J-1502001-03 AA Facilities Investment Equipment and Systems Inventory Amend 0004.xlsx
XLSX spreadsheet 86 KB Posted
- Attached to
- N62470-21-R-0002 Base Operations Support (BOS) Services at Naval Support Facility (NSF) Redzikowo, Poland
- Solicitation number
- N62470-21-R-0002
View the file
Other files
Show 40 more
Latest 50 of 91 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AA Facility Systems Matrix Attachment J-1502001-03 - Preventive Maintenance (PM) Program Services Matrix
| Spec Item: | 3.2.1 | 3.2.2 | 3.2.3 | 3.2.4 | 3.2.5 | 3.2.6 | 3.2.7 | 3.2.8 | 3.2.9 | |||
| FACILITY NO | Facility Name | AREA | AREA UM | HVAC and Refrigeration Systems | Interior and Exterior Lighting Systems | Lightning Arrestors and Grounding Devices | Fire Protection Systems | Mass Notification Systems | UPS Systems | Emergency Showers and Eyewash Stations | VTE (Scissor Lift) | Overhead Doors |
| 2200 | DECK HOUSE SUPPORT BUILDING (DSB) | 29100 | SF | x | x | x | x | x | x | x | x | x |
| 2400 | SM-3 MAGAZINE (SM3) | 1200 | SF | x | ||||||||
| 2401 | SUPPORT UTILITY BLDG @ SM-3 | 162 | SF | |||||||||
| 2500 | GENERAL PURPOSE WAREHOUSE #1 (GPW1) | 2500 | SF | x | x | x | x | x | x | x | ||
| 2600 | UTILITY BLDG FOR DIESEL GENERATOR#1 | 1032 | SF | x | x | |||||||
| 2601 | UTILITY BLDG FOR DIESEL GENERATOR#2 | 1032 | SF | x | x | |||||||
| 2602 | UTILITY BLDG FOR DIESEL GENERATOR#3 | 1032 | SF | x | x | |||||||
| 2603 | UTILITY BLDG FOR DIESEL GENERATOR#4 | 1032 | SF | x | x | |||||||
| 2604 | UTILITY BLDG FOR LOAD BANK SWITCH | 366 | SF | |||||||||
| 2605 | UTILITY BLDG FOR SWITCHGEAR A | 857 | SF | |||||||||
| 2606 | UTILITY BLDG FOR SWITCHGEAR B | 857 | SF | |||||||||
| 2607 | UTILITY BLDG FOR MV DISCONNECT SWITCH | 203 | SF | |||||||||
| 2608 | UTILITY BLDG FOR INPUT MODULE A | 794 | SF | |||||||||
| 2609 | UTILITY BLDG FOR SCF MODULE A | 1209 | SF | |||||||||
| 2610 | UTILITY BLDG FOR SCF MODULE B | 1209 | SF | |||||||||
| 2611 | UTILITY BLDG FOR INPUT MODULE B | 794 | SF | |||||||||
| 2612 | STORAGE FOR UTILITY SYSTEMS @ MCPE | 203 | SF | x | x | |||||||
| 2700 | MDA ENTRY CONTROL FACILITY (ECF) | 2800 | SF | x | x | x | x | x | x | |||
| 2710 | OVERWATCH AT ECF | 538.2 | SF | x | x | x | ||||||
| 2901 | CM SWITCH STATION BLDG | 604 | SF | x | x | |||||||
| 9200 | MISSION CRITICAL POWER PLANT | x | x | x |
HVAC - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
HVAC SYSTEMS - MDA
| CONDENSING UNIT | |||||||
| FACILITY NAME | COOLING CAPACITY | HEATING CAPACITY | CONDENSER AIR TEMP | MIN EER | SEER | ELECTRICAL | |
| kW | kW | °C | MCA | V/PH/Hz | |||
| GENERAL PURPOSE WAREHOUSE #1 | 7 | 1 | 33 | 11 | 13 | 15 | 230/1/50 |
| SPLIT SYSTEM HP | |||||||||
| FACILITY NAME | ROOM SERVED | COOLING CAPACITY | CONDENSER AIR TEMP | MIN SEER | HEATING CAPACITY | INDOOR UNIT | OUTDOOR UNIT | ||
| ELECTRICAL | ELECTRICAL | ||||||||
| kW | °C | kW | MCA | V/PH/Hz | MCA | V/PH/Hz | |||
| GENERAL PURPOSE WAREHOUSE #1 | M07 COMM | 7 | 33 | 13 | 1 | 1 | 230/1/50 | 12 | 230/1/50 |
| HEAT PUMP | ||||||
| FACILITY NAME | COOLING CAP | HEATTNG CAP | EER | COP | ELECTRICAL | |
| kW | kW | kW | V/PH/Hz | |||
| SM-3 MAGAZINE | 11.2 | 12.5 | 32 | 230/1/50 | ||
| ENTRY CONTROL FACILITY | 22.4 | 28 | 17.1 | 400/3/50 | ||
| ENTRY CONTROL FACILITY | 12.3 | 13.8 | 24 | 230/1/50 | ||
| WATER SUPPLY BUILDING | 5.3 | 3.8 | 3.62 | 230/1/50 |
| BOILER | ||||||||
| FACILITY NAME | INPUT CAPACITY | FUEL | FLOWRATE | PRESSURE DROP | ENTERING FLUID | LEAVING FLUID | EFFICIENCY (MINIMUM) | ELECTRICAL DATA |
| kW | L/s | kPa | °C | °C | VPH/Hz | |||
| WATER SUPPLY BUILDING | 40 | Electric | 0.8 | 61 | 71 | - | 400/3/50 |
| FAN COIL UNIT | ||||||||||||
| FACILITY NAME | AIR FLOW | COOLING, AIRSIDE | HEATING AIRSIDE | ELECTRICAL DATA | Filter Data | |||||||
| REQUIRED TOTAL | REQUIRED SENSIBLE | EDB | EWB | REQUIRED TOTAL | EDB | POWER | V/PH/Hz | Type | Thickness | Weight | ||
| L/s | kW | kW | °C | °C | kW | °C | Watts | mm | kg | |||
| SM-3 MAGAZINE | 1667 | 11.2 | 11.2 | 30.2 | 19.4 | Washable | -- | 50 | ||||
| GENERAL PURPOSE WAREHOUSE #1 | 300 | 7 | 7 | 24 | 24 | 1 | 20 | |||||
| ENTRY CONTROL FACILITY | 165 | 3.1 | 1.7 | 24 | 20 | 2 | 8.3 | 0.05 | 230/1/50 | Washable | - | 20 |
| ENTRY CONTROL FACILITY | 105 | 2.3 | 1.3 | 24 | 20 | 1.9 | 8.3 | 0.07 | 230/1/50 | Washable | - | 18 |
| ENTRY CONTROL FACILITY | 190 | 2.4 | 2.4 | 24 | 20 | 0.8 | 8.3 | 0.02 | 230/1/50 | Washable | - | 14 |
| ENTRY CONTROL FACILITY | 795 | 10.1 | 10 | 24 | 20 | 0.4 | 8.3 | 3.49 | 230/1/50 | Washable | - | 47 |
| ENTRY CONTROL FACILITY | 25 | 0.3 | 0.3 | 24 | 20 | 0.8 | 8.3 | 0.02 | 230/1/50 | Washable | - | 11 |
| ENTRY CONTROL FACILITY | 155 | 2.3 | 1.9 | 24 | 20 | 0.8 | 8.3 | 0.08 | 230/1/50 | Washable | - | 18 |
| ENTRY CONTROL FACILITY | 145 | 2.1 | 1.8 | 24 | 20 | 1 | 8.3 | 0.08 | 230/1/50 | Washable | - | 18 |
| ENTRY CONTROL FACILITY | 150 | 1.7 | 1.6 | 24 | 20 | 1.9 | 8.3 | 0.05 | 230/1/50 | Washable | - | 23 |
| WATER SUPPLY BUILDING | 265 | 5.3 | 5.3 | 30.2 | 19.4 | 5.6 | 3.8 kW | Washable | --- | 40 |
| ELECTRIC HEATERS (Wall, Unit, Baseboard) | |||
| FACILITY NAME | TYPE | HEATING CAPACITY (KW) | V/PH/Hz |
| SM-3 MAGAZINE | Structure Hung | 5 | 230/1/50 |
| SM-3 MAGAZINE | Structure Hung | 5 | 230/1/50 |
| SM-3 MAGAZINE | Structure Hung | 5 | 230/1/50 |
| SM-3 MAGAZINE | Structure Hung | 5 | 230/1/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Resistance | 4 | 230/3/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Resistance | 4 | 230/3/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Resistance | 2 | 230/3/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Resistance | 2 | 230/3/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Resistance | 1 | 230/3/50 |
| ENTRY CONTROL FACILITY | Resistance | 2 | 230/1/50 |
| ENTRY CONTROL FACILITY | Resistance | 2 | 230/1/50 |
| ENTRY CONTROL FACILITY | Resistance | 2 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 9.6 | 230/1/50 |
| WATER SUPPLY BUILDING | Electric | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | Hot Water | 3.5 | 230/1/50 |
| WATER SUPPLY BUILDING | 2 | 230/1/50 |
| FAN | |||||||
| FACILITY NAME | FAN DATA | MOTOR DATA | |||||
| TYPE | AIRFLOW | RPM | STATIC PRESSURE | MAX SONES | POWER | V/PH/Hz | |
| L/a | Pa | kW | |||||
| GENERAL PURPOSE WAREHOUSE #1 | Centrifugal Inline | 425 | 1725 | 240 | 6.5 | 0.1 | 230/1/50 |
| GENERAL PURPOSE WAREHOUSE #1 | Centrifugal Inline | 35 | 950 | 60 | 3 | 0.05 | 230/1/50 |
| WATER SUPPLY BUILDING | Propeller Fan | 1,300 | 1109 | 90 | - | 0.373 | 400/3/50 |
| WATER SUPPLY BUILDING | Propeller Fan | 1,600 | 1219 | 90 | - | 0.373 | 400/3/50 |
| WATER SUPPLY BUILDING | Inline Centrifugal | 25 | 1682 | 100 | - | 0.373 | 230/1/50 |
| ENERGY RECOVERY VENTILATOR | |||||||||||
| FACILITY NAME | EXTERNAL STATIC PRESSURE | SUPPLY FAN | EXHAUST FAN | ELECTRICAL | |||||||
| OUTSIDE AIR EAT DB | SUPPLY AIR EAT DB | AIRFLOW | MOTOR | RETURN AIR EAT DB | EXHAUST AIR EAT DB | AIRFLOW | MOTOR | DRIVE | V/PH/Hz | ||
| Pa | °C | °C | L/s | kW | °C | °C | L/s | kW | |||
| ENTRY CONTROL FACILITY | 54 | 33 | 27 | 130 | 0.1 | 24 | 30 | 85 | 0.1 | Direct | 230/1/501.4 |
| DUCT HEATING COIL | |||
| FACILITY NAME | PRESSURE DROP | HEATING CAPACITY | V/Hz |
| Pa | kW | ||
| ENTRY CONTROL FACILITY | 60 | 5 | 230/50 |
AHU - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
| AHU - MDA | ||||
| Air Handling Units - MDA | ||||
| Supply Fan Data | Cooling Coil | Heating | Filter Data |
| FACILITY NAME | Equipment Type | Location | V/PH/Hz | Air Flow Rate | Ext. Static Pressure | Type | Motor | EAT DB | EAT WB | Sensible Capacity | Total Capacity | EWT | LWT | Water Flowrate | Water Press. Drop | EAT DB | Total Capacity | V/PH/Hz | Min. Cap. States | Type | Thickness | Max. Filter Face Vel. | Weight |
| L/s | Pa | kW | °C | °C | kW | kW | °C | °C | L/s | kPa | °C | kW | mm | m/s | kg | ||||||||
| GENERAL PURPOSE WAREHOUSE #1 | DX | Admin | 230/1/50 | 345 | 100 | Centrifugal | 0.2 | 26 | 18 | 5.8 | 7 | 125 | 14 | 7.2 | 7 | 14 | 7.2 | G4 | 25 | 2.5 | 57 |
UPS - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
UPS SYSTEMS - MDA
| Uninterruptible Power Supply Systems | ||
| FACILITY NAME | Location | Remarks |
ENTRY CONTROL FACILITY Electrical Room - M06
Fire Protection - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
FIRE SYSTEMS - MDA
| Fire Detection and Suppression Systems Equipment | ||||||||||||||||||
| FACILITY NAME | Fire Alarm Control Panel | Fire Alarm Annunciator | Wet Pipe Sprinkler System | Dry Pipe Sprinkler System | Wet Chemical Ext. Sys. | Clean Agent System | Fire Alarm Annunciator | Smoke Detector | Manual Pull Station | Fire Alarm Bell | Tamper Switch | Flow Switch | Pressure Switch | Duct Detector | Dry Chemical Fire Extinguisher | Addressable Initiating Device Module | Addressable Control Module | Post Indicator Valve |
| DECKHOUSE SUPPORT BUILDING | 2 | Y | Y | 3 | 10 | 1 | 6 | 3 | 4 | 11 | 20 | 13 | 1 | 1 |
| SM-3 MAGAZINE | 1 | 5 | 3 | |||||||||||
| GENERAL PURPOSE WAREHOUSE #1 | 1 | Y | 2 | 5 | 1 | 6 | 2 | 1 | ||||||
| ENTRY CONTROL FACILITY | 6 | |||||||||||||
| WATER SUPPLY BUILDING | 1 | Y | 2 | 2 | 16 | 1 | 4 | 35 |
| Fire Pumps | ||||||
| FACILITY NAME | TYPE | L/min. | BAR | RPM | Elec. (V/PH/Hz) | HP |
| WATER SUPPLY BUILDING | Horiz. Centrifugal | 5677 | 7.93 | 2900 | 400/5/50 | 150 |
| WATER SUPPLY BUILDING | Horiz. Centrifugal | 5677 | 7.93 | 2900 | 400/5/51 | 150 |
| WATER SUPPLY BUILDING | Vert. Centrifugal | 95 | 8.62 | 3500 | 400/5/52 | 3 |
POL Systems - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
POL SYSTEMS - MDA
| PUMPS | ||||||
| FACILITY NAME | Description | Fluid | FLOW RATE (L/s) | HEAD (kPa) | MOTOR (kW) | ELECTRICAL (V/PH/Hz) |
| Mission Critical Power Enclosure | DEF Uloading Pump | DEF | 150 | 15.07 | 1.12 | 400/3/50 |
| Mission Critical Power Enclosure | Fuel Forwarding Pump | EURO-5 | 757 | 21.46 | 5.59 | 400/3/50 |
| Fuel Station | Vehicle Fueling Pump | EURO-5 | 757 | 21.46 | 5.59 | 400/3/50 |
| FUEL POLISHER | |||||
| FACILITY NAME | Service Area | Fluid | FLOW RATE (L/s) | MOTOR HP) | ELECTRICAL (V/PH/Hz) |
| Mission Critical Power Enclosure | Bulk Fuel tanks | EURO-5 | 1.9 | 2 | 230/1/50 |
| FUEL STORAGE TANKS | ||||||||
| FACILITY NAME | Descr. | Fluid | Net Capacity | Material | Design Pressure | Operating Pressure | Min Design Temp | Max Design Temp |
| L | (°C) | (°C) | ||||||
| Fuel Station | Vehicle Fueling Fueling Tank/Pump | EURO-5 | 37,900 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
MDA Power BU Generator Fuel Storage EURO-5 37,900 Carbon Steel Atmospheric Atmospheric -31.7 43.3
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
| Mission Critical Power Enclosure | BU Generator Fuel Storage | EURO-5 | 45,500 | Carbon Steel | Atmospheric | Atmospheric | -31.7 | 43.3 |
Mission Critical Power Enclosure Fuel Polisher Draw-off Tank Water & EURO-5 760 Carbon Steel Atmospheric Atmospheric -31.7 43.3
Site BU Generator Fuel Storage EURO-5 37900 Carbon Steel Atmospheric Atmospheric -31.7 43.3
| Other - Miscellaneous | ||
| FACILITY NAME | Service Area | Equipment/System Descriptin |
| POL | POL Systems | Leak Detection System |
Int - Ext. Lighting - AA
| Attachment J-1502001-04 | |||||||||||||||||||||||||||||||||||||||||||||||||
| MCSS Equipment Inventory | |||||||||||||||||||||||||||||||||||||||||||||||||
| Notes: Tab updated in entirety to reflect PL conditions | |||||||||||||||||||||||||||||||||||||||||||||||||
| Removed Facilites not in MDA MILCON for PL | |||||||||||||||||||||||||||||||||||||||||||||||||
| Facility Description | A | AX | A1 | AX1 | B | BX | C | C1 | D | DX | D1 | DX1 | E | EX | E1 | EX1 | F | FX | F1 | FX1 | G | GX | H | HX | JX | K | KX | L1 | LX1 | L | LX | M | MX | N | N1 | NX | Q | S | S2 | P1 | P2 | P3 | TX | U2 | UX | V | W | W1 | |
| DHSB | 121 | 63 | 5 | 8 | 2 | 31 | 9 | 6 | 5 | 5 | 7 | 9 | 6 | 2 | 22 | 16 | |||||||||||||||||||||||||||||||||
| RDH | 9 | 8 | 9 | 2 | 10 | 7 | 5 | 16 | 38 | 34 | 3 | 17 | 16 | ||||||||||||||||||||||||||||||||||||
| MCPE | See Schedules at bottom of this tab for MCPE 50Hz and 60Hz fixtures and quantities | ||||||||||||||||||||||||||||||||||||||||||||||||
| LSUE | See Schedules at bottom of this tab for LSUE 60Hz fixtures and quantities (included in MCPE quantities) | ||||||||||||||||||||||||||||||||||||||||||||||||
| SM-3 | 9 | 1 | |||||||||||||||||||||||||||||||||||||||||||||||
| General Purpose Warehouse 1 | 10 | 10 | 1 | 1 | 2 | 2 | 1 | 6 | 1 | 6 | 3 | ||||||||||||||||||||||||||||||||||||||
| ECF | 4 | 4 | 1 | 5 | 5 | 8 | 4 | 6 | 2 | 5 | 4 | 2 | |||||||||||||||||||||||||||||||||||||
| Water Supply Building | 30 | 27 | 1 | 2 | 1 | ||||||||||||||||||||||||||||||||||||||||||||
| Site - Roadways, Parking, Fenceline, Entry, etc. | 17 | 22 | 23 | 12 | 25 | 86 | |||||||||||||||||||||||||||||||||||||||||||
| 60 Hz Lighting Fixture Schedule | |||||||||||||||||||||||||||||||||||||||||||||||||
| FIXTURE TYPE | DESCRIPTION | MOUNTING STYLE & HEIGHT | MANUFACTURER'S CATALOG NO. | LAMP | FIXTURE VOLTAGE | FIXTURE VA | REMARKS | ||||||||||||||||||||||||||||||||||||||||||
| TYPE | NO. | WATTS | |||||||||||||||||||||||||||||||||||||||||||||||
| A | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMPS | SUSPENDED AT 2895 AFF OR CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 63 | PROVIDE WITH ELECTRONIC BALLAST. PROVIDE WITH WIREGUARD. | ||||||||||||||||||||||||||||||||||||||||
| AX | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMPS WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AT 2895 AFF OR CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST. PROVIDE WITH WIREGUARD. | ||||||||||||||||||||||||||||||||||||||||
| B | 300 X 1200 SURFACE MOUNTED LIGHT FIXTURE T5 FLUORESCENT LAMPS | CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 63 | PROVIDE WITH ELECTRONIC BALLAST, PROVIDE SEALED AND GASKETED FOR HIGH PRESSURE WATER LOCATIONS | ||||||||||||||||||||||||||||||||||||||||
| BX | 300 X 1200 SURFACE MOUNTED LIGHT FIXTURE T5 FLUORESCENT LAMP WITH SELF CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST, PROVIDE SEALED AND GASKETED FOR HIGH PRESSURE WATER LOCATIONS | ||||||||||||||||||||||||||||||||||||||||
| D | RECESSED 600 X 600 DIRECT/INDIRECT FLUORESCENT FIXTURE | RECESSED CEILING | - | FLUOR (T5) | 2 | 14 | MVOLT | 34 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| DX | RECESSED 600 X 600 DIRECT/INDIRECT FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | FLUOR (T5) | 2 | 14 | MVOLT | 34 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| E | RECESSED 600 X 600 DIRECT/INDIRECT FLUORESCENT FIXTURE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | MVOLT | 44 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| EX | RECESSED 600 X 600 DIRECT/INDIRECT FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | MVOLT | 44 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| FX | COMPACT FLUORESCENT FULL CUT-OFF TYPE EXTERIOR WALL PACK FIXTURE WITH (1) INTEGRAL 12 VOLT DC, 20W EMERGENCY LAMP FOR REMOTE MOUNTED BATTERY PACK WHERE INDICATED. SUITABLE FOR WET LOCATION | WALL MOUNT AS NOTED ON PLANS | - | COMPACT FLUOR | 2 | 32 | 277 | 72 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| K | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T8 FLUORESCENT LAMP | SUSPENDED AT 2895 AFF | - | FLUOR (T5) | 3 | 28 | MVOLT | 94 | PROVIDE WITH ELECTRONIC BALLAST. PROVIDE WITH WIREGUARD. | ||||||||||||||||||||||||||||||||||||||||
| KX | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T8 FLUORESCENT LAMP WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AT 2895 AFF | - | FLUOR (T5) | 3 | 28 | MVOLT | 98 | PROVIDE WITH ELECTRONIC BALLAST. PROVIDE WITH WIREGUARD. | ||||||||||||||||||||||||||||||||||||||||
| L | 200 OPEN DOWNLIGHT WITH SPECULAR REFLECTOR | RECESSED CEILING | - | COMPACT FLUOR | 1 | 32 | 277 | 36 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| LX | 200 OPEN DOWNLIGHT WITH SPECULAR REFELECTOR WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | COMPACT FLUOR | 2 | 32 | 277 | 36 | PROVIDED WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| N | STRIP LIGHT 300 X 1200 T5 FLUORESCENT LAMP | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST, PROVIDE WITH WIREGUARD | ||||||||||||||||||||||||||||||||||||||||
| NX | STRIP LIGHT 300 X 1200 T5 FLUORESCENT LAMP WITH SELF CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST, PROVIDE WITH WIREGUARD | ||||||||||||||||||||||||||||||||||||||||
| M | 300 X 1200 SURFACE MOUNTED LIGHT FIXTURE T5 FLUORESCENT LAMPS | CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| MX | 300 X 1200 SURFACE MOUNTED LIGHT FIXTURE T5 FLUORESCENT LAMP WITH SELF CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | CEILING MOUNTED | - | FLUOR (T5) | 2 | 28 | MVOLT | 67 | PROVIDE WITH ELECTRONIC BALLAST | ||||||||||||||||||||||||||||||||||||||||
| X | EXIT SIGN WITH SELF-CONTAINED EMERGENCY BATTERY, UNIVERSAL MOUNT | WALL MOUNT 2300 AFF OR SURFACE CEILING AS INDICATED BY SYMBOL | - | LED | - | - | 120/277 | 2 | REFER TO PLAN AND LEGEND SHEETS FOR REQUIRED MOUNTING | ||||||||||||||||||||||||||||||||||||||||
| Y | EMERGENCY BATTERY PACK UNIT AND LAMPS WITH MINIMUM 125W BATTERY CAPACITY | WALL MOUNT 2300 AFF | - | HALOGEN | 2 | 12 | 120/277 | 30 |
| 50 HERTZ LIGHTING FIXTURE SCHEDULE | ||||||||||||
| FIXTURE TYPE | DESCRIPTION | MOUNTING STYLE & HEIGHT (mm) | MANUFACTURER'S CATALOG NO. | LAMP | FIXTURE VOLTAGE | FIXTURE VA | REMARKS | |||||
| TYPE | NO. | WATTS | ||||||||||
| A1 | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 28 | 230 | 66 | PROVIDE WITH ELECTRONIC BALLAST | |||
| AX1 | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 28 | 230 | 66 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| B1 | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 1 | 14 | 230 | 30 | PROVIDE WITH ELECTRONIC BALLAST | |||
| BX1 | 'INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 1 | 14 | 230 | 30 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| C1 | WALL MOUNTED 600 MIRROR LIGHT T5 LINIEAR FLUORESCENT | WALL MOUNT 2286 AFF | - | FLUOR (T5) | 1 | 14 | 230 | 25 | SUITABLE FOR DAMP LOCATIONS, PROVIDE WITH ELECTRONIC BALLAST | |||
| D1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | 230 | 49 | PROVIDE WITH ELECTRONIC BALLAST | |||
| DX1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | 230 | 49 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| E1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE | RECESSED CEILING | - | FLUOR (T5) | 4 | 14 | 230 | 66 | PROVIDE WITH ELECTRONIC BALLAST | |||
| EX1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | FLUOR (T5) | 4 | 14 | 230 | 66 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| EA1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | 230 | 26 | PROVIDE WITH ELECTRONIC BALLAST | |||
| EAX1 | RECESSED 600 X 600 TROFFER T5 LINEAR FLUORESCENT FIXTURE WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | FLUOR (T5) | 3 | 14 | 230 | 46 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| F1 | FULL CUT-OFF LED TYPE EXTERIOR WALL PACK | WALL MOUNT AS NOTED ON PLANS | - | LED | - | 2300 LUMENS | 230 | 30 | PROVIDE WITH LED DRIVER WITH NO EMERGENCY BACK-UP | |||
| FX1 | FULL CUT-OFF LED TYPE EXTERIOR WALL PACK | WALL MOUNT AS NOTED ON PLANS | - | LED | - | 2300 LUMENS | 230 | 30 | PROVIDE WITH LED DRIVER. INTEGRAL EMERGENCY BATTERY PACK SHALL PROVIDE A MINIMUM 460 LUMENS WITH 90 MINUTE BACK-UP | |||
| K1 | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 54 | 230 | 127 | PROVIDE WITH ELECTRONIC BALLAST | |||
| KX1 | INDUSTRIAL OPEN TYPE FIXTURE 300 X 1200 T5 FLUORESCENT LAMP WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | SUSPENDED AS NOTED ON PLANS | - | FLUOR (T5) | 2 | 54 | 230 | 127 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| L1 | 200 OPEN DOWNLIGHT WITH REFLECTOR | RECESSED CEILING | - | COMPACT FLUOR | 1 | 26 | 230 | 31 | PROVIDE WITH ELECTRONIC BALLAST | |||
| LX1 | 200 OPEN DOWNLIGHT WITH REFLECTOR WITH SELF-CONTAINED EMERGENCY BATTERY AND SELF DIAGNOSTICS MODULE | RECESSED CEILING | - | COMPACT FLUOR | 1 | 26 | 230 | 31 | PROVIDE WITH ELECTRONIC BALLAST. BATTERY PACK SHALL BE MINIMUM 1200 LUMENS WITH 90 MINUTE BACKUP. | |||
| N1 | EMBEDDED OPTICAL FIBER LIGHT STRIP FOR UNDER VEHICLE SEARCH LIGHTING | RECESSED IN GROUND | - | FIBER OPTIC | 1 | 150 | 230 | 176 | PROVIDE WITH ILLUMINATOR ASSEMBLY WITH LAMP | |||
| P1 | POLE MOUNTED ROADWAY FULL CUT-OFF FIXTURE FOR SECURITY & PARKING LOT LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 10000 AFG UNO | - | MH | 1 | 250 | 230 | 290 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| P2 | POLE MOUNTED ROADWAY FULL CUT-OFF FIXTURE FOR SECURITY LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 6000 AFG | - | MH | 1 | 175 | 230 | 208 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| P3 | POLE MOUNTED ROADWAY FULL CUT-OFF FIXTURE FOR SECURITY LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 12000 AFG UNO | - | MH | 1 | 400 | 230 | 456 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| S1 | METAL HALIDE EXTERIOR WALL PACK FIXTURE | WALL MOUNT AS NOTED ON PLANS | - | MH | 1 | 175 | 230 | 208 | FIXTURE SHALL BE CORROSION PROOF | |||
| S2 | METAL HALIDE EXTERIOR WALL PACK FIXTURE | WALL MOUNT AS NOTED ON PLANS | - | MH | 1 | 250 | 230 | 288 | FIXTURE SHALL BE CORROSION PROOF | |||
| S3 | METAL HALIDE EXTERIOR WALL PACK FIXTURE | WALL MOUNT AS NOTED ON PLANS | - | MH | 1 | 50 | 230 | 72 | FIXTURE SHALL BE CORROSION PROOF | |||
| U2 | POLE MOUNTED ROADWAY FIXTURE, IES TYPE II DISTRIBUTION AND FULL CUT-OFF FOR ROADWAY LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 10000 AFG WITH ARM 2.5 METERS HORIZONTAL LENGTH | - | MH | 1 | 250 | 230 | 290 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| W1 | POLE MOUNTED LED FULL CUT-OFF FIXTURE FOR PERIMETER SECURITY FENCE LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 8000 AFG WITH ARM 2.2 METERS HORIZONTAL LENGTH | - | LED | LED | 21350 | ||||||
| LUMENS | 230 | 231 | FIXTURE SHALL BE LED ONLY. FIXTURE SHALL BE CORROSION PROOF. TYPICAL FIXTURE/POLE SPACING IS 32.5 METERS. | |||||||||
| W2 | POLE OR WALL MOUNTED LED FULL CUT-OFF FIXTURE FOR SECURITY LIGHTING. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | SEE DRAWINGS | - | LED | LED | 25620 | ||||||
| LUMENS | 230 | 272 | FIXTURE SHALL BE LED ONLY. FIXTURE SHALL BE CORROSION PROOF. | |||||||||
| X1 | EXIT SIGN WITH SELF-CONTAINED EMERGENCY BATTERY, UNIVERSAL MOUNT | WALL MOUNT 2300 AFF OR SURFACE CEILING AS INDICATED BY SYMBOL | - | LED | - | 5 | 230 | 6.4 | ||||
| Z1 | POLE MOUNTED FLOODLIGHT FIXTURE FOR SECURITY LIGHTING. TILT SHALL BE ADJUSTED DURING INSTALLATION. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 12000 AFG UNO | - | MH | 1 | 400 | 230 | 465 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| Z2 | POLE MOUNTED FLOODLIGHT FIXTURE FOR SECURITY LIGHTING. TILT SHALL BE ADJUSTED DURING INSTALLATION. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | POLE MOUNT 6000 AFG | - | MH | 1 | 400 | 230 | 465 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| Z3 | POLE MOUNTED FLOODLIGHT FIXTURE FOR MAINTENANCE LIGHTING. TILT & DIRECTION SHALL BE ADJUSTED DURING INSTALLATION. COLOR TEMPERATURE SHALL BE 4000 KELVIN NOMINAL. | MOUNT 24000 AFG ON LIGHTNING PROTECTION MAST | - | MH | 1 | 1000 | 230 | 1080 | FIXTURE SHALL BE CORROSION PROOF. CONTRACTOR SHALL USE METAL HALIDE OR EQUIVALENT LED FIXTURE. | |||
| RDH Fixture Schedule | ||||||||||||
| MCPE LIGHTING FIXTURE SCHEDULE 50Hz | ||||||||||||
| TYPE | DESCRIPTION | LAMP | VOLTAGE | Electrical Frequency | TOTAL WATTS | LIGHT FIXTURE LUMENS | BALLAST / LED DRIVER | MOUNTING | Quantity | MANUFACTURER | MODEL | |
| B1 | LENSED 2 x 2 LED LIGHT PANEL w/SURFACE TRIM KIT | LED | 230 V | 50 Hz | 45 W | 3825 fc | 230V DRIVER | SURFACE | 33 | WESTGATE MFG | LP-2x2-45W-35K-D | |
| B1e | LENSED 2 x 2 LED LIGHT PANEL w/SURFACE TRIM KIT and EMERGENCY BATTERY | LED | 230 V | 50 Hz | 45 W | 3825 fc | 230V DRIVER | SURFACE | 30 | WESTGATE MFG | LP-2x2-45W-35K-D | |
| MCPE and LSUE LIGHTING FIXTURE SCHEDULE 60HZ | ||||||||||||
| TYPE | DESCRIPTION | LAMP | VOLTAGE | Electrical Frequency | TOTAL WATTS | LIGHT FIXTURE LUMENS | BALLAST / LED DRIVER | MOUNTING | Quantity | MANUFACTURER | MODEL | |
| A1 | LENSED 2 x 2 LED SURFACE LIGHT FIXTURE | LED | 120 V | 60 Hz | 35 W | 3922 fc | 120V DRIVER | SURFACE | 34 | LITHONIA LIGHTING | 2TLX-40L-FW-A19 | |
| A1e | LENSED 2 x 2 LED SURFACE LIGHT FIXTURE | |||||||||||
| Emergency Fixture with 90min Battery | LED | 120 V | 60 Hz | 35 W | 3922 fc | 120V DRIVER | SURFACE | 30 | LITHONIA LIGHTING | 2TLX-40L-FW-A19-EM | ||
| A2 | LENSED 2 x 2 LED (Lower Lumen Output) SURFACE LIGHT FIXTURE | LED | 120 V | 60 Hz | 18 W | 2035 fc | 120V DRIVER | SURFACE | 2 | LITHONIA LIGHTING | 2TLX-20L-FW-A12 | |
| A2e | LENSED 2 x 2 LED (Lower Lumen Output) SURFACE LIGHT FIXTURE Emergency Fixture with 90min Battery | LED | 120 V | 60 Hz | 18 W | 2035 fc | 120V DRIVER | SURFACE | 16 | LITHONIA LIGHTING | 2TLX-20L-FW-A12-EM |
Int. - Ext. Lighting - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
| INTERIOR/EXTERIOR LIGHTING SYSTEMS - MDA | |||||||||||||||||||||||||||||||||||||||||||||||||
| Facility Name | A | AX | A1 | AX1 | B | BX | C | C1 | D | DX | D1 | DX1 | E | EX | E1 | EX1 | F | FX | F1 | FX1 | G | GX | H | HX | J | K | KX | K1 | KX1 | L1 | LX1 | M | MX | N | N1 | NX | P1 | P2 | P3 | Q | R | S1 | S2 | S3 | T | TX | U2 | UX | |
| Deckhouse Support Building | 130 | 60 | 8 | 2 | 31 | 9 | 6 | 5 | 2 | 6 | 5 | 2 | 22 | 16 | |||||||||||||||||||||||||||||||||||
| SM-3 Magazine | 8 | ||||||||||||||||||||||||||||||||||||||||||||||||
| General Purpose Warehouse 1 | 8 | 12 | 1 | 1 | 1 | 1 | 5 | 2 | 3 | ||||||||||||||||||||||||||||||||||||||||
| Entry Control Facility | 4 | 4 | 15 | 10 | 4 | 4 | 6 | 2 | 2 | 4 | |||||||||||||||||||||||||||||||||||||||
| Water Building | 19 | 21 | 2 |
SITE Roadways, Parking, Fenceline, Entry, etc. TBD
| FIXTURE TYPE | DESCRIPTION | SIZE | Mtg Style | LAMP | FIXTURE | |||
| Type | No. | Watts | V | VA | ||||
| A | Industrial Open Type Fixture | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | MVOLT | 63 |
| AX | Industrial Open Type w/ Emer. Battery Pack | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | MVOLT | 67 |
| A1 | Industrial Open Type Fixture | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | 230 | 66 |
| AX1 | Industrial Open Type w/ Emer. Battery Pack | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | 230 | 66 |
| B | Flourescent Fixture | 600 x 1200 | Recessed | FLOUR (T5) | 3 | 28 | MVOLT | 63 |
| BX | Flour. Fixture w/ Self Contained Battery and Diagnostics Module | 600 x 1200 | Recessed | FLOUR (T5) | 3 | 28 | MVOLT | 67 |
| D | Direct/Indirect Flourescent Fixture | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | MVOLT | 34 |
| DX | Direct/Indirect Flourescent Fixture w/ Emer. Battery Pack | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | MVOLT | 34 |
| D1 | Troffer | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | 230 | 49 |
| DX1 | Troffer w/ Emer. Battery Pack | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | 230 | 49 |
| E | Direct/Indirect Flourescent Fixture | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | MVOLT | 44 |
| EX1 | Direct/Indirect Flourescent Fixture w/ Emer. Battery Pack | 600 x 600 | Recessed | FLOUR (T5) | 3 | 14 | MVOLT | 44 |
| E1 | Troffer | 600 x 600 | Recessed | FLOUR (T5) | 4 | 14 | 230 | 66 |
| EX1 | Troffer w/ Emer. Battery Pack | 600 x 600 | Recessed | FLOUR (T5) | 4 | 14 | 230 | 66 |
| F | Compact Full Cut-Off Type Exterior | Wall | Comp. FLOUR | 2 | 32 | 277 | 72 | |
| F1 | Compact Full Cut-Off Type Exterior | Wall | Comp. FLOUR | 1 | 18 | 230 | 21 | |
| FX1 | Compact Full Cut-Off Type Exterior w/ Emer. Battery Pack | Wall | Comp. FLOUR | 1 | 18 | 230 | 21 | |
| G | Haz. Loc., Class 1, Division 2 Fixture | 300 x 1200 | Wall | FLOUR (T5) | 2 | 28 | 230 | 66 |
| GX | Haz. Loc., Class 1, Division 2 Fixture w/ Emer. Battery Pack | 300 x 1200 | Wall | FLOUR (T5) | 2 | 28 | 230 | 66 |
| K | Industrial Open Type Fixture | 300 x 1200 | Suspended | FLOUR (T5) | 3 | 28 | MVOLT | 94 |
| KX | Industrial Open Type w/ Emer. Battery Pack | 300 x 1200 | Suspended | FLOUR (T5) | 3 | 28 | MVOLT | 98 |
| K1 | Industrial Open Type Fixture | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 54 | 230 | 127 |
| KX1 | Industrial Open Type w/ Emer. Battery Pack | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 54 | 230 | 127 |
| L1 | 200 Open Downlight w/ Reflector | 200 | Suspended | Comp. FLOUR | 1 | 26 | 230 | 31 |
| LX1 | 200 Open Downlight w/ Reflector w/ Emer. Battery Pack | 200 | Suspended | Comp. FLOUR | 1 | 26 | 230 | 31 |
| M | Flourescent Lamp | Ceiling | FLOUR (T5) | 2 | 28 | MVOLT | 67 | |
| MX | Flour. Lamp w/ Self Contained Battery and Diagnostics Module | Ceiling | FLOUR (T5) | 2 | 28 | MVOLT | 67 | |
| N | Strip Light | Suspended | FLOUR (T5) | 2 | 28 | MVOLT | 67 | |
| NX | Strip Light w/ Self Contained Battery and Diagnostics Module | Suspended | FLOUR (T5) | 2 | 28 | MVOLT | 67 | |
| N1 | Embedded Fiber Optic Light Strip | Recessed | Fiber Optic | 1 | 150 | 230 | 176 | |
| P1 | Roadway Full Cut-Off Fixture for Security and Parking | Pole | MH | 1 | 250 | 230 | 290 | |
| P2 | Roadway Full Cut-Off Fixture for Security | Pole | MH | 1 | 175 | 230 | 208 | |
| P3 | Roadway Full Cut-Off Fixture for Security | Pole | MH | 1 | 400 | 230 | 456 | |
| Q | 402 Round Twin Tube | 402 | Surface | Comp. FLOUR | 1 | 36 | 230 | 37 |
| R | Canopy Fixture | Canopy | LED | - | 4800 Lumens | 230 | 58 | |
| S1 | Metal Halide Exterior Wall Pack Fixture | Wall | MH | 1 | 175 | 230 | 208 | |
| S2 | Metal Halide Exterior Wall Pack Fixture | Wall | MH | 1 | 250 | 230 | 288 | |
| S3 | Metal Halide Exterior Wall Pack Fixture | Wall | MH | 1 | 50 | 230 | 72 | |
| T | Haz. Loc., Class 1, Division 2 Fixture | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | 230 | 66 |
| TX | Haz. Loc., Class 1, Division 2 Fixture w/ Emer. Battery Pack | 300 x 1200 | Suspended | FLOUR (T5) | 2 | 28 | 230 | 66 |
| U2 | Roadway Fixture, IES Type II Distr. and Full Cut-Off | Pole | MH | 1 | 250 | 230 | 290 | |
| UX | Diffuser Wrap Around w/ Emer. Battery Pack | 1200 x 200 | Surface | FLOUR (T5) | 2 | 28 | 230 | 66 |
| V | 512 Round Twin Tube | 512 | Surface | Comp. FLOUR | 2 | 36 | 230 | 70 |
| W1 | LED Full Cut-Off Fixture for Perimeter Security Fence | LED | - | 21350 LUMENS | 230 | 231 | ||
| W2 | LED Full Cut-Off Fixture for Security Lighting | LED | - | 25620 LUMENS | 230 | 272 | ||
| X1 | Exit Sign w/ Emergency Battery | Wall | LED | - | 5 | 230 | 6.4 | |
| Y | Emergency Battery Packu Units and Lamps | Wall | Halogen | 2 | 12 | 120/277 | 30 | |
| Z1 | Floodlight Fixture for Security Lighting | Pole | MH | 1 | 400 | 230 | 465 | |
| Z2 | Floodlight Fixture for Security Lighting | Pole | MH | 1 | 400 | 230 | 465 | |
| Z3 | Floodlight Fixture for Maintenance Lighting | Lightning Mast | MH | 1 | 1000 | 230 | 1080 |
Lgtning- Grnd - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
LIGHTNING PROTECTION/GROUNDING SYSTEMS - MDA
| Lightning Protection Systems | ||||||
| FACILITY NAME | No. Ground Points | Conductor Wire | Air Terminal | |||
| Size | Type | Size | Type | Qty | ||
| DECKHOUSE SUPPORT BUILDING | 10 | 50 mm2 | Bare Copper | 10 Dia x 610 | Solid Copper | 46 |
| SM-3 MAGAZINE | 4 | 50 mm2 | Bare Copper | 10 Dia x 610 | Solid Copper | 10 |
| GP WAREHOUSE #1 | 2 | 50 mm2 | Bare Copper | 10 Dia x 610 | Solid Copper | 12 |
| ENTRY CONTROL FACILITY | 6 | 50 mm2 | Bare Copper | 10 Dia x 610 | Solid Copper | 14 |
| WATER SUPPLY BUILDING | 5 | 50 mm2 | Bare Copper | 10 Dia x 610 | Solid Copper | 32 |
| Grounding Systems | ||||||||
| FACILITY NAME | No. Ground Points | Conductor Wire | Perimeter Ground Loop | Perimeter Ground Rod | ||||
| Size | Type | Size | Type | Size | Type | Qty | ||
| DECKHOUSE SUPPORT BUILDING | 27 | 70 mm2 | Bare Copper | 70 mm2 | Bare Copper | 19 Dia x 3000 | Copper-Clad | 43 |
| SM-3 MAGAZINE | 12 | 70 mm2 | Bare Copper | 70 mm2 | Bare Copper | 19 Dia x 3000 | Copper-Clad | 17 |
| GP WAREHOUSE #1 | 6 | 70 mm2 | Bare Copper | 70 mm2 | Bare Copper | 19 Dia x 3000 | Copper-Clad | 12 |
| ENTRY CONTROL FACILITY | 8 | 70 mm2 | Bare Copper | 70 mm2 | Bare Copper | 19 Dia x 3000 | Copper-Clad | 14 |
| WATER SUPPLY BUILDING | 12 | 70 mm2 | Bare Copper | 70 mm2 | Bare Copper | 19 Dia x 3000 | Copper-Clad | 20 |
Water - AA
| Attachment J-1502001-03 |
| Notional Equipment Inventory (MILCON Facilities) |
WATER SYSTEMS - MDA
| WATER METERS | ||||||
| FACILITY NAME | SERVICE | TYPE | BODY SIZE | FLOW RANGE | MAXIMUM PRESSURE LOSS kPa | |
| mm | MIN | MAX | ||||
| L/s | L/s | |||||
| DECKHOUSE SUPPORT BUILDING | Building Domestic Water Supply | Positive Displacement | 50 | 0.125 | 8.31 | 82 |
| WATER SUPPLY BUILDING | Building Domestic Water Supply | Positive Displacement | 40 | 0.32 | 6.31 | 34.48 |
| HOT WATER HEATERS | ||||||||
| FACILITY NAME | SERVICE | TYPE | STORAGE CAPACITY | RECOVERY RATE | ELECTRICAL | |||
| L | VOLUME / HOUR | TEMP RISE °C | kW | V | Hz | |||
| L | ||||||||
| DECKHOUSE SUPPORT BUILDING | Domestic Water | Storage Tank | 189 | 92 | 55.5 | 6 | 480 | 60 |
| DECKHOUSE SUPPORT BUILDING | CCA Shower | Instantaneous | - | 7949 | 16.7 | (2)108 | 480 | 60 |
| GENERAL PURPOSE WAREHOUSE #1 | Domestic Hot Water | Storage Tank | 125 | 87 | 55.5 | 5.6 | 230 | 50 |
| ENTRY CONTROL FACILITY | Domestic Hot Water | Storage Tank | 125 | 87 | 55.5 | 5.6 | 230 | 50 |
| WATER SUPPLY BUILDING | Emergency Shower | Instantaneous | - | - | 16.7 | 108 | 400 | 50 |
| EXPANSION TANKS | ||||
| FACILITY NAME | SERVICE | TYPE | MINIMUM TANK | MINIMUM ACCEPTANCE VOLUME |
| VOLUME | L | |||
| L | ||||
| DECKHOUSE SUPPORT BUILDING | Domestic Water | Diaphragm | 3.9 | 6.2 |
| GENERAL PURPOSE WAREHOUSE #1 | Domestic Water | Diaphragm | 8 | 3.4 |
| ENTRY CONTROL FACILITY | Domestic Water | Diaphragm | 8 | 3.4 |
| BOOSTER PUMP | |||||||
| FACILITY NAME | SERVICE | TYPE | FLOW RATE | MINIMUM INLET PRESSURE | BOOST PRESSURE | MOTOR KW | ELECTRICAL |
| L/s | KPa | KPa | V/PH/Hz | ||||
| DECKHOUSE SUPPORT BUILDING | CCA Shower/ Demineralizer Skid | Inline | 2.52 | 0 | 586 | 476 | 5.6 |
image1.emf
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .