MPCMS I/O LIST - WT/CFPM
ABBREVIATION LEGEND-MACHINERY CONTROL SYSTEM HMI ALARM GROUPS
SERIAL=SECOND PARTY GENERATED SIGNAL AI-ANALOG IN 1 = CMON = Control & Monitoring 7 = FIRE = Fire
SOFT = SOFTW ARE DERIVED ALARM IAI=ISOLATED ANALOG INPUT 2 = PM = Port Main Engine 8 = FO = Fuel Oil
SPU = SIGNAL PROCESSING UNIT AO=ANALOG OUTPUT 3 = SM = Stbd Main Engine 9 = BLST = Ballast
RTD=RESISTANCE TEMPERATURE DETECTOR IAO=ISOLATED ANALOG OUTPUT 4 = GENS = Generators 10 = MISC = Miscellaneous
CONT = RELAY CONTACT DI=DIGITAL INPUT 5 = SW BD = Switchboard 11 = BM = Beach Module Summary
N/A=NOT APPLICABLE DO=DIGITAL OUTPUT 6 = GA = General Alarm
SW BS
MCS
DATABASE
NUMBER SYSTEM I.D. DESCRIPTION ANALOG DIGITAL LOCAL MCC LOS LOCAL MCC LOS LOCAL MCC LOS
ALARM
LEVEL
ALARM
GROUP
ALARM TIME
DELAY SENSOR BY PLC INPUT PLC LOCATION SPU NODE
PRODUCED
TAG
W ORD/BIT REMARKS
INPUT/OUTPUT TYPE INDICATOR ALARM CONTROL
FUEL OIL SERVICE
261 FOS-200 FUEL FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH HIGH AI X X X X X LVL 4 8 0.5 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]
FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH AI X X X X X LVL 4 8 0.5 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]
FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW AI X X X X X LVL 4 8 10 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]
FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW LOW AI X X X X X LVL 4 8 10 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]
GENERATOR ENGINE NO.1
310 G1-300 GEN-1 LOCAL / REMOTE CONTROL LOCATION SERIAL X X X X DEIF PLC FS_X30_07:I.Data[27].6 Digital_In[250] 40028/0
310 G1-900 GEN-1 START COMMAND X X X DEIF PLC See Remarks 40003/8 GEN is Started By DEIF after BRKR is Closed
310 G1-901 GEN-1 STOP COMMAND X X X DEIF PLC See Remarks 40003/8 GEN is Stopped By DEIF after BRKR is Opened
310 G1-500 GEN-1 EMERGENCY STOP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[27].9 Digital_In[251] 40025/5
310 G1-700 GEN-1 OVERSPEED TRIP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[23].12 Digital_In[252] 40023/12
310 G1-200 GEN-1 DIESEL RPM SERIAL X X DEIF PLC FS_X30_07:I.Data[40] Analog_In[250] 40040
310 G1-201 GEN-1 EXHAUST TEMPERATURE SERIAL X X LVL 2 4 0.5 DEIF PLC FS_X30_07:I.Data[58] Analog_In[251] 40061
310 G1-100 GEN-1 EXPANSION TANK LEVEL LOW DI X X LVL 2 4 20 MMC ACNR_03:1:I.Data.8 Digital_In[25]
310 G1-101 GEN-1 JACKET W ATER TEMPERATURE HIGH SERIAL X X LVL 2 4 0 DEIF PLC FS_X30_07:I.Data[25].3 Digital_In[253] 40025/14
310 G1-202 GEN-1 LUBE OIL PRESSURE SERIAL X X X LO LO LVL 2 4 0.5 DEIF PLC FS_X30_07:I.Data[42] Analog_In[252] 40042
310 G1-701 GEN-1 LUBE OIL PRESSURE SHUTDOW N SERIAL X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[24].14 Digital_In[254] 40025/13
GENERATOR NO.1
310 G1-102 GEN-1 STATOR W INDING TEMPERATURE SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_07:I.Data[25].4 Digital_In[257]
310 G1-301 GEN-1 GENERATOR NO. 1 RUNNING DI X X X CAT FS_X30_07:I.Data[27].3 Digital_In[255]
310 G1-103 GEN-1 GENERATOR NO. 1 SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_07:I.Data[27].0 Digital_In[256]
310 G1-106 GEN-1 BATTLE OVERRIDE
GENERATOR ENGINE NO.2
310 G2-300 GEN-2 LOCAL / REMOTE CONTROL LOCATION SERIAL X X X X DEIF PLC FS_X30_08:I.Data[27].6 Digital_In[260] 40028/0
310 G2-900 GEN-2 START COMMAND X X X See Remarks 40003/8 GEN is Started By DEIF after BRKR is Closed
310 G2-901 GEN-2 STOP COMMAND X X X See Remarks 40003/8 GEN is Stopped By DEIF after BRKR is Opened
310 G2-500 GEN-2 EMERGENCY STOP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[27].9 Digital_In[261] 40025/5
310 G2-700 GEN-2 OVERSPEED TRIP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[23].12 Digital_In[262] 40023/12
310 G2-200 GEN-2 DIESEL RPM SERIAL X X DEIF PLC FS_X30_08:I.Data[40] Analog_In[260] 40040
310 G2-201 GEN-2 EXHAUST TEMPERATURE SERIAL X X LVL 2 4 0.5 DEIF PLC FS_X30_08:I.Data[58] Analog_In[261] 40061
310 G2-100 GEN-2 EXPANSION TANK LEVEL LOW DI X X LVL 2 4 20 MMC ACNR_04:1:I.Data.8 Digital_In[57]
310 G2-101 GEN-2 JACKET W ATER TEMPERATURE HIGH SERIAL X X LVL 2 4 0 DEIF PLC FS_X30_08:I.Data[25].3 Digital_In[263] 40025/14
310 G2-202 GEN-2 LUBE OIL PRESSURE SERIAL X X X LO LO LVL 2 4 0.5 DEIF PLC FS_X30_08:I.Data[42] Analog_In[262] 40042
310 G2-701 GEN-2 LUBE OIL PRESSURE SHUTDOW N SERIAL X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[24].14 Digital_In[264] 40025/13
GENERATOR NO.2
310 G2-203 GEN-2 STATOR W INDING TEMPERATURE SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_08:I.Data[25].4 Digital_In[267]
310 G2-301 GEN-2 GENERATOR NO. 2 RUNNING DI X X X CAT FS_X30_08:I.Data[27].3 Digital_In[265]
310 G2-103 GEN-2 GENERATOR NO. 2 SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_08:I.Data[27].0 Digital_In[266]
310 G2-106 GEN-2 BATTLE OVERRIDE
BATTERY CHARGER & UPS FAILURE ALARM
313 BC-100 ALM - BATT STBD ENGINE & GEN NO. 1 BATTERY LOW CHARGE DI X X LVL 4 3 0 MMC ACNR_03:1:I.Data.0 Digital_In[17]
313 BC-101 ALM - BATT PORT ENGINE GEN NO. 2 BATTERY LOW CHARGE DI X X LVL 4 2 0 MMC ACNR_04:1:I.Data.2 Digital_In[51]
313 BC-104 ALM - UPS MCS UPS LINE FAILURE DI X X LVL 2 1 0 L3 ACNR_03:1:I.Data.3 Digital_In[20]
313 BC-200 ALM - UPS MCS UPS VOLTAGE MONITOR HIGH AI X X HI HI LVL 2 1 0.5 L3 ACNR_03:3:I.Ch4Data Analog_In[5]
313 BC-201 ALM - UPS MCS UPS VOLTAGE MONITOR LOW AI X X LO LO LVL 2 1 0.5 L3 ACNR_03:3:I.Ch4Data Analog_In[5]
POWER CONVERSION EQUIPMENT
314 INV-100 ALM - INV INVERTER BATTERY CHARGER FAILURE DI X X LVL 4 10 0 MMC ACNR_03:1:I.Data.6 Digital_In[23]
13:09
SHEET 7 OF 62
MMC DW G # 0003-202-03
NAVFAC DW G # 1600419
REV H
SENSOR L IST - WT/CFPM
MPCMS
DATABASE
NUMBER DESCRIPTION TYPE MANUFACTURER PART NUMBER
UNITS
MEAS
RANGE
MINIMUM
VALUE
RANGE
MAXIMUM
VALUE
RANGE
NORMAL
VALUE ALARM SET POINTS
FURNISHED
BY MMC PART NUMBER REMARKS
VERIFIED
INIT IAL/DATE
FUEL OIL SERVICE
FOS-200 FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH HIGH 4-20 Ma EMS 25165-300-1 GAL 156 1560 >1550 8 1/2 SECOND DELAY
FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH 4-20 Ma EMS 25165-300-1 GAL 156 1560 1510 8 5 SECOND DELAY
FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW 4-20 Ma EMS 25165-300-1 GAL 156 1560 238 8 5 SECOND DELAY
FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW LOW 4-20 Ma EMS 25165-300-1 GAL 156 1560 127 8 5 SECOND DELAY
GENERATOR ENGINE NO.1
G1-300 LOCAL / REMOTE CONTROL LOCATION CONT 0
G1-900 START COMMAND CONT 0
G1-901 STOP COMMAND CONT 0
G1-500 EMERGENCY STOP ACTIVATED CONT 4
G1-700 OVERSPEED TRIP ACTIVATED CONT 4
G1-200 DIESEL RPM 0
G1-201 EXHAUST TEMPERATURE Cat TBD C -40 1076 580 W arn 4
G1-100 EXPANSION TANK LEVEL LOW CONT 4
G1-101 JACKET W ATER TEMPERATURE HIGH SOFT Cat 237-2727 C -40 150 92 warn/99 shutdown 4
G1-202 LUBE OIL PRESSURE SOFT Cat 237-2340 PSI 0 72.5 20 warn 4
G1-701 LUBE OIL PRESSURE SHUTDOW N CONT Cat 237-2340 PSI 0 72.5 11.6 shutdown 4
GENERATOR NO.1
G1-102 STATOR W INDING TEMPERATURE SUMMARY ALARM RTD series sw 4
G1-301 GENERATOR NO. 1 RUNNING CONT 0
G1-103 GENERATOR NO. 1 SUMMARY ALARM CONT 4
GENERATOR ENGINE NO.2
G2-300 LOCAL / REMOTE CONTROL LOCATION CONT 0
G2-900 START COMMAND CONT 0
G2-901 STOP COMMAND CONT 0
G2-500 EMERGENCY STOP ACTIVATED CONT 4
G2-700 OVERSPEED TRIP ACTIVATED CONT 4
G2-200 DIESEL RPM 0
G2-201 EXHAUST TEMPERATURE Cat TBD C -40 1076 580 W arn 4
G2-100 EXPANSION TANK LEVEL LOW CONT 4
G2-101 JACKET W ATER TEMPERATURE HIGH SOFT Cat 237-2727 C -40 150 92 warn/99 shutdown 4
G2-202 LUBE OIL PRESSURE Cat 237-2340 PSI 0 72.5 20 warn 4
G2-701 LUBE OIL PRESSURE SHUTDOW N CONT Cat 237-2340 PSI 0 72.5 11.6 shutdown 4
GENERATOR NO.2
G2-203 STATOR W INDING TEMPERATURE SUMMARY ALARM RTD series sw 4
G2-301 GENERATOR NO. 2 RUNNING CONT 0
G2-103 GENERATOR NO. 2 SUMMARY ALARM CONT 4
BATTERY CHARGER & UPS FAILURE ALARM
BC-100 STBD ENGINE & GEN NO. 1 BATTERY LOW CHARGE CONT VOLT <19 3
BC-101 PORT ENGINE GEN NO. 2 BATTERY LOW CHARGE CONT VOLT <19 2
BC-104 MCS UPS LINE FAILURE CONT L3
BC-200 MCS UPS VOLTAGE MONITOR HIGH VOLT <28 L3
BC-201 MCS UPS VOLTAGE MONITOR LOW VOLT <22 L3
POWER CONVERSION EQUIPMENT
INV-100 INVERTER BATTERY CHARGER FAILURE CONT VLOT <19 10
13:09
SHEET 8 OF 62
MMC DW G # 0003-202-03
ABBREVIATION LEGEND-MACHINERY CONTROL SYSTEM HMI ALARM GROUPS
SERIAL=SECOND PARTY GENERATED SIGNAL AI-ANALOG IN 1 = CMON = Control & Monitoring 7 = FIRE = Fire
SOFT = SOFTW ARE DERIVED ALARM IAI=ISOLATED ANALOG INPUT 2 = PM = Port Main Engine 8 = FO = Fuel Oil
SPU = SIGNAL PROCESSING UNIT AO=ANALOG OUTPUT 3 = SM = Stbd Main Engine 9 = BLST = Ballast
RTD=RESISTANCE TEMPERATURE DETECTOR IAO=ISOLATED ANALOG OUTPUT 4 = GENS = Generators 10 = MISC = Miscellaneous
CONT = RELAY CONTACT DI=DIGITAL INPUT 5 = SW BD = Switchboard 11 = BM = Beach Module Summary
N/A=NOT APPLICABLE DO=DIGITAL OUTPUT 6 = GA = General Alarm
SW BS
MCS
DATABASE
NUMBER SYSTEM I.D. DESCRIPTION ANALOG DIGITAL LOCAL MCC LOS LOCAL MCC LOS LOCAL MCC LOS
ALARM
LEVEL
ALARM
GROUP
ALARM TIME
DELAY SENSOR BY PLC INPUT PLC LOCATION SPU NODE
PRODUCED
TAG
W ORD/BIT REMARKS
INPUT/OUTPUT TYPE INDICATOR ALARM CONTROL
SHIP SERVICE SWITCHBOARD
320 SSS-309 SS-SW BD POW ER MANAGEMENT MODE ACTIVE GEN #1 DI X X GCP ACNR_06:0:I.Data.2 Digital_In[83]
320 SSS-310 SS-SW BD POW ER MANAGEMENT MODE ACTIVE GEN #2 DI X X GCP ACNR_06:0:I.Data.8 Digital_In[89]
320 SSS-300 SS-SW BD MANUAL CONTROL LOCATION GEN-1 DI X X GCP ACNR_06:0:I.Data.0 Digital_In[81]
320 SSS-311 SS-SW BD AUTOMATIC CONTROL LOCATION GEN-1 DI X X GCP ACNR_06:0:I.Data.1 Digital_In[82]
320 SSS-306 SS-SW BD MANUAL CONTROL LOCATION GEN-2 DI X X GCP ACNR_06:0:I.Data.6 Digital_In[87]
320 SSS-312 SS-SW BD AUTOMATIC CONTROL LOCATION GEN-2 DI X X GCP ACNR_06:0:I.Data.7 Digital_In[88]
320 SSS-200 SS-SW BD A-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001
A-PHASE VOLTAGE GEN-1 HIGH X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001
A-PHASE VOLTAGE GEN-1 LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001
A-PHASE VOLTAGE GEN-1 LOW LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001
320 SSS-201 SS-SW BD B-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003
B-PHASE VOLTAGE GEN-1 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003
B-PHASE VOLTAGE GEN-1 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003
B-PHASE VOLTAGE GEN-1 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003
320 SSS-202 SS-SW BD C-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005
C-PHASE VOLTAGE GEN-1 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005
C-PHASE VOLTAGE GEN-1 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005
C-PHASE VOLTAGE GEN-1 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005
320 SSS-203 SS-SW BD A-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[7], [8] Analog_In[307] 30007
320 SSS-204 SS-SW BD B-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[9], [10] Analog_In[309] 30009
320 SSS-205 SS-SW BD C-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[11], [12] Analog_In[311] 30011
320 SSS-206 SS-SW BD POW ER GEN-1 SERIAL X X X 5 TYCO PR SW BD_ReadData[18], [19] Analog_In[318] 30053
320 SSS-207 SS-SW BD FREQUENCY GEN-1 HIGH SERIAL X X X HI HI LVL 2 5 5 TYCO PR SW BD_ReadData[36], [37] Analog_In[336] 30071
FREQUENCY GEN-1 LOW SERIAL X X X LO LO LVL 2 5 5 TYCO PR SW BD_ReadData[36], [37] Analog_In[336] 30071
320 SSS-212 SS-SW BD A-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001
A-PHASE VOLTAGE GEN-2 HIGH X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001
A-PHASE VOLTAGE GEN-2 LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001
A-PHASE VOLTAGE GEN-2 LOW LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001
320 SSS-213 SS-SW BD B-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003
B-PHASE VOLTAGE GEN-2 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003
B-PHASE VOLTAGE GEN-2 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003
B-PHASE VOLTAGE GEN-2 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003
320 SSS-214 SS-SW BD C-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005
C-PHASE VOLTAGE GEN-2 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005
C-PHASE VOLTAGE GEN-2 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005
C-PHASE VOLTAGE GEN-2 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005
320 SSS-215 SS-SW BD A-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[52], [53] Analog_In[352] 30007
320 SSS-216 SS-SW BD B-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[54], [55] Analog_In[354] 30009
320 SSS-217 SS-SW BD C-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[56], [57] Analog_In[356] 30011
320 SSS-218 SS-SW BD POW ER GEN-2 SERIAL X X X 5 TYCO PR SW BD_ReadData[63], [64] Analog_In[363] 30053
320 SSS-219 SS-SW BD FREQUENCY GEN-2 HIGH SERIAL X X X HI HI LVL 2 5 5 TYCO PR SW BD_ReadData[81], [82] Analog_In[381] 30071
FREQUENCY GEN-2 LOW SERIAL X X X LO LO LVL 2 5 5 TYCO PR SW BD_ReadData[81], [82] Analog_In[381] 30071
320 SSS-301 SS-SW BD GENERATOR #1 RUNNING X X FS_X30_07:I.Data[27].3 Digital_In[255]
320 SSS-302 SS-SW BD GENERATOR #2 RUNNING X X FS_X30_08:I.Data[27].3 Digital_In[265]
320 SSS-900 SS-SW BD GEN NO.1 CIRCUIT BREAKER OPEN COMMAND DO X X GCP ACNR_06:1:O.Data.0 SS_Gen[0].Brkr_Open_CMD
320 SSS-901 SS-SW BD GEN NO.1CIRCUIT BREAKER CLOSE COMMAND DO X X GCP ACNR_06:1:O.Data.1 SS_Gen[0].Brkr_cls_CMD
320 SSS-303 SS-SW BD GEN NO.1 CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.3 Digital_In[84]
320 SSS-313 SS-SW BD GEN NO.1 CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.4 Digital_In[85]
320 SSS-306 SS-SW BD GEN NO.1 CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.5 Digital_In[86]
320 SSS-902 SS-SW BD GEN NO.2 CIRCUIT BREAKER OPEN COMMAND DO X X GCP ACNR_06:1:O.Data.2 SS_Gen[1].Brkr_Open_CMD
320 SSS-903 SS-SW BD GEN NO.2 CIRCUIT BREAKER CLOSE COMMAND DO X X GCP ACNR_06:1:O.Data.3 SS_Gen[1].Brkr_cls_CMD
320 SSS-304 SS-SW BD GEN NO.2 CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.9 Digital_In[90]
320 SSS-314 SS-SW BD GEN NO.2 CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.10 Digital_In[91]
320 SSS-307 SS-SW BD GEN NO.2 CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.11 Digital_In[92]
320 SSS-305 SS-SW BD SHORE PW R CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.12 Digital_In[93]
320 SSS-315 SS-SW BD SHORE PW R CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.13 Digital_In[94]
320 SSS-308 SS-SW BD SHORE PW R CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.14 Digital_In[95]
13:09
SHEET 9 OF 62
MMC DW G # 0003-202-03
SENSOR L IST - WT/CFPM
MPCMS
DATABASE
NUMBER DESCRIPTION TYPE MANUFACTURER PART NUMBER
UNITS
MEAS
RANGE
MINIMUM
VALUE
RANGE
MAXIMUM
VALUE
RANGE
NORMAL
VALUE ALARM SET POINTS
FURNISHED
BY MMC PART NUMBER REMARKS
VERIFIED
INIT IAL/DATE
SHIP SERVICE SWITCHBOARD
SSS-309 POW ER MANAGEMENT MODE ACTIVE GEN #1 CONT 0
SSS-310 POW ER MANAGEMENT MODE ACTIVE GEN #2 CONT 0
SSS-300 MANUAL CONTROL LOCATION GEN-1 CONT 0
SSS-311 AUTOMATIC CONTROL LOCATION GEN-1 CONT 0
SSS-306 MANUAL CONTROL LOCATION GEN-2 CONT 0
SSS-312 AUTOMATIC CONTROL LOCATION GEN-2 CONT 0
SSS-200 A-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-201 B-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-202 C-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-203 A-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-204 B-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-205 C-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-206 POW ER GEN-1 CROMPTON SRP-01 KW ATT 0 125 0 5 SECOND DELAY
SSS-207 FREQUENCY GEN-1 HIGH CROMPTON SRP-01 Hz 56.2 62.3 60 >61 5 5 SECOND DELAY
0 FREQUENCY GEN-1 LOW CROMPTON SRP-01 Hz 56.2 62.3 60 <59 5 5 SECOND DELAY
SSS-212 A-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 A-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-213 B-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 B-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-214 C-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY
0 C-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY
SSS-215 A-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-216 B-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-217 C-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY
SSS-218 POW ER GEN-2 CROMPTON SRP-01 KW ATT 0 125 0 5 SECOND DELAY
SSS-219 FREQUENCY GEN-2 HIGH CROMPTON SRP-01 Hz 56.2 62.3 60 >61 5 5 SECOND DELAY
0 FREQUENCY GEN-2 LOW CROMPTON SRP-01 Hz 56.2 62.3 60 <59 5 5 SECOND DELAY
SSS-301 GENERATOR #1 RUNNING CONT N/A N/A 0
SSS-302 GENERATOR #2 RUNNING CONT N/A N/A 0
SSS-900 GEN NO.1 CIRCUIT BREAKER OPEN COMMAND CONT 0
SSS-901 GEN NO.1CIRCUIT BREAKER CLOSE COMMAND CONT 0
SSS-303 GEN NO.1 CIRCUIT BREAKER OPEN STATUS CONT 0
SSS-313 GEN NO.1 CIRCUIT BREAKER CLOSED STATUS CONT 0
SSS-306 GEN NO.1 CIRCUIT BREAKER TRIPPED STATUS CONT 5
SSS-902 GEN NO.2 CIRCUIT BREAKER OPEN COMMAND CONT 0
SSS-903 GEN NO.2 CIRCUIT BREAKER CLOSE COMMAND CONT 0
SSS-304 GEN NO.2 CIRCUIT BREAKER OPEN STATUS CONT 0
SSS-314 GEN NO.2 CIRCUIT BREAKER CLOSED STATUS CONT 0
SSS-307 GEN NO.2 CIRCUIT BREAKER TRIPPED STATUS CONT 5
SSS-305 SHORE PW R CIRCUIT BREAKER OPEN STATUS CONT 0
SSS-315 SHORE PW R CIRCUIT BREAKER CLOSED STATUS CONT 0
SSS-308 SHORE PW R CIRCUIT BREAKER TRIPPED STATUS CONT 5
13:09