Copy_of_Attachment_3_-_DEIF_Configuration_Parameter.xlsx

XLSX spreadsheet 29 KB Posted

Attached to
The development of Three (3) generator and switchboard control, monitoring and protection systems, along with the associated integration and installation service support.
Solicitation number
N64498-16-R-5019
Issued by

About this file

Attachment 3- DEIF Configuration Parameter

View the file

Other files

File Type Posted
Admendment_0002.pdf PDF
Attachment_17-_Woodword_L-Series_Integrate_Speed_Control.pdf PDF
Attachment_15-_WT CFPM_SWBD_Layout.pdf PDF
Attachment_20-_BM_SWBD_Layout.pdf PDF
Attachment_21-_BM_Field_Termination_Drawings.pdf PDF
Attachment_16-_WT CPFM_Field_Termination_Drawings.pdf PDF
Attachment_7_Rev.__1-_Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_24-_DEIF_Crompton_Site_Visit_Power_Point_Part_2.pdf PDF
Attachment_5_Rev.__1-Attachment_5_-_Crompton_Configuration_Parameter.pdf PDF
Attachment_19-_DEIF_Layout.pdf PDF
Attachment_23-_DEIF_Crompton_Site_Visit_Power_Point.pdf PDF
Attachment_22-_ASME_Y14.100.pdf PDF
N64498-16-R-5019-0001.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_10_-Generator_System_Operational_Test_BM.docx DOCX document
Attachment_6_-_Generator_System_Wiring_Diagram.pdf PDF
Attachment_4b_-_Welding_Tasks_Electrical_Isolation_Tech_Refresh.pdf PDF
Attachment_12_-Switchboard_System_Operational_Test_BM.docx DOCX document
Attachment_1_-_Alarm_Set_Points_(2).pdf PDF
Attachment_2_-_Crafts_Network_Diagram_(2).pdf PDF
Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_5_-_Crompton_Configuration_Parameter.pdf PDF
cdrls.pdf PDF
Attachment_8_-_Generator_and_Switchboard_System_Input_Output_Test.docx DOCX document
Attachment_11_-Switchboard_System_Operational_Test_WT_PM.docx DOCX document
Attachment_8_Appendix_-_Generator_and_Switchboard_System_IO_Table.pdf PDF
Attachment_14_-_S9074-AR-GIB-010_278.pdf PDF
Attachment_4a_-_Welding_Tasks_Electrical_Isolation_Non_Tech.pdf PDF
Attachment_13_-_S0400-AD-URM-010_TUM.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_9_-_Generator_System_Operational_Test_WT_PM.docx DOCX document
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 3 - DEIF Configurati

CategoryAddressVTAOptionChannelTextValueEngUnitTimerOutputAOutputBEnabledEnabledRunHigh alarmMismatchPwdLevelShowCanChangeEnabledFailClass
Protection111010Reverse power-5%1019TrueONFalseFalseTrueTrueN/A
Protection211016Rev. P. InverseN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
Protection311020Over current 1115%1009TrueONFalseFalseTrueTrueN/A
Protection411030Over current 2120%510TrueONFalseFalseTrueTrueN/A
Protection511041Over curr. inv. 1110%5N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection611042Over curr. inv. 2120%3.8N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection711043Over curr. inv. 3140%2.5N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection811051Over curr. inv. 4160%1.5N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection911052Over curr. inv. 5180%1N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection1011053Over curr. inv. 6200%0.5N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection1111060Over curr. invN/A** NULL **N/A00FalseOFFFalseFalseTrueTrueN/A
Protection4511400Reverse pow. S2-5%10N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection4611410h-current 1 S2115%10N/AN/AFalseOFFFalseFalseTrueFalseN/A
Protection4711420h-current 2 S2120%5N/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7012011Static syncN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
Control7112021Sync. dfMax0.3HzN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7212022Sync. dfMin0HzN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7312023Sync. dUMax6%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7412024Sync. t CB70msN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7512031Static sync df max0.1HzN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7612032Static sync dU max5%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7712033Static close window10degN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7812034Static phase Kp10** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control7912035Static phase KI160** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control8012041Blackout dfMax3HzN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control8112042Blackout dUMax5%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control8212043Blackout EnableN/A** NULL **N/AN/AN/ATrueONFalseFalseTrueTrueN/A
Control8312050Sync Window15%0.500FalseOFFFalseFalseTrueTrueN/A
Control8412060Sync. failureN/A** NULL **6000FalseOFFFalseFalseTrueTrueN/A
Control8512070General failureN/A** NULL **N/A00FalseOFFFalseFalseTrueTrueN/A
Control9012110Modes Active1** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9112121Freq. Control DB0.2%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9212122Freq. Control Kp40** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9312123Freq. Control KI300** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9412124Freq. Control Droop4%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9512131Power Control DB0.2%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9612132Power Control Kp50** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9712133Power Control KI130** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9812141Power ramp up speed20%/sN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control9912142Power ramp up point1%0N/AN/AFalseOFFFalseFalseTrueFalseN/A
Control10012151Power ramp d. speed20%/sN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control10112152Power ramp d. point5%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control10212160Analogue GOV Offset50** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control10612180GOV reg. fail30%6000FalseOFFFalseFalseTrueTrueN/A
Control11712230AVR reg. fail30%6000TrueONFalseFalseTrueTrueN/A
Control12112251GOV Min ON time500msN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control12212252GOV Period time2500msN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control12312253AVR Min ON time100msN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Control12412254AVR Period time500msN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
Input14413120Alarm InhibitN/A** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input14513130Alarm AckN/A** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input14613140Start/SynchN/A** NULL **100FalseOFFFalseFalseTrueTrueN/A
Input14713150Dig. Input 26N/A** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input14813160Dig. Input 27N/A** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input14913170DeloadN/A** NULL **1000FalseOFFFalseFalseTrueTrueN/A
Input15013180Man Speed +N/A** NULL **0.200FalseOFFTrueFalseTrueTrueN/A
Input15113190Man Speed -N/A** NULL **0.200FalseOFFTrueFalseTrueTrueN/A
Input15213200Man Volt +N/A** NULL **0.200FalseOFFTrueFalseTrueTrueN/A
Input15313210Man Volt -N/A** NULL **0.200FalseOFFTrueFalseTrueTrueN/A
Input15413220Mode 1N/A** NULL **0.288TrueONFalseFalseTrueTrueN/A
Input15513230Mode 2N/A** NULL **0.577FalseOFFFalseFalseTrueTrueN/A
Input15613240Gov FailureN/A** NULL **1000TrueONFalseFalseTrueTrueN/A
Input15713250Hi Pres Fuel LeN/A** NULL **200TrueONFalseFalseTrueTrueN/A
Input15813260Air Shut inh.N/A** NULL **0.277TrueONFalseFalseTrueTrueN/A
Input15913270Emg. Stop. 2N/A** NULL **0.255TrueONFalseFalseTrueTrueN/A
Input16013280Hi Oil T AlarmN/A** NULL **500TrueONTrueFalseTrueTrueN/A
Input16113290Low Oil Pr SDN/A** NULL **190TrueONTrueFalseTrueTrueN/A
Input16213300Hi Eng Temp SDN/A** NULL **1009TrueONTrueFalseTrueTrueN/A
Input16313310Low Oil Pr WrN/A** NULL **200TrueONFalseFalseTrueTrueN/A
Input16413320SD OverrideN/A** NULL **100FalseOFFTrueFalseTrueTrueN/A
Input16513330Start EnableN/A** NULL **500TrueONFalseFalseTrueTrueN/A
Input16613340Hi Eng Cool AlmN/A** NULL **500TrueONTrueFalseTrueTrueN/A
Input16713350Stator Hi TempN/A** NULL **500TrueONFalseFalseTrueTrueN/A
Input16813360Emerg StopN/A** NULL **0.290TrueONFalseFalseTrueTrueN/A
Input13313440Oil Press D/P1000mbar500TrueONTrueFalseTrueTrueN/A
Input354134501.2 4-20mA10** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input13413460Fuel Press D/P350mbar500TrueONTrueFalseTrueTrueN/A
Input355134702.2 4-20mA10** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input13513480Exhaust Temp1100°F500TrueONTrueFalseTrueTrueN/A
Input356134903.2 4-20mA10** NULL **1000FalseOFFTrueFalseTrueTrueN/A
Input14313640Oversp. 12000** NULL **159TrueONTrueFalseTrueTrueN/A
Input36413650Oversp. 22000** NULL **10.109FalseOFFTrueFalseTrueTrueN/A
Input17613660Oil Press18** NULL **500TrueONFalseFalseTrueTrueN/A
Input36513670Oil Pressure 240** NULL **500FalseOFFFalseFalseTrueTrueN/A
Input17813680Coolant Temp99** NULL **590TrueONTrueFalseTrueTrueN/A
Input36613690Cool W. Temp 2120** NULL **500FalseOFFTrueFalseTrueTrueN/A
Input18013700Fuel Press0** NULL **1000TrueONFalseFalseTrueTrueN/A
Input36713710Fuel Level 210** NULL **1000FalseOFFFalseFalseTrueTrueN/A
System18214011Nom. Frequency60HzN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18314012Nom. Power80kWN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18414013Nom. Current125AN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18514014Nom. Voltage460VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18614021Volt prim GEN460VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18714022Volt sec GEN460VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18814023Current prim200AN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System18914024Current sec5AN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System19014031Volt prim BUS460VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System19114032Volt sec BUS460VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System19214041Contr. settings P100%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System19614051Comm. bus control PN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System19714052Comm. bus control fN/A** NULL **N/AN/AN/ATrueONFalseFalseTrueTrueN/A
System19814053Comm. bus control UN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System19914054Comm. bus control QN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System20014055Comm. bus control PN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System20114061Ext. Comm. ID3** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System20214062Ext. Comm.Speed1** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System36814063Ext. Comm. Mode0** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System20314091Ext Comm. ErrorN/A** NULL **1000FalseOFFFalseFalseTrueTrueN/A
System20414121Running Time9** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System20514122CB Operations21** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System20614123Reset KWh Coun.N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System20814220Battery low V18V100TrueONFalseFalseTrueTrueN/A
System20914231Language0** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System21014240Loadshare out5VN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System21114250L. Sharing Type0** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System21214260Start next gen.80%1000FalseOFFFalseFalseTrueTrueN/A
System21314270Stop next gen.20%3000FalseOFFFalseFalseTrueTrueN/A
System21414351Running RPM600** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System21514352Number of Teeth126** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System35014353Nom RPM1800** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System21614361Start PrepareN/A** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System21714362Start On TimeN/A** NULL **10N/AN/AFalseOFFFalseFalseTrueFalseN/A
System21814363Start Off TimeN/A** NULL **10N/AN/AFalseOFFFalseFalseTrueFalseN/A
System21914371Start attempts3** NULL **N/A00TrueONFalseFalseTrueTrueN/A
System22014381f/U OKN/A** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System22114391f/U failureN/A** NULL **3000FalseOFFFalseFalseTrueTrueN/A
System22214401Cooldown TimeN/A** NULL **60N/AN/AFalseOFFFalseFalseTrueFalseN/A
System22314402Extended Stop TimeN/A** NULL **10N/AN/AFalseOFFFalseFalseTrueFalseN/A
System22414403Coil type0** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System22514410Stop failureN/A** NULL **3000FalseOFFFalseFalseTrueTrueN/A
System22614420Run statusN/A** NULL **1.531TrueONFalseFalseTrueTrueN/A
System22714430Remote statusN/A** NULL **0.566TrueONFalseFalseTrueTrueN/A
System22814440Generator readyN/A** NULL **1.200FalseOFFFalseFalseTrueTrueN/A
System25114600Relay 0 virtual0** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25214610Relay 12** NULL **0N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25314620Relay 20** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25414630Relay 32** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25514640Relay 40** NULL **5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25614650Relay 52** NULL **0.5N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25714660Relay 62** NULL **0N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25814670Relay 72** NULL **0.1N/AN/AFalseOFFFalseFalseTrueFalseN/A
System25914680Relay 82** NULL **0.1N/AN/AFalseOFFFalseFalseTrueFalseN/A
System34614941Asynchron GenN/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System34714942Slip Frequency1%N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System31714971Password******** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System31915011VDO 1 at 0.0 bar11OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32015012VDO 1 at 2.5 bar100OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32115013VDO 1 at 5.0 bar184OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32215014VDO 1 at 6.0 bar195.2OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32315021VDO 1 at 7.0 bar204.4OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32415022VDO 1 at 8.0 bar213.6OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32515023VDO 1 at 9.0 bar221.5OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32615024VDO 1 at 10.0 bar230.8OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32715031VDO 2 at 40 deg. C292OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32815032VDO 2 at 50 deg. C197OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System32915033VDO 2 at 60 deg. C134OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33015034VDO 2 at 70 deg. C97OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33115041VDO 2 at 80 deg. C70OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33215042VDO 2 at 90 deg. C51OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33315043VDO 2 at 100 deg. C39OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33415044VDO 2 at 110 deg. C29OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33515051VDO 3 at 0.0 bar10OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33615052VDO 3 at 2.5 bar235OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33715053VDO 3 at 5.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33815054VDO 3 at 6.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System33915061VDO 3 at 7.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System34015062VDO 3 at 8.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System34115063VDO 3 at 9.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System34215064VDO 3 at 10.0 bar240OhmN/AN/AN/AFalseOFFFalseFalseTrueFalseN/A
System3691511112345678901N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System3701511212345678902N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System3711511312345678903N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System3721511412345678904N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System3731511512345678905N/A** NULL **N/AN/AN/AFalseOFFFalseFalseTrueTrueN/A
System37415116GSM Pin code1933** NULL **N/AN/AN/AFalseOFFFalseFalseTrueFalseN/A