Electrical.pdf

PDF 2 MB Posted

Attached to
Tax Collector Interior Renovations and Restoration
Solicitation number
25-B-127LL
Issued by
Volusia County, Florida

About this file

This document is an electrical drawing set for the Volusia County Tax Collector Interior Renovation project located in DeLand, Florida. The electrical documents include a comprehensive set of drawings covering electrical symbols and legends, demolition plans, new electrical power and lighting plans, electrical riser diagrams, panel schedules, fire alarm system details, and electrical penetration details. The drawings are dated 05.15.2025 and are marked "Issue for Permit", indicating the project is in the final design stages preparatory to construction authorization.

The electrical design encompasses first-level renovation work including power distribution, lighting layouts, fire alarm system modifications, and mechanical equipment electrical connections. The drawings show detailed electrical infrastructure for various rooms including entry, waiting areas, check-in spaces, offices, break rooms, and service areas. Specific technical elements include occupancy sensors, fire wall penetration details, panel schedules showing existing and new electrical loads, and comprehensive fire alarm system sequence of operations. The electrical design appears to be part of a broader renovation project for the Volusia County Tax Collector's administration office, with a focus on modernizing electrical systems while maintaining existing infrastructure where possible.

View the file

Other files

File Type Posted
Tax_Collector_Interior_Renovations_and_Restoration_(Addendum_#3_Revision).pdf PDF
M1.101_-_FIRST_LEVEL_PLAN_AND_SCHEDULES_MECHANICAL.pdf PDF
E1.102_-_FIRST_LEVEL_PLAN_LIGHTING.pdf PDF
E1.101_-_FIRST_LEVEL_PLAN_POWER.pdf PDF
E0.001_-_ELECTRICAL_LEGEND_NOTES_ABBREVIATIONS.pdf PDF
Attachment_E_-_Additional_Renderings.pdf PDF
Attachment_D_-_Fire_Alarm_Panel.pdf PDF
Tax_Collector_Interior_Renovations_and_Restoration.pdf PDF
MASTER_Construction_Contract.pdf PDF
Attachment_C_-_Staging_2.png PNG image
Attachment_B_-_Staging_1.png PNG image
Attachment_A_-_Parking.png PNG image
COV_Division_27,_IT_Systems_Design_and_Installation_Guidelines_for_A-E.pdf PDF
Sales_Tax_Exemption_Procedure.pdf PDF
PRIME-SUB_FORM.xls XLS spreadsheet
VC_Tax_Collector_DeLand_Office_Project_Manuals_5.15.2025.pdf PDF
VC_Tax_Collector_DeLand_Office_Renovation_Bid_Set_5.15.2025.pdf PDF
Payment_and_Performance_Bond.pdf PDF
Basic_Insurance_Requirements.pdf PDF
Special_Conditions.pdf PDF
Bid_Documents.pdf PDF
VCTCO_Architectural.pdf PDF
VCTCO_Volume_2_specs.pdf PDF
Mechanical.pdf PDF
VCTCO_Volume_1_specs.pdf PDF
Fire_Protection.pdf PDF
2025-05-15_-_BID_&_PERMIT_SET_-_Telecommunications.pdf PDF
VOLUSIA_COUNTY_TC_Form_C402.pdf PDF
Plumbing.pdf PDF
staging_(1).png PNG image
Pre-Bid_Meeting_Invitee_Listing.docx DOCX document
Staging.png PNG image
Parking.png PNG image
PRIME-SUB_FORM_for_Contractors_rev._01.15.2025_(lock_before_publishing)_(1).xls XLS spreadsheet
SPECIAL_CONDITIONS_FOR_BIDDERS.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SERVICE AND DISTRIBUTION

ELECTRICAL SYMBOLS LEGEND

ABBREVIATIONS

DUPLEX RECEPTACLE - TOP HALF SWITCHED - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE , COMMUNICATIONS AND DATA OUTLETS MOUNTED TOGETHER IN A

FLUSH MOUNTED FLOOR BOX. BOX TO HAVE A LISTED DIVIDER BETWEEN LINE VOLTAGE AND

LOW VOLTAGE CONNECTIONS.

DUPLEX RECEPTACLE - FLUSH MOUNTED IN FLOOR BOX

SPECIAL PURPOSE OUTLET - COORDINATE EXACT NEMA CONFIGURATION

AMPACITY RATING AS INDICATED

"GFI" DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING/WEATHERPROOF COVER -

MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE, COUNTER HEIGHT

DOUBLE DUPLEX RECEPTACLE MOUNTED TOGETHER IN A FLUSH

MOUNTED FLOOR BOX

S

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING - MOUNT AT 18"

AFF, UNLESS OTHERWISE NOTED

"GFI" DOUBLE DUPLEX RECEPTACLE/GROUND FAULT INTERRUPTING, COUNTER HEIGHT

SWITCHES

TS

FS

POWER

EF

FIRE ALARM

WP

F

DUPLEX RECEPTACLE - MOUNT AT 18" AFF, UNLESS OTHERWISE NOTED

(WP) WEATHERPROOF

(H) HORIZONTALLY MOUNTED

(C) CEILING MOUNTED

SINGLE POLE SWITCH - TOGGLE TYPE - MOUNT AT 48" AFF

(3) 3 WAY

(4) 4 WAY

(2) DOUBLE POLE

(D) DIMMER OPERATED

(M) MOTOR RATED SWITCH - 1 POLE OR 2 POLE 30 AMP WITH INTEGRAL THERMAL OVERLOADS

(OS) WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH

WP

ELECTRICAL SERVICE SHUNT TRIP BREAK GLASS STATION SQUARE "D" CLASS#900 1-K15 W/ CLASS

9001-K25 STAINLESS STEEL COVER PLATE. ENGRAVE "SERVICE DISCONNECT" MOUNT 7'-0" AFF. WITHIN

WEATHERPROOF KNOX BOX HOUSING

METER SOCKET

TIME CLOCK

LIGHTING CONTACTOR - * DENOTES CONTACTOR NUMBER

PHOTO CELL

MOTOR

(EF) EXHAUST FAN

(AHU) AIR HANDLING UNIT

CEILING FAN JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)

WALL MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)

SPRINKLER TAMPER SWITCH CONNECTION

SPRINKLER WATERFLOW SWITCH CONNECTION

POST INDICATOR VALVEPIV

J

PC

FIRE/SMOKE OR SMOKE DAMPER FIRE ALARM CONNECTION. PROVIDE FIRE ALARM SYSTEM

ADDRESSABLE SMOKE DETECTOR WITHIN 60" OF DAMPER LOCATION. PROVIDE 120V/20A POWER

CONNECTION TO EACH DAMPER. SMOKE DETECTOR SHALL HAVE ADDRESSABLE RELAY BASE OR

CONTROL MODULE TO ACTIVATE DAMPER SHOWN ON DRAWINGS. REFER TO MECHANICAL DRAWINGS

FOR EXACT DAMPER LOCATIONS.

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, "*" INDICATES

FIXTURES IN SENSOR'S ZONE OF CONTROL.

(DS) DAYLIGHT SENSOR

OS

BRANCH CIRCUIT PANELBOARD, 120/208V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED

FUSED DISCONNECT SWITCH

(3) NUMBER OF POLES

(30) AMPERAGE SIZE

(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.

(NF) NON FUSED

(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS

NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.

COMBINATION STARTER/DISCONNECT SWITCH

(3) NUMBER OF POLES

(30) AMPERAGE SIZE

(*) FUSE ACCORDING TO MANUFACTURERS RECOMMENDATIONS.

(NF) NON FUSED

(WP) OUTDOOR RATED AS SPECIFIED ON DRAWINGS

NEMA 1 RATED INDOORS, NEMA 3R RATED OUTDOORS UNLESS OTHERWISE NOTED.

UTILITY TRANSFORMER

SURGE PROTECTION DEVICE

GROUND BARGB

LC-*

J

TC

(REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT)

BRANCH CIRCUIT PANELBOARD, 277/480V, SURFACE MOUNTED, UNLESS OTHERWISE NOTED

SPD

DRY TYPE TRANSFORMER

H

RTI

"FACP"

DH

FAJB

FAAP

MANUAL PULL STATION - MOUNT AT 48" AFF

COMBINATION AUDIBLE/VISUAL SIGNALING UNIT- SPEAKER/FLASHING "FIRE" LIGHT WALL - MOUNTED

96" AFF UNLESS OTHERWISE NOTED. 75 CANDELA UNLESS NOTED OTHERWISE

(WP) WEATHER PROOF

(A) AUDIBLE ONLY.

COMBINATION AUDIBLE/VISUAL SIGNALING UNIT CEILING MOUNTED- SPEAKER/FLASHING "FIRE" LIGHT

75 CANDELA UNLESS NOTED OTHERWISE

(WP) WEATHER PROOF

(A) AUDIBLE ONLY.

VISUAL SIGNALING UNIT, WALL MOUNTED- FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)

75 CANDELA, UNLESS NOTED OTHERWISE.

VISUAL SIGNALING UNIT, CEILING MOUNTED - FLASHING "FIRE" LIGHT ONLY (NO AUDIO DEVICE)

75 CANDELA, UNLESS NOTED OTHERWISE

PHOTOELECTRIC DUCT SMOKE DETECTOR, R=RETURN / S=SUPPLY

FIRE ALARM SHUTDOWN OR CONTROL RELAY

DUCT DETECTOR REMOTE TROUBLE INDICATOR - MOUNT ADJACENT TO UNIT

FIRE ALARM HEAT DETECTOR. (2) INDICATES TO PROVIDE DUAL CONVERTIBLE CONTACTS

CEILING OR WALL MOUNTED SMOKE DETECTOR. SMOKE DETECTOR SHALL BE TIED TO MAIN FIRE

ALARM SYSTEM.

(2) PROVIDE DUAL CONTACT.

(CO) CARBON MONOXIDE DETECTOR.

(LF) LOW-FREQUENCY SOUNDER BASE WITH INTEGRAL BATTERY BACK UP.

DOOR HOLDER

FIRE ALARM CONTROL PANEL - FLUSH MOUNTED

FIRE ALARM JUNCTION BOX

REMOTE FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

SPRINKLER TAMPER SWITCH CONNECTION

S

R

F

F

F

F

F

C

R

CEILING MOUNTED DAYLIGHT SENSOR, "*" INDICATES FIXTURES IN SENSOR'S ZONE

OF CONTROL. SENSOR TO AUTO-DIM FIXTURES WITHIN BUILDING CODE PRESCRIBED

DAYLIGHT ZONE.

DS

FSD

VARIABLE FREQUENCY DRIVEVFD

FATC FIRE ALARM TERMINAL CABINET, FLUSHED MOUNTED

DDS HEARING IMPAIRED DUAL SMOKE SENSOR AND STROBE

TFR HEARING IMPAIRED LOW VOLTAGE TRANSFORMER FOR DOORBELL SYSTEM

"DO NOT USE" ELEVATOR WARNING LIGHT. BY ELEVATOR CONTRACTORWL

CEILING MOUNTED JUNCTION BOX (SIZE AS REQUIRED PER N.E.C.)J

C

DATA/COMM

DATA/COMM OUTLET WITH FLUSH MOUNTED 4" SQUARE SINGLE GANG JUNCTION BOX. MOUNT AT 18"

AFF, UNLESS OTHERWISE NOTED. PROVIDE BLANK STAINLESS STEEL COVER PLATE. EXTEND 1" CONCEALED CONDUIT TO ABOVE ACCESSIBLE CEILING AND STUB-OUT WITH PLASTIC BUSHING, OR AS

NOTED; INSTALL PULL WIRE.

(WH) WALL MOUNTED

(AC) 6" ABOVE COUNTER BACK SPLASH

(TV) TV - REFER TO ARCHITECTURAL DRAWINGS FOR HEIGHT

DATA/COMM OUTLET FLUSH MOUNTED IN FLOOR

TELEVISION OUTLET - MOUNT 18 " ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED

STRUCTURED MEDIA COMPONENT FLUSH MTD. BOX FOR RESIDENTIAL USE PROVIDED AND INSTALLED

BY CONTRACTOR - MOUNT 48" AFF TO BOARD, UNLESS OTHERWISE NOTED

TELEPHONE TERMINAL BOARD

SMC

TV

C

FIRE ALARM SYSTEM, RESIDENTIAL UNIT MINI-HORN LOW FREQUENCY SOUNDER (520HZ) - MOUNT AT

96" AFF TO TOP OF SOUNDER

S

CARD READER - MOUNT 48" AFF, UNLESS OTHERWISE NOTEDCR

A - AMPERES

A/C - AIR CONDITIONING

AC - ALTERNATING CURRENT

ADA - AMERICANS WITH DISABILITIES ACT

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AHU - AIR HANDLING UNIT

ATS - AUTOMATIC TRANSFER SWITCH

AWG - AMERICAN WIRE GAUGE

BFG - BELOW FINISHED GROUND

C - CONDUIT

COND - CONDUIT

CH - COUNTER HEIGHT

CONC - CONCRETE

CU - COPPER

DISC - DISCONNECT

DBL - DOUBLE

ECB - ENCLOSED CIRCUIT BREAKER

ELEC - ELECTRICAL

EM - EMERGENCY

EF - EXHAUST FAN

EPO - EMERGENCY POWER OFF

EV - ELECTRIC VEHICLE

EWC - ELECTRIC WATER COOLER

EX - EXISTING

EXT - EXTENSION

FA - FIRE ALARM

FACP - FIRE ALARM CONTROL PANEL

FBC - FLORIDA BUILDING CODE

GACP - GENERATOR ANNUNCIATOR CONTROL PANEL

G - GROUND

GND - GROUND

GFI - GROUND FAULT INTERRUPTER

GRC - GALVANIZED RIGID CONDUIT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

IAW - IN ACCORDANCE WITH

IWH - INSTANTANEOUS WATER HEATER

I.G. - ISOLATED GROUND

J - JUNCTION

KAIC - (THOUSAND) AMPERE INTERRUPTING CAPACITY

KCMIL - THOUSAND CIRCULAR MILLS

KVA - KILOVOLT-AMPERES

KW - KILOWATT

LTG - LIGHTING

LTS - LIGHTING

MCB - MAIN CIRCUIT BREAKER

MH - MOUNTING HEIGHT

MLO - MAIN LUG ONLY

N - NEUTRAL

NA - NOT APPLICABLE

NEC - NATIONAL ELECTRICAL CODE

NEMA - NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA - NATIONAL FIRE PROTECTION ASSOCIATION

NF - NON-FUSED

NIC - NOT IN CONTRACT

NL - NIGHT LIGHT

O.C. - ON CENTER

P - POLE

PNL - PANELBOARD

PVC - POLYVINYL CHLORIDE

RGS - RIGID GALVANIZED STEEL

RM - ROOM

SPEC - SPECIFICATION

SPD - SURGE PROTECTION DEVICE

SS - STAINLESS STEEL

SWBD - SWITCHBOARD

TYP - TYPICAL

UON - UNLESS OTHERWISE NOTED

UNV - UNIVERSAL

V - VOLTS

W - WIRE

WP - WEATHERPROOF

T

TS

GACP

GENERATOR ANNUNCIATOR CONTROL PANEL - FLUSH MOUNTED

GENERAL NOTE

1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY

CONSERVATION C405.6.3 AND 2020 NEC 210.19 WITH

REGARDS TO VOLTAGE DROP (5%).

2. THE ELECTRICAL DESIGN HAS BEEN DESIGNED IN

ACCORDANCE WITH THE 2020 NATIONAL ELECTRICAL CODE,

2023 FLORIDA BUILDING CODE.

FLORIDA ADMINISTRATIVE CODE

ARTICLE 61G15.32.008(4)a-o

61G15-32.008(4) - TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND DETECTION SYSTEMS

ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL INCLUDE AS A MINIMUM THE FOLLOWING

INFORMATION WHEN APPLICABLE:

(a) SYMBOL LEGEND IS FOUND ON SHEET E0.001 AND SYSTEM RISER IS FOUND ON SHEET

E6.000

(b) LOCATIONS FOR INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS ARE

FOUND ON FLOOR PLAN SHEETS E1.101

(c) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS ARE FOUND IN THE SYMBOL

LEGEND ON SHEET E0.001

(d) CIRCUITS SHALL BE CLASS B TYPE, AS PER SPECIFICATION SECTION 283000

(e) IDENTIFICATION OF FUNCTIONS REQUIRED BY THE ALARM AND CONTROL SYSTEMS IS

FOUND ON SHEET E6.000

(f) FIRE ALARM SHALL BE ADDRESSABLE AND ZONING IS INDICATED IN SPECIFICATION

SECTION 283000

(g) SURGE PROTECTION DEVICES ARE FOUND ON ELECTRICAL RISER ON SHEET E6.000

(h) DEVICES THAT ARE SUBJECT TO ENVIRONMENTAL FACTORS AND REQUIREMENTS FOR

PROTECTION ARE FOUND ON FLOOR PLAN SHEETS E1.101

(i) SITE PLAN AND ANY FIRE ALARM DEVICES REQUIRED OUTSIDE ARE NOT APPLICABLE

(j) SMOKE DETECTION DEVICES TO MITIGATE OBSTRUCTIONS ARE NOT APPLICABLE

(k) SMOKE DETECTION DEVICES TO MITIGATE DETECTION PROBLEMS WHERE SMOKE

STRATIFICATION IS ANTICIPATED ARE NOT APPLICABLE.

(l) DESIGN GUIDES AND STANDARDS USED FOR PERFORMANCE BASED FIRE ALARM

SYSTEM ARE FOUND ON SHEET E6.000

(m) INDICATION OF GENERAL EVACUATION SIGNAL OR A ZONED EVACUATION FOR ALL

HIGH-RISE BUILDINGS OR MULTI-TENANTED PROPERTIES IS NOT APPLICABLE

(n) WIRING REQUIREMENTS AND BURIAL DEPTH FOR UNDERGROUND, WET LOCATIONS

AND CAMPUS STYLE WIRING ARE NOT APPLICABLE

(o) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND OWNER INSTRUCTIONS ARE INDICATED IN SPECIFICATION

SECTION 283000

LIGHTING (SEE LIGHTING FIXTURE SCHEDULE)

2'X 2' LIGHT FIXTURE

EMERGENCY 2' x 2' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

2'X 4' LIGHT FIXTURE

EMERGENCY 2' x 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

1'X 4' LIGHT FIXTURE

EMERGENCY 1'X 4' LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

LIGHT FIXTURE - WALL MOUNTED

EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR

STRIP LIGHT

EMERGENCY STRIP LIGHT CONNECTED TO EMERGENCY GENERATOR

DOWNLIGHT LIGHT FIXTURE

LIGHT FIXTURE - WALL MOUNTED

WALL WASH / ACCENT FIXTURE - CEILING MOUNTED

EMERGENCY DOWNLIGHT LIGHT FIXTURE CONNECTED TO EMERGENCY GENERATOR

EMERGENCY LIGHT FIXTURE - WALL MOUNTED CONNECTED TO EMERGENCY GENERATOR

EXIT SIGN - SINGLE FACE ARROW INDICATES DIRECTION - CEILING MOUNTED-WITH INTEGRAL

EMERGENCY BACKUP

EXIT SIGN - SINGLE FACE - ARROW INDICATES DIRECTION - WALL MOUNTED - WITH INTEGRAL

EMERGENCY BACKUP

EXIT SIGN - DOUBLE FACE - ARROW INDICATES DIRECTION - CEILING MOUNTED - WITH INTEGRAL

EMERGENCY BACKUP

EMERGENCY LIGHT WITH INTEGRAL EMERGENCY BACKUP - DUAL HEAD

DECORATIVE PENDANT

LIGHT TRACK - CEILING MOUNTED

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:14 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

ELECTRICAL LEGEND,

NOTES &

ABBREVIATIONS

E0.001

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

IE - ELECTRICAL SHEET LIST

Sheet Number Sheet Name Project Issue Date Project Status Current Revision Current Revision Date Current Revision Description Sheet Discipline

E0.001 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E1.100 FIRST LEVEL DEMOLITION PLAN ELECTRICAL 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E1.101 FIRST LEVEL PLAN POWER 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E1.102 FIRST LEVEL PLAN LIGHTING 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E6.000 ELECTRICAL RISERS AND PANEL SCHEDULES 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

E8.000 ELECTRICAL DETAILS 05.15.2025 ISSUE FOR PERMIT ELECTRICAL

Grand total: 6

6. ALL SITE, POOL DECK, AND PARKING GARAGE ALTERNATE FIXTURES SHALL BE SUBMITTED WITH PHOTOMETRIC STUDY TO BE REVIEWED AS PART OF THE SUBMITTAL

PROCESS.

5. COORDINATE THE ACTUAL TYPE OF CEILING FOR EACH FIXTURE WITH ARCHITECTURAL AND INTERIOR DRAWING'S REFLECTED CEILING PLANS AND PROVIDE FIXTURE

TRIM AS REQUIRED.

4. REFER TO ARCHITECTURAL REFLECTED CEILING LIGHTING PLAN FOR EXACT FINAL LOCATION OF LIGHTING FIXTURES.

3. COORDINATE THE ACTUAL TYPE OF LIGHTING FIXTURES WITH ARCHITECTURAL LIGHTING SCHEDULES, INTERIOR DESIGN LIGHTING SCHEDULE/DRAWINGS AND OWNER

LIGHTING FIXTURE STANDARD CRITERIA AS REQUIRED.

2. PROVIDE ALL DEVICES, DRYWALL FLANGES, MOUNTING EQUIPMENT, CHAIN, STRAIN REFLIEFS, CLIPS, ESCUTCHEONS, PLATES AND STRUCTURAL SUPPORTS FOR THE

INSTALLATION AND CONNECTION OF ALL LIGHTING FIXTURES.

1. PROVIDE ALL REQUIRED MOUNTING HARDWARE AND WIRING TO CONNECT LIGHTING FIXTURES AT HOLLOW CORE, POST TENSION SLAB, AND STRUCTURAL STEEL

LOCATIONS INCLUDING BOXES, HANGER BARS, STRUCTURAL APPROVED FASTENERS AND UL APPROVED CONNECTORS.

LIGHTING FIXTURE SCHEDULE NOTES

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER & CATALOG NO. DESCRIPTION LAMPS LOAD VOLTS REMARKS

A

LITHONIA LTG:

CPX-2X4-AL08-80CRI-SWW7-SWL-MVOLT

2'x4' FLAT PANEL LED 47.9 VA 277 AS APPROVED BY OWNER

B

GOTHAM LTG:

IVO4SQS-D-07LM-35K-80CRI-MWD-MIN10-MVOL

T-EZT-NCH-P-AR-LSS-F

4" SQUARE DOWNLIGHT LED 7.8 VA 277 AS APPROVED BY OWNER

C2 SAME AS TYPE 'C4' EXCEPT 2' IN LENGTH 2' RECESSED LINEAR LED 13.2 VA 277 AS APPROVED BY OWNER

C4

NEXA LTG:

807-NX3-RS-4-48-RECESSED-0-IP-AE-2-Z-SO-C3

4' RECESSED LINEAR LED 26.4 VA 277 AS APPROVED BY OWNER

C6 SAME AS TYPE 'C4' EXCEPT 6' IN LENGTH 6' RECESSED LINEAR LED 39.6 VA 277 AS APPROVED BY OWNER

C8 SAME AS TYPE 'C4' EXCEPT 8' IN LENGTH 8' RECESSED LINEAR LED 52.8 VA 277 AS APPROVED BY OWNER

C10 SAME AS TYPE 'C4' EXCEPT 10' IN LENGTH 10' RECESSED LINEAR LED 66.0 VA 277 AS APPROVED BY OWNER

EX LITHONIA LTG: EDG-1/2-R EDGE LITE EXIT SIGN LED 2.8 VA 277 AS APPROVED BY OWNER

REVISIONS

J

J J

JJJ

A A

B B

G G

H H

J J

C C

D D

E E

F F

1 1

VAV

2-12

VAV

2-11

VAV

2-10

VAV

2-09

VAV

2-07

VAV

2-08

VAV

2-05

VAV

2-06

VAV

2-02

VAV

2-04

VAV

2-01

VAV

2-03

VAV

2-13

NIC

GENERAL

DEMOLITION NOTE

1. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE

THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY

THIS WORK BEFORE SUBMITTING PROPOSAL SO AS TO

BECOME FAMILIAR WITH EXISTING WORK. SUBMISSION OF A

PROPOSAL WILL BE CONSTRUED AS EVIDENCE. THAT SUCH

EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR

LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE BY

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED. IT

IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS

PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD

LOCATED EXACTLY AS SHOWN ON THE DRAWINGS.

COOPERATION WITH OTHER TRADES IN EQUIPMENT

ROUTING AS DETERMINED DURING CONSTRUCTION AND AS

DIRECTED BY THE ARCHITECT/ENGINEER MAY BE

NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS

SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT IS

ALSO UNDERSTOOD THAT THE PLANS ARE NOT

COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD

VERIFY DIMENSIONS OF ALL EXISTING CONDITIONS, PRIOR

TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.

2. ALL DEVICES AND EQUIPMENT NOT SHOWN AND IN AREAS

OUTSIDE OF CONSTRUCTION AREA SHALL REMAIN ACTIVE

UNLESS OTHERWISE NOTED. INSTALL AS REQUIRED TO

MAINTAIN CONTINUITY TO EXISTING DEVICES AND

EQUIPMENT THAT REMAIN.

3. ALL BRANCH CIRCUIT WIRING SHALL BE CONCEALED

UNLESS OTHERWISE NOTED.

4. ALL EQUIPMENT AND MATERIAL REMOVED AND NOT

REUSED SHALL BE TURNED OVER TO THE OWNER OR AT

THE OWNERS REQUEST DISPOSED OF BY THE

CONTRACTOR.

5. ALL ELECTRICAL DEVICES THAT ARE REMOVED SHALL BE

REMOVED AS DIRECTED BY THE OWNER, AND CEILING OR

WALL SHALL BE PATCHED TO MATCH EXISTING OR NEW

FINISH. ALL PATCHES OR CEILING PLATES SHALL BE

PATCHED OR PAINTED AS DIRECTED BY ARCHITECT.

6. ALL EXISTING ELECTRICAL EQUIPMENT IS NOT SHOWN. IT IS

THE CONTRACTORS RESPONSIBILITY TO BECOME FAMILIAR

WITH ALL EXISTING CONDITIONS PRIOR TO BID, AND

INCLUDE IN HIS BID THE REMOVAL OF ALL EQUIPMENT,

CONDUIT, WIRE, ETC. THAT IS NOT BEING REUSED BACK TO

ITS SOURCE.

7. ALL CONCRETE, WALL PATCHING, CEILING REPAIR, AND

OTHER GENERAL WORK REQUIRED FOR INSTALLING THE

ELECTRICAL SYSTEMS AND TO REPAIR TO "LIKE NEW

CONDITION" TO BE PROVIDED AND INSTALLED BY

CONTRACTOR. COORDINATE WITH GENERAL

CONTRACTOR.

8. PROVIDE AND INSTALL ANY ADDITIONAL

HANGERS/SUPPORTS REQUIRED TO ACCOMMODATE ANY

EQUIPMENT RELOCATION.

9. COORDINATE ALL CEILING MOUNTED DEVICES WITH

ARCHITECTURAL REFLECTED CEILING AND WORK OF ALL

OTHER TRADES.

10. ITEMS NOTED AS EXISTING TO BE REMOVED "DEMO" SHALL

BE REMOVED COMPLETELY. REMOVAL SHALL INCLUDE

CONDUIT BOXES, HANGERS AND CONDUCTORS BACK TO

BRANCH PANELBOARD. ALL LIGHTING EQUIPMENT TO BE

"DEMO" SHALL INCLUDE REMOVAL OF LIGHTING CONTROL

CIRCUIT WITH ALL ASSOCIATED WIRING, BOXES, SUPPORTS

AND CONDUIT BACK TO POINT OF BRANCH CIRCUIT ORIGIN

WITHIN PANELBOARD AND RE FEED ALL DOWN STREAM

DEVICES TO REMAIN. PATCH DISTURBED AREA. UPDATE

SCHEDULE AS REQUIRED.

FLOOR

PLAN

NORTH

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:23 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

FIRST LEVEL

DEMOLITION PLAN

ELECTRICAL

E1.100

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

1/8" = 1'-0"E1.100

1 1ST LEVEL - Demo Work Electrical

REFERENCE NOTE

1 REMOVE RECEPTACLES, LIGHT FIXTURES, SWITCHES, FIRE

ALARM DEVICES, WIRE, AND CONDUIT IN WALLS THAT ARE

TO BE REMOVED BACK TO POINT OF CIRCUIT ORIGIN.

MAINTAIN CIRCUIT CONTINUITY TO DEVICES LOCATED

OUTSIDE OF SCOPE OF WORK.

2 EXISTING DISCONNECT FOR PARALLEL FAN-POWERED BOX

TO BE REMOVED. REMOVE EXISTING WIRING, BOXES,

SUPPORTS, AND CONDUIT IN WALLS. BRANCH CIRCUIT

TO REMOVED BACK TO PANEL OF ORIGIN.

EXISTING CONNECTION FOR UNDERFLOOR ELECTRICAL

SYSTEM. REMOVE EXISTING WIRING, BOXES AND CONDUITS

IN FLOORS. BRANCH CIRCUIT TO BE REMOVED BACK TO

PANEL OF ORIGIN. VERIFY IN FIELD EXACT LOCATIONS OF

CONNECTIONS.

F F

F F

F

F

F

F F

F

FFF

F

F

F

S M

S M

S M

F

F

F

F

J J

J

A A

B B

G G

H H

J J

D D

E E

F F

BREAK

ROOM

OFFICE

CASH

IT

HALL

STORAGE

HALL

CHECK-IN

STAFF

CHECK-IN

ENTRY

WAITING A

WAITING B

SERVICE

TESTING

CUSTOMER

SERVICE

HALL

HALL

HALL

NIC

1 1 1

1 1

D/W

ELEC

TV TV

MICRO.

MICRO.

TV TV

REFRIG.

COFFEE

H1B

BUS

DUCT B

DISC. T-1

DISC. H1B

L1B

EL1

L1B- 35

L1B- 35

L1B- 35

L1B- 35

L1B- 10

L1B- 50L1B- 52

L1B- 8

L1B- 12

L1B- 35L1B- 35

L1B- 22

L1B- 26

L1B- 28 L1B- 28

L1B- 28

L1B- 28

L1B- 30

L1B- 32

L1B- 32

L1B- 34

L1B- 34

L1B- 34

L1B- 34

L1B- 34L1B- 34

L1B- 36 L1B- 36

L1B- 44 L1B- 44

L1B- 44

L1B- 46

L1B- 46

L1B- 46

L1B- 46

L1B- 27

L1B- 27 L1B- 27 L1B- 27

L1B- 27 L1B- 27 L1B- 27 L1B- 27

L1B- 33L1B- 33

PTU

1.4

PTU

1.3

PTU

1.1

VAV

1.1

PTU

1.5

PTU

1.2

VAV

1.3

VAV

1.2

L1B- 29

L1B- 29

L1B- 29

T-1

L1B- 54

3 4

L1B-

56,58,60

L1B- 62

3 4

L1B-

64,66,68

3 4

L1B- 70 L1B-

72,74,76

NIC

GENERAL NOTE

1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY

CONSERVATION C405.5.3 AND 2020 NEC 210.19 WITH

REGARDS TO VOLTAGE DROP (5%).

2. FIRE ALARM DEVICES WHERE REQUIRED SHALL BE

INSTALLED IN COMPLIANCE WITH NFPA AND FLORIDA FIRE

PREVENTION CODE.

3. REFER TO ARCHITECTURAL AND INTERIOR DESIGNER

DRAWINGS FOR ALL ELECTRICAL DEVICE MOUNTING

HEIGHTS, QUANTITIES AND LOCATIONS.

4. COORDINATE WITH OWNER FOR EXACT DATA/COMM

REQUIREMENTS.

5. SEAL ALL FIRE WALLS, ROOF, AND FLOOR PENETRATIONS

WITH UL LISTED FIRE SEALANT.

FLOOR

PLAN

NORTH

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:34 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

FIRST LEVEL PLAN

POWER

E1.101

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

1/8" = 1'-0"E1.101

1 1ST LEVEL - New Work Electrical Power

REFERENCE NOTE

1 NEW FIRE ALARM DEVICE. DEVICE SHALL BE COMPATIBLE

WITH EXITING FIRE ALARM SYSTEM. CONNECT TO EXISTING

NOTIFICATION CIRCUIT. VERIFY CIRCUIT AND BATTERY

CAPACITY.

2 SEE MECHANICAL EQUIPMENT CONNECTION SCHEDULE ON

THIS SHEET FOR ELECTRICAL REQUIREMENTS FOR

MECHANICAL EQUIPMENT.

3 PROVIDE 3-POLE BREAKERS SERVING THE SAME

PIECE OF MODULAR FURNITURE.

4 PROVIDE CONNECTION FOR MODULAR OFFICE FURNITURE.

PROVIDE FLEXIBLE CONDUIT CONNECTION FROM WALL

J-BOX TO POWER FURNITURE JUNCTION BOX FOR POWER

AND SEPARATE CONDUIT CONNECTION FOR

COMMUNICATIONS SERVICE, COORDINATE WITH ID.

6. VARIABLE FREQUENCY DRIVE (VFD) IS FURNISHED BY DIVISION 23, INSTALLED ANY CONNECTED BY DIVISION 26. DISCONNECTING MEANS IS INTEGRAL TO VFD.

5. INTERIOR FAN COIL UNIT IS POWERED BY OUTDOOR CONDENSING UNIT WITH 3#10 AWG IN 3/4"C.

4. ALL EQUIPMENT RECEIVING CONTROL POWER ONLY ARE NOT SHOWN ON THIS SCHEDULE. REFER TO DIVISION 23 MECHANICAL SCHEDULES AND POWER PLANS FOR CIRCUITING REQUIREMENTS.

3. ELEVATOR SIZE IS ESTIMATED AS SHOP DRAWINGS HAVE NOT BEEN CREATED. VERIFY OVER CURRENT PROTECTING SIZE REQUIRED ON ELEVATOR SHOP DRAWINGS PRIOR TO ORDERING EQUIPMENT.

2. DISCONNECT IS INTEGRAL TO FAN COIL UNIT.

1. VERIFY DISCONNECT CIRCUIT BREAKER SIZE, FRAME SIZE, AND FUSE RATING/TYPE BASED ON DIVISION 22/23 SHOP DRAWINGS PRIOR TO BIDDING. ADJUST AS NECESSARY.

MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES

MECHANICAL EQUIPMENT CONNECTION SCHEDULE

EQUIPMENT AMPS LOAD VOLTAGE

NO. OF

POLES PANEL

CIRCUIT

NUMBER

COMBINATION STARTER/DISCONNECT

FEEDER CB RATING NOTESFRAME RATING FUSE RATING NEMA RATING

PTU-1.1 12 A 3.4 kVA 277 V 1 H1B 7 30 * 1 2#12, 1#12G, 1/2"C 20 A 1

PTU-1.2 9 A 2.4 kVA 277 V 1 H1B 9 30 * 1 2#12, 1#12G, 1/2"C 20 A 1

PTU-1.3 9 A 2.6 kVA 277 V 1 H1B 11 30 * 1 2#12, 1#12G, 1/2"C 20 A 1

PTU-1.4 8 A 2.2 kVA 277 V 1 H1B 13 30 * 1 2#12, 1#12G, 1/2"C 20 A 1

PTU-1.5 8 A 2.2 kVA 277 V 1 H1B 15 30 * 1 2#12, 1#12G, 1/2"C 20 A 1

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OSOSOS

OS

S

S

SOS

S

S

S c

OS

OS

OS

SOS

S

S3

OS

Sa

Se

S c

S

S 4c

S3

R

R

R

R

R

R

R

R

R

R

S3 S

S

S3 S

S d

Sf

S 3d

Sb

S d

DS

DS

DS

A A

B B

G G

H H

J J

C C

D D

E E

F F

C10 B

B

B

B

B

B

B

B

B B B B B B B

B

BB

C10

C10

C10

C10

C10

C10

B

A A

C10C10C10C10C10

C6C6 C6

C10

C10

C10C10C10

C4C4C4C4C4C4C4C4C4C4C4C4

B

B

B

B

B

B B

A

A

A A A

A A A

A A A

AA

A

A

BREAK

ROOM

OFFICE

CASH

IT

HALL

CHECK-IN

STAFF

CHECK-IN

ENTRY

WAITING A

WAITING B

SERVICE

TESTING

CUSTOMER

SERVICE

HALL

HALL

HALL

EX

EX

EX

EX

EX

EX

EX

EXEX

NIC

C8 C8 C8 C8

B C10

C2 C2 C2 C2

EX

H1B- 2 H1B- 2

H1B- 2 H1B- 2

H1B- 2

H1B- 2

PERMITTING

EX

H1B- 2

H1B- 2

H1B- 2

H1B- 2

H1B- 2 H1B- 2

A

H1B- 2

H1B- 2

H1B- 2

H1B- 2

H1B- 2

H1B- 2

H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4

H1B- 2

H1B- 2

H1B- 2

H1B- 2

H1B- 4

H1B- 4

H1B- 4H1B- 4H1B- 4H1B- 4H1B- 4

H1B- 4

H1B- 4H1B- 4

H1B- 4H1B- 4H1B- 4

H1B- 4

H1B- 4 H1B- 4

H1B- 4

H1B- 4

H1B- 4 H1B- 4

H1B- 4 H1B- 4

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2

EL2B-2EL2B-2

EL2B-4

EL2B-4 EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4 EL2B-4

EL2B-4

EL2B-4

EL2B-4 EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4

EL2B-4EL2B-4

EL2B-4

EL2B-2

EL2B-2

EL2B-4

1 1

NIC

DS

STORAGE

d d d d d d d c c c c c c a a aa a a a a a a a a a a a a a b b a ab b b b bb b e e e e e e e e e e e f f f f f f f f e,f e,f e,f e,f e,f a,b a,b a,b a,b

GENERAL NOTE

1. THIS PROJECT IS IN COMPLIANCE WITH 2023 FBC-ENERGY

CONSERVATION C405.5.3 AND 2020 NEC 210.19 WITH

REGARDS TO VOLTAGE DROP (5%).

2. ALL EMERGENCY AND EXIT LIGHTING SHALL BE

CONNECTED AHEAD OF ANY SWITCHING ARRANGEMENTS

OR CONTROLLED BY A LISTED UL924 CONTROLLER PER

N.E.C.

3. REFER TO ARCHITECTURAL AND LIGHTING DESIGNER

LIGHTING PLANS FOR ANY AND ALL LIGHTING FIXTURE

MOUNTING DIMENSIONS AND LOCATIONS.

4. SEAL ALL FIRE WALLS, ROOF, AND FLOOR PENETRATIONS

WITH UL LISTED FIRE SEALANT.

5. NEW EMERGENCY LIGHTING TO BE POWERED FROM

EXISTING CIRCUITS INDICATED. EXTEND WIRE AND

CONDUIT TO NEW EMERGENCY FIXTURES AS SHOWN.

FLOOR

PLAN

NORTH

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:45 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

FIRST LEVEL PLAN

LIGHTING

E1.102

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

1/8" = 1'-0"E1.102

1 1ST LEVEL - New Work Electrical Lighting

REFERENCE NOTE

1 EVERYTHING IN THIS SPACE IS EXISTING TO REMAIN

UNLESS OTHERWISE NOTED.

2 PROVIDE UL 924 RELAY TO TURN EMERGENCY LIGHTS IN

THE AREA TO FULL BRIGHTNESS UPON LOSS OF POWER.

3 LIGHTING IN INDICATED DAYLIGHT ZONE SHALL BE

CONTROLLED THE DAYLIGHT SENSOR IN SPACE. DAYLIGHT

CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH

2023 FBC ENERGY CONSERVATION SECTION C405.2.3.

GROUND LEVEL

SWBD-MDP

HOUSE

DISTRIBUTION

4000 AMPS

277/480V

3ø, 4W

BOND

N G

N.T.S.

PARTIAL EXISTING ELECTRICAL RISER DIAGRAM

ALL PANELS EXISTING TO REMAIN. RISER SHOWN FOR REFERENCE ONLY

PB

SECOND LEVEL

T1

75 KVA

M.C.B.

120/208V

225 AMP

3ø, 4W

L1B

PANEL

M.L.O.

120/208V

225 AMP

3ø, 4W

L1B

PANEL

M.L.O.

120/208V

225 AMP

3ø, 4W

L1B

PANELPANEL

M.L.O.

480/277V

250 AMP

3ø, 4W

H1B

ELEC B-110 MAIN ELECTRICAL ROOM

ETR BUSWAY

N.T.S.

FIRE ALARM RISER DIAGRAM

J J JJ J J JJJJ

FAAP

SEE POWER PLAN FOR EXACT QUANTITIES

PROVIDE NEW POWER

SUPPLY AS REQUIRED

FOR THE TOTAL BUILD

OUT OF THE NEW AREA

EXTEND NEW FIRE ALARM

CONDUCTORS TO NEW FIRE

ALARM SYSTEM DEVICES.

120V SURGE

SUPPRESSOR

FINISHED FLOOR FINISHED FLOOR

TYP. CLG

MOUNTED

S.D.

TYP. HVAC

EQUIPMENT

FIRE ALARM SYSTEM NOTE:

FIRE ALARM SYSTEM RISER DIAGRAM IS DIAGRAMMATICAL AND IN

ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE ARTICLE 61G15

DESIGN OF ALARM SYSTEMS. SEE POWER PLAN FOR EXACT

QUANTITIES OF DEVICES. WIRING SHALL BE AS RECOMMENDED BY

SYSTEMS MANUFACTURER AND PER NFPA 72. THE FIRE ALARM

CONTRACTOR IS REQUIRED TO PROVIDE ENGINEERED FIRE ALARM

DOCUMENTS PER THE FLORIDA ADMINISTRATIVE CODE 61G15.

A. FIRE ALARM SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES:

1. MANUAL STATIONS.

2. HEAT DETECTORS.

3. SMOKE DETECTORS.

4. VERIFIED AUTOMATIC ALARM OPERATION OF SMOKE DETECTORS.

5. AUTOMATIC SPRINKLER SYSTEM WATER FLOW.

B. FIRE ALARM SIGNAL SHALL INITIATE THE FOLLOWING ACTIONS:

1. ALARM NOTIFICATION APPLIANCES SHALL OPERATE CONTINUOUSLY

2. IDENTIFY ALARM AT THE FACP AND REMOTE ANNUNCIATORS.

3. TRANSMIT AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION.

4. SWITCH HEATING, VENTILATING, AND AIR-CONDITIONING EQUIPMENT CONTROLS TO

FIRE ALARM MODE.

5. RECORD EVENTS IN THE SYSTEM MEMORY.

C. SUPERVISORY SIGNAL INITIATION SHALL BE BY OPERATION OF A FIRE-PROTECTION

SYSTEM VALVE TAMPER.

D. SYSTEM TROUBLE SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING

DEVICES OR ACTIONS:

1. OPEN CIRCUITS, SHORTS AND GROUNDS OF WIRING FOR INITIATING DEVICE,

SIGNALING LINE, AND NOTIFICATION-APPLIANCE CIRCUITS.

2. OPENING, TAMPERING, OR REMOVAL OF ALARM-INITIATING AND SUPERVISORY

SIGNAL-INITIATING DEVICES.

3. LOSS OF PRIMARY POWER AT THE FACP.

4. GROUND OR A SINGLE BREAK IN FACP INTERNAL CIRCUITS.

5. ABNORMAL AC VOLTAGE AT THE FACP.

6. A BREAK IN STANDBY BATTERY CIRCUITRY.

7. FAILURE OF BATTERY CHARGING.

8. ABNORMAL POSITION OF ANY SWITCH AT THE FACP OR ANNUNCIATOR.

E. SYSTEM TROUBLE AND SUPERVISORY SIGNAL ACTIONS: RING TROUBLE BELL AND

ANNUNCIATE AT THE FACP AND REMOTE ANNUNCIATORS. RECORD THE EVENT.

FIRE ALARM SYSTEM SEQUENCE OF OPERATIONS (REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS)

F FF FF FFF

EXIST. FIRE

ALARM

CONTROL

PANEL

F. ACTUATION OF ALARM NOTIFICATION APPLIANCES, ANNUNCIATION, ELEVATOR RECALL, AND

ACTUATION OF SUPPRESSION SYSTEMS SHALL OCCUR WITHIN 10 SECONDS AFTER THE

ACTIVATION OF AN INITIATING DEVICE.

G. SMOKE-ALARM VERIFICATION:

1. INITIATE AUDIBLE AND VISIBLE INDICATION OF AN "ALARM VERIFICATION" SIGNAL AT

THE FACP.

2. ACTIVATE A LISTED AND APPROVED "ALARM VERIFICATION" SEQUENCE AT THE

FACP AND THE DETECTOR.

3. RECORD EVENTS.

4. SOUND GENERAL ALARM IF THE ALARM IS VERIFIED.

5. CANCEL FACP INDICATION AND SYSTEM RESET IF THE ALARM IS NOT VERIFIED.

H. POWER SUPPLY FOR SUPERVISION EQUIPMENT: SUPPLY FOR AUDIBLE AND VISUAL

EQUIPMENT FOR SUPERVISION OF THE AC POWER SHALL BE FROM A DEDICATED DC POWER

SUPPLY, AND POWER FOR THE DC COMPONENT SHALL BE FROM THE AC SUPPLY.

I. ALARM SILENCING, TROUBLE, AND SUPERVISORY ALARM RESET: MANUAL RESET AT THE

FACP AND REMOTE ANNUNCIATORS, AFTER INITIATING DEVICES ARE RESTORED TO

NORMAL.

1. SILENCING-SWITCH OPERATION HALTS ALARM OPERATION OF NOTIFICATION

APPLIANCES AND ACTIVATES AN "ALARM SILENCE" LIGHT. DISPLAY OF IDENTITY OF

THE ALARM ZONE OR DEVICE IS RETAINED.

2. SUBSEQUENT ALARM SIGNALS FROM OTHER DEVICES OR ZONES REACTIVATE

NOTIFICATION APPLIANCES UNTIL SILENCING SWITCH IS OPERATED AGAIN.

3. WHEN ALARM-INITIATING DEVICES RETURN TO NORMAL AND SYSTEM RESET SWITCH

IS OPERATED, NOTIFICATION APPLIANCES OPERATE AGAIN UNTIL ALARM SILENCE

SWITCH IS RESET.

J. DUCT SMOKE DETECTORS SHALL BE PROGRAMMED AS A SUPERVISORY SIGNAL/FUNCTION

IN ACCORDANCE WITH 9.6.3.2.2, NFPA 101, 2012 ED. AS ADOPTED IN THE FFPC, 5TH ED.

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:53 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

ELECTRICAL RISERS AND

PANEL SCHEDULES

E6.000

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

ELECTRICAL RISER NOTE

1. ALL ELECTRICAL EQUIPMENT ARE EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

SHOWN FOR REFERENCE ONLY.

Notes:

Receptacle 7.76 kVA 100.00% 7.76 kVA Demand Amps: 70 A

Other 0.00 kVA 0.00% 0.00 kVA Total Demand Load: 58.6 kVA

Lighting 20.52 kVA 100.00% 20.52 kVA Total Connected Load: 58.6 kVA

HVAC 30.28 kVA 100.00% 30.28 kVA

CONN.

LOAD...

DEMAND

FACTOR

DEMAND

LOAD...

Phase Connected Load: 23.6 18.9 16.1

41 SPACE -- 1 -- -- -- -- 1 -- SPACE 42

39 SPACE -- 1 -- -- -- -- 1 -- SPACE 40

37 SPACE -- 1 -- -- -- -- 1 -- SPACE 38

35 SPACE -- 1 -- -- -- -- 1 -- SPACE 36

33 SPACE -- 1 -- -- -- -- 1 -- SPACE 34

31 SPACE -- 1 -- -- -- -- 1 -- SPACE 32

29 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 30

27 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 28

25 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 26

23 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 24

21 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 3.88 3.88 EXISTING TO REMAIN 1 20 A EX-UV LIGHTS 22

19 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 3.88 3.88 EXISTING TO REMAIN 1 20 A EXISTING LOAD 20

17 SPARE 30 A 1 -- 0.00 3.88 EXISTING TO REMAIN 1 20 A EXISTING LOAD 18

15 PTU-1.5 20 A 1 2#12, 1#12G, 1/2"C 2.19 0.00 -- 1 20 A SPARE 16

13 PTU-1.4 20 A 1 2#12, 1#12G, 1/2"C 2.19 0.00 -- 1 20 A SPARE 14

11 PTU-1.3 20 A 1 2#12, 1#12G, 1/2"C 2.56 0.00 -- 1 20 A SPARE 12

9 PTU-1.2 20 A 1 2#12, 1#12G, 1/2"C 2.44 0.00 -- 1 20 A SPARE 10

7 PTU-1.1 20 A 1 2#12, 1#12G, 1/2"C 3.44 3.88 EXISTING TO REMAIN 1 20 A EX-LTG 51 8

5 EX-VAV 2-01, 2-04 30 A 1 EXISTING TO REMAIN 5.82 3.88 EXISTING TO REMAIN 1 20 A EX-LTG 59, 60, 61, 62,... 6

3 EX-VAV 2-17 30 A 1 EXISTING TO REMAIN 5.82 0.66 2#12, 1#12G, 1/2"C 1 20 A CUSTOMER SERVICE... 4

1 EX-VAV 2-15 30 A 1 EXISTING TO REMAIN 5.82 0.63 2#12, 1#12G, 1/2"C 1 20 A CHECK-IN LIGHTS 2

C K T

LOAD NAME TRIP

P O L E S

WIRE SIZE A B C WIRE SIZE

P O L

E...

TRIP LOAD NAME

C K T

FLUSH MTD: 240/120V

SURFACE MTD: X X 480Y/277V

K.A.I.C. : EX. AMPS 208Y/120V Fed From: SWBD-MDP

MAIN LUGS: 250 AMPS 4 WIRE Project Number: I24027

MAIN BREAKER: AMPS 3 PHASE Project Name: VOLUSIA COUNTY TAX COLLECTOR

Name: H1B

* REUSE EXISTING BREAKERS FOR NEW EQUIPMENT.

Notes:

Continuous 21.85 kVA 125.00% 27.31 kVA

Receptacle 65.11 kVA 57.68% 37.56 kVA Demand Amps: 219 A

Motor 0.15 kVA 108.33% 0.16 kVA Total Demand Load: 78.7 kVA

Lighting 10.08 kVA 100.00% 10.08 kVA Total Connected Load: 100.8 kVA

Equipment 3.62 kVA 100.00% 3.62 kVA

CONN.

LOAD...

DEMAND

FACTOR

DEMAND

LOAD...

Phase Connected Load: 34.4 36.4 30.0

125 SPACE -- 1 -- -- -- -- 1 -- SPACE 126

123 SPACE -- 1 -- -- -- -- 1 -- SPACE 124

121 SPACE -- 1 -- -- -- -- 1 -- SPACE 122

119 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 120

117 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 118

115 SPARE 20 A 1 -- 0.00 -- -- 1 -- SPACE 116

113 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 114

111 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 112

109 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 110

107 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 108

105 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 106

103 EX-TAG OFFICE 20 A 1 EXISTING TO REMAIN 0.90 0.90 EXISTING TO REMAIN 1 20 A EX-TAG OFFICE 104

101 FIRE ALARM PANEL 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 102

99 SPARE 20 A 1 -- 0.00 0.90 EXISTING TO REMAIN 1 20 A EX-FLR. BOX RECP RM

97 EX-LTG. RMS. 30, 34 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 98

95 EX-LTG. RMS.30, 34 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 96

93 EX-LTG. RMS. 84, 81, 2, 29 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 94

91 EX-LTG .RM. 29 20 A 1 EXISTING TO REMAIN 1.00 0.00 -- 1 20 A SPARE 92

89 EX-LTG. RMS. 118, 1 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-NEW MONITOR 90

87 EX-LTG. RMS. 118, 85 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-LTG 88

85 EX-LTG EXT. 20 A 1 EXISTING TO REMAIN 1.00 1.00 EXISTING TO REMAIN 1 20 A EX-LTG EXT. 86

83 SPARE 20 A 1 -- 0.00 0.00 -- 1 20 A SPARE 84

81 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 82

79 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 80

77 EX-POWER OUTLET 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 78

75 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 -- -- -- -- 76

73 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 -- -- -- -- 74

71 EX-COLUMN FURNITURE... 20 A 1 EXISTING TO REMAIN 1.68 0.23 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 72

69 -- -- -- -- 2.19 0.23 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 70

67 EX-TRAINING ROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 -- -- -- -- 68

65 -- -- -- -- 2.19 0.45 -- -- -- -- 66

63 EX-MENS RESTROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 64

61 -- -- -- -- 2.19 0.45 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 62

59 EX-MENS RESTROOM... 30 A 2 EXISTING TO REMAIN 2.19 0.45 -- -- -- -- 60

57 -- -- -- -- 2.19 0.45 -- -- -- -- 58

55 EX-WOMENS RESTROO... 30 A 2 EXISTING TO REMAIN 2.19 0.45 3#12, 1#12G, 1/2"C 3 20 A MODULAR FURNITURE 56

53 -- -- -- -- 2.19 0.45 2#12, 1#12G, 1/2"C 1 20 A MODULAR FURNITURE 54

51 EX-WOMENS RESTROO... 30 A 2 EXISTING TO REMAIN 2.19 0.60 2#12, 1#12G, 1/2"C 1 20 A REFRIGERATOR 52

49 EX-DIRT WALL RECEPT 20 A 1 EXISTING TO REMAIN 1.68 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 50

47 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.00 -- 1 20 A SPARE 48

45 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.72 2#12, 1#12G, 1/2"C 1 20 A WAITING B RM. REC. 46

43 EX-BREAKROOM... 20 A 1 EXISTING TO REMAIN 1.68 0.54 2#12, 1#12G, 1/2"C 1 20 A HALLWAY REC. 44

41 SPARE 20 A 1 -- 0.00 0.36 EXISTING TO REMAIN 1 20 A EX-CONF. RECPS 42

39 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 1.20 0.36 EXISTING TO REMAIN 1 20 A EX-LOAD 40

37 EXISTING LOAD 20 A 1 EXISTING TO REMAIN 1.20 0.36 EXISTING TO REMAIN 1 20 A EX-LOAD 38

35 BREAK ROOM REC. 20 A 1 2#12, 1#12G, 1/2"C 1.08 0.72 2#12, 1#12G, 1/2"C 1 20 A IT RM. REC. 36

33 SERVICE RM. REC. 20 A 1 2#12, 1#12G, 1/2"C 0.36 1.08 2#12, 1#12G, 1/2"C 1 20 A CASH RM. REC. 34

31 SPARE 20 A 1 -- 0.00 0.36 2#12, 1#12G, 1/2"C 1 20 A HALLWAY REC. 32

29 VAV-1.1, VAV-1.2, VAV-1.3 20 A 1 2#12, 1#12G, 1/2"C 0.15 0.18 2#12, 1#12G, 1/2"C 1 20 A CHECK-IN REC. 30

27 TESTING RM. REC. 20 A 1 2#12, 1#12G, 1/2"C 1.44 0.72 2#12, 1#12G, 1/2"C 1 20 A OFFICE RM REC. 28

25 EX-LTGS RM 036 20 A 1 EXISTING TO REMAIN 1.08 1.20 2#12, 1#12G, 1/2"C 1 20 A COFFEE 26

23 EX-POWER OUTLETS 20 A 1 EXISTING TO REMAIN 0.36 0.54 EXISTING TO REMAIN 1 20 A EWC RM 54 24

21 EX-FLAT BOX 20 A 1 EXISTING TO REMAIN 0.36 0.50 2#12, 1#12G, 1/2"C 1 20 A DISHWASHER 22

19 EX-FLOOR BOX3 20 A 1 EXISTING TO REMAIN 0.36 0.00 -- 1 20 A SPARE 20

17 RECEPS. - RM 50, 52 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-ALERTON CTRLS 18

15 EX-RECEPS. - RM 50, 51 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-CONF. RM 65 16

13 RECEPS. - RM 64, 63 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-CONF. TV 14

11 RECEPS. - RM 52, 51 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 12

9 RECEPS. - RM 53, 52 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 10

7 RECPS. - RM 61, 53, 55 20 A 1 EXISTING TO REMAIN 1.08 1.00 2#12, 1#12G, 1/2"C 1 20 A MICROWAVE REC. 8

5 RECPS. - RM 42, 41, 45,... 20 A 1 EXISTING TO REMAIN 1.08 0.54 EXISTING TO REMAIN 1 20 A EX-RECPS RM 55, 57, 57 6

3 EX-RECPS. - RM 044 20 A 1 EXISTING TO REMAIN 1.08 1.08 EXISTING TO REMAIN 1 20 A EX-COLUMN FURNITURE... 4

1 EX-RECPS. - RM 50, 44 20 A 1 EXISTING TO REMAIN 1.08 0.54 EXISTING TO REMAIN 1 20 A EX-COLUMN FURNITURE... 2

C K T

LOAD NAME TRIP

P O L E S

WIRE SIZE A B C WIRE SIZE

P O L

TRIP LOAD NAME

C K T

FLUSH MTD: 240/120V

SURFACE MTD: X 480Y/277V

K.A.I.C. : EX. AMPS X 208Y/120V Fed From: T1

MAIN LUGS: 225 AMPS 4 WIRE Project Number: I24027

MAIN BREAKER: AMPS 3 PHASE Project Name: VOLUSIA COUNTY TAX COLLECTOR

Name: L1B

System No. W-J-1020

SECTION A-A

A

F Rating — 2 Hr

T Ratings — 0 and 1/4 Hr (See Item 3B)

L Rating At Ambient — Less Than 1 CFM/Sq Ft L Rating At 400 F — 4 CFM/Sq Ft

A

3B

3A

1. WALL ASSEMBLY - MIN 5 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE

CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 8 IN.

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR

ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL

ASSEMBLY. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3-1/2 IN. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.

B. COPPER TUBING - NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

C. COPPER PIPE - NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FIRESTOP SYSTEM - THE HOURLY F AND T RATING FOR THE FIRESTOP SYSTEMS ARE DEPENDENT UPON THE TYPE AND SIZE OF

PIPE, ANNULAR SPACE, FILL MATERIAL THICKNESS AND FILL MATERIAL TYPE AS DESCRIBED IN THE TABLE BELOW. WHEN THE ANNULAR

SPACE IN THE TABLE SHOWS A RANGE OF DISTANCES, THE PENETRATING ITEM MAY BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE FIRESTOP SYSTEMS SHALL CONSIST OF THE FOLLOWING:

A. PACKING MATERIAL - MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. AS AN

OPTION TO THE ABOVE, BACKER ROD AND/OR FOAMED PLASTIC BACKER MATERIAL MAY BE USED. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

B. FILL, VOID OR CAVITY MATERIAL - SEALANT* - APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL AS

SHOWN IN THE TABLE BELOW:

HILTI CONSTRUCTION CHEMICALS, DIV OF

HILTI INC — FS-One Sealant

*Bearing the UL Classification Mark

Pipe Type Min Fill Mtl Thkns In. F Rating Hr. T Rating Hr.

2A 1/4 2 1/4

2B 1/2 2 0

CEILING OCCUPANCY SENSOR DETAIL

H (BLACK)

LOAD

120/277 VAC BLACK BLUE

NEUTRAL

GROUND

GREEN

ONW AND VNW MANUAL MODE

1. SWITCH IS REQUIRED

TO TURN LOAD ON.

2. LOAD TURNS OFF

WHEN SENSOR TIMES

OUT OR WITH SWITCH.

3. IF DAYLIGHT SENSOR IS ENABLED AND

LIGHT LEVEL IS ABOVE SETPOINT,

LOAD WILL NOT TURN ON.

ONW - AUTOMATIC MODE

1. WHEN SENSOR ACTIVATES LOAD

TURNS ON.

2. SWITCH CAN BE USED TO TURN

LOAD ON OR OFF.

3. IF DAYLIGHT SENSOR IS ENABLED AND

LIGHT LEVEL IS ABOVE SETPOINT,

LOAD WILL NOT TURN ON.

WALL MOUNT OCCUPANCY SENSOR DETAIL

LOAD "A"

RED (RELAY 2)

NEUTRAL

HOT

**USE BLACK LEAD FOR 120VAC.

USE ORANGE LEAD FOR 277VAC.

CAP UNUSED LEAD.

LINE

BLACK BLACK (COMMON)

BLUE (CONTROL -RELAY 1)

RED (24VDC)

AUTOMATIC MODE OPERATION:

1. WHEN SENSOR ACTIVATES, BOTH

LOADS TURN ON.

2. LOADS TURN OFF WHEN SENSOR

TIMES OUT.

RECOMMENDED WIRE:

18-3 AWG STRANDED WIRE SHIELDED OR

NON/SHIELDED

NOTES

1. SPD20-MV-NO SWITCHPACK SHOWN.

120/277VAC 20AMP RATING PER RELAY.

2. BLUE AND RED WIRE LEADS ARE

NON-POLARITY SENSITIVE.

YELLOW(CONTROL- RELAY 2)

RED (RELAY 2)

BLUE (RELAY 1)

BLUE (RELAY 1)

WHITE

HOT ** LOAD "B"

BLUE (CONTROL)

RED (10-30VDC)

(OPTIONAL

MANUAL-OFF

TOGGLE

SWITCHES)

TYPICAL FIRE WALL PENETRATION DETAIL

NTS

OCCUPANCY SENSORS

NTS

N.T.S.

SYSTEM NO. WL2004

SECTION A-A

3B

A

3C

A

3B

3A

3A

1B

3C

1A

THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS:

STEEL SLEEVE - NOM 8 IN. LONG CYLINDRICAL SLEEVE WITH NOM

7/8 IN. WIDE BY 1-3/4 IN. LONG ANCHOR TABS AND NOM 3/4 IN.

LONG TABS TO RETAIN WRAP STRIP LAYER (ITEM B). SHEET OF

PRECUT 0.016 THICK (30 GAUGE) GALV SHEET STEEL AVAILABLE

FROM WRAP STRIP MANUFACTURER. AS AN ALTERNATE, CYLINDRICAL

SLEEVE MAY BE FABRICATED FROM MIN 0.016 IN. THICK (NO. 30

GAUGE) GALV SHEET STEEL IN ACCORDANCE WITH INSTRUCTION SHEET

SUPPLIED BY WRAP STRIP MANUFACTURER. SHEET STEEL FORMED

INTO CYLINDRICAL SLEEVE WITH INSIDE DIAM OF STEEL SLEEVE AND

DIAM OF THROUGH OPENING IN THE GYPSUM WALLBOARD LAYERS TO

BE EQUAL TO OUTSIDE DIAM OF WRAP STRIP (ITEM B) LAYERS ON

PIPE (-0, +1/8 IN.). CYLINDRICAL SLEEVE INSERTED IN ANNULAR

SPACE AROUND NONMETALLIC PIPE, CENTERED IN WALL AND LOCKED

IN POSITION BY BENDING THE ANCHOR TABS OUTWARD 90 DEG

AGAINST THE INNER LAYER OF GYPSUM WALLBOARD WITHIN THE STUD

CAVITY. AFTER INSTALLATION OF WRAP STRIP LAYERS (ITEM B),

RETAINER TABS OF CYLINDRICAL SLEEVE BENT 90 DEG TOWARD PIPE

ON BOTH SIDES OF WALL ASSEMBLY TO LOCK WRAP STRIP LAYERS IN

POSITION.

FILL, VOID OR CAVITY MATERIALS* - WRAP STRIP - NOM 1/4 IN.

THICK INTUMESCENT ELASTOMERIC MATERIAL FACED ON ONE SIDE

WITH ALUMINUM FOIL, SUPPLIED IN 2 IN. WIDE STRIPS. NOM 2 IN.

WIDE STRIPS TIGHTLY WRAPPED AROUND NONMETALLIC PIPE (FOIL SIDE

EXPOSED) AND SLID INTO STEEL SLEEVE ON BOTH SIDES OF WALL

ASSEMBLY. FOR NOM 1/2 IN. TO NOM 2 IN. DIAM NONMETALLIC

PIPES, ONE LAYER OF WRAP STRIP IS REQUIRED. FOR NOM 2-1/2

IN. AND NOM 3 IN. DIAM NONMETALLIC PIPES, TWO LAYERS OF WRAP

STRIP ARE REQUIRED. FOR NOM 3-1/2 IN. AND NOM 4. IN. DIAM

NON METALLIC PIPES, THREE LAYERS OF WRAP STRIP ARE REQUIRED.

EACH LAYER OF WRAP STRIP TO BE INSTALLED WITH BUTTED SEAM,

WITH BUTTED SEAMS IN SUCCESSIVE LAYERS STAGGERED. WRAP STRIP

LAYERS ON EACH SIDE OF WALL TO PROTRUDE 3/4 IN. FROM WALL

SURFACE WITH THE EXPOSED EDGES ABUTTING THE RETAINER TABS

OF THE STEEL SLEEVE. MINNESOTA MINING & MFG. CO. - TYPE

FS-195

FILL, VOID OR CAVITY MATERIALS* - CAULK - GENEROUS BEAD OF

CAULK APPLIED TO OUTER PERIMETER OF STEEL SLEEVE AT

INTERFACE WITH WALL SURFACE AND TO PERIMETER OF NONMETALLIC

PIPE AT ITS EGRESS FROM THE WRAP STRIP LAYERS APPROX 3/4 IN.

FROM THE WALL SURFACE. MINNESOTA MINING & MFG. CO. - TYPES

CP-25 S/L, CP-25 N/S, CP- 25 WB, CP-25 WB+

FILL, VOID OR CAVITY MATERIALS* - MAT WRAP - (NOT SHOWN) -

FLEXIBLE SHEET MATERIAL, FACED ON ONE SIDE WITH ALUMINUM FOIL,

SUPPLIED IN ROLLS. WHEN REQUIRED (SEE TABLE), MIN 6 IN. WIDE

STRIP OF MAT WRAPPED TIGHTLY AROUND CIRCUMFERENCE OF PIPE

(FOIL FACE EXPOSED) AT ITS EGRESS FROM WRAP STRIP ON BOTH

SIDES OF WALL. MAT WRAP OVERLAPPED MIN 1/2 IN. AT SEAM AND

SECURED IN PLACE WITH STEEL WIRE TIES, OR EQUIVALENT, SPACED

MAX 4 IN. OC. EDGE OF MAT ABUTTING WRAP STRIP TO BE SEALED

WITH A MIN 1/4 IN. DIAM BEAD OF CAULK (ITEM C). MINNESOTA

MINING & MFG. CO. - TYPE E-5A *BEARING THE UL CLASSIFICATION

MARKING

A.

B.

C.

D.

WALL ASSEMBLY - THE 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD

WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN

THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL

OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND

SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR

STEEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER

SPACED 16 IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATES AND

CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8

IN. DEEP CHANNELS SPACED MAX 24 IN. OC.

WALLBOARD, GYPSUM* - TWO LAYERS OF NOM 5/8 IN. THICK GYPSUM

WALLBOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION

DESIGN. MAX DIAM OF OPENING IS 6-1/4 IN.

NONMETALLIC PIPE OR CONDUIT - ONE NONMETALLIC PIPE OR CONDUIT

CENTERED IN FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY

SUPPORTED ON BOTH SIDES OF WALL. THE FOLLOWING TYPES AND SIZES

OF NONMETALLIC PIPES OR CONDUIT MAY BE USED IN CLOSED

(PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING

SYSTEMS:

NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 POLYVINYL CHLORIDE

(PVC) PIPE.

NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 SOLID-CORE

ACRYLONITRILE BUTADIENE-STYRENE (ABS) PIPE.

NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) FIRE

RETARDANT POLYPROPYLENE (FRPP) PIPE.

NOM 4 IN. DIAM (OR SMALLER) RIGID NONMETALLIC CONDUIT FORMED OF

PVC.

NOM 1 IN. DIAM (OR SMALLER) ELECTRICAL NONMETALLIC TUBING

FORMED OF PVC.

NOM 2 IN. DIAM (OR SMALLER) SDR11 (OR HEAVIER) POLYBUTYLENE

(PB) PIPE.

NOM 3 IN. DIAM (OR SMALLER) SDR13.5 (OR HEAVIER) CHLORINATED

POLYVINYL CHLORIDE (CPVC) PIPE.

SEE RIGID NONMETALLIC CONDUIT (DZKT) AND ELECTRICAL NONMETALLIC

TUBING (FKHU) CATEGORIES IN ELECTRICAL CONSTRUCTION MATERIALS

DIRECTORY FOR NAMES OF MANUFACTURERS.

1.

A.

B.

2.

A.

B.

C.

D.

E.

F.

G.

3. FIRESTOP SYSTEM - INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY.

THE HOURLY T RATINGS FOR THE FIRESTOP SYSTEM ARE DEPENDENT UPON THE TYPE

AND SIZE OF NONMETALLIC PIPE OR CONDUIT, AS TABULATED BELOW:

PIPE/ NOM ANNULAR F T

CONDUIT PIPE SPACE, RATING RATING

TYPE DIAM, IN. IN. HR HR

PB 1/2 TO 2 1/4-3/8 2 2

PVC, ABS CPVC, 2-1/2 TO 3 1/2-5/8 2 2

PVC,ABS 3-1/2 TO 4 3/4-7/8 2 1-1/2

PP+ 2-1/2 TO 3 1/2-5/8 2 3/4

PP+ 3-1/2 TO 4 3/4-7/8 2 3/4

+MAT WRAP REQUIRED ON PIPE ON BOTH SIDES OF WALL.

PENETRATION DETAIL

NTS

DRAWING NUMBER

SEAL

S

RACH ITECTS

TITLE

DATE

LOCATION

OWNER

PROJECT

605 E. Robinson Street Suite 630

Orlando, Florida 32801 Office 321.296.8100 silling.com

CA# 26308 I24027.00

5/16/2025 8:50:56 AMAutodesk Docs://VOLUSIA-TC Office Deland/VCTCO-Elec.rvt

ELECTRICAL DETAILS

E8.000

Volusia County Tax Collector

Thomas C Kelley Administration Center 123 W. Indiana Avenue Deland, Florida 32720

Volusia County Tax Collector - Deland Office Renovation

Joseph B Harrill PE 73015

05.15.2025

E0.001 - ELECTRICAL LEGEND, NOTES & ABBREVIATIONS
E1.100 - FIRST LEVEL DEMOLITION PLAN ELECTRICAL
E1.101 - FIRST LEVEL PLAN POWER
E1.102 - FIRST LEVEL PLAN LIGHTING
E6.000 - ELECTRICAL RISERS AND PANEL SCHEDULES
E8.000 - ELECTRICAL DETAILS

File details come from the government source that posted it. Updated .