Electrical.pdf
PDF 2 MB Posted
- Solicitation number
- 25-B-127LL
- Issued by
- Volusia County, Florida
About this file
This document is an electrical drawing set for the Volusia County Tax Collector Interior Renovation project located in DeLand, Florida. The electrical documents include a comprehensive set of drawings covering electrical symbols and legends, demolition plans, new electrical power and lighting plans, electrical riser diagrams, panel schedules, fire alarm system details, and electrical penetration details. The drawings are dated 05.15.2025 and are marked "Issue for Permit", indicating the project is in the final design stages preparatory to construction authorization.
The electrical design encompasses first-level renovation work including power distribution, lighting layouts, fire alarm system modifications, and mechanical equipment electrical connections. The drawings show detailed electrical infrastructure for various rooms including entry, waiting areas, check-in spaces, offices, break rooms, and service areas. Specific technical elements include occupancy sensors, fire wall penetration details, panel schedules showing existing and new electrical loads, and comprehensive fire alarm system sequence of operations. The electrical design appears to be part of a broader renovation project for the Volusia County Tax Collector's administration office, with a focus on modernizing electrical systems while maintaining existing infrastructure where possible.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SERVICE AND DISTRIBUTION
ELECTRICAL SYMBOLS LEGEND
ABBREVIATIONS
DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE , COMMUNICATIONS AND DATA OUTLETS MOUNTED TOGETHER IN A
FLUSH MOUNTED FLOOR BOX. BOX TO HAVE A LISTED DIVIDER BETWEEN LINE VOLTAGE AND
LOW VOLTAGE CONNECTIONS.
DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX
SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION
AMPACITY RATING AS INDICATED
"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER -
MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT
DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH
MOUNTED FLOOR BOX
S
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING - MOUNT AT 18"
AFF, UNLESS OTHERWISE NOTED
"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT
SWITCHES
TS
FS
POWER
EF
FIRE ALARM
WP
F
DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED
(WP) WEATHERPROOF
(H) HORIZONTALLY MOUNTED
(C) CEILING MOUNTED
SINGLE POLE SWITCH - TOGGLE TYPE - MOUNT AT 48" AFF
(3) 3 WAY
(4) 4 WAY
(2) DOUBLE POLE
(D) DIMMER OPERATED
(M) MOTOR RATED SWITCH - 1 POLE OR 2 POLE 30 AMP WITH INTEGRAL THERMAL OVERLOADS
(OS) WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
WP
ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION SQUARE "D" CLASS#900 1-K15 W/ CLASS
9001-K25 STAINLESS STEEL COVER PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF. WITHIN
WEATHERPROOF KNOX BOX HOUSING
METER SOCKET
TIME CLOCK
LIGHTING CONTACTOR - * DENOTES CONTACTOR NUMBER
PHOTO CELL
MOTOR
(EF) EXHAUST FAN
(AHU) AIR HANDLING UNIT
CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)
WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)
SPRINKLER TAMPER SWITCH CONNECTION
SPRINKLER WATERFLOW SWITCH CONNECTION
POST INDICATOR VALVEPIV
J
PC
FIRE/SMOKE OR SMOKE DAMPER FIRE ALARM CONNECTION. PROVIDE FIRE ALARM SYSTEM
ADDRESSABLE SMOKE DETECTOR WITHIN 60" OF DAMPER LOCATION. PROVIDE 120V/20A POWER
CONNECTION TO EACH DAMPER. SMOKE DETECTOR SHALL HAVE ADDRESSABLE RELAY BASE OR
CONTROL MODULE TO ACTIVATE DAMPER SHOWN ON DRAWINGS. REFER TO MECHANICAL DRAWINGS
FOR EXACT DAMPER LOCATIONS.
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, "*" INDICATES
FIXTURES IN SENSOR'S ZONE OF CONTROL.
(DS) DAYLIGHT SENSOR
OS
BRANCH CIRCUIT PANELBOARD, 120/208V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED
FUSED DISCONNECT SWITCH
(3) NUMBER OF POLES
(30) AMPERAGE SIZE
(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
(NF) NON FUSED
(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS
NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.
COMBINATION STARTER/DISCONNECT SWITCH
(3) NUMBER OF POLES
(30) AMPERAGE SIZE
(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
(NF) NON FUSED
(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS
NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.
UTILITY TRANSFORMER
SURGE PROTECTION DEVICE
GROUND BARGB
LC-*
J
TC
(REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT)
BRANCH CIRCUIT PANELBOARD, 277/480V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED
SPD
DRY TYPE TRANSFORMER
H
RTI
"FACP"
DH
FAJB
FAAP
MANUAL PULL STATION - MOUNT AT 48" AFF
COMBINATION AUDIBLE/VISUAL SIGNALING UNIT- SPEAKER/FLASHING "FIRE" LIGHT WALL - MOUNTED
96" AFF UNLESS OTHERWISE NOTED. 75 CANDELA UNLESS NOTED OTHERWISE
(WP) WEATHER PROOF
(A) AUDIBLE ONLY.
COMBINATION AUDIBLE/VISUAL SIGNALING UNIT CEILING MOUNTED- SPEAKER/FLASHING "FIRE" LIGHT
75 CANDELA UNLESS NOTED OTHERWISE
(WP) WEATHER PROOF
(A) AUDIBLE ONLY.
VISUAL SIGNALING UNIT, WALL MOUNTED- FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)
75 CANDELA, UNLESS NOTED OTHERWISE.
VISUAL SIGNALING UNIT, CEILING MOUNTED - FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)
75 CANDELA, UNLESS NOTED OTHERWISE
PHOTOELECTRIC DUCT SMOKE DETECTOR, R=RETURN / S=SUPPLY
FIRE ALARM SHUTDOWN OR CONTROL RELAY
DUCT DETECTOR REMOTE TROUBLE INDICATOR - MOUNT ADJACENT TO UNIT
FIRE ALARM HEAT DETECTOR. (2) INDICATES TO PROVIDE DUAL CONVERTIBLE CONTACTS
CEILING OR WALL MOUNTED SMOKE DETECTOR. SMOKE DETECTOR SHALL BE TIED TO MAIN FIRE
ALARM SYSTEM.
(2) PROVIDE DUAL CONTACT.
(CO) CARBON MONOXIDE DETECTOR.
(LF) LOW-FREQUENCY SOUNDER BASE WITH INTEGRAL BATTERY BACK UP.
DOOR HOLDER
FIRE ALARM CONTROL PANEL - FLUSH MOUNTED
FIRE ALARM JUNCTION BOX
REMOTE FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
SPRINKLER TAMPER SWITCH CONNECTION
S
R
F
F
F
F
F
C
R
CEILING MOUNTED DAYLIGHT SENSOR, "*" INDICATES FIXTURES IN SENSOR'S ZONE
OF CONTROL. SENSOR TO AUTO-DIM FIXTURES WITHIN BUILDING CODE PRESCRIBED
DAYLIGHT ZONE.
DS
FSD
VARIABLE FREQUENCY DRIVEVFD
FATC FIRE ALARM TERMINAL CABINET, FLUSHED MOUNTED
DDS HEARING IMPAIRED DUAL SMOKE SENSOR AND STROBE
TFR HEARING IMPAIRED LOW VOLTAGE TRANSFORMER FOR DOORBELL SYSTEM
"DO NOT USE" ELEVATOR WARNING LIGHT. BY ELEVATOR CONTRACTORWL
CEILING MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)J
C
DATA/COMM
DATA/COMM OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANG JUNCTION BOX. MOUNT AT 18"
AFF, UNLESS OTHERWISE NOTED. PROVIDE BLANK STAINLESS STEEL COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING, OR AS
NOTED; INSTALL PULL WIRE.
(WH) WALL MOUNTED
(AC) 6" ABOVE COUNTER BACK SPLASH
(TV) TV - REFER TO ARCHITECTURAL DRAWINGS FOR HEIGHT
DATA/COMM OUTLET FLUSH MOUNTED IN FLOOR
TELEVISION OUTLET - MOUNT 18 " ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED
STRUCTURED MEDIA COMPONENT FLUSH MTD. BOX FOR RESIDENTIAL USE PROVIDED AND INSTALLED
BY CONTRACTOR - MOUNT 48" AFF TO BOARD, UNLESS OTHERWISE NOTED
TELEPHONE TERMINAL BOARD
SMC
TV
C
FIRE ALARM SYSTEM, RESIDENTIAL UNIT MINI-HORN LOW FREQUENCY SOUNDER (520HZ) - MOUNT AT
96" AFF TO TOP OF SOUNDER
S
CARD READER - MOUNT 48" AFF, UNLESS OTHERWISE NOTEDCR
A - AMPERES
A/C - AIR CONDITIONING
AC - ALTERNATING CURRENT
ADA - AMERICANS WITH DISABILITIES ACT
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AHU - AIR HANDLING UNIT
ATS - AUTOMATIC TRANSFER SWITCH
AWG - AMERICAN WIRE GAUGE
BFG - BELOW FINISHED GROUND
C - CONDUIT
COND - CONDUIT
CH - COUNTER HEIGHT
CONC - CONCRETE
CU - COPPER
DISC - DISCONNECT
DBL - DOUBLE
ECB - ENCLOSED CIRCUIT BREAKER
ELEC - ELECTRICAL
EM - EMERGENCY
EF - EXHAUST FAN
EPO - EMERGENCY POWER OFF
EV - ELECTRIC VEHICLE
EWC - ELECTRIC WATER COOLER
EX - EXISTING
EXT - EXTENSION
FA - FIRE ALARM
FACP - FIRE ALARM CONTROL PANEL
FBC - FLORIDA BUILDING CODE
GACP - GENERATOR ANNUNCIATOR CONTROL PANEL
G - GROUND
GND - GROUND
GFI - GROUND FAULT INTERRUPTER
GRC - GALVANIZED RIGID CONDUIT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
IAW - IN ACCORDANCE WITH
IWH - INSTANTANEOUS WATER HEATER
I.G. - ISOLATED GROUND
J - JUNCTION
KAIC - (THOUSAND) AMPERE INTERRUPTING CAPACITY
KCMIL - THOUSAND CIRCULAR MILLS
KVA - KILOVOLT-AMPERES
KW - KILOWATT
LTG - LIGHTING
LTS - LIGHTING
MCB - MAIN CIRCUIT BREAKER
MH - MOUNTING HEIGHT
MLO - MAIN LUG ONLY
N - NEUTRAL
NA - NOT APPLICABLE
NEC - NATIONAL ELECTRICAL CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
NF - NON-FUSED
NIC - NOT IN CONTRACT
NL - NIGHT LIGHT
O.C. - ON CENTER
P - POLE
PNL - PANELBOARD
PVC - POLYVINYL CHLORIDE
RGS - RIGID GALVANIZED STEEL
RM - ROOM
SPEC - SPECIFICATION
SPD - SURGE PROTECTION DEVICE
SS - STAINLESS STEEL
SWBD - SWITCHBOARD
TYP - TYPICAL
UON - UNLESS OTHERWISE NOTED
UNV - UNIVERSAL
V - VOLTS
W - WIRE
WP - WEATHERPROOF
T
TS
GACP
GENERATOR ANNUNCIATOR CONTROL PANEL - FLUSH MOUNTED
GENERAL NOTE
1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY
CONSERVATION C405.6.3 AND 2020 NEC 210.19 WITH
REGARDS TO VOLTAGE DROP (5%).
2. THE ELECTRICAL DESIGN HAS BEEN DESIGNED IN
ACCORDANCE WITH THE 2020 NATIONAL ELECTRICAL CODE,
2023 FLORIDA BUILDING CODE.
FLORIDA ADMINISTRATIVE CODE
ARTICLE 61G15.32.008(4)a-o
61G15-32.008(4) - TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND DETECTION SYSTEMS
ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING
INFORMATION WHEN APPLICABLE:
(a) SYMBOL LEGEND IS FOUND ON SHEET E0.001 AND SYSTEM RISER IS FOUND ON SHEET
E6.000
(b) LOCATIONS FOR INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS ARE
FOUND ON FLOOR PLAN SHEETS E1.101
(c) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS ARE FOUND IN THE SYMBOL
LEGEND ON SHEET E0.001
(d) CIRCUITS SHALL BE CLASS B TYPE, AS PER SPECIFICATION SECTION 283000
(e) IDENTIFICATION OF FUNCTIONS REQUIRED BY THE ALARM AND CONTROL SYSTEMS IS
FOUND ON SHEET E6.000
(f) FIRE ALARM SHALL BE ADDRESSABLE AND ZONING IS INDICATED IN SPECIFICATION
SECTION 283000
(g) SURGE PROTECTION DEVICES ARE FOUND ON ELECTRICAL RISER ON SHEET E6.000
(h) DEVICES THAT ARE SUBJECT TO ENVIRONMENTAL FACTORS AND REQUIREMENTS FOR
PROTECTION ARE FOUND ON FLOOR PLAN SHEETS E1.101
(i) SITE PLAN AND ANY FIRE ALARM DEVICES REQUIRED OUTSIDE ARE NOT APPLICABLE
(j) SMOKE DETECTION DEVICES TO MITIGATE OBSTRUCTIONS ARE NOT APPLICABLE
(k) SMOKE DETECTION DEVICES TO MITIGATE DETECTION PROBLEMS WHERE SMOKE
STRATIFICATION IS ANTICIPATED ARE NOT APPLICABLE.
(l) DESIGN GUIDES AND STANDARDS USED FOR PERFORMANCE BASED FIRE ALARM
SYSTEM ARE FOUND ON SHEET E6.000
(m) INDICATION OF GENERAL EVACUATION SIGNAL OR A ZONED EVACUATION FOR ALL
HIGH-RISE BUILDINGS OR MULTI-TENANTED PROPERTIES IS NOT APPLICABLE
(n) WIRING REQUIREMENTS AND BURIAL DEPTH FOR UNDERGROUND, WET LOCATIONS
AND CAMPUS STYLE WIRING ARE NOT APPLICABLE
(o) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND OWNER INSTRUCTIONS ARE INDICATED IN SPECIFICATION
SECTION 283000
LIGHTING (SEE LIGHTING FIXTURE SCHEDULE)
2'X 2' LIGHT FIXTURE
EMERGENCY 2' x 2' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
2'X 4' LIGHT FIXTURE
EMERGENCY 2' x 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
1'X 4' LIGHT FIXTURE
EMERGENCY 1'X 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
LIGHT FIXTURE - WALL MOUNTED
EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR
STRIP LIGHT
EMERGENCY STRIP LIGHT CONNECTED TO EMERGENCY GENERATOR
DOWNLIGHT LIGHT FIXTURE
LIGHT FIXTURE - WALL MOUNTED
WALL WASH / ACCENT FIXTURE - CEILING MOUNTED
EMERGENCY DOWNLIGHT LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR
EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR
EXIT SIGN - SINGLE FACE ARROW INDICATES DIRECTION - CEILING MOUNTED-WITH INTEGRAL
EMERGENCY BACKUP
EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION - WALL MOUNTED - WITH INTEGRAL
EMERGENCY BACKUP
EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION - CEILING MOUNTED - WITH INTEGRAL
EMERGENCY BACKUP
EMERGENCY LIGHT WITH INTEGRAL EMERGENCY BACKUP - DUAL HEAD
DECORATIVE PENDANT
LIGHT TRACK - CEILING MOUNTED
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:14 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
ELECTRICAL LEGEND,
NOTES &
ABBREVIATIONS
E0.001
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
IE - ELECTRICAL SHEET LIST
Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline
E0.001 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E1.100 FIRST LEVEL DEMOLITION PLAN ELECTRICAL 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E1.101 FIRST LEVEL PLAN POWER 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E1.102 FIRST LEVEL PLAN LIGHTING 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E6.000 ELECTRICAL RISERS AND PANEL SCHEDULES 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
E8.000 ELECTRICAL DETAILS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL
Grand total: 6
6. ALL SITE, POOL DECK, AND PARKING GARAGE ALTERNATE FIXTURES SHALL BE SUBMITTED WITH PHOTOMETRIC STUDY TO BE REVIEWED AS PART OF THE SUBMITTAL
PROCESS.
5. COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL AND INTERIOR DRAWING'S REFLECTED CEILING PLANS AND PROVIDE FIXTURE
TRIM AS REQUIRED.
4. REFER TO ARCHITECTURAL REFLECTED CEILING LIGHTING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.
3. COORDINATE THE ACTUAL TYPE OF LIGHTING FIXTURES WITH ARCHITECTURAL LIGHTING SCHEDULES, INTERIOR DESIGN LIGHTING SCHEDULE/DRAWINGS AND OWNER
LIGHTING FIXTURE STANDARD CRITERIA AS REQUIRED.
2. PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN REFLIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE
INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.
1. PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB, AND STRUCTURAL STEEL
LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENERS AND UL APPROVED CONNECTORS.
LIGHTING FIXTURE SCHEDULE NOTES
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS LOAD VOLTS REMARKS
A
LITHONIA LTG:
CPX-2X4-AL08-80CRI-SWW7-SWL-MVOLT
2'x4' FLAT PANEL LED 47.9 VA 277 AS APPROVED BY OWNER
B
GOTHAM LTG:
IVO4SQS-D-07LM-35K-80CRI-MWD-MIN10-MVOL
T-EZT-NCH-P-AR-LSS-F
4" SQUARE DOWNLIGHT LED 7.8 VA 277 AS APPROVED BY OWNER
C2 SAME AS TYPE 'C4' EXCEPT 2' IN LENGTH 2' RECESSED LINEAR LED 13.2 VA 277 AS APPROVED BY OWNER
C4
NEXA LTG:
807-NX3-RS-4-48-RECESSED-0-IP-AE-2-Z-SO-C3
4' RECESSED LINEAR LED 26.4 VA 277 AS APPROVED BY OWNER
C6 SAME AS TYPE 'C4' EXCEPT 6' IN LENGTH 6' RECESSED LINEAR LED 39.6 VA 277 AS APPROVED BY OWNER
C8 SAME AS TYPE 'C4' EXCEPT 8' IN LENGTH 8' RECESSED LINEAR LED 52.8 VA 277 AS APPROVED BY OWNER
C10 SAME AS TYPE 'C4' EXCEPT 10' IN LENGTH 10' RECESSED LINEAR LED 66.0 VA 277 AS APPROVED BY OWNER
EX LITHONIA LTG: EDG-1/2-R EDGE LITE EXIT SIGN LED 2.8 VA 277 AS APPROVED BY OWNER
REVISIONS
J
J J
JJJ
A A
B B
G G
H H
J J
C C
D D
E E
F F
1 1
VAV
2-12
VAV
2-11
VAV
2-10
VAV
2-09
VAV
2-07
VAV
2-08
VAV
2-05
VAV
2-06
VAV
2-02
VAV
2-04
VAV
2-01
VAV
2-03
VAV
2-13
NIC
GENERAL
DEMOLITION NOTE
1. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE
THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY
THIS WORK BEFORE SUBMITTING PROPOSAL SO AS TO
BECOME FAMILIAR WITH EXISTING WORK. SUBMISSION OF A
PROPOSAL WILL BE CONSTRUED AS EVIDENCE. THAT SUCH
EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR
LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE BY
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED. IT
IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS
PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD
LOCATED EXACTLY AS SHOWN ON THE DRAWINGS.
COOPERATION WITH OTHER TRADES IN EQUIPMENT
ROUTING AS DETERMINED DURING CONSTRUCTION AND AS
DIRECTED BY THE ARCHITECT/ENGINEER MAY BE
NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS
SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT IS
ALSO UNDERSTOOD THAT THE PLANS ARE NOT
COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD
VERIFY DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR
TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
2. ALL DEVICES AND EQUIPMENT NOT SHOWN AND IN AREAS
OUTSIDE OF CONSTRUCTION AREA SHALL REMAIN ACTIVE
UNLESS OTHERWISE NOTED. INSTALL AS REQUIRED TO
MAINTAIN CONTINUITY TO EXISTING DEVICES AND
EQUIPMENT THAT REMAIN.
3. ALL BRANCH CIRCUIT WIRING SHALL BE CONCEALED
UNLESS OTHERWISE NOTED.
4. ALL EQUIPMENT AND MATERIAL REMOVED AND NOT
REUSED SHALL BE TURNED OVER TO THE OWNER OR AT
THE OWNERS REQUEST DISPOSED OF BY THE
CONTRACTOR.
5. ALL ELECTRICAL DEVICES THAT ARE REMOVED SHALL BE
REMOVED AS DIRECTED BY THE OWNER, AND CEILING OR
WALL SHALL BE PATCHED TO MATCH EXISTING OR NEW
FINISH. ALL PATCHES OR CEILING PLATES SHALL BE
PATCHED OR PAINTED AS DIRECTED BY ARCHITECT.
6. ALL EXISTING ELECTRICAL EQUIPMENT IS NOT SHOWN. IT IS
THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR
WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND
INCLUDE IN HIS BID THE REMOVAL OF ALL EQUIPMENT,
CONDUIT, WIRE, ETC. THAT IS NOT BEING REUSED BACK TO
ITS SOURCE.
7. ALL CONCRETE, WALL PATCHING, CEILING REPAIR, AND
OTHER GENERAL WORK REQUIRED FOR INSTALLING THE
ELECTRICAL SYSTEMS AND TO REPAIR TO "LIKE NEW
CONDITION" TO BE PROVIDED AND INSTALLED BY
CONTRACTOR. COORDINATE WITH GENERAL
CONTRACTOR.
8. PROVIDE AND INSTALL ANY ADDITIONAL
HANGERS/SUPPORTS REQUIRED TO ACCOMMODATE ANY
EQUIPMENT RELOCATION.
9. COORDINATE ALL CEILING MOUNTED DEVICES WITH
ARCHITECTURAL REFLECTED CEILING AND WORK OF ALL
OTHER TRADES.
10. ITEMS NOTED AS EXISTING TO BE REMOVED "DEMO" SHALL
BE REMOVED COMPLETELY. REMOVAL SHALL INCLUDE
CONDUIT BOXES, HANGERS AND CONDUCTORS BACK TO
BRANCH PANELBOARD. ALL LIGHTING EQUIPMENT TO BE
"DEMO" SHALL INCLUDE REMOVAL OF LIGHTING CONTROL
CIRCUIT WITH ALL ASSOCIATED WIRING, BOXES, SUPPORTS
AND CONDUIT BACK TO POINT OF BRANCH CIRCUIT ORIGIN
WITHIN PANELBOARD AND RE FEED ALL DOWN STREAM
DEVICES TO REMAIN. PATCH DISTURBED AREA. UPDATE
SCHEDULE AS REQUIRED.
FLOOR
PLAN
NORTH
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:23 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
FIRST LEVEL
DEMOLITION PLAN
ELECTRICAL
E1.100
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
1/8" = 1'-0"E1.100
1 1ST LEVEL - Demo Work Electrical
REFERENCE NOTE
1 REMOVE RECEPTACLES, LIGHT FIXTURES, SWITCHES, FIRE
ALARM DEVICES, WIRE, AND CONDUIT IN WALLS THAT ARE
TO BE REMOVED BACK TO POINT OF CIRCUIT ORIGIN.
MAINTAIN CIRCUIT CONTINUITY TO DEVICES LOCATED
OUTSIDE OF SCOPE OF WORK.
2 EXISTING DISCONNECT FOR PARALLEL FAN-POWERED BOX
TO BE REMOVED. REMOVE EXISTING WIRING, BOXES,
SUPPORTS, AND CONDUIT IN WALLS. BRANCH CIRCUIT
TO REMOVED BACK TO PANEL OF ORIGIN.
EXISTING CONNECTION FOR UNDERFLOOR ELECTRICAL
SYSTEM. REMOVE EXISTING WIRING, BOXES AND CONDUITS
IN FLOORS. BRANCH CIRCUIT TO BE REMOVED BACK TO
PANEL OF ORIGIN. VERIFY IN FIELD EXACT LOCATIONS OF
CONNECTIONS.
F F
F F
F
F
F
F F
F
FFF
F
F
F
S M
S M
S M
F
F
F
F
J J
J
A A
B B
G G
H H
J J
D D
E E
F F
BREAK
ROOM
OFFICE
CASH
IT
HALL
STORAGE
HALL
CHECK-IN
STAFF
CHECK-IN
ENTRY
WAITING A
WAITING B
SERVICE
TESTING
CUSTOMER
SERVICE
HALL
HALL
HALL
NIC
1 1 1
1 1
D/W
ELEC
TV TV
MICRO.
MICRO.
TV TV
REFRIG.
COFFEE
H1B
BUS
DUCT B
DISC. T-1
DISC. H1B
L1B
EL1
L1B- 35
L1B- 35
L1B- 35
L1B- 35
L1B- 10
L1B- 50L1B- 52
L1B- 8
L1B- 12
L1B- 35L1B- 35
L1B- 22
L1B- 26
L1B- 28 L1B- 28
L1B- 28
L1B- 28
L1B- 30
L1B- 32
L1B- 32
L1B- 34
L1B- 34
L1B- 34
L1B- 34
L1B- 34L1B- 34
L1B- 36 L1B- 36
L1B- 44 L1B- 44
L1B- 44
L1B- 46
L1B- 46
L1B- 46
L1B- 46
L1B- 27
L1B- 27 L1B- 27 L1B- 27
L1B- 27 L1B- 27 L1B- 27 L1B- 27
L1B- 33L1B- 33
PTU
1.4
PTU
1.3
PTU
1.1
VAV
1.1
PTU
1.5
PTU
1.2
VAV
1.3
VAV
1.2
L1B- 29
L1B- 29
L1B- 29
T-1
L1B- 54
3 4
L1B-
56,58,60
L1B- 62
3 4
L1B-
64,66,68
3 4
L1B- 70 L1B-
72,74,76
NIC
GENERAL NOTE
1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY
CONSERVATION C405.5.3 AND 2020 NEC 210.19 WITH
REGARDS TO VOLTAGE DROP (5%).
2. FIRE ALARM DEVICES WHERE REQUIRED SHALL BE
INSTALLED IN COMPLIANCE WITH NFPA AND FLORIDA FIRE
PREVENTION CODE.
3. REFER TO ARCHITECTURAL AND INTERIOR DESIGNER
DRAWINGS FOR ALL ELECTRICAL DEVICE MOUNTING
HEIGHTS, QUANTITIES AND LOCATIONS.
4. COORDINATE WITH OWNER FOR EXACT DATA/COMM
REQUIREMENTS.
5. SEAL ALL FIRE WALLS, ROOF, AND FLOOR PENETRATIONS
WITH UL LISTED FIRE SEALANT.
FLOOR
PLAN
NORTH
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:34 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
FIRST LEVEL PLAN
POWER
E1.101
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
1/8" = 1'-0"E1.101
1 1ST LEVEL - New Work Electrical Power
REFERENCE NOTE
1 NEW FIRE ALARM DEVICE. DEVICE SHALL BE COMPATIBLE
WITH EXITING FIRE ALARM SYSTEM. CONNECT TO EXISTING
NOTIFICATION CIRCUIT. VERIFY CIRCUIT AND BATTERY
CAPACITY.
2 SEE MECHANICAL EQUIPMENT CONNECTION SCHEDULE ON
THIS SHEET FOR ELECTRICAL REQUIREMENTS FOR
MECHANICAL EQUIPMENT.
3 PROVIDE 3-POLE BREAKERS SERVING THE SAME
PIECE OF MODULAR FURNITURE.
4 PROVIDE CONNECTION FOR MODULAR OFFICE FURNITURE.
PROVIDE FLEXIBLE CONDUIT CONNECTION FROM WALL
J-BOX TO POWER FURNITURE JUNCTION BOX FOR POWER
AND SEPARATE CONDUIT CONNECTION FOR
COMMUNICATIONS SERVICE, COORDINATE WITH ID.
6. VARIABLE FREQUENCY DRIVE (VFD) IS FURNISHED BY DIVISION 23, INSTALLED ANY CONNECTED BY DIVISION 26. DISCONNECTING MEANS IS INTEGRAL TO VFD.
5. INTERIOR FAN COIL UNIT IS POWERED BY OUTDOOR CONDENSING UNIT WITH 3#10 AWG IN 3/4"C.
4. ALL EQUIPMENT RECEIVING CONTROL POWER ONLY ARE NOT SHOWN ON THIS SCHEDULE. REFER TO DIVISION 23 MECHANICAL SCHEDULES AND POWER PLANS FOR CIRCUITING REQUIREMENTS.
3. ELEVATOR SIZE IS ESTIMATED AS SHOP DRAWINGS HAVE NOT BEEN CREATED. VERIFY OVER CURRENT PROTECTING SIZE REQUIRED ON ELEVATOR SHOP DRAWINGS PRIOR TO ORDERING EQUIPMENT.
2. DISCONNECT IS INTEGRAL TO FAN COIL UNIT.
1. VERIFY DISCONNECT CIRCUIT BREAKER SIZE, FRAME SIZE, AND FUSE RATING/TYPE BASED ON DIVISION 22/23 SHOP DRAWINGS PRIOR TO BIDDING. ADJUST AS NECESSARY.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT AMPS LOAD VOLTAGE
NO. OF
POLES PANEL
CIRCUIT
NUMBER
COMBINATION STARTER/DISCONNECT
FEEDER CB RATING NOTESFRAME RATING FUSE RATING NEMA RATING
PTU-1.1 12 A 3.4 kVA 277 V 1 H1B 7 30 * 1 2#12, 1#12G, 1/2"C 20 A 1
PTU-1.2 9 A 2.4 kVA 277 V 1 H1B 9 30 * 1 2#12, 1#12G, 1/2"C 20 A 1
PTU-1.3 9 A 2.6 kVA 277 V 1 H1B 11 30 * 1 2#12, 1#12G, 1/2"C 20 A 1
PTU-1.4 8 A 2.2 kVA 277 V 1 H1B 13 30 * 1 2#12, 1#12G, 1/2"C 20 A 1
PTU-1.5 8 A 2.2 kVA 277 V 1 H1B 15 30 * 1 2#12, 1#12G, 1/2"C 20 A 1
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OSOSOS
OS
S
S
SOS
S
S
S c
OS
OS
OS
SOS
S
S3
OS
Sa
Se
S c
S
S 4c
S3
R
R
R
R
R
R
R
R
R
R
S3 S
S
S3 S
S d
Sf
S 3d
Sb
S d
DS
DS
DS
A A
B B
G G
H H
J J
C C
D D
E E
F F
C10 B
B
B
B
B
B
B
B
B B B B B B B
B
BB
C10
C10
C10
C10
C10
C10
B
A A
C10C10C10C10C10
C6C6 C6
C10
C10
C10C10C10
C4C4C4C4C4C4C4C4C4C4C4C4
B
B
B
B
B
B B
A
A
A A A
A A A
A A A
AA
A
A
BREAK
ROOM
OFFICE
CASH
IT
HALL
CHECK-IN
STAFF
CHECK-IN
ENTRY
WAITING A
WAITING B
SERVICE
TESTING
CUSTOMER
SERVICE
HALL
HALL
HALL
EX
EX
EX
EX
EX
EX
EX
EXEX
NIC
C8 C8 C8 C8
B C10
C2 C2 C2 C2
EX
H1B- 2 H1B- 2
H1B- 2 H1B- 2
H1B- 2
H1B- 2
PERMITTING
EX
H1B- 2
H1B- 2
H1B- 2
H1B- 2
H1B- 2 H1B- 2
A
H1B- 2
H1B- 2
H1B- 2
H1B- 2
H1B- 2
H1B- 2
H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4
H1B- 2
H1B- 2
H1B- 2
H1B- 2
H1B- 4
H1B- 4
H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4
H1B- 4
H1B- 4H1B- 4
H1B- 4H1B- 4H1B- 4
H1B- 4
H1B- 4 H1B- 4
H1B- 4
H1B- 4
H1B- 4 H1B- 4
H1B- 4 H1B- 4
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2
EL2B-2EL2B-2
EL2B-4
EL2B-4 EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4 EL2B-4
EL2B-4
EL2B-4
EL2B-4 EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4
EL2B-4EL2B-4
EL2B-4
EL2B-2
EL2B-2
EL2B-4
1 1
NIC
DS
STORAGE
d d d d d d d c c c c c c a a aa a a a a a a a a a a a a a b b a ab b b b bb b e e e e e e e e e e e f f f f f f f f e,f e,f e,f e,f e,f a,b a,b a,b a,b
GENERAL NOTE
1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY
CONSERVATION C405.5.3 AND 2020 NEC 210.19 WITH
REGARDS TO VOLTAGE DROP (5%).
2. ALL EMERGENCY AND EXIT LIGHTING SHALL BE
CONNECTED AHEAD OF ANY SWITCHING ARRANGEMENTS
OR CONTROLLED BY A LISTED UL924 CONTROLLER PER
N.E.C.
3. REFER TO ARCHITECTURAL AND LIGHTING DESIGNER
LIGHTING PLANS FOR ANY AND ALL LIGHTING FIXTURE
MOUNTING DIMENSIONS AND LOCATIONS.
4. SEAL ALL FIRE WALLS, ROOF, AND FLOOR PENETRATIONS
WITH UL LISTED FIRE SEALANT.
5. NEW EMERGENCY LIGHTING TO BE POWERED FROM
EXISTING CIRCUITS INDICATED. EXTEND WIRE AND
CONDUIT TO NEW EMERGENCY FIXTURES AS SHOWN.
FLOOR
PLAN
NORTH
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:45 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
FIRST LEVEL PLAN
LIGHTING
E1.102
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
1/8" = 1'-0"E1.102
1 1ST LEVEL - New Work Electrical Lighting
REFERENCE NOTE
1 EVERYTHING IN THIS SPACE IS EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
2 PROVIDE UL 924 RELAY TO TURN EMERGENCY LIGHTS IN
THE AREA TO FULL BRIGHTNESS UPON LOSS OF POWER.
3 LIGHTING IN INDICATED DAYLIGHT ZONE SHALL BE
CONTROLLED THE DAYLIGHT SENSOR IN SPACE. DAYLIGHT
CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH
2023 FBC ENERGY CONSERVATION SECTION C405.2.3.
GROUND LEVEL
SWBD-MDP
HOUSE
DISTRIBUTION
4000 AMPS
277/480V
3ø, 4W
BOND
N G
N.T.S.
PARTIAL EXISTING ELECTRICAL RISER DIAGRAM
ALL PANELS EXISTING TO REMAIN. RISER SHOWN FOR REFERENCE ONLY
PB
SECOND LEVEL
T1
75 KVA
M.C.B.
120/208V
225 AMP
3ø, 4W
L1B
PANEL
M.L.O.
120/208V
225 AMP
3ø, 4W
L1B
PANEL
M.L.O.
120/208V
225 AMP
3ø, 4W
L1B
PANELPANEL
M.L.O.
480/277V
250 AMP
3ø, 4W
H1B
ELEC B-110 MAIN ELECTRICAL ROOM
ETR BUSWAY
N.T.S.
FIRE ALARM RISER DIAGRAM
J J JJ J J JJJJ
FAAP
SEE POWER PLAN FOR EXACT QUANTITIES
PROVIDE NEW POWER
SUPPLY AS REQUIRED
FOR THE TOTAL BUILD
OUT OF THE NEW AREA
EXTEND NEW FIRE ALARM
CONDUCTORS TO NEW FIRE
ALARM SYSTEM DEVICES.
120V SURGE
SUPPRESSOR
FINISHED FLOOR FINISHED FLOOR
TYP. CLG
MOUNTED
S.D.
TYP. HVAC
EQUIPMENT
FIRE ALARM SYSTEM NOTE:
FIRE ALARM SYSTEM RISER DIAGRAM IS DIAGRAMMATICAL AND IN
ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE ARTICLE 61G15
DESIGN OF ALARM SYSTEMS. SEE POWER PLAN FOR EXACT
QUANTITIES OF DEVICES. WIRING SHALL BE AS RECOMMENDED BY
SYSTEMS MANUFACTURER AND PER NFPA 72. THE FIRE ALARM
CONTRACTOR IS REQUIRED TO PROVIDE ENGINEERED FIRE ALARM
DOCUMENTS PER THE FLORIDA ADMINISTRATIVE CODE 61G15.
A. FIRE ALARM SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES:
1. MANUAL STATIONS.
2. HEAT DETECTORS.
3. SMOKE DETECTORS.
4. VERIFIED AUTOMATIC ALARM OPERATION OF SMOKE DETECTORS.
5. AUTOMATIC SPRINKLER SYSTEM WATER FLOW.
B. FIRE ALARM SIGNAL SHALL INITIATE THE FOLLOWING ACTIONS:
1. ALARM NOTIFICATION APPLIANCES SHALL OPERATE CONTINUOUSLY
2. IDENTIFY ALARM AT THE FACP AND REMOTE ANNUNCIATORS.
3. TRANSMIT AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION.
4. SWITCH HEATING, VENTILATING, AND AIR-CONDITIONING EQUIPMENT CONTROLS TO
FIRE ALARM MODE.
5. RECORD EVENTS IN THE SYSTEM MEMORY.
C. SUPERVISORY SIGNAL INITIATION SHALL BE BY OPERATION OF A FIRE-PROTECTION
SYSTEM VALVE TAMPER.
D. SYSTEM TROUBLE SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING
DEVICES OR ACTIONS:
1. OPEN CIRCUITS, SHORTS AND GROUNDS OF WIRING FOR INITIATING DEVICE,
SIGNALING LINE, AND NOTIFICATION-APPLIANCE CIRCUITS.
2. OPENING, TAMPERING, OR REMOVAL OF ALARM-INITIATING AND SUPERVISORY
SIGNAL-INITIATING DEVICES.
3. LOSS OF PRIMARY POWER AT THE FACP.
4. GROUND OR A SINGLE BREAK IN FACP INTERNAL CIRCUITS.
5. ABNORMAL AC VOLTAGE AT THE FACP.
6. A BREAK IN STANDBY BATTERY CIRCUITRY.
7. FAILURE OF BATTERY CHARGING.
8. ABNORMAL POSITION OF ANY SWITCH AT THE FACP OR ANNUNCIATOR.
E. SYSTEM TROUBLE AND SUPERVISORY SIGNAL ACTIONS: RING TROUBLE BELL AND
ANNUNCIATE AT THE FACP AND REMOTE ANNUNCIATORS. RECORD THE EVENT.
FIRE ALARM SYSTEM SEQUENCE OF OPERATIONS (REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)
F FF FF FFF
EXIST. FIRE
ALARM
CONTROL
PANEL
F. ACTUATION OF ALARM NOTIFICATION APPLIANCES, ANNUNCIATION, ELEVATOR RECALL, AND
ACTUATION OF SUPPRESSION SYSTEMS SHALL OCCUR WITHIN 10 SECONDS AFTER THE
ACTIVATION OF AN INITIATING DEVICE.
G. SMOKE-ALARM VERIFICATION:
1. INITIATE AUDIBLE AND VISIBLE INDICATION OF AN "ALARM VERIFICATION" SIGNAL AT
THE FACP.
2. ACTIVATE A LISTED AND APPROVED "ALARM VERIFICATION" SEQUENCE AT THE
FACP AND THE DETECTOR.
3. RECORD EVENTS.
4. SOUND GENERAL ALARM IF THE ALARM IS VERIFIED.
5. CANCEL FACP INDICATION AND SYSTEM RESET IF THE ALARM IS NOT VERIFIED.
H. POWER SUPPLY FOR SUPERVISION EQUIPMENT: SUPPLY FOR AUDIBLE AND VISUAL
EQUIPMENT FOR SUPERVISION OF THE AC POWER SHALL BE FROM A DEDICATED DC POWER
SUPPLY, AND POWER FOR THE DC COMPONENT SHALL BE FROM THE AC SUPPLY.
I. ALARM SILENCING, TROUBLE, AND SUPERVISORY ALARM RESET: MANUAL RESET AT THE
FACP AND REMOTE ANNUNCIATORS, AFTER INITIATING DEVICES ARE RESTORED TO
NORMAL.
1. SILENCING-SWITCH OPERATION HALTS ALARM OPERATION OF NOTIFICATION
APPLIANCES AND ACTIVATES AN "ALARM SILENCE" LIGHT. DISPLAY OF IDENTITY OF
THE ALARM ZONE OR DEVICE IS RETAINED.
2. SUBSEQUENT ALARM SIGNALS FROM OTHER DEVICES OR ZONES REACTIVATE
NOTIFICATION APPLIANCES UNTIL SILENCING SWITCH IS OPERATED AGAIN.
3. WHEN ALARM-INITIATING DEVICES RETURN TO NORMAL AND SYSTEM RESET SWITCH
IS OPERATED, NOTIFICATION APPLIANCES OPERATE AGAIN UNTIL ALARM SILENCE
SWITCH IS RESET.
J. DUCT SMOKE DETECTORS SHALL BE PROGRAMMED AS A SUPERVISORY SIGNAL/FUNCTION
IN ACCORDANCE WITH 9.6.3.2.2, NFPA 101, 2012 ED. AS ADOPTED IN THE FFPC, 5TH ED.
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:53 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
ELECTRICAL RISERS AND
PANEL SCHEDULES
E6.000
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
ELECTRICAL RISER NOTE
1. ALL ELECTRICAL EQUIPMENT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
SHOWN FOR REFERENCE ONLY.
Notes:
Receptacle 7.76 kVA 100.00% 7.76 kVA Demand Amps: 70 A
Other 0.00 kVA 0.00% 0.00 kVA Total Demand Load: 58.6 kVA
Lighting 20.52 kVA 100.00% 20.52 kVA Total Connected Load: 58.6 kVA
HVAC 30.28 kVA 100.00% 30.28 kVA
CONN.
LOAD...
DEMAND
FACTOR
DEMAND
LOAD...
Phase Connected Load: 23.6 18.9 16.1
41 SPACE -- 1 -- -- -- -- 1 -- SPACE 42
39 SPACE -- 1 -- -- -- -- 1 -- SPACE 40
37 SPACE -- 1 -- -- -- -- 1 -- SPACE 38
35 SPACE -- 1 -- -- -- -- 1 -- SPACE 36
33 SPACE -- 1 -- -- -- -- 1 -- SPACE 34
31 SPACE -- 1 -- -- -- -- 1 -- SPACE 32
29 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 30
27 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 28
25 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 24
21 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 3.88 3.88 EXISTING TO REMAIN 1 20 A EX-UV LIGHTS 22
19 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 3.88 3.88 EXISTING TO REMAIN 1 20 A EXISTING LOAD 20
17 SPARE 30 A 1 -- 0.00 3.88 EXISTING TO REMAIN 1 20 A EXISTING LOAD 18
15 PTU-1.5 20 A 1 2#12, 1#12G, 1/2"C 2.19 0.00 -- 1 20 A SPARE 16
13 PTU-1.4 20 A 1 2#12, 1#12G, 1/2"C 2.19 0.00 -- 1 20 A SPARE 14
11 PTU-1.3 20 A 1 2#12, 1#12G, 1/2"C 2.56 0.00 -- 1 20 A SPARE 12
9 PTU-1.2 20 A 1 2#12, 1#12G, 1/2"C 2.44 0.00 -- 1 20 A SPARE 10
7 PTU-1.1 20 A 1 2#12, 1#12G, 1/2"C 3.44 3.88 EXISTING TO REMAIN 1 20 A EX-LTG 51 8
5 EX-VAV 2-01, 2-04 30 A 1 EXISTING TO REMAIN 5.82 3.88 EXISTING TO REMAIN 1 20 A EX-LTG 59, 60, 61, 62,... 6
3 EX-VAV 2-17 30 A 1 EXISTING TO REMAIN 5.82 0.66 2#12, 1#12G, 1/2"C 1 20 A CUSTOMER SERVICE... 4
1 EX-VAV 2-15 30 A 1 EXISTING TO REMAIN 5.82 0.63 2#12, 1#12G, 1/2"C 1 20 A CHECK-IN LIGHTS 2
C K T
LOAD NAME TRIP
P O L E S
WIRE SIZE A B C WIRE SIZE
P O L
E...
TRIP LOAD NAME
C K T
FLUSH MTD: 240/120V
SURFACE MTD: X X 480Y/277V
K.A.I.C. : EX. AMPS 208Y/120V Fed From: SWBD-MDP
MAIN LUGS: 250 AMPS 4 WIRE Project Number: I24027
MAIN BREAKER: AMPS 3 PHASE Project Name: VOLUSIA COUNTY TAX COLLECTOR
Name: H1B
* REUSE EXISTING BREAKERS FOR NEW EQUIPMENT.
Notes:
Continuous 21.85 kVA 125.00% 27.31 kVA
Receptacle 65.11 kVA 57.68% 37.56 kVA Demand Amps: 219 A
Motor 0.15 kVA 108.33% 0.16 kVA Total Demand Load: 78.7 kVA
Lighting 10.08 kVA 100.00% 10.08 kVA Total Connected Load: 100.8 kVA
Equipment 3.62 kVA 100.00% 3.62 kVA
CONN.
LOAD...
DEMAND
FACTOR
DEMAND
LOAD...
Phase Connected Load: 34.4 36.4 30.0
125 SPACE -- 1 -- -- -- -- 1 -- SPACE 126
123 SPACE -- 1 -- -- -- -- 1 -- SPACE 124
121 SPACE -- 1 -- -- -- -- 1 -- SPACE 122
119 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 120
117 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 118
115 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 116
113 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 114
111 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 112
109 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 110
107 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 108
105 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 106
103 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 104
101 FIRE ALARM PANEL 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 102
99 SPARE 20 A 1 -- 0.00 0.90 EXISTING TO REMAIN 1 20 A EX-FLR. BOX RECP RM
97 EX-LTG. RMS. 30, 34 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 98
95 EX-LTG. RMS.30, 34 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 96
93 EX-LTG. RMS. 84, 81, 2, 29 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 94
91 EX-LTG .RM. 29 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 92
89 EX-LTG. RMS. 118, 1 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-NEW MONITOR 90
87 EX-LTG. RMS. 118, 85 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-LTG 88
85 EX-LTG EXT. 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-LTG EXT. 86
83 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 84
81 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 82
79 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 80
77 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 78
75 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 -- -- -- -- 76
73 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 -- -- -- -- 74
71 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 72
69 -- -- -- -- 2.19 0.23 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 70
67 EX-TRAINING ROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 -- -- -- -- 68
65 -- -- -- -- 2.19 0.45 -- -- -- -- 66
63 EX-MENS RESTROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 64
61 -- -- -- -- 2.19 0.45 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 62
59 EX-MENS RESTROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 -- -- -- -- 60
57 -- -- -- -- 2.19 0.45 -- -- -- -- 58
55 EX-WOMENS RESTROO... 30 A 2 EXISTING TO REMAIN 2.19 0.45 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 56
53 -- -- -- -- 2.19 0.45 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 54
51 EX-WOMENS RESTROO... 30 A 2 EXISTING TO REMAIN 2.19 0.60 2#12, 1#12G, 1/2"C 1 20 A REFRIGERATOR 52
49 EX-DIRT WALL RECEPT 20 A 1 EXISTING TO REMAIN 1.68 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 50
47 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 48
45 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.72 2#12, 1#12G, 1/2"C 1 20 A WAITING B RM. REC. 46
43 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.54 2#12, 1#12G, 1/2"C 1 20 A HALLWAY REC. 44
41 SPARE 20 A 1 -- 0.00 0.36 EXISTING TO REMAIN 1 20 A EX-CONF. RECPS 42
39 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 1.20 0.36 EXISTING TO REMAIN 1 20 A EX-LOAD 40
37 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 1.20 0.36 EXISTING TO REMAIN 1 20 A EX-LOAD 38
35 BREAK ROOM REC. 20 A 1 2#12, 1#12G, 1/2"C 1.08 0.72 2#12, 1#12G, 1/2"C 1 20 A IT RM. REC. 36
33 SERVICE RM. REC. 20 A 1 2#12, 1#12G, 1/2"C 0.36 1.08 2#12, 1#12G, 1/2"C 1 20 A CASH RM. REC. 34
31 SPARE 20 A 1 -- 0.00 0.36 2#12, 1#12G, 1/2"C 1 20 A HALLWAY REC. 32
29 VAV-1.1, VAV-1.2, VAV-1.3 20 A 1 2#12, 1#12G, 1/2"C 0.15 0.18 2#12, 1#12G, 1/2"C 1 20 A CHECK-IN REC. 30
27 TESTING RM. REC. 20 A 1 2#12, 1#12G, 1/2"C 1.44 0.72 2#12, 1#12G, 1/2"C 1 20 A OFFICE RM REC. 28
25 EX-LTGS RM 036 20 A 1 EXISTING TO REMAIN 1.08 1.20 2#12, 1#12G, 1/2"C 1 20 A COFFEE 26
23 EX-POWER OUTLETS 20 A 1 EXISTING TO REMAIN 0.36 0.54 EXISTING TO REMAIN 1 20 A EWC RM 54 24
21 EX-FLAT BOX 20 A 1 EXISTING TO REMAIN 0.36 0.50 2#12, 1#12G, 1/2"C 1 20 A DISHWASHER 22
19 EX-FLOOR BOX3 20 A 1 EXISTING TO REMAIN 0.36 0.00 -- 1 20 A SPARE 20
17 RECEPS. - RM 50, 52 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-ALERTON CTRLS 18
15 EX-RECEPS. - RM 50, 51 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-CONF. RM 65 16
13 RECEPS. - RM 64, 63 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-CONF. TV 14
11 RECEPS. - RM 52, 51 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 12
9 RECEPS. - RM 53, 52 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 10
7 RECPS. - RM 61, 53, 55 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 8
5 RECPS. - RM 42, 41, 45,... 20 A 1 EXISTING TO REMAIN 1.08 0.54 EXISTING TO REMAIN 1 20 A EX-RECPS RM 55, 57, 57 6
3 EX-RECPS. - RM 044 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-COLUMN FURNITURE... 4
1 EX-RECPS. - RM 50, 44 20 A 1 EXISTING TO REMAIN 1.08 0.54 EXISTING TO REMAIN 1 20 A EX-COLUMN FURNITURE... 2
C K T
LOAD NAME TRIP
P O L E S
WIRE SIZE A B C WIRE SIZE
P O L
TRIP LOAD NAME
C K T
FLUSH MTD: 240/120V
SURFACE MTD: X 480Y/277V
K.A.I.C. : EX. AMPS X 208Y/120V Fed From: T1
MAIN LUGS: 225 AMPS 4 WIRE Project Number: I24027
MAIN BREAKER: AMPS 3 PHASE Project Name: VOLUSIA COUNTY TAX COLLECTOR
Name: L1B
System No. W-J-1020
SECTION A-A
A
F Rating — 2 Hr
T Ratings — 0 and 1/4 Hr (See Item 3B)
L Rating At Ambient — Less Than 1 CFM/Sq Ft L Rating At 400 F — 4 CFM/Sq Ft
A
3B
3A
1. WALL ASSEMBLY - MIN 5 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 8 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL
ASSEMBLY. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3-1/2 IN. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
B. COPPER TUBING - NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
C. COPPER PIPE - NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. FIRESTOP SYSTEM - THE HOURLY F AND T RATING FOR THE FIRESTOP SYSTEMS ARE DEPENDENT UPON THE TYPE AND SIZE OF
PIPE, ANNULAR SPACE, FILL MATERIAL THICKNESS AND FILL MATERIAL TYPE AS DESCRIBED IN THE TABLE BELOW. WHEN THE ANNULAR
SPACE IN THE TABLE SHOWS A RANGE OF DISTANCES, THE PENETRATING ITEM MAY BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE FIRESTOP SYSTEMS SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. AS AN
OPTION TO THE ABOVE, BACKER ROD AND/OR FOAMED PLASTIC BACKER MATERIAL MAY BE USED. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID OR CAVITY MATERIAL - SEALANT* - APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL AS
SHOWN IN THE TABLE BELOW:
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — FS-One Sealant
*Bearing the UL Classification Mark
Pipe Type Min Fill Mtl Thkns In. F Rating Hr. T Rating Hr.
2A 1/4 2 1/4
2B 1/2 2 0
CEILING OCCUPANCY SENSOR DETAIL
H (BLACK)
LOAD
120/277 VAC BLACK BLUE
NEUTRAL
GROUND
GREEN
ONW AND VNW MANUAL MODE
1. SWITCH IS REQUIRED
TO TURN LOAD ON.
2. LOAD TURNS OFF
WHEN SENSOR TIMES
OUT OR WITH SWITCH.
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
LOAD WILL NOT TURN ON.
ONW - AUTOMATIC MODE
1. WHEN SENSOR ACTIVATES LOAD
TURNS ON.
2. SWITCH CAN BE USED TO TURN
LOAD ON OR OFF.
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
LOAD WILL NOT TURN ON.
WALL MOUNT OCCUPANCY SENSOR DETAIL
LOAD "A"
RED (RELAY 2)
NEUTRAL
HOT
**USE BLACK LEAD FOR 120VAC.
USE ORANGE LEAD FOR 277VAC.
CAP UNUSED LEAD.
LINE
BLACK BLACK (COMMON)
BLUE (CONTROL -RELAY 1)
RED (24VDC)
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, BOTH
LOADS TURN ON.
2. LOADS TURN OFF WHEN SENSOR
TIMES OUT.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
NOTES
1. SPD20-MV-NO SWITCHPACK SHOWN.
120/277VAC 20AMP RATING PER RELAY.
2. BLUE AND RED WIRE LEADS ARE
NON-POLARITY SENSITIVE.
YELLOW(CONTROL- RELAY 2)
RED (RELAY 2)
BLUE (RELAY 1)
BLUE (RELAY 1)
WHITE
HOT ** LOAD "B"
BLUE (CONTROL)
RED (10-30VDC)
(OPTIONAL
MANUAL-OFF
TOGGLE
SWITCHES)
TYPICAL FIRE WALL PENETRATION DETAIL
NTS
OCCUPANCY SENSORS
NTS
N.T.S.
SYSTEM NO. WL2004
SECTION A-A
3B
A
3C
A
3B
3A
3A
1B
3C
1A
THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS:
STEEL SLEEVE - NOM 8 IN. LONG CYLINDRICAL SLEEVE WITH NOM
7/8 IN. WIDE BY 1-3/4 IN. LONG ANCHOR TABS AND NOM 3/4 IN.
LONG TABS TO RETAIN WRAP STRIP LAYER (ITEM B). SHEET OF
PRECUT 0.016 THICK (30 GAUGE) GALV SHEET STEEL AVAILABLE
FROM WRAP STRIP MANUFACTURER. AS AN ALTERNATE, CYLINDRICAL
SLEEVE MAY BE FABRICATED FROM MIN 0.016 IN. THICK (NO. 30
GAUGE) GALV SHEET STEEL IN ACCORDANCE WITH INSTRUCTION SHEET
SUPPLIED BY WRAP STRIP MANUFACTURER. SHEET STEEL FORMED
INTO CYLINDRICAL SLEEVE WITH INSIDE DIAM OF STEEL SLEEVE AND
DIAM OF THROUGH OPENING IN THE GYPSUM WALLBOARD LAYERS TO
BE EQUAL TO OUTSIDE DIAM OF WRAP STRIP (ITEM B) LAYERS ON
PIPE (-0, +1/8 IN.). CYLINDRICAL SLEEVE INSERTED IN ANNULAR
SPACE AROUND NONMETALLIC PIPE, CENTERED IN WALL AND LOCKED
IN POSITION BY BENDING THE ANCHOR TABS OUTWARD 90 DEG
AGAINST THE INNER LAYER OF GYPSUM WALLBOARD WITHIN THE STUD
CAVITY. AFTER INSTALLATION OF WRAP STRIP LAYERS (ITEM B),
RETAINER TABS OF CYLINDRICAL SLEEVE BENT 90 DEG TOWARD PIPE
ON BOTH SIDES OF WALL ASSEMBLY TO LOCK WRAP STRIP LAYERS IN
POSITION.
FILL, VOID OR CAVITY MATERIALS* - WRAP STRIP - NOM 1/4 IN.
THICK INTUMESCENT ELASTOMERIC MATERIAL FACED ON ONE SIDE
WITH ALUMINUM FOIL, SUPPLIED IN 2 IN. WIDE STRIPS. NOM 2 IN.
WIDE STRIPS TIGHTLY WRAPPED AROUND NONMETALLIC PIPE (FOIL SIDE
EXPOSED) AND SLID INTO STEEL SLEEVE ON BOTH SIDES OF WALL
ASSEMBLY. FOR NOM 1/2 IN. TO NOM 2 IN. DIAM NONMETALLIC
PIPES, ONE LAYER OF WRAP STRIP IS REQUIRED. FOR NOM 2-1/2
IN. AND NOM 3 IN. DIAM NONMETALLIC PIPES, TWO LAYERS OF WRAP
STRIP ARE REQUIRED. FOR NOM 3-1/2 IN. AND NOM 4. IN. DIAM
NON METALLIC PIPES, THREE LAYERS OF WRAP STRIP ARE REQUIRED.
EACH LAYER OF WRAP STRIP TO BE INSTALLED WITH BUTTED SEAM,
WITH BUTTED SEAMS IN SUCCESSIVE LAYERS STAGGERED. WRAP STRIP
LAYERS ON EACH SIDE OF WALL TO PROTRUDE 3/4 IN. FROM WALL
SURFACE WITH THE EXPOSED EDGES ABUTTING THE RETAINER TABS
OF THE STEEL SLEEVE. MINNESOTA MINING & MFG. CO. - TYPE
FS-195
FILL, VOID OR CAVITY MATERIALS* - CAULK - GENEROUS BEAD OF
CAULK APPLIED TO OUTER PERIMETER OF STEEL SLEEVE AT
INTERFACE WITH WALL SURFACE AND TO PERIMETER OF NONMETALLIC
PIPE AT ITS EGRESS FROM THE WRAP STRIP LAYERS APPROX 3/4 IN.
FROM THE WALL SURFACE. MINNESOTA MINING & MFG. CO. - TYPES
CP-25 S/L, CP-25 N/S, CP- 25 WB, CP-25 WB+
FILL, VOID OR CAVITY MATERIALS* - MAT WRAP - (NOT SHOWN) -
FLEXIBLE SHEET MATERIAL, FACED ON ONE SIDE WITH ALUMINUM FOIL,
SUPPLIED IN ROLLS. WHEN REQUIRED (SEE TABLE), MIN 6 IN. WIDE
STRIP OF MAT WRAPPED TIGHTLY AROUND CIRCUMFERENCE OF PIPE
(FOIL FACE EXPOSED) AT ITS EGRESS FROM WRAP STRIP ON BOTH
SIDES OF WALL. MAT WRAP OVERLAPPED MIN 1/2 IN. AT SEAM AND
SECURED IN PLACE WITH STEEL WIRE TIES, OR EQUIVALENT, SPACED
MAX 4 IN. OC. EDGE OF MAT ABUTTING WRAP STRIP TO BE SEALED
WITH A MIN 1/4 IN. DIAM BEAD OF CAULK (ITEM C). MINNESOTA
MINING & MFG. CO. - TYPE E-5A *BEARING THE UL CLASSIFICATION
MARKING
A.
B.
C.
D.
WALL ASSEMBLY - THE 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD
WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN
THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL
OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND
SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR
STEEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER
SPACED 16 IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATES AND
CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8
IN. DEEP CHANNELS SPACED MAX 24 IN. OC.
WALLBOARD, GYPSUM* - TWO LAYERS OF NOM 5/8 IN. THICK GYPSUM
WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION
DESIGN. MAX DIAM OF OPENING IS 6-1/4 IN.
NONMETALLIC PIPE OR CONDUIT - ONE NONMETALLIC PIPE OR CONDUIT
CENTERED IN FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY
SUPPORTED ON BOTH SIDES OF WALL. THE FOLLOWING TYPES AND SIZES
OF NONMETALLIC PIPES OR CONDUIT MAY BE USED IN CLOSED
(PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING
SYSTEMS:
NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 POLYVINYL CHLORIDE
(PVC) PIPE.
NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 SOLID-CORE
ACRYLONITRILE BUTADIENE-STYRENE (ABS) PIPE.
NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) FIRE
RETARDANT POLYPROPYLENE (FRPP) PIPE.
NOM 4 IN. DIAM (OR SMALLER) RIGID NONMETALLIC CONDUIT FORMED OF
PVC.
NOM 1 IN. DIAM (OR SMALLER) ELECTRICAL NONMETALLIC TUBING
FORMED OF PVC.
NOM 2 IN. DIAM (OR SMALLER) SDR11 (OR HEAVIER) POLYBUTYLENE
(PB) PIPE.
NOM 3 IN. DIAM (OR SMALLER) SDR13.5 (OR HEAVIER) CHLORINATED
POLYVINYL CHLORIDE (CPVC) PIPE.
SEE RIGID NONMETALLIC CONDUIT (DZKT) AND ELECTRICAL NONMETALLIC
TUBING (FKHU) CATEGORIES IN ELECTRICAL CONSTRUCTION MATERIALS
DIRECTORY FOR NAMES OF MANUFACTURERS.
1.
A.
B.
2.
A.
B.
C.
D.
E.
F.
G.
3. FIRESTOP SYSTEM - INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY.
THE HOURLY T RATINGS FOR THE FIRESTOP SYSTEM ARE DEPENDENT UPON THE TYPE
AND SIZE OF NONMETALLIC PIPE OR CONDUIT, AS TABULATED BELOW:
PIPE/ NOM ANNULAR F T
CONDUIT PIPE SPACE, RATING RATING
TYPE DIAM, IN. IN. HR HR
PB 1/2 TO 2 1/4-3/8 2 2
PVC, ABS CPVC, 2-1/2 TO 3 1/2-5/8 2 2
PVC,ABS 3-1/2 TO 4 3/4-7/8 2 1-1/2
PP+ 2-1/2 TO 3 1/2-5/8 2 3/4
PP+ 3-1/2 TO 4 3/4-7/8 2 3/4
+MAT WRAP REQUIRED ON PIPE ON BOTH SIDES OF WALL.
PENETRATION DETAIL
NTS
DRAWING NUMBER
SEAL
S
RACH ITECTS
TITLE
DATE
LOCATION
OWNER
PROJECT
605 E. Robinson Street Suite 630
Orlando, Florida 32801 Office 321.296.8100 silling.com
CA# 26308 I24027.00
5/16/2025 8:50:56 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt
ELECTRICAL DETAILS
E8.000
Volusia County Tax Collector
Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720
Volusia County Tax Collector - Deland Office Renovation
Joseph B Harrill PE 73015
05.15.2025
| E0.001 - ELECTRICAL LEGEND, NOTES & ABBREVIATIONS |
| E1.100 - FIRST LEVEL DEMOLITION PLAN ELECTRICAL |
| E1.101 - FIRST LEVEL PLAN POWER |
| E1.102 - FIRST LEVEL PLAN LIGHTING |
| E6.000 - ELECTRICAL RISERS AND PANEL SCHEDULES |
| E8.000 - ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .