Mechanical.pdf
PDF 2 MB Posted
- Solicitation number
- 25-B-127LL
- Issued by
- Volusia County, Florida
About this file
These mechanical design documents are for the Volusia County Tax Collector's Office Interior Renovation project located in DeLand, Florida. The documents include detailed mechanical plans, legends, abbreviations, and installation details for HVAC systems, specifically focusing on the first-level demolition and new work mechanical plans. The plans outline the mechanical system components including VAV (Variable Air Volume) terminal units, parallel fan-powered terminal units, air devices, and ductwork configurations for various rooms such as waiting areas, offices, customer service spaces, and mechanical rooms. The project is dated for permit issue on 05.15.2025 and includes comprehensive mechanical system schedules detailing equipment specifications, airflow requirements, and installation guidelines.
The mechanical plans specify technical details for multiple HVAC components, including five parallel fan-powered terminal units (PTU-1.1 through PTU-1.5) and three VAV boxes (VAV-1.1 through VAV-1.3) manufactured by Trane. The equipment is designed with specific performance parameters, such as design CFM (cubic feet per minute), minimum and maximum airflow, and electrical specifications. The documents include detailed installation instructions for ductwork, including hanger details, flexible duct installation guidelines, and specific mounting requirements for sensors and devices. The mechanical system is designed to provide precise air distribution and temperature control throughout the renovated Tax Collector office space, with attention to proper ventilation, air quality, and energy efficiency.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M
ABBREVIATIONSMECHANICAL LEGEND
RADIATION DAMPER INSTALLED IN DUCT.
RADIATION DAMPER INSTALLED IN AIR DEVICE.
OPENING IN WALL ABOVE CEILING.
EQUIPMENT TAG.
HEATING WATER SUPPLY PIPING.
RECTANGULAR BRANCH DUCT CONNECTION.
L=1/4W, Min. 4"
HEATING WATER RETURN PIPING.
CONDENSATE DRAIN PIPING.
CHILLED WATER RETURN PIPING.
WALL MOUNTED DDC TEMPERATURE SENSOR
MOUNT 4'-0" ABOVE FINISHED FLOOR.
WALL MOUNTED DDC HUMIDITY SENSOR
MOUNT 4'-0" ABOVE FINISHED FLOOR.
INDICATES POINT OF CONNECTION BETWEEN NEW
AND EXISTING.
IDENTIFICATION TARGET.
A = DETAIL NUMBER.
B = SHEET NUMBER ON WHICH DETAIL IS LOCATED.
CONDENSER WATER SUPPLY PIPING.
CONDENSER WATER RETURN PIPING.
WALL MOUNTED THERMOSTAT
MOUNT 4'-0" ABOVE FINISHED FLOOR.
AIR DEVICE TAG.
MARK-CFM
SIDEWALL TRANSFER GRILLE.
SIDEWALL SUPPLY/RETURN/EXHAUST REGISTER.
WALL MOUNTED CARBON MONOXIDE SENSOR
MOUNT 4'-0" ABOVE FINISHED FLOOR.
WALL MOUNTED DIFFERENTIAL PRESSURE SENSOR.
MOUNT 4'-0" ABOVE FINISHED FLOOR.
POINT OF DISCONNECT.
CHILLED WATER SUPPLY PIPING.
1" DOOR UNDER CUT. ARROW INDICATES DIRECTION
OF FLOW.
REFRIGERANT PIPING.
A-100
UC
CWS
EQUIPMENT
TYPE
MARK
SIDEWALL FRESH AIR INTAKE LOUVER
OR EXHAUST LOUVER.
CONDENSING UNIT OR HEAT PUMP.
WALL MOUNTED CARBON DIOXIDE SENSOR
MOUNT 4'-0" ABOVE FINISHED FLOOR.
EXPOSED DOUBLE WALL INSULATED DUCTWORK.
LOCATION MATERIAL NOTES
INSULATION
R-VALUE
RETURN
UNINSULATEDSHEET METAL
DUCTWORK SCHEDULE/ COMMERCIAL
OTHER OPTIONS INCLUDE INTERNALLY
LINED OR DOUBLE WALL.
CONDITIONED
SPACE
SERVICE
TYPE
ABV - ABOVE
AC - AIR CONDITIONER
ACT - ACOUSTIC CEILING TILE
ADJ - ADJUSTABLE
AFD - ADJUSTABLE FREQUENCY DRIVE
AFF - ABOVE FINISHED FLOOR
AFUE - ANNUAL FUEL UTILIZATION EFFICIENCY
AHU - AIR HANDLING UNIT
BAS - BUILDING AUTOMATION SYSTEM
BDD - BACKDRAFT DAMPER
BI - BACKWARD INCLINE
BLDG - BUILDING
BHP - BRAKE HORSEPOWER
BTUH - BRITISH THERMAL UNIT PER HOUR
CD - CONDENSATE DRAIN
CFM - CUBIC FEET PER MINUTE
CH - CHILLER
CHW - CHILLED WATER
CHWP - CHILLED WATER PUMP
CHWR - CHILLED WATER RETURN
CHWS - CHILLED WATER SUPPLY
CLG - CEILING
COND - CONDENSATE
CONT - CONTINUOUS
CO - CARBON MONOXIDE
CO2 - CARBON DIOXIDE
COP2 - COEFFICIENT OF PERFORMANCE 2
CT - COOLING TOWER
CU - CONDENSING UNIT
CU-FT - CUBIC FEET
CW - CONDENSER WATER
CWP - CONDENSER WATER PUMP
CWR - CONDENSER WATER RETURN
CWS - CONDENSER WATER SUPPLY
DB - DRY BULB
DDC - DIRECT DIGITAL CONTROL
DN - DOWN
DP - DEW POINT
DWGS - DRAWINGS
DX - DIRECT EXPANSION
EF - EXHAUST FAN
EFF - EFFICIENCY
EXH - EXHAUST
EA - EACH
EAT - ENTERING AIR TEMPERATURE
EER2 - ENERGY EFFICIENCY RATIO 2
ELEC - ELECTRICAL
ENT - ENTERING
ESP - EXTERNAL STATIC PRESSURE
ETR - EXISTING TO REMAIN
EWT - ENTERING WATER TEMPERATURE
FC - FORWARD CURVED
FCU - FAN COIL UNIT
FD - FIRE DAMPER
FLA - FULL LOAD AMPS
FLEX - FLEXIBLE CONNECTOR OR DUCT
FPB - FAN POWERED BOX
FPM - FEET PER MINUTE
FSD - COMBINATION FIRE AND SMOKE DAMPER
FT-HD - FEET OF HEAD
°F - DEGREES FAHRENHEIT
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GPM - GALLONS PER MINUTE
HGR - HOT GAS REHEAT
HP - HORSEPOWER / HEAT PUMP
HSPF2 - HEATING SEASONAL PERFORMANCE FACTOR 2
HW - HOT WATER
HWR - HOT WATER RETURN
HWS - HOT WATER SUPPLY
HVAC - HEATING VENTILATION AND AIR CONDITIONING
HV - HEATING AND VENTILATING
HX - HEAT EXCHANGER
IEER2 - INTEGRATED ENERGY EFFICIENCY RATIO 2
IN-WG - INCHES WATER GAUGE
IN-WC - INCHES WATER COLUMN
S
T
CO
CO2
H
DP
SUPPLY DIFFUSER. DIRECTION OF AIRFLOW
INDICATED WITH ARROWS AND AIR DEVICE TAG.
RETURN OR OUTDOOR AIR GRILLE.
EXHAUST GRILLE.
SIDEWALL MOUNTED EXHAUST FAN.
SUPPLY DUCT UP SECTION (RECTANGULAR).
RETURN DUCT UP SECTION (RECTANGULAR).
EXHAUST DUCT UP SECTION (RECTANGULAR).
SUPPLY DUCT DOWN SECTION (RECTANGULAR).
RETURN DUCT DOWN SECTION (RECTANGULAR).
EXHAUST DUCT DOWN SECTION (RECTANGULAR).
SUPPLY DUCT UP SECTION (ROUND).
SUPPLY DUCT DOWN SECTION (ROUND).
RECT DUCTWORK WITH TAKE-OFF, BALANCING DAMPER AND
INSULATED FLEXIBLE ROUND DUCT. SAME SIZE AS DIFFUSER INLET
UNLESS NOTED OTHERWISE. FIRST DIMENSION IS THAT OF SIDE SHOWN.
ROUND DUCTWORK.
CONICAL FITTING WITH DAMPER ON BRANCH CONNECTION TO RECT
MAIN. PROVIDE DAMPER IN LOW PRESSURE DUCTWORK ONLY.
EXISTING DUCTWORK TO REMAIN.
MANUAL VOLUME DAMPER (VD).
OPPOSED BLADE MANUAL VOLUME DAMPER (OBMVD).
FLEXIBLE DUCT CONNECTION.
FIRE DAMPER WITH ACCESS PANEL. SEE LIFE
SAFETY PLANS FOR RATING REQUIREMENTS.
SMOKE DAMPER WITH ACCESS PANEL. SEE LIFE SAFETY PLANS
FOR RATING REQUIREMENTS. DUCT SMOKE DETECTOR TO BE
PLACED WITHIN 5'-0" OF DAMPER.
COMBINATION FIRE/SMOKE DAMPER WITH ACCESS PANEL.
SEE LIFE SAFETY PLANS FOR RATING REQUIREMENTS. DUCT
SMOKE DETECTOR TO BE PLACED WITHIN 5'-0" OF DAMPER.
EXISTING DUCTWORK TO BE REMOVED.
DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY ELEC
CONTRACTOR AND INSTALLED IN DUCT BY MECH CONTRACTOR.
REFER TO SPECIFICATIONS FOR CONTROL REQUIREMENTS.
A∅
SD
B
A
AHU
ELBOW WITH TURNING VANES.
MOTORIZED ACTUATOR.
WALL MOUNTED NITROGEN SENSOR.
MOUNT 1'-0" BELOW CEILING.
N2
CWR
CHWS
CHWS
HWS
HWS
CD
REF
CEILING MOUNTED EXHAUST FAN.
X REFERENCE NOTES.
RD
RD
LINEAR SLOT DIFFUSER.
STACKED DUCTWORK.
FD
SDMP
FSD
ABBREVIATIONS
KW - KILOWATTS
LAT - LEAVING AIR TEMPERATURE
LBS - POUNDS
LD - LINEAR DIFFUSER
LWT - LEAVING WATER TEMPERATURE
MAT - MIXED AIR TEMPERATURE
MAX - MAXIMUM
MBH - 1000 X BTUH
MCA - MIN CIRCUIT AMPACITY
MECH - MECHANICAL
MIN - MINIMUM
MOCP - MAXIMUM OVER CURRENT PROTECTION
MVD - MOTORIZED VOLUME DAMPER
MZ - MULTI-ZONE
NC - NOISE CRITERIA
NEC - NATIONAL ELECTRICAL CODE
N.I.C. - NOT IN CONTRACT
N.F.C. - NOT FOR CONSTRUCTION
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
NO2 - NITROGEN DIOXIDE
N.T.S. - NOT TO SCALE
OA - OUTSIDE AIR
OBMVD - OPPOSED BLADE MANUAL VOLUME DAMPER
PROP - PROPELLER
PD - PRESSURE DROP
PLUM - PLUMBING
PSIA - POUNDS PER SQUARE INCH ABSOLUTE
PSIG - POUNDS PER SQUARE INCH GAUGE
PTU - PARALLEL FAN-POWERED BOX/TERMINAL
UNIT
QTY - QUANTITY
RA - RETURN AIR
RD - RADIATION DAMPER
RECT - RECTANGULAR
REQ'D - REQUIRED
RH - RELATIVE HUMIDITY
RL - REFRIGERANT LIQUID
RLA - RUNNING LOAD AMPS
RLS - REFRIGERANT LINE SET
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RTU - ROOFTOP UNIT
SA - SUPPLY AIR
SEER2 - SEASONAL ENERGY EFFICIENCY RATIO 2
SF - SUPPLY FAN
SD - SMOKE DETECTOR
SDMP - SMOKE DAMPER
SQ-FT - SQUARE FOOT
SQ-IN - SQUARE INCH
SZ - SINGLE ZONE
TEMP - TEMPERATURE
TG - TRANSFER GRILLE
T'STAT - THERMOSTAT
TSP - TOTAL STATIC PRESSURE
TYP - TYPICAL
UC - UNDERCUT (DOOR)
UP - UPWARD
UV - ULTRAVIOLET LIGHT
VAV - VARIABLE AIR VOLUME
VD - MANUAL VOLUME DAMPER
VFD - VARIABLE FREQUENCY DRIVE
VFDC - VARIABLE FREQUENCY DRIVE CONTROLLER
V/PH - VOLTS AND PHASE
VRF - VARIBLE REFRIGERANT FLOW
VRV - VARIBLE REFRIGERANT VOLUME
VVT - VARIABLE VOLUME AND TEMPERATURE
W - WATTS
W/ - WITH
W/O - WITHOUT
WB - WET BULB
WMS - WIRE MESH SCREEN
ZD - ZONE DAMPER
FBC - FLORIDA BUILDING CODE
FMC - FLORIDA MECHANICAL CODE
FPC - FLORIDA PLUMBING CODE
FECC - FLORIDA ENERGY CONSERVATION CODE
EXTERIOR SHEET METAL R-8.0
ATTIC SHEET METAL R-8.0
PLENUM SHEET METAL R-4.2
SUPPLY
R-4.2SHEET METAL
CONDITIONED
SPACE
EXTERIOR SHEET METAL R-8.0
ATTIC SHEET METAL R-8.0
PLENUM SHEET METAL R-4.2
BACKDRAFT DAMPER (BDD).
ELBOW (PLAN, UP, DOWN).
TEE (PLAN, UP, DOWN).
A/B
W
L45°
CONDENSING UNIT OR HEAT PUMP (SIDE DISCHARGE).
DEMOLITION NOTES
1. ALL EXISTING EQUIPMENT AND MATERIALS TO BE REMOVED
UNDER THIS CONTRACT SHALL REMAIN THE PROPERTY OF
THE OWNER. CONTRACTOR SHALL SUBMIT A LIST OF
EQUIPMENT TO BE REMOVED TO THE OWNER.
CONTRACTOR SHALL RETAIN OR DISPOSE OF MATERIALS
AND EQUIPMENT AS DIRECTED BY THE OWNER.
2. ALL EQUIPMENT SHALL BE REMOVED IN A CAREFULLY
PLANNED MANNER. ALL CEILING-HUNG EQUIPMENT SHALL
BE REMOVED BY PROVIDING SUPPORTS FROM BELOW. NO
DROPPING OF EXISTING EQUIPMENT ONTO THE FLOOR
SLAB WILL BE ALLOWED.
3. REMOVE CONTROL WIRING OR PNEUMATIC TUBING
ASSOCIATED WITH EQUIPMENT BEING REMOVED,
COORDINATE WITH ELECTRICAL CONTRACTOR AS
REQUIRED. THE REMOVAL OF CONTROL APPARATUS SHALL
NOT INTERFERE WITH NORMAL OPERATION OF REMAINING
EQUIPMENT OR SYSTEMS.
4. REMOVE ALL CHILLED WATER SUPPLY AND RETURN PIPING
AND VALVES.
5. NOT ALL HVAC EQUIPMENT, DUCTWORK, PIPING, AND/OR
OTHER PIPING SYSTEMS ARE SHOWN ON THESE
DEMOLITION DRAWINGS. CONTRACTOR SHALL IDENTIFY ALL
DUCTS AND PIPES PRIOR TO DEMOLITION.
6. SIZES OF PIPING AND DUCTWORK TO BE REMOVED AND/OR
REMAIN MAY NOT HAVE BEEN INDICATED. CONTRACTOR
SHALL SURVEY EXISTING SPACE, VERIFY SIZES, AND
INCLUDE IN SCOPE OF WORK. DISCREPANCIES DISCOVERED
BETWEEN FIELD CONDITIONS AND CONSTRUCTION
DOCUMENTS SHALL BE REPORTED TO THE ENGINEER
PROMPTLY.
7. NO PIPING SHALL BE REMOVED UNLESS BRANCH SHUTOFF
VALVES ARE IDENTIFIED AND CLOSED PRIOR TO ACTUAL
REMOVAL.
8. DRAIN ALL PIPING SECTIONS TO BE REMOVED PRIOR TO
ACTUAL REMOVAL. NO SPILLING OVER FLOOR SLABS
SHALL BE PERMITTED. DRAIN PIPES INTO PORTABLE
CONTAINERS TO BE DISPOSED OF AS REQUIRED.
9. PROVIDE TEMPORARY SHEET METAL CAP ON ALL OPEN
END DUCTWORK THAT IS TO REMAIN.
10. ALL SERVICES PASSING THROUGH DEMOLITION CONTRACT
AREA SERVING OTHER AREAS SHALL REMAIN AND SHALL
BE PROTECTED UNLESS OTHERWISE NOTED.
11. CONSIDER USING A NEGATIVE PRESSURE MACHINE:
MAINTAIN DEMOLITION/CONSTRUCTION AREA AT A
NEGATIVE PRESSURE RELATIVE TO THE ADJOINING NON-
WORK AREAS IN ORDER TO LIMIT THE SPREAD OF
AIRBORNE CONTAMINATION. PROVIDE A TEMPORARY HEPA-
FILTERED NEGATIVE AIR FAN FOR CONSTRUCTION AREA.
MAINTAIN A 0.05” NEGATIVE PRESSURE IN THE
CONSTRUCTION AREA RELATIVE TO THE ADJACENT
SPACES. PROVIDE ADDITIONAL NEGATIVE AIR MACHINES AS
REQUIRED TO ACHIEVE MINIMUM NEGATIVE PRESSURE.
PROVIDE WELL-SEALED TEMPORARY DUCT BARRIER
PARTITIONS. ALL EXISTING RETURN REGISTERS LOCATED
WITHIN THE RENOVATION AREA SHALL BE BLANKED OFF.
TEMPORARILY REDUCE SUPPLY CFM TO MAINTAIN0.05”
NEGATIVE PRESSURE. ROUTE TEMPORARY FLEXIBLE DUCT
FROM DISCHARGE OF HEPA UNIT TO OUTSIDE OF
TEMPORARY BARRIER. LOCATE EXHAUST FAN DISCHARGE
MINIMUM 25’-0” FROM OPERABLE WINDOWS AND OUTSIDE
AIR INTAKES. FAN CRITERIA: MANUFACTURED BY ‘HEPA-
AIRE’, MODEL -1800 PAS VARIABLE CFM, 1000 TO 1800 CFM,
115V/60HZ, 10 FLA.
12. IN CONJUNCTION WITH ABOVE NEGATIVE PRESSURE
REQUIREMENT, PROVIDE AN INCLINED MANOMETER,
DIFFERENTIAL PRESSURE TYPE, WITH WHITE FACE GAUGE
AND BLACK LETTERS. THIS SHALL BE USED BY THE
CONTRACTOR TO RECORD, ON A DAILY BASIS, THE
NEGATIVE PRESSURE IN THE RENOVATION AREA RELATIVE
TO THE ADJACENT SPACES.
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:37:44 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt
MECHANICAL LEGEND,
NOTES &
ABBREVIATIONS
M0.001
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Eric S Cepull PE 64750
05.15.2025
IE - MECHANICAL SHEET LIST
Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline
M0.001 MECHANICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT MECHANICAL
M1.100 FIRST LEVEL DEMOLITION PLAN MECHANICAL 05.15.2025 ISSUE FOR PERMIT MECHANICAL
M1.101 FIRST LEVEL PLAN AND SCHEDULES MECHANICAL 05.15.2025 ISSUE FOR PERMIT MECHANICAL
M8.000 MECHANICAL DETAILS 05.15.2025 ISSUE FOR PERMIT MECHANICAL
Grand total: 4
REVISIONS
A A
B B
G G
H H
J J
C C
D D
E E
F F
M
M
M T
T
T
T
T
T
T
T
T
T
18" W x 8" D x 7' L
PLENUM (TYP.6)
M
M
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:37:57 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt
FIRST LEVEL
DEMOLITION PLAN
MECHANICAL
M1.100
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Eric S Cepull PE 64750
05.15.2025
1/8" = 1'-0"M1.100
1 1ST LEVEL - Demo Work Mechanical
GENERAL NOTES
1. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE
PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK
BEFORE SUBMITTING PROPOSAL SO AS TO BECOME FAMILIAR
WITH EXISTING WORK. SUBMISSION OF A PROPOSAL WILL BE
CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN
MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS
REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED. IT IS TO BE UNDERSTOOD THAT UNFORESEEN
CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD
LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION
WITH OTHER TRADES IN EQUIPMENT ROUTING AS DETERMINED
DURING CONSTRUCTION AND AS DIRECTED BY THE
ARCHITECT/ENGINEER MAY BE NECESSARY AND IT IS INTENDED
THAT SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS
CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT
COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY
DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR TO BID AND
INCLUDE ANY DEVIATIONS IN THE CONTRACT.
REFERENCE NOTES
TEST AND BALANCE REQUIRED FOR OUT OF SCOPE EXISTING ITEMS (I.E.,
DIFFUSERS, GRILLES, ETC.) THAT ARE TO BE TIED INTO NEW WORK.
COORDINATE WITH EXISTING CONDITIONS FOR CONNECTION OF OLD
AND NEW DUCTWORK. REFER TO SHEET M1.101 FOR POINTS OF
CONNECTION.
REMOVE EXISTING THERMOSTAT.
REMOVE EXISTING AIR DEVICES IN AREA, ASSOCIATED DUCTWORK AND
ALL OTHER APPURTENANCES.
EXISTING PARALLEL FAN-POWERED BOX TO BE REMOVED.
A A
B B
G G
H H
J J
D D
E E
F F
28"/14"
40"/14"
32"/14"
FSD
FSD
FSD
M
M
M
FD
FD
10"/6"
10X6 UP
TO EF-6
SF
34X10 DN
16"/16"
14"/12"
6"/6"
16"/14"
12"/10"
14"/14"
16"/14"
12"/12"
BREAK
ROOM
OFFICE
CASH
IT
MECHANICAL
STAIR
HALL
STORAGE
HALL
ELEC
IT
STORAGE
PERMITTING
HALL
TOILET
TOILET
CHECK-IN
STAFF
CHECK-IN
ENTRY
WAITING A
WAITING B
SERVICE
TESTING
CUSTOMER
SERVICE
HALL
HALL
HALL
14"ø
PTU
1.3
PTU
1.4
10"ø
8"ø
12"ø
A-300
A-60 ø10" A-295 ø10"
A-295
A-240 ø10"
A-205
A-205
A-205 A-205ø8" ø8"ø8"
A-220 ø10"
A-170 ø8" ø8"
A-165
A-220 ø10"
A-330A-330
A-385 ø12"A-380 ø10"
A-285 ø8"
A-105
A-105 ø8"
A-105 ø8" ø6"
A-80
A-90
A-100 ø6" ø10"
A-325 ø10"
A-255ø10"
A-260 ø10"A-185 ø8"
A-180 ø8"
A-80 ø6"
A-130 ø8"
A-225 ø10" ø10"
A-220
A-225
PTU
1.1
PTU
1.2
20"/14"
VAV
1.1
4" ø ø6"
VAV
1.2
VAV
1.3
4" ø ø6"
A-60
A-130
PTU
1.5
"ø
6 6
2 7
2 72 7
1 7 1 7
1 7
1 7
1 7
T3
T
T
3 T
T
T
T
T
A-30
UC
PROVIDE MANUAL
VOLUME DAMPER
AND SET AT
670CFM
PROVIDE MANUAL
VOLUME DAMPER
AND SET AT
630CFM
ø10" ø12" ø10"
ROUTE FLEX DUCT
ABOVE MINIMUM PTU
SERVICE CLEARANCE
AT THIS LOCATION.
FD
28"/14"
8" ø ø6" ø10"
6" ø
A-306 ø6"
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:38:09 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt
FIRST LEVEL PLAN AND
SCHEDULES
MECHANICAL
M1.101
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Eric S Cepull PE 64750
05.15.2025
1/8" = 1'-0"M1.101
1 1ST LEVEL - New Work Mechanical
GENERAL NOTES
1.
2.
DUCTS ENTERING THE VAV BOX/PARALLEL FAN-POWERED
BOX (VAV/PTU, RESPECTIVELY) MUST REDUCE TO INLET SIZE
AT LEAST THREE DUCT DIAMETERS BEFORE THE VAV BOX
INLET AND SHALL BE STRAIGHT DUCT.
COORDINATE FINAL DIFFUSER LOCATION WITH
ARCHITECTURAL DRAWINGS.
REFERENCE NOTES
REFER TO PARALLEL TERMINAL UNIT DETAIL 05 ON SHEET
M8.000 FOR ADDITIONAL INFORMATION. ENSURE FAN-
POWERED BOX HAS NECESSARY CLEARANCE AS INDICATED
ON PLANS.
REFER TO VAV DETAIL 01 ON SHEET M8.000 FOR ADDITIONAL
INFORMATION. ENSURE FAN-POWERED BOX HAS NECESSARY
CLEARANCE AS INDICATED ON PLANS.
THERMOSTAT TO BE MOUNTED A MINIMUM 48" AFF.
COORDINATE WITH ARCHITECTURAL DRAWINGS FOR FINAL
THERMOSTAT LOCATION AND/OR ELEVATION.
EXISTING DUCTWORK TO CONTINUE TO AREA OUTSIDE OF
CURRENT SCOPE. REFER TO EXISTING DRAWINGS FOR
CONTINUATION.
EXISTING DUCTWORK TO CONTINUE INTO EXISTING
MECHANICAL ROOM. DUCT MAIN, TRANSITIONS, AND DUCT
ACCESSORIES (I.E., DAMPERS) ARE TO REMAIN. CONTRACTOR
TO VERIFY ITEMS ARE IN PROPER CONDITION.
RA GRILLE, TYPE-C (IN AIR DEVICE SCHEDULE) TO ROUTE TO
PLENUM ABOVE.
PROVIDE A MEANS OF ACCESS/ACCESS PANEL TO VAV/FAN-
POWERED BOX IF NOT LOCATED IN EXPOSED AREA OR
ABOVE ACOUSTIC CEILING TILE (ACT).
SPACE IS NOT IN CONTRACT. ROUTE NEW DUCTWORK ABOVE
THIS SPACE. COORDINATE WITH EXISTING CONDITIONS.
CFM RANGE
0 - 95
NECK SIZE
6"Ø
96 - 205 8"Ø
10"Ø
12"Ø
14"Ø
A-CFM
206 - 375
376 - 605
606 - 850
CFM RANGE
0 - 2500
NECK SIZE
22"X22"
C-CFM
AIR DEVICE SCHEDULE
MARK DESCRIPTION FACE SIZE NECK MATERIAL
MANUFACTURER/MODEL #
NOTES
EGGCRATE RET./EXH. GRILLE (1/2"x1/2"x1/2")
LOUVERED FACE 2 CONE ADJUSTABLE SUPPLY DIFFUSER 24"x24" SEE TABLE BELOW ALUMINUM GREENHECK/METAL AIRE 5700-AL
C 24"x24" 22"X22" ALUMINUM
A
BASIS OF DESIGN
DAMPER
Y
NGREENHECK/METAL AIRE CC-5
NOTES:
1. COORDINATE COLOR AND SURFACE FINISHES WITH ARCHITECTURAL DRAWINGS.
2. PROVIDE RAPID MOUNT T-BAR FRAME FOR PLASTER AND SHEET ROCK CEILINGS.
3. SUPPLY COMPLETE WITH FACTORY INSTALLED 1/2" THICK FOIL BACKED INSULATION.
1, 2, 3
1, 2
4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.
3.SINGLE POINT CONNECTION UNITS. TERMINAL UNITS TO BE PROVIDED WITH CONTROL POWER TRANSFORMER.
2.FAN MOTOR SHALL BE 208/3/60 AND HEATER SHALL BE 208/3/60.
1.PROVIDE ELECTRONIC ROOM SENSOR WITH DIGITAL DISPLAY CONTROLLER. DDC CONTROLLER SHALL BE INTERFACED WITH BASE BUILDING MANAGEMENT SYSTEM. REFER TO BASE BUILDING DRAWINGS AND BUILDING ENGINEER FOR INSTALLATION REQUIREMENTS.
NOTES:
PARALLEL FAN POWERED TERMINAL UNIT SCHEDULE
EQUIPMENT TAG
LOCATION
PRIMARY VALVE AIR FLOW INLET
SIZE DIA.
IN.
E.S.P.
(IN. WG.)
OPERATING
WEIGHT (LBS)
FAN MOTOR HEATING DATA
MCA MOCP MANUFACTURER
MODEL
NUMBER
NOTES
DESIGN CFM MINIMUM CFM MAXIMUM CFM CFM HP V/Ø/HZ HEATING FAN CFM VALVE HEATING CFM EAT/LAT (°F) KW STAGES V/Ø/HZ
PTU-1.1 WAITING A/B 1615 240 1615 12" 0.25 114 440 0.33 277/1 680 240 64.71/78.59 3 1 277/1 15.54 20 TRANE VPEF 1-4
PTU-1.2 CHECKING 1605 240 1605 12" 0.25 114 340 0.33 277/1 580 240 63.79/74.65 2 1 277/1 11.03 15 TRANE VPEF 1-4
PTU-1.3 SERVICE 2735 320 2735 14" 0.25 116 320 0.33 277/1 740 320 63.51/72.02 2 1 277/1 11.53 15 TRANE VPEF 1-4
PTU-1.4 CUSTOMER SERVICE 950 190 950 10" 0.25 111 380 0.125 277/1 570 190 65.00/76.04 2 1 277/1 9.90 15 TRANE VPEF 1-4
PTU-1.5 BREAK ROOM 1370 165 1375 10" 0.25 111 300 0.125 277/1 465 165 64.68/78.21 2 1 277/1 9.90 15 TRANE VPEF 1-4
5.EXHAUST CFM FROM SPACE IS NOT TO EXCEED MINIMUM CFM VALUE.
4.PROVIDE FUSED DISCONNECT DOOR SWITCH AND 1" FOIL FACED LINER COMPATIBLE WITH NFPA 90/225 AND UL 181/723.
3.PROVIDE PRESSURE INDEPENDENT TYPE. PROVIDE ALL NECESSARY EQUIPMENT TO ALLOW COMMUNICATION WITH BUILDING MANAGEMENT SYSTEM (BMS)
2.PROVIDE FUSED CONTROL POWER TRANSFORMER.
1.PROVIDE ELECTRONIC ROOM THERMOSTAT WITH DIGITAL DISPLAY, ADJUSTABLE SETPOINT AND NIGHT SET-BACK OVERRIDE AND CANCEL BUTTONS.
NOTES:
VAV BOX SCHEDULE
EQUIPMENT TAG LOCATION
AIR DATA INLET
SIZE DIA.
IN.
E.S.P.
(IN. WG.)
MAX.
N.C.
OPERATING
WEIGHT (LBS)
MANUFACTURER
MODEL
NUMBER
NOTES
DESIGN CFM MINIMUM CFM MAXIMUM CFM
VAV-1.1 ELEC 90 50 90 4" 0.25 29 21 TRANE VCEF 1-5
VAV-1.2 TELE 100 50 100 4" 0.25 29 21 TRANE VCEF 1-5
VAV-1.3 IT 220 70 220 4" 0.25 29 21 TRANE VCEF 1-4
VAV
TERMINAL UNIT
SECTION OF STRAIGHT PIECE
OF ROUND DUCT EQUAL TO
BOX INLET SIZE
SEE PLAN FOR SIZE
FLEX DUCT
(TYPICAL)
PROVIDE TRANSITION
AS REQUIRED
HANGER RODS. LOCATED
TO CLEAR ALL VALVE
CONTROLS
SUPPLY DUCT.
SEE PLAN FOR SIZE
ANCHOR TO
STRUCTURE
NOTES:
1.
2.
3.
4.
ON DUCTS OVER 48" WIDE, BOTTOM
SHALL BE BRACED BY ANGLE. FOR
CROSS SECTION AREA MORE THAN 8
SQ FT, DUCT SHALL BE BRACED BY
ANGLES ON ALL FOUR SIDES.
CUTTING AND PATCHING SHALL BE
LIMITED TO A MINIMUM AS REQUIRED
FOR PROPER INSTALLATION.
REFER TO SMACNA FOR SPECIFIC
RECOMMENDED HANGER TYPES NO TED.
MAXIMUM SPACING BETWEEN HANGER
LOCATIONS SHALL BE 8'-0" PER
PAIR. STRAPS SHALL BE MINIMUM 1
1/2" X 22 GAGE GALVANIZED STEEL.
THREADED
HANGER ROD
GALVANIZED
HANGER
STRAP
UNISTRUT
OR ANGLE
IRON
STRAP HANGERS TRAPEZE HANGERS
STRAP
OR ANGLE
HANGER RODS
OVER 60"SEE NOTE 3MAX. 60"
SCREWS TYPICAL
1" MIN
3"
M A
X . S
P A
C
IN
G
HANGER BAND
CONTINUOUS HANGER
STRAP AROUND DUCT
36" DIA. MAX.
36" DIA. MAX.
HANGER
BAND
STRAPS
BAND
CONICAL FITTING WITH LOCKING TYPE VOLUME DAMPER.
DAMPER AND DAMPER STAND-OFF EQUAL TO CROWN
PRODUCTS COMPANY MODEL 3200-DS.
FLEX DUCT OR ROUND SHEET METAL DUCT. FLEX
DUCT MAX. 8'-0" LONG, USE CLAMP TO ATTACH
FLEX DUCTS AND SEAL AS PER SPECIFICATIONS,
SUPPORT FLEX DUCT EVERY 3'-0" FROM STRUCTURE.
TO AIR
VALVE
SIDE TAKE-OFF FITTING - EQUAL
TO FLEXMASTER STO (22 GA.
MIN.)
RECTANGULAR DUCT
VOLUME DAMPER
MAX. 15° TRANSITION 0.25 D
1.
D
ROUND DUCT
S U
P P
L Y
A
IR
F L
O W
S U
P P
L Y
A
IR
F L
O W
D
PROVIDE CEILING ACCESS
PANEL FOR DAMPER ACCESS
IN NON-ACCESSIBLE CEILINGS
AIR DISTRIBUTION DEVICE, SEE
SCHEDULE. LAY-IN SHOWN-
SURFACE MOUNT SIMILAR
VOLUME DAMPER WITH LOCKING
QUADRANT AND 2" STANDOFF
SUPPLY DUCT SIZE AS
SHOWN ON PLANS
DUCT SEALER AT SPIN
COLLAR CONNECTION
TO MAIN
ROUND SPIN-IN COLLAR MOUNT
IN SIDE OF DUCT UNLESS
SPECIFICALLY SHOWN OTHERWISE
MAXIMUM D/8 OFFSET
ALLOWED IN LAST D INCHES
TO DEVICE WHERE D IS THE
INTERNAL FLEX DIAMETER
NECK SIZE TO MATCH
FLEX DUCT SIZE INDICATED
INSULATE TOP PANEL
OF LAY-IN DIFFUSER
CEILING (T-BAR SHOWN)
GYPSUM BOARD SIMILAR
ADJUSTABLE CLAMP
UPPER ATTACHMENT PER SMACNA
DUCT SEALER
ADJUSTABLE CLAMP STAINLESS STEEL
SEE NOTE 3
MAX. SAG 1/2" PER FOOT
BETWEEN SUPPORT POINTS
NOTES:
1.
2.
3.
4.
FLEXIBLE DUCTS SHALL BE ONE-PIECE AND SHALL NOT BE SPLICED TOGETHER.
EXTEND FLEXIBLE DUCT INSULATION TO DUCT/DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC.
MINIMUM 1-1/2" WIDE 22 GAUGE GALVANIZED STRAP HANGER. INSTALL PER GUIDELINES SETFORTH IN CHAPTER 3 OF THE MOST CURRENT EDITION OF THE S.M.A.C.N.A. TECHNICAL MANUAL TITLED "HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE".
FLEXIBLE AIR DUCT SHALL BE FULLY EXTENDED AND NOT COMPRESSED. ELBOW RADIUS SHALL BE NO LESS THAN R/D=1.0.
ELECTRIC HEATER
FAN POWERED TERMINAL UNIT
HANG UNIT FROM BUILDING
STRUCTURE WITH THREADED ROD
AND SPRING TYPE VIBRATION
ISOLATORS
MEDIUM PRESSURE FLEXIBLE DUCT,
REFER TO PLANS FOR SIZE
CONTROL PANEL FOR
ELECTRIC HEATER, PROVIDE
REQUIRED SERVICE
CLEARANCE IN FRONT OF DOOR
(LEFT-HANDED PTU IS SHOWN,
REFER TO DRAWINGS FOR
CORRECT HANDING)
PRIMARY AIR INLET
GALVANIZED
SHEETMETAL
REDUCER
PLENUM
RETURN
AIR INLET
FILTER
LOW PRESSURE SUPPLY
DUCT, REFER TO PLANS
FOR SIZE
FLEXIBLE
DUCT
CONNECTION
NOTE
COORDINATE INSTALLATION OF FAN TERMINAL
UNIT TO PROVIDE ADEQUATE SERVICE ACCESS.
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:38:12 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Mech.rvt
MECHANICAL DETAILS
M8.000
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Eric S Cepull PE 64750
05.15.2025
SCALE: NTSM8.000
1 VAV TERMINAL UNIT CONNECTION DETAIL
SCALE: NTSM8.000
2 DUCT HANGER DETAIL
SCALE: NTSM8.000
3 DUCT CONNECTION DETAILS
SCALE: NTSM8.000
4 FLEXIBLE DUCT INSTALLATION DETAIL
SCALE: NTSM8.000
5 FAN POWERED TERMINAL UNIT INSTALLATION DETAIL
| M0.001 - MECHANICAL LEGEND, NOTES & ABBREVIATIONS |
| M0.001 - MECHANICAL LEGEND, NOTES & ABBREVIATIONS |
| M1.100 - FIRST LEVEL DEMOLITION PLAN MECHANICAL |
| M1.100 - FIRST LEVEL DEMOLITION PLAN MECHANICAL |
| M1.101 - FIRST LEVEL PLAN AND SCHEDULES MECHANICAL |
| M1.101 - FIRST LEVEL PLAN AND SCHEDULES MECHANICAL |
| M8.000 - MECHANICAL DETAILS |
| M8.000 - MECHANICAL DETAILS |
File details come from the government source that posted it. Updated .