M1.101_-_FIRST_LEVEL_PLAN_AND_SCHEDULES_MECHANICAL.pdf

PDF 462 KB Posted

Attached to
Tax Collector Interior Renovations and Restoration
Solicitation number
25-B-127LL
Issued by
Volusia County, Florida

About this file

This is a mechanical systems plan and schedule document for the Volusia County Tax Collector's office interior renovation and restoration project located at 123 W. Indiana Avenue in DeLand, Florida. The document provides detailed first-level mechanical HVAC design specifications including ductwork layout, terminal unit configurations, diffuser placements, and control system requirements for the approximately 6,766 square-foot renovation project. The plan designates five parallel fan-powered terminal units (PTU-1.1 through PTU-1.5) serving distinct areas including Waiting Rooms A/B, Check-in, Service, Customer Service, and Break Room, with design airflow ranging from 950 to 2,735 CFM and corresponding inlet sizes from 10 to 14 inches. Three VAV boxes (VAV-1.1 through VAV-1.3) are specified for the Electrical, Telephone, and IT spaces with design airflows between 90 and 220 CFM. The plan includes general notes requiring duct transitions to occur at least three diameters before VAV/PTU inlets, minimum 48-inch thermostat mounting heights, and coordination with architectural drawings for final diffuser locations and access panels. The document references additional detail sheets (M8.000) for parallel terminal unit and VAV box specifications and incorporates a pre-bid clarification revision dated July 16, 2025.

The mechanical plan specifies equipment manufacturers and models, with all terminal units utilizing Trane VPEF and VCEF series units. The parallel fan-powered units are equipped with 0.33 horsepower motors operating at 277 volts, single phase, 60 hertz, with heating capacities ranging from 9.90 to 15.54 kilowatts and corresponding MCA/MOCP ratings. The plan mandates integration with the existing building management system to include complete graphics, points, alarms, and control coordination, with pressure-independent type VAV boxes and fused disconnect door switches meeting NFPA 90/225 and UL 181/723 standards. Supply diffusers are specified as 24-inch by 24-inch cone adjustable units with Greenheck Metal Aire 5700-AL models featuring factory-installed 1/2-inch foil-backed insulation. The document establishes construction cost estimates of $950,000 with a 150-day contract timeline, funded through Volusia County appropriations with potential tax exemptions available through the county's Consumer's Certificate of Exemption for direct material purchases.

View the file

Other files

File Type Posted
Tax_Collector_Interior_Renovations_and_Restoration_(Addendum_#3_Revision).pdf PDF
E1.102_-_FIRST_LEVEL_PLAN_LIGHTING.pdf PDF
E1.101_-_FIRST_LEVEL_PLAN_POWER.pdf PDF
E0.001_-_ELECTRICAL_LEGEND_NOTES_ABBREVIATIONS.pdf PDF
Attachment_E_-_Additional_Renderings.pdf PDF
Attachment_D_-_Fire_Alarm_Panel.pdf PDF
Tax_Collector_Interior_Renovations_and_Restoration.pdf PDF
MASTER_Construction_Contract.pdf PDF
Attachment_C_-_Staging_2.png PNG image
Attachment_B_-_Staging_1.png PNG image
Attachment_A_-_Parking.png PNG image
COV_Division_27,_IT_Systems_Design_and_Installation_Guidelines_for_A-E.pdf PDF
Sales_Tax_Exemption_Procedure.pdf PDF
PRIME-SUB_FORM.xls XLS spreadsheet
VC_Tax_Collector_DeLand_Office_Project_Manuals_5.15.2025.pdf PDF
VC_Tax_Collector_DeLand_Office_Renovation_Bid_Set_5.15.2025.pdf PDF
Payment_and_Performance_Bond.pdf PDF
Basic_Insurance_Requirements.pdf PDF
Special_Conditions.pdf PDF
Bid_Documents.pdf PDF
VCTCO_Architectural.pdf PDF
VCTCO_Volume_2_specs.pdf PDF
Mechanical.pdf PDF
VCTCO_Volume_1_specs.pdf PDF
Fire_Protection.pdf PDF
Electrical.pdf PDF
2025-05-15_-_BID_&_PERMIT_SET_-_Telecommunications.pdf PDF
VOLUSIA_COUNTY_TC_Form_C402.pdf PDF
Plumbing.pdf PDF
staging_(1).png PNG image
Pre-Bid_Meeting_Invitee_Listing.docx DOCX document
Staging.png PNG image
Parking.png PNG image
PRIME-SUB_FORM_for_Contractors_rev._01.15.2025_(lock_before_publishing)_(1).xls XLS spreadsheet
SPECIAL_CONDITIONS_FOR_BIDDERS.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A A

B B

G G

H H

J J

D D

E E

F F

28"/14"

40"/14"

32"/14"

FSD

FSD

FSD

M

M

M

FD

FD

10"/6"

10X6 UP

TO EF-6

SF

34X10 DN

16"/16"

14"/12"

6"/6"

16"/14"

12"/10"

14"/14"

16"/14"

12"/12"

BREAK

ROOM

OFFICE

CASH

IT

MECHANICAL

STAIR

HALL

STORAGE

HALL

ELEC

IT

STORAGE

PERMITTING

HALL

TOILET

TOILET

CHECK-IN

STAFF

CHECK-IN

ENTRY

WAITING A

WAITING B

SERVICE

TESTING

CUSTOMER

SERVICE

HALL

HALL

HALL

14"ø

PTU

1.3

PTU

1.4

10"ø

8"ø

12"ø

A-300

A-60 ø10" A-295 ø10"

A-295

A-240 ø10"

A-205

A-205

A-205 A-205ø8" ø8"ø8"

A-220 ø10"

A-170 ø8" ø8"

A-165

A-220 ø10"

A-330A-330

A-385 ø12"A-380 ø10"

A-285 ø8"

A-105

A-105 ø8"

A-105 ø8" ø6"

A-80

A-90

A-100 ø6" ø10"

A-325 ø10"

A-255ø10"

A-260 ø10"A-185 ø8"

A-180 ø8"

A-80 ø6"

A-130 ø8"

A-225 ø10" ø10"

A-220

A-225

PTU

1.1

PTU

1.2

20"/14"

VAV

1.1

4" ø ø6"

VAV

1.2

VAV

1.3

4" ø ø6"

A-60

A-130

PTU

1.5

"ø

6 6

2 7

2 72 7

1 7 1 7

1 7

1 7

1 7

T3

T

T

3 T

T

T

T

T

A-30

UC

PROVIDE MANUAL

VOLUME DAMPER

AND SET AT

670CFM

PROVIDE MANUAL

VOLUME DAMPER

AND SET AT

630CFM

ø10" ø12" ø10"

ROUTE FLEX DUCT

ABOVE MINIMUM PTU

SERVICE CLEARANCE

AT THIS LOCATION.

FD

28"/14"

8" ø ø6" ø10"

6" ø

A-306 ø6"

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

7/17/2025 1:47:43 PMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt

FIRST LEVEL PLAN AND

SCHEDULES

MECHANICAL

M1.101

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Eric S Cepull PE 64750

05.15.2025

1/8" = 1'-0"M1.101

1 1ST LEVEL - New Work Mechanical

GENERAL NOTES

1.

2.

DUCTS ENTERING THE VAV BOX/PARALLEL FAN-POWERED

BOX (VAV/PTU, RESPECTIVELY) MUST REDUCE TO INLET SIZE

AT LEAST THREE DUCT DIAMETERS BEFORE THE VAV BOX

INLET AND SHALL BE STRAIGHT DUCT.

COORDINATE FINAL DIFFUSER LOCATION WITH

ARCHITECTURAL DRAWINGS.

REFERENCE NOTES

REFER TO PARALLEL TERMINAL UNIT DETAIL 05 ON SHEET

M8.000 FOR ADDITIONAL INFORMATION. ENSURE FAN-

POWERED BOX HAS NECESSARY CLEARANCE AS INDICATED

ON PLANS.

REFER TO VAV DETAIL 01 ON SHEET M8.000 FOR ADDITIONAL

INFORMATION. ENSURE FAN-POWERED BOX HAS NECESSARY

CLEARANCE AS INDICATED ON PLANS.

THERMOSTAT TO BE MOUNTED A MINIMUM 48" AFF.

COORDINATE WITH ARCHITECTURAL DRAWINGS FOR FINAL

THERMOSTAT LOCATION AND/OR ELEVATION.

EXISTING DUCTWORK TO CONTINUE TO AREA OUTSIDE OF

CURRENT SCOPE. REFER TO EXISTING DRAWINGS FOR

CONTINUATION.

EXISTING DUCTWORK TO CONTINUE INTO EXISTING

MECHANICAL ROOM. DUCT MAIN, TRANSITIONS, AND DUCT

ACCESSORIES (I.E., DAMPERS) ARE TO REMAIN. CONTRACTOR

TO VERIFY ITEMS ARE IN PROPER CONDITION.

RA GRILLE, TYPE-C (IN AIR DEVICE SCHEDULE) TO ROUTE TO

PLENUM ABOVE.

PROVIDE A MEANS OF ACCESS/ACCESS PANEL TO VAV/FAN-

POWERED BOX IF NOT LOCATED IN EXPOSED AREA OR

ABOVE ACOUSTIC CEILING TILE (ACT).

SPACE IS NOT IN CONTRACT. ROUTE NEW DUCTWORK ABOVE

THIS SPACE. COORDINATE WITH EXISTING CONDITIONS.

CFM RANGE

0 - 95

NECK SIZE

6"Ø

96 - 205 8"Ø

10"Ø

12"Ø

14"Ø

A-CFM

206 - 375

376 - 605

606 - 850

CFM RANGE

0 - 2500

NECK SIZE

22"X22"

C-CFM

AIR DEVICE SCHEDULE

MARK DESCRIPTION FACE SIZE NECK MATERIAL

MANUFACTURER/MODEL #

NOTES

EGGCRATE RET./EXH. GRILLE (1/2"x1/2"x1/2")

LOUVERED FACE 2 CONE ADJUSTABLE SUPPLY DIFFUSER 24"x24" SEE TABLE BELOW ALUMINUM GREENHECK/METAL AIRE 5700-AL

C 24"x24" 22"X22" ALUMINUM

A

BASIS OF DESIGN

DAMPER

Y

NGREENHECK/METAL AIRE CC-5

NOTES:

1. COORDINATE COLOR AND SURFACE FINISHES WITH ARCHITECTURAL DRAWINGS.

2. PROVIDE RAPID MOUNT T-BAR FRAME FOR PLASTER AND SHEET ROCK CEILINGS.

3. SUPPLY COMPLETE WITH FACTORY INSTALLED 1/2" THICK FOIL BACKED INSULATION.

1, 2, 3

1, 2

5.UNIT TO TIE INTO EXISTING HVAC CONTROLS SYSTEM TO INCLUDE GRAPHICS, POINTS, ALARMS, ETC. TO PROVIDE A COMPLETE AND OPERATING SYSTEM.

4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.

3.SINGLE POINT CONNECTION UNITS. TERMINAL UNITS TO BE PROVIDED WITH CONTROL POWER TRANSFORMER.

2.FAN MOTOR SHALL BE 208/3/60 AND HEATER SHALL BE 208/3/60.

1.PROVIDE ELECTRONIC ROOM SENSOR WITH DIGITAL DISPLAY CONTROLLER. DDC CONTROLLER SHALL BE INTERFACED WITH BASE BUILDING MANAGEMENT SYSTEM. REFER TO BASE BUILDING DRAWINGS AND BUILDING ENGINEER FOR INSTALLATION REQUIREMENTS.

NOTES:

PARALLEL FAN POWERED TERMINAL UNIT SCHEDULE

EQUIPMENT TAG

LOCATION

PRIMARY VALVE AIR FLOW INLET

SIZE DIA.

IN.

E.S.P.

(IN. WG.)

OPERATING

WEIGHT (LBS)

FAN MOTOR HEATING DATA

MCA MOCP MANUFACTURER

MODEL

NUMBER

NOTES

DESIGN CFM MINIMUM CFM MAXIMUM CFM CFM HP V/Ø/HZ HEATING FAN CFM VALVE HEATING CFM EAT/LAT (°F) KW STAGES V/Ø/HZ

PTU-1.1 WAITING A/B 1615 240 1615 12" 0.25 114 440 0.33 277/1 680 240 64.71/78.59 3 1 277/1 15.54 20 TRANE VPEF 1-5

PTU-1.2 CHECKING 1605 240 1605 12" 0.25 114 340 0.33 277/1 580 240 63.79/74.65 2 1 277/1 11.03 15 TRANE VPEF 1-5

PTU-1.3 SERVICE 2735 320 2735 14" 0.25 116 320 0.33 277/1 740 320 63.51/72.02 2 1 277/1 11.53 15 TRANE VPEF 1-5

PTU-1.4 CUSTOMER SERVICE 950 190 950 10" 0.25 111 380 0.125 277/1 570 190 65.00/76.04 2 1 277/1 9.90 15 TRANE VPEF 1-5

PTU-1.5 BREAK ROOM 1370 165 1375 10" 0.25 111 300 0.125 277/1 465 165 64.68/78.21 2 1 277/1 9.90 15 TRANE VPEF 1-5

6.UNIT TO TIE INTO EXISTING HVAC CONTROLS SYSTEM TO INCLUDE GRAPHICS, POINTS, ALARMS, ETC. TO PROVIDE A COMPLETE AND OPERATING SYSTEM.

5.EXHAUST CFM FROM SPACE IS NOT TO EXCEED MINIMUM CFM VALUE.

4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.

3.PROVIDE PRESSURE INDEPENDENT TYPE. PROVIDE ALL NECESSARY EQUIPMENT TO ALLOW COMMUNICATION WITH BUILDING MANAGEMENT SYSTEM (BMS)

2.PROVIDE FUSED CONTROL POWER TRANSFORMER.

1.PROVIDE ELECTRONIC ROOM THERMOSTAT WITH DIGITAL DISPLAY, ADJUSTABLE SETPOINT AND NIGHT SET-BACK OVERRIDE AND CANCEL BUTTONS.

NOTES:

VAV BOX SCHEDULE

EQUIPMENT TAG LOCATION

AIR DATA INLET

SIZE DIA.

IN.

E.S.P.

(IN. WG.)

MAX.

N.C.

OPERATING

WEIGHT (LBS)

MANUFACTURER

MODEL

NUMBER

NOTES

DESIGN CFM MINIMUM CFM MAXIMUM CFM

VAV-1.1 ELEC 90 50 90 4" 0.25 29 21 TRANE VCEF 1-6

VAV-1.2 TELE 100 50 100 4" 0.25 29 21 TRANE VCEF 1-6

VAV-1.3 IT 220 70 220 4" 0.25 29 21 TRANE VCEF 1-4, 6

REVISIONS

A PREBID

CLARIFICATION

07/16/2025

A

A

A

A

VCTCO-Mech
M1.101 - FIRST LEVEL PLAN AND SCHEDULES MECHANICAL