This document is an electrical legend, notes, and abbreviations sheet for the Volusia County Tax Collector's DeLand office interior renovation and restoration project located at 123 W. Indiana Avenue in DeLand, Florida. The sheet establishes standardized electrical symbols, device designations, and abbreviations for use across the project's electrical design documents. The comprehensive legend includes symbols for receptacles, switches, lighting fixtures, fire alarm systems, data communication outlets, and various electrical equipment such as panelboards, transformers, surge protection devices, and motor controls. The document references related electrical sheets including the First Level Demolition Plan, First Level Power and Lighting Plans, Electrical Risers and Panel Schedules, and Electrical Details. The project adheres to the 2020 National Electrical Code, 2023 Florida Building Code, and Florida Administrative Code Article 61G15.32.008(4), with design compliance for voltage drop at 5% and fire alarm and detection system requirements. A prebid clarification revision was issued on July 16, 2025, with the original issue for permit dated May 15, 2025.
The lighting fixture schedule specifies LED fixtures from manufacturers including Lithonia, Gotham, and Nexa, with voltage requirements of 277V for standard fixtures and 120V for exit signs. Fixture types include 2'×4' and 2'×2' flat panel fixtures, 4" square downlights, and recessed linear LED fixtures ranging from 2' to 10' in length, with loads varying from 2.8 VA to 66.0 VA. The document establishes that all mounting hardware, wiring connections, drywall flanges, structural supports, and device plates shall be provided by the contractor, with coordination required between electrical, architectural, and interior design teams for final fixture placement and ceiling type compatibility. Alternate site, pool deck, and parking garage fixtures must be submitted with photometric studies for review during the submittal process.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SERVICE AND DISTRIBUTION
ELECTRICAL SYMBOLS LEGEND
ABBREVIATIONS
DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE , COMMUNICATIONS AND DATA OUTLETS MOUNTED TOGETHER IN A
FLUSH MOUNTED FLOOR BOX. BOX TO HAVE A LISTED DIVIDER BETWEEN LINE VOLTAGE AND
LOW VOLTAGE CONNECTIONS.
DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX
SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION
AMPACITY RATING AS INDICATED
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER -
MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH
MOUNTED FLOOR BOX
S
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING - MOUNT AT 18"
AFF, UNLESS OTHERWISE NOTED
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT
SWITCHES
TS
FS
POWER
EF
FIRE ALARM
WP
F
DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
(WP) WEATHERPROOF
(H) HORIZONTALLY MOUNTED
(C) CEILING MOUNTED
SINGLE POLE SWITCH - TOGGLE TYPE - MOUNT AT 48" AFF
(3) 3 WAY
(4) 4 WAY
(2) DOUBLE POLE
(D) DIMMER OPERATED
(M) MOTOR RATED SWITCH - 1 POLE OR 2 POLE 30 AMP WITH INTEGRAL THERMAL OVERLOADS
(OS) WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
WP
ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION SQUARE "D" CLASS#900 1-K15 W/ CLASS
9001-K25 STAINLESS STEEL COVER PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF. WITHIN
WEATHERPROOF KNOX BOX HOUSING
METER SOCKET
TIME CLOCK
LIGHTING CONTACTOR - * DENOTES CONTACTOR NUMBER
PHOTO CELL
MOTOR
(EF) EXHAUST FAN
(AHU) AIR HANDLING UNIT
CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)
WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)
SPRINKLER TAMPER SWITCH CONNECTION
SPRINKLER WATERFLOW SWITCH CONNECTION
POST INDICATOR VALVEPIV
J
PC
FIRE/SMOKE OR SMOKE DAMPER FIRE ALARM CONNECTION. PROVIDE FIRE ALARM SYSTEM
ADDRESSABLE SMOKE DETECTOR WITHIN 60" OF DAMPER LOCATION. PROVIDE 120V/20A POWER
CONNECTION TO EACH DAMPER. SMOKE DETECTOR SHALL HAVE ADDRESSABLE RELAY BASE OR
CONTROL MODULE TO ACTIVATE DAMPER SHOWN ON DRAWINGS. REFER TO MECHANICAL DRAWINGS
FOR EXACT DAMPER LOCATIONS.
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, "*" INDICATES
FIXTURES IN SENSOR'S ZONE OF CONTROL.
(DS) DAYLIGHT SENSOR
OS
BRANCH CIRCUIT PANELBOARD, 120/208V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED
FUSED DISCONNECT SWITCH
(3) NUMBER OF POLES
(30) AMPERAGE SIZE
(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
(NF) NON FUSED
(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS
NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.
COMBINATION STARTER/DISCONNECT SWITCH
(3) NUMBER OF POLES
(30) AMPERAGE SIZE
(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
(NF) NON FUSED
(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS
NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.
UTILITY TRANSFORMER
SURGE PROTECTION DEVICE
GROUND BARGB
LC-*
J
TC
(REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT)
BRANCH CIRCUIT PANELBOARD, 277/480V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED
SPD
DRY TYPE TRANSFORMER
H
RTI
"FACP"
DH
FAJB
FAAP
MANUAL PULL STATION - MOUNT AT 48" AFF
COMBINATION AUDIBLE/VISUAL SIGNALING UNIT- SPEAKER/FLASHING "FIRE" LIGHT WALL - MOUNTED
96" AFF UNLESS OTHERWISE NOTED. 75 CANDELA UNLESS NOTED OTHERWISE
(WP) WEATHER PROOF
(A) AUDIBLE ONLY.
COMBINATION AUDIBLE/VISUAL SIGNALING UNIT CEILING MOUNTED- SPEAKER/FLASHING "FIRE" LIGHT
75 CANDELA UNLESS NOTED OTHERWISE
(WP) WEATHER PROOF
(A) AUDIBLE ONLY.
VISUAL SIGNALING UNIT, WALL MOUNTED- FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)
75 CANDELA, UNLESS NOTED OTHERWISE.
VISUAL SIGNALING UNIT, CEILING MOUNTED - FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)
75 CANDELA, UNLESS NOTED OTHERWISE
PHOTOELECTRIC DUCT SMOKE DETECTOR, R=RETURN / S=SUPPLY
FIRE ALARM SHUTDOWN OR CONTROL RELAY
DUCT DETECTOR REMOTE TROUBLE INDICATOR - MOUNT ADJACENT TO UNIT
FIRE ALARM HEAT DETECTOR. (2) INDICATES TO PROVIDE DUAL CONVERTIBLE CONTACTS
CEILING OR WALL MOUNTED SMOKE DETECTOR. SMOKE DETECTOR SHALL BE TIED TO MAIN FIRE
ALARM SYSTEM.
(2) PROVIDE DUAL CONTACT.
(CO) CARBON MONOXIDE DETECTOR.
(LF) LOW-FREQUENCY SOUNDER BASE WITH INTEGRAL BATTERY BACK UP.
DOOR HOLDER
FIRE ALARM CONTROL PANEL - FLUSH MOUNTED
FIRE ALARM JUNCTION BOX
REMOTE FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
SPRINKLER TAMPER SWITCH CONNECTION
S
R
F
F
F
F
F
C
R
CEILING MOUNTED DAYLIGHT SENSOR, "*" INDICATES FIXTURES IN SENSOR'S ZONE
OF CONTROL. SENSOR TO AUTO-DIM FIXTURES WITHIN BUILDING CODE PRESCRIBED
DAYLIGHT ZONE.
DS
FSD
VARIABLE FREQUENCY DRIVEVFD
FATC FIRE ALARM TERMINAL CABINET, FLUSHED MOUNTED
DDS HEARING IMPAIRED DUAL SMOKE SENSOR AND STROBE
TFR HEARING IMPAIRED LOW VOLTAGE TRANSFORMER FOR DOORBELL SYSTEM
"DO NOT USE" ELEVATOR WARNING LIGHT. BY ELEVATOR CONTRACTORWL
CEILING MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)J
C
DATA/COMM
DATA/COMM OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANG JUNCTION BOX. MOUNT AT 18"
AFF, UNLESS OTHERWISE NOTED. PROVIDE BLANK STAINLESS STEEL COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING, OR AS
NOTED; INSTALL PULL WIRE.
(WH) WALL MOUNTED
(AC) 6" ABOVE COUNTER BACK SPLASH
(TV) TV - REFER TO ARCHITECTURAL DRAWINGS FOR HEIGHT
DATA/COMM OUTLET FLUSH MOUNTED IN FLOOR
TELEVISION OUTLET - MOUNT 18 " ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED
STRUCTURED MEDIA COMPONENT FLUSH MTD. BOX FOR RESIDENTIAL USE PROVIDED AND INSTALLED
BY CONTRACTOR - MOUNT 48" AFF TO BOARD, UNLESS OTHERWISE NOTED
TELEPHONE TERMINAL BOARD
SMC
TV
C
FIRE ALARM SYSTEM, RESIDENTIAL UNIT MINI-HORN LOW FREQUENCY SOUNDER (520HZ) - MOUNT AT
96" AFF TO TOP OF SOUNDER
S
CARD READER - MOUNT 48" AFF, UNLESS OTHERWISE NOTEDCR
A - AMPERES
A/C - AIR CONDITIONING
AC - ALTERNATING CURRENT
ADA - AMERICANS WITH DISABILITIES ACT
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLING UNIT
ATS - AUTOMATIC TRANSFER SWITCH
AWG - AMERICAN WIRE GAUGE
BFG - BELOW FINISHED GROUND
C - CONDUIT
COND - CONDUIT
CH - COUNTER HEIGHT
CONC - CONCRETE
CU - COPPER
DISC - DISCONNECT
DBL - DOUBLE
ECB - ENCLOSED CIRCUIT BREAKER
ELEC - ELECTRICAL
EM - EMERGENCY
EF - EXHAUST FAN
EPO - EMERGENCY POWER OFF
EV - ELECTRIC VEHICLE
EWC - ELECTRIC WATER COOLER
EX - EXISTING
EXT - EXTENSION
FA - FIRE ALARM
FACP - FIRE ALARM CONTROL PANEL
FBC - FLORIDA BUILDING CODE
GACP - GENERATOR ANNUNCIATOR CONTROL PANEL
G - GROUND
GND - GROUND
GFI - GROUND FAULT INTERRUPTER
GRC - GALVANIZED RIGID CONDUIT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
IAW - IN ACCORDANCE WITH
IWH - INSTANTANEOUS WATER HEATER
I.G. - ISOLATED GROUND
J - JUNCTION
KAIC - (THOUSAND) AMPERE INTERRUPTING CAPACITY
KCMIL - THOUSAND CIRCULAR MILLS
KVA - KILOVOLT-AMPERES
KW - KILOWATT
LTG - LIGHTING
LTS - LIGHTING
MCB - MAIN CIRCUIT BREAKER
MH - MOUNTING HEIGHT
MLO - MAIN LUG ONLY
N - NEUTRAL
NA - NOT APPLICABLE
NEC - NATIONAL ELECTRICAL CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
NF - NON-FUSED
NIC - NOT IN CONTRACT
NL - NIGHT LIGHT
O.C. - ON CENTER
P - POLE
PNL - PANELBOARD
PVC - POLYVINYL CHLORIDE
RGS - RIGID GALVANIZED STEEL
RM - ROOM
SPEC - SPECIFICATION
SPD - SURGE PROTECTION DEVICE
SS - STAINLESS STEEL
SWBD - SWITCHBOARD
TYP - TYPICAL
UON - UNLESS OTHERWISE NOTED
UNV - UNIVERSAL
V - VOLTS
W - WIRE
WP - WEATHERPROOF
T
TS
GACP
GENERATOR ANNUNCIATOR CONTROL PANEL - FLUSH MOUNTED
GENERAL NOTE
1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY
CONSERVATION C405.6.3 AND 2020 NEC 210.19 WITH
REGARDS TO VOLTAGE DROP (5%).
2. THE ELECTRICAL DESIGN HAS BEEN DESIGNED IN
ACCORDANCE WITH THE 2020 NATIONAL ELECTRICAL CODE,
2023 FLORIDA BUILDING CODE.
FLORIDA ADMINISTRATIVE CODE
ARTICLE 61G15.32.008(4)a-o
61G15-32.008(4) - TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND DETECTION SYSTEMS
ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING
INFORMATION WHEN APPLICABLE:
(a) SYMBOL LEGEND IS FOUND ON SHEET E0.001 AND SYSTEM RISER IS FOUND ON SHEET
E6.000
(b) LOCATIONS FOR INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS ARE
FOUND ON FLOOR PLAN SHEETS E1.101
(c) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS ARE FOUND IN THE SYMBOL
LEGEND ON SHEET E0.001
(d) CIRCUITS SHALL BE CLASS B TYPE, AS PER SPECIFICATION SECTION 283000
(e) IDENTIFICATION OF FUNCTIONS REQUIRED BY THE ALARM AND CONTROL SYSTEMS IS
FOUND ON SHEET E6.000
(f) FIRE ALARM SHALL BE ADDRESSABLE AND ZONING IS INDICATED IN SPECIFICATION
SECTION 283000
(g) SURGE PROTECTION DEVICES ARE FOUND ON ELECTRICAL RISER ON SHEET E6.000
(h) DEVICES THAT ARE SUBJECT TO ENVIRONMENTAL FACTORS AND REQUIREMENTS FOR
PROTECTION ARE FOUND ON FLOOR PLAN SHEETS E1.101
(i) SITE PLAN AND ANY FIRE ALARM DEVICES REQUIRED OUTSIDE ARE NOT APPLICABLE
(j) SMOKE DETECTION DEVICES TO MITIGATE OBSTRUCTIONS ARE NOT APPLICABLE
(k) SMOKE DETECTION DEVICES TO MITIGATE DETECTION PROBLEMS WHERE SMOKE
STRATIFICATION IS ANTICIPATED ARE NOT APPLICABLE.
(l) DESIGN GUIDES AND STANDARDS USED FOR PERFORMANCE BASED FIRE ALARM
SYSTEM ARE FOUND ON SHEET E6.000
(m) INDICATION OF GENERAL EVACUATION SIGNAL OR A ZONED EVACUATION FOR ALL
HIGH-RISE BUILDINGS OR MULTI-TENANTED PROPERTIES IS NOT APPLICABLE
(n) WIRING REQUIREMENTS AND BURIAL DEPTH FOR UNDERGROUND, WET LOCATIONS
AND CAMPUS STYLE WIRING ARE NOT APPLICABLE
(o) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND OWNER INSTRUCTIONS ARE INDICATED IN SPECIFICATION
SECTION 283000
LIGHTING (SEE LIGHTING FIXTURE SCHEDULE)
2'X 2' LIGHT FIXTURE
EMERGENCY 2' x 2' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
2'X 4' LIGHT FIXTURE
EMERGENCY 2' x 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
1'X 4' LIGHT FIXTURE
EMERGENCY 1'X 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
LIGHT FIXTURE - WALL MOUNTED
EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR
STRIP LIGHT
EMERGENCY STRIP LIGHT CONNECTED TO EMERGENCY GENERATOR
DOWNLIGHT LIGHT FIXTURE
LIGHT FIXTURE - WALL MOUNTED
WALL WASH / ACCENT FIXTURE - CEILING MOUNTED
EMERGENCY DOWNLIGHT LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR
EXIT SIGN - SINGLE FACE ARROW INDICATES DIRECTION - CEILING MOUNTED-WITH INTEGRAL
EMERGENCY BACKUP
EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION - WALL MOUNTED - WITH INTEGRAL
EMERGENCY BACKUP
EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION - CEILING MOUNTED - WITH INTEGRAL
EMERGENCY BACKUP
EMERGENCY LIGHT WITH INTEGRAL EMERGENCY BACKUP - DUAL HEAD
DECORATIVE PENDANT
LIGHT TRACK - CEILING MOUNTED
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
7/17/2025 1:42:28 PMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
ELECTRICAL LEGEND,
NOTES &
ABBREVIATIONS
E0.001
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
IE - ELECTRICAL SHEET LIST
Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline
E0.001 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL
E1.100 FIRST LEVEL DEMOLITION PLAN ELECTRICAL 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E1.101 FIRST LEVEL PLAN POWER 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL
E1.102 FIRST LEVEL PLAN LIGHTING 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL
E6.000 ELECTRICAL RISERS AND PANEL SCHEDULES 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E8.000 ELECTRICAL DETAILS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
Grand total: 6
6. ALL SITE, POOL DECK, AND PARKING GARAGE ALTERNATE FIXTURES SHALL BE SUBMITTED WITH PHOTOMETRIC STUDY TO BE REVIEWED AS PART OF THE SUBMITTAL
PROCESS.
5. COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL AND INTERIOR DRAWING'S REFLECTED CEILING PLANS AND PROVIDE FIXTURE
TRIM AS REQUIRED.
4. REFER TO ARCHITECTURAL REFLECTED CEILING LIGHTING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.
3. COORDINATE THE ACTUAL TYPE OF LIGHTING FIXTURES WITH ARCHITECTURAL LIGHTING SCHEDULES, INTERIOR DESIGN LIGHTING SCHEDULE/DRAWINGS AND OWNER
LIGHTING FIXTURE STANDARD CRITERIA AS REQUIRED.
2. PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN REFLIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE
INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.
1. PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB, AND STRUCTURAL STEEL
LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENERS AND UL APPROVED CONNECTORS.
LIGHTING FIXTURE SCHEDULE NOTES
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS LOAD VOLTS REMARKS
A
LITHONIA LTG:
CPX-2X4-AL08-80CRI-SWW7-SWL-MVOLT
2'x4' FLAT PANEL LED 47.9 VA 277 AS APPROVED BY OWNER
B
GOTHAM LTG:
IVO4SQS-D-07LM-35K-80CRI-MWD-MIN10-MVOL
T-EZT-NCH-P-AR-LSS-F
4" SQUARE DOWNLIGHT LED 7.8 VA 277 AS APPROVED BY OWNER
C2 SAME AS TYPE 'C4' EXCEPT 2' IN LENGTH 2' RECESSED LINEAR LED 13.2 VA 277 AS APPROVED BY OWNER
C4
NEXA LTG:
807-NX3-RS-4-48-RECESSED-0-IP-AE-2-Z-SO-C3
4' RECESSED LINEAR LED 26.4 VA 277 AS APPROVED BY OWNER
C6 SAME AS TYPE 'C4' EXCEPT 6' IN LENGTH 6' RECESSED LINEAR LED 39.6 VA 277 AS APPROVED BY OWNER
C8 SAME AS TYPE 'C4' EXCEPT 8' IN LENGTH 8' RECESSED LINEAR LED 52.8 VA 277 AS APPROVED BY OWNER
C10 SAME AS TYPE 'C4' EXCEPT 10' IN LENGTH 10' RECESSED LINEAR LED 66.0 VA 277 AS APPROVED BY OWNER
EX LITHONIA LTG: EDG-1/2-R EDGE LITE EXIT SIGN LED 2.8 VA 277 AS APPROVED BY OWNER
Z INTRA LTG: ZOE S DUO Z3 PENDANT LIGHT LED 12.0 VA 277
REMOTE DRIVER TO BE ORDERED
SEPARATELY AND INSTALLED ABOVE
PENDANT. AS APPROVED BY OWNER.
REVISIONS
A PREBID
CLARIFICATION
07/16/2025
A
| VCTCO-Elec |
| E0.001 - ELECTRICAL LEGEND, NOTES & ABBREVIATIONS |