21R1337_AMD3.pdf
PDF 2 MB Posted
- Attached to
- FY22 MCAF P-1366/AJJY073105P2, APR – MUNITIONS STORAGE IGLOOS PHASE 2, ANDERSEN AIR FORCE BASE, GUAM
- Solicitation number
- N6274221R1337
About this file
This solicitation requests proposals for the construction of eight new earth-covered munitions storage igloos and four optional igloos at Andersen Air Force Base in Guam. The structural, lightning protection, and mechanical work will utilize a design-bid-build approach, while the earth berm, coatings, site improvements, roadways, aprons, utilities, and incidental work will be design-build. Proposals are due within 365 days of contract award date. The new igloos will provide 16,000 square feet of 7-bar rated munitions storage space using conventional design and construction methods. The Naval Facilities Engineering Command is the contracting agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 21R1337_AMD5.pdf | ||
| 21R1337 Note 8.pdf | ||
| 21R1337 Note 7.pdf | ||
| 21R1337_AMD4.pdf | ||
| 21R1337 Note 5.pdf | ||
| 21R1337 Note 6.pdf | ||
| 21R1337 Note 4.pdf | ||
| 21R1337 Note 3.pdf | ||
| 21R1337_AMD2.pdf | ||
| P1366 SV SignIn.pdf | ||
| 21R1337 Note 2.pdf | ||
| 21R1337_AMD1.pdf | ||
| 21R1337 Note 1.pdf | ||
| 1a_P-1366 - Final RFP - DB RFP.pdf | ||
| 1b_P-1366 - Final RFP - Drawings.pdf | ||
| 21R1337-RFP.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP No. N6274221R1337 Amendment No. 0003
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
PART 2: GENERAL REQUIREMENTS
SECTION 01 33 00.05 20 – CONSTRUCTION SUBMITTAL PROCEEDURES
Remove Replace with
“Submittal Register” “Submittal Register”
Pages 16-22 Pages 16-22
Amendment No. 0002 Amendment No. 0003
PART 6: ATTACHMENTS
ATTACHMENT A: PART A DRAWINGS
The following drawings, bearing the revision date of 08/13/2021, supersede previously issued drawings bearing the same number and title:
DRAWING
NUMBER
NAVFAC
DRAWING
NUMBER
REVISION
NUMBER DRAWING TITLE
B-002 17240908 3 FOUNDATION NOTES
S-301 17240929 3 BUILDING SECTIONS
S-302 17240930 3 WALL SECTIONS
ATTACHMENT B: PART A (DESIGN-BID-BUILD) SPECIFICATIONS
SECTION 03 45 33 – PRECAST STRUCTURAL CONCRETE
Remove Replace with
Pages 1-16 Pages 1-15
FY22 MCAF PROJECT P-1366 / AJJY073105P2 APR - Munitions Storage Igloos, Phase 2 Andersen Air Force Base, Guam
1181839 1571341
AMENDMENT No. 0003
REPLACEMENT SHEETS
PART 2: GENERAL REQUIREMENTS
DIVISION 01
GENERAL REQUIRMENTS
SECTION 01 33 00.05 20
CONSTRUCTION SUBMITTAL PROCEDURES
SUBMITTAL REGISTER
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 16 OF 22 PAGES
N62742-16-D0001
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
03 31 30 1.8.3.1Cementitious Material Mill
Certificates
1.6.1.2Field Testing Technician and
Testing Agency
SD-08 Manufacturer’s Instructions
1.8.2.6Coatings
SD-11 Closeout Submittals
1.8.3.1Aggregate Moisture Content
1.8.3.1Aggregate Sampling
1.8.5Concrete Test Reports
1.8.4.3Quality Control Charts
1.8.4.1Daily Inspection Reports
1.8.4.4Quality Team Meetings
1.8.4.2Sampling Logs
03 45 33 SD-02 Shop Drawings
2.1.1.2 GDrawings of Precast Members
SD-03 Product Data
2.2.8.1Inserts
2.2.9Bearing Pads
SD-04 Samples
2.3.9Surface Finish
SD-05 Design Data
2.1.1.2 GDesign Calculations
1.4.3 GConcrete Mix Design
SD-06 Test Reports
1.4.3 GConcrete Mix Design
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P H
C L A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
(a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) (o) (p) (q) (r)
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 17 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
03 45 33 2.2.4Aggregates
1.4.1.1Concrete and Aggregate Quality
Control Testing
2.2.3Water
SD-07 Certificates
2.3Quality Control Procedures
3.12 GConstruction Records
SD-11 Closeout Submittals
1.4.4Batch Ticket
2.2.1 SRecycled Content for Fly Ash and
Pozzolan
2.2.1 SRecycled Content for Ground Iron
Blast-Furnace Slag
05 12 00 SD-01 Preconstruction Submittals
1.5.1.1 GErection and Erection Bracing
Drawings
SD-02 Shop Drawings
1.5.2 GFabrication Drawings
SD-03 Product Data
2.6.2Shop Primer
2.4.1Welding Electrodes and Rods
2.4.2 GNon-Shrink Grout
SD-05 Design Data
3.2 GDesign Calculations for Steel
Connections
1.5.2 GShoring and Temporary Bracing
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 18 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
05 12 00 SD-06 Test Reports
2.6.2Class B Coating
2.3Bolts, Nuts, and Washers
3.7.1.2Weld Inspection Reports
3.7.2.1Bolt Testing Reports
3.7.3Embrittlement Test Reports
SD-07 Certificates
2.2Steel
2.3Bolts, Nuts, and Washers
2.5Galvanizing
1.3AISC Structural Steel Fabricator
Quality Certification
1.3AISC Structural Steel Erector
Quality Certification
1.5.3.1 GWelding Procedures and
Qualifications
2.4.1Welding Electrodes and Rods
3.7.1.1Certified Welding Inspector
3.7.1.2NDT Technician
3.4 GWelding Procedure Specifications
(WPS)
25 05 11 SD-01 Preconstruction Submittals
3.2.6.1 GWireless Communication
Request
3.2.3.2 GDevice Account Lock Exception
Request
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 19 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
25 05 11 3.10 GMultiple IP Connection Device
Request
1.9.1.4 GContractor Computer
Cybersecurity Compliance
Statements
1.9.6 GContractor Temporary Network
Cybersecurity Compliance
Statements
1.4.3ICS Change Request Form
1.4.3ICS SAAR-N Systems Access
Authorization Request Forms
1.4.3ICS Privileged Access Form
SD-02 Shop Drawings
3.2.4.1 GUser Interface Banner Schedule
1.7.2 GNetwork Communication Report
1.7.5 GCybersecurity Riser Diagram
1.7.3 GControl System Inventory Report
1.7.1 GCybersecurity Interconnection
Schedule
SD-03 Product Data
1.7.6 GControl System Cybersecurity
Documentation
1.7.7 GSustainment Materials
1.7.8 GSecurity Controls Documentation
SD-06 Test Reports
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 20 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
25 05 11 1.4.2 GWireless Communication Test
Report
SD-07 Certificates
1.8 GSoftware Licenses
1.6.1 GCybersecurity Representative's
Certification Of Qualifications
SD-08 Manufacturer’s Instructions
3.15 GOperator Manual
SD-11 Closeout Submittals
3.6.2.2.5 GPassword Summary Report
1.7.4 GSoftware Recovery And
Reconstitution Images
3.3.2.1 GDevice Audit Record Upload
Software
25 08 11.00 20 SD-01 Preconstruction Submittals
1.8.1 GAuthorization Strategy Plan
SD-05 Design Data
3.1.2.1 GControl System Security Controls
3.1.2.3 GSecurity Plan
3.1.2.4 GPorts, Protocols, And Services
Management Registration Form
SD-06 Test Reports
3.1.3.3 GACAS Vulnerability Reports
3.1.3.5 GSecurity Technical
Implementation Guide Checklists
3.1.3.4 GSCAP Report
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 21 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
25 08 11.00 20 3.1.3.7 GISSE Checklist (Step 3)
3.1.4.3 GISSE Checklist (Step 4)
SD-07 Certificates
1.7.1 GInformation Assurance Technical
Level II/Security +
26 41 00 SD-02 Shop Drawings
1.4.1.1 GOverall lightning protection
system
1.4.1.2 GEach major component
SD-06 Test Reports
1.4.3 GLightning Protection and
Grounding System Test Plan
3.4.1 GLightning Protection and
Grounding System Test
SD-07 Certificates
1.2.3 GLightning Protection System
Installers Documentation
1.4.2 GComponent UL Listed and
Labeled
1.4.4 GLightning protection system
inspection certificate
3.1.1 GRoof manufacturer's warranty
31 23 00.00 20 SD-01 Preconstruction Submittals
1.9.1Shoring and Sheeting Plan
SD-06 Test Reports
1.8 GBorrow Site Testing
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
SUBMITTAL FORM,Jan 96 PREVIOUS EDITION IS OBSOLETE PAGE 22 OF 22 PAGES
FY22 MCAF P-1366 /AJJY073015P2 Munition Storage Igloos (Phase 2)
31 23 00.00 20 3.14.2.1Fill and backfill
3.14.2.2Select granular material
3.3Test pit logs
3.4.1Boring logs
1.9.3Moisture-density relations
1.9.4Field dry density and moisture content
2.2Bedding material
1.9.5Controlled low strength material
(CLSM)
31 32 23 SD-01 Preconstruction Submittals
1.4.1 GProbing and Grouting Plan
SD-03 Product Data
3.1.2Drilling Equipment
3.1.3Grouting Equipment
SD-11 Closeout Submittals
1.4.2 GProbing and Grouting Logs
SUBMITTAL REGISTER
CONTRACT NO.
TITLE AND LOCATION CONTRACTOR
CONTRACTOR:
SCHEDULE DATES
CONTRACTOR
ACTION
APPROVING AUTHORITY
A C T I V I T Y
N O
T R A N S M I T T A L
N O
S P E C
S E C T
DESCRIPTION
ITEM SUBMITTED
P A R A G R A P
A S S I F I C A T I O N
G O V T
O R
A E
R E V W
R SUBMIT
APPROVAL
NEEDED
BY
MATERIAL
NEEDED
BY
A C T I O N
C O D E
DATE
OF
ACTION
DATE FWD
TO APPR
AUTH/
DATE RCD
FROM
CONTR
DATE FWD
TO OTHER
REVIEWER
DATE RCD
FROM OTH
REVIEWER
A C T I O N
C O D E
DATE
OF
ACTION
MAILED
TO
CONTR/
DATE RCD
FRM APPR
AUTH REMARKS
ATTACHMENT A: PART A DRAWINGS
B-002 – FOUNDATION NOTES
S-301 – BUILDING SECTIONS
S-302 – WALL SECTIONS
STRUCTURAL GENERAL NOTES
SCHEDULE - FOUNDATION SUBGRADE PREPARATION - BASIS OF BID
B-002
08/13/2021
KO
EVAN MIZUE
B1TRANSVERSE BUILDING SECTION
C1LONGITUDINAL BUILDING SECTION
S-301
08/13/2021
A1WALL SECTION AT DOOR A3SIDE WALL SECTION A4REAR WALL SECTION
S-302
08/13/2021
ATTACHMENT B:
PART A (DESIGN BID-BUILD) SPECIFICATIONS
DIVISION 03
CONCRETE
SECTION 03 45 33
PRECAST STRUCTURAL CONCRETE
FY22 MCAF PROJECT P-1366/AJJY073105P2 APR - Munitions Storage 1181839 Igloos, Phase 2, Andersen Air Force Base, Guam
SECTION 03 45 33
PRECAST STRUCTURAL CONCRETE
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO LRFDCONS (3rd Edition; 2010, 2011, 2012, 2014, 2015, and 2016 Int) Bridge Construction Specifications
AASHTO M 251 (2006; R 2011) Standard Specification for Plain and Laminated Elastomeric Bridge Bearings
AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)
ACI 318 (2014; Errata 1-2 2014; Errata 3-5 2015;
Errata 6 2016; Errata 7-9 2017) Building Code Requirements for Structural Concrete (ACI 318-14) and Commentary (ACI 318R-14)
AMERICAN HARDBOARD ASSOCIATION (AHA)
AHA A135.4 (1995; R 2004) Basic Hardboard
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
AWS D1.4/D1.4M (2011) Structural Welding Code - Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A27/A27M (2017) Standard Specification for Steel Castings, Carbon, for General Application
ASTM A47/A47M (1999; R 2014) Standard Specification for Ferritic Malleable Iron Castings
PART 6 - SECTION 03 45 33 Page 1
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM C1107/C1107M (2017) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C1218/C1218M (2017) Standard Test Method for Water-Soluble Chloride in Mortar and Concrete
ASTM C94/C94M (2017a) Standard Specification for Ready-Mixed Concrete
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM D2240 (2015; E 2017) Standard Test Method for Rubber Property - Durometer Hardness
PRECAST/PRESTRESSED CONCRETE INSTITUTE (PCI)
PCI MNL-116 (1999) Manual for Quality Control for Plants and Production of Structural Precast Concrete Products, 4th Edition
PCI MNL-120 (2010) PCI Design Handbook - Precast and Prestressed Concrete, 6th Edition
PCI MNL-124 (2011) Design for Fire Resistance of Precast Prestressed Concrete, Third Edition
PCI MNL-135 (2000) Tolerance Manual for Precast and Prestressed Concrete Consturction
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-C-882 (1989; Rev E) Cloth, Duck, Cotton or Cotton-Polyester Blend, Synthetic Rubber, Impregnated, and Laminated, Oil Resistant
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2014) Fire Resistance Directory
1.2 MODIFICATION TO REFERENCE
In the ACI publications, reference to the "Building Official," the "Structural Engineer" and the "Architect/Engineer" must be interpreted to mean the Contracting Officer.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING. Submit the following in accordance with
PART 6 - SECTION 03 45 33 Page 2
Section 01 33 00.05 20 CONSTRUCTION SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Drawings of Precast Members ; G
SD-03 Product Data
Anchorage and Lifting Inserts and devices
Bearing Pads
SD-04 Samples
Surface Finish
SD-05 Design Data
Precast Concrete Members Design Calculations ; G
Concrete Mix Design ; G
SD-06 Test Reports
Concrete Mix Design ; G
Fly Ash
Pozzolan
Ground Granulated Blast-Furnace Slag
Aggregates
Concrete and Aggregate Quality Control Testing
Water
SD-07 Certificates
Quality Control Procedures
Construction Records ; G
SD-11 Closeout Submittals
Concrete Batch Ticket Information
Recycled Content for Fly Ash and Pozzolan ; S
Recycled Content for Ground Iron Blast-Furnace Slag ; S
1.4 QUALITY ASSURANCE
1.4.1 Qualifications
1.4.1.1 Manufacturer Qualifications
PCI MNL-116 . Plants must be certified by the PCI Plant Certification
PART 6 - SECTION 03 45 33 Page 3
Program for Category C1 work. At the Contracting Officer's option, PCI Plant quality control program records must be available for review.
PCI MNL-116 . Where panels are manufactured by specialists in plants not currently enrolled in the PCI "Quality Control Program," provide a product quality control system in accordance with PCI MNL-116 and perform concrete and aggregate quality control testing using an approved, independent commercial testing laboratory. Submit test results to the Contracting Officer.
1.4.1.2 Erector Certification
Erector with erecting organization and all erecting crews certified and designated by PCI's Certificate of Compliance to erect Category S2 (Complex Structural Systems).
1.4.1.3 Welding Qualifications
Provide AWS D1.1/D1.1M qualified welders who are currently certified at contract award date and have maintained their certificates over the past year.
1.4.2 Regulatory Requirements
Provide precast members in conformance with ACI 318 and PCI MNL-120 .
1.4.3 Concrete Mix Design
ACI 318 . The minimum compressive strength of concrete at 28 days must be 5000 psi , unless otherwise indicated. Concrete mix design must meet requirements specified in Section 03 31 30 MARINE CONCRETE.
Sixty days minimum prior to concrete placement, submit a mix design for each strength and type of concrete. Submit a complete list of materials including type; brand; source and amount of cement, complementary cementitious materials, and admixtures; and applicable reference specifications. Submit mill test and all other test for cement, complementary cementitious materials, aggregates, and admixtures. Provide documentation of maximum nominal aggregate size, gradation analysis, percentage retained and passing sieve, and a graph of percentage retained verses sieve size. Provide mix proportion data using at least three different water-cementitious material ratios for each type of mixture, which produce a range of strength encompassing those required for each type of concrete required. If source material changes, resubmit mix proportion data using revised source material. Provide only materials that have been proven by trial mix studies to meet the requirements of this specification, unless otherwise approved in writing by the Contracting Officer. Indicate clearly in the submittal where each mix design is used when more than one mix design is submitted. Resubmit data on concrete components if the qualities or source of components changes.
For previously approved concrete mix designs used within the past twelve months, the previous mix design may be re-submitted without further trial batch testing if accompanied by material test data conducted within the last six months. Obtain mix design approval from the contracting officer prior to concrete placement.
1.4.4 Certificates: Record Requirement
ASTM C94/C94M. Submit mandatory batch ticket information for each load of
PART 6 - SECTION 03 45 33 Page 4 ready-mixed concrete.
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Transportation
1.5.1.1 Transporting Members
Transport members in a manner to avoid excessive stresses that could cause cracking or other damage.
1.5.1.2 Lateral Deflection or Vibration
Any noticeable indication of lateral deflection or vibration during transportation must be corrected by rigid bracing between members or by means of lateral trussing.
1.5.2 Storage
1.5.2.1 Storage Areas
Storage areas for precast members must be stabilized, and suitable foundations must be provided, so differential settlement or twisting of members will not occur.
1.5.2.2 Stacked Members
Stack members with adequate dunnage and bracing to control cracking, distortion, warping or other physical damage. Stack members such that lifting devices will be accessible and undamaged.
1.5.3 Handling of Members
The location of pickup points for handling of the members and details of the pickup devices must be shown in shop drawings. Members must be handled only by means of approved devices at designated locations.
Members must be maintained in an upright position at all times and picked up and supported as shown in approved shop drawings.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
The work includes the provision of precast non-prestressed concrete herein referred to as precast members. Precast members must be the product of a manufacturer specializing in the production of precast concrete members.
2.1.1 Design Requirements
Design precast members in accordance with ACI 318 and the PCI MNL-120 .
Design precast members (including connections) for the design load conditions and spans indicated, and handling and erection stresses, and for additional loads imposed by openings and supports of the work of other trades. Design precast members for handling without cracking in accordance with the PCI MNL-120 .
2.1.1.1 Loads
Loadings for members and connections must include all dead load, live
PART 6 - SECTION 03 45 33 Page 5 load, applicable lateral loads such as wind and earthquake, applicable construction loads such as handling, erection loads, and other applicable loads.
2.1.1.2 Drawing and Design Calculation Information
Submit drawings and design calculations indicating complete information for the fabrication, handling, and erection of the precast member.
Include a cover page with the design calculations, signed and sealed by the registered design professional who prepared the design. Drawings must not be reproductions of contract drawings. Design calculations, drawings of precast members (including connections) must be made by a registered professional engineer experienced in the design of precast concrete members, and submitted for approval prior to fabrication. The drawings must indicate, as a minimum, the following information:
a. Plans, elevations and other drawing views showing the following:
(1) Member piece marks locating and defining products furnished by the manufacturer.
(2) Headers for openings.
(3) Location and size of openings.
(4) Relationships to adjacent material.
(5) Joints and openings between members and between members and other construction.
(6) Location of field installed anchors.
(7) Erection sequences and handling requirements
(8) Areas receiving toppings and magnitude of topping thickness.
Identify areas where topping is an integral part of the structural capacity of the precast members.
(9) Lifting and erection inserts
b. Elevations, sections and other details for each member showing the following:
(1) Connections between members and connections between members and other construction.
(2) Connections for work of other trades and cast-in items and their relation to other trades.
(3) Dimensioned size and shape for each member with quantities, position and other details of reinforcing steel, anchors, inserts and other embedded items.
(4) Lifting, erection and other handling devices and inserts.
(5) Surface finishes of each member.
(6) Estimated cambers
PART 6 - SECTION 03 45 33 Page 6
d. Strength properties for concrete, steel and other materials.
e. Methods for storage and transportation.
f. Description of loose, cast-in and field hardware.
g. All dead, live, handling, erection and other applicable loads used in the design.
h. Signature and seal of the registered design professional who prepared the design.
2.1.2 Performance Requirements
Precast members where indicated must have a fire rating as indicated in accordance with UL Fire Resistance , or as designed in accordance with
PCI MNL-124 .
2.2 MATERIALS
2.2.1 Material Sustainability Criteria
For products in this section, where applicable and to extent allowed by performance criteria, provide and document the following in accordance with Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING:
a. Recycled content for fly ash and pozzolan
b. Recycled content for Ground Iron Blast-Furnace Slag
2.2.2 Cementitious Materials
For exposed concrete, use one manufacturer and one source for each type of cement, ground slag, fly ash, and pozzolan. Refer to Section 03 31 30
MARINE CONCRETE.
2.2.2.1 Fly Ash
ASTM C618, Class F, except that the maximum allowable loss on ignition must not exceed 6 percent. Class F fly ash for use in mitigating Alkali-Silica Reactivity must have a Calcium Oxide (CaO) content of less than 8 percent and a total equivalent alkali content less than 1.5 percent.
Add with cement. Fly ash content must be a minimum of 15 percent by weight of cementitious material, provided the fly ash does not reduce the amount of cement in the concrete mix below the minimum requirements of local building codes. Where the use of fly ash cannot meet the minimum level, provide the maximum amount of fly ash permittable that meets the code requirements for cement content. Report the chemical analysis of the fly ash in accordance with ASTM C311/C311M. Evaluate and classify fly ash in accordance with ASTM D5759.
2.2.2.2 Raw or Calcined Natural Pozzolan
Natural pozzolan must be raw or calcined and conform to ASTM C618, Class N, including the optional requirements for uniformity and effectiveness in controlling Alkali-Silica reaction and must have an ignition loss not exceeding 3 percent. Class N pozzolan for use in mitigating Alkali-Silica Reactivity must have a Calcium Oxide (CaO) content of less than 13 percent and total equivalent alkali content less than 3 percent.
PART 6 - SECTION 03 45 33 Page 7
2.2.2.3 Ultra Fine Fly Ash and Ultra Fine Pozzolan
Ultra Fine Fly Ash (UFFA) and Ultra Fine Pozzolan (UFP) must conform to ASTM C618, Class F or N, and the following additional requirements:
a. The strength activity index at 28 days of age must be at least 95 percent of the control specimens.
b. The average particle size must not exceed 6 microns.
c. The sum of SiO2 + Al2O3 + Fe2O3 must be greater than 77 percent.
2.2.2.4 Ground Granulated Blast-Furnace Slag
ASTM C989/C989M, Grade 100. Slag content must be a minimum of 25 percent by weight of cementitious material.
2.2.2.5 Portland Cement
Provide cement that conforms to ASTM C150/C150M, Type II, low alkali including false set requirements with tri-calcium aluminates (C3A) content less than 10 percent and a maximum cement-alkali content of 0.80 percent Na2Oe (sodium oxide) equivalent. Use one brand and type of cement for formed concrete having exposed-to-view finished surfaces.
2.2.3 Water
Water must comply with the requirements of ASTM C1602/C1602M . Minimize the amount of water in the mix. Improve workability by adjusting the grading rather than by adding water. Water must be potable; free from injurious amounts of oils, acids, alkalis, salts, organic materials, or other substances deleterious to concrete. Submit test report showing water complies with ASTM C1602/C1602M . Refer to Section 03 31 30 MARINE
CONCRETE.
2.2.4 Aggregates
ASTM C33/C33M, except as modified herein. Furnish aggregates for exposed concrete surfaces from one source. Provide aggregates that do not contain any substance which may be deleteriously reactive with the alkalies in the cement. Submit test report showing compliance with ASTM C33/C33M.
Fine and coarse aggregates must show expansions less than 0.08 percent at 28 days after casting when testing in accordance with ASTM C1260. Should the test data indicate an expansion of 0.08 percent or greater, reject the aggregate(s) or perform additional testing using ASTM C1567 using the Contractor's proposed mix design. In this case, include the mix design low alkali portland cement and one of the following supplementary cementitious materials: Refer to Section 03 31 30 MARINE CONCRETE.
a. GGBF slag at a minimum of 40 percent of total cementitious
b. Fly ash or natural pozzolan at a minimum of total cementitious of
(1) 30 percent if (SiO2 plus Al2O3 plus Fe2O3) is 65 percent or more,
(2) 25 percent if (SiO2 plus Al2O3 plus Fe2O3) is 70 percent or more,
(3) 20 percent if (SiO2 plus Al2O3 plus Fe2O3) is 80 percent or more,
(4) 15 percent if (SiO2 plus Al2O3 plus Fe2O3) is 90 percent or more.
PART 6 - SECTION 03 45 33 Page 8
If a combination of these materials is chosen, the minimum amount must be a linear combination of the minimum amounts above. Include these materials in sufficient proportion to show less than 0.08 percent expansion at 28 days after casting when tested in accordance with
ASTM C1567.
Aggregates must not possess properties or constituents that are known to have specific unfavorable effects in concrete when tested in accordance with ASTM C295/C295M.
2.2.5 Grout
2.2.5.1 Nonshrink Grout
ASTM C1107/C1107M .
2.2.5.2 Cementitious Grout
Must be a mixture of portland cement, sand, and water. Proportion one part cement to approximately 2.5 parts sand, with the amount of water based on placement method.
2.2.6 Admixtures
Refer to Section 03 31 30 MARINE CONCRETE.
2.2.6.1 Accelerating
ASTM C494/C494M, Type C or E.
2.2.6.2 Water Reducing
ASTM C494/C494M, Type A, E, or F.
2.2.7 Reinforcement
2.2.7.1 Reinforcing Bars
ASTM A615/A615M , Grade 60 ; ASTM A706/A706M , Grade 60 .
Refer to Section 03 31 30 MARINE CONCRETE.
2.2.7.2 Wire
ASTM A1064/A1064M .
2.2.7.3 Supports for Concrete Reinforcement
Include bolsters, chairs, spacers, and other devices necessary for proper spacing, supporting, and fastening reinforcement bars and wire in place.
Ensure legs of supports in contact with formwork for sections that will be exposed to weather are hot-dip galvanized after fabrication, plastic coated, or corrosion-resistant steel bar supports.
2.2.8 Metal Accessories
Provide ASTM A123/A123M or ASTM A153/A153M galvanized.
PART 6 - SECTION 03 45 33 Page 9
2.2.8.1 Inserts
ASTM A47/A47M, Grade 32510 , or ASTM A27/A27M Grade 60-30 . Submit product data.
2.2.8.2 Structural Steel
ASTM A36/A36M. Refer to Section 05 12 00 STRUCTURAL STEEL.
2.2.8.3 Bolts
ASTM A307; ASTM A325Refer to Section 05 12 00 STRUCTURAL STEEL.
2.2.8.4 Nuts
ASTM A563Refer to Section 05 12 00 STRUCTURAL STEEL.
2.2.8.5 Washers
ASTM F844 washers for ASTM A307 bolts, and ASTM F436 washers for ASTM A325 bolts. Refer to Section 05 12 00 STRUCTURAL STEEL.
2.2.9 Bearing Pads
Submit product data for all bearing pads being used.
2.2.9.1 Elastomeric
AASHTO M 251, for plain neoprene bearings.
2.2.9.2 Hardboard (Interior Only)
AHA A135.4 , class as specified by the precast manufacturer.
2.2.9.3 Random-Oriented, Fiber-Reinforced Elastomeric Pads
Preformed, randomly oriented synthetic fibers set in elastomer. Surface hardness of 70 to 90 Shore A durometer according to ASTM D2240. Capable of supporting a compressive stress of 3000 psi with no cracking, splitting or delaminating in the internal portion of the pad.
2.2.9.4 Cotton-Duck-Fabric-Reinforced Elastomeric Pads
Preformed, horizontally layered cotton-duck fabric bonded to an elastomer. Surface hardness of 80 to 100 Shore A durometer according to ASTM D2240. Conforming to Division II, Section 18.10.2 of AASHTO LRFDCONS Bridge Design Specifications or Military Specification MIL-C-882 .
2.2.9.5 Frictionless Pads
Polytetrafluoroethylene (PTFE), glass-fiber reinforced, bonded to stainless or mild-steel plates, or random-oriented, fiber-reinforced elastomeric pads, of type required for in-service stress.
2.2.9.6 High-Density Plastic
Multimonomer, nonleaching, plastic strip capable of supporting loads with no visible overall expansion.
PART 6 - SECTION 03 45 33 Page 10
2.3 PRODUCTION QUALITY CONTROL PROCEDURES
PCI MNL-116 unless specified otherwise. Submit quality control procedures established in accordance with PCI MNL-116 by the precast manufacturer.
2.3.1 Forms
Brace forms to prevent deformation. Forms must produce a smooth, dense surface. Use forms and form-facing materials that are nonreactive with concrete such as wood, metal, plastic, or other approved materials.
Conform to the shapes, lines, and dimensions indicated and are within the limits of the specified fabrication tolerances. Chamfer exposed edges of columns and beams 3/4 inch , unless otherwise indicated. Provide threaded or snap-off type form ties.
2.3.2 Tolerances
Fabricate structural precast concrete members of shapes, lines and dimensions indicated, so each finished member complies with PCI MNL-135 product tolerances as well as position tolerances for cast-in items.
2.3.3 Reinforcement Placement
ACI 318 and PCI MNL-116 for placement and splicing. Place and secure steel bars, and other reinforcement by means of metal bar supports and spacers. Reinforcement may be preassembled before placement in forms.
Provide exposed connecting bars, or other approved connection methods, between precast and cast-in-place construction. Remove any excess mortar that adheres to the exposed connections.
2.3.4 Built-In Anchorage Devices
Position, anchor, and locate anchorage devices where they do not affect the position of the main reinforcement or placing concrete. Bearing plates; set level, aligned properly, and anchored in the exact location indicated.
2.3.5 Lifting Devices
Provide lifting devices designed for 100-percent impact, and of materials sufficiently ductile to ensure visible deformation before fracture.
2.3.6 Blockouts
Provide blockouts as indicated.
2.3.7 Identification Markings
Clearly mark each structural section in a permanent manner to indicate its location and orientation in the building and the pickup points.
Ensure each structural section has the date of casting plainly indented in the unexposed face of the concrete.
PART 6 - SECTION 03 45 33 Page 11
2.3.8 Concrete
2.3.8.1 Concrete Mixing
ASTM C94/C94M. Mixing operations must produce batch-to-batch uniformity of strength, consistency, and appearance.
2.3.8.2 Concrete Placing
PCI MNL-116 .
2.3.8.3 Concrete Curing
PCI MNL-116 .
2.3.9 Surface Finish
Repairs located in a bearing area must be approved by the Contracting Officer prior to repairs. Defects must be repaired or rejected as specified in paragraph ACCEPTANCE/REJECTION OF DEFECTS.
2.3.9.1 Unformed Surfaces
Provide a steel troweled finish. For top face of roof panels provide a roughened/scratched surface.
2.3.9.2 Formed Surfaces
PCI MNL-116 , Appendix C, for grades of surface finishes.
a. Unexposed Surfaces: Provide a standard grade surface finish.
b. Exposed Surfaces: Provide a standard grade surface finish.
2.3.10 Acceptance/Rejection of Defects
2.3.10.1 Minor Defects
All honeycombed areas, chipped corners, air pockets over 1/4 inch in diameter, and other minor defects involve less than 36 square inches of concrete must be repaired. Form offsets of fins over 1/8 inch must be ground smooth. All unsound concrete must be removed from defective areas prior to repairing. All surfaces permanently exposed to view must be repaired by a blend of portland cement and white cement properly proportioned so that the final color when cured will be the same as adjacent concrete. Precast members containing hairline cracks which are visible and are less than 0.01 inches in width, may be accepted, except that cracks larger than 0.005 inches in width for surfaces exposed to the weather must be repaired.
2.3.10.2 Major Defects
Major defects are those which involve more than 36 square inches of concrete or expose stressing tendons or reinforcing steel. If one or more major defects appear in a member, it will be rejected. Cracks of a width of more than 0.01 inch will be cause for rejection of the member.
PART 6 - SECTION 03 45 33 Page 12
2.4 TESTS, INSPECTIONS, AND VERIFICATIONS
2.4.1 Chloride Ion Concentration Test
Sampling and determination of water soluble chloride ion content in accordance with ASTM C1218/C1218M . Maximum water soluble chloride ion concentrations in hardened concrete at ages from 28 to 42 days contributed from the ingredients including water, aggregates, cementitious materials, and admixtures must not exceed 0.06 percent by weight of cement.
2.4.2 Factory Inspection
At the option of the Contracting Officer, precast units may be inspected by the Contracting Officer prior to being transported to the job site.
The Contractor must give notice 14 days prior to the time the units will be available for plant inspection. Neither the exercise nor waiver of inspection at the plant will affect the Government's right to enforce contractual provisions after units are transported or erected.
PART 3 EXECUTION
3.1 EXAMINATION
Prior to erection, and again after installation, precast members must be checked for damage, such as cracking, spalling, and honeycombing. As directed by the Contracting Officer, precast members that do not meet the surface finish requirements specified in paragraph SURFACE FINISH must be repaired, or removed and replaced with new precast members.
3.2 ERECTION
Precast members must be erected after the concrete has attained the specified compressive strength, unless otherwise approved by the precast manufacturer. Erect in accordance with the approved shop drawings.
PCI MNL-135 for tolerances. Provide a 1:500 tolerance, if no tolerance is specified. Brace precast members, unless design calculations submitted with the shop drawings indicate bracing is not required. Follow the manufacturer's recommendations for maximum construction loads. Place precast members level, plumb, square, and true within tolerances. Align member ends.
3.3 BEARING SURFACES
Must be flat, free of irregularities, and properly sized. Size bearing surfaces to provide for the indicated clearances between the precast member and adjacent precast members or adjoining field placed surfaces.
Correct bearing surface irregularities with nonshrink grout. Provide bearing pads where indicated or required. Do not use hardboard bearing pads in exterior locations. Place precast members at right angles to the bearing surface, unless indicated otherwise, and draw-up tight without forcing or distortion, with sides plumb.
3.4 ANCHORAGE
Provide anchorage for fastening work in place. Conceal fasteners where practicable. Make threaded connections up tight and nick threads to prevent loosening.
PART 6 - SECTION 03 45 33 Page 13
3.5 WELDING
AWS D1.1/D1.1M , AWS D1.4/D1.4M for welding connections and reinforcing splices. Protect the concrete and other reinforcing from heat during welding. Weld continuously along the entire area of contact. Grind smooth visible welds in the finished installation.
3.6 OPENINGS
Holes or cuts requiring reinforcing to be cut, which are not indicated on the approved shop drawing, must only be made with the approval of the Contracting Officer and the precast manufacturer. Drill holes less than 12 inches in diameter with a diamond tipped core drill. Ensure cuts are straight and at 90 degrees to the surfaces without breaking or spalling the edges.
3.7 GALVANIZING REPAIR
Repair damage to galvanized coatings using ASTM A780/A780M zinc rich paint for galvanized surfaces damaged by handling, transporting, cutting, welding, bolting, or acid washing. Do not heat surfaces to which repair paint has been applied.
3.8 GROUTING
Clean and fill keyways between precast members, and other indicated areas, solidly with nonshrink grout or cementitious grout. Provide reinforcing where indicated. Remove excess grout before hardening.
3.9 SEALANTS
ASTM C920, Type S or M.
Provide as indicated.
Where surfaces have been treated with curing compounds, oil, or other such materials, remove materials by sandblasting or wire brushing. Remove laitance, efflorescence and loose mortar from the joint cavity. Remove resulting debris prior to sealant installation.
Provide sealants compatible with the material and locations to which they are applied. Do not use a sealant that has exceeded its shelf life or has jelled and cannot be discharged in a continuous flow from the sealant gun.
Apply sealants in accordance with the manufacturer's printed instructions with a gun having a nozzle that fits the joint width. Work sealant into joints so as to fill the joints solidly without air pockets. Tool sealant after application to ensure adhesion. Apply sealant uniformly smooth and free of wrinkles. Upon completion of sealant application, roughen partially filled or unfilled joints, apply additional sealant. Apply sealer over sealants in accordance with the sealant manufacturer's printed instructions.
3.10 PROTECTION AND CLEANING
Protect exposed-to-view surfaces against staining and other damage until completion of the work.
Upon completion of installation, swept clean and leave ready slab surfaces to receive concrete floor topping, roofing, or other covering.
PART 6 - SECTION 03 45 33 Page 14
3.11 CONCRETE TOPPING
Provide as indicated and as specified in Section 03 31 30 MARINE CONCRETE.
3.12 CONSTRUCTION RECORDS
Complete construction records must be kept of the manufacturing, handling, and erection of the precast-prestressed concrete members and submitted.
Records must be kept for, but not limited to, the following items:
a. Specifications of material used in the manufacture of the members.
b. Time-temperature history of the concrete members from casting to the transfer of the prestress force.
c. Records of the tendon stressing operation including initial prestress force, measured elongation, how it was measured, and how the tendons were stressed and destressed.
d. Records of inspection of the members before and after the prestress force is transferred to the members.
e. Records of the inspection of the members each time they are moved.
f. Records of any defects in the member and any corrective measures taken.
-- End of Section --
PART 6 - SECTION 03 45 33 Page 15
| AMD 0003 |
| P-1366 - DB RFP - Amendment #0003 (2021-08-13) - Attachments |
| REPLACEMENT SHEETS |
| PART 2: GENERAL REQUIREMENTS |
| DIVISION 1 - GENERAL REQUIREMENTS |
| SECTION 01 33 00.05 20 CONSTRUCTION SUBMITTAL PROCEEDURES |
| SUBMITTAL REGISTER |
| PART 6: ATTACHMENTS |
| ATTACHMENT A: PART A DRAWINGS |
| GEOTECHNICAL |
| B-002 - FOUNDATION NOTES |
| STRUCTURAL |
| S-301 - BUILDING SECTIONS |
| S-302 - WALL SECTIONS |
| ATTACHMENT B: PART A (DESING-BID-BUILD) SPECIFICATIONS |
| DIVISION 3 - CONCRETE |
| SECTION 03 45 33 - PRECAST STRUCTURAL CONCRETE |
File details come from the government source that posted it. Updated .