e) SPR Configuration.txt
"SPR_CONFIG_FILE"
General Configuration
System Type: 3 Phase 3 Wire Primary CT Value: 150 Primary VT Value: 480
Relay #1 Trip Name: "Power Available (No Delay)" Trip Function: Under Voltage (ANSI 27)
Paramaters:
Trip Point: 395 Volts Differential: 4.80 Volts Time Delay: 1.00 Sec.
Latched: No Alarm: No Inverted: Yes Logged: No
Relay #2 Trip Name: "Power Available" Trip Function: "Over Voltage (ANSI 59)
Paramaters:
Trip Point: 432 Volts Differential: 15.00 Volts Time Delay: 5.00 Sec.
Latched: No Alarm: No Inverted: No Logged: No
Relay #3 Trip Name: "Sync Check" Trip Function; "Synchronizing Check with Deadbus (ANSI 25)
Paramaters:
Phase Angle: 2.00 Deg Voltage Delta: 5.00 Volts Voltage Min.: 456.00 Volts Deadbus: 48.00 Volts Time Delay: 0.00 Sec.
Slip Frequency: .37 Hz Latched: No Alarm: No Inverted: No Logged: No
Relay #4 Trip Name: "Reverse Power" Trip Function: Reverse Power (ANSI 32R)
Paramaters:
Trip Point: 6235.38 W Differential: 3115.00 W Time Delay: 5.00 Sec.
Latched: Yes