N4008525B0029 Dwgs.pdf
PDF 34 MB Posted
- Attached to
- P1625 MARSOC Storage and Training Facilities
- Solicitation number
- N4008526R9012
About this file
This file is a set of construction drawings for the Practical Application Training Facility (MARSOC) at Camp Lejeune, North Carolina, designated as Project LE22S03R with NAVFAC Drawing Number 6005-22-0047. The facility is a single-phase, approximately 5,460-square-foot building designed as a mixed-use structure with Group B (Business), Group S-1 (Storage), and Group A-3 (Assembly) occupancies. The building is Type II-B construction with a 20-foot height and includes classroom space (624 SF), open training bay with 12 medical triage training stations accommodating 72 occupants (2,700 SF), toilet facilities (102 SF), and storage (450 SF), plus covered awning and exterior gravel areas. The design incorporates a pre-engineered metal building (PEMB) frame with cold-formed metal stud exterior walls, split-face CMU and brick veneer cladding, standing seam metal roof system, and concrete slab-on-grade foundation with spread footings and piers.
The facility incorporates comprehensive mechanical, electrical, plumbing, fire protection, and civil infrastructure systems. Mechanical systems include a roof-mounted air handler with supply and return ductwork, ceiling-mounted exhaust fan, thermostats, and humidistats. Plumbing includes water service from an 8-inch main with 1.5-inch domestic taps, a packaged grinder pump station for wastewater, floor drains, fixtures including water closets, lavatories, service sink, emergency eyewash station, and utility sinks. Fire protection features a combined fire alarm and mass notification system with manual pull stations, speaker/strobes, area smoke detectors, and integration with the base-wide mass notification system. Civil work includes new water line, sanitary sewer forcemain with grinder pump station, storm water management with grading and erosion control measures, new fire hydrants, yard hydrants, chain-link fence with gates, concrete sidewalk, and gravel parking and training areas. The design must comply with UFC standards, IBC 2021, NFPA codes, and North Carolina Department of Environmental Quality requirements, with coordination required for utility shutdowns not to exceed three hours.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0015.pdf | ||
| Amend 0015 Pricing Sheet.pdf | ||
| Amend 0014 Pricing Sheet.pdf | ||
| Amend 0014.pdf | ||
| Amend 0013.pdf | ||
| Amend 0012.pdf | ||
| Amendment 0011.pdf | ||
| Amend 0010.pdf | ||
| Amend 0009.pdf | ||
| 22-0047 Prac App Combined Sheets - ASI 01.pdf | ||
| Amend 0008.pdf | ||
| Amendment 0007.pdf | ||
| Amendment 0006.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| N4008525B0029_Dwgs.pdf | ||
| 250029 Geotechnical Report.pdf | ||
| 250029 BASIS OF DESIGN.pdf | ||
| 250029_APPXD.pdf | ||
| 250029 APPXD.pdf | ||
| Gen MACC RFP.pdf | ||
| N4008525B0029 Specs.pdf | ||
| N4008525B0029_Specs.pdf | ||
| 250029 Facility Geotechnical Report.pdf | ||
| Encl 1 Pricing Sheet.pdf |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WAKE
DURHAM
PERSON
GRANVILLE
FRANKLIN
WARREN
COLUMBUS
BLADEN
HARNETT
WAYNE
JOHNSTON
WILSON
NASH
EDGECOMBE
SAMPSON
DUPLIN
JONES
GREENE
LENOIR
PITT
HERTFORD
GATES
CARTERET
CRAVEN
ONSLOW
PENDER
NEW
HANOVER
BRUNSWICK
PAMLICO
BEAUFORT
HYDE
DARE
C A M
D E N
PA
SQ
U O
TAN K
TYRRELL
PER
Q
UI M
ANS
C H O W
A N
MARTIN WASHINGTON
NORTHAMPTON
CUR
I
U K
T R
C
BERTIE
VANCE
CUMBERLAND
HALIFAX
ATLANTIC OCEAN
CAMP LEJEUNE
BASE MAP
MAR
IN
ES
R
OAD
COURTHOUSE
BAY
N.C. HIGHWAY 172
STONE
BAY
N.C. HIGHWAY 172
N.
C.
H
IG
HW
AY
N .C
. H
IG
H W
AY
MARSOC
COMPLEX
SITE
PRACTICAL APPLICATION
TRAINING FACILITY
EVERETT CREEK ROAD
NEW RIVER
RR635
RR633
RR631
RR637
STONE BAY
NOT TO SCALE1 LOCATION MAP
NORTH
NOT TO SCALE1" = 600 FEET2 ENLARGED BASE MAP
NORTH
3BASE MAP
NORTH
FINAL
22-0047 PRACTICAL APPLICATION TRAINING
FACILITY (LE22S03R) MARSOC
G-001
COVER SHEET
12-18-2025
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
60037281
· ALL SHUTDOWNS INCLUDING UTILITY SHUTDOWNS ESPECIALLY OF WATER OR ELECTRICAL SYSTEMS MUST BE COORDINATED WITH THE
CONTRACTING OFFICER (ROICC), AND MUST NOT EXCEED (3) HOURS.
· CONTRACTOR MUST TAKE NECESSARY MEASURES TO PROTECT ALL EXISTING COMMUNICATION UTILITIES IN AND AROUND THE PROJECT AREA. EXERCISE CAUTION IN CONSTRUCTION AND EXCAVATION ACTIVITIES ESPECIALLY IN THE VICINITY OF THE ROAD TO PROTECT THE
EXISTING FIBER OPTIC LINE(S).
· THE BUILDING AND SITE WILL BE CONSTRUCTED IN A SINGLE PHASE.
· CONSTRUCTION ACTIVITIES MUST NOT IMPEDE OR INTERFERE WITH NORMAL OPERATIONS OF THE ADJACENT BUILDINGS OR OF CONSTRUCTION ACCESS TO OTHER PROJECTS SOUTHEAST OF THIS SITE DURING THE CONSTRUCTION PERIOD.
· THE SPECIFIC EXTENT OF AREAS PERMITTED TO BE USED FOR STAGING / LAYDOWN WILL BE COORDINATED AND COMMUNICATED TO THE CONTRACTOR BY THE CONTRACTING OFFICER (ROICC) AFTER AWARD. AREAS PERMITTED TO BE USED FOR STAGING / LAYDOWN MUST BE RESTORED TO THEIR CONDITION PRIOR TO START OF CONSTRUCTION. GRASSED AREAS MUST BE STRIPPED, PREPARED AND RE-SODDED AT COMPLETION OF WORK; SEE SPECIFICATIONS 32 05 33 LANDSCAPE ESTABLISHMENT, AND 32 92 23 SODDING.
· A CLIN IS REQUIRED FOR THIS PROJECT FOR PER-PLANT PRICE INSTALLED FOR SUPPLEMENTAL SCREENING. REFER TO BIDDING CONTRACT DOCUMENTS, SPECIFICATIONS AND CIVIL DRAWINGS FOR ADDITIONAL INFORMATION. THE CLIN WILL BE EXERCISED IF REQUIRED AT THE OPTION OF THE GOVERNMENT ONCE THE SITE HAS BEEN COMPLETELY CLEARED, AND THE BUILDING HAS BEEN ERECTED.
CONSTRUCTION REQUIREMENT NOTES
G-002
SHEET INDEX AND GENERAL NOTES
60037282 151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
12-18-2025
INDEX OF DRAWINGS
GENERAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
G-001 60037281 1 COVER SHEET
G-002 60037282 2 SHEET INDEX AND GENERAL NOTES
GI001 60037283 3 CODE SUMMARY
GI002 60037284 4 CODE COMPLIANCE SITE PLAN
GI101 60037285 5 LIFE SAFETY PLAN
CIVIL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
VF100 60037286 6 CIVIL OVERALL EXISTING CONDITIONS
VF101 60037286A 7 CIVIL EXISTING CONDITIONS
C-001 60037287 8 CIVIL GENERAL NOTES
C-002 60037288 9 CIVIL LEGEND AND ABBREVIATIONS
CD100 60037289 10 CIVIL DEMOLITION PLAN
CS100 60037290 11 CIVIL SITE PLAN
CU100 60037291 12 CIVIL OVERALL UTILITY PLAN
CU101 60037291A 13 CIVIL UTILITY PLAN
CG100 60037292 14 CIVIL GRADING PLAN
CG101 60037293 15 CIVIL EROSION CONTROL PLAN
C-500 60037294 16 CIVIL EROSION DETAILS
C-501 60037295 17 CIVIL EROSION DETAILS
C-502 60037296 18 CIVIL UTILITY DETAILS
C-503 60037297 19 CIVIL UTILITY DETAILS
C-504 60037298 20 CIVIL SITE DETAILS
STRUCTURAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
S-001 60037299 21 STRUCTURAL GENERAL NOTES
S-101 60037300 22 STRUCTURAL FOUNDATION PLAN
S-201 60037301 23 STRUCTURAL FOUNDATION SECTIONS
ARCHITECTURAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
A-001 60037302 24 GENERAL NOTES, DETAILS, LEGEND, AND ABBREVIATIONS
A-101 60037303 25 ARCHITECTURAL FLOOR PLAN
A-102 60037304 26 REFLECTED CEILING/ROOFING PLAN
A-201 60037305 27 BUILDING ELEVATIONS
A-301 60037306 28 BUILDING SECTIONS
A-302 60037307 29 WALL SECTIONS AND DETAILS
A-601 60037308 30 DOOR AND FINISH SCHEDULES
FIRE PROTECTION
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
FA001 60037309 31 FIRE ALARM LEGEND
FA101 60037310 32 FIRE ALARM FLOOR PLAN
FA501 60037311 33 FIRE ALARM DETAILS
PLUMBING
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
P-001 60037312 34 PLUMBING COVER SHEET
P-101 60037313 35 FLOOR PLAN - WASTE AND VENT
P-102 60037314 36 FLOOR PLAN - WATER
P-501 60037315 37 PLUMBING DETAILS
P-601 60037316 38 PLUMBING SCHEDULES
P-701 60037317 39 PLUMBING RISERS
MECHANICAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
M-001 60037318 40 MECHANICAL COVER SHEET
M-101 60037319 41 FLOOR PLAN - MECHANICAL
M-501 60037320 42 MECHANICAL DETAILS
M-601 60037321 43 MECHANICAL SCHEDULES
M-701 60037322 44 MECHANICAL CONTROLS
ELECTRICAL
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
E-001 60037323 45 ELECTRICAL NOTES AND LEGEND
ES101 60037324 46 SITE PLAN - ELECTRICAL
ES501 60037325 47 SITE ELECTRICAL DETAILS
ES502 60037326 48 SITE ELECTRICAL DETAILS
ES503 60037327 49 SITE ELECTRICAL DETAILS
E-101 60037328 50 FLOOR PLAN - POWER
E-102 60037329 51 FLOOR PLAN - EQUIPMENT CONNECTIONS
E-103 60037330 52 FLOOR PLAN - LIGHTING
E-501 60037331 53 ELECTRICAL DETAILS
E-502 60037332 54 ELECTRICAL DETAILS
E-601 60037333 55 ELECTRICAL SCHEDULES
E-602 60037334 56 ELECTRICAL SCHEDULES
TELECOMMUNICATIONS
SHEET NAME NAVFAC DRAWING NO. PAGE SHEET DESCRIPTION
T-001 60037335 57 TELECOMMUNICATIONS NOTES AND LEGEND
T-101 60037336 58 FLOOR PLAN - TELECOMMUNICATIONS
T-501 60037337 59 TELECOMMUNICATIONS DETAILS
T-502 60037338 60 TELECOMMUNICATIONS DETAILS
GENERAL DESIGN AND CONSTRUCTION NOTES:
1. ANY REFERENCES TO STATE GOVERNMENT, FEDERAL GOVERNMENT, OR INDUSTRY
STANDARDS OR SPECIFICATION MADE HEREIN SHALL FORM A PART OF THE WORK TO THE
EXTENT REFERENCED THERETO AND ALL MATERIALS AND WORKMANSHIP UNDER THIS
CONTRACT SHALL COMPLY WITH OR EXCEED THESE STANDARDS AND REFERENCE. ALL
REFERENCED STANDARDS SHALL BE THE LATEST EDITION.
2. ALL MANUFACTURED EQUIPMENT AND PRODUCTS SHALL BE NEW MATERIALS IN UNDAMAGED
CONDITION AND INSTALLED AS PER MANUFACTURER'S LATEST PRINTED INSTRUCTIONS,
UNLESS SPECIFIED OTHERWISE HEREIN.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF ANY EXISTING FACILITIES AND ANY
EQUIPMENT FROM DAMAGE DURING INSTALLATION AND TESTING OPERATIONS.
4. CONTRACTOR SHALL TAKE INTO ACCOUNT THE SPECIAL TREATMENT OF ANY HAZARDOUS
WASTE, AS WELL AS THE RELATED ENVIRONMENTAL IMPLICATIONS. COORDINATE WITH
CONTRACTING OFFICER REGARDING AVAILABLE TEST REPORTS ON ANY EXISTING
CONDITIONS. REFER ALSO TO GEOTECHNICAL REPORT WHICH IS AVAILABLE UPON REQUEST.
EVERY EFFORT SHALL BE MADE TO RECYCLE ELIGIBLE MATERIALS, AND THOSE NOT SUITABLE, SHALL BE DISPOSED OF OFF BASE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
(NCDEQ) NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY.
5. ENSURE THAT ANY DEMOLITION, UTILITY CUT AND CAPPING, AND DEBRIS REMOVAL SERVICE
PERFORMED AT THE BASE IS COMPLETED IN SUCH A MANNER THAT WILL RESTORE A NEAT
AND PROFESSIONAL APPEARANCE OF BASE AREAS.
6. THE FACILITY/AREA SHALL BE CLEANED IN ITS ENTIRETY, INCLUDING EXTERIOR AREAS,
BEFORE BEING RETURNED TO THE GOVERNMENT.
WARRANTY:
1. CONTRACTOR SHALL FURNISH A MINIMUM ONE YEAR WARRANTY AGAINST DEFECTS IN
MATERIAL AND WORKMANSHIP STARTING ON THE BENEFICIAL OCCUPANCY DATE.
GENERAL INFORMATION:
1. THE CONTRACTOR SHALL PROVIDE ALL MANAGEMENT, TOOLS, SUPPLIES, EQUIPMENT, LABOR, AND APPLICABLE LICENSES AND PERMITS NECESSARY TO COMPLETE REQUIREMENTS WITHIN.
ALL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE STATEMENT OF WORK AND
SUBJECT TO THE TERMS AND CONDITIONS OF THE CONTRACT AND IN ACCORDANCE WITH
(UFC) UNITED FACILITIES CRITERIA, UNIFIED FACILITIES GUIDE SPECIFICATIONS (UFGS), THE
INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL PLUMBING CODE (IPC), NATIONAL
ELECTRICAL CODE (NEC), NATIONAL ELECTRICAL SAFETY CODE (NESC), NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA), EPA 402-K-01-001 (2008), NORTH CAROLINA DEPARTMENT
OF TRANSPORTATION (NCDOT), NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
(NCDEQ), BASE DESIGN AND CONSTRUCTION STANDARDS INCLUDING BASE EXTERIOR
ARCHITECTURAL PLAN (BEAP), AND ALL OTHER APPLICABLE CODES.
WORKING CONDITIONS:
1. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO INSURE THAT OPERATIONS ARE
CONDUCTED IN A MANNER AS TO MINIMALLY INTERFERE WITH THE NORMAL OPERATIONS OF
THE BASE AND THE SAFETY AND CONVENIENCE OF THE BASE PERSONNEL. THE CONTRACTOR
SHALL COORDINATE UTILITY OUTAGES WITH THE APPROPRIATE BASE UTILITY SERVICE
OFFICE AND THE USER.
GENERAL PROJECT NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS, QUANTITIES AND SQUARE
FOOTAGES. ALL DIMENSIONS, QUANTITIES AND SQUARE FOOTAGES INCLUDED ARE
APPROXIMATIONS. CONSTRUCTION AND DEMOLITION SHALL BE IN STRICT ACCORDANCE WITH
THE BASE DESIGN AND CONSTRUCTION STANDARDS. THE INFORMATION PROVIDED IN THE
STATEMENT OF WORK (SOW), THE PROVIDED DRAWINGS, AND THE REQUIREMENTS OF THE
BASE DESIGN AND CONSTRUCTION STANDARDS SHALL BE DETERMINED TO BE THE MINIMUM
STANDARDS REQUIRED IN THIS PROJECT.
2. UFC'S TAKE PRECEDENCE OVER ALL STANDARDS, CODES AND BASE DESIGN STANDARDS AND
REQUIREMENTS THAT PERTAIN TO THE WORK WITHIN THIS SOW.
3. DURING CONSTRUCTION, THE CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EXISTING
STRUCTURES, ETC. THAT WILL NOT BE REPLACED AS PART OF THIS CONTRACT. CONTRACTOR
SHALL BE RESPONSIBLE FOR THE TEMPORARY SUPPORT OF ALL DEVICES AS REQUIRED TO
PERFORM WORK. ANY DEMOLITION WORK THAT NEEDS TO BE ACCOMPLISHED TO COMPLETE
THE CONTRACT IS THE RESPONSIBILITY OF THE CONTRACTOR. ALL MATERIAL SHALL BE
INSTALLED PER MANUFACTURERS' RECOMMENDATIONS. ALL ITEMS LISTED IN THE SOW ARE
TO BE SUPPLIED AND INSTALLED BY THE CONTRACTOR UNLESS OTHERWISE NOTED.
4. A PRE-CONSTRUCTION MEETING WILL BE HELD AT THE BASE TO INCLUDE THE CONTRACTOR
AND GOVERNMENT REPRESENTATIVES. THE GOVERNMENT SHALL SET UP THIS MEETING WITH
THE CONTRACTOR AND GOVERNMENT REPRESENTATIVES, TO DISCUSS ALL PERTINENT
PROJECT REQUIREMENTS, AS WELL AS ANY OTHER CONSTRUCTION ISSUES THE
CONTRACTOR MAY HAVE. ALL FINISHES SHALL BE PRESENTED TO THE CONTRACTING
OFFICER AS ONE SUBMITTAL FOR SELECTION AND APPROVAL PRIOR TO INSTALLATION. ALL
FINISH MATERIALS THAT COULD BE DISCONTINUED SHALL BE ON-SITE PRIOR TO STARTING
PROJECT SO THERE WILL BE NO DIFFERENCES IN COLOR.
5. WHERE SPECIFIC PART NUMBERS OR MANUFACTURER'S ARE REFERENCED, IT SHALL BE
UNDERSTOOD THAT THE CONTRACTOR MAY SUBMIT A PROPOSED EQUAL.
6. THE TERM "SHALL" WHERE USED IS EQUIVALENT TO "MUST". ALL WORK AND MATERIALS
NOTED ARE NEW UNLESS NOTED OTHERWISE.
7. THE TERM "INSTALL" WHERE USED IS EQUIVALENT TO "PROVIDE", (FURNISH AND INSTALL
COMPLETE).
8. THE TERMS "OWNER" AND "GOVERNMENT" WILL BE CONSIDERED TO BE THE SAME /
INTERCHANGEABLE FOR THIS PROJECT.
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
12-18-2025
GI001
CODE SUMMARY
1. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS, 1 SEPTEMBER 2022
2. UFC 3-600-01 DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021
3. UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 30 JULY 2022
4. UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, JANUARY 2010
5. IBC INTERNATIONAL BUILDING CODE, 2021
6. NFPA 10 PORTABLE FIRE EXTINGUISHERS, 2022
7. NFPA 70 NATIONAL ELECTRICAL CODE, 2023
8. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2022
9. NFPA 90A INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2021
10. NFPA 101 LIFE SAFETY CODE, 2021 (LSC)
11. ABA ARCHITECTURAL BARRIERS ACT
APPLICABLE BUILDING CODES
USE GROUP/OCCUPANCY
FIRE PROTECTION SYSTEMS
CONSTRUCTION TYPE
ALLOWABLE AREA & HEIGHT
ACTUAL AREA & HEIGHT
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
EXTERIOR WALLS
INTERIOR FINISH CLASSIFICATION
TRAVEL DISTANCES
CAPACITY OF EXITS (INTERIOR SPACE ONLY)
ADDITIONAL LIFE SAFETY CRITERIA
REQUIRED EXIT
CAPACITY
AVAILABLE EXIT
CAPACITY
NUMBER OF EXITS
REQUIRED
NUMBER OF EXITS
PROVIDED
170 [1-36" WIDE DOOR]
170 [1-36" WIDE DOOR]
170 [1-36" WIDE DOOR]
FIRE SEPARATION DISTANCE (FSD)
FSD < 5-FT
5 FT < FSD < 10-FT
GROUPS B & A-3
TYPE II-B
1-HR
1-HR
LEGEND
B BUSINESS (IBC 304.1, LSC 6.1.11) - ORDINARY HAZARD (LSC 38.1.5)
S-1 STORAGE (IBC 311.2, LSC 6.1.13) - ORDINARY HAZARD (LSC 42.1.5.1)
A-3 ASSEMBLY (IBC 303.4, LSC 6.1.2.1) - ORDINARY HAZARD (LSC 12.1.5, 6.2.2.3)
PER IBC, THE BUILDING IS CLASSIFIED AS AN UNSEPARATED MIXED USE GROUP B, GROUP S-1, AND
GROUP A-3 OCCUPANCY.
PER LSC, THE BUILDING IS CLASSIFIED AS A MIXED USE BUSINESS, STORAGE, AND ASSEMBLY
OCCUPANCY.
EMERGENCY VOICE FIRE ALARM & MASS NOTIFICATION SYSTEM 1
SPRINKLER SYSTEM - NOT REQUIRED
1 MASS NOTIFICATION TRANSMITTER PROVIDED BY NIWCS (NOT IN CONTRACT)
TYPE II-B
BASED ON S-1 // B // A-3 USE GROUP:
ALLOWABLE AREA PER TABLE (IBC TABLE 506.2): 17,500-SF // 23,000-SF // 9,500-SF
ALLOWABLE STORIES (IBC TABLE 504.4): 2-STORY // 3-STORY // 2-STORY
ALLOWABLE HEIGHT (IBC TABLE 504.3): 55-FT // 55-FT // 55-FT
TOTAL BUILDING AREA: 5,460-SF
* TOTAL BUILDING AREA INCLUDES AREAS WITHOUT EXTERIOR WALLS (OPEN TRAINING BAY)
BENEATH THE HORIZONTAL PROJECTION OF THE ROOF
TOTAL BUILDING HEIGHT: 1-STORY/20-FT
(IBC TABLE 601, TYPE II-B CONSTRUCTION)
STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS & TRUSSES 0-HR
BEARING WALLS, EXTERIOR 0-HR
BEARING WALLS, INTERIOR 0-HR
NON-BEARING WALLS, EXTERIOR* 0-HR
NON-BEARING WALLS, INTERIOR** 0-HR
FLOOR CONSTRUCTION 0-HR
ROOF CONSTRUCTION 0-HR
*BASED ON IBC TABLE 602 FOR A FIRE SEPARATION DISTANCE OF 10-FT OR MORE
**MINIMUM RATING PER CONSTRUCTION TYPE
EXTERIOR FIRE-RESISTANCE RATING BASED ON FIRE SEPARATION DISTANCE
LIMITS* (BASED ON NON-SPRINKLERED STORAGE // BUSINESS // ASSEMBLY OCCUPANCY):
EXITS (TABLE A.10.2.2) MINIMUM CLASS B // B // A
EXIT ACCESS CORRIDORS (TABLE A.10.2.2) MINIMUM CLASS C // B // B
OTHER SPACES (TABLE A.10.2.2) MINIMUM CLASS C // C // C
* MUST COMPLY WITH MOST RESTRICTIVE REQUIREMENT
COMMON PATH OF TRAVEL* (LSC TABLE A.7.6) BUSINESS/STORAGE/ASSEMBLY: 75/50/20** FT
**75 FEET WHERE OCCUPANT LOAD IS LESS THAN 50
DEAD END CORRIDOR* (LSC TABLE A.7.6) BUSINESS/STORAGE/ASSEMBLY: 20/50/20 FT
EXIT ACCESS TRAVEL* (LSC TABLE A.7.6) BUSINESS/STORAGE/ASSEMBLY: 200/200/200 FT
* MUST COMPLY WITH MOST RESTRICTIVE REQUIREMENT
CAPACITY OF EXITS (LSC TABLE 7.3.3.1):
LEVEL COMPONENTS (WIDTH/PERSON) 0.2 IN/PERSON
NUMBER OF EXITS (LSC 7.4)
1 FOR ORDINARY HAZARD STORAGE OCCUPANCIES WHERE THE EXIT CAN BE REACHED WITHIN THE DISTANCE
PERMITTED AS A COMMON PATH OF TRAVEL (LSC 42.2.4.1(2))
1 FOR BUSINESS OCCUPANCIES WITH AN OCCUPANT LOAD OF LESS THAN 100 PERSONS WITH EXITS DISCHARGING DIRECTLY TO THE EXTERIOR AND TOTAL TRAVEL DISTANCE NOT EXCEEDING 100 FT (LSC 38.2.4.3)
ALL MEANS OF EGRESS ARE REQUIRED TO BE ILLUMINATED IN ACCORDANCE WITH LSC 7.8 (LSC
38.2.8 & 42.2.8).
EMERGENCY LIGHTING SYSTEMS MUST BE PROVIDED IN ACCORDANCE WITH LSC 7.9.2.1 & 7.9.2.2
(LSC 38.2.9.1 & 42.2.9).
MEANS OF EGRESS MUST BE PROVIDED WITH SIGNS IN ACCORDANCE WITH LSC 7.10 AND UFC
3-600-01 10-2 (LSC 38.2.10 & 42.2.10). SIGNS MUST HAVE LETTERING ON AN OPAQUE BACKGROUND.
INTERNALLY ILLUMINATED SIGNS MUST BE LIGHT EMITTING DIODE (LED) TYPE,
ELECTROLUMINESCENCE (LEC), OR COLD CATHODE TYPE. INCANDESCENT FIXTURES ARE NOT
PERMITTED. RADIOLUMINOUS EXIT SIGNS ARE NOT PERMITTED (UFC 3-600-01 10-2.2).
FIRE EXTINGUISHERS MUST BE PROVIDED IN BUSINESS OCCUPANCIES AND LOCATED IN
ACCORDANCE WITH NFPA 10 (LSC 38.3.5).
TD = XX FT
CPT = XX FT
X=REQUIRED EGRESS CAPACITY
Y=PROVIDED EGRESS CAPACITY
AREA (SQ. FT.)
OCCUPANT LOAD (SQ. FT./PERSON)
OCCUPANTS (PERSONS)
TRAVEL PATH AND DISTANCE
COMMON PATH OF TRAVEL DISTANCE
DEAD END TRAVEL DISTANCE
FIRE EXTINGUISHER CABINET
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
KNOX BOX
FIRE HYDRANT
WATER LINE
FIRE WATER LINE
THE DISTANCE BETWEEN THE PRACTICAL APPLICATION TRAINING FACILITY AND THE CLOSEST
BUILDING IS MORE THAN 40-FT, WHICH PROVIDES A FIRE SEPARATION DISTANCE OF AT LEAST 10-FT FROM THE PRACTICAL APPLICATION TRAINING FACILITY TO THE IMAGINARY LOT LINE AND MORE THAN 30-FT FROM THE IMAGINARY LOT LINE TO THE CLOSEST BUILDING; THEREFORE, THE EXTERIOR WALLS
OF THE PRACTICAL APPLICATION TRAINING FACILITY ARE NOT REQUIRED TO BE RATED.
GROUP S-1
TYPE II-B
2-HR
1-HR
10 FT < FSD 0-HR 0-HR
MEANS OF EGRESS
OCCUPANT LOADS (LSC TABLE 7.3.1.2)
BUSINESS 150-SF/PERSON
STORAGE 500-SF/PERSON
CLASSROOM 20-SF/PERSON
* THE OCCUPANT LOAD FOR THE OPEN TRAINING BAY IS BASED ON SIX PEOPLE PER MEDICAL TRIAGE
TRAINING STATION. 12 TRAINING STATIONS ARE PROVIDED
AREA USE
APPROX. AREA
(SF)
OCCUPANT LOAD
FACTOR
(SF/PERSON)
OCCUPANT LOAD
(PERSONS)
STORAGE 450STORAGE 103
TOTAL
OPEN TRAINING BAY 100 2,700 72*ASSEMBLY*
-3,847 106
BUSINESS 73TOILET 102 1150
CLASSROOM 624CLASSROOM 101 3220
DE = XX FT
REQUIRED FIRE FLOW
ON SEPTEMBER 25, 2025, HYDRANT FLOW TESTING CONDUCTED BY MCB CAMP LEJEUNE BASE
UTILITIES AND WITNESSED BY JENSEN HUGHES YIELDED THE FOLLOWING RESULTS:
STATIC PRESSURE: 76 PSI
RESIDUAL PRESSURE: 49 PSI
FLOW: 1,060 GPM
FLOW AT 20 PSI: 1,572 GPM
UFC 3-600-01 PARAGRAPH 9-2.2 REQUIRES THE FIRE FLOW FOR NON-SPRINKLERED FACILITIES TO
BE IN ACCORDANCE WITH NFPA 1. THE MINIMUM REQUIRED FIRE FLOW PER NFPA 1 TABLE
18.4.5.2.1 IS 1500 GPM. THE FLOW AVAILABLE AT 20 PSI IS SUFFICIENT TO MEET THE BUILDING
FIRE FLOW DEMAND.
AREA
CLASSROOM 101
TOILET 102
STORAGE 103
OPEN TRAINING BAY OCCUPANTS HAVE UNOBSTRUCTED EGRESS FROM THE COVERED AREA
OCCUPANT LOAD TOTAL AREA DIFFERS FROM TOTAL BUILDING AREA DUE TO DIFFERENCE IN IBC DEFINITION OF
"AREA, BUILDING" AND "FLOOR AREA, GROSS"
2/10/2312/18/25 santinid Snapshot
X
X X
SS
W W W W W W W W W
W W
W W
W W
W
W
X X X X X X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXXXXXXX
STORAGE
OPENTRAININGBAYFFE: 29.5'FG: 29.0'
CLASSROOM
G
RA
VE
L
AHU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
W W
W
W
F
F F
F F
W
W
X
X X X
SS
W W W W W W W W W
W W
W W
W W
W
W
X X X X X X X
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXXXXXXX
SCALE: 1/32" = 1'-0"
CODE COMPLIANCE SITE PLAN
PLAN
NORTH
2' 4' 8' 16'0'
1/4" =1'-0"SCALE:
GRAPHIC SCALE
NOTE: IF THIS DRAWING IS A REDUCTION, GRAPHIC SCALE
MUST BE USED.
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025
GI002
CODE COMPLIANCE SITE PLAN
1. OVERALL BUILDING AREA IS WITHIN IBC LIMIT WITHOUT FRONTAGE INCREASE.
2. FIRE DEPARTMENT ACCESS ROADS MUST MEET THE PROVISIONS OF NFPA 1
SECTION 18.2.3.5 IN ACCORDANCE WITH UFC-3-600-01: 9-1.3, AS OUTLINED
BELOW:
2.1. UNOBSTRUCTED WIDTH:
20 FT
THE WIDTH MAY BE REDUCED WHERE APPROVED BY THE AHJ
2.2. UNOBSTRUCTED VERTICAL CLEARANCE:
13 FT 6 IN
2.3. ROAD SURFACE:
THE ROAD MUST BE CAPABLE OF SUPPORTING THE IMPOSED LOADS
OF FIRE APPARATUS.
THE ROAD MUST HAVE AN ALL-WEATHER DRIVING SURFACE.
2.4. TURNING RADIUS:
THE TURNING RADIUS MUST MAINTAIN THE MINIMUM ROAD WIDTH
1. EXIT DISCHARGE PATH
2. FIRE HYDRANT
3. INTENDED FIRE DEPARTMENT MAIN ENTRANCE TO
FACILITY
4. FIRE DEPARTMENT ACCESS ROAD
5. KNOX BOX
2/10/2312/18/25 santinid Snapshot santinid Snapshot santinid Snapshot santinid Snapshot santinid Snapshot santinid Snapshot
TD/CPT = 40 FT
A.1
5 4 3 12
B
A
C
A.1
D D.1D.1
TD/CPT = 46 FT
MEDICAL TRIAGE TRAINING STATIONS
(12 TOTAL)
EACH STATION ACCOMMODATES 6
PERSONS
72 OCCUPANTS
STORAGE
CLASSROOM
TOILET
OPEN TRAINING BAY
COVERED AWNING
SCALE: 1/4" = 1'-0"
OVERALL LIFE SAFETY FLOOR PLAN
PLAN
NORTH
2' 4' 8' 16'0'
1/4" =1'-0"SCALE:
GRAPHIC SCALE
NOTE: IF THIS DRAWING IS A REDUCTION, GRAPHIC SCALE
MUST BE USED.
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
12-18-2025
GI101
LIFE SAFETY PLAN
2/10/2312/18/25
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
UC
UC
UC
UC
UC
UC
UC
UC
UC
U C
U C
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
UC
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
UC
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP UP
UP
UP
UP
UP UP
UP
UP
U P
U P
U P
U P
U P
UP
UP
UP
U P
U P
U P
U P
UP
UP
U P
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
U P
X X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXX
X
X X
X
X
X
XXXXXX
X
X X
X X
XXXXXXXXX
X
X
X
X
X X
X X
X
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W W W W W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W W
W W
W W
W W W
W W
W
WW
W
C
C
C
CO
CO
CO
CO
COCO
CO
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
S
S
S
S
X X
MW
S
BLDG RR633
BLDG RR635
BLDG RR637
T
CONTROL POINT:
RBC400
CONTROL POINT:
RBC401
LOOP ROAD
T
SSMH
RIM ELEV: 31.55'
6" (W) IE: 18.06'
6" (S) IE: 18.15'
TO CONTROL POINT:
RBC402
690.99' N89° 53' 50.89"W 26
23242526
18 19 20 21 22 23 24 25 26 27 28
345678
21 22 23 24 25 26 27
22 23 24 25
5 6 7
9 10
17 18 19 20
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 VF100
CIVIL OVERALL EXISTING CONDITIONS
60037286
SURVEY CONTROL DATA
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS.
1. EXISTING CONDITIONS SURVEY PERFORMED BY CAPE FEAR ENGINEERING
IN SEPTEMBER 2025.
2. SURVEY CONTROL DATA ESTABLISHED, UTILIZING NORTH CAROLINA
VIRTUAL REFERENCE STATION (VRS) SYSTEM.
3. HORIZONTAL DATUM IS NAD '83 AND ELEVATIONS ARE BASED ON NAVD '88
(2011) VERTICAL DATUM.
4. CONTROL POINTS:
RBC400
N: 304045.96' E: 2473462.58'
ELEV: 29.63'
RBC401
N: 304097.39' E: 2472914.20'
ELEV: 28.93'
RBC402
N: 304279.22' E: 2472390.22'
ELEV: 30.74
5. EXISTING UTILITIES SHOWN ARE A COMBINATION OF FIELD SURVEY,
ASBUILT DRAWINGS FROM THE MARCH 2022 P1219 PROJECT IN RELATION
TO BUILDINGS RR631, RR633, RR635, RR637 AND MCBCL GIS.
6. WETLANDS PER MCBCL GIS AND HAVE NOT BEEN FIELD VERIFIED.
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
CURRENT
GRAVEL ROAD
FUTURE PAVED ROAD, PART
OF ADJACENT PROJECT
FUTURE CONCRETE SIDEWALK,
PART OF ADJACENT PROJECT
WETLANDS, TYP.
WETLANDS, TYP.
1" = 50'-0" 0 50 1001 CIVIL OVERALL EXISTING CONDITIONS
PLAN
NORTH
FO FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
CONTROL POINT:
RBC400
LOOP ROAD
18 19 20 21 22 23 24 25 26 27 28
21 22 23 24 25 26 27
22 23 24
TO CONTROL POINT:
RBC402
1,058.20' N77° 14' 24.68"W
TO CONTROL POINT:
RBC401
510.55' N84° 10' 28.13"W
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 VF101
CIVIL EXISTING CONDITIONS
60037286A
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS.
SURVEY CONTROL DATA
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
CURRENTGRAVEL ROAD
FUTUREADJACENT
PAVED ROAD
FUTURE SIDEWALK
1" = 20'-0" 0 20 401 CIVIL EXISTING CONDITIONS
PLAN
NORTH
1. EXISTING CONDITIONS SURVEY PERFORMED BY CAPE FEAR ENGINEERING
IN SEPTEMBER 2025.
2. SURVEY CONTROL DATA ESTABLISHED, UTILIZING NORTH CAROLINA
VIRTUAL REFERENCE STATION (VRS) SYSTEM.
3. HORIZONTAL DATUM IS NAD '83 AND ELEVATIONS ARE BASED ON NAVD '88
(2011) VERTICAL DATUM.
4. CONTROL POINTS:
RBC400
N: 304045.96' E: 2473462.58'
ELEV: 29.63'
RBC401
N: 304097.39' E: 2472914.20'
ELEV: 28.93'
RBC402
N: 304279.22' E: 2472390.22'
ELEV: 30.74
5. EXISTING UTILITIES SHOWN ARE A COMBINATION OF FIELD SURVEY,
ASBUILT DRAWINGS FROM THE MARCH 2022 P1219 PROJECT IN RELATION
TO BUILDINGS RR631, RR633, RR635, RR637 AND MCBCL GIS.
6. WETLANDS PER MCBCL GIS AND HAVE NOT BEEN FIELD VERIFIED.
www.capefearengineering.com | N.C. LICENSE # C-1621
12-18-2025
CIVIL GENERAL NOTES
C-001
60037287
CIVIL GENERAL NOTES:
1. REFER TO THE PROJECT SPECIFICATIONS IN ALL SITUATIONS.
BRING CONFLICTS BETWEEN PROJECT SPECIFICATIONS AND
PLANS TO THE ATTENTION OF THE CONTRACTING OFFICER
AND/OR ENGINEER FOR RESOLUTION. ALL MATERIALS AND
WORKMANSHIP MUST CONFORM TO THE PROJECT
SPECIFICATIONS.
2. EXISTING UTILITY INFORMATION IS NOT TO BE RELIED ON AS BEING
EXACT OR COMPLETE. LOCATION, VERIFICATION, SUPPORT AND
PROTECTION OF ALL ABOVE GROUND AND UNDERGROUND
UTILITIES TO REMAIN IN PLACE, INCLUDING ANY UTILITIES NOT
INDICATED ON CONTRACT DRAWINGS IS REQUIRED. ANY
CONFLICTS OR DISCREPANCIES MUST BE BROUGHT TO THE
CONTRACTING OFFICER'S AND/OR ENGINEER'S ATTENTION
IMMEDIATELY. CAPE FEAR ENGINEERING HAS NOT PHYSICALLY
LOCATED ANY UNDERGROUND UTILITIES.
3. PRIOR TO ANY EXCAVATION, CONTRACTOR MUST HAVE THE
EXISTING UNDERGROUND LINES MARKED ON THE GROUND
SURFACE IN THE AREAS OF CONSTRUCTION. POTHOLE AND
PHYSICALLY VERIFY DEPTH AND LOCATION OF ALL UTILITY LINES
IN THE WORK AREA THAT REQUIRE COORDINATION WITH WORK
ITEMS. POTHOLE VERIFICATION MUST BE DONE WELL IN ADVANCE
OF ACTUAL WORK SO THAT POTENTIAL UTILITY CONFLICTS CAN BE
VERIFIED AND RESOLVED WITHOUT CAUSING SCHEDULE DELAYS.
4. PROTECT ALL EXISTING STRUCTURES, TREES, PAVEMENT,
UTILITIES, AND OTHER PROPERTY UNLESS THEY ARE TO BE
DEMOLISHED. ANY PROPERTY NOT AUTHORIZED FOR REMOVAL,
BUT DAMAGED BY THE CONTRACTOR MUST BE RESTORED BY THE
CONTRACTOR TO THEIR PRE-CONSTRUCTION CONDITION OR
BETTER AT NO ADDITIONAL EXPENSE TO THE OWNER.
5. MAKE EVERY EFFORT TO SAVE PROPERTY IRONS, MONUMENTS,
OTHER PERMANENT POINTS AND LINES OF REFERENCE AND
CONSTRUCTION STAKES. PROPERTY IRONS, MONUMENTS, AND
OTHER PERMANENT POINTS OF REFERENCE DESTROYED BY THE
CONTRACTOR MUST BE REPLACED AT THE CONTRACTOR'S
EXPENSE.
6. WORK PERFORMED UNDER THIS CONTRACT MUST NOT IMPACT
THE OPERATION OF ANY ADJACENT PROPERTIES UNLESS A
UTILITY OUTAGE HAS BEEN APPROVED IN ADVANCE.
7. SEQUENCE WORK AS NECESSARY TO ENSURE THAT ALL UTILITY
SERVICES, INCLUDING FIRE HYDRANTS, REMAIN OPERATIONAL
DURING CONSTRUCTION.
8. RESTORE ANY ACCESS ROADS AND STAGING AREAS USED BACK
TO THEIR PRE-CONSTRUCTION CONDITION OR BETTER. VEGETATE
ALL DISTURBED AREAS IN ACCORDANCE WITH THE PROJECT
SPECIFICATIONS.
9. TAKE ADEQUATE PROTECTIVE MEASURES TO ENSURE THAT
EXISTING PAVEMENT SURFACES ARE NOT DAMAGED FROM
TRACKED CONSTRUCTION EQUIPMENT OR ANY OTHER POSSIBLE
SOURCE WHEN EQUIPMENT IS BEING MOVED. REPAIR ANY PAVED
AREAS DAMAGED DURING CONSTRUCTION TO THEIR
PRE-CONSTRUCTION CONDITION OR BETTER.
10. EXISTING PAVEMENTS AND ALL OTHER AREAS ADJACENT TO THE
SITE MUST BE KEPT CLEAN AT ALL TIMES. DO NOT ALLOW BUILD
UP OF SOIL, MUD, DUST OR OTHER DEBRIS.
11. CONTRACTOR IS RESPONSIBLE FOR ALL SURVEYING AND STAKING
TO COMPLETE THE WORK.
12. ANY AND ALL MATERIAL QUANTITIES INDICATED ON THIS PLAN SET
ARE FOR REFERENCE ONLY. CONTRACTOR MUST VERIFY ALL
MATERIAL QUANTITIES SHOWN.
13. KEEP REDLINE MARK-UPS OF ANY CHANGES MADE FROM THE
APPROVED PLAN AND PROVIDE COPY OF REDLINES TO ENGINEER
UPON PROJECT COMPLETION.
14. THERE ARE POTENTIAL JURISDICTIONAL WETLANDS IN THE
VICINITY OF THE PROJECT AREA. A MINIMUM 50-FT BUFFER SHALL
BE MAINTAINED.
EXISTING CONDITION NOTES:
1. SEE SHEETS VF100 AND VF101 FOR EXISTING CONDITIONS AND
SURVEY INFORMATION.
OFFSITE BORROW AREA NOTES
1. CONTRACTOR IS RESPONSIBLE FOR ENSURING OFFSITE BORROW
AREA HAS AN APPROVED EROSION CONTROL PERMIT AND
APPROPRIATE MEASURES IN PLACE PRIOR TO LAND DISTURBING
ACTIVITY.
2. NO BORROW MATERIALS ARE AVAILABLE ON GOVERNMENT
PROPERTY.
DEMOLITION PLAN NOTES:
1. LOCATE UNDERGROUND UTILITIES AND COORDINATE DEMOLITION
AND / OR RELOCATION WORK. SPECIFICALLY TAKE EXTRA
CAUTIONARY MEASURES TO PREVENT DISRUPTION OF ANY
TELECOM FIBER IN THE PROJECT AREA. ONCE LOCATED IN THE
FIELD, POSITIVE VERIFICATION BY POTHOLING IS REQUIRED.
REPORT ANY CONFLICTS OR DISCREPANCIES TO ENGINEER.
2. LIMITS OF DEMOLITION AND DIMENSIONS ARE SHOWN FOR
GENERAL REFERENCE. CONTRACTOR MUST BE RESPONSIBLE FOR
REMOVAL OF ALL ITEMS, INCLUDING ALL EXCAVATED MATERIALS
NECESSARY TO COMPLETE WORK WITHIN THIS CONTRACT.
3. WHERE ASPHALT/CONCRETE DEMOLITION IS REQUIRED, USE A
SAW CUT AT THE LIMITS OF DEMOLITION OR NEAREST JOINT TO
OBTAIN A CLEAN VERTICAL EDGE.
4. DEDICATED DEMOLITION AND OTHER WASTE AREAS/EARTHEN
MATERIAL STOCKPILES MUST BE LOCATED AT LEAST 50' FROM
STORMDRAINS OR STREAMS.
5. REPORT ANY UNSUITABLE SOILS, CONTAMINATED SOILS, AND
BURIED CONCRETE AND DEBRIS TO THE CONTRACTING OFFICER
IMMEDIATELY.
6. CONTRACTOR MUST PROVIDE TEMPORARY THRUST BLOCKS AND
TEMPORARILY CAP WATERLINES FOR SEQUENCING OF
WATERLINE DEMOLITION AND INSTALLATION OF NEW TEES AND
FITTINGS.
7. CONTRACTOR MUST SEQUENCE DEMOLITION OF STORM AND
SANITARY SEWER TO ENSURE ALL SYSTEMS REMAIN ONLINE
DURING WORK. CONTRACTOR MUST PROVIDE TEMPORARY CAPS
AND PLUGS AND BYPASS PUMPING AS REQUIRED FOR
SEQUENCING OF DEMOLITION AND NEW WORK.
8. UNDERGROUND UTILITIES SHOWN ON THE DEMOLITION PLANS
MAY EXTEND FURTHER THAN SHOWN. CONTRACTOR IS
RESPONSIBLE FOR COMPLETE REMOVAL OF UTILITIES WITHIN THE
ENTIRE PROJECT SITE UNLESS OTHERWISE NOTED.
SIGNAGE, STRIPING, AND MARKING NOTES:
1. THE CONTRACTOR IS RESPONSIBLE FOR ALL PEDESTRIAN AND
VEHICULAR TRAFFIC DETOURS AND MUST USE APPROPRIATE
SIGNAGE AND BARRICADES IN ACCORDANCE WITH ALL BASE,
STATE, AND FEDERAL REQUIREMENTS.
2. ALL ROAD AND LANE CLOSURES MUST BE REQUESTED AND
APPROVED BY THE CONTRACTING OFFICER PRIOR TO CLOSING OF
ANY ROADWAYS.
3. ALL ROAD CLOSURES MUST BE SUBMITTED TO THE CONTRACTING
OFFICER A MINIMUM OF 15 DAYS PRIOR TO THE REQUIRED DATE
OF CLOSURE AND MUST INCLUDE A TRAFFIC CONTROL PLAN IN
ACCORDANCE WITH MUTCD AND EM 385-1-1.
4. ALL TRAFFIC CONTROL METHODS AND DEVICES, BOTH
TEMPORARY AND PERMANENT, MUST BE IN ACCORDANCE WITH
THE U.S. DEPARTMENT OF TRANSPORTATION FEDERAL HIGHWAY
ADMINISTRATION'S "MANUAL ON UNIFORM TRAFFIC CONTROL
DEVICES" (MUTCD), MOST RECENT EDITION AND THE NORTH
CAROLINA DEPARTMENT OF TRANSPORTATION (NCDOT).
5. USE THE COLOR WHITE FOR ALL PAVEMENT MARKINGS AND
SYMBOLS UNLESS OTHERWISE NOTED.
6. DO NOT LOCATE PAVEMENT MARKING SYMBOLS AS TO ENCROACH
INTO INTERSECTION AREAS.
7. DO NOT PLACE PAVEMENT MARKING SYMBOLS ACROSS
TRANSVERSE EXPANSION JOINTS ON PORTLAND CONCRETE
PAVEMENTS UNLESS APPROVED BY THE ENGINEER.
8. CONFORM ALL SYMBOLS TO THE NCDOT STANDARDS AND
PROJECT SPECIFICATIONS AND DETAILS.
9. SEE SIGNAGE & PAVEMENT MARKINGS ON SITE PLAN AND DETAIL
SHEETS, WHERE SHOWN.
10. PAVEMENT MARKINGS MUST BE COLORED PER THE PLANS,
WHERE SHOWN. PAVEMENT MARKINGS LOCATED IN PARKING
AREAS MUST BE WATER-BASED. CROSSWALKS AND PAVEMENT
MARKINGS IN TRAFFIC AREAS MUST BE THERMOPLASTIC.
11. ANY EXISTING PAVEMENT MARKINGS IN THE VICINITY OF THE
PROJECT LIMITS THAT ARE DAMAGED DURING CONSTRUCTION
MUST BE REPAIRED OR REPLACED TO THE CONTRACTING
OFFICER'S SATISFACTION.
SIDEWALK AND PAVING NOTES:
1. COMPLY WITH THE CURRENT NCDOT STANDARDS AND
SPECIFICATIONS FOR ROADS AND STRUCTURES UNLESS
OTHERWISE NOTED.
2. INSTALL EXPANSION JOINT WITH THICKENED EDGE WHERE
CONCRETE PAVEMENT ABUTS BUILDINGS, MANHOLES, INLETS,
AND OTHER STRUCTURES IN THE PAVEMENT UNLESS NOTED
OTHERWISE.
3. FREE CONCRETE PAVEMENT EDGES THAT ABUT GRAVEL OR
ASPHALT PAVEMENT AREAS MUST BE THICKENED.
4. CONSTRUCTION JOINTS MUST BE USED AT THE END OF EACH
DAY'S PLACING OPERATIONS AND WHEN CONCRETE PLACEMENT
IS INTERRUPTED FOR 30 MINUTES OR LONGER.
5. ODD SHAPED SLABS (WHERE L:W RATIO IS GREATER THAN 1.25)
AND SLABS WITH PENETRATIONS (FOR UTILITIES, BASINS,
BOLLARDS, ETC) MUST BE REINFORCED WITH WWF (6X6-W2.1X2.1)
IN CENTER OF SLAB.
6. REFER TO PROJECT SPECIFICATIONS FOR SPACING AND
DIMENSIONS OF ALL CONSTRUCTION AND EXPANSION JOINTS.
STORMWATER AND GRADING NOTES:
1. NO INSTALLATION OF IMPERVIOUS SURFACES IN EXCESS OF 10,000
SF MUST BE DONE PRIOR TO OBTAINING APPROVAL FROM NORTH
CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY (NCDEQ).
2. ALL CUT OR FILL SLOPES MUST BE 3:1 OR FLATTER UNLESS
OTHERWISE NOTED.
3. DURING CONSTRUCTION, PERFORM GRADING IN A MANNER AND
SEQUENCE THAT WILL PROVIDE PROPER DRAINAGE AT ALL TIMES.
4. ADJUST AND/OR CUT EXISTING PAVEMENT AS NECESSARY TO
ASSURE A SMOOTH FIT AND CONTINUOUS GRADE.
5. FOR ALL NEW BUILDINGS, PROVIDE A MINIMUM 5% SLOPE AWAY
FROM THE BUILDING FOR THE FIRST 10-FEET AND ASSURE THAT
FINISHED FLOOR ELEVATIONS ARE A MINIMUM OF 6-INCHES ABOVE
THE ADJACENT SITE GRADE IN NON-PAVED AREAS.
6. ALL STORM PIPE MUST BE CLASS III REINFORCED CONCRETE PIPE
(RCP), UNLESS OTHERWISE NOTED ON THE PLANS.
7. UPON THE COMPLETION OF CONSTRUCTION AND SITE
STABILIZATION, ALL NEW PIPES AND EXISTING PIPES IMPACTED BY
CONSTRUCTION MUST BE CLEANED TO REMOVE ALL
ACCUMULATED SILT, SEDIMENT AND DEBRIS.
8. ALL STORM PIPE ENTERING STRUCTURES (NEW AND EXISTING)
MUST BE CUT FLUSH TO INSIDE OF THE BOX AND GROUTED TO
ASSURE CONNECTION AT STRUCTURE IS WATER TIGHT; MAXIMUM
PROTRUSION MUST BE 6 INCHES.
9. ALL STORMWATER STRUCTURES IN PAVED AREAS MUST BE FLUSH
WITH PAVEMENT AND BE HEAVY-DUTY TRAFFIC RATED.
GENERAL UTILITY NOTES:
1. ALL UTILITY MATERIALS, CONSTRUCTION, TESTING AND
WORKMANSHIP MUST CONFORM TO THE PROJECT
SPECIFICATIONS, UFC STANDARDS, AND MUST MEET OR EXCEED
NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
AND CAMP LEJEUNE STANDARDS AND SPECIFICATIONS.
2. A NORTH CAROLINA LICENSED UTILITY CONTRACTOR MUST
PERFORM ALL UTILITY WORK INVOLVED IN CONSTRUCTING THIS
PROJECT.
3. COORDINATE WITH THE UTILITY PROVIDERS FOR REQUIRED
UTILITY ADJUSTMENTS AND/OR RELOCATIONS.
4. ISOLATE ALL NEW PIPING FROM EXISTING PIPING UNTIL ALL NEW
PIPING HAS BEEN TESTED, CERTIFIED TO UTILITY PROVIDER AND
ACCEPTED FOR SERVICE.
5. FIELD VERIFY THE LOCATION AND DEPTH OF ALL EXISTING UTILITY
LINES PRIOR TO THE INSTALLATION OF ANY NEW LINES.
6. ALL FILL MATERIAL IS TO BE IN PLACE, AND COMPACTED BEFORE
INSTALLATION OF UTILITIES. IF NOT, CONTRACTOR MUST ENSURE
THAT MINIMUM COVER REQUIREMENTS ARE MET AND THAT
UTILITIES ARE ADEQUATELY PROTECTED.
7. ADJUST ALL UTILITY STRUCTURE RIM ELEVATIONS AS NECESSARY
TO MATCH FINAL ELEVATIONS.
8. NOTIFY THE UTILITY PROVIDER'S INSPECTORS AND CONTRACTING
OFFICER, AND ENGINEER AT LEAST 72 HOURS BEFORE
CONNECTING TO ANY EXISTING LINE AND/OR BEGINNING UTILITY
LINE INSTALLATION.
9. NOTIFY AND RECEIVE APPROVAL FROM THE UTILITY PROVIDER'S
INSPECTORS AND CONTRACTING OFFICER AT LEAST 15 DAYS
PRIOR TO ANY UTILITY DISRUPTIONS.
10. REFER TO INTERIOR PLUMBING DRAWINGS FOR TIE-IN OF ALL
UTILITIES. ANY DISCREPANCIES MUST BE BROUGHT TO
ENGINEER'S ATTENTION IMMEDIATELY.
11. THE UTILITY DRAWINGS DO NOT SHOW EVERY OFFSET,
TRANSITION, AND FITTING THAT MAY BE REQUIRED. DETERMINE
AND PROVIDE FITTINGS AND CONCRETE THRUST BLOCKS
NECESSARY FOR COMPLETION OF THE SYSTEM.
12. PROVIDE EXTERIOR CORROSION PROTECTION ON UNDERGROUND
METALLIC PIPE LINES UNLESS OTHERWISE NOTED.
13. ALL UNDERGROUND UTILITIES MUST BE INSTALLED A MINIMUM OF
5 FEET FROM NEW OR EXISTING STRUCTURES.
WATER NOTES:
1. A NCDEQ WATER EXTENSION PERMIT IS REQUIRED FOR THIS
PROJECT.
2. ALL BACKFLOW PREVENTION ASSEMBLIES AND METERS MUST BE
LOCATED WITHIN THE BUILDING MECHANICAL ROOMS UNLESS
LOCATED OTHERWISE ON PLANS.
3. MINIMUM UTILITY SEPARATIONS
SANITARY SEWER - 10-FEET (LATERALLY)
- 18-INCHES (VERTICAL - WATER
OVER SEWER)
STORM SEWER - 18-INCHES (VERTICAL)
4. WHERE A WATER MAIN PASSES OVER A SEWER, AND THE
VERTICAL SEPARATION IS LESS THAN 18" OR WHERE WATER
PASSES UNDER SEWER, THE SEWER AND WATERMAIN MUST BOTH
BE DUCTILE IRON PIPE FOR A DISTANCE OF 10' ON EACH SIDE OF
THE CROSSING (20' LENGTH CENTERED AT CROSSING - NO
JOINTS)..
5. ALL WATERLINES MUST HAVE A MINIMUM OF 36-INCHES OF COVER
FROM FINISHED GRADE, UNLESS DUCTILE IRON IS SPECIFIED.
6. ALL WATERLINES MUST HAVE A MINIMUM OF 18-INCHES OF
SEPARATION BETWEEN UNDERGROUND POWER &
COMMUNICATION LINES. COORDINATE WITH THE SITE ELECTRICAL
/ COMMUNICATIONS CONTRACTOR.
7. WHERE A WATERLINE PASSES UNDER A STORM DRAIN PIPE, THE
WATERLINE MUST MAINTAIN A MINIMUM OF 18-INCHES OF
VERTICAL SEPARATION FOR A DISTANCE OF 10' ON EACH SIDE OF
THE CROSSING (20' LENGTH CENTERED AT CROSSING - NO
JOINTS).
8. ALL WATERLINES MUST HAVE A MINIMUM OF 18-INCHES OF
SEPARATION FROM GAS LINES. COORDINATE WITH SITE GAS
CONTRACTOR.
SANITARY SEWER NOTES:
1. A NCDEQ SEWER EXTENSION PERMIT IS NOT REQUIRED FOR THIS
PROJECT.
2. ALL CLEANOUT SYMBOLS SHOWN REPRESENT THE LOCATION OF
SURFACE ACCESS POINTS. CONTRACTOR MUST LOCATE WYE
APPROPRIATELY BASED ON PIPE SIZE AND PIPE DEPTH.
3. MAXIMUM DISTANCE BETWEEN CLEANOUTS ON SERVICE LINES IS
100-FEET. CLEANOUTS MUST BE PLACED AT VERTICAL AND
HORIZONTAL CHANGES OF DIRECTION.
4. MANHOLES AND CLEANOUTS LOCATED IN PAVEMENT, CONCRETE
OR OTHER TRAFFIC AREAS MUST BE SET FLUSH TO FINISHED
GRADE AND BE HEAVY-DUTY TRAFFIC RATED (HS-20).
5. MANHOLES AND CLEANOUTS IN UNPAVED AND NON-TRAFFIC
AREAS MUST BE SET 1-INCH ABOVE FINISHED GRADE.
6. ALL SEWER LINES MUST HAVE A MINIMUM OF 36-INCHES OF COVER
FROM FINISHED GRADE UNLESS DUCTILE IRON PIPE.
7. MINIMUM UTILITY SEPARATIONS:
WATER - SEE WATER NOTES
STORM SEWER - 24-INCHES (VERTICAL)
8. ALL SEWER LINES MUST HAVE A MINIMUM OF 18-INCHES OF
SEPARATION FROM UNDERGROUND POWER AND COMMUNICATION
LINES. COORDINATE WITH SITE ELECTRICAL/COMMUNICATION
CONTRACTOR.
9. ALL SEWER LINES MUST HAVE A MINIMUM OF 18-INCHES OF
SEPARATION FROM GAS LINES.
EROSION CONTROL NOTES:
1. TOTAL DISTURBED AREA IS MORE THAN 1.0 ACRE. A LAND
DISTURBANCE PERMIT IS REQUIRED.
2. ALL EROSION AND SEDIMENT CONTROL MEASURES MUST BE IN
ACCORDANCE WITH THE NORTH CAROLINA SEDIMENTATION AND
EROSION CONTROL DESIGN MANUAL (LATEST EDITION).
3. DIMENSIONS AND GRADES SHOWN ON THE PLANS MUST BE FIELD
VERIFIED BY THE CONTRACTOR PRIOR TO CONSTRUCTION.
NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES EXIST
PRIOR TO PROCEEDING WITH CONSTRUCTION FOR NECESSARY
PLAN OR GRADE CHANGES.
4. PROVIDE POSITIVE DRAINAGE AWAY FROM THE SITE AT ALL TIMES.
A/C AIR CONDITIONER
ATFP ANTI TERRORISM FORCE PROTECTION
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMP BEST MANAGEMENT PRACTICE
BW BARBED WIRE
C&G CURB AND GUTTER
CB CATCH BASIN
CC CONCRETE CURB
CI CURB DROP INLET
CJ CONTRACTION JOINT
CLF CHAIN LINK FENCE
CMH COMMUNICATION MANHOLE
CONC CONCRETE
D/B DESIGN/BUILD
DCJ DOWELED CONSTRUCTION JOINT
DI DROP INLET
DPW DEPARTMENT OF PUBLIC WORKS
DUMP DUMPSTER
E EAST
EHH ELECTRICAL HANDHOLE
EG EXISTING GAS
EJ EXPANSION JOINT
ELEC ELECTRIC
EMH ELECTRICAL MANHOLE
EL ELEVATION
FDC FIRE DEPARTMENT CONNECTION
FES FLARED END SECTION
FFE FINISH FLOOR ELEVATION
FL FLOW LINE
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GPM GALLONS PER MINUTE
HW HEAD WALL
IE INVERT ELEVATION
LOD LIMITS OF DISTURBANCE
LP LIGHT POLE
LSA LANDSCAPE STONE
MAT MATERIAL
MH MANHOLE
MOF METAL ORNAMENTAL FENCE
MUTCD MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES
N NORTH
NCDEQ NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY
NCDOT NORTH CAROLINA DIVISION OF TRANSPORTATION
NE NORTHEAST
NIC NOT IN CONTRACT
NOAA NATIONAL OCEANIC AND ATMOSPHERIC ADMINISTRATION
NW NORTHWEST
PNG PIEDMONT NATURAL GAS
PP POWER POLE
PT PHYSICAL TRAINING
PVC POLYVINYL CHLORIDE
RCP REINFORCED CONCRETE PIPE
S SOUTH
SCM STORMWATER CONTROL MEASURE
SDMH STORM DRAIN MANHOLE
SE SOUTHEAST
SEP SEPARATION
SMH SANITARY SEWER MANHOLE
STA STATION
STY STORY
SW SOUTHWEST
TC TOP OF CURB
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TE THICKENED EDGE
TEJ THICKENED EDGE EXPANSION JOINT
THH TELECOMMUNICATION HANDHOLE
TMH TELECOMMUNICATION MANHOLE
TRANS TRANSFORMER
TSB TEMPORARY SEDIMENT BASIN
TYP TYPICAL
UG UNDERGROUND
UNK UNKNOWN
W WEST
W/BW WITH BARBED WIRE
WV WATER VALVE
WW WING WALL
ABBREVIATIONS
C-500
1DETAIL
REFERENCE
SECTION
SYMBOL LEGEND:
IDENTIFICATION NUMBER
SHEET # FOR
SECTION/DETAIL
IDENTIFICATION NUMBER
SHEET # FOR
SECTION/DETAILC-500
A1
VIEW TITLE
VIEW TITLE
1 1" = 20'
SCALE
PLAN
NORTH
IDENTIFICATION
NUMBER1
SCALE
NOT TO SCALE
DETAIL TITLE
DETAIL TITLE
C-002
CIVIL LEGEND AND ABBREVIATIONS
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
12-18-2025
XX
BUILDING
GRAVEL DRIVE/PARKING
GRAVEL ROAD
CONCRETE STRIP
ASPHALT PAVEMENT
BOLLARD
CHAIN LINK FENCE
WATER LINE
PIPE BENDS AND TEES
VALVE
SEWER FORCEMAIN
SANITARY SEWER SERVICE
PUMPSTATION AND CONTROLS
INLINE SEWER CLEANOUT
UNDERGROUND COMM LINE
UNDERGROUND POWER
DRAINAGE SWALE
YARD HYDRANT
COMMUNICATION MANHOLE
FIRE HYDRANT
STONE CHECK DAM
TEMPORARY DIVERSION SWALE
TEMPORARY SILT FENCE
SILT FENCE ROCK OUTLET
CONCRETE SPLASH BLOCK
CONTOUR
SPOT ELEVATION
TRANSFORMER
ELECTRICAL JUNCTION BOX
LIMITS OF DISTURBANCE
LEGEND: EXISTING
FEATURES:
DEMOLISHED
FEATURES:
LEGEND: PROPOSED
FEATURES:
X X
S
W
C
SS
UC
UP
OE
E
C
PP
T
SD
CB
W
P2FM
UC
UP
BUILDING
ASPHALT PAVEMENT
CONCRETE SIDEWALK
GRAVEL ROAD
FENCE
GUY WIRE(S)
BOLLARD
WATERLINE
FIRE HYDRANT
WATERLINE VALVE
SANITARY SEWER LINE
SANITARY SEWER MANHOLE
UNDERGROUND COMM
COMM MANHOLE
COMM HAND HOLE
UNDERGROUND ELECTRIC
OVERHEAD ELECTRIC
ELECTRIC MANHOLE
LIGHT POLE
POWER POLE
TRANSFORMER
GAS LINE
STORM PIPE
DROP INLET / CATCH BASIN
CONTOURS
FLARED END SECTION
WETLANDS
WOODS/VEGETATION
MONITORING WELL
LP
G
C
W U
W U
W U
SS
X X X
9.40
LOD
T
60037288
MW
P8WL
F
J
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROAD
18 19 20 21 22 23 24 25 26 27 28
21 22 23 24 25 26 27
22 23 24
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 CD100
CIVIL DEMOLITION PLAN
60037289
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, ABBREVIATIONS.
2. SEE SHEET VF100 FOR EXISTING CONDITIONS.
1. REMOVE EXISTING VEGETATION. NO CLEARING IS ALLOWED OUTSIDE OF
AREA SHOWN.
2. REMOVE AND REPAIR GRAVEL PAVEMENT FOR WATER LINE AND HYDRANT
INSTALLATION, MATCH EXISTING SECTION.
3. OPEN CUT/ PATCH ASPHALT ROAD FOR UTILITY CONNECTION, SEE SHEET
CU100.
1" = 20'-0" 0 20 401 CIVIL DEMOLITION PLAN
PLAN
NORTH
C-504
CURRENTGRAVEL ROAD
FUTUREADJACENT
PAVED ROAD
FUTURE SIDEWALK
CONTRACTOR SHALL TAKE NECESSARY MEASURES TO
PROTECT ALL EXISTING COMMUNICATIONS UTILITIES IN
AND AROUND THE PROJECT AREA.
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROAD
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROAD
STORAGE
OPENTRAINING BAY
FFE: 29.5'FG: 29.0'
CLASSROOM
G
RA
VE
L
AHU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
T
J
C
SSCO
RIM: 28.78
C
C
C
54.1'
44.7'
56.7'
6.
3'
R50.0
R30 .0
R25.0
R25.0
2'
194.4' 192.4'
0'
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 CS100
CIVIL SITE PLAN
60037290
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, ABBREVIATIONS.
1. GRAVEL PARKING/PAVEMENT
2. GRAVEL TRAINING AREA WITH CONTAINMENT CURB
(SEE ARCHITECTURAL PLANS AND DETAIL 11 ON SHEET C-504)
3. HIGH SECURITY CHAINLINK FENCE
4. DOUBLE SWING GATE
5. PEDESTRIAN GATE
6. PROTECTIVE BOLLARD
7. CONCRETE SPLASHBLOCK
8. ASPHALT PAVEMENT
9. GRAVEL DRIVEWAY
10. GRAVEL ROAD REPAIR, MATCH EXISTING SECTION AND GRADE
1" = 20'-0" 0 20 401 CIVIL SITE PLAN
PLAN
NORTH
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
TYP
C-504
C-504
C-504
C-504
C-504
TYP
C-504
TYP
C-504
C-504
C-504
C-504
CURRENTGRAVEL ROAD
FUTUREADJACENT
PAVED ROAD
FUTURE SIDEWALK
CONTRACTOR SHALL TAKE NECESSARY MEASURES TO
PROTECT ALL EXISTING COMMUNICATIONS UTILITIES IN
AND AROUND THE PROJECT AREA.
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
UC
UC
UC
UC
UC
UC
UC
UC
UC
U C
U C
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
UC
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
UC
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP UP
UP
UP
UP
UP UP
UP
UP
U P
U P
U P
U P
U P
UP
UP
UP
U P
U P
U P
U P
UP
UP
U P
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
U P
X X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXX
X
X X
X
X
X
XXXXXX
X
X X
X X
XXXXXXXXX
X
X
X
X
X X
X X
X
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W W W W W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W W
W W
W W
W W W
W W
W
WW
W
C
C
C
CO
CO
CO
CO
COCO
CO
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
S
S
S
S
X X
MW
S
BLDG RR633
BLDG RR635
BLDG RR637
T
LOOP ROAD
T
SSMH
RIM ELEV: 31.55'
6" (W) IE: 18.06'
6" (S) IE: 18.15'
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
UC
UC
UC
UC
UC
UC
UC
UC
UC
U C
U C
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
UC
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
UC
U C
U C
U C
U C
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP
U P
U P
UP
UP
UP UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
UP
UP
UP UP
UP
UP
UP
UP UP
UP
UP
U P
U P
U P
U P
U P
UP
UP
UP
U P
U P
U P
U P
UP
UP
U P
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
U P
X X
X
X
X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
X X
X X
X X
X X
X X
X X
X
XXXXXXXXX
X
X X
X
X
X
XXXXXX
X
X X
X X
XXXXXXXXX
X
X
X
X
X X
X X
X
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W W W W W W
W W
W W
W W
W W
W W
W
W
W
W
W
W
W
W W
W W
W W
W W W
W W
W
WW
W
C
C
C
CO
CO
CO
CO
COCO
CO
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
S
S
S
S
X X
MW
S
BLDG RR633
BLDG RR635
BLDG RR637
T
LOOP ROAD
T
SSMH
RIM ELEV: 31.55'
6" (W) IE: 18.06'
6" (S) IE: 18.15'
STORAGE
OPEN
TRAINING BAY
FFE: 29.5'FG: 29.0'
CLASSROOM
G
RA
VE
L
AHU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
U P
T
J
W
C
SSCO
RIM: 28.78
U C
UC
UC
UP
UP
U P
U P
UP
UP
UP
UP
UP
UP
U P
U P
U P
C
J
P2
FM
P2FM
P2FM
P8WL
P8W L
P8W L
C
P8WL
P8WL
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM
UC
UC
UC
C
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 CU100
CIVIL OVERALL UTILITY PLAN
60037291
1. 4" SEWER SERVICE WITH CLEANOUT (SCHEDULE 40 PVC).
2. PACKAGE GRINDER PUMP STATION (SIMPLEX).
3. 2" FORCEMAIN (SDR-21).
4. CONNECT TO EXISTING SEWER STRUCTURE.
5. 2" ISOLATION GATE VALVE.
6. 8" WATER LINE C900 DR-18 (MINIMUM 36" DEPTH OF COVER).
7. CONNECT TO EXISTING WATERLINE.
8. FIRE HYDRANT.
9. YARD HYDRANT.
10. TAP FOR 1-1/2" DOMESTIC WATER SERVICE.
11. 8" GATE VALVE AND PLUG FOR FUTURE EXTENSION.
12. PROTECT EXISTING FENCE TO REMAIN, EXCAVATE ON BOTH SIDES OF FENCE FOR
UTILITY INSTALLATION.
13. OPEN CUT/PATCH AS REQUIRED FOR UTILITY INSTALLATION.
14. REMOVE TREES/VEGETATION AS REQUIRED FOR UTILITY INSTALLATION.
15. PAD MOUNTED TRANSFORMER W/ PROTECTIVE BOLLARDS (SEE ELECTRICAL).
16. UTILITY CROSSING, SEE DETAIL 8 ON SHEET C-503.
17. UNDERGROUND ELECTRICAL LINE, CONNECT TO EXISTING TRANSFORMER
(SEE ELECTRICAL).
18. UNDERGROUND COMMUNICATIONS LINE (SEE ELECTRICAL SITE SHEET ES101).
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, ABBREVIATIONS.
1" = 50'-0" 0 50 1001 CIVIL OVERALL UTILITY PLAN
PLAN
NORTH
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
CURRENT
GRAVEL ROAD
FUTURE PAVED ROAD, PART
OF ADJACENT PROJECT
FUTURE CONCRETE SIDEWALK,
PART OF ADJACENT PROJECT
WETLANDS, TYP.
WETLANDS, TYP.
C-504
C-503
C-503
C-503
TYP
C-503
C-503
C-503
C-503
C-504
C-502
TYP
CONTRACTOR SHALL TAKE NECESSARY MEASURES TO
PROTECT ALL EXISTING COMMUNICATIONS UTILITIES IN
AND AROUND THE PROJECT AREA.
C-503
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROADFO FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROAD
STORAGE
OPENTRAINING BAY
FFE: 29.5'FG: 29.0'
CLASSROOM
G
RA
VE
L
AHU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
SS
UP
U P
U P
U P
T
J
W
W
W
C
SSCO
RIM: 28.78
U C
U C
U C
U C
UC
UC
UC
UC
UC
U C
UP
UP
UP
U P
U P
U P
UP UP
UP
UP
C
P2
FM
P2
FM
P2
FM
P2
FM
P2FM
P2FM
P2FM
P2FM
P2FM
P8WL
P8WL
P8W L
P8W L
P8W L
P8W L
P8W L
P8W L
P8W L
C
P8WL
P8 W
L
P8WL
P8WL
P8WL
P8WL
P8WL
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM P2FM P2FM
P2FM
P2FM
P2FM
P2FM
UC
UC
UC
UC
UC
UC
UC
UC
UC
C
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 CU101
CIVIL UTILITY PLAN
60037291A
1. SEE SHEET C-001 AND C-002 FOR GENERAL NOTES, LEGEND, ABBREVIATIONS.
C-504
1&4
1" = 20'-0" 0 20 401 CIVIL UTILITY PLAN
PLAN
NORTH
C-504
C-503
C-503
C-503
TYP
C-503
SE
E
SH
EE
T C
U
FO
R C
O N
TI
N
U
AT
IO
N
O F
FO
R
C
EM
AI
N
C O
N N
EC
TI
O N
SEE SHEET CU100
FOR CONTINUATION OF UNDERGROUND
POWER AND WATER CONNECTION
C-503
TYP
C-503
WETLANDS, TYP.
50' WETLAND
BUFFER
50' WETLAND
BUFFER
CURRENTGRAVEL ROAD
FUTUREADJACENT
PAVED ROAD
FUTURE SIDEWALKCONTRACTOR SHALL TAKE NECESSARY MEASURES TO
PROTECT ALL EXISTING COMMUNICATIONS UTILITIES IN
AND AROUND THE PROJECT AREA.
C-503
1. 4" SEWER SERVICE WITH CLEANOUT (SCHEDULE 40 PVC).
2. PACKAGE GRINDER PUMP STATION (SIMPLEX).
3. 2" FORCEMAIN (SDR-21).
4. CONNECT TO EXISTING SEWER STRUCTURE (NOT USED - SEE SHEET CU100).
5. 2" ISOLATION GATE VALVE.
6. 8" WATER LINE C900 DR-18 (MINIMUM 36" DEPTH OF COVER).
7. CONNECT TO EXISTING WATERLINE.
8. FIRE HYDRANT.
9. YARD HYDRANT.
10. TAP FOR 1-1/2" DOMESTIC WATER SERVICE.
11. 8" GATE VALVE AND PLUG FOR FUTURE EXTENSION.
12. PROTECT EXISTING FENCE TO REMAIN, EXCAVATE ON BOTH SIDES OF FENCE FOR
UTILITY INSTALLATION.
13. OPEN CUT/PATCH AS REQUIRED FOR UTILITY INSTALLATION.
14. REMOVE TREES/VEGETATION AS REQUIRED FOR UTILITY INSTALLATION.
15. PAD MOUNTED TRANSFORMER W/ PROTECTIVE BOLLARDS (SEE ELECTRICAL).
16. UTILITY CROSSING, SEE DETAIL 8 ON SHEET C-503.
17. UNDERGROUND ELECTRICAL LINE, CONNECT TO EXISTING TRANSFORMER
(SEE ELECTRICAL).
18. UNDERGROUND COMMUNICATIONS LINE (SEE ELECTRICAL SITE SHEET ES101).
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROADFO FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO
FO
FO
FO
FO
FO
FO FO FO FO FO FO FO FO FO
FO FO FO FO FO FO FO FO FO FO
FO
FO
FO
UP
UP
UP
UP
U
P U
P
U P
UP
UP
UP
UP
UP
X X X X X X X X X X X X X X X X X X X X X X X X X
X X
X X
X X
X X
X
W W W W W W
W W
W W
W W
W
C
CB
MW
S
LOOP ROAD
STORAGE
OPENTRAINING BAY
FFE: 29.5'FG: 29.0'
CLASSROOM
G
RA
VE
L
AHU
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
SS
UP
U P
U P
U P
T
J
P8WL
P8WL
P8WL
C
U C
U C
U C
U C
UC
UC
UC
UC
UC
U C
UP
UP
UP
U P
U P
U P
UP UP
UP
UP
C
P2
FM
P2
FM
P2
FM
P2
FM
P2FM
P2FM
P2FM
P2FM
P2FM
P8WL
P8WL
P8W L
P8W L
P8W L
P8W L
P8W L
P8W L
P8W L
C
29.25
29.25
22 23 24 26 27 28
10 15 20 258 9 11 12 13 14 16 17 18 19 21 22 23 24 26
20 2521 22 23 24 26 27 28
26 27
P8WL
P8 W
L
P8WL
P8WL
P8WL
P8WL
P8WL
LO
D
LO
D
LO
D LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD LOD
LOD
LOD
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LODLODLOD
LOD
LOD
LODLODLODLODLODLOD
LOD LOD LOD LOD LOD LOD LOD
LOD
LOD
LOD
LO
DLOD
LO
D
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LO
D
LOD
LOD
P2FM
P2FM
P2FM
P2FM
P2FM
P2FM P2FM P2FM
P2FM
P2FM
P2FM
P2FM
UC
UC
UC
UC
UC
UC
UC
UC
UC
C
151 Poole Rd. Suite 100 | Leland, NC, 28451
TEL (910) 383-1044 | FAX (910) 383-1045
www.capefearengineering.com | N.C. LICENSE # C-1621
GENERAL SHEET NOTES
SHEET KEYNOTES
12-18-2025 CG100
CIVIL GRADING PLAN
60037292
1. GRADE SITE TO PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDING
2. DRAINAGE SWALE
3. APPROXIMATE LOCATIONS OF CLIN PLANTINGS, IF GOVERNMENT
EXERCISES THE CLIN OPTION TO PROVIDE ADDITIONAL SCREENING
FOR THE PROJECT. QUANTITY AND LOCATIONS AS DIRECTED BY
CONTRACTING OFFICER. PLANTING LOCATIONS…