This solicitation is for project P-828 SMART ENERGY at Naval Station Great Lakes in Great Lakes, Illinois. The solicitation seeks proposals for energy efficiency upgrades that will include installation of variable frequency drives, lighting retrofits, building automation systems, and energy management and control systems. Proposals are due by the date and time specified in the solicitation and will be evaluated based on technical qualifications, past performance, and price. The contract will be awarded to the responsible offeror whose conforming proposal provides the best value to the government. The Naval Facilities Engineering Command is the contracting agency.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SCADA DATABASE 8-9-22

[NodeName : ENG1Database : GLNTC_6RFile Name : C:\Users\Landrumjr\Desktop\SCADA DATABASE 8-9-22.csvDate : 8/9/2022Time : 12:59:36 PM]
#AI259AO1DI472DO104AR176MDI3BL20AA536DA1630CA57FN6TX2TT1EV97PG24ETR6#
[BLOCK TYPETAGNEXT BLKDESCRIPTIONINITIAL SCANSCAN TIMESMOOTHINGI/O DEVICEH/W OPTIONSI/O ADDRESSSIGNAL CONDITIONINGLOW EGU LIMITHIGH EGU LIMITEGU TAGINITIAL A/M STATUSALARM ENABLEALARM AREA(S)LO LO ALARM LIMITLO ALARM LIMITHI ALARM LIMITHI HI ALARM LIMITROC ALARM LIMITDEAD BANDALARM PRIORITYENABLE OUTPUTSECURITY AREA 1SECURITY AREA 2SECURITY AREA 3ALARM AREA 1ALARM AREA 2ALARM AREA 3ALARM AREA 4ALARM AREA 5ALARM AREA 6ALARM AREA 7ALARM AREA 8ALARM AREA 9ALARM AREA 10ALARM AREA 11ALARM AREA 12ALARM AREA 13ALARM AREA 14ALARM AREA 15USER FIELD 1USER FIELD 2ESIG TYPEESIG ALLOW CONT USEESIG XMPT ALARM ACKESIG UNSIGNED WRITESPDR Update Rate
!A_NAMEA_TAGA_NEXTA_DESCA_ISCANA_SCANTA_SMOTHA_IODVA_IOHTA_IOADA_IOSCA_ELOA_EHIA_EGUDESCA_IAMA_IENABA_ADIA_LOLOA_LOA_HIA_HIHIA_ROCA_DBANDA_PRIA_EOUTA_SA1A_SA2A_SA3A_AREA1A_AREA2A_AREA3A_AREA4A_AREA5A_AREA6A_AREA7A_AREA8A_AREA9A_AREA10A_AREA11A_AREA12A_AREA13A_AREA14A_AREA15A_ALMEXT1A_ALMEXT2A_ESIGTYPEA_ESIGCONTA_ESIGACKA_ESIGTRAPA_PDR_UPDATERATE
AIDG3_300G_7KV (VCA)ON10MBEM6A:463517None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB3114A_P2_SPD_SPP2 Speed Setpoint (%) 12/10/2020ON10IDSB3114A.PLC.F8:4None0100AUTOENABLENONE0010010005LOWYESNONENONENONEALLNONEYESNOREJECT1,000
AIB3114_P1_SPD_FBPump 1 Speed Feedback 12/10/2020ON10IDSB3114A.PLC.F8:154None0100AUTODISABLENONE0010010005LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB3114_P2_SPD_FBPump 2 Speed Feedback 12/10/2020ON10IDSB3114A.PLC.F8:155None0100AUTODISABLENONE0010010005LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_PI001Bldg 6531 Steam Boiler Steam PressureON10IDSB6531.B6531.B6531_PI001None0100PSIAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB01_FI001Bldg 6531 Steam Boiler 1 Gas FlowON10IDSB6531.B6531.B6531_SB01_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB01_FI002Bldg 6531 Steam Boiler 1 Combustion AirON10IDSB6531.B6531.B6531_SB01_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB01_LI001Bldg 6531 Steam Boiler 1 Water LevelON10IDSB6531.B6531.B6531_SB01_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB01_PI001Bldg 6531 Steam Boiler 1 Gas PressureON10IDSB6531.B6531.B6531_SB01_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB02_FI001Bldg 6531 Steam Boiler 2 Gas FlowON10IDSB6531.B6531.B6531_SB02_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB02_FI002Bldg 6531 Steam Boiler 2 Combustion AirON10IDSB6531.B6531.B6531_SB02_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB02_LI001Bldg 6531 Steam Boiler 2 Water LevelON10IDSB6531.B6531.B6531_SB02_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB02_PI001Bldg 6531 Steam Boiler 2 Gas PressureON10IDSB6531.B6531.B6531_SB02_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB03_FI001Bldg 6531 Steam Boiler 3 Gas FlowON10IDSB6531.B6531.B6531_SB03_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB03_FI002Bldg 6531 Steam Boiler 3 Combustion AirON10IDSB6531.B6531.B6531_SB03_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB03_LI001Bldg 6531 Steam Boiler 3 Water LevelON10IDSB6531.B6531.B6531_SB03_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB03_PI001Bldg 6531 Steam Boiler 3 Gas PressureON10IDSB6531.B6531.B6531_SB03_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB04_FI001Bldg 6531 Steam Boiler 4 Gas FlowON10IDSB6531.B6531.B6531_SB04_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB04_FI002Bldg 6531 Steam Boiler 4 Combustion AirON10IDSB6531.B6531.B6531_SB04_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB04_LI001Bldg 6531 Steam Boiler 4 Water LevelON10IDSB6531.B6531.B6531_SB04_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB04_PI001Bldg 6531 Steam Boiler 4 Gas PressureON10IDSB6531.B6531.B6531_SB04_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB05_FI001Bldg 6531 Steam Boiler 5 Gas FlowON10IDSB6531.B6531.B6531_SB05_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB05_FI002Bldg 6531 Steam Boiler 5 Combustion AirON10IDSB6531.B6531.B6531_SB05_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB05_LI001Bldg 6531 Steam Boiler 5 Water LevelON10IDSB6531.B6531.B6531_SB05_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB6531_SB05_PI001Bldg 6531 Steam Boiler 5 Gas PressureON10IDSB6531.B6531.B6531_SB05_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_PI001Bldg 7104 Steam Boiler Steam PressureON10IDSB7104.B7104.B7104_PI001None0100PSIAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB01_FI001Bldg 7104 Steam Boiler 1 Gas FlowON10IDSB7104.B7104.B7104_SB01_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB01_FI002Bldg 7104 Steam Boiler 1 Combustion AirON10IDSB7104.B7104.B7104_SB01_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB01_LI001Bldg 7104 Steam Boiler 1 Water LevelON10IDSB7104.B7104.B7104_SB01_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB01_PI001Bldg 7104 Steam Boiler 1 Gas PressureON10IDSB7104.B7104.B7104_SB01_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB02_FI001Bldg 7104 Steam Boiler 2 Gas FlowON10IDSB7104.B7104.B7104_SB02_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIM6_MWH_PVON10SIM769-5100AUTODISABLENONE-5-510010005LOWYESNONENONENONEALM ALLALM ELECALM M6NONEYESNOREJECT1,000
AIM6_MVAR_PVON10SIM7680100AUTODISABLENONE0010010005LOWNONONENONENONEALM ALLALM ELECALM M6NONEYESNOREJECT1,000
AIB7104_SB02_FI002Bldg 7104 Steam Boiler 2 Combustion AirON10IDSB7104.B7104.B7104_SB02_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB02_LI001Bldg 7104 Steam Boiler 2 Water LevelON10IDSB7104.B7104.B7104_SB02_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB02_PI001Bldg 7104 Steam Boiler 2 Gas PressureON10IDSB7104.B7104.B7104_SB02_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB03_FI001Bldg 7104 Steam Boiler 3 Gas FlowON10IDSB7104.B7104.B7104_SB03_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB03_FI002Bldg 7104 Steam Boiler 3 Combustion AirON10IDSB7104.B7104.B7104_SB03_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB03_LI001Bldg 7104 Steam Boiler 3 Water LevelON10IDSB7104.B7104.B7104_SB03_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIM6A_TEMPSETPOINTKWTemporary Set Point KWON10SIM50006,000AUTOENABLENONE006,0006,00000LOWYESSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB7104_SB03_PI001Bldg 7104 Steam Boiler 3 Gas PressureON10IDSB7104.B7104.B7104_SB03_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB04_FI001Bldg 7104 Steam Boiler 4 Gas FlowON10IDSB7104.B7104.B7104_SB04_FI001None0100SCFHAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB04_FI002Bldg 7104 Steam Boiler 4 Combustion AirON10IDSB7104.B7104.B7104_SB04_FI002None0100SCFMAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB04_LI001Bldg 7104 Steam Boiler 4 Water LevelON10IDSB7104.B7104.B7104_SB04_LI001None0100INCHESAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7104_SB04_PI001Bldg 7104 Steam Boiler 4 Gas PressureON10IDSB7104.B7104.B7104_SB04_PI001None0100IN WCAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB7811_DATEB7811 DATE FROM PLCON10IDSServer1.B7811.N7:81None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_DATE_SPB7811 DATE FOR PLC SETPOINTON10IDSServer1.B7811.N7:32None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_DIS_PRESS_SPB7811_DIS_PRESS_SP_TB7811 PRESSURE (LOCAL) CTRL SETPOINTON10IDSServer1.B7811.PD9:00.SPSNone-32,76832,767PSIAUTODISABLENONE-32,768-32,76832,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALLNONEYESNOREJECT1,000
AIB7811_DIS_PRESS_SPSDB7811 PUMP DISCH HEADER PR SP SUMMER DAYON10IDSServer1.B7811.N7:38None-32,76832,767PSIAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_DIS_PRESS_SPSNB7811 PUMP DISCH HDR PR SP SUMMER NITEON10IDSServer1.B7811.N7:39None-32,76832,767PSIAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_DIS_PRESS_SPWDB7811 PUMP DISCH HEADER PR SP WINTER DAYON10IDSServer1.B7811.N7:40None-32,76832,767PSIAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_DIS_PRESS_SPWNB7811 PUMP DISCH HDR PR SP WINTER NITEON10IDSServer1.B7811.N7:41None-32,76832,767PSIAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_HOURB7811 HOUR FROM PLCON10IDSServer1.B7811.N7:77None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_HOUR_SPB7811 HOUR FOR PLC SETPOINTON10IDSServer1.B7811.N7:28None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LAG1_PMPB7811 BOOSTER PUMP SELECTED AS LAG 1ON10IDSServer1.B7811.N7:21None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LAG1_REM_REQB7811 LAG1 PUMP REQD 4 LVL CTRL % PID SPON10IDSServer1.B7811.N7:52None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LAG2_PMPB7811 BOOSTER PUMP SELECTED AS LAG 2ON10IDSServer1.B7811.N7:22None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LAG2_REM_REQB7811 LAG2 PUMP REQD 4 LVL CTRL % PID SPON10IDSServer1.B7811.N7:53None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LAG12_LOC_NREQB7811 LAG1^2 ~REQD 4 PR CTRL %PID OUTPON10IDSServer1.B7811.N7:68None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIM6A_SEL_551_10PROTECTIVE RELAY SEL551 A (IC)ON10MBEM6A:463510None0500AAUTODISABLENONE00500500026LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_SEL_551_9PROTECTIVE RELAY SEL551 A (IB)ON10MBEM6A:463509None0500AAUTODISABLENONE00500500025LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_SEL_551_8PROTECTIVE RELAY SEL551 A (IA)ON10MBEM6A:463508None0500AAUTODISABLENONE00500500025LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB7811_LAG12_LOC_REQB7811 LAG1^2 REQD 4 PR CTRL %PID OUTPON10IDSServer1.B7811.N7:49None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LEAD_LOC_NREQB7811 LEAD PUMP NOT REQ'D % PID OUTPUTON10IDSServer1.B7811.N7:48None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LEAD_PMPB7811 BOOSTER PUMP SELECTED AS LEADON10IDSServer1.B7811.N7:20None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LEAD_REM_REQB7811 LEAD PUMP REQD 4 LVL CTRL % PID SPON10IDSServer1.B7811.N7:51None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LOC_CNTRL_KVB7811 PUMPS PR CTRL TIME DELAY VALUEON10IDSServer1.B7811.N7:70None-32,76832,767SECAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_LOC_OUT_IB7811_LOC_OUT_TB7811 PR CTRL OUTPUT INDON10IDSServer1.B7811.N7:61None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_MINUTEB7811 MINUTE FROM PLCON10IDSServer1.B7811.N7:78None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_MINUTE_SPB7811 MINUTE FOR PLC SETPOINTON10IDSServer1.B7811.N7:29None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_MONTHB7811 MONTH FROM PLCON10IDSServer1.B7811.N7:80None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_MONTH_SPB7811 MONTH FOR PLC SETPOINTON10IDSServer1.B7811.N7:31None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP1_MANL_SOB7811 BOOSTER PUMP 1 MANUAL SET OUTON10IDSServer1.B7811.N7:54None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERNONEALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP1_OUT_IB7811 BOOSTER PUMP 1 OUTPUT IND 0-100%ON10IDSServer1.B7811.N7:63None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP2_MANL_SOB7811 BOOSTER PUMP 2 MANUAL SET OUTON10IDSServer1.B7811.N7:55None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERNONEALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP2_OUT_IB7811 BOOSTER PUMP 2 OUTPUT IND 0-100%ON10IDSServer1.B7811.N7:64None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP3_MANL_SOB7811 BOOSTER PUMP 3 MANUAL SET OUTON10IDSServer1.B7811.N7:56None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERNONEALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP3_OUT_IB7811 BOOSTER PUMP 3 OUTPUT IND 0-100%ON10IDSServer1.B7811.N7:65None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP4_MANL_SOB7811 BOOSTER PUMP 4 MANUAL SET OUTON10IDSServer1.B7811.N7:57None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERNONEALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP4_OUT_IB7811 BOOSTER PUMP 4 OUTPUT IND 0-100%ON10IDSServer1.B7811.N7:66None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP_RMP_MINB7811 PUMP RAMP RATE/MINUTE IN PID CTRLON10IDSServer1.B7811.N7:59None-32,76832,767GPMAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PMP_RMP_PERB7811 PUMP RAMP RATE PERCENT IN PID CTRLON10IDSServer1.B7811.N7:58None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_PUMP_CNTRLB7811 BOOST PUMP CTRL 1'=PR 2=LVL 3=MANL'ON10IDSServer1.B7811.N7:60None-32,76832,767#AUTOENABLENONE113300HIGHYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_REM_CNTRL_KVB7811 PUMPS LEVEL CTRL TIME DELAY VALUEON10IDSServer1.B7811.N7:71None-32,76832,767SECAUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_REM_OUT_IB7811_REM_OUT_TB7811 REMOTE CTRL OUTPUT INDON10IDSServer1.B7811.N7:62None-32,76832,767%AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_SECONDB7811 SECOND FROM PLCON10IDSServer1.B7811.N7:79None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_SECOND_SPB7811 SECOND FOR PLC SETPOINTON10IDSServer1.B7811.N7:30None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AISYSTEM_WIDE_UNACK_ALMPLAY-WAV-EVENTON10SIMC:UTOT0100AUTODISABLENONE0010010005LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIM6A_ASCO_UTILITY_RESTORE_SPUTILITY RESTORE SPON10IDSGE_MASTER.MASTER.%R01250None01,000,000AUTODISABLENONE001,000,0001,000,000050,000LOWYESSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_RESTORE_DISPUTILITY RESTORE DISPLAYON10IDSGE_MASTER.MASTER.%R01204None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_RESTORE_ACCUTILITY RESTORE ACCON10IDSGE_MASTER.MASTER.%R01205None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_FAILURE_SPUTILITY FAILURE SPON10IDSGE_MASTER.MASTER.%R01249None0100AUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_FAILURE_DISPUTILITY FAILURE DISPLAYON10IDSGE_MASTER.MASTER.%R01200None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIB7811_STNDBY_PMPB7811 BOOSTER PUMP SELECTED AS STANDBYON10IDSServer1.B7811.N7:23None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_SUM_HR_DAYB7811 HOUR TO START DAYTIME SUMMER CTRLON10IDSServer1.B7811.N7:43None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_SUM_HR_NGHTB7811 HOUR TO START NIGHT SUMMER CTRLON10IDSServer1.B7811.N7:44None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_SUM_MONTHB7811 MONTH TO START SUMMER CONTROLON10IDSServer1.B7811.N7:42None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_TANK_LVL_SPB7811_TANK_LVL_SP_CALCB7811 LEVEL (REMOTE) CTRL SETPOINTON10IDSServer1.B7811.PD9:30.SPSNone-327.68327.67FTAUTODISABLENONE-327.68-327.68327.67327.6700LOWYESSEC ALLSEC WATERSEC B7811ALLNONEYESNOREJECT1,000
AIB7811_TNK_LVL_SPSDB7811 H2O TOWER TANK LEVEL SP SUMMER DAYON10IDSServer1.B7811.N7:34None03,408FTAUTODISABLENONE1,7041,7043,4083,40800LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIAMMONIA_FORWARDING_PRESSUREAMMONIA FORWARDING PRESUREON10IDSAMMONIA.PLC.Urea_Forwarding_Pressure_ActualNone0100PSIAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB7811_TNK_LVL_SPSNB7811 H2O TOWER TANK LVL SP SUMMER NIGHTON10IDSServer1.B7811.N7:35None-327.68327.67FTAUTODISABLENONE-0.01-0.01327.67327.6700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_TNK_LVL_SPWDB7811 H2O TOWER TANK LEVEL SP WINTER DAYON10IDSServer1.B7811.N7:36None-327.68327.67FTAUTODISABLENONE-0.01-0.01327.67327.6700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIAMMONIA_FRWD_PRES_SPAN_4MAAMMONIA FORWARDING PRESURE SPAN 4MAON10IDSAMMONIA.PLC.Urea_Forwarding_Pressure_Lower_SpanNone0100AUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_FRWD_PRES_SPAN_20MAAMMONIA FORWARDING PRESURE SPAN 20MAON10IDSAMMONIA.PLC.Urea_Forwarding_Pressure_Upper_SpanNone0600AUTODISABLENONE00600600030LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_HIGH_FRWD_PRS_DLYAMMONIA HIGH FORWARDING PRESS TIME DELAYON10IDSAMMONIA.PLC.TD_UREA_FORWARDING_PRESSURE_HIGHNone0100SECAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_HIGH_FRWRD_PRESS_ALMAMMONIA HIGH FORWARDING PRESSURE ALM SPON10IDSAMMONIA.PLC.UREA_FORWARDING_PRESSURE_SPNone0100PSIAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB7811_TNK_LVL_SPWNB7811 H2O TOWER TANK LVL SP WINTER NIGHTON10IDSServer1.B7811.N7:37None-327.68327.67FTAUTODISABLENONE-0.01-0.01327.67327.6700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_TNK_LV_SPSDB7811 Tank Summer Day SetpointON10IDSServer1.b7811.B7810_SPSD_001None0100AUTODISABLENONE0010010005LOWYESNONENONENONEALLNONEYESNOREJECT1,000
AIB7811_TNK_LV_SPSNB7811 Tank Summer NIGHT SetpointON10IDSServer1.b7811.B7810_SPSN_002None0100AUTODISABLENONE0010010005LOWYESNONENONENONEALLNONEYESNOREJECT1,000
AIB7811_TNK_LV_SPWDB7811 Tank WINTER DAY SetpointON10IDSServer1.b7811.B7810_SPWD_003None0100AUTODISABLENONE0010010005LOWYESNONENONENONEALLNONEYESNOREJECT1,000
AIAMMONIA_LEVELAMMONIA LEVELON10IDSAMMONIA.PLC.Urea_Tank_Level_ActualNone0100GALAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_HI_HI_SPAMMONIA LEVEL HIGH HIGH SETPOINTON10IDSAMMONIA.PLC.Urea_Tank_Level_HiHi_SPNone0500GALAUTODISABLENONE00500500025LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_HI_SPAMMONIA LEVEL HIGH SETPOINTON10IDSAMMONIA.PLC.Urea_Tank_Level_Hi_SPNone0500GALAUTODISABLENONE00500500025LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_LOW_LOW_SPAMMONIA LEVEL LOW LOW SETPOINTON10IDSAMMONIA.PLC.Urea_Tank_Level_LoLo_SPNone-300300GALAUTODISABLENONE-300-300300300030LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_LOW_SPAMMONIA LEVEL LOW SETPOINTON10IDSAMMONIA.PLC.Urea_Tank_Level_Lo_SPNone-300300GALAUTODISABLENONE-300-300300300030LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_SPAN_4MAAMMONIA LEVEL SPAN 4MAON10IDSAMMONIA.PLC.Urea_Tank_Level_Lower_SpanNone0100AUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_LEVEL_SPAN_20MAAMMONIA LEVEL SPAN 20MAON10IDSAMMONIA.PLC.Urea_Tank_Level_Upper_SpanNone0600AUTODISABLENONE00600600030LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB7811_TNK_LV_SPWNB7811 Tank WINTER NIGHT SetpointON10IDSServer1.b7811.B7810_SPWN_004None0100AUTODISABLENONE0010010005LOWYESNONENONENONEALLNONEYESNOREJECT1,000
AIAMMONIA_LOW_FLOW_TIME_DELAYAMMONIA LOW FLOW TIME DELAYON10IDSAMMONIA.PLC.TD_UREA_LOW_FLOWNone0100SECAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB7811_WIN_HR_DAYB7811 HOUR TO START DAYTIME WINTER CTRLON10IDSServer1.B7811.N7:46None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_WIN_HR_NGHTB7811 HOUR TO START NIGHT WINTER CTRLON10IDSServer1.B7811.N7:47None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_WIN_MONTHB7811 MONTH TO START WINTER CONTROLON10IDSServer1.B7811.N7:45None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB7811_YEARB7811 YEAR FROM PLCON10IDSServer1.B7811.N7:82None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWNOSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIAMMONIA_PUMP_1_RUNTIMEAMMONIA PUMP 1 RUNTIMEON10IDSAMMONIA.PLC.Pump1RuntimeHrsNone0100HRSAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB7811_YEAR_SPB7811 YEAR FOR PLC SETPOINTON10IDSServer1.B7811.N7:33None-32,76832,767#AUTODISABLENONE-1-132,76732,76700LOWYESSEC ALLSEC WATERSEC B7811ALM ALLALM WATERALM B7811NONEYESNOREJECT1,000
AIB8002_TANK_LEVEL_INCHESTank level inches 12/10/2020ON10IDSB3114A.PLC.F8:152None0100INAUTOENABLENONE0010010005LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB8300_PUMP_1_RUNTIMEB8300_PUMP_1_RUNTIMEON10IDSServer1.B8300.F8:3None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_PUMP_2_RUNTIMEB8300_PUMP_2_RUNTIMEON10IDSServer1.B8300.F8:4None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_START_LAG_SPB8300_START_LAG_SPON10IDSServer1.B8300.F8:25None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIAMMONIA_PUMP_2_RUNTIMEAMMONIA PUMP 2 RUNTIMEON10IDSAMMONIA.PLC.Pump2RuntimeHrsNone0100HRSAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB8300_START_LEAD_SPB8300_START_LEAD_SPON10IDSServer1.B8300.F8:23None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_STATION_DISCHARGE_FLOW_TB8300_STATION_DISCHARGE_FLOW_TOTALON10IDSServer1.B8300.F8:2None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIAMMONIA_PUMP_OVERLAP_RUNTIMEAMMONIA PMP OVERLAP RUNTIME DURING SWITCON10IDSAMMONIA.PLC.TD_PUMP_OVERLAPNone0100SECAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB8300_STOP_LAG_SPB8300_STOP_LAG_SPON10IDSServer1.B8300.F8:24None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_STOP_LEAD_SPB8300_STOP_LEAD_SPON10IDSServer1.B8300.F8:22None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_WET_WELL_DISCHARGE_FLOWB8300_WET_WELL_DISCHARGE_FLOWON10IDSServer1.B8300.F8:1None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIAMMONIA_SWITCH_PUMP_TIMEAMMONIA SWITCH PUMP TIMEON10IDSAMMONIA.PLC.TD_PUMP_SWITCHNone0100HRAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIAMMONIA_TANK_FAULT_TIME_DELAYAMMONIA TANK FAULT TIME DELAYON10IDSAMMONIA.PLC.TD_UREA_TANK_FAULTNone0100SECAUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIB8300_WET_WELL_HIGH_LEVEL_SPB8300_WET_WELL_HIGH_LEVEL_SPON10IDSServer1.B8300.F8:21None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_WET_WELL_LEVELB8300_WET_WELL_LEVELON10IDSServer1.B8300.F8:0None025AUTODISABLENONE00252501LOWNOSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIB8300_WET_WELL_LOW_LEVEL_SPB8300_WET_WELL_LOW_LEVEL_SPON10IDSServer1.B8300.F8:20None025FTAUTODISABLENONE00252501LOWYESSEC ALLSEC SEWAGEALM ALLALM SEWAGEALM B8300NONEYESNOREJECT1,000
AIDG2_300G_5KV (VAB)ON10MBEM6A:463532None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIAMMONIA_TANK_LEVEL_STATEAMMONIA TANK LEVEL STATEON10IDSAMMONIA.PLC.Urea_Tank_Level_StateNone0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALM ALLALM ELECALM AMMNONEYESNOREJECT1,000
AIM6A_ASCO_UTILITY_FAILURE_ACCUTILITY FAILURE ACCON10IDSGE_MASTER.MASTER.%R01201None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_EXT_PARAL_SPUTILITY EXTENDED PARALLEL SPON10IDSGE_MASTER.MASTER.%R01251None010,000,000AUTODISABLENONE0010,000,00010,000,0000500,000LOWYESSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_EXT_PARAL_DSPUTILITY EXTENDED PARALLEL DISPON10IDSGE_MASTER.MASTER.%R01211None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_UTILITY_EXT_PARAL_ACCUTILITY EXTENDED PARALLEL ACCON10IDSGE_MASTER.MASTER.%R01212None0100AUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIDG2_300G_6KV (VBC)ON10MBEM6A:463533None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_7KV (VCA)ON10MBEM6A:463534None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_8A (IA)ON10MBEM6A:463529None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_9A (IB)ON10MBEM6A:463530None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_10A (IC)ON10MBEM6A:463531None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB12_F01_AI001B12 Filter 1 TurbidityON10IDSB12_WTP.B12_WTP_ODD.B12_F01_AI001None01NTUAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB12_F01_FLTR_HRSB12 Filter 1 Filter Effluent HoursON10IDSB12_WTP.B12_WTP_ODD.B12_F01_FLTR_HRSNone0999.99HRSAUTODISABLENONE00999.99999.9900LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIDG2_300G_11NUMERIC INDICATOR FOR KWON10MBEM6A:463536None01,800KWAUTODISABLENONE001,8001,800090LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_12HZON10MBEM6A:463543None070HzAUTODISABLENONE00707004LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_13POWER FACTORON10MBEM6A:463542None01.5AUTODISABLENONE001.51.500LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_38KV (VS)ON10MBEM6A:463535None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_39NUMERIC INDICATOR FOR KVAON10MBEM6A:463540None01,800AUTODISABLENONE001,8001,800092LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_300G_40NUMERIC INDICATOR FOR KVARON10MBEM6A:463538None01,800AUTODISABLENONE001,8001,800090LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_1Engine SpeedON10IDSBOPS.PLC.CATData2_INT[68]None032,767RPMAUTODISABLENONE0032,76732,76701,638LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_2Coolant TemperatureON10IDSBOPS.PLC.CATData2_INT[70]None0999,999CAUTOENABLENONE454520020000LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG2_CCM_3Filtered Oil PressureON10IDSBOPS.PLC.CATData2_Real[9]None0999,999PSIAUTODISABLENONE0200000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_ASCO_MAX_BASELOAD_KW_SETMAX BASELOAD SETON10IDSGE_MASTER.MASTER.%R01228None016,000KWAUTODISABLENONE0016,00016,0000800LOWYESSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_ASCO_MAX_BASELOAD_KW_DISPMAX BASELOAD DISPLAYON10IDSGE_MASTER.MASTER.%R00174None016,000KWAUTODISABLENONE0016,00016,0000800LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_5Hour MeterON10IDSBOPS.PLC.CATData2_INT[73]None0100HRSAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_6Engine Battery VoltsON10IDSBOPS.PLC.CATData2_Real[1]None060VDCAUTODISABLENONE60600000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_7EMCP II Control Switch PositionON10IDSBOPS.PLC.CATData2_INT[14]None0100BOPSAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_9Fuel Consumption RateON10IDSBOPS.PLC.CATData2_Real[49]None0999,999GPHAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_10Fuel Consumption CumulativeON10IDSBOPS.PLC.CATData2_Real[70]None0999,999GALAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_11CCM DG2 Air Filter Retriction #901ON10IDSBOPS.PLC.CATDATA3_REAL[11]None09,999,999PSIAUTOENABLENONE00909000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_12Engine LoadON10IDSBOPS.PLC.CATData2_INT[42]None0225%AUTODISABLENONE00225225011LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_13Engine Oil Pressure Diff.ON10IDSBOPS.PLC.CATData2_Real[17]None032,767PSI BOPS CATData2_Real[17]AUTOENABLENONE0015015000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_14Fuel PressureON10IDSBOPS.PLC.CatData2_Real[36]None0999,999PSIAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_15Fuel Pressure DiffON10IDSBOPS.PLC.CATData2_Real[23]None0999,999PSIAUTOENABLENONE00110110050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_16Exhaust Manifold Temperature RightON10IDSBOPS.PLC.CATData2_INT[76]None01,400Deg C BOPS CATData2_INT[76]AUTOENABLENONE001,3001,30000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB12_F02_AI001B12 Filter 2 TurbidityON10IDSB12_WTP.B12_WTP_EVEN.B12_F02_AI001None01NTUAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB12_F02_FLTR_HRSB12 Filter 2 Filter Effluent HoursON10IDSB12_WTP.B12_WTP_EVEN.B12_F02_FLTR_HRSNone0999.99HRSAUTODISABLENONE00999.99999.9900LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIM6A_ASCO_MASTER_47MAX ALLOWED OUTPUTON10IDSGE_MASTER.MASTER.%R30None016,000GE MASTER.MASTER.ASCO_Master_47AUTODISABLENONE0016,00016,0000800LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_ASCO_MASTER_45LEAD GENERATOR 3/DG2 4/DG3 OLDON10IDSGE_MASTER.MASTER.%R400None0100GE MASTER.ASCO_Master_45AUTODISABLENONE0010010005LOWYESSEC ALLSEC ELECALLPERFVERIYESNOACCEPT1,000
AIM6A_ASCO_MASTER_44Plant OutputON10IDSGE_MASTER.MASTER.%R66None01,000GE MASTER.ASCO_Master_44AUTODISABLENONE001,0001,000050LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_17Exhaust Manifold Temperature LeftON10IDSBOPS.PLC.CATData2_INT[77]None01,400Deg CAUTOENABLENONE001,3001,30000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_18Boost PressureON10IDSBOPS.PLC.CATData2_REAL[10]None0999,999PSIAUTOENABLENONE0015015000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_19Air Filter Restriction RightON10IDSBOPS.PLC.CATData2_REAL[46]None099,999PSI BOPS : CATData2_REAL[46]AUTODISABLENONE0099,99999,99905,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_20Air Filter Restriction LeftON10IDSBOPS.PLC.CATData2_REAL[47]None0999,999PSIAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_CCM_23Total EnergyON10IDSBOPS.PLC.CATData2_DINT[4]None0100MWHAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_SCR_F8_60Catalyst Diff PressureON10IDSDG2_SCR.DG2_SCR.F8:60None0100PSIAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG2_SCR_F8_61M6A_DG2_SCR_COM_EVCatalyst TemperatureON10IDSDG2_SCR.DG2_SCR.F8:61None01,000DEG F DG2_SCR F8:61AUTODISABLENONE001,0001,000050LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_5KV (VAB)ON10MBEM6A:463515None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_6KV (VBC)ON10MBEM6A:463516None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_8A (IA)ON10MBEM6A:463512None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_9A (IB)ON10MBEM6A:463513None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_10A (IC)ON10MBEM6A:463514None0125AAUTODISABLENONE0012512506LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_11NUMERIC INDICATOR FOR KWON10MBEM6A:463519None01,800AUTODISABLENONE001,8001,800090LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_12HZON10MBEM6A:463526None070HzAUTODISABLENONE00707004LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_13POWER FACTORON10MBEM6A:463525None01.5AUTODISABLENONE001.51.500.1LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_38KV (VS)ON10MBEM6A:463518None035KVAUTODISABLENONE00353502LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_39NUMERIC INDICATOR FOR KVAON10MBEM6A:463523None01,800AUTODISABLENONE001,8001,800092LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_300G_40NUMERIC INDICATOR FOR KVARON10MBEM6A:463521None01,800AUTODISABLENONE001,8001,800090LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_1Engine SpeedON10IDSBOPS.PLC.CATData3_INT[68]None0100RPMAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIB12_F03_AI001B12 Filter 3 TurbidityON10IDSB12_WTP.B12_WTP_ODD.B12_F03_AI001None01NTUAUTODISABLENONE001100LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIB12_F03_FLTR_HRSB12 Filter 3 Filter Effluent HoursON10IDSB12_WTP.B12_WTP_ODD.B12_F03_FLTR_HRSNone0999.99HRSAUTODISABLENONE00999.99999.9900LOWNONONENONENONEALLNONEYESNOREJECT1,000
AIDG3_CCM_2Coolant TemperatureON10IDSBOPS.PLC.CATData3_INT[70]None0999,999CAUTOENABLENONE454520020000LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG3_CCM_3Filtered Oil PressureON10IDSBOPS.PLC.CATData3_Real[9]None0999,999PSIAUTOENABLENONE2020999,999999,99900LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG3_CCM_5Hour MeterON10IDSBOPS.PLC.CATData3_INT[73]None0100HRSAUTODISABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_6Engine Battery VoltsON10IDSBOPS.PLC.CATData3_Real[1]None0200VDCAUTOENABLENONE606020020000LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG3_CCM_7EMCP II Control Switch PositionON10IDSBOPS.PLC.CATData3_INT[14]None0100AUTOENABLENONE0010010005LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_9Fuel Consumption RateON10IDSBOPS.PLC.CATData3_Real[49]None0999,999GPHAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_10Fuel Consumed CumulativeON10IDSBOPS.PLC.CATData3_Real[70]None0999,999GALAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_11CCM DG3 Air Filter Retriction #901ON10IDSBOPS.PLC.CATDATA3_REAL[11]None09,999,999PSIAUTOENABLENONE00909000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_12Engine LoadON10IDSBOPS.PLC.CATData3_INT[42]None0225%AUTODISABLENONE00225225011LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_13Engine Oil Press DiffON10IDSBOPS.PLC.CATData3_Real[17]None032,767PSIAUTOENABLENONE505015015000LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG3_CCM_14M6A_BOPS_COM_EVFuel PressON10IDSBOPS.PLC.CATData3_Real[36]None0999,999.00PSIAUTODISABLENONE00999,999.00999,999.00050,000.00LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIM6A_ASCO_MASTER_1SET POINT REMOTE kWON10IDSGE_MASTER.MASTER.%R176None06,000kWAUTODISABLENONE006,0006,0000300LOWYESSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_15Fuel Press DiffON10IDSBOPS.PLC.CATData3_Real[23]None0999,999PSIAUTOENABLENONE0011011000LOWNOSEC ALLSEC ELECALM ALLALM ELECALM M6ANONEYESNOREJECT1,000
AIDG3_CCM_16Exhaust Manifold Temperature RightON10IDSBOPS.PLC.CATData3_INT[76]None02,000Deg CAUTOENABLENONE001,3001,30000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_17Exhaust Manifold Temperature LeftON10IDSBOPS.PLC.CATData3_INT[77]None02,000Deg CAUTOENABLENONE001,3001,30000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_18Boost PressureON10IDSBOPS.PLC.CATData3_REAL[10]None0999,999PSIAUTOENABLENONE00150150050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_19Air Filter Restriction RightON10IDSBOPS.PLC.CATData3_REAL[46]None0999,999PSIAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_20Air Filter Restriction LeftON10IDSBOPS.PLC.CATData3_REAL[47]None0999,999PSIAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_CCM_23Total EnergyON10IDSBOPS.PLC.CATData3_DINT[4]None0999,999MWHAUTODISABLENONE00999,999999,999050,000LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000
AIDG3_SCR_F8_60Catalyst Diff PressureON10IDSDG3_SCR.DG3_SCR.F8:60None01,000PSIAUTODISABLENONE001,0001,000050LOWNOSEC ALLSEC ELECALLNONEYESNOREJECT1,000