MIA ATCT Precast Panel Repair Drawings REVISED.pdf
PDF 715 KB Posted
- Attached to
- MIA ATCT Precast Panel Repair Federal contract opportunity
- Solicitation number
- 697DCK-22-R-00172
About this file
This solicitation requests proposals for precast panel repairs at the Miami International Airport Air Traffic Control Tower located in Miami, Florida. The Federal Aviation Administration is seeking to repair cracked and damaged precast concrete panels on the tower's cable access and cab levels, including cleaning, concrete surface preparation, fiber-reinforced polymer composite strengthening, new sealants and flashing. Offerors must be registered in the System for Award Management and submit proposals by the due date of May 2, 2022. An optional site visit is available and proposal requirements are defined in the solicitation.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F LOR ID A
L ICE NSER
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:55 PM JST
RAB
G000
JST
COVER SHEET
08/31/2017
MIAMI INTERNATIONAL AIRPORT
MIAMI, FL
AUGUST 31, 2017
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
REV
1605415
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:55 PM JST
RAB
G001
JST
DRAWING INDEX
08/31/2017
DRAWING NUMBER
GENERAL
MIA-D-ATCT-G000
MIA-D-ATCT-G001
MIA-D-ATCT-G010
MIA-D-ATCT-G015
MIA-D-ATCT-G040
STRUCTURAL
MIA-D-ATCT-S000
MIA-D-ATCT-S001
MIA-D-ATCT-S002
MIA-D-ATCT-S100
TITLE
COVER SHEET
DRAWING INDEX
ABBREVIATIONS - SHEET 1
SYMBOL LEGEND
CONSTRUCTION COORDINATION NOTES
GENERAL NOTES
CABLE ACCESS FRAMING PLAN.
CAB LEVEL FRAMING PLAN
SECTIONS AND DETAILS
MIA-D-ATCT-G011 ABBREVIATIONS - SHEET 2
MIA-D-ATCT-S101 SECTIONS AND DETAILS
MIA-D-ATCT-S102 SECTIONS AND DETAILS
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:55 PM JST
RAB
G010
JST
ABBREVIATIONS - SHEET 1
08/31/2017
A
A AMPERE
AA AIR COOLED
AAV AUTOMATIC AIR VENT
ABG ABOVE FINISHED GRADE
AC ALTERNATING CURRENT, ABOVE CEILING
A/C AIR CONDITIONING
ACC AIR COOLED CHILLER
ACDFC AIR COOLED DRY FLUID COOLER
ACI AMERICAN CONCRETE INSTITUTE
ACM ASBESTOS CONTAINING MATERIAL
ACT ACOUSTICAL CEILING TILE, ACCESS CONTROL TERMINAL
AD ACCESS DOOR, AREA DRAIN
ADJ ADJUSTABLE
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AH AIR HANDLER
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AIC AMPERE INTERRUPTING CAPACITY
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AL AIRPORT LIGHTING, ALUMINUM
AL-GL ALUMINUM AND GLASS
ALUM ALUMINUM
AMM AMMETER
ANN ANNUNCIATOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AO ANALOG OUTPUT
AP ANNUNCIATOR POINT, ACCESS PANEL
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
ARTS AUTOMATED RADAR
AS AIR SEPARATOR
A/S AUDIBLE STROBE
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION
AND AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AT AMPERE TRIP
ATBM AIRWAY/TERMINAL BUILDING MAINTENANCE FACILITY
ATC ACOUSTICAL TILE CEILING
ATC AIR TRAFFIC CONTROL
ATCT AIRPORT TRAFFIC CONTROL TOWER
ATS AUTOMATIC TRANSFER SWITCH
ATV ATMOSPHERIC VENT
AUX AUXILIARY
AV AUTOMATIC VENT
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
AWS AMERICAN WELDING SOCIETY
B
BAT CHGR BATTERY CHARGER
BBHWH BASEBOARD HOT WATER HEATER
BC BARE COPPER
BCKP BACKUP
BDD BACKDRAFT DAMPER
BF BELOW FLOOR (PIPE SIZE)
BFC BELOW FINISHED CEILING
BFP BACKFLOW PREVENTER
BI BACKWARD INCLINED
BITS BYPASS ISOLATION TRANSFER SWITCH
BLDG BUILDING
BLK BLACK
BOD BOTTOM OF DUCT, BACKDRAFT DAMPER
BOF BOTTOM OF FIXTURE
BOP BOTTOM OF PIPING
BOT BOTTOM
BP BOOSTER PUMP
BPU BREAKER PROGRAMMING UNIT
BSDC BARE SOFT DRAWN COPPER
BSMT BASEMENT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT/HOUR
C
C CONDUIT
CAP CAPACITY
CAV CONSTANT AIR VOLUME
CB CIRCUIT BREAKER
CBCR CURVED BLADE CEILING REG.
CCTV CLOSED CIRCUIT TELEVISION
CD CEILING DIFFUSER, CONDENSATE DRAIN
CENT CENTRIFUGAL
CENTRIF CENTRIFUGAL
CAF COMBUSTION AIR FAN
CF CUBIC FOOT/FEET
CFACC CENTRIFUGAL FAN AIR COOLED CONDENSER
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHKD CHECKERED
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CWP CHILLED WATER PUMP
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
C.I.P. CAST IN PLACE
CKT CIRCUIT
CL CENTERLINE
CLF CURRENT LIMITING FUSE
CLG CEILING
CLR CLEAR
CM COMMUNICATION MANHOLE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT, CONDUIT ONLY
COL COLUMN
COMM COMMUNICATIONS
CONC CONCRETE
COND CONDENSATE
CONFIG CONFIGURATION
CONN CONNECTION
CONT CONTINUATION
CONTR CONTRACTOR
COR CONTRACTING OFFICER'S REPRESENTATIVE
CPC CRITICAL POWER CENTER
CPT CARPET
CPU CENTRAL PROCESSING UNIT
CR CONTROL RELAY
CS CONTROL SWITCH
CSF CHEMICAL SHOT FEEDER
CT COOLING TOWER, CABLE TRAY, CURRENT
TRANSFORMER, CERAMIC TILE
CTL CONTROL
CU CONDENSING UNIT, COPPER
CU FT CUBIC FOOT/FEET
CV CONSTANT VOLUME, CONTROL VALVE
CVC CENTRAL VACUUM CLEANER
CW COLD (DOMESTIC) WATER
CWP CONDENSER WATER PUMP, CHILLED WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CWV COMBINATION WASTE AND VENT
CY YD CUBIC YARD
D
D DRAIN
DAMP DAMPER
DB DRY BULB, DIRECT BURIAL, DUCTBANK
DBL DOUBLE
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DG DOOR GRILLE
DHW DOMESTIC HOT WATER
DI DIGITAL INPUT
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DISC DISCONNECT
DF DEGREES FAHRENHEIT
DM DEMAND METER
DN DOWN
DO DIGITAL OUTPUT
DP DIFFERENTIAL PRESSURE
DPDT DOUBLE POLE DOUBLE THROW
D PNL DISTRIBUTION PANEL
DPST DOUBLE POLE SINGLE THROW
DPT DIFFERENTIAL PRESSURE TRANSMITTER
DSF DESTRATIFICATION FAN
DT DOUBLE THROW, DIAPHRAM TANK
DTS DOUBLE THROW SWITCH
DWBP DOMESTIC WATER BOOSTER PUMP
DWDI DOUBLE WIDTH DOUBLE INLET
DWGS DRAWINGS
DWL DOWEL
E
E EAST
EA EACH, EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECP ENGINE CONTROL PANEL
EDAM ELECTRICAL DATA ACQUISITION AND MONITORING
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EG, E/G ENGINE GENERATOR, EXHAUST GRILLE
EMERGENCY GENERATOR
EH ELECTRIC HEATER, ELECTRONIC HUMIDIFIER
EHC ELECTRIC HEATING COIL
EIFS EXTERIOR INSULATION FINISH SYSTEM
ELEC ELECTRIC
ELEV, EL ELEVATION, ELEVATOR
EMCS ENERGY MANAGEMENT AND CONTROL SYSTEM
EMERG EMERGENCY
EMI ELECTROMAGNETIC INTERFACE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
ENT ENTERING
EQ EQUAL
EQUIP EQUIPMENT
ER EXHAUST REGISTER
ERMS ENVIRONMENTAL REMOTE MONITORING SYSTEM
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EWH ELECTRIC WALL HEATER, ELECTRIC WATER HEATER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED, EXPANSION
F
F FIRE WATER SUPPLY
°F DEGREES FAHRENHEIT
FA FIRE ALARM, FREE AREA, FAN COOLED, FRESH AIR
FAA FEDERAL AVIATION ADMINISTRATION
FACP FIRE ALARM CONTROL PANEL
FACT FACTORY
FC FACE OF CURB, FLEXIBLE CONNECTION
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FCV FLOW CONTROL VALVE
FD FLOOR DRAIN, FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDR FEEDER
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FLY FAN
FFE FINISHED FLOOR ELEVATION
FG FIBERGLASS
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FHV FIRE HOSE VALVE
FIG FIGURE
FIN FINISH
FLA FULL LOAD AMPERES
FLR FLOOR
FLEX FLEXIBLE
FLS FLOW SWITCH, FIRE AND LIFE SAFETY
FLUOR FLUORESCENT
FM FACTORY MUTUAL, FORCE MAIN
FO FIBER OPTIC
FOD FACE OPERATED DAMPER
FOG FUEL OIL GAGE
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FIBER OPTIC TERMINAL, FUEL OIL TRANSFER
FP FIRE PUMP
FPM FEET PER MINUTE
FPU FIELD PROGRAMMING UNIT
FS FLOW SWITCH, FLOOR SINK
FSD FIRE/SMOKE DAMPER
FSS FUSIBLE SAFETY SWITCH
FT FEET
FTG FOOTING, FITTING
FV FULL VOLTAGE
FVC FIRE VALVE CABINET
FW FIRE WATER
FWS FIRE WATER SUPPLY
FWD FORWARD, FIRE SPRINKLER WATER DRAIN
G
G GROUND
GA GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERAL, GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFE GOVERNMENT FURNISHED EQUIPMENT
GFM GOVERNMENT FURNISHED MATERIAL
GND GROUND CONNECTOR
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRN GREEN
GRS GALVANIZED RIGID STEEL
GUH GAS FIRED UNIT HEATER
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HAZMAT HAZARDOUS MATERIALS
HB HOSE BIBB
HEX HEXAGONAL
HH HAND HOLE
HM HOLLOW METAL
H. MET. HOLLOW METAL
HOA HAND-OFF-AUTOMATIC
HORIZ HORIZONTAL
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HR HOUR
HS HIGH STRENGTH
HSB HIGH STRENGTH BOLT
HT HEIGHT
HTG HEATING
HTR HEATER
HU HUMIDIFIER
HVAC HEATING, VENTILATION AND AIR CONDITIONING
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
J
JB JUNCTION BOX
JP JOCKEY PUMP
JT JOINT
K
KA KILOAMPERES
KCMIL THOUSAND CIRCULAR MILLS
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES-REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
L
L&S LOUVER AND SCREEN
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBG LINEAR BAR GRILLE
LBR LINEAR BAR RETURN
LBS POUNDS
LD LINEAR DIFFUSER
LF LINEAR FEET
LG LONG
LFS LIGHTING FIXTURE SCHEDULE
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LOSP LOCAL OPERATING STATUS PANEL
LP LOW POINT
LRA LOCKED ROTOR AMPERE
LRAG LINEAR RETURN AIR GRILLE
LRG LINEAR RETURN GRILLE
LS LIGHT STANDARD
LSH LONG SLOTTED HOLE
LSD LINEAR SLOT DIFFUSER
LT LIQUID TIGHT
LTG LIGHTING
LV LOW VOLTAGE
LVL LEVEL
LWT LEAVING WATER TEMPERATURE
M
MAG MAGNETIC DOOR HOLD OPEN
MAINT MAINTENANCE
MAX MAXIMUM
MBH THOUSAND BTU/HOUR
MBP MAINTENANCE BYPASS PANEL
MCB MOLDED CASE BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILLS
MCP MOTOR CIRCUIT PROTECTOR
MD MANUAL DAMPER
MDF MEDIUM DENSITY FIBERBOARD
MDT MAIN DISTRIBUTION TERMINAL
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIL THOUSANDTHS OF AN INCH
MIL ST MILITARY STANDARD
MIN MINIMAL, MINUTE, MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MM MILLIMETER
MOD MOTOR OPERATED DAMPER
MPG MULTI-POINT GROUND
MTD MOUNTED
MTL METAL
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MV MANUAL VENT
MVA MEGAVOLT AMPERE
MVD MANUAL VOLUME DAMPER
I
IC INTERCOMMUNICATION, INTERCOM
IE INVERT ELEVATION
IN INCHES
INCAND INCANDESCENT
INCL INCLUDE
INDIC INDICATOR
INSUL INSULATED
INT INTERIOR
INV INVERT
ISMS INTEGRATED SECURITY MANAGEMENT SYSTEM REV
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:56 PM JST
RAB
G011
JST
ABBREVIATIONS - SHEET 2
08/31/2017
N
N NORTH, NEUTRAL
NA NOT APPLICABLE
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEG NEGATIVE
NEMA NATIONAL ELECTRICAL MANUFACTURERS' ASSOCIATION
NFHB NON-FREEZE HOSE BIB
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NG NATURAL GAS
NIC NOT IN CONTRACT
NK NECK
NO NUMBER OF DESIGNATION
N.O. NORMALLY OPEN
NOM NOMINAL
NTE NOT TO EXCEED
NTS NOT TO SCALE
O
OA OUTSIDE AIR
OAF OUTSIDE AIR FAN
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER, OVERFLOW DRAIN
ODP OPEN DRIP PROOF
OE OPEN END
OH OPPOSITE HAND, OVERHEAD
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
ORL OVERFLOW ROOF LEADER
OSA OUTSIDE SUPPLY AIR
OSCO OUTSIDE CLEANOUT
OVHD OVERHEAD
OZ OUNCES
P
P POLE, PAINT, PUMP
PABX PRIVATE AUTOMATIC BRANCH EXCHANGE
PART PARTITION
PB PULL BOX
PCF POUNDS PER CUBIC FOOT
PCHWR PRIMARY CHILLED WATER RETURN
PCHWS PRIMARY CHILLED WATER SUPPLY
PCMS POWER CONTROL MONITORING SYSTEM
PCS POWER CONDITIONING SYSTEM
PD PRESSURE DROP
PF POWER FACTOR
PFD PERFORATED FACE DIFFUSER
PFR PERFORATED FACE RETURN
PH ELECTRICAL PHASE
PI PRESSURE INDICATOR
PIU POWER INDUCTION UNIT
PL PLATE
PLBG PLUMBING
PLCS PLACES
PLYWD PLYWOOD
PM POWER MANHOLE
PMB POWER MIXING BOX
PNL PANEL, PANELBOARD
P.O.C. POINT OF CONNECTION
POS POSITIVE, POSITION
PP POWER POLE, PATCH PANEL
PREFAB PREFABRICATED
PRESS PRESSURE
PRMY PRIMARY
PRSR PRESSURIZATION
PROP PROPELLER
PRV PRESSURE REDUCING VALVE
PS PRESSURE SWITCH
PSF POUNDS PER SQ. FOOT
PSI POUNDS PER SQ. INCH
PSIA POUNDS PER SQ.IN. ABSOLUTE
PSIG POUNDS PER SQ.IN. GAUGE
PT PRESSURE TRANSMITTER, PRESSURE-TEMPERATURE PORT
PTAC PACKAGED TERMINAL AIR CONDITIONER
PVC POLYVINYL CHLORIDE, POINT OF VERTICAL CURVATURE
PVMT PAVEMENT
Q
QUA QUARTER
R
R RED, RISER, RADIATOR, RADIUS, REFRIGERANT
RA RETURN AIR, REMOTE ANNUNCIATOR
RACP REMOTE ACCESS CONTROL PANEL
RAD RADIUS
RAG RETURN AIR GRILLE
RAR RETURN AIR REGISTER
RB RUBBER BASE
RCP REINFORCED CONCRETE PIPE, REFLECTED CEILING PLAN
RD ROOF DRAIN
RDF RUBBER RAISED DISK FLOOR
RE RESIDENT ENGINEER
REBAR REINFORCING STEEL BAR
REC RECEPTACLE
REC'D RECEIVED
RECP RECEPTACLE
RECT RECTIFIER, RECEPTACLE
REF REFERENCE
REG REGISTER
REINF REINFORCEMENT, REINFORCED
REQ'D REQUIRED
RET RETURN
REV REVISION
RF RETURN FAN
RFI RADIO FREQUENCY INTERFERENCE
RG RETURN GRILLE
RGS RIGID GALVANIZED STEEL
RL RAIN LEADER
RM ROOM
RMH ROOF MOUNTED HOOD
RML RADAR MICROWAVE LINK
RMS ROOT MEAN SQUARE
RO REVERSE OSMOSIS
RP BP REDUCED PRESSURE BACKFLOW PREVENTER
RPM ROTATIONS PER MINUTE, REVOLUTIONS PER MINUTE
RPZ REDUCED PRESSURE ZONE
RQMTS REQUIREMENTS
RTN RETURN
RTU ROOF TOP UNIT
RV RELIEF VALVE
S
S SOUTH, STAIN COLOR, SANITARY
SA SUPPLY AIR
SAN SANITARY
SC SPIN IN COLLAR WITH VOLUME DAMPER, SENSIBLE COOLING
S.C. SOLID CORE
SCC SECURITY CONTROL CENTER
SCHED SCHEDULE
SCHWP SECONDARY CHILLED WATER PUMP
SCHWR SECONDARY CHILLED WATER RETURN
SCHWS SECONDARY CHILLED WATER SUPPLY
SCND SECONDARY
SCP SYSTEM CONTROL PANEL, SMOKE CONTROL PANEL
SD SPLITTER DAMPER STORM DRAIN, SMOKE DETECTOR
S.D. SUPPLY DIFFUSER
SEC SECONDARY
SECT SECTION
SENS SENSIBLE
SF SQUARE FEET
SG SUPPLY GRILLE
SGL SINGLE
SHDWN SHUT DOWN
SHLD SHIELDED
SHT SHEET
SIM SIMILAR
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS'
NATIONAL ASSOCIATION
SOV SHUT-OFF VALVE
SP STATIC PRESSURE(IN W.G.), SINGLE POLE, SUMP PUMP
SPEC SPECIFICATION
SPF STAIRWELL PRESSURIZATION FAN
SPST SINGLE POLE SINGLE THROW
SPT STATIC PRESSURE TRANSMITTER
SPVR SUPERVISORY CONDITION
SQ SQUARE
SQ.FT. SQUARE FOOT/FEET
SR SUPPLY REGISTER
SRG SIGNAL REFERENCE GRID
SS STAINLESS STEEL, SANITARY SEWER
S/S START-STOP
ST SHUNT TRIP
STD STANDARD
STGP SIGNAL TRANSPORT GROUND PLANE
STL STEEL
STP SHIELDED TWISTED PAIR
STRUCT STRUCTURAL
SUBJ SUBJUNCTION
SUSP SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWG SIDEWALL GRILLE
SWGR SWITCHGEAR
SWR SIDEWALL REGISTER
SWSI SINGLE WIDTH SINGLE INLET
SWSR SIDE WALL SUPPLY REGISTER
SYM SYMMETRICAL
SYS SYSTEM
T
T TRANSDUCER
T&B TOP AND BOTTOM
T&P TEMPERATURE AND PRESSURE
TB TERMINAL BOX, TERMINAL BOARD
TC TRIP COIL, TOTAL COOLING, TIME CLOCK
TD TIME DELAY, TRENCH DRAIN
TEF TOILET EXHAUST FAN
TEL TELEPHONE
TELCO TELEPHONE COMPANY
TEMP TEMPERATURE
TERM TERMINAL
TG TRANSFER GRILLE
THK THICK, THICKNESS
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS,T/S TOP OF STEEL
TOWB ATCT AND ATTACHED BASE BUILDING
TP TRAP PRIMER, TWISTER PAIR
TRBL TROUBLE CONDITION
TRACO TERMINAL RADAR APPROACH CONTROL BUILDING
TS TWO SPEED
TSP TOTAL STATIC PRESSURE, TRAP SEAL PRIMER
T^STAT THERMOSTAT
TT TEMPERATURE TRANSMITTER
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION, TEMPERING VALVE
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR (GFM)
TYP TYPICAL
TW TEMPERED WATER
U
UBC UNIFORM BUILDING CODE
UC UNDERCUT
UG UNDERGROUND
UGP UNDERGROUND POWER
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UNF UNFUSED
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UPC UNIFORM PLUMBING CODE
UPS,U UNINTERUPTIBLE POWER SUPPLY
UTIL UTILITY
V
V VOLT, VOLTAGE, VENT
VA VOLT AMPERE, VOICE ALARM
VAC VACUUM
VAV VARIABLE AIR VOLUME
VB VACUUM BREAKER
VCT VINYL COMPOSITE TILE
VD VOLUME DAMPER - MANUAL
VDT VIDEO DISPLAY TERMINAL
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY DRIVE
VM VOLTMETER
VPF VESTIBLE PRESSURIZATION FAN
VTR VENT THROUGH ROOF
W
W WEST, WIDTH, WATT
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN, WATER CLOSET, WALL COVERING
WCO WALL CLEANOUT
WG WATER GAUGE
WH WATER HEATER, WALL HEATER, WALL HYDRANT
WHA WATER HAMMER ARRESTER
WM WATT METER
WMS WIRE MESH SCREEN
WP SUBSCRIPT "WP" APPLIED TO ANY SYMBOL INDICATES
WEATHERPROOF NEMA TYPE 3R OR EQUIVALENT, UON
WPD WATER PRESSURE DROP
WSW WASHDOWN SUPPLYWATER
WT WATER TANK
WTR WATER
WWF WELDED WIRE FABRIC
X
X AUXILIARY RELAY
XFR TRANSFER
XFMR TRANSFORMER
XMTR TRANSMITTER
XDCR TRANSDUCER
Y
Y WYE
Y-D WYE DELTA
Z
Z IMPEDANCE
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
A
AXXX
AXXX
AXXX
AXXX
TITLE OF PLAN, SECTION OR DETAIL
* SCALE OR OTHER INFORMATION
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:57 PM JST
RAB
G015
JST
SYMBOL LEGEND
08/31/2017
GENERAL SYMBOL LEGEND:
SECTION CUT
SHEET NUMBER WHERE
SECTION IS LOCATED
DETAIL
SECTION LETTER
THIS SCALE REFERS TO FULL SIZE DRAWING
(22" X 34" DRAWING SHEET SIZE) AND IS
USED FOR SCALING AT FULL SIZE AND FOR
USING THE APPROPRIATE BAR SCALE WHEN
THE SHEET IS REDUCED IN SIZE.
GENERAL NOTES
1. FOR ALL ABBREVIATIONS REFERENCE DRAWINGS G010 & G011.
2. DO NOT SCALE DRAWINGS.
3. VERIFY FIELD CONDITIONS PRIOR TO COMMENCING EACH PORTION OF THE WORK.
ELEVATION
DETAIL TITLE
GRAPHIC SCALE
ARCHITECTURAL
GRAPHIC SCALE
ENGINEERING
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
DETAIL NUMBER
SHEET NUMBER WHERE
PLAN, SECTION OR DETAIL
IS LOCATED
ELEVATION NUMBER
SHEET NUMBER WHERE
ELEVATION IS LOCATED
8'4'2'0'
SCALE: 1/4"=1'-0"
40'20'10'0'
SCALE IN FEET*
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
GENERAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:57 PM JST
RAB
G040
JST
CONSTRUCTION COORDINATION NOTES
08/31/2017
CONSTRUCTION STAGING NOTES
THE FOLLOWING NOTES REPRESENT MANY OF THE MAJOR REQUIREMENTS STATED IN "DIVISION 1 - GENERAL REQUIREMENTS" OF THE SPECIFICATIONS. THESE NOTES PARAPHRASE OR SUPPLEMENT DIVISION 1 REQUIREMENTS AND ARE NOT INTENDED TO REPLACE DIVISION 1 REQUIREMENTS.
CONSTRUCTION ACCESS (VEHICLE, PEDESTRIAN AND DELIVERIES), CONTRACTOR'S PARKING, CONSTRUCTION OFFICES AND THE EXTENT/SIZE OF THE CONSTRUCTION STAGING AREA MUST BE COORDINATED WITH SITE PERSONNEL VIA THE FAA CONTRACTING OFFICERS REPRESENTATIVE.
A. CONSTRUCTION ACCESS
1. DELIVERIES SHALL BE SCHEDULED IN ADVANCE WITH THE FAA CONTRACTING OFFICERS REPRESENTATIVE AND AT TIMES OTHER THAN THE FAA EMPLOYEE SHIFT
CHANGES TO AVOID CONGESTION.
B. CONTRACTOR STAGING AREA AND PARKING
1. CONTRACTOR'S STAGING AND PERSONNEL PARKING IS LIMITED AND SHALL BE DETERMINED AT THE PRECONSTRUCTION CONFERENCE. CONTRACTOR SHALL
PROVIDE SIGNS AS NECESSARY TO RESERVE AN AREA FOR CONSTRUCTION PARKING ONLY.
2. UNLESS NOTIFIED OTHERWISE DURING THE PRE-CONSTRUCTION CONFERENCE, STAGING AREA SHALL ACCOMMODATE FAA COR TRAILER.
C. FAA SECURITY REQUIREMENTS
1. AN ADVANCE LIST OF THE CONTRACTOR'S PERSONNEL SHALL BE PROVIDED TO THE FAA CONTRACTING OFFICERS REPRESENTATIVE. CONTRACTOR SUPERINTENDENT IS REQUIRED TO OBTAIN AN FAA CONTRACTOR BADGE PRIOR TO THE START OF WORK. A FACILITY ACCESS CARD WILL BE ISSUED AND WILL ALLOW ACCESS TO THE PERIMETER GATE. CONTRACTOR TO COORDINATE WITH HIS SUBS AND EMPLOYEES THE ACCESS TO THE FACILITY. TEMPORARY SECURITY BADGES MAY BE ISSUED TO THOSE CONSTRUCTION PERSONNEL. CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONDUCT OF CONTRACTOR'S PERSONNEL ON SITE. CONTRACTOR VEHICLES SHALL BE IDENTIFIED AS SUCH. EACH CONSTRUCTION EMPLOYEE SHALL CHECK IN AND OUT UPON ENTERING AND LEAVING THE SITE.
2. THE BUILDING IS A SECURE AREA, AND CONSTRUCTION PERSONNEL SHALL REMAIN IN THE CONSTRUCTION AREAS. CONTRACTOR SHALL MINIMIZE INGRESS AND
EGRESS.
D. CONSTRUCTION MATERIAL STORAGE
1. STORAGE OF CONSTRUCTION MATERIALS AND TRAILERS ON THE SITE SHALL BE LIMITED TO THE CONSTRUCTION STAGING AREA. MATERIALS SHALL BE NEATLY STORED AND PROTECTED. A CONSTRUCTION FENCE SHALL BE PROVIDED AT THE DISCRETION OF THE FAA CONTRACTING OFFICERS REPRESENTATIVE.
CONTRACTOR SHALL NOT PERFORM ANY DIGGING WITHOUT PERMISSION FROM THE FAA CONTRACTING OFFICERS REPRESENTATIVE. BURIED CABLES AND OTHER
EXISTING UNDERGROUND UTILITIES MAY RUN THROUGH THE STAGING AREA AND ELSEWHERE.
E. CONSTRUCTION DEBRIS
1. ENCLOSED DUMPSTERS FOR DISPOSAL OF CONSTRUCTION DEBRIS SHALL BE PROVIDED BY THE CONTRACTOR WITHIN THE STAGING AREA. THE AREAS AROUND THE DUMPSTERS SHALL BE KEPT CLEAN AND FREE OF DEBRIS AND DUST DURING CONSTRUCTION. DEBRIS SHALL BE REMOVED BY THE CONTRACTOR IN A TIMELY MANNER.
2. ALL AREAS BELOW ATCT WITHIN 50 FEET OF THE TOWER SHAFT SHALL BE PROTECTED FROM FALLING DEBRIS.
F. DEMOLITION AND CONSTRUCTION HOURS
1. THE CONTRACTOR SHALL NOT INTERFERE WITH THE AIR TRAFFIC CONTROL FUNCTION OF THE FACILITY. DEMOLITION NOISE, CONSTRUCTION NOISE AND ALL WORK IN AREAS ADJACENT TO THE AIR TRAFFIC CONTROL FUNCTION MUST BE ACCOMPLISHED AFTER NORMAL OPERATING HOURS. COORDINATE NIGHT WORK AND OVERTIME CONSTRUCTION IN ADVANCE WITH THE FAA CONTRACTING OFFICERS REPRESENTATIVE.
2. SEE CONSTRUCTION SEQUENCE NOTES FOR FURTHER INFORMATION.
3. CONCRETE SAWING, GRINDING, CORE DRILLING, CONCRETE DEMOLITION AND ANCHOR DRILLING WILL BE ALLOWED ONLY AT PREARRANGED TIMES APPROVED
BY THE FAA CONTRACTING OFFICERS REPRESENTATIVE.
G. EQUIPMENT PROTECTION
1. EXISTING FAA AIR TRAFFIC COMPUTERS AND EQUIPMENT SHALL REMAIN OPERATIONAL THROUGHOUT THE DURATION OF THIS CONTRACT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTINUOUS PROTECTION OF THIS EQUIPMENT FROM PHYSICAL AND ELECTRICAL DAMAGE AS A RESULT OF INCIDENTAL OR ACCIDENTAL NEGLIGENCE SUCH AS, BUT NOT LIMITED TO, DISRUPTION OF POWER TO THE UNITS. INFORM THE FAA CONTRACTING OFFICERS REPRESENTATIVE IMMEDIATELY IF SUCH DAMAGE OR DISRUPTION OF POWER SHOULD OCCUR. THE LOSS OF THESE COMPUTERS AND EQUIPMENT FOR ANY AMOUNT OF TIME WILL JEOPARDIZE THE
SAFETY OF THE FLYING PUBLIC.
2. SHUTDOWNS, CUTOVERS AND ANY TEMPORARY PROVISIONS FOR PLUMBING, MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE ACCOMPLISHED AFTER NORMAL OPERATING HOURS. PREPARATORY WORK SHALL BE COMPLETED PRIOR TO SHUTDOWN. CUTOVER WORK SHALL BE SCHEDULED AND COORDINATED WITH THE FAA CONTRACTING OFFICERS REPRESENTATIVE A MINIMUM OF 10 WORKING DAYS IN ADVANCE OF THE SHUTDOWN OR CUTOVER.
3. WELDING EQUIPMENT SHALL NOT BE POWERED BY THE FACILITY ELECTRICAL SYSTEM. WELDING SHALL NOT BE PERMITTED IN FAA OCCUPIED AREA. CONTRACTOR SHALL COORDINATE WITH COR TO FIELD TEST GROUND FAULT CONDITIONS OF WELDING EQUIPMENT TO ASSURE THAT FIELD WELDING DOES NOT INTERFERE WITH
FAA RADIO FREQUENCIES.
H. CONSTRUCTION MATERIAL DELIVERIES
1. ALL DELIVERIES MUST BE COORDINATED THROUGH THE FAA CONTRACTING OFFICERS REPRESENTATIVE AND SCHEDULED WITH A MINIMUM OF 48 HOURS NOTICE TO
THE ATCT FACILITY.
2. THE ATCT ELEVATOR INTERIOR SHALL BE PROTECTED PRIOR TO DELIVERY OF ANY MATERIALS. ANY DAMAGE TO ELEVATOR OR ANY ACCESS WAYS SHALL BE REPAIRED
OR REPLACED AT CONTRACTOR'S COST.
3. MAXIMUM ELEVATOR CAPACITY IS 3500 LBS. DELIVERY OF ANY HEAVY OR BULKY MATERIALS WILL BE COORDINATED WITH COR. THIS MAIN SERVICE ELEVATOR SHALL BE WELL PROTECTED BEFORE CONSTRUCTION. TIMES OF ELEVATOR USE SHALL BE COORDINATED WITH THE COR BEFORE COMMENCING CONSTRUCTION.
I. STAGING AND STORAGE AREA
1. ON SITE CONSTRUCTION MATERIAL STAGING AREA WILL BE VERY LIMITED. COORDINATE WITH THE CONTRACTING OFFICERS REPRESENTATIVE FOR STAGING AND
STORAGE AREAS
CONSTRUCTION NOTES
1. FAA WILL COORDINATE PHASING PLAN WITH FACILITY TO MINIMIZE THE DISRUPTION OF OPERATIONS. THE CONTRACTOR SHALL USE THIS PHASING PLAN AND PROVIDE A COMPLETE AND COMPREHENSIVE SCHEDULE TO THE CONTRACTING OFFICERS REPRESENTATIVE FOR REVIEW AND APPROVAL BEFORE A NOTICE TO PROCEED IS ISSUED. SCHEDULE SHALL OUTLINE ALL PHASES OF THE WORK AND THEIR IMPACT ON THE OPERATION OF
THE FACILITY. SEE SPECIFICATION 01 10 00 FOR PRELIMINARY PHASING SCHEDULE.
2. SIGNIFICANT AMOUNTS OF WORK MUST BE COMPLETED AFTER NORMAL OPERATING HOURS.
3. CONSTRUCTION NOISE, DUST AND DEBRIS MUST NOT INTERFERE WITH OPERATION OF ATCT FACILITY.
MAINTAIN HEPA FILTRATION OF CONSTRUCTION AREA DURING ALL GENERAL CONSTRUCTION SEQUENCES.
4. CONTRACTOR SHALL USE VERY LOW VOC PAINTS AND COATINGS AND PROVIDE ADEQUATE MEASURES FOR VENTILATION TO MINIMIZE ODORS DURING PAINTING, CURING OF FRP RESINS AND OTHER CONSTRUCTION ACTIVITIES THAT HAVE THE POTENTIAL FOR STRONG ODORS. THE CONTRACTIN OFFICERS REPRESENTATIVE
SHALL APPROVE THE SYSTEM TO BE UTILIZED FOR VENTILATION PRIOR TO USE.
5. HVAC FILTERS SERVING THE CAB AND CABLE ACCESS LEVELS SHALL BE REPLACED AFTER EACH
CONSTRUCTION WORK PHASE WITH NEW MERV 10 FILTERS.
6. A MINIMUM OF FOUR (4) COMMERCIAL GRADE DEHUMIDIFIERS WILL BE REQUIRED FOR CABLE ACCESS LEVEL. SEE SPECIFICATION SECTION 23 84 15 AND 01 78 23 FOR ADDITIONAL INFORMATION. FLOOR GRATES SHALL BE BLOCKED OFF PRIOR TO CONSTRUCTION AND DURING THE ENTIRE DEHUMIDIFICATION PROCESS.
7. THE CONSTRUCTION OF THIS PROJECT MUST NOT INTERFERE WITH OPERATION OF THE AIR TRAFFIC CONTROL FUNCTION DURING NORMAL OPERATING HOURS. NORMAL HOURS OF OPERATION ARE STATED IN DIVISION 1
OF THE SPECIFICATIONS.
8. LOCKOUT AND TAG PROCEDURES MUST BE FOLLOWED AT ALL TIMES.
9. IF NECESSARY ALL ELECTRONIC EQUIPMENT CIRCUITS SHALL BE RELOCATED BY THE FAA. ALL OTHER BUILDING SYSTEMS CIRCUITS SHALL BE RELOCATED BY THE CONTRACTOR. COORDINATE WITH CONTRACTING OFFICERS
REPRESENTATIVE.
10. DO NOT PAINT OVER ANY FIRE DOOR LABEL.
11. REINSTALL ALL SMOKE/FIRE DETECTORS AS REQUIRED.
12. THE PURCHASE OF A 4-POINT WENNER PROBE WITH TRAINING FOR FAA STAFF/COR IS REQUIRED FOR THIS CONTRACT AS DESCRIBED IN SPECIFICATION SECTION 03 01 30, PARAGRAPH 2.6. EARLY PRE-CAST PANEL MATERIAL DATA COLLECTION SHALL ESTABLISH IN-SITU CONDITIONS AND PROPERTIES OF THE EXISTING CONCRETE, IT'S pH CHARACTERISTICS AND POTENTIAL LONG-TERM IMPACT OF THE REINFORCING STEEL WITHIN THE PANELS. TESTING SHOULD REMAIN UNOBTRUSIVE AND PERFORMED FROM THE INSIDE SURFACE OF THE PANELS WITHIN THE VICINITY OF THE CRACKING. SUBJECT WORK SHALL BE ACCOMPLISHED BY THIS HAND-HELD METER, MEASURING BOTH pH AND RH LEVELS WITHIN THE PANELS. THIS IS TO VERIFY THE PROPENSITY FOR REINFORCING STEEL CORROSION.
RESULTING DATA SHOULD PROVIDE SUFFICIENT QUALITY ASSURANCE OF THE PANEL'S LONG-TERM PERFORMANCE;
BUT ALSO CONFIRMING PROPER SELECTION OF THE FRP STRENGTHENING SYSTEM.
G
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
STRUCTURAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:57 PM JST
RAB
S000
JST
GENERAL NOTES
08/31/2017
A. GENERAL:
1. APPLICABLE CODES:
FLORIDA BUILDING CODE (FBC), 5TH EDITION
ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
AISC STEEL CONSTRUCTION MANUAL, 14TH EDITION
AMERICAN IRON & STEEL INSTITUTE, 2012 EDITION
ACI 318 LATEST EDITION BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE
2. DESIGN DEAD LOADS:
WALKWAY FLOOR 40 PSF
CAB FLOOR 100 PSF
DEAD LOAD ONLY INCLUDES SUPERIMPOSED LOADINGS, IT DOES NOT
INCLUDE THE SELF WEIGHT OF THE STRUCTURAL MEMBERS. SEE PLAN
FOR SIZING OF STRUCTURAL COMPONENTS.
3. WIND LOADS:
BASIC WIND SPEED 155 MPH
EXPOSURE CATEGORY C
BUILDING CATEGORY IV
INTERNAL PRESSURE COEFFICIENT, GCPi +/- 0.18
COMPONENTS AND CLADDING PRESSURES
SEE (E) SHEET S41 OF EXISTING DRAWINGS
4. DISCREPANCIES: CONTRACTOR SHALL VERIFY ALL DIMENSIONS,
CONDITIONS, AND ELEVATIONS AT JOB SITE AND BRING TO THE
ATTENTION OF THE FAA CONTRACTING OFFICER'S REPRESENTATIVE
ANY DISCREPANCIES.
5. OTHER TRADES: SEE EXISTING ARCHITECTURAL, ELECTRICAL, AND
MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF PIPE, VENT, DUCT, AND
OTHER OPENINGS AND DETAILS NOT SHOWN IN THESE STRUCTURAL
DRAWINGS. ALL DIMENSIONS ARE TO BE CHECKED AND VERIFIED WITH THE
ARCHITECTURAL DRAWINGS.
6. NO STRUCTURAL MEMBER SHALL BE CUT, NOTCHED, OR OTHERWISE
ALTERED UNLESS APPROVED IN WRITING BY THE COR.
C. STEEL CONSTRUCTION (CONT.):
8. GALVANIZING OF STRUCTURAL SHAPES AND FABRICATED PARTS SHALL BE DONE
IN ACCORDANCE WITH ASTM A123 AFTER FABRICATION. GALVANIZING OF THREADED
PARTS, BOLTS, NUTS, AND WASHERS SHALL BE DONE IN ACCORDANCE WITH ASTM
A153. UNLESS NOTED OTHERWISE, ALL EXPOSED STRUCTURAL STEEL SHALL BE
HOT-DIPPED GALVANIZED AFTER FABRICATION. ALL WELDED AND DAMAGED
GALVANIZED SURFACES SHALL BE REPAIRED PER SPECIFICATIONS.
9. SHOP PAINT ALL STRUCTURAL STEEL EXCEPT STEEL SURFACES EMBEDDED IN
CONCRETE, GALVANIZED SURFACES, BEARING SURFACES, SURFACES SCHEDULED
TO RECEIVE SPRAYED-ON FIREPROOFING, CONTACT SURFACES FOR ALL SLIP
CRITICAL BOLTED CONNECTIONS, OR SURFACES WITHIN 1/2 INCH OF THE TOE OF THE
WELDS PRIOR TO WELDING, INCLUDING SURFACES ON WHICH METAL DECKING OR
SHEAR STUDS ARE TO BE WELDED. TOUCH-UP PAINT ALL AREAS SUBJECT TO PAINT
ALTERATION AFTER ERECTION. PROVIDE A ONE-COAT SHOP-APPLIED ZINC-RICH
PAINTING SYSTEM COMPLYING WITH STEEL STRUCTURES PAINTING COUNCIL (SSPC)
PAINTING SYSTEM SPECIFICATION NUMBER 12.01.
10. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM
SPECIFICATIONS UNLESS NOTED OTHERWISE:
STRUCTURAL STEEL WIDE FLANGES A992 FY = 50 KSI
STEEL ANGLES AND PLATES A36 FY = 36 KSI
STEEL TUBING A500 GRADE B FY = 46 KSI
STEEL CHANNELS A572 GRADE 50 FY = 50 KSI
11. DRILLED IN CONCRETE ANCHORS SHALL BE GALVANIZED OR STAINLESS
HILTI KWIK BOLTS OR APPROVED EQUIVALENT AS APPROVED BY THE FAA
CONTRACTING OFFICER'S REPRESENTATIVE.
12. STRUCTURAL STEEL FABRICATOR SHALL REVIEW ALL CONNECTIONS SHOWN ON
THESE DRAWINGS FOR SHEAR CAPACITY, MOMENT CAPACITY, CONSTRUCTION
TOLERANCES, AND ERECTION TOLERANCES. CONNECTIONS SHALL DEVELOP THE
REQUIRED MOMENT AND SHEAR CAPACITY, AND SHALL BE DETAILED PER THE AISC
SEISMIC PROVISIONS.
13. ALL GLASS MUST BE PROTECTED FROM WELD SPLATTER. ANY GLASS MARRED BY
WELD SPLATTER MUST BE REPLACED.
STRUCTURAL GENERAL NOTES:
D. STRUCTURAL COLD-FORMED STEEL
1. ALL GALVANIZED TRACK, BRIDGING, END CLOSURES AND ACCESSORIES SHALL
BE FORMED FROM STEEL THAT CONFORMS TO THE REQUIREMENTS OF ASTM
A1003, GRADE ST33H, WITH A MINIMUM YIELD STRENGTH OF 33,000 PSI.
A. COLD-FORMED STEEL CONSTRUCTION SHALL CONFORM WITH THE AISI
SPECIFICATIONS, LATEST EDITION.
B. COLD-FORMED STEEL MEMBERS SHALL BE GALVANIZED WITH G90
COATING.
C. FIELD CUTTING OF COLD-FORMED STEEL MEMBERS SHALL BE
COMPLETED BY SAWING OR SHEARING. TORCH CUTTING IS NOT
PERMITTED.
2. ANY SUBSTITUTIONS MUST BE APPROVED BY THE CONTRACTING OFFICER'S
REPRESENTATIVE.
3. WELDING SHALL CONFORM TO AWS D1.1, AWS D1.3 AND AISI MANUAL SECTION 4.2.
4. WELDING SHALL BE BY FUSION WELDING UTILIZING ELECTRODES WITH ASTM
CLASSIFICATION E60. ALL WELDERS SHALL BE QUALIFIED BY TESTING IN
ACCORDANCE WITH THE “CODE FOR WELDING IN BUILDING CONSTRUCTION”,
AWS D.1, 1-81 OF THE AMERICAN WELDING SOCIETY.
5. MILL CERTIFICATION OF THE STEEL PROPERTIES SHALL BE REQUIRED. ALL
STEEL SHALL BE OF DOMESTIC MANUFACTURE.
B. ERECTION:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGN AND PROVISION OF ALL
TEMPORARY GUYS, BRACING AND OTHER SUPPORTS AS NEEDED TO SAFELY
RESIST ALL LOADS TO WHICH STRUCTURE MAY BE SUBJECTED, INCLUDING
LOADS FROM ERECTION EQUIPMENT AND OPERATIONS, AND ALL WIND OR
SEISMIC FORCES COMPARABLE IN INTENSITY FOR WHICH STRUCTURE WAS
DESIGNED. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATE LATERAL SUPPORT FOR TOWER DURING CONSTRUCTION UNTIL
ALL STRUCTURAL ELEMENTS HAVE BEEN ERECTED AND CONNECTED PER
DRAWINGS.
C. STEEL CONSTRUCTION
1. SUBMIT SHOP AND ERECTION DRAWINGS FOR ALL STRUCTURAL STEEL
WORK. DO NOT BEGIN FABRICATION UNTIL THE SHOP DRAWINGS HAVE
BEEN APPROVED BY THE CONTRACTING OFFICER'S REPRESENTATIVE.
2. CONTRACTOR SHALL REVIEW ALL CONTRACT DRAWINGS FOR
MISCELLANEOUS STEEL.
3. SPLICING OF STRUCTURAL MEMBERS OTHER THAN INDICATED ON THE
DRAWINGS SHALL NOT BE PERMITTED WITHOUT PRIOR APPROVAL BY THE
CONTRACTING OFFICER'S REPRESENTATIVE.
4. ALL WELDING AND HIGH STRENGTH BOLTING MUST BE INSPECTED BY AN
FAA APPROVED QUALIFIED TESTING LABORATORY. ALL WELDING WILL BE
INSPECTED IN ACCORDANCE WITH THE AWS STRUCTURAL WELDING CODE
BY AN INSPECTOR CERTIFIED IN ACCORDANCE WITH THE PROVISIONS OF
AWS D1.1. SEE SPECIFICATIONS FOR MORE INFORMATION.
5. ALL SHOP AND FIELD WELDING SHALL BE PERFORMED ONLY BY WELDERS
QUALIFIED PER AWS D1.1 STRUCTURAL WELDING CODE - STEEL. ALL
WELDING SHALL CONFIRM TO AWS D1.1, LATEST EDITION. MINIMUM WELDS
SHALL BE CONTINUOUS 3/16 INCH FILLET UNLESS NOTED OTHERWISE.
ELECTRODES SHALL BE LOW HYDROGEN E70XX. EACH WELDER SHALL BE
ASSIGNED AN IDENTIFYING MARK. ALL WELDS EXCEPT 5/16 INCH AND
SMALLER FILLET WELDS SHALL BE PERMANENTLY MARKED WITH THE
WELDER'S IDENTIFYING MARK. THOSE WELDERS PRODUCING
UNSATISFACTORY WELDING, EVEN THOUGH THEY HAVE PASSED
QUALIFICATION TESTS, SHALL BE IMMEDIATELY RECERTIFIED OR
REPLACED WITH QUALIFIED WELDERS. .
6. BOLTS: ALL BOLTS FOR STRUCTURAL CONNECTIONS ARE HIGH-STRENGTH
BOLTS PER ASTM A325. ALL HIGH-STRENGTH BOLTS SHALL HAVE DIRECT
TENSION INDICATOR BOLTS. ALL OTHER BOLTS SHALL BE ASTM A307 AND
SHALL BE PROVIDED WITH WASHERS UNDER NUTS. ALL STRUCTURAL
BOLTS SHALL BE OF SUFFICIENT LENGTH TO EXTEND AT LEAST 2 THREADS
BEYOND THE STRUCTURE WHEN FULLY TIGHTENED.
7. UNLESS NOTED OTHERWISE ANCHOR BOLTS SHALL CONFORM TO A307.
PROTECT BOLTS FROM DAMAGE DURING CONSTRUCTION.
E. FIBER-REINFORCED POLYMERS (FRP) (CONT.):
6. ALL CRACKS WHICH ARE WIDER THAN 0.010 IN SHALL BE PRESSURE INJECTED
WITH EPOXY PER ACI 224.1R PRIOR TO FRP INSTALLATION.
7. UPON COMPLETION OF THOROUGHLY PREPPING/CLEANING CONCRETE
SURFACES, MITIGATING ANTI-CORROSIVE INHIBITOR, COMPATIBLE WITH FRP
LAMINATE SYSTEM, SHALL BE APPLIED PRIOR TO LAMINATION IN ACCORDANCE
WITH THE MANUFACTURER'S SPECIFICATIONS. ALTERNATIVELY, THIS INHIBITOR
MAY BE AN EPOXY RESIN MATRIX ADDITIVE. FRP LAMINATE MANUFACTURER/
SUPPLIER TO SPECIFY INHIBITOR REQUIREMENTS WITHIN THEIR SHOP
DRAWINGS SUBMITTAL.
8. ALL LAITANCE, DUST, DIRT, OIL, CURING COMPOUND, EXISTING COATINGS, AND
ANY OTHER MATTER THAT COULD INTERFERE WITH THE BOND OF THE FRP
SYSTEM TO THE CONCRETE SHALL BE REMOVED.
9. THE CONCRETE SURFACE SHALL BE PREPARED TO THE MINIMUM CONCRETE
SURFACE PROFILE (CSP) 3 AS DEFINED BY ICRI SURFACE PROFILE CHIPS.
10. LOCALIZED OUT OF PLANE VARIATIONS (INCLUDING FORM LINES) SHOULD NOT
EXCEED 1/32 OF AN INCH OR THE TOLERANCE SET FORTH BY THE FRP
MANUFACTURER. LOCALIZED OUT OF PLANE VARIATIONS CAN BE REMOVED
BY GRINDING OR WATER BLASTING. BUG HOLES AND SMALL VOIDS SHALL BE
FILLED WITH RESIN BASED PUTTY.
11. SURFACE SHALL BE COATED WITH A CORROSIVE INHIBITOR SUCH AS SIKA
FERROGARD 903 OR APPROVED EQUAL.
12. MIXING OF RESINS AND PLACEMENT OF SYSTEM SHALL BE PER THE
REQUIREMENTS OF THE FRP MANUFACTURER.
13. REPORTS SHALL BE PROVIDED TO THE COR INDICATING THE MINIMUM
INSPECTION AND EVALUATION REQUIREMENTS OF ACI 440.2R CHAPTER 7 HAVE
BEEN PERFORMED AND MET.
14. BASIS OF DESIGN IS SIKA WRAP HEX 103C FIBER (550 KSI, 0.04 IN THICK) TO BE
USED WITH SIKA CARBODUR ADHESIVE RESIN. EQUIVALENT PRODUCT MAY BE
SUBMITTED FOR COR APPROVAL.
E. FIBER-REINFORCED POLYMERS (FRP)
1. ALL FRP INSTALLATIONS SHALL FOLLOW THE MANUFACTURER’S
REQUIREMENTS AND ACI 440.2R-08 AT A MINIMUM.
2. ALL PRODUCTS SHALL BE STORED PER MANUFACTURER'S RECOMMENDED
STANDARDS, AND MSDS SHEETS FOR ALL PRODUCTS SHALL BE PROVIDED
ON SITE WITH ASSOCIATED MATERIALS.
3. THE FRP INSTALLATION CONTRACTOR SHOULD DEMONSTRATE COMPETENCY
FOR FRP INSTALLATION AND CONTRACTOR SHALL PROVIDE STATEMENTS OF A
MINIMUM OF FIVE PRIOR PROJECTS WHERE THEY PARTICIPATED IN THE
INSTALLATION OF FRP SYSTEMS.
4. FRP CONCRETE STRENGTHENING SHALL NOT TAKE PLACE IF THE CONCRETE
SURFACE IS BELOW 40 DEGREES FAHRENHEIT OR IF THE CONCRETE SURFACE
IS DAMP.
5. ALL SUBSTRATE SHALL BE PREPARED AND REPAIRED AS NECESSARY AS
SPECIFIED IN ACI 546R AND ICRI 03730. THE CONTRACTOR IS RESPONSIBLE
TO CONTACT THE FRP MANUFACTURER PRIOR TO CONCRETE REPAIR TO
CONFIRM THAT ALL REPAIR MATERIALS ARE COMPATIBLE WITH THE FRP
SYSTEM.
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
1 2
A
B
W33X130
W X9 4 W X9
W27X146
W X4
W X4
W X4
W X1
W X1
W27X94
W X1
W27X94W27X94
W X8
W X1
W33X130
W X4
W X4
W X5
W X1
W8X18 W8X18 W8X18 W8X18 W8X18
W8X18 W8X18 W8X18 W8X18 W8X18
W8X18 W8X18 W8X18 W8X18 W8X18
W8X18 W8X18 W8X18W8X18
W 8X
W 8X
W 8X
W24X117
W18X50
W24X117
W18X40
W 8X
W 8X
W18X46
W18X40
W18X40
W18X46
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W 8X
W24X55W14X22
W2 4X
W1 4X
W24X55 W14X22
W1 4X
W2
4X
W27X94W27X94
W X9
W X9
T
T1
T
W
W
W
W
TT T1
T1 T T
T1
T
T
W
W
W
W8 X1
8 W8X18
W8 X1 8W8X18W8X24 W8 X2
W8X24W8 X2
TS 6X6X1/4 COLUMN ABOVE 2'-0"
FROM OUTSIDE FACE OF PRECAST
PANELS (TYP. 28 PLACES)
A S100
( 61' - 8" )
(6 1' -8
L3X3X1/4 (TYP.
16 PLACES)
TS 6X6X3/8
COLUMN
ABOVE (TYP.)
TS 8X6X3/8
COLUMN
ABOVE (TYP.
4 PLACES)
TS 14X14
COLUMN
ABOVE (TYP.
4 PLACES)
TS 10X6X1/2
COLUMN
ABOVE (TYP.)
( 1' - 0" ) ( 6' - 0" ) (TYP.)
(TYP.)
PRECAST SUPPORT
LOCATIONS FOR PANEL T
PRECAST CONCRETE
PANELS, SEE S30
(TY
P.)
3 A T (
4'- 8")
0"
W
EDGE OF SLAB
W8X18
( 6' - 8" )(TYP.) PRECAST SUPPORT
LOCATIONS FOR PANEL T1( 10' - 2" )(TYP.)
TS 4X4X3/8 "X"
BRACING ABOVE,
THIS BAY ONLY
W8X35
W8X35
TS 4X4X3/8
BRACING
ABOVE
TS 4X4X3/8
BRACING ABOVE
2W16X67
TS 6X6X3/8
BRACING
ABOVE
2W16X67
2W16X67 TS 6X6X3/8
BRACING
ABOVE
TS 6X6X3/8
BRACING
ABOVE
TS 4X4X3/8
BRACING
ABOVE
TS 6X6X3/8
BRACING
ABOVE
W8X35
W8X35
2W16X67
TS 4X4X3/8
BRACING
ABOVE
W 8X
W 8X
W 8X
W8X10
PR
EC
AS
T S
UP
PO
RT
LO
CA
TIO
N
FO
R
PA
NE
L W
CLOSE OFF FLOOR GRATES PRIOR TO
CONSTRUCTION AND DEHUMIDIFICATION
PROCESS. REFER TO GENERAL
CONSTRUCTION COORDINATION NOTES
SHEET G040 AND SPECIFICATIONS
SECTION 23 84 15 FOR ADDITIONAL
INFORMATION (TYP.)
NOTE 6
SEE NOTES 5
AND 7, TYP 2
PER LONG SIDE
OF TOWER
NOTE 4
TYP
SEE NOTES 5
AND 7, TYP 1
PER ANGLED SIDE
OF TOWER
SEE NOTES 5
AND 7, TYP
AT ALL CORNERS
T
N
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
STRUCTURAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:58 PM JST
RAB
S001
JST
CABLE ACCESS FRAMING PLAN
08/31/2017SCALE: 1/4" = 1'-0"S001
1 CABLE ACCESS (LEVEL-24)
8'4'2'0'
SCALE: 1/4"=1'-0"
NOTES:
LEGEND:
PRECAST PANEL DESIGNATIONS
SEE S101
1. ALL EXISTING STEEL MEMBERS ARE SHOWN FOR INFORMATION ONLY.
CONTRACTOR SHOULD FIELD VERIFY ALL DIMENSIONS INCLUDING STEEL
AND CONCRETE SIZES PRIOR TO FABRICATION AND ANY FIELD WORK.
2. ALL NEW STEEL MEMBERS AND CONNECTIONS SHALL RECEIVE
CORROSION PROTECTION.
3. REPAIR DAMAGED SPRAY-ON FIREPROOFING THROUGHOUT. IN ADDITION, NEW
STRUCTURAL STEEL MEMBERS SHALL BE PROPERLY COATED WITH MATCHING
SPRAY-ON FIREPROOFING.
4. AS PART OF THE PRECAST CONCRETE FRP REPAIRS, REPLACE ANCHORS FOR
CAB WASHDOWN PIPING WITH STAINLESS STEEL EPOXY ANCHORS TO MATCH
EXISTING, HAS-R 304 SS OR APPROVED EQUAL. CUT EXISTING BOLTS DOWN TO
FLUSH WITH CONCRETE SURFACE AND COAT WITH ZINC-RICH PRIMER COMPATIBLE
WITH FRP REPAIRS. NEW ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S
RECOMMENDATIONS INCLUDING MINIMUM SPACING REQUIREMENTS.
5. ALL JOINT SEALANTS BETWEEN PRECAST PANELS ON THE CABLE ACCESS LEVEL
WILL BE REPLACED. SEE DETAILS ON DRAWINGS S102 AND SPECIFICATIONS FOR
INFORMATION.
6. AS PART OF THE PRECAST CONCRETE FRP REPAIRS, ENTIRE CONCRETE
SURFACE OF PRECAST PANELS ON THE CABLE ACCESS LEVEL SHALL BE
COATED. SEE A/S101 SPECIFICATION FOR FURTHER INFORMATION.
7. AFTER FRP REPAIRS, INSTALLATION OF JOINT SEALANTS, AND COATING OF
PRECAST PANELS, SHEET METAL FLASHING SHALL BE INSTALLED OVER EACH
JOINT. SEE S102 FOR DETAILS AND INFORMATION.
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
1 2
A
B
A S100
TS
8X 6X 3/
TS
8X 6X 3/
TS8X6X3/8
TS8X6X3/8
TS
8X 6X 3/
TS
8X 6X 3/
TS8X6X3/8
TS8X6X3/8
TS
8X 6X 3/8
TS8X6X3/8
TS
8X
6X 3/8
TS 6X6X1/4
COLUMN BELOW
(TYP. 56 PLACES)
TS
8X 6X 3/8
TS8X6X3/8
TS
8X
6X 3/8
TS8X6X3/8
C15X33.9
C15X33.9
C X3 3.
C1 5X
.9
C X3 3.
C1 5X .9
C15X33.9
C15X33.9
TS8X4X1/4
TS8X4X1/4
TS
8X 4X 1/4
TS
8X 4X 1/
TS
8X 4X 1/
TS
8X
4X 1/4
TS8X4X1/4
TS8X4X1/4 TS8X4X5/16
TS
8X 4X 5/
TS8X4X5/16
TS
8X 4X 5/
TS5X3X3/16
TS
5X 3X 3/
TS5X3X3/16
TS
5X 3X 3/
TS8X4X5/16 TS
8X
4X 5/1
TS8X4X5/16TS
8X 4X 5/1
TS5X3X3/16 TS
5X
3X 3/1
TS
5X 3X 3/1
6 TS5X3X3/16
W14X22W10X12
W X9
W14X22W10X12
W X3
W X1
W X1
W X1
W X1
W10X12W8X10
W X3
W10X12W8X10
( 4" )
EDGE OF SLAB
TUBES SUPPORTING PRECAST
STOP SHORT 4" OF COL. LINE (TYP.)
BUILT-UP
14X14 COL.
(4 PLACES)
( 57' - 8" )
(5 7' -8
S101
NEW BENT C6X13 WELDED
TO PERIMETER TUBE
SECTIONS, TYP. AT
CORNERS SEE 5/S101
TS10X6X1/2 COL BELOW,
TS8X6X4X1/2 MULLIONS
ABOVE (TYP. 16 PLACES)
BRACING
BELOW (TYP.)
TS8X6X3/8
COL BELOW
(TYP. 4 PLACES)
"X" BRACING BELOW
THIS BAY ONLY
L5X5X3/8 BRACING
BELOW (TYP.)
W4X13 EMBEDDED
IN CONC SLAB
(TYP. 8 PLACES)
TS4X4X1/4 ELEVATION
VARIES (TYP. 16 PLACES)
NEW 2-C6X13 BACK
TO BACK AT EACH
COLUMN, TYP. EA. SIDE
OF TOWER SEE S100
NOTES 4
AND 5
NOTE 6
NEW 2-C6X13 BACK
TO BACK AT EACH
COLUMN, TYP. EA.
SIDE OF TOWER SEE S100
N
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
STRUCTURAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:5
PM
9/18/2017 5:05:59 PM JST
RAB
S002
JST
CAB LEVEL FRAMING PLAN
08/31/2017SCALE: 1/4" = 1'-0"S002
1 CAB LEVEL (LEVEL-25)
NOTES:
8'4'2'0'
SCALE: 1/4"=1'-0"
1. ALL EXISTING STEEL MEMBERS ARE SHOWN FOR INFORMATION ONLY.
CONTRACTOR SHOULD FIELD VERIFY ALL DIMENSIONS INCLUDING STEEL
AND CONCRETE SIZES PRIOR TO FABRICATION AND ANY FIELD WORK.
2. ALL NEW STEEL MEMBERS AND CONNECTIONS SHALL RECEIVE
CORROSION PROTECTION.
3. REPAIR DAMAGED SPRAY-ON FIREPROOFING THROUGHOUT. IN ADDITION, NEW
STRUCTURAL STEEL MEMBERS SHALL BE PROPERLY COATED WITH MATCHING
SPRAY-ON FIREPROOFING.
4. CLEAN AND RESEAL CONCRETE CAB CATWALK SURFACE WITH WATERPROOF
DECK COATING. SEE SECTION 1/S100 AND SPECIFICATIONS FOR MORE
INFORMATION ON COATING AND EXPANSION JOINTS. ASSURE THAT NEW
COATING ALLOWS FOR DRAINAGE OF CATWALK TO EXISTING DRAINS. CLEAN
OUT EXISTING DRAINS AND DRAINLINES ON CATWALK AFTER INSTALLATION OF
NEW COATING.
5. WIRE BRUSH, CLEAN, AND COAT EXPOSED WEATHERHEAD PIPE ELBOWS ON
CATWALK WITH ZINC RICH PRIMER AND TOP COAT. SEE SPECIFICATIONS FOR
FURTHER INFORMATION.
6. WIRE BRUSH, CLEAN, AND COAT AREAS OF DAMAGED METAL PANELS ADJACENT
TO CATWALK WITH ZINC RICH PRIMER AND TOP COAT. SEE SPECIFICATIONS FOR
FURTHER INFORMATION.
EOB
R
S A
SIONA N G
INE
L E
T SBA
No. 44228
ER
PROF ES
STATE OF
EXIST.
PRECAST PANEL T
SEE 1/S101
EXIST.
PRECAST PANEL AG
EXIST. W27
EXIST. W8
EXIST. W33
EXIST. W8
EXIST. PRECAST PANEL
CONNECTION
TO STRUCTURE
( 4' - 10" )( 4' - 0" )( 3" )( 1' - 11" )
W.P.
(1 0"
EXIST. C15
EXIST. 3 1/4"
CONC. ON 3" DECK
EXIST. L5X5X3/8
EXIST. CONC.
TOPPING
CABLE
ACCESS LEVEL T.O.S.
EL. 287'-0 3/4"
WALKWAY.
EL. 294'-3 3/4" EL. 293'-9 1/2"
CAB FLOOR T.O.S.
EL. 299'-6 3/4"
EL. 300'-0"(5
1/ 4"
EXIST. W16
EXIST.
TS 10X6
COLUMN
3 1/4" CONC.
ON 2" DECK
EL. 296'-8"( 6" )
S100
S100
S100
EXIST. W18
EXIST. C8
SLAB STOPS AT
COLUMN FACE
AT STAIRS
POUR STOP
TO FORM CURB
EXIST.
TS8X6
EL. 300'-0"
EL. 302'-7"
( 4" )
EXIST. CONC. SLAB
ON STEEL DECK
EXIST. W14
EXIST.
TS 4X4
BRACING
EXIST. TS 4X4X3/16
ELEVATION VARIES
NEW 2-C6X13 BACK TO
BACK BRACE AT EACH
COL.
EXIST. TS5
EXIST. TS8
EXIST.
TS8
EXIST. TS8
EXIST
TS6X6
EXIST. TS8
EXIST
TS 6X6
B S100
SEE NOTE 6
ON S002
SEE DETAIL 6/S101
AT CORNERS
( 1" )
EXIST. 4" DIA. PIPE
EXTRA STRONG
STAINLESS STEEL
AT 6'-0" O.C. MAX
EXIST PIPE 8" EXTRA STRONG
STAINLESS STEEL POST
EL. 296'-8"
3/4" CHAMFER EXIST. PRECAST
PANEL CONNECTION
BY PRECASTER
EXIST. TS 8X6
EXIST. TS 6X6 POST
PRECAST PANEL
REMOVE FIREPROOFING AND
CLEAN COLUMN BEFORE WELDING3/16
NEW 3/8"x4"x0'-7" LG SHEAR
PLATE ALIGNED WITH CONCRETE
SLAB BEHIND COLUMN
NEW (2) 5/8"Ø A325 BOLTS IN FIELD
DRILLED 11/16"Ø HOLES AT 3" O.C.
NEW 2-C6X13 BACK
TO BACK BRACE
EXIST. 1/2"
CAP PLATE
EXIST. C15x33.9
( 2 1/2" )
EXIST.
L3x3x1/4
NEW CONCRETE RESURFACING,
SEE SPECS. FOR MORE INFO.
AFTER CONCRETE RESURFACING,
CLEAN AND DRY EXISTING PANELS.
INSTALL NEW PANELS DIRECTLY
OVER EXISTING. SEE SPECS.
EXIST. 2" INSULATED
METAL PANEL
(5
W.P.
EXIST. TS 6X6
POST
EXIST.
TS 8X6
EXIST.
L5X5X3/8
EXIST. EMBED AND
CONNECTIONS
PER PRECAST MFR
EXIST. 2" X 1" CONTINUOUS HALF
ROD STAINLESS STEEL BAR
EXIST. STAINLESS STEEL
EMBED AT 4'-0" O.C.
BY PRECAST MFR
3/16
REMOVE FIREPROOFING
AND CLEAN BEAM
BEFORE WELDING
NEW 2-C6X13 BACK
TO BACK BRACE
S100
NEW 3/8"x4"x0'-7"
LG SHEAR PLATE
NEW (2) 5/8"Ø A325
BOLTS IN FIELD DRILLED
11/16"Ø HOLES AT 3" O.C.
EXIST.
PRECAST
PANEL
(5 1/ 4"
( 1' - 5" )( 8" )
EXIST.
PRECAST PANEL AG
EXIST. C6X8X1'-7" LONG
PRECAST SUPPORT
POSTCL
EXIST. W33
EXIST.
TS6X6
POST
EXIST. W6X12X10"
LONG AT EACH
PRECAST PANEL
SUPPORT
(2 PER PANEL)
EXIST. L6X4X3/8X6" LG
( 6" )
( 1" )
EXIST. EMBED AND
CONNECTIONS
PER PRECAST MFR
( 1" )
BEAMCL
EXIST. EMBED AND
CONNECTIONS
PER PRECAST MFR
EXIST. EMBED AND
CONNECTIONS
PER PRECAST MFR
(3 /4
S100
EXIST.
PRECAST PANEL
NEW 20 GAUGE G90 GALVANIZED
COLD-FORMED STEEL BENT PLATE
AROUND ENTIRE PERIMETER
SEALED WEATHER TIGHT
FIELD DRILL 11/16"x 1 9/16"
LSH FOR 5/8"Ø A325
BOLT SPACED AT 24" O.C.
TIGHTEN BOLT TO
SNUG TIGHT
FACTORY APPLIED
TRAFFIC GRADE GRAY
SILICON FACE
2" 2"
2" 2"
PRE-COMPRESSED IMPREGNATED
OPEN CELL FOAM SEALED BY FIELD
APPLIED 2-PART EPOXY ADHESIVE
PRESSURE FIT POLYURETHANE
FOAM EXPANSION JOINT5"
3/ 4"
1/2"Ø HILTI HAS-E RODSW/
2 3/4" EMBED. IN HIT-HY 200
ADHESIVE OR EQUAL
SPACED AT 24" O.C.
*VERIFY DIMENSION IN FIELD
PROVIDE NYLON
WASHER ABOVE
PLATE
NEW L5x5x1/2x0'-8"
SPACED AMIN. OF 8"
FROM EXIST. FIELD
INSTALLED PLATE
3/16 5
REMOVE FIREPROOFING AND
CLEAN BEAM BEFORE WELDING
EXIST. FIELD
INSTALLED PLATE
NEW (2) 1/2"Ø HILTI HAS-E RODS
AT 5" O.C. W/ 4 1/2" EMBED. IN
HIT-HY 200 ADHESIVE OR EQUAL
NEW 2-C6X13 BACK
TO BACK BRACE
NEW (2) 5/8"Ø A325 BOLTS IN FIELD
DRILLED 11/16"Ø HOLES AT 3" O.C.
NEW 3/8"x4"x0'-7"
LG SHEAR PLATE
EXIST.
TS 6X6 POST
EXIST.
TS 8X6
EXIST. 1/2"
CAP PLATE
EXIST.
PRECAST
PANEL
CHECKED
DESIGNED DATE
H
G
F
E
D
C
B
A
7 6 5 4 3 2 1
H
G
F
E
D
C
B
A
8 7 6 5 4 3 2 1
DRAWN
APPROVED BY
JCNISSUED BY
SUBMITTED BY
DRAWING NO
SCALES SHOWN FOR 22" X 34" SHEET. ADJUST SCALE FOR OTHER SIZES
REVIEWED BY
MIA-D-ATCT-
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
AIRPORT TRAFFIC CONTROL TOWER
PRECAST PANEL REPAIR
EASTERN SERVICE AREA ATLANTA, GEORGIA
MIAMI FL(MIAMI INTERNATIONAL AIRPORT)
PROJECT/SYSTEM ENGINEER ENGINEERING MANAGER
REV APPROVED
DATE
REDLINE
DATEDESCRIPTION JCN APVD
PUBLIC AVAILABILITY TO BE DETERMINED UNDER 5 USC 552
FOR OFFICIAL USE ONLY
STRUCTURAL
ATLANTA TERMINAL
ENGINEERING
CENTERW|W PROJECT NUMBER 216103
5901 Peachtree Dunwoody Road| Bldg C| Suite 515 Atlanta, Georgia 30328-6055 phone 678.320.1888 | fax 770.522.8115 wileywilson.com
1600271
JONATHAN S. KREINER VINCENT L. WILLIAMS
9/ /2 5:
:0
PM
9/18/2017 5:06:01 PM JST
RAB
S100
JST
SECTIONS AND DETAILS
08/31/2017
SCALE: 1/2" = 1'-0"S100
A SECTION
SCALE: 1" = 1'-0"S100
1 DETAIL
SCALE: 1" = 1'-0"S100
2 DETAIL
SCALE: 1" = 1'-0"S100
3 DETAIL
8'4'2'0'
SCALE: 1/4"=1'-0"
2'1'6"0'
SCALE: 1"=1'-0"
18"1'6"0'
SCALE: 1-1/2"=1'-0"
SCALE: 1 1/2" = 1'-0"S100