN. PROVIDE NEOPRENE
WASHERS AT FASTENER HEAD. NO STEEL TO STEEL CONNECTION
0' - 1"
MINIMUM SEPARATION
BETWEEN PEMB FRAME
AND STUD
M
IN
IM
U
M
R-19 FIBERGLASS SOUND
ATTENUATION INSULATION W/ 1" STEEL
BANDING PERPENDICULAR TO PURLINS
@30" O.C.
12" ROOF PURLIN
7/8" x 20GA. HAT CHANNEL @ 16" O.C.
1/2" DIA. THREADED SUSPENSION RODS @ PURLIN.
PROVIDE (2) BEVELED WASHERS AND (2) SOUND
DEADENING 60 SHORE HARDNESS NEOPRENE
WASHERS AT CONNECTION TO ROOF PURLIN AND
UPPER CHANNEL.
PROVIDE 1-5/8" x 2-7/16" x 12GA. CHANNEL @
48"MAX. PARALLEL WITH PEMB FRAME. (CHANNEL
FOR EQUIPMENT SUPPORT @ NON-STC RATED
ROOF SYSTEM)
PROVIDE UNISTRUT FRAMING @ 48"MAX.
PERPENDICULAR TO UPPER CHANNEL. CHANNEL
FOR EQUIPMENT SUSPENSION SUPPORT. CEILING.
ASSUME MEP LOAD OF 10 PSF.
3/8"DIA THREADED ROD @ 48"MAX. SPACING W/ (2)
BEVELED WASHERS AND (2) NEOPRENE WASHERS
@ UPPER CHANNEL. (2) SELF LOCKING NUTS @
LOWER CHANNEL.
(2) LAYERS 5/8"
TYPE "X" GYP.BD.
EQUIPMENT SUPPORT WIRE/STRAP.
COORDINATE WITH MECHANICAL,
ELECTRICAL, AND FIRE PROTECTION
SUB-CONTRACTORS.
R-11 FIBERGLASS SOUND ATTENUATION INSULATION
R-2.5 THERMAL SPACER
24 GA. STANDING SEAM METAL ROOF PANEL
/4
/8
/8
SEE A1/A-604 FOR
STC RATED ROOF SYSTEM
UNISTRUT FOR
PROJECTOR SUPPORT,
COORDINATE NUMBER
AND SPACING WITH AV
CONTRACTOR
12"x12"x3/4" PLYWOOD
ANCHORED TO
UNISTRUT.
VIBRATION ISOLATION
STRUCTURAL CEILING
ADAPTER
PROJECTOR SUPPORT
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-604
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
D E
T A
IL
S
D.R.L.
15154747
R.E.H J.L.F.
1651221
SCALE: 1 1/2" = 1'-0" (A-302)
C1
DETAIL AT RAISED FLOOR AND PARTITION
SCALE: 1 1/2" = 1'-0" (A-302)
C2
FURRING AT RIGID FRAME AT STC RATED ROOF ASSEMBLY
SCALE: 1 1/2" = 1'-0"
A1
STC-58 ROOF SYSTEM- MBMA DATA FILE NO. G9721.04 (UL P516)
SCALE: 1 1/2" = 1'-0"
A3
NON STC RATED ROOF SYSTEM
4"0' 8" 1'-4" 4"0' 8" 1'-4"
4"0' 8" 1'-4" 4"0' 8" 1'-4"
SCALE: 1 1/2" = 1'-0" (A-301)
C4
DETAIL AT TOP OF PARTITION
4"0' 8" 1'-4"
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
PLUMBING VENT SEE ROOF PLAN FOR SIZE.
SEE PLUMBING DRAWINGS
BAND CLAMP
PRE-FABRICATED ROOF
PENETRATION BOOT
STANDING SEAM METAL ROOF
R-11 FIBERGLASS INSULATION
R-19 FIBERGLASS INSULATION W/ 1"
STEEL BANDING PERPENDICULAR
TO PURLINS @30" O.C.
12" ROOF PURLIN
ROOF SYSTEM CLIP ANCHOR
/ R-2.5 THERMAL SPACER
STRUCTURAL PEMB FRAME BEYOND
R-11 FIBERGLASS INSULATION
R-19 FIBERGLASS INSULATION W/ 1"
STEEL BANDING PERPENDICULAR
TO PURLINS @30" O.C.
12" ROOF PURLIN
ROOF SYSTEM CLIP ANCHOR
/ R-2.5 THERMAL SPACER
STRUCTURAL PEMB FRAME BEYOND
BOILER FLUE SEE PLAN FOR SIZE
STAINLESS STEEL CLAMPING COLLAR
METAL RAIN HOOD TO MATCH ROOF
COLOR
HIGH TEMPERATURE BOOT
CLAMPING RING FASTENERS SET IN MASTIC
STAINLESS STEEL BAND CLAMP
STANDING SEAM METAL ROOF
R-19 FIBERGLASS INSULATION W/ 1"
STEEL BANDING PERPENDICULAR
TO PURLINS @30" O.C.
STRUCTURAL PEMB FRAME BEYOND
R-11 FIBERGLASS INSULATION
12" ROOF PURLIN
ROOF SYSTEM CLIP ANCHOR
/ R-2.5 THERMAL SPACER
BOILER INTAKE AIR SEE PLAN FOR SIZE
CURB MOUNTED INTAKE AIR HOOD
SEE MECHANICAL
PREFABRICATED ROOF CURB
WATER DIVERTER
STANDING SEAM METAL ROOF
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-606
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
R O
O F
D E
TA
IL
S
D.R.L.
15154749
R.E.H J.L.F.
1651221
SCALE: 1 1/2" = 1'-0"
C1
PLUMBING VENT STACK DETAIL
SCALE: 1 1/2" = 1'-0"
A1
BOILER FLUE DETAIL
4"0' 8" 1'-4"
4"0' 8" 1'-4" SCALE: 1 1/2" = 1'-0"
A3
BOILER INTAKE DETAIL
4"0' 8" 1'-4"
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
/2
2/
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
2" ANTENNA CONDUIT
BAND CLAMP
PRE-FABRICATED ROOF
PENETRATION BOOT
STANDING SEAM METAL ROOF
R-11 FIBERGLASS INSULATION
12" ROOF PURLIN
ROOF SYSTEM CLIP ANCHOR
/ R-2.5 THERMAL SPACER
STRUCTURAL PEMB FRAME
BEYOND
GPS ANTENNA AND
COAX PROVIDED AND
INSTALLED BY
LOCKHEED MARTIN
PEMB CHANNEL CLIPPED AT EACH
END TO THE ROOF PURLINS AT
EACH ANTENNA LOCATION.
ANCHOR CONDUIT
TO CHANNEL
1/8" 7x19 STAINLESS STEEL WIRE CABLE
ANTENNA CONDUIT SUPPORT (3) PER ANTENNA
CLIP ANTENNA SUPPORT GUY WIRE TO RIB
OF STANDING SEAM METAL ROOF WITH NON
PENETRATING STANDING SEAM RIB CLIP
WEATHERHEAD
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
DRAWFORM REVISION: 31 JANUARY 2017
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
S
O U
T H
E A
S T
N A
S J
R B
F
O R
T W
O R
T H
T
X
N A
V Y
A
IR
S T
A T
IO
N
J O
IN
T
R E
S E
R V
E B
A S
E F
O R
T W
O R
T H
T
E X
A S
AS NOTED
U N
C L A
S S
IF
IE
D
The Johnson-McAdams Firm P.A.
A-607
F A
F L
IG
H T
S
IM
U L A
T O
R F
A C
IL
IT
Y
R O
O F
D E
T A
IL
D.R.L.
15154750
R.E.H J.L.F.
1651221
SCALE: 1 1/2" = 1'-0"
A1
ANTENNA MOUNT DETAIL
4"0' 8" 1'-4"
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
R
T A
S U
B M
IT
T
A L
/2
2/
A
M D
T
R E
V
IS
E D
N O
T E
J F
/1
3/
GENERAL ROOM FINISH SCHEDULE NOTES:
REFER TO SPECIFICATIONS FOR THE BASIS OF DESIGN OR EQUIVALENT
MANUFACTURER TECHNICAL REQUIREMENTS.
REFER TO INTERIOR ELEVATIONS, REFLECTED CEILING DRAWINGS,
FLOOR FINISH DRAWINGS, WALL FINISH DRAWINGS, ENLARGED PLAN
DRAWINGS AND INTERIOR DETAIL DRAWINGS FOR ADDITIONAL FINISH
PLACEMENT INFORMATION.
REFER TO ELECTRICAL DRAWINGS, MECHANICAL DRAWINGS,
STRUCTURAL DRAWINGS AND COMMUNICATION DRAWINGS FOR
COORDINATION OF BUILDING FINISHES TO BUILDING SYSTEMS.
REFER TO FLOOR FINISH DRAWINGS FOR PLACEMENT OF FLOOR
FINISHES, FLOOR PATTERNS AND FLOOR MATERIAL CHANGES. REFER TO
FLOORING TRANSITION DETAILS FOR TRANSITIONS BETWEEN ADJOINING
FLOORING MATERIALS.
REFER TO WALL FINISH DRAWINGS FOR WALL FINISH EXTENTS, CORNER
GUARD LOCATIONS, SIGNAGE LOCATIONS.
REFER TO REFLECTED CEILING DRAWINGS FOR CEILING HEIGHTS AND
CEILING MATERIAL EXTENTS.
REFER TO ACCESS FLOOR DRAWINGS FOR COORDINATION OF FLOOR
FINISHES TO ACCESS FLOOR LOCATIONS.
REFER TO ENLARGED TOILET DRAWINGS, WALL FINISH PLANS AND
INTERIOR ELEVATIONS FOR PLACEMENT OF INTERIOR FINISHES IN
TOILET/LOCKER ROOMS.
REFER TO STAIR DETAILS FOR TYPICAL STAIR FINISH ASSIGNMENT.
REFER TO ELEVATOR SPECIFICATION SECTIONS FOR PASSENGER AND
FREIGHT ELEVATOR FINISHES.
CASEWORK LOWER AND UPPER CABINETS TO BE PLAM-1 WITH SOLID
SURFACE COUNTER SSF-1. LAVATORY COUNTERS TO BE SSF-1.
PROVIDE BLOCKING AS REQUIRED TO SECURE ALL WALL MOUNTED
ITEMS INCLUDING TOILET FIXTURES, TOILET ACCESSORIES, TOILET
PARTITIONS, MILLWORK, SHELVES, COUNTERTOP SUPPORTS,
MARKERBOARDS, TACKBOARDS, FLAT PANEL DISPLAYS, CAMERAS,
ACOUSTICAL WALL PANELS, MURAL OR ART CABLE SYSTEMS, AND ANY
OTHER WALL MOUNTED OBJECT.
UNLESS NOTED OTHERWISE, ALL EXPOSED STRUCTURAL STEEL TO BE
PAINTED TO MATCH ADJACENT WALL OR CEILING.
UNLESS NOTED OTHERWISE, ALL EXTERIOR / PERIMETER WINDOWS TO
RECEIVE RS-1.
ALL WINDOW SILLS TO BE SSF-3.
ALL DOOR FRAMES TO BE PA-4, EXEPT WHERE NOTED TO BE PAINTED
PA-6.
ALL METAL FABRICATIONS AND HANDRAILS TO BE PA-4.
INTERIOR CAULKING TO MATCH ADJACENT WALL FINISH COLOR.
NO FINISHES REQUIRED ON CONCRETE WALLS OR CONCRETE CEILINGS
UNLESS NOTED OTHERWISE.
ALL EXPOSED CONCRETE FLOORS SHALL BE SEALED.
WALL CORNER GUARDS TO BE INSTALLED STARTING AT THE TOP OF THE
SCHEDULED WALL BASE.
AT GYPSUM BOARD SOFFITS AND BULKHEADS, PAINT ALL EXPOSED
SURFACES.
PAINT ALL EXPOSED STRUCTURAL STEEL ELEMENTS, MISCELLANEOUS
STEEL, PIPING, HANGERS, VALVES AND CONDUITS EXCEPT PRE-
FINISHED LINER PANELS AND FOAM GENERATORS. THE PAINT COLOR
SHALL BE AS INDICATED ON SCHEDULE. ALL FIRE PROTECTION PIPING
COLOR SHALL BE SAFETY RED.
ALL EXPOSED MECHANICAL AND ELECTRICAL EQUIPMENT AND
ASSOCIATED SUPPORTING EQUIPMENT TO BE PAINTED TO MATCH
ADJACENT WALL OF CEILING UNLESS OTHERWISE REQUIRED BY CODE.
COORDINATE WITH MECHANICAL / ELECTRICAL FOR FINISHES ON
MECHANICAL OR ELECTRICAL EQUIPMENT.
DO NOT PAINT PRE-FINISHED ITEMS, FINISHED METAL SURFACES,
OPERATING PARTS, LABELS OR WARNINGS.
REFER TO AND…