This document is an electrical legend, notes, and abbreviations sheet for the Volusia County Tax Collector's DeLand office interior renovation and restoration project located at 123 W. Indiana Avenue in DeLand, Florida. The sheet establishes standardized electrical symbols, device designations, and abbreviations for use across the project's electrical design documents. The comprehensive legend includes symbols for receptacles, switches, lighting fixtures, fire alarm systems, data communication outlets, and various electrical equipment such as panelboards, transformers, surge protection devices, and motor controls. The document references related electrical sheets including the First Level Demolition Plan, First Level Power and Lighting Plans, Electrical Risers and Panel Schedules, and Electrical Details. The project adheres to the 2020 National Electrical Code, 2023 Florida Building Code, and Florida Administrative Code Article 61G15.32.008(4), with design compliance for voltage drop at 5% and fire alarm and detection system requirements. A prebid clarification revision was issued on July 16, 2025, with the original issue for permit dated May 15, 2025.

The lighting fixture schedule specifies LED fixtures from manufacturers including Lithonia, Gotham, and Nexa, with voltage requirements of 277V for standard fixtures and 120V for exit signs. Fixture types include 2'×4' and 2'×2' flat panel fixtures, 4" square downlights, and recessed linear LED fixtures ranging from 2' to 10' in length, with loads varying from 2.8 VA to 66.0 VA. The document establishes that all mounting hardware, wiring connections, drywall flanges, structural supports, and device plates shall be provided by the contractor, with coordination required between electrical, architectural, and interior design teams for final fixture placement and ceiling type compatibility. Alternate site, pool deck, and parking garage fixtures must be submitted with photometric studies for review during the submittal process.

View the file

Other files

File Type Posted
Tax_Collector_Interior_Renovations_and_Restoration_(Addendum_#3_Revision).pdf PDF
M1.101_-_FIRST_LEVEL_PLAN_AND_SCHEDULES_MECHANICAL.pdf PDF
E1.102_-_FIRST_LEVEL_PLAN_LIGHTING.pdf PDF
E1.101_-_FIRST_LEVEL_PLAN_POWER.pdf PDF
Attachment_E_-_Additional_Renderings.pdf PDF
Attachment_D_-_Fire_Alarm_Panel.pdf PDF
Tax_Collector_Interior_Renovations_and_Restoration.pdf PDF
MASTER_Construction_Contract.pdf PDF
Attachment_C_-_Staging_2.png PNG image
Attachment_B_-_Staging_1.png PNG image
Attachment_A_-_Parking.png PNG image
COV_Division_27,_IT_Systems_Design_and_Installation_Guidelines_for_A-E.pdf PDF
Sales_Tax_Exemption_Procedure.pdf PDF
PRIME-SUB_FORM.xls XLS spreadsheet
VC_Tax_Collector_DeLand_Office_Project_Manuals_5.15.2025.pdf PDF
VC_Tax_Collector_DeLand_Office_Renovation_Bid_Set_5.15.2025.pdf PDF
Payment_and_Performance_Bond.pdf PDF
Basic_Insurance_Requirements.pdf PDF
Special_Conditions.pdf PDF
Bid_Documents.pdf PDF
VCTCO_Architectural.pdf PDF
VCTCO_Volume_2_specs.pdf PDF
Mechanical.pdf PDF
VCTCO_Volume_1_specs.pdf PDF
Fire_Protection.pdf PDF
Electrical.pdf PDF
2025-05-15_-_BID_&_PERMIT_SET_-_Telecommunications.pdf PDF
VOLUSIA_COUNTY_TC_Form_C402.pdf PDF
Plumbing.pdf PDF
staging_(1).png PNG image
Pre-Bid_Meeting_Invitee_Listing.docx DOCX document
Staging.png PNG image
Parking.png PNG image
PRIME-SUB_FORM_for_Contractors_rev._01.15.2025_(lock_before_publishing)_(1).xls XLS spreadsheet
SPECIAL_CONDITIONS_FOR_BIDDERS.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SERVICE AND DISTRIBUTION

ELECTRICAL SYMBOLS LEGEND

ABBREVIATIONS

DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE , COMMUNICATIONS AND DATA OUTLETS MOUNTED TOGETHER IN A

FLUSH MOUNTED FLOOR BOX. BOX TO HAVE A LISTED DIVIDER BETWEEN LINE VOLTAGE AND

LOW VOLTAGE CONNECTIONS.

DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX

SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION

AMPACITY RATING AS INDICATED

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER -

MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH

MOUNTED FLOOR BOX

S

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING - MOUNT AT 18"

AFF, UNLESS OTHERWISE NOTED

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT

SWITCHES

TS

FS

POWER

EF

FIRE ALARM

WP

F

DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

(WP) WEATHERPROOF

(H) HORIZONTALLY MOUNTED

(C) CEILING MOUNTED

SINGLE POLE SWITCH - TOGGLE TYPE - MOUNT AT 48" AFF

(3) 3 WAY

(4) 4 WAY

(2) DOUBLE POLE

(D) DIMMER OPERATED

(M) MOTOR RATED SWITCH - 1 POLE OR 2 POLE 30 AMP WITH INTEGRAL THERMAL OVERLOADS

(OS) WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH

WP

ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION SQUARE "D" CLASS#900 1-K15 W/ CLASS

9001-K25 STAINLESS STEEL COVER PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF. WITHIN

WEATHERPROOF KNOX BOX HOUSING

METER SOCKET

TIME CLOCK

LIGHTING CONTACTOR - * DENOTES CONTACTOR NUMBER

PHOTO CELL

MOTOR

(EF) EXHAUST FAN

(AHU) AIR HANDLING UNIT

CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)

WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)

SPRINKLER TAMPER SWITCH CONNECTION

SPRINKLER WATERFLOW SWITCH CONNECTION

POST INDICATOR VALVEPIV

J

PC

FIRE/SMOKE OR SMOKE DAMPER FIRE ALARM CONNECTION. PROVIDE FIRE ALARM SYSTEM

ADDRESSABLE SMOKE DETECTOR WITHIN 60" OF DAMPER LOCATION. PROVIDE 120V/20A POWER

CONNECTION TO EACH DAMPER. SMOKE DETECTOR SHALL HAVE ADDRESSABLE RELAY BASE OR

CONTROL MODULE TO ACTIVATE DAMPER SHOWN ON DRAWINGS. REFER TO MECHANICAL DRAWINGS

FOR EXACT DAMPER LOCATIONS.

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, "*" INDICATES

FIXTURES IN SENSOR'S ZONE OF CONTROL.

(DS) DAYLIGHT SENSOR

OS

BRANCH CIRCUIT PANELBOARD, 120/208V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED

FUSED DISCONNECT SWITCH

(3) NUMBER OF POLES

(30) AMPERAGE SIZE

(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.

(NF) NON FUSED

(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS

NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.

COMBINATION STARTER/DISCONNECT SWITCH

(3) NUMBER OF POLES

(30) AMPERAGE SIZE

(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.

(NF) NON FUSED

(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS

NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.

UTILITY TRANSFORMER

SURGE PROTECTION DEVICE

GROUND BARGB

LC-*

J

TC

(REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT)

BRANCH CIRCUIT PANELBOARD, 277/480V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED

SPD

DRY TYPE TRANSFORMER

H

RTI

"FACP"

DH

FAJB

FAAP

MANUAL PULL STATION - MOUNT AT 48" AFF

COMBINATION AUDIBLE/VISUAL SIGNALING UNIT- SPEAKER/FLASHING "FIRE" LIGHT WALL - MOUNTED

96" AFF UNLESS OTHERWISE NOTED. 75 CANDELA UNLESS NOTED OTHERWISE

(WP) WEATHER PROOF

(A) AUDIBLE ONLY.

COMBINATION AUDIBLE/VISUAL SIGNALING UNIT CEILING MOUNTED- SPEAKER/FLASHING "FIRE" LIGHT

75 CANDELA UNLESS NOTED OTHERWISE

(WP) WEATHER PROOF

(A) AUDIBLE ONLY.

VISUAL SIGNALING UNIT, WALL MOUNTED- FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)

75 CANDELA, UNLESS NOTED OTHERWISE.

VISUAL SIGNALING UNIT, CEILING MOUNTED - FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)

75 CANDELA, UNLESS NOTED OTHERWISE

PHOTOELECTRIC DUCT SMOKE DETECTOR, R=RETURN / S=SUPPLY

FIRE ALARM SHUTDOWN OR CONTROL RELAY

DUCT DETECTOR REMOTE TROUBLE INDICATOR - MOUNT ADJACENT TO UNIT

FIRE ALARM HEAT DETECTOR. (2) INDICATES TO PROVIDE DUAL CONVERTIBLE CONTACTS

CEILING OR WALL MOUNTED SMOKE DETECTOR. SMOKE DETECTOR SHALL BE TIED TO MAIN FIRE

ALARM SYSTEM.

(2) PROVIDE DUAL CONTACT.

(CO) CARBON MONOXIDE DETECTOR.

(LF) LOW-FREQUENCY SOUNDER BASE WITH INTEGRAL BATTERY BACK UP.

DOOR HOLDER

FIRE ALARM CONTROL PANEL - FLUSH MOUNTED

FIRE ALARM JUNCTION BOX

REMOTE FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

SPRINKLER TAMPER SWITCH CONNECTION

S

R

F

F

F

F

F

C

R

CEILING MOUNTED DAYLIGHT SENSOR, "*" INDICATES FIXTURES IN SENSOR'S ZONE

OF CONTROL. SENSOR TO AUTO-DIM FIXTURES WITHIN BUILDING CODE PRESCRIBED

DAYLIGHT ZONE.

DS

FSD

VARIABLE FREQUENCY DRIVEVFD

FATC FIRE ALARM TERMINAL CABINET, FLUSHED MOUNTED

DDS HEARING IMPAIRED DUAL SMOKE SENSOR AND STROBE

TFR HEARING IMPAIRED LOW VOLTAGE TRANSFORMER FOR DOORBELL SYSTEM

"DO NOT USE" ELEVATOR WARNING LIGHT. BY ELEVATOR CONTRACTORWL

CEILING MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)J

C

DATA/COMM

DATA/COMM OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANG JUNCTION BOX. MOUNT AT 18"

AFF, UNLESS OTHERWISE NOTED. PROVIDE BLANK STAINLESS STEEL COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING, OR AS

NOTED; INSTALL PULL WIRE.

(WH) WALL MOUNTED

(AC) 6" ABOVE COUNTER BACK SPLASH

(TV) TV - REFER TO ARCHITECTURAL DRAWINGS FOR HEIGHT

DATA/COMM OUTLET FLUSH MOUNTED IN FLOOR

TELEVISION OUTLET - MOUNT 18 " ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED

STRUCTURED MEDIA COMPONENT FLUSH MTD. BOX FOR RESIDENTIAL USE PROVIDED AND INSTALLED

BY CONTRACTOR - MOUNT 48" AFF TO BOARD, UNLESS OTHERWISE NOTED

TELEPHONE TERMINAL BOARD

SMC

TV

C

FIRE ALARM SYSTEM, RESIDENTIAL UNIT MINI-HORN LOW FREQUENCY SOUNDER (520HZ) - MOUNT AT

96" AFF TO TOP OF SOUNDER

S

CARD READER - MOUNT 48" AFF, UNLESS OTHERWISE NOTEDCR

A - AMPERES

A/C - AIR CONDITIONING

AC - ALTERNATING CURRENT

ADA - AMERICANS WITH DISABILITIES ACT

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLING UNIT

ATS - AUTOMATIC TRANSFER SWITCH

AWG - AMERICAN WIRE GAUGE

BFG - BELOW FINISHED GROUND

C - CONDUIT

COND - CONDUIT

CH - COUNTER HEIGHT

CONC - CONCRETE

CU - COPPER

DISC - DISCONNECT

DBL - DOUBLE

ECB - ENCLOSED CIRCUIT BREAKER

ELEC - ELECTRICAL

EM - EMERGENCY

EF - EXHAUST FAN

EPO - EMERGENCY POWER OFF

EV - ELECTRIC VEHICLE

EWC - ELECTRIC WATER COOLER

EX - EXISTING

EXT - EXTENSION

FA - FIRE ALARM

FACP - FIRE ALARM CONTROL PANEL

FBC - FLORIDA BUILDING CODE

GACP - GENERATOR ANNUNCIATOR CONTROL PANEL

G - GROUND

GND - GROUND

GFI - GROUND FAULT INTERRUPTER

GRC - GALVANIZED RIGID CONDUIT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

IAW - IN ACCORDANCE WITH

IWH - INSTANTANEOUS WATER HEATER

I.G. - ISOLATED GROUND

J - JUNCTION

KAIC - (THOUSAND) AMPERE INTERRUPTING CAPACITY

KCMIL - THOUSAND CIRCULAR MILLS

KVA - KILOVOLT-AMPERES

KW - KILOWATT

LTG - LIGHTING

LTS - LIGHTING

MCB - MAIN CIRCUIT BREAKER

MH - MOUNTING HEIGHT

MLO - MAIN LUG ONLY

N - NEUTRAL

NA - NOT APPLICABLE

NEC - NATIONAL ELECTRICAL CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

NF - NON-FUSED

NIC - NOT IN CONTRACT

NL - NIGHT LIGHT

O.C. - ON CENTER

P - POLE

PNL - PANELBOARD

PVC - POLYVINYL CHLORIDE

RGS - RIGID GALVANIZED STEEL

RM - ROOM

SPEC - SPECIFICATION

SPD - SURGE PROTECTION DEVICE

SS - STAINLESS STEEL

SWBD - SWITCHBOARD

TYP - TYPICAL

UON - UNLESS OTHERWISE NOTED

UNV - UNIVERSAL

V - VOLTS

W - WIRE

WP - WEATHERPROOF

T

TS

GACP

GENERATOR ANNUNCIATOR CONTROL PANEL - FLUSH MOUNTED

GENERAL NOTE

1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY

CONSERVATION C405.6.3 AND 2020 NEC 210.19 WITH

REGARDS TO VOLTAGE DROP (5%).

2. THE ELECTRICAL DESIGN HAS BEEN DESIGNED IN

ACCORDANCE WITH THE 2020 NATIONAL ELECTRICAL CODE,

2023 FLORIDA BUILDING CODE.

FLORIDA ADMINISTRATIVE CODE

ARTICLE 61G15.32.008(4)a-o

61G15-32.008(4) - TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND DETECTION SYSTEMS

ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING

INFORMATION WHEN APPLICABLE:

(a) SYMBOL LEGEND IS FOUND ON SHEET E0.001 AND SYSTEM RISER IS FOUND ON SHEET

E6.000

(b) LOCATIONS FOR INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS ARE

FOUND ON FLOOR PLAN SHEETS E1.101

(c) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS ARE FOUND IN THE SYMBOL

LEGEND ON SHEET E0.001

(d) CIRCUITS SHALL BE CLASS B TYPE, AS PER SPECIFICATION SECTION 283000

(e) IDENTIFICATION OF FUNCTIONS REQUIRED BY THE ALARM AND CONTROL SYSTEMS IS

FOUND ON SHEET E6.000

(f) FIRE ALARM SHALL BE ADDRESSABLE AND ZONING IS INDICATED IN SPECIFICATION

SECTION 283000

(g) SURGE PROTECTION DEVICES ARE FOUND ON ELECTRICAL RISER ON SHEET E6.000

(h) DEVICES THAT ARE SUBJECT TO ENVIRONMENTAL FACTORS AND REQUIREMENTS FOR

PROTECTION ARE FOUND ON FLOOR PLAN SHEETS E1.101

(i) SITE PLAN AND ANY FIRE ALARM DEVICES REQUIRED OUTSIDE ARE NOT APPLICABLE

(j) SMOKE DETECTION DEVICES TO MITIGATE OBSTRUCTIONS ARE NOT APPLICABLE

(k) SMOKE DETECTION DEVICES TO MITIGATE DETECTION PROBLEMS WHERE SMOKE

STRATIFICATION IS ANTICIPATED ARE NOT APPLICABLE.

(l) DESIGN GUIDES AND STANDARDS USED FOR PERFORMANCE BASED FIRE ALARM

SYSTEM ARE FOUND ON SHEET E6.000

(m) INDICATION OF GENERAL EVACUATION SIGNAL OR A ZONED EVACUATION FOR ALL

HIGH-RISE BUILDINGS OR MULTI-TENANTED PROPERTIES IS NOT APPLICABLE

(n) WIRING REQUIREMENTS AND BURIAL DEPTH FOR UNDERGROUND, WET LOCATIONS

AND CAMPUS STYLE WIRING ARE NOT APPLICABLE

(o) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND OWNER INSTRUCTIONS ARE INDICATED IN SPECIFICATION

SECTION 283000

LIGHTING (SEE LIGHTING FIXTURE SCHEDULE)

2'X 2' LIGHT FIXTURE

EMERGENCY 2' x 2' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

2'X 4' LIGHT FIXTURE

EMERGENCY 2' x 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

1'X 4' LIGHT FIXTURE

EMERGENCY 1'X 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

LIGHT FIXTURE - WALL MOUNTED

EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR

STRIP LIGHT

EMERGENCY STRIP LIGHT CONNECTED TO EMERGENCY GENERATOR

DOWNLIGHT LIGHT FIXTURE

LIGHT FIXTURE - WALL MOUNTED

WALL WASH / ACCENT FIXTURE - CEILING MOUNTED

EMERGENCY DOWNLIGHT LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR

EXIT SIGN - SINGLE FACE ARROW INDICATES DIRECTION - CEILING MOUNTED-WITH INTEGRAL

EMERGENCY BACKUP

EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION - WALL MOUNTED - WITH INTEGRAL

EMERGENCY BACKUP

EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION - CEILING MOUNTED - WITH INTEGRAL

EMERGENCY BACKUP

EMERGENCY LIGHT WITH INTEGRAL EMERGENCY BACKUP - DUAL HEAD

DECORATIVE PENDANT

LIGHT TRACK - CEILING MOUNTED

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

7/17/2025 1:42:28 PMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

ELECTRICAL LEGEND,

NOTES &

ABBREVIATIONS

E0.001

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

IE - ELECTRICAL SHEET LIST

Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline

E0.001 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL

E1.100 FIRST LEVEL DEMOLITION PLAN ELECTRICAL 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E1.101 FIRST LEVEL PLAN POWER 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL

E1.102 FIRST LEVEL PLAN LIGHTING 05.15.2025 ISSUE FOR PERMIT A 07/16/2025 PREBID CLARIFICATION ELECTRICAL

E6.000 ELECTRICAL RISERS AND PANEL SCHEDULES 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E8.000 ELECTRICAL DETAILS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

Grand total: 6

6. ALL SITE, POOL DECK, AND PARKING GARAGE ALTERNATE FIXTURES SHALL BE SUBMITTED WITH PHOTOMETRIC STUDY TO BE REVIEWED AS PART OF THE SUBMITTAL

PROCESS.

5. COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL AND INTERIOR DRAWING'S REFLECTED CEILING PLANS AND PROVIDE FIXTURE

TRIM AS REQUIRED.

4. REFER TO ARCHITECTURAL REFLECTED CEILING LIGHTING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.

3. COORDINATE THE ACTUAL TYPE OF LIGHTING FIXTURES WITH ARCHITECTURAL LIGHTING SCHEDULES, INTERIOR DESIGN LIGHTING SCHEDULE/DRAWINGS AND OWNER

LIGHTING FIXTURE STANDARD CRITERIA AS REQUIRED.

2. PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN REFLIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE

INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.

1. PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB, AND STRUCTURAL STEEL

LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENERS AND UL APPROVED CONNECTORS.

LIGHTING FIXTURE SCHEDULE NOTES

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS LOAD VOLTS REMARKS

A

LITHONIA LTG:

CPX-2X4-AL08-80CRI-SWW7-SWL-MVOLT

2'x4' FLAT PANEL LED 47.9 VA 277 AS APPROVED BY OWNER

B

GOTHAM LTG:

IVO4SQS-D-07LM-35K-80CRI-MWD-MIN10-MVOL

T-EZT-NCH-P-AR-LSS-F

4" SQUARE DOWNLIGHT LED 7.8 VA 277 AS APPROVED BY OWNER

C2 SAME AS TYPE 'C4' EXCEPT 2' IN LENGTH 2' RECESSED LINEAR LED 13.2 VA 277 AS APPROVED BY OWNER

C4

NEXA LTG:

807-NX3-RS-4-48-RECESSED-0-IP-AE-2-Z-SO-C3

4' RECESSED LINEAR LED 26.4 VA 277 AS APPROVED BY OWNER

C6 SAME AS TYPE 'C4' EXCEPT 6' IN LENGTH 6' RECESSED LINEAR LED 39.6 VA 277 AS APPROVED BY OWNER

C8 SAME AS TYPE 'C4' EXCEPT 8' IN LENGTH 8' RECESSED LINEAR LED 52.8 VA 277 AS APPROVED BY OWNER

C10 SAME AS TYPE 'C4' EXCEPT 10' IN LENGTH 10' RECESSED LINEAR LED 66.0 VA 277 AS APPROVED BY OWNER

EX LITHONIA LTG: EDG-1/2-R EDGE LITE EXIT SIGN LED 2.8 VA 277 AS APPROVED BY OWNER

Z INTRA LTG: ZOE S DUO Z3 PENDANT LIGHT LED 12.0 VA 277

REMOTE DRIVER TO BE ORDERED

SEPARATELY AND INSTALLED ABOVE

PENDANT. AS APPROVED BY OWNER.

REVISIONS

A PREBID

CLARIFICATION

07/16/2025

A

VCTCO-Elec
E0.001 - ELECTRICAL LEGEND, NOTES & ABBREVIATIONS