Mechanical.pdf

PDF 2 MB Posted

Attached to
Tax Collector Interior Renovations and Restoration
Solicitation number
25-B-127LL
Issued by
Volusia County, Florida

About this file

This file contains mechanical drawings and specifications for the Volusia County Tax Collector's interior renovation project at the Thomas C Kelley Administration Center in DeLand, Florida. The mechanical documentation includes a comprehensive legend of HVAC abbreviations and symbols, demolition plans for the first level, new work plans with equipment schedules, and detailed installation specifications. The project scope encompasses removal of existing HVAC equipment including chilled water piping and controls, and installation of new mechanical systems including five parallel fan-powered terminal units (PTU-1.1 through PTU-1.5) with capacities ranging from 950 to 2,735 CFM, three variable air volume (VAV) boxes, supply and return ductwork with various insulation R-values, thermostats, and associated controls and sensors. The renovation affects approximately 6,766 square feet across multiple office spaces, break rooms, and support areas on the first level. All existing equipment and materials removed under the contract shall remain the property of the owner, and the contractor must submit removal lists and coordinate with other trades. Critical demolition requirements include careful removal procedures without dropping equipment, identification and verification of all existing ducts and pipes prior to removal, proper drainage of piping sections, and maintenance of a negative pressure environment during construction using a HEPA-filtered fan maintaining 0.05 inches of negative pressure to limit airborne contamination spread.

The mechanical specifications detail equipment manufacturers and models, including Trane VPEF and VCEF series units, and establish strict installation standards for ductwork hangers, flexible duct connections, and transition fittings. Ductwork hanger spacing shall not exceed 8 feet between locations, with straps minimum 1.5 inches by 22 gauge galvanized steel, and flexible ducts shall not exceed 8 feet in length without splicing. All air distribution devices, including diffusers and grilles, must coordinate with architectural drawings for final location, and access panels are required for non-accessible ceilings. The VAV and PTU units include heating and fan motor specifications with control power transformers, and all controls must interface with the building management system. Test and balancing is required for existing items tied into new work, and all installations must comply with NFPA 90/225 and UL 181/723 standards. The project includes comprehensive control requirements with DDC controllers and sensors for temperature, humidity, carbon monoxide, carbon dioxide, and differential pressure monitoring, with thermostats mounted at 4 feet above finished floor unless otherwise noted.

View the file

Other files

File Type Posted
Tax_Collector_Interior_Renovations_and_Restoration_(Addendum_#3_Revision).pdf PDF
M1.101_-_FIRST_LEVEL_PLAN_AND_SCHEDULES_MECHANICAL.pdf PDF
E1.102_-_FIRST_LEVEL_PLAN_LIGHTING.pdf PDF
E1.101_-_FIRST_LEVEL_PLAN_POWER.pdf PDF
E0.001_-_ELECTRICAL_LEGEND_NOTES_ABBREVIATIONS.pdf PDF
Attachment_E_-_Additional_Renderings.pdf PDF
Attachment_D_-_Fire_Alarm_Panel.pdf PDF
Tax_Collector_Interior_Renovations_and_Restoration.pdf PDF
MASTER_Construction_Contract.pdf PDF
Attachment_C_-_Staging_2.png PNG image
Attachment_B_-_Staging_1.png PNG image
Attachment_A_-_Parking.png PNG image
COV_Division_27,_IT_Systems_Design_and_Installation_Guidelines_for_A-E.pdf PDF
Sales_Tax_Exemption_Procedure.pdf PDF
PRIME-SUB_FORM.xls XLS spreadsheet
VC_Tax_Collector_DeLand_Office_Project_Manuals_5.15.2025.pdf PDF
VC_Tax_Collector_DeLand_Office_Renovation_Bid_Set_5.15.2025.pdf PDF
Payment_and_Performance_Bond.pdf PDF
Basic_Insurance_Requirements.pdf PDF
Special_Conditions.pdf PDF
Bid_Documents.pdf PDF
VCTCO_Architectural.pdf PDF
VCTCO_Volume_2_specs.pdf PDF
Mechanical.pdf PDF
VCTCO_Volume_1_specs.pdf PDF
Fire_Protection.pdf PDF
Electrical.pdf PDF
2025-05-15_-_BID_&_PERMIT_SET_-_Telecommunications.pdf PDF
VOLUSIA_COUNTY_TC_Form_C402.pdf PDF
Plumbing.pdf PDF
staging_(1).png PNG image
Pre-Bid_Meeting_Invitee_Listing.docx DOCX document
Staging.png PNG image
Parking.png PNG image
PRIME-SUB_FORM_for_Contractors_rev._01.15.2025_(lock_before_publishing)_(1).xls XLS spreadsheet
SPECIAL_CONDITIONS_FOR_BIDDERS.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

ABBREVIATIONSMECHANICAL LEGEND

RADIATION DAMPER INSTALLED IN DUCT.

RADIATION DAMPER INSTALLED IN AIR DEVICE.

OPENING IN WALL ABOVE CEILING.

EQUIPMENT TAG.

HEATING WATER SUPPLY PIPING.

RECTANGULAR BRANCH DUCT CONNECTION.

L=1/4W, Min. 4"

HEATING WATER RETURN PIPING.

CONDENSATE DRAIN PIPING.

CHILLED WATER RETURN PIPING.

WALL MOUNTED DDC TEMPERATURE SENSOR

MOUNT 4'-0" ABOVE FINISHED FLOOR.

WALL MOUNTED DDC HUMIDITY SENSOR

MOUNT 4'-0" ABOVE FINISHED FLOOR.

INDICATES POINT OF CONNECTION BETWEEN NEW

AND EXISTING.

IDENTIFICATION TARGET.

A = DETAIL NUMBER.

B = SHEET NUMBER ON WHICH DETAIL IS LOCATED.

CONDENSER WATER SUPPLY PIPING.

CONDENSER WATER RETURN PIPING.

WALL MOUNTED THERMOSTAT

MOUNT 4'-0" ABOVE FINISHED FLOOR.

AIR DEVICE TAG.

MARK-CFM

SIDEWALL TRANSFER GRILLE.

SIDEWALL SUPPLY/RETURN/EXHAUST REGISTER.

WALL MOUNTED CARBON MONOXIDE SENSOR

MOUNT 4'-0" ABOVE FINISHED FLOOR.

WALL MOUNTED DIFFERENTIAL PRESSURE SENSOR.

MOUNT 4'-0" ABOVE FINISHED FLOOR.

POINT OF DISCONNECT.

CHILLED WATER SUPPLY PIPING.

1" DOOR UNDER CUT. ARROW INDICATES DIRECTION

OF FLOW.

REFRIGERANT PIPING.

A-100

UC

CWS

EQUIPMENT

TYPE

MARK

SIDEWALL FRESH AIR INTAKE LOUVER

OR EXHAUST LOUVER.

CONDENSING UNIT OR HEAT PUMP.

WALL MOUNTED CARBON DIOXIDE SENSOR

MOUNT 4'-0" ABOVE FINISHED FLOOR.

EXPOSED DOUBLE WALL INSULATED DUCTWORK.

LOCATION MATERIAL NOTES

INSULATION

R-VALUE

RETURN

UNINSULATEDSHEET METAL

DUCTWORK SCHEDULE/ COMMERCIAL

OTHER OPTIONS INCLUDE INTERNALLY

LINED OR DOUBLE WALL.

CONDITIONED

SPACE

SERVICE

TYPE

ABV - ABOVE

AC - AIR CONDITIONER

ACT - ACOUSTIC CEILING TILE

ADJ - ADJUSTABLE

AFD - ADJUSTABLE FREQUENCY DRIVE

AFF - ABOVE FINISHED FLOOR

AFUE - ANNUAL FUEL UTILIZATION EFFICIENCY

AHU - AIR HANDLING UNIT

BAS - BUILDING AUTOMATION SYSTEM

BDD - BACKDRAFT DAMPER

BI - BACKWARD INCLINE

BLDG - BUILDING

BHP - BRAKE HORSEPOWER

BTUH - BRITISH THERMAL UNIT PER HOUR

CD - CONDENSATE DRAIN

CFM - CUBIC FEET PER MINUTE

CH - CHILLER

CHW - CHILLED WATER

CHWP - CHILLED WATER PUMP

CHWR - CHILLED WATER RETURN

CHWS - CHILLED WATER SUPPLY

CLG - CEILING

COND - CONDENSATE

CONT - CONTINUOUS

CO - CARBON MONOXIDE

CO2 - CARBON DIOXIDE

COP2 - COEFFICIENT OF PERFORMANCE 2

CT - COOLING TOWER

CU - CONDENSING UNIT

CU-FT - CUBIC FEET

CW - CONDENSER WATER

CWP - CONDENSER WATER PUMP

CWR - CONDENSER WATER RETURN

CWS - CONDENSER WATER SUPPLY

DB - DRY BULB

DDC - DIRECT DIGITAL CONTROL

DN - DOWN

DP - DEW POINT

DWGS - DRAWINGS

DX - DIRECT EXPANSION

EF - EXHAUST FAN

EFF - EFFICIENCY

EXH - EXHAUST

EA - EACH

EAT - ENTERING AIR TEMPERATURE

EER2 - ENERGY EFFICIENCY RATIO 2

ELEC - ELECTRICAL

ENT - ENTERING

ESP - EXTERNAL STATIC PRESSURE

ETR - EXISTING TO REMAIN

EWT - ENTERING WATER TEMPERATURE

FC - FORWARD CURVED

FCU - FAN COIL UNIT

FD - FIRE DAMPER

FLA - FULL LOAD AMPS

FLEX - FLEXIBLE CONNECTOR OR DUCT

FPB - FAN POWERED BOX

FPM - FEET PER MINUTE

FSD - COMBINATION FIRE AND SMOKE DAMPER

FT-HD - FEET OF HEAD

°F - DEGREES FAHRENHEIT

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GPM - GALLONS PER MINUTE

HGR - HOT GAS REHEAT

HP - HORSEPOWER / HEAT PUMP

HSPF2 - HEATING SEASONAL PERFORMANCE FACTOR 2

HW - HOT WATER

HWR - HOT WATER RETURN

HWS - HOT WATER SUPPLY

HVAC - HEATING VENTILATION AND AIR CONDITIONING

HV - HEATING AND VENTILATING

HX - HEAT EXCHANGER

IEER2 - INTEGRATED ENERGY EFFICIENCY RATIO 2

IN-WG - INCHES WATER GAUGE

IN-WC - INCHES WATER COLUMN

S

T

CO

CO2

H

DP

SUPPLY DIFFUSER. DIRECTION OF AIRFLOW

INDICATED WITH ARROWS AND AIR DEVICE TAG.

RETURN OR OUTDOOR AIR GRILLE.

EXHAUST GRILLE.

SIDEWALL MOUNTED EXHAUST FAN.

SUPPLY DUCT UP SECTION (RECTANGULAR).

RETURN DUCT UP SECTION (RECTANGULAR).

EXHAUST DUCT UP SECTION (RECTANGULAR).

SUPPLY DUCT DOWN SECTION (RECTANGULAR).

RETURN DUCT DOWN SECTION (RECTANGULAR).

EXHAUST DUCT DOWN SECTION (RECTANGULAR).

SUPPLY DUCT UP SECTION (ROUND).

SUPPLY DUCT DOWN SECTION (ROUND).

RECT DUCTWORK WITH TAKE-OFF, BALANCING DAMPER AND

INSULATED FLEXIBLE ROUND DUCT. SAME SIZE AS DIFFUSER INLET

UNLESS NOTED OTHERWISE. FIRST DIMENSION IS THAT OF SIDE SHOWN.

ROUND DUCTWORK.

CONICAL FITTING WITH DAMPER ON BRANCH CONNECTION TO RECT

MAIN. PROVIDE DAMPER IN LOW PRESSURE DUCTWORK ONLY.

EXISTING DUCTWORK TO REMAIN.

MANUAL VOLUME DAMPER (VD).

OPPOSED BLADE MANUAL VOLUME DAMPER (OBMVD).

FLEXIBLE DUCT CONNECTION.

FIRE DAMPER WITH ACCESS PANEL. SEE LIFE

SAFETY PLANS FOR RATING REQUIREMENTS.

SMOKE DAMPER WITH ACCESS PANEL. SEE LIFE SAFETY PLANS

FOR RATING REQUIREMENTS. DUCT SMOKE DETECTOR TO BE

PLACED WITHIN 5'-0" OF DAMPER.

COMBINATION FIRE/SMOKE DAMPER WITH ACCESS PANEL.

SEE LIFE SAFETY PLANS FOR RATING REQUIREMENTS. DUCT

SMOKE DETECTOR TO BE PLACED WITHIN 5'-0" OF DAMPER.

EXISTING DUCTWORK TO BE REMOVED.

DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY ELEC

CONTRACTOR AND INSTALLED IN DUCT BY MECH CONTRACTOR.

REFER TO SPECIFICATIONS FOR CONTROL REQUIREMENTS.

A∅

SD

B

A

AHU

ELBOW WITH TURNING VANES.

MOTORIZED ACTUATOR.

WALL MOUNTED NITROGEN SENSOR.

MOUNT 1'-0" BELOW CEILING.

N2

CWR

CHWS

CHWS

HWS

HWS

CD

REF

CEILING MOUNTED EXHAUST FAN.

X REFERENCE NOTES.

RD

RD

LINEAR SLOT DIFFUSER.

STACKED DUCTWORK.

FD

SDMP

FSD

ABBREVIATIONS

KW - KILOWATTS

LAT - LEAVING AIR TEMPERATURE

LBS - POUNDS

LD - LINEAR DIFFUSER

LWT - LEAVING WATER TEMPERATURE

MAT - MIXED AIR TEMPERATURE

MAX - MAXIMUM

MBH - 1000 X BTUH

MCA - MIN CIRCUIT AMPACITY

MECH - MECHANICAL

MIN - MINIMUM

MOCP - MAXIMUM OVER CURRENT PROTECTION

MVD - MOTORIZED VOLUME DAMPER

MZ - MULTI-ZONE

NC - NOISE CRITERIA

NEC - NATIONAL ELECTRICAL CODE

N.I.C. - NOT IN CONTRACT

N.F.C. - NOT FOR CONSTRUCTION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

NO2 - NITROGEN DIOXIDE

N.T.S. - NOT TO SCALE

OA - OUTSIDE AIR

OBMVD - OPPOSED BLADE MANUAL VOLUME DAMPER

PROP - PROPELLER

PD - PRESSURE DROP

PLUM - PLUMBING

PSIA - POUNDS PER SQUARE INCH ABSOLUTE

PSIG - POUNDS PER SQUARE INCH GAUGE

PTU - PARALLEL FAN-POWERED BOX/TERMINAL

UNIT

QTY - QUANTITY

RA - RETURN AIR

RD - RADIATION DAMPER

RECT - RECTANGULAR

REQ'D - REQUIRED

RH - RELATIVE HUMIDITY

RL - REFRIGERANT LIQUID

RLA - RUNNING LOAD AMPS

RLS - REFRIGERANT LINE SET

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

RTU - ROOFTOP UNIT

SA - SUPPLY AIR

SEER2 - SEASONAL ENERGY EFFICIENCY RATIO 2

SF - SUPPLY FAN

SD - SMOKE DETECTOR

SDMP - SMOKE DAMPER

SQ-FT - SQUARE FOOT

SQ-IN - SQUARE INCH

SZ - SINGLE ZONE

TEMP - TEMPERATURE

TG - TRANSFER GRILLE

T'STAT - THERMOSTAT

TSP - TOTAL STATIC PRESSURE

TYP - TYPICAL

UC - UNDERCUT (DOOR)

UP - UPWARD

UV - ULTRAVIOLET LIGHT

VAV - VARIABLE AIR VOLUME

VD - MANUAL VOLUME DAMPER

VFD - VARIABLE FREQUENCY DRIVE

VFDC - VARIABLE FREQUENCY DRIVE CONTROLLER

V/PH - VOLTS AND PHASE

VRF - VARIBLE REFRIGERANT FLOW

VRV - VARIBLE REFRIGERANT VOLUME

VVT - VARIABLE VOLUME AND TEMPERATURE

W - WATTS

W/ - WITH

W/O - WITHOUT

WB - WET BULB

WMS - WIRE MESH SCREEN

ZD - ZONE DAMPER

FBC - FLORIDA BUILDING CODE

FMC - FLORIDA MECHANICAL CODE

FPC - FLORIDA PLUMBING CODE

FECC - FLORIDA ENERGY CONSERVATION CODE

EXTERIOR SHEET METAL R-8.0

ATTIC SHEET METAL R-8.0

PLENUM SHEET METAL R-4.2

SUPPLY

R-4.2SHEET METAL

CONDITIONED

SPACE

EXTERIOR SHEET METAL R-8.0

ATTIC SHEET METAL R-8.0

PLENUM SHEET METAL R-4.2

BACKDRAFT DAMPER (BDD).

ELBOW (PLAN, UP, DOWN).

TEE (PLAN, UP, DOWN).

A/B

W

L45°

CONDENSING UNIT OR HEAT PUMP (SIDE DISCHARGE).

DEMOLITION NOTES

1. ALL EXISTING EQUIPMENT AND MATERIALS TO BE REMOVED

UNDER THIS CONTRACT SHALL REMAIN THE PROPERTY OF

THE OWNER. CONTRACTOR SHALL SUBMIT A LIST OF

EQUIPMENT TO BE REMOVED TO THE OWNER.

CONTRACTOR SHALL RETAIN OR DISPOSE OF MATERIALS

AND EQUIPMENT AS DIRECTED BY THE OWNER.

2. ALL EQUIPMENT SHALL BE REMOVED IN A CAREFULLY

PLANNED MANNER. ALL CEILING-HUNG EQUIPMENT SHALL

BE REMOVED BY PROVIDING SUPPORTS FROM BELOW. NO

DROPPING OF EXISTING EQUIPMENT ONTO THE FLOOR

SLAB WILL BE ALLOWED.

3. REMOVE CONTROL WIRING OR PNEUMATIC TUBING

ASSOCIATED WITH EQUIPMENT BEING REMOVED,

COORDINATE WITH ELECTRICAL CONTRACTOR AS

REQUIRED. THE REMOVAL OF CONTROL APPARATUS SHALL

NOT INTERFERE WITH NORMAL OPERATION OF REMAINING

EQUIPMENT OR SYSTEMS.

4. REMOVE ALL CHILLED WATER SUPPLY AND RETURN PIPING

AND VALVES.

5. NOT ALL HVAC EQUIPMENT, DUCTWORK, PIPING, AND/OR

OTHER PIPING SYSTEMS ARE SHOWN ON THESE

DEMOLITION DRAWINGS. CONTRACTOR SHALL IDENTIFY ALL

DUCTS AND PIPES PRIOR TO DEMOLITION.

6. SIZES OF PIPING AND DUCTWORK TO BE REMOVED AND/OR

REMAIN MAY NOT HAVE BEEN INDICATED. CONTRACTOR

SHALL SURVEY EXISTING SPACE, VERIFY SIZES, AND

INCLUDE IN SCOPE OF WORK. DISCREPANCIES DISCOVERED

BETWEEN FIELD CONDITIONS AND CONSTRUCTION

DOCUMENTS SHALL BE REPORTED TO THE ENGINEER

PROMPTLY.

7. NO PIPING SHALL BE REMOVED UNLESS BRANCH SHUTOFF

VALVES ARE IDENTIFIED AND CLOSED PRIOR TO ACTUAL

REMOVAL.

8. DRAIN ALL PIPING SECTIONS TO BE REMOVED PRIOR TO

ACTUAL REMOVAL. NO SPILLING OVER FLOOR SLABS

SHALL BE PERMITTED. DRAIN PIPES INTO PORTABLE

CONTAINERS TO BE DISPOSED OF AS REQUIRED.

9. PROVIDE TEMPORARY SHEET METAL CAP ON ALL OPEN

END DUCTWORK THAT IS TO REMAIN.

10. ALL SERVICES PASSING THROUGH DEMOLITION CONTRACT

AREA SERVING OTHER AREAS SHALL REMAIN AND SHALL

BE PROTECTED UNLESS OTHERWISE NOTED.

11. CONSIDER USING A NEGATIVE PRESSURE MACHINE:

MAINTAIN DEMOLITION/CONSTRUCTION AREA AT A

NEGATIVE PRESSURE RELATIVE TO THE ADJOINING NON-

WORK AREAS IN ORDER TO LIMIT THE SPREAD OF

AIRBORNE CONTAMINATION. PROVIDE A TEMPORARY HEPA-

FILTERED NEGATIVE AIR FAN FOR CONSTRUCTION AREA.

MAINTAIN A 0.05” NEGATIVE PRESSURE IN THE

CONSTRUCTION AREA RELATIVE TO THE ADJACENT

SPACES. PROVIDE ADDITIONAL NEGATIVE AIR MACHINES AS

REQUIRED TO ACHIEVE MINIMUM NEGATIVE PRESSURE.

PROVIDE WELL-SEALED TEMPORARY DUCT BARRIER

PARTITIONS. ALL EXISTING RETURN REGISTERS LOCATED

WITHIN THE RENOVATION AREA SHALL BE BLANKED OFF.

TEMPORARILY REDUCE SUPPLY CFM TO MAINTAIN0.05”

NEGATIVE PRESSURE. ROUTE TEMPORARY FLEXIBLE DUCT

FROM DISCHARGE OF HEPA UNIT TO OUTSIDE OF

TEMPORARY BARRIER. LOCATE EXHAUST FAN DISCHARGE

MINIMUM 25’-0” FROM OPERABLE WINDOWS AND OUTSIDE

AIR INTAKES. FAN CRITERIA: MANUFACTURED BY ‘HEPA-

AIRE’, MODEL -1800 PAS VARIABLE CFM, 1000 TO 1800 CFM,

115V/60HZ, 10 FLA.

12. IN CONJUNCTION WITH ABOVE NEGATIVE PRESSURE

REQUIREMENT, PROVIDE AN INCLINED MANOMETER,

DIFFERENTIAL PRESSURE TYPE, WITH WHITE FACE GAUGE

AND BLACK LETTERS. THIS SHALL BE USED BY THE

CONTRACTOR TO RECORD, ON A DAILY BASIS, THE

NEGATIVE PRESSURE IN THE RENOVATION AREA RELATIVE

TO THE ADJACENT SPACES.

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:37:44 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt

MECHANICAL LEGEND,

NOTES &

ABBREVIATIONS

M0.001

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

IE - MECHANICAL SHEET LIST

Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline

M0.001 MECHANICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT MECHANICAL

M1.100 FIRST LEVEL DEMOLITION PLAN MECHANICAL 05.15.2025 ISSUE FOR PERMIT MECHANICAL

M1.101 FIRST LEVEL PLAN AND SCHEDULES MECHANICAL 05.15.2025 ISSUE FOR PERMIT MECHANICAL

M8.000 MECHANICAL DETAILS 05.15.2025 ISSUE FOR PERMIT MECHANICAL

Grand total: 4

REVISIONS

A A

B B

G G

H H

J J

C C

D D

E E

F F

M

M

M T

T

T

T

T

T

T

T

T

T

18" W x 8" D x 7' L

PLENUM (TYP.6)

M

M

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:37:57 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt

FIRST LEVEL

DEMOLITION PLAN

MECHANICAL

M1.100

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

1/8" = 1'-0"M1.100

1 1ST LEVEL - Demo Work Mechanical

GENERAL NOTES

1. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE

PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK

BEFORE SUBMITTING PROPOSAL SO AS TO BECOME FAMILIAR

WITH EXISTING WORK. SUBMISSION OF A PROPOSAL WILL BE

CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN

MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS

REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE

RECOGNIZED. IT IS TO BE UNDERSTOOD THAT UNFORESEEN

CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD

LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION

WITH OTHER TRADES IN EQUIPMENT ROUTING AS DETERMINED

DURING CONSTRUCTION AND AS DIRECTED BY THE

ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED

THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS

CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT

COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY

DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR TO BID AND

INCLUDE ANY DEVIATIONS IN THE CONTRACT.

REFERENCE NOTES

TEST AND BALANCE REQUIRED FOR OUT OF SCOPE EXISTING ITEMS (I.E.,

DIFFUSERS, GRILLES, ETC.) THAT ARE TO BE TIED INTO NEW WORK.

COORDINATE WITH EXISTING CONDITIONS FOR CONNECTION OF OLD

AND NEW DUCTWORK. REFER TO SHEET M1.101 FOR POINTS OF

CONNECTION.

REMOVE EXISTING THERMOSTAT.

REMOVE EXISTING AIR DEVICES IN AREA, ASSOCIATED DUCTWORK AND

ALL OTHER APPURTENANCES.

EXISTING PARALLEL FAN-POWERED BOX TO BE REMOVED.

A A

B B

G G

H H

J J

D D

E E

F F

28"/14"

40"/14"

32"/14"

FSD

FSD

FSD

M

M

M

FD

FD

10"/6"

10X6 UP

TO EF-6

SF

34X10 DN

16"/16"

14"/12"

6"/6"

16"/14"

12"/10"

14"/14"

16"/14"

12"/12"

BREAK

ROOM

OFFICE

CASH

IT

MECHANICAL

STAIR

HALL

STORAGE

HALL

ELEC

IT

STORAGE

PERMITTING

HALL

TOILET

TOILET

CHECK-IN

STAFF

CHECK-IN

ENTRY

WAITING A

WAITING B

SERVICE

TESTING

CUSTOMER

SERVICE

HALL

HALL

HALL

14"ø

PTU

1.3

PTU

1.4

10"ø

8"ø

12"ø

A-300

A-60 ø10" A-295 ø10"

A-295

A-240 ø10"

A-205

A-205

A-205 A-205ø8" ø8"ø8"

A-220 ø10"

A-170 ø8" ø8"

A-165

A-220 ø10"

A-330A-330

A-385 ø12"A-380 ø10"

A-285 ø8"

A-105

A-105 ø8"

A-105 ø8" ø6"

A-80

A-90

A-100 ø6" ø10"

A-325 ø10"

A-255ø10"

A-260 ø10"A-185 ø8"

A-180 ø8"

A-80 ø6"

A-130 ø8"

A-225 ø10" ø10"

A-220

A-225

PTU

1.1

PTU

1.2

20"/14"

VAV

1.1

4" ø ø6"

VAV

1.2

VAV

1.3

4" ø ø6"

A-60

A-130

PTU

1.5

"ø

6 6

2 7

2 72 7

1 7 1 7

1 7

1 7

1 7

T3

T

T

3 T

T

T

T

T

A-30

UC

PROVIDE MANUAL

VOLUME DAMPER

AND SET AT

670CFM

PROVIDE MANUAL

VOLUME DAMPER

AND SET AT

630CFM

ø10" ø12" ø10"

ROUTE FLEX DUCT

ABOVE MINIMUM PTU

SERVICE CLEARANCE

AT THIS LOCATION.

FD

28"/14"

8" ø ø6" ø10"

6" ø

A-306 ø6"

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:38:09 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt

FIRST LEVEL PLAN AND

SCHEDULES

MECHANICAL

M1.101

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

1/8" = 1'-0"M1.101

1 1ST LEVEL - New Work Mechanical

GENERAL NOTES

1.

2.

DUCTS ENTERING THE VAV BOX/PARALLEL FAN-POWERED

BOX (VAV/PTU, RESPECTIVELY) MUST REDUCE TO INLET SIZE

AT LEAST THREE DUCT DIAMETERS BEFORE THE VAV BOX

INLET AND SHALL BE STRAIGHT DUCT.

COORDINATE FINAL DIFFUSER LOCATION WITH

ARCHITECTURAL DRAWINGS.

REFERENCE NOTES

REFER TO PARALLEL TERMINAL UNIT DETAIL 05 ON SHEET

M8.000 FOR ADDITIONAL INFORMATION. ENSURE FAN-

POWERED BOX HAS NECESSARY CLEARANCE AS INDICATED

ON PLANS.

REFER TO VAV DETAIL 01 ON SHEET M8.000 FOR ADDITIONAL

INFORMATION. ENSURE FAN-POWERED BOX HAS NECESSARY

CLEARANCE AS INDICATED ON PLANS.

THERMOSTAT TO BE MOUNTED A MINIMUM 48" AFF.

COORDINATE WITH ARCHITECTURAL DRAWINGS FOR FINAL

THERMOSTAT LOCATION AND/OR ELEVATION.

EXISTING DUCTWORK TO CONTINUE TO AREA OUTSIDE OF

CURRENT SCOPE. REFER TO EXISTING DRAWINGS FOR

CONTINUATION.

EXISTING DUCTWORK TO CONTINUE INTO EXISTING

MECHANICAL ROOM. DUCT MAIN, TRANSITIONS, AND DUCT

ACCESSORIES (I.E., DAMPERS) ARE TO REMAIN. CONTRACTOR

TO VERIFY ITEMS ARE IN PROPER CONDITION.

RA GRILLE, TYPE-C (IN AIR DEVICE SCHEDULE) TO ROUTE TO

PLENUM ABOVE.

PROVIDE A MEANS OF ACCESS/ACCESS PANEL TO VAV/FAN-

POWERED BOX IF NOT LOCATED IN EXPOSED AREA OR

ABOVE ACOUSTIC CEILING TILE (ACT).

SPACE IS NOT IN CONTRACT. ROUTE NEW DUCTWORK ABOVE

THIS SPACE. COORDINATE WITH EXISTING CONDITIONS.

CFM RANGE

0 - 95

NECK SIZE

6"Ø

96 - 205 8"Ø

10"Ø

12"Ø

14"Ø

A-CFM

206 - 375

376 - 605

606 - 850

CFM RANGE

0 - 2500

NECK SIZE

22"X22"

C-CFM

AIR DEVICE SCHEDULE

MARK DESCRIPTION FACE SIZE NECK MATERIAL

MANUFACTURER/MODEL #

NOTES

EGGCRATE RET./EXH. GRILLE (1/2"x1/2"x1/2")

LOUVERED FACE 2 CONE ADJUSTABLE SUPPLY DIFFUSER 24"x24" SEE TABLE BELOW ALUMINUM GREENHECK/METAL AIRE 5700-AL

C 24"x24" 22"X22" ALUMINUM

A

BASIS OF DESIGN

DAMPER

Y

NGREENHECK/METAL AIRE CC-5

NOTES:

1. COORDINATE COLOR AND SURFACE FINISHES WITH ARCHITECTURAL DRAWINGS.

2. PROVIDE RAPID MOUNT T-BAR FRAME FOR PLASTER AND SHEET ROCK CEILINGS.

3. SUPPLY COMPLETE WITH FACTORY INSTALLED 1/2" THICK FOIL BACKED INSULATION.

1, 2, 3

1, 2

4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.

3.SINGLE POINT CONNECTION UNITS. TERMINAL UNITS TO BE PROVIDED WITH CONTROL POWER TRANSFORMER.

2.FAN MOTOR SHALL BE 208/3/60 AND HEATER SHALL BE 208/3/60.

1.PROVIDE ELECTRONIC ROOM SENSOR WITH DIGITAL DISPLAY CONTROLLER. DDC CONTROLLER SHALL BE INTERFACED WITH BASE BUILDING MANAGEMENT SYSTEM. REFER TO BASE BUILDING DRAWINGS AND BUILDING ENGINEER FOR INSTALLATION REQUIREMENTS.

NOTES:

PARALLEL FAN POWERED TERMINAL UNIT SCHEDULE

EQUIPMENT TAG

LOCATION

PRIMARY VALVE AIR FLOW INLET

SIZE DIA.

IN.

E.S.P.

(IN. WG.)

OPERATING

WEIGHT (LBS)

FAN MOTOR HEATING DATA

MCA MOCP MANUFACTURER

MODEL

NUMBER

NOTES

DESIGN CFM MINIMUM CFM MAXIMUM CFM CFM HP V/Ø/HZ HEATING FAN CFM VALVE HEATING CFM EAT/LAT (°F) KW STAGES V/Ø/HZ

PTU-1.1 WAITING A/B 1615 240 1615 12" 0.25 114 440 0.33 277/1 680 240 64.71/78.59 3 1 277/1 15.54 20 TRANE VPEF 1-4

PTU-1.2 CHECKING 1605 240 1605 12" 0.25 114 340 0.33 277/1 580 240 63.79/74.65 2 1 277/1 11.03 15 TRANE VPEF 1-4

PTU-1.3 SERVICE 2735 320 2735 14" 0.25 116 320 0.33 277/1 740 320 63.51/72.02 2 1 277/1 11.53 15 TRANE VPEF 1-4

PTU-1.4 CUSTOMER SERVICE 950 190 950 10" 0.25 111 380 0.125 277/1 570 190 65.00/76.04 2 1 277/1 9.90 15 TRANE VPEF 1-4

PTU-1.5 BREAK ROOM 1370 165 1375 10" 0.25 111 300 0.125 277/1 465 165 64.68/78.21 2 1 277/1 9.90 15 TRANE VPEF 1-4

5.EXHAUST CFM FROM SPACE IS NOT TO EXCEED MINIMUM CFM VALUE.

4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.

3.PROVIDE PRESSURE INDEPENDENT TYPE. PROVIDE ALL NECESSARY EQUIPMENT TO ALLOW COMMUNICATION WITH BUILDING MANAGEMENT SYSTEM (BMS)

2.PROVIDE FUSED CONTROL POWER TRANSFORMER.

1.PROVIDE ELECTRONIC ROOM THERMOSTAT WITH DIGITAL DISPLAY, ADJUSTABLE SETPOINT AND NIGHT SET-BACK OVERRIDE AND CANCEL BUTTONS.

NOTES:

VAV BOX SCHEDULE

EQUIPMENT TAG LOCATION

AIR DATA INLET

SIZE DIA.

IN.

E.S.P.

(IN. WG.)

MAX.

N.C.

OPERATING

WEIGHT (LBS)

MANUFACTURER

MODEL

NUMBER

NOTES

DESIGN CFM MINIMUM CFM MAXIMUM CFM

VAV-1.1 ELEC 90 50 90 4" 0.25 29 21 TRANE VCEF 1-5

VAV-1.2 TELE 100 50 100 4" 0.25 29 21 TRANE VCEF 1-5

VAV-1.3 IT 220 70 220 4" 0.25 29 21 TRANE VCEF 1-4

VAV

TERMINAL UNIT

SECTION OF STRAIGHT PIECE

OF ROUND DUCT EQUAL TO

BOX INLET SIZE

SEE PLAN FOR SIZE

FLEX DUCT

(TYPICAL)

PROVIDE TRANSITION

AS REQUIRED

HANGER RODS. LOCATED

TO CLEAR ALL VALVE

CONTROLS

SUPPLY DUCT.

SEE PLAN FOR SIZE

ANCHOR TO

STRUCTURE

NOTES:

1.

2.

3.

4.

ON DUCTS OVER 48" WIDE, BOTTOM

SHALL BE BRACED BY ANGLE. FOR

CROSS SECTION AREA MORE THAN 8

SQ FT, DUCT SHALL BE BRACED BY

ANGLES ON ALL FOUR SIDES.

CUTTING AND PATCHING SHALL BE

LIMITED TO A MINIMUM AS REQUIRED

FOR PROPER INSTALLATION.

REFER TO SMACNA FOR SPECIFIC

RECOMMENDED HANGER TYPES NO TED.

MAXIMUM SPACING BETWEEN HANGER

LOCATIONS SHALL BE 8'-0" PER

PAIR. STRAPS SHALL BE MINIMUM 1

1/2" X 22 GAGE GALVANIZED STEEL.

THREADED

HANGER ROD

GALVANIZED

HANGER

STRAP

UNISTRUT

OR ANGLE

IRON

STRAP HANGERS TRAPEZE HANGERS

STRAP

OR ANGLE

HANGER RODS

OVER 60"SEE NOTE 3MAX. 60"

SCREWS TYPICAL

1" MIN

3"

M A

X . S

P A

C

IN

G

HANGER BAND

CONTINUOUS HANGER

STRAP AROUND DUCT

36" DIA. MAX.

36" DIA. MAX.

HANGER

BAND

STRAPS

BAND

CONICAL FITTING WITH LOCKING TYPE VOLUME DAMPER.

DAMPER AND DAMPER STAND-OFF EQUAL TO CROWN

PRODUCTS COMPANY MODEL 3200-DS.

FLEX DUCT OR ROUND SHEET METAL DUCT. FLEX

DUCT MAX. 8'-0" LONG, USE CLAMP TO ATTACH

FLEX DUCTS AND SEAL AS PER SPECIFICATIONS,

SUPPORT FLEX DUCT EVERY 3'-0" FROM STRUCTURE.

TO AIR

VALVE

SIDE TAKE-OFF FITTING - EQUAL

TO FLEXMASTER STO (22 GA.

MIN.)

RECTANGULAR DUCT

VOLUME DAMPER

MAX. 15° TRANSITION 0.25 D

1.

D

ROUND DUCT

S U

P P

L Y

A

IR

F L

O W

S U

P P

L Y

A

IR

F L

O W

D

PROVIDE CEILING ACCESS

PANEL FOR DAMPER ACCESS

IN NON-ACCESSIBLE CEILINGS

AIR DISTRIBUTION DEVICE, SEE

SCHEDULE. LAY-IN SHOWN-

SURFACE MOUNT SIMILAR

VOLUME DAMPER WITH LOCKING

QUADRANT AND 2" STANDOFF

SUPPLY DUCT SIZE AS

SHOWN ON PLANS

DUCT SEALER AT SPIN

COLLAR CONNECTION

TO MAIN

ROUND SPIN-IN COLLAR MOUNT

IN SIDE OF DUCT UNLESS

SPECIFICALLY SHOWN OTHERWISE

MAXIMUM D/8 OFFSET

ALLOWED IN LAST D INCHES

TO DEVICE WHERE D IS THE

INTERNAL FLEX DIAMETER

NECK SIZE TO MATCH

FLEX DUCT SIZE INDICATED

INSULATE TOP PANEL

OF LAY-IN DIFFUSER

CEILING (T-BAR SHOWN)

GYPSUM BOARD SIMILAR

ADJUSTABLE CLAMP

UPPER ATTACHMENT PER SMACNA

DUCT SEALER

ADJUSTABLE CLAMP STAINLESS STEEL

SEE NOTE 3

MAX. SAG 1/2" PER FOOT

BETWEEN SUPPORT POINTS

NOTES:

1.

2.

3.

4.

FLEXIBLE DUCTS SHALL BE ONE-PIECE AND SHALL NOT BE SPLICED TOGETHER.

EXTEND FLEXIBLE DUCT INSULATION TO DUCT/DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC.

MINIMUM 1-1/2" WIDE 22 GAUGE GALVANIZED STRAP HANGER. INSTALL PER GUIDELINES SETFORTH IN CHAPTER 3 OF THE MOST CURRENT EDITION OF THE S.M.A.C.N.A. TECHNICAL MANUAL TITLED "HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE".

FLEXIBLE AIR DUCT SHALL BE FULLY EXTENDED AND NOT COMPRESSED. ELBOW RADIUS SHALL BE NO LESS THAN R/D=1.0.

ELECTRIC HEATER

FAN POWERED TERMINAL UNIT

HANG UNIT FROM BUILDING

STRUCTURE WITH THREADED ROD

AND SPRING TYPE VIBRATION

ISOLATORS

MEDIUM PRESSURE FLEXIBLE DUCT,

REFER TO PLANS FOR SIZE

CONTROL PANEL FOR

ELECTRIC HEATER, PROVIDE

REQUIRED SERVICE

CLEARANCE IN FRONT OF DOOR

(LEFT-HANDED PTU IS SHOWN,

REFER TO DRAWINGS FOR

CORRECT HANDING)

PRIMARY AIR INLET

GALVANIZED

SHEETMETAL

REDUCER

PLENUM

RETURN

AIR INLET

FILTER

LOW PRESSURE SUPPLY

DUCT, REFER TO PLANS

FOR SIZE

FLEXIBLE

DUCT

CONNECTION

NOTE

COORDINATE INSTALLATION OF FAN TERMINAL

UNIT TO PROVIDE ADEQUATE SERVICE ACCESS.

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:38:12 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt

MECHANICAL DETAILS

M8.000

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

SCALE: NTSM8.000

1 VAV TERMINAL UNIT CONNECTION DETAIL

SCALE: NTSM8.000

2 DUCT HANGER DETAIL

SCALE: NTSM8.000

3 DUCT CONNECTION DETAILS

SCALE: NTSM8.000

4 FLEXIBLE DUCT INSTALLATION DETAIL

SCALE: NTSM8.000

5 FAN POWERED TERMINAL UNIT INSTALLATION DETAIL

M0.001 - MECHANICAL LEGEND, NOTES & ABBREVIATIONS
M0.001 - MECHANICAL LEGEND, NOTES & ABBREVIATIONS
M1.100 - FIRST LEVEL DEMOLITION PLAN MECHANICAL
M1.100 - FIRST LEVEL DEMOLITION PLAN MECHANICAL
M1.101 - FIRST LEVEL PLAN AND SCHEDULES MECHANICAL
M1.101 - FIRST LEVEL PLAN AND SCHEDULES MECHANICAL
M8.000 - MECHANICAL DETAILS
M8.000 - MECHANICAL DETAILS

File details come from the government source that posted it. Updated .