Attachment_5_Rev.__1-Attachment_5_-_Crompton_Configuration_Parameter.pdf

PDF 46 KB Posted

Attached to
The development of Three (3) generator and switchboard control, monitoring and protection systems, along with the associated integration and installation service support.
Solicitation number
N64498-16-R-5019
Issued by

About this file

Attachment 5 Rev. 1 Attachment_5_-_Crompton_Configuration_ParameterAttachment

View the file

Other files

File Type Posted
Admendment_0002.pdf PDF
Attachment_17-_Woodword_L-Series_Integrate_Speed_Control.pdf PDF
Attachment_15-_WT CFPM_SWBD_Layout.pdf PDF
Attachment_20-_BM_SWBD_Layout.pdf PDF
Attachment_21-_BM_Field_Termination_Drawings.pdf PDF
Attachment_16-_WT CPFM_Field_Termination_Drawings.pdf PDF
Attachment_7_Rev.__1-_Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_24-_DEIF_Crompton_Site_Visit_Power_Point_Part_2.pdf PDF
Attachment_19-_DEIF_Layout.pdf PDF
Attachment_23-_DEIF_Crompton_Site_Visit_Power_Point.pdf PDF
Attachment_22-_ASME_Y14.100.pdf PDF
N64498-16-R-5019-0001.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_10_-Generator_System_Operational_Test_BM.docx DOCX document
Attachment_6_-_Generator_System_Wiring_Diagram.pdf PDF
Attachment_4b_-_Welding_Tasks_Electrical_Isolation_Tech_Refresh.pdf PDF
Attachment_12_-Switchboard_System_Operational_Test_BM.docx DOCX document
Attachment_1_-_Alarm_Set_Points_(2).pdf PDF
Copy_of_Attachment_3_-_DEIF_Configuration_Parameter.xlsx XLSX spreadsheet
Attachment_2_-_Crafts_Network_Diagram_(2).pdf PDF
Attachment_7_-_Switchboard_System_Wiring_Diagram.pdf PDF
Attachment_5_-_Crompton_Configuration_Parameter.pdf PDF
cdrls.pdf PDF
Attachment_8_-_Generator_and_Switchboard_System_Input_Output_Test.docx DOCX document
Attachment_11_-Switchboard_System_Operational_Test_WT_PM.docx DOCX document
Attachment_8_Appendix_-_Generator_and_Switchboard_System_IO_Table.pdf PDF
Attachment_14_-_S9074-AR-GIB-010_278.pdf PDF
Attachment_4a_-_Welding_Tasks_Electrical_Isolation_Non_Tech.pdf PDF
Attachment_13_-_S0400-AD-URM-010_TUM.pdf PDF
N64498-16-R-5019.pdf PDF
Attachment_9_-_Generator_System_Operational_Test_WT_PM.docx DOCX document
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

From: Joe Messenger To: "Hannink, Gerrit CWO3 PHIBCB ONE, BRAVO" Cc: "Lyons, Tom L CIV ACB-1 Port Engineer"; "Royce Cearley" Subject: SWBD Crompton settings Date: Wednesday, May 09, 2012 4:45:24 PM

Gerrit, Preprogrammed Crompton shipped this PM for overnight standard delivery via FEDEX. Tracking # is 793546969271.

Listed below are the settings for the Crompton:

Configuration, Communications, Display, and Relay Setup:

• Communications

- Baud Rate = 19200

- Parity = N

- Stop = 1

- Node = 1 for Gen1, 2 for Gen2 – Node 2 on Gen 2 needs to be verified

- Byte Reverse = N

• Relay 1:

- Trip Under Volts = 27

- Caption = 27

- Logged = N

- Latched = N

- Alarm = N

- Failsafe = Y

- Trip point = 395.0

- Diff = 4.8

- Time Delay = 1.0

• Relay 2:

- Trip Over Volts = 59

- Caption = 59

- Logged = N

- Latched = N

- Alarm = N

- Failsafe = N

- Trip point = 432.0

- Diff = 15.0

- Time Delay = 5.0

• Relay 3:

- Trip Sync+DB = 25D

- Caption = 25D

- Logged = N

- Latched = N

- Alarm = N

- Failsafe = Y

- PH Angle = 2

- V Delta = 5

- V Min = 437

- Deadbus = 46

- Time Delay = 0

- Slip Freq. = .37

• Relay 4:

- Trip Reverse Pwr = 32R

- Caption = 32R

- Logged = N

- Latched = Y

- Alarm = N

- Failsafe = N

- Trip point = 6.24kw

- Diff = 3.12kw

• Relay 5:

- Trip Over Volts = 59

- Caption = 59

- Logged = N

- Latched = N

- Alarm = N

- Failsafe = N

- Trip point = 432.0

- Diff = 15.0

• Range:

- SYS Volts = 480

- SYS Amps = 150

- SYS Power = 124.7

- Cutoff = 0A

• User Screens:

- Line 1 = Vavg

- Line 2 = Iavg

- Line 1 = Freq

- Line 1 = Wsum

• Display:

- Date = MM/DD/YY

- LCD Cont = 99

- Backlight = ON

- Input 1 = Gen

- Input 2 = Bus

You should be able to plug and play the unit that we shipped. I included the settings for future use. If you have any problems just give me a call.

V/r, Joe Messenger Software Support Activity Sealift Support Program Office / Jacksonville 8500 Heckscher Drive Jacksonville, FL 32226 Phone: (904) 251-2774 Cell: (715) 587-5871 Fax: (904) 251-2773 Alt. E-mail: Joseph.Messenger@Navy.Mil

File details come from the government source that posted it. Updated .