About this file

Attachment 1- Alarm Set Points

View the file

Other files

File Type Posted
Admendment_0002.pdf PDF
Attachment_17-_Woodword_L-Series_Integrate_Speed_Control.pdf PDF
Attachment_15-_WT CFPM_SWBD_Layout.pdf PDF
Attachment_20-_BM_SWBD_Layout.pdf PDF
Attachment_21-_BM_Field_Termination_Drawings.pdf PDF
Attachment_16-_WT CPFM_Field_Termination_Drawings.pdf PDF
Attachment_7_Rev.__1-_Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_24-_DEIF_Crompton_Site_Visit_Power_Point_Part_2.pdf PDF
Attachment_5_Rev.__1-Attachment_5_-_Crompton_Configuration_Parameter.pdf PDF
Attachment_19-_DEIF_Layout.pdf PDF
Attachment_23-_DEIF_Crompton_Site_Visit_Power_Point.pdf PDF
Attachment_22-_ASME_Y14.100.pdf PDF
N64498-16-R-5019-0001.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_10_-Generator_System_Operational_Test_BM.docx DOCX document
Attachment_6_-_Generator_System_Wiring_Diagram.pdf PDF
Attachment_4b_-_Welding_Tasks_Electrical_Isolation_Tech_Refresh.pdf PDF
Attachment_12_-Switchboard_System_Operational_Test_BM.docx DOCX document
Copy_of_Attachment_3_-_DEIF_Configuration_Parameter.xlsx XLSX spreadsheet
Attachment_2_-_Crafts_Network_Diagram_(2).pdf PDF
Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_5_-_Crompton_Configuration_Parameter.pdf PDF
cdrls.pdf PDF
Attachment_8_-_Generator_and_Switchboard_System_Input_Output_Test.docx DOCX document
Attachment_11_-Switchboard_System_Operational_Test_WT_PM.docx DOCX document
Attachment_8_Appendix_-_Generator_and_Switchboard_System_IO_Table.pdf PDF
Attachment_14_-_S9074-AR-GIB-010_278.pdf PDF
Attachment_4a_-_Welding_Tasks_Electrical_Isolation_Non_Tech.pdf PDF
Attachment_13_-_S0400-AD-URM-010_TUM.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_9_-_Generator_System_Operational_Test_WT_PM.docx DOCX document
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MPCMS I/O LIST - WT/CFPM

ABBREVIATION LEGEND-MACHINERY CONTROL SYSTEM HMI ALARM GROUPS

SERIAL=SECOND PARTY GENERATED SIGNAL AI-ANALOG IN 1 = CMON = Control & Monitoring 7 = FIRE = Fire

SOFT = SOFTW ARE DERIVED ALARM IAI=ISOLATED ANALOG INPUT 2 = PM = Port Main Engine 8 = FO = Fuel Oil

SPU = SIGNAL PROCESSING UNIT AO=ANALOG OUTPUT 3 = SM = Stbd Main Engine 9 = BLST = Ballast

RTD=RESISTANCE TEMPERATURE DETECTOR IAO=ISOLATED ANALOG OUTPUT 4 = GENS = Generators 10 = MISC = Miscellaneous

CONT = RELAY CONTACT DI=DIGITAL INPUT 5 = SW BD = Switchboard 11 = BM = Beach Module Summary

N/A=NOT APPLICABLE DO=DIGITAL OUTPUT 6 = GA = General Alarm

SW BS

MCS

DATABASE

NUMBER SYSTEM I.D. DESCRIPTION ANALOG DIGITAL LOCAL MCC LOS LOCAL MCC LOS LOCAL MCC LOS

ALARM

LEVEL

ALARM

GROUP

ALARM TIME

DELAY SENSOR BY PLC INPUT PLC LOCATION SPU NODE

PRODUCED

TAG

W ORD/BIT REMARKS

INPUT/OUTPUT TYPE INDICATOR ALARM CONTROL

FUEL OIL SERVICE

261 FOS-200 FUEL FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH HIGH AI X X X X X LVL 4 8 0.5 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]

FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH AI X X X X X LVL 4 8 0.5 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]

FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW AI X X X X X LVL 4 8 10 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]

FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW LOW AI X X X X X LVL 4 8 10 MMC ACNR_03:3:I.Ch0Data Analog_In [1] to Analog_In[91]

GENERATOR ENGINE NO.1

310 G1-300 GEN-1 LOCAL / REMOTE CONTROL LOCATION SERIAL X X X X DEIF PLC FS_X30_07:I.Data[27].6 Digital_In[250] 40028/0

310 G1-900 GEN-1 START COMMAND X X X DEIF PLC See Remarks 40003/8 GEN is Started By DEIF after BRKR is Closed

310 G1-901 GEN-1 STOP COMMAND X X X DEIF PLC See Remarks 40003/8 GEN is Stopped By DEIF after BRKR is Opened

310 G1-500 GEN-1 EMERGENCY STOP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[27].9 Digital_In[251] 40025/5

310 G1-700 GEN-1 OVERSPEED TRIP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[23].12 Digital_In[252] 40023/12

310 G1-200 GEN-1 DIESEL RPM SERIAL X X DEIF PLC FS_X30_07:I.Data[40] Analog_In[250] 40040

310 G1-201 GEN-1 EXHAUST TEMPERATURE SERIAL X X LVL 2 4 0.5 DEIF PLC FS_X30_07:I.Data[58] Analog_In[251] 40061

310 G1-100 GEN-1 EXPANSION TANK LEVEL LOW DI X X LVL 2 4 20 MMC ACNR_03:1:I.Data.8 Digital_In[25]

310 G1-101 GEN-1 JACKET W ATER TEMPERATURE HIGH SERIAL X X LVL 2 4 0 DEIF PLC FS_X30_07:I.Data[25].3 Digital_In[253] 40025/14

310 G1-202 GEN-1 LUBE OIL PRESSURE SERIAL X X X LO LO LVL 2 4 0.5 DEIF PLC FS_X30_07:I.Data[42] Analog_In[252] 40042

310 G1-701 GEN-1 LUBE OIL PRESSURE SHUTDOW N SERIAL X X LVL 1 4 0 DEIF PLC FS_X30_07:I.Data[24].14 Digital_In[254] 40025/13

GENERATOR NO.1

310 G1-102 GEN-1 STATOR W INDING TEMPERATURE SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_07:I.Data[25].4 Digital_In[257]

310 G1-301 GEN-1 GENERATOR NO. 1 RUNNING DI X X X CAT FS_X30_07:I.Data[27].3 Digital_In[255]

310 G1-103 GEN-1 GENERATOR NO. 1 SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_07:I.Data[27].0 Digital_In[256]

310 G1-106 GEN-1 BATTLE OVERRIDE

GENERATOR ENGINE NO.2

310 G2-300 GEN-2 LOCAL / REMOTE CONTROL LOCATION SERIAL X X X X DEIF PLC FS_X30_08:I.Data[27].6 Digital_In[260] 40028/0

310 G2-900 GEN-2 START COMMAND X X X See Remarks 40003/8 GEN is Started By DEIF after BRKR is Closed

310 G2-901 GEN-2 STOP COMMAND X X X See Remarks 40003/8 GEN is Stopped By DEIF after BRKR is Opened

310 G2-500 GEN-2 EMERGENCY STOP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[27].9 Digital_In[261] 40025/5

310 G2-700 GEN-2 OVERSPEED TRIP ACTIVATED SERIAL X X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[23].12 Digital_In[262] 40023/12

310 G2-200 GEN-2 DIESEL RPM SERIAL X X DEIF PLC FS_X30_08:I.Data[40] Analog_In[260] 40040

310 G2-201 GEN-2 EXHAUST TEMPERATURE SERIAL X X LVL 2 4 0.5 DEIF PLC FS_X30_08:I.Data[58] Analog_In[261] 40061

310 G2-100 GEN-2 EXPANSION TANK LEVEL LOW DI X X LVL 2 4 20 MMC ACNR_04:1:I.Data.8 Digital_In[57]

310 G2-101 GEN-2 JACKET W ATER TEMPERATURE HIGH SERIAL X X LVL 2 4 0 DEIF PLC FS_X30_08:I.Data[25].3 Digital_In[263] 40025/14

310 G2-202 GEN-2 LUBE OIL PRESSURE SERIAL X X X LO LO LVL 2 4 0.5 DEIF PLC FS_X30_08:I.Data[42] Analog_In[262] 40042

310 G2-701 GEN-2 LUBE OIL PRESSURE SHUTDOW N SERIAL X X LVL 1 4 0 DEIF PLC FS_X30_08:I.Data[24].14 Digital_In[264] 40025/13

GENERATOR NO.2

310 G2-203 GEN-2 STATOR W INDING TEMPERATURE SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_08:I.Data[25].4 Digital_In[267]

310 G2-301 GEN-2 GENERATOR NO. 2 RUNNING DI X X X CAT FS_X30_08:I.Data[27].3 Digital_In[265]

310 G2-103 GEN-2 GENERATOR NO. 2 SUMMARY ALARM DI X X X LVL 2 4 0 CAT FS_X30_08:I.Data[27].0 Digital_In[266]

310 G2-106 GEN-2 BATTLE OVERRIDE

BATTERY CHARGER & UPS FAILURE ALARM

313 BC-100 ALM - BATT STBD ENGINE & GEN NO. 1 BATTERY LOW CHARGE DI X X LVL 4 3 0 MMC ACNR_03:1:I.Data.0 Digital_In[17]

313 BC-101 ALM - BATT PORT ENGINE GEN NO. 2 BATTERY LOW CHARGE DI X X LVL 4 2 0 MMC ACNR_04:1:I.Data.2 Digital_In[51]

313 BC-104 ALM - UPS MCS UPS LINE FAILURE DI X X LVL 2 1 0 L3 ACNR_03:1:I.Data.3 Digital_In[20]

313 BC-200 ALM - UPS MCS UPS VOLTAGE MONITOR HIGH AI X X HI HI LVL 2 1 0.5 L3 ACNR_03:3:I.Ch4Data Analog_In[5]

313 BC-201 ALM - UPS MCS UPS VOLTAGE MONITOR LOW AI X X LO LO LVL 2 1 0.5 L3 ACNR_03:3:I.Ch4Data Analog_In[5]

POWER CONVERSION EQUIPMENT

314 INV-100 ALM - INV INVERTER BATTERY CHARGER FAILURE DI X X LVL 4 10 0 MMC ACNR_03:1:I.Data.6 Digital_In[23]

13:09

SHEET 7 OF 62

MMC DW G # 0003-202-03

NAVFAC DW G # 1600419

REV H

SENSOR L IST - WT/CFPM

MPCMS

DATABASE

NUMBER DESCRIPTION TYPE MANUFACTURER PART NUMBER

UNITS

MEAS

RANGE

MINIMUM

VALUE

RANGE

MAXIMUM

VALUE

RANGE

NORMAL

VALUE ALARM SET POINTS

FURNISHED

BY MMC PART NUMBER REMARKS

VERIFIED

INIT IAL/DATE

FUEL OIL SERVICE

FOS-200 FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH HIGH 4-20 Ma EMS 25165-300-1 GAL 156 1560 >1550 8 1/2 SECOND DELAY

FUEL OIL SERVICE TANK 2-12-01-F LEVEL HIGH 4-20 Ma EMS 25165-300-1 GAL 156 1560 1510 8 5 SECOND DELAY

FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW 4-20 Ma EMS 25165-300-1 GAL 156 1560 238 8 5 SECOND DELAY

FUEL OIL SERVICE TANK 2-12-01-F LEVEL LOW LOW 4-20 Ma EMS 25165-300-1 GAL 156 1560 127 8 5 SECOND DELAY

GENERATOR ENGINE NO.1

G1-300 LOCAL / REMOTE CONTROL LOCATION CONT 0

G1-900 START COMMAND CONT 0

G1-901 STOP COMMAND CONT 0

G1-500 EMERGENCY STOP ACTIVATED CONT 4

G1-700 OVERSPEED TRIP ACTIVATED CONT 4

G1-200 DIESEL RPM 0

G1-201 EXHAUST TEMPERATURE Cat TBD C -40 1076 580 W arn 4

G1-100 EXPANSION TANK LEVEL LOW CONT 4

G1-101 JACKET W ATER TEMPERATURE HIGH SOFT Cat 237-2727 C -40 150 92 warn/99 shutdown 4

G1-202 LUBE OIL PRESSURE SOFT Cat 237-2340 PSI 0 72.5 20 warn 4

G1-701 LUBE OIL PRESSURE SHUTDOW N CONT Cat 237-2340 PSI 0 72.5 11.6 shutdown 4

GENERATOR NO.1

G1-102 STATOR W INDING TEMPERATURE SUMMARY ALARM RTD series sw 4

G1-301 GENERATOR NO. 1 RUNNING CONT 0

G1-103 GENERATOR NO. 1 SUMMARY ALARM CONT 4

GENERATOR ENGINE NO.2

G2-300 LOCAL / REMOTE CONTROL LOCATION CONT 0

G2-900 START COMMAND CONT 0

G2-901 STOP COMMAND CONT 0

G2-500 EMERGENCY STOP ACTIVATED CONT 4

G2-700 OVERSPEED TRIP ACTIVATED CONT 4

G2-200 DIESEL RPM 0

G2-201 EXHAUST TEMPERATURE Cat TBD C -40 1076 580 W arn 4

G2-100 EXPANSION TANK LEVEL LOW CONT 4

G2-101 JACKET W ATER TEMPERATURE HIGH SOFT Cat 237-2727 C -40 150 92 warn/99 shutdown 4

G2-202 LUBE OIL PRESSURE Cat 237-2340 PSI 0 72.5 20 warn 4

G2-701 LUBE OIL PRESSURE SHUTDOW N CONT Cat 237-2340 PSI 0 72.5 11.6 shutdown 4

GENERATOR NO.2

G2-203 STATOR W INDING TEMPERATURE SUMMARY ALARM RTD series sw 4

G2-301 GENERATOR NO. 2 RUNNING CONT 0

G2-103 GENERATOR NO. 2 SUMMARY ALARM CONT 4

BATTERY CHARGER & UPS FAILURE ALARM

BC-100 STBD ENGINE & GEN NO. 1 BATTERY LOW CHARGE CONT VOLT <19 3

BC-101 PORT ENGINE GEN NO. 2 BATTERY LOW CHARGE CONT VOLT <19 2

BC-104 MCS UPS LINE FAILURE CONT L3

BC-200 MCS UPS VOLTAGE MONITOR HIGH VOLT <28 L3

BC-201 MCS UPS VOLTAGE MONITOR LOW VOLT <22 L3

POWER CONVERSION EQUIPMENT

INV-100 INVERTER BATTERY CHARGER FAILURE CONT VLOT <19 10

13:09

SHEET 8 OF 62

MMC DW G # 0003-202-03

ABBREVIATION LEGEND-MACHINERY CONTROL SYSTEM HMI ALARM GROUPS

SERIAL=SECOND PARTY GENERATED SIGNAL AI-ANALOG IN 1 = CMON = Control & Monitoring 7 = FIRE = Fire

SOFT = SOFTW ARE DERIVED ALARM IAI=ISOLATED ANALOG INPUT 2 = PM = Port Main Engine 8 = FO = Fuel Oil

SPU = SIGNAL PROCESSING UNIT AO=ANALOG OUTPUT 3 = SM = Stbd Main Engine 9 = BLST = Ballast

RTD=RESISTANCE TEMPERATURE DETECTOR IAO=ISOLATED ANALOG OUTPUT 4 = GENS = Generators 10 = MISC = Miscellaneous

CONT = RELAY CONTACT DI=DIGITAL INPUT 5 = SW BD = Switchboard 11 = BM = Beach Module Summary

N/A=NOT APPLICABLE DO=DIGITAL OUTPUT 6 = GA = General Alarm

SW BS

MCS

DATABASE

NUMBER SYSTEM I.D. DESCRIPTION ANALOG DIGITAL LOCAL MCC LOS LOCAL MCC LOS LOCAL MCC LOS

ALARM

LEVEL

ALARM

GROUP

ALARM TIME

DELAY SENSOR BY PLC INPUT PLC LOCATION SPU NODE

PRODUCED

TAG

W ORD/BIT REMARKS

INPUT/OUTPUT TYPE INDICATOR ALARM CONTROL

SHIP SERVICE SWITCHBOARD

320 SSS-309 SS-SW BD POW ER MANAGEMENT MODE ACTIVE GEN #1 DI X X GCP ACNR_06:0:I.Data.2 Digital_In[83]

320 SSS-310 SS-SW BD POW ER MANAGEMENT MODE ACTIVE GEN #2 DI X X GCP ACNR_06:0:I.Data.8 Digital_In[89]

320 SSS-300 SS-SW BD MANUAL CONTROL LOCATION GEN-1 DI X X GCP ACNR_06:0:I.Data.0 Digital_In[81]

320 SSS-311 SS-SW BD AUTOMATIC CONTROL LOCATION GEN-1 DI X X GCP ACNR_06:0:I.Data.1 Digital_In[82]

320 SSS-306 SS-SW BD MANUAL CONTROL LOCATION GEN-2 DI X X GCP ACNR_06:0:I.Data.6 Digital_In[87]

320 SSS-312 SS-SW BD AUTOMATIC CONTROL LOCATION GEN-2 DI X X GCP ACNR_06:0:I.Data.7 Digital_In[88]

320 SSS-200 SS-SW BD A-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001

A-PHASE VOLTAGE GEN-1 HIGH X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001

A-PHASE VOLTAGE GEN-1 LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001

A-PHASE VOLTAGE GEN-1 LOW LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[1], [2] Analog_In[301] 30001

320 SSS-201 SS-SW BD B-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003

B-PHASE VOLTAGE GEN-1 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003

B-PHASE VOLTAGE GEN-1 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003

B-PHASE VOLTAGE GEN-1 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[3], [4] Analog_In[303] 30003

320 SSS-202 SS-SW BD C-PHASE VOLTAGE GEN-1 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005

C-PHASE VOLTAGE GEN-1 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005

C-PHASE VOLTAGE GEN-1 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005

C-PHASE VOLTAGE GEN-1 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[5], [6] Analog_In[305] 30005

320 SSS-203 SS-SW BD A-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[7], [8] Analog_In[307] 30007

320 SSS-204 SS-SW BD B-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[9], [10] Analog_In[309] 30009

320 SSS-205 SS-SW BD C-PHASE CURRENT GEN-1 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[11], [12] Analog_In[311] 30011

320 SSS-206 SS-SW BD POW ER GEN-1 SERIAL X X X 5 TYCO PR SW BD_ReadData[18], [19] Analog_In[318] 30053

320 SSS-207 SS-SW BD FREQUENCY GEN-1 HIGH SERIAL X X X HI HI LVL 2 5 5 TYCO PR SW BD_ReadData[36], [37] Analog_In[336] 30071

FREQUENCY GEN-1 LOW SERIAL X X X LO LO LVL 2 5 5 TYCO PR SW BD_ReadData[36], [37] Analog_In[336] 30071

320 SSS-212 SS-SW BD A-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001

A-PHASE VOLTAGE GEN-2 HIGH X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001

A-PHASE VOLTAGE GEN-2 LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001

A-PHASE VOLTAGE GEN-2 LOW LOW X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[46], [47] Analog_In[346] 30001

320 SSS-213 SS-SW BD B-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003

B-PHASE VOLTAGE GEN-2 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003

B-PHASE VOLTAGE GEN-2 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003

B-PHASE VOLTAGE GEN-2 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[48], [49] Analog_In[348] 30003

320 SSS-214 SS-SW BD C-PHASE VOLTAGE GEN-2 HIGH HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005

C-PHASE VOLTAGE GEN-2 HIGH SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005

C-PHASE VOLTAGE GEN-2 LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005

C-PHASE VOLTAGE GEN-2 LOW LOW SERIAL X X X X X LVL 2 5 2 TYCO PR SW BD_ReadData[50], [51] Analog_In[350] 30005

320 SSS-215 SS-SW BD A-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[52], [53] Analog_In[352] 30007

320 SSS-216 SS-SW BD B-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[54], [55] Analog_In[354] 30009

320 SSS-217 SS-SW BD C-PHASE CURRENT GEN-2 SERIAL X X X LO/HI LO/HI LVL 2 5 5 TYCO PR SW BD_ReadData[56], [57] Analog_In[356] 30011

320 SSS-218 SS-SW BD POW ER GEN-2 SERIAL X X X 5 TYCO PR SW BD_ReadData[63], [64] Analog_In[363] 30053

320 SSS-219 SS-SW BD FREQUENCY GEN-2 HIGH SERIAL X X X HI HI LVL 2 5 5 TYCO PR SW BD_ReadData[81], [82] Analog_In[381] 30071

FREQUENCY GEN-2 LOW SERIAL X X X LO LO LVL 2 5 5 TYCO PR SW BD_ReadData[81], [82] Analog_In[381] 30071

320 SSS-301 SS-SW BD GENERATOR #1 RUNNING X X FS_X30_07:I.Data[27].3 Digital_In[255]

320 SSS-302 SS-SW BD GENERATOR #2 RUNNING X X FS_X30_08:I.Data[27].3 Digital_In[265]

320 SSS-900 SS-SW BD GEN NO.1 CIRCUIT BREAKER OPEN COMMAND DO X X GCP ACNR_06:1:O.Data.0 SS_Gen[0].Brkr_Open_CMD

320 SSS-901 SS-SW BD GEN NO.1CIRCUIT BREAKER CLOSE COMMAND DO X X GCP ACNR_06:1:O.Data.1 SS_Gen[0].Brkr_cls_CMD

320 SSS-303 SS-SW BD GEN NO.1 CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.3 Digital_In[84]

320 SSS-313 SS-SW BD GEN NO.1 CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.4 Digital_In[85]

320 SSS-306 SS-SW BD GEN NO.1 CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.5 Digital_In[86]

320 SSS-902 SS-SW BD GEN NO.2 CIRCUIT BREAKER OPEN COMMAND DO X X GCP ACNR_06:1:O.Data.2 SS_Gen[1].Brkr_Open_CMD

320 SSS-903 SS-SW BD GEN NO.2 CIRCUIT BREAKER CLOSE COMMAND DO X X GCP ACNR_06:1:O.Data.3 SS_Gen[1].Brkr_cls_CMD

320 SSS-304 SS-SW BD GEN NO.2 CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.9 Digital_In[90]

320 SSS-314 SS-SW BD GEN NO.2 CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.10 Digital_In[91]

320 SSS-307 SS-SW BD GEN NO.2 CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.11 Digital_In[92]

320 SSS-305 SS-SW BD SHORE PW R CIRCUIT BREAKER OPEN STATUS DI X X X GCP ACNR_06:0:I.Data.12 Digital_In[93]

320 SSS-315 SS-SW BD SHORE PW R CIRCUIT BREAKER CLOSED STATUS DI X X X GCP ACNR_06:0:I.Data.13 Digital_In[94]

320 SSS-308 SS-SW BD SHORE PW R CIRCUIT BREAKER TRIPPED STATUS DI X X X LVL 1 5 0 GCP ACNR_06:0:I.Data.14 Digital_In[95]

13:09

SHEET 9 OF 62

MMC DW G # 0003-202-03

SENSOR L IST - WT/CFPM

MPCMS

DATABASE

NUMBER DESCRIPTION TYPE MANUFACTURER PART NUMBER

UNITS

MEAS

RANGE

MINIMUM

VALUE

RANGE

MAXIMUM

VALUE

RANGE

NORMAL

VALUE ALARM SET POINTS

FURNISHED

BY MMC PART NUMBER REMARKS

VERIFIED

INIT IAL/DATE

SHIP SERVICE SWITCHBOARD

SSS-309 POW ER MANAGEMENT MODE ACTIVE GEN #1 CONT 0

SSS-310 POW ER MANAGEMENT MODE ACTIVE GEN #2 CONT 0

SSS-300 MANUAL CONTROL LOCATION GEN-1 CONT 0

SSS-311 AUTOMATIC CONTROL LOCATION GEN-1 CONT 0

SSS-306 MANUAL CONTROL LOCATION GEN-2 CONT 0

SSS-312 AUTOMATIC CONTROL LOCATION GEN-2 CONT 0

SSS-200 A-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-201 B-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-202 C-PHASE VOLTAGE GEN-1 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-1 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-1 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-1 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-203 A-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-204 B-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-205 C-PHASE CURRENT GEN-1 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-206 POW ER GEN-1 CROMPTON SRP-01 KW ATT 0 125 0 5 SECOND DELAY

SSS-207 FREQUENCY GEN-1 HIGH CROMPTON SRP-01 Hz 56.2 62.3 60 >61 5 5 SECOND DELAY

0 FREQUENCY GEN-1 LOW CROMPTON SRP-01 Hz 56.2 62.3 60 <59 5 5 SECOND DELAY

SSS-212 A-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 A-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-213 B-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 B-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-214 C-PHASE VOLTAGE GEN-2 HIGH HIGH CROMPTON SRP-01 VOLT 0 552 460 510 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-2 HIGH CROMPTON SRP-01 VOLT 0 552 460 500 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-2 LOW CROMPTON SRP-01 VOLT 0 552 460 430 5 2 SECOND DELAY

0 C-PHASE VOLTAGE GEN-2 LOW LOW CROMPTON SRP-01 VOLT 0 552 460 420 5 2 SECOND DELAY

SSS-215 A-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-216 B-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-217 C-PHASE CURRENT GEN-2 CROMPTON SRP-01 AMP 0 150 >117 5 5 SECOND DELAY

SSS-218 POW ER GEN-2 CROMPTON SRP-01 KW ATT 0 125 0 5 SECOND DELAY

SSS-219 FREQUENCY GEN-2 HIGH CROMPTON SRP-01 Hz 56.2 62.3 60 >61 5 5 SECOND DELAY

0 FREQUENCY GEN-2 LOW CROMPTON SRP-01 Hz 56.2 62.3 60 <59 5 5 SECOND DELAY

SSS-301 GENERATOR #1 RUNNING CONT N/A N/A 0

SSS-302 GENERATOR #2 RUNNING CONT N/A N/A 0

SSS-900 GEN NO.1 CIRCUIT BREAKER OPEN COMMAND CONT 0

SSS-901 GEN NO.1CIRCUIT BREAKER CLOSE COMMAND CONT 0

SSS-303 GEN NO.1 CIRCUIT BREAKER OPEN STATUS CONT 0

SSS-313 GEN NO.1 CIRCUIT BREAKER CLOSED STATUS CONT 0

SSS-306 GEN NO.1 CIRCUIT BREAKER TRIPPED STATUS CONT 5

SSS-902 GEN NO.2 CIRCUIT BREAKER OPEN COMMAND CONT 0

SSS-903 GEN NO.2 CIRCUIT BREAKER CLOSE COMMAND CONT 0

SSS-304 GEN NO.2 CIRCUIT BREAKER OPEN STATUS CONT 0

SSS-314 GEN NO.2 CIRCUIT BREAKER CLOSED STATUS CONT 0

SSS-307 GEN NO.2 CIRCUIT BREAKER TRIPPED STATUS CONT 5

SSS-305 SHORE PW R CIRCUIT BREAKER OPEN STATUS CONT 0

SSS-315 SHORE PW R CIRCUIT BREAKER CLOSED STATUS CONT 0

SSS-308 SHORE PW R CIRCUIT BREAKER TRIPPED STATUS CONT 5

13:09

SHEET 10 OF 62

MMC DW G # 0003-202-03